LIGHTING ANALYSIS
1|Page
TABLE OF CONTENT ABSTRACT 1. INTRODUCTION 1.1. OBJECTIVES & AIM 1.2. SITE STUDY 1.2.1. INTRODUCTION 1.2.2. SITE SELECTION REASONS 1.2.3. MEASURED DRAWINGS 2. PRECEDENT STUDY 2.1. CASE STUDY OF A FINISH RESEARCH UNIT 2.2. CONCLUSION OF THE CASE STUDY 3. LITERATURE REVIEW & METHODOLOGY 3.1. LITERATURE REVIEW 3.1.1. WHAT IS LIGHT? 3.1.2. LUMEN 3.1.3. ILLUMINANCE 3.1.4. BRIGHTNESS & LUMINANCE 3.1.5. DAYLIGHTING & ARTIFICIAL LIGHTING 3.1.6. SECTION ASPECT RATIO (SAR) 3.1.7. DAYLIGHT FACTOR 3.1.8. LUMEN METHOD 3.1.9. LIGHTING STANDARDS 3.2. RESEARCH METHODOLOGY 3.2.1. LIGHTING ANALYSIS 3.2.2. DESCRIPTION OF EQUIPMENT 3.2.3. DATA COLLECTION METHOD 3.2.4. PROCEDURE 4. CASE STUDY 4.1. LIGHTING_PHYSIOLOGICAL ROOM 4.1.1. SITE STUDY & ZONING 4.1.2. TABULATION & INTERPRETATION OF DATA 4.1.3. LIGHTING FIXTURES & SPRECIFICATIONS 4.1.4. DAYLIGHT FACTOR ANALYSIS 4.1.5. ARTIFICIAL LIGHTING ANALYSIS 4.1.6. ANALYSIS & EVALUATION 4.2. LIGHTING_GYMNASIUM 4.2.1. SITE STUDY & ZONING 4.2.2. TABULATION & INTERPRETATION OF DATA 4.2.3. LIGHTING FIXTURES & SPECIFICATIONS 4.2.4. DAYLIGHT FACTOR ANALYSIS 4.2.5. ARTIFICIAL LIGHTING ANALYSIS 4.2.6. ANALYSIS & EVALUATION 5. REFERENCES ABSTRACT
2|Page
This report consists of the study of lighting performance of an environment that is conducted at SOSCO Rehabilitation Centre, Melacca. In order to carry out the performance evaluation, we’ve requested the proper floor plans from the facilities management that govern the site buildings, and also produced elevations and sections for the ease of data collection. Collection of lighting performance data is carried out at the functioning hour of the building to quantify and qualify the existing condition of the site. All the data and drawings collected were then further used to carry out an analysis to study the performance of the building. All analysis is supported by technical input such as formulas and equations to calculate luminance of the environment. A list of figures and tables are used as well. A list of references is provided at the end of the report for the ease of navigation.
1. INTRODUCTION Day lighting or natural lighting is the origin light source. Almost every building must design a space for that to receive natural light. For lighting design, the enclosed spaces, colors, solid volumes and the texture can only be appreciated fully when they are imaginatively lit. Light is always design at the place where people gather around. Especially at night, light is very crucial as it can lead people to places they wanted to go. In short, this project is design to expose and introduce us today lighting and lighting requirement in a suggested space. In a group of 7, we have chosen SOSCO Rehabilitation Centre, Melacca, as our site study. We have conducted several site visits to ensure the success of the project outcome. Measurement and calculations of the lighting readings and site measurement are done during the visits and after the visit respectively. Lastly, we concluded the analysis based on the results of our findings and observations.
1.1 Objectives & Aim 3|Page
1. To understand the characteristics of day-lighting and artificial lighting. 2. To understand the lighting requirement in a suggested place. 3. To determine the characteristics and function of day lighting and artificial lighting within the intended space. 4. To critically report and analyze the space and suggest methods to improvise the lighting qualities within the space for intended uses. 5. To understand the impact of building construction technology and building materials on lighting. 6. To determine the lighting requirements based on lighting inadequacy. 7. To determine the different types of lighting throughout the project. The primary objective of this project is to impart the understanding of the lighting and characteristic and requirement in a suggested space, thereby determine their functions and various factors affecting it. With the data collected and the relevant knowledge, an analysis is to perform to evaluate the suggested space with a critical mindset. Besides that, understanding the lighting layout and arrangement helps in determining the lighting requirements based on lighting inadequacy that is reflected in the data collection by using certain methods or calculations. Backed up with precedent studies, drawing comparison with the site study, our precedent studies will aid in achieving all the objectives above.
1.2 Site Study 4|Page
Case Study:
SOCSO Rehabilitation Center, Melacca.
Identification of space: Gymnasium rehabilitation space and physiotherapy room. Address:
Pusat Rehabilitasi Perkeso Lot PT 7263 [H.S (D) 18923] Bandar Hijau, Hang Tuah Jaya, Melaka, 75450, Malaysia.
1.2.1 Introduction
SOCSO Rehabilitation Centre is located at Bandar Hijau, Hang Tuah Jaya, Melacca. It is a rehabilitation centre that consists of an administration block and 5 extended wings. Namely, The Gymnasium, Vocational, Physiotherapy, Hydrotherapy and The Speech and Audio therapy. Under SOCSO’s "Return to Work" program, disabled patients undergo physical and vocational rehabilitation in order to rejoin the workforce. The architect, Anuar Aziz Architect, called this process the "Journey to Healing," where the patients will heal physically and mentally, and lead a normal working life after the rehabilitation process.
5|Page
The allied health institute will provide the skilled personnel. This green certified complex was designed with ‘nature’ and ‘spirituality’ integral to the healing process. A universal access-for-all concept and Malaysian Standard for disabled access is applied throughout. The concept of the building is each building is given a different identity according to functions and ease of way finding. Calming and soft colors are utilized throughout the complex.
1.2.2 Site Selection Reasons
Based on observation, the building provides sufficient functional spaces to conduct out an analysis on lighting conditions. The gymnasium space and the physiological therapy space with specific function would help us develop an understanding on how to manage a lighting level to achieve comfort for users based on different programs and functions. In terms of lighting properties, the gymnasium space and the physiological therapy space can be categorized into semi enclosed space. Array of natural day lighting can be found are design in both spaces, the spaces also aids with a series of artificial lighting. As for the choices of materials, the spaces uses materials that is visually and psychologically comfortable for users in order to allow the patient to feel calmer in a sense. The choices of finishes found are in a calmer tone.
6|Page
1.2.3 Measured Drawings
7|Page
Figure 1: Floor Plan of Physiotherapy Room
8|Page
Figure 2: Floor plan of Gymnasium Room
9|Page
2. PRECEDENT STUDY 2.1 Case study of a finish research unit Place:
Finland (Helsinki)
Building type:
Office Building
Figure 3: Page 1 of 9 of the case study.
10 | P a g e
Figure 4: Page 2 of 9 of the case study.
11 | P a g e
Figure 5: Page 3 of 9 of the case study.
12 | P a g e
Figure 6: Page 4 of 9 of the case study.
13 | P a g e
Figure 7: Page 5 of 9 of the case study.
14 | P a g e
Figure 8: Page 6 of 9 of the case study.
15 | P a g e
Figure 9: Page 7 of 9 of the case study.
16 | P a g e
Figure 10: Page 8 of 9 of the case study.
17 | P a g e
Figure 11: Page 9 of 9 of the case study.
18 | P a g e
2.2 Conclusion of the case study: Based on the case study of the Finnish office, it can be seen that the site of the case study are quite similar to our site as it is an semi enclosed space that has a row of day lighting source on a side of the space. The research team had documented the positions of the lighting fixtures in that spaces as well as the types of fixtures used. The measurement they did included measuring the illuminance as well as comparing them to the power consumption of the space used thoroughly during the day and during the whole week. At the end of the study, the team had concluded their finding to see if the finding regarding the power consumptions of the building is the average power consumptions in Finland’s, this would be benchmarking so that would further understand the performance of the building. Reflecting on the study, we could enhance our own study and research by conducting an analysis and benchmark our findings to the standards of the requirement, this would let us understand how is our building performing in term of lighting.
19 | P a g e
3. LITERATURE REVIEW & RESEARCH METHODOLOGY 3.1 Literature Review 3.1.1 What is Light? Light is electromagnetic radiation within a certain portion of the electromagnetic spectrum. The word usually refers to visible light, which is visible to the human eye and is responsible for the sense of sight. The main source of light on Earth is the Sun. The primary properties of visible light are intensity, propagation direction, frequency or wavelength spectrum, and polarization, while its speed in a vacuum, 299,792,458 meters per second, is one of the fundamental constants of nature. Lighting in Architecture “Architecture is the skillful, accurate and magnificent plays of volumes seen in light.” -Le Corbusier In architectural competitions, light has often been a mentioned term in the jury’s comments; even if it has not been a criterion of the program. Light is the most important factor in the appreciation and understanding of Architecture. The relationship between light and architecture is grounded in the principles of physics; it is about energy and matter but in this particular case it also implies an emotional effect on people. Generally in form of daylight, the generous use of both sunlight and skylight in the spaces is considered positive; adding tremendous value to the architectural object. The dynamic daylight and the controlled artificial lighting are able to affect not only distinct physical measurable conditions in a space, but also to instigate and provoke different visual experiences and moods.
3.1.2 Lumen Lumen The lumen (lm) is the SI derived unit of luminous flux, a measure of the total “amount” of visible light emitted by a source. Luminous flux differs from power (radiant flux) in that luminous flux measurements reflect the varying sensitivity of the human eye to different wavelengths of light, while radiant flux measurements indicate the total power of all electromagnetic waves emitted, independent of the eye’s ability to perceive it. Thus the amount of light emits in all direction is determined by its lumen value.
20 | P a g e
3.1.3 Illuminance The lux (lx) is the SI unit of illuminance and luminous emittance measuring luminous flux per unit area. It is equal to one lumen per square meter. In photometry, this is used as a measure of intensity as perceived by the human eye, of light that hits or passes through a surface
3.1.4 Brightness & Luminance Brightness and luminance are two closely related terms. The brightness of an object refers to the subjective perception of an individual; luminance of an object is usually subject to the objective measurements of a lux meter. (Lechner, 2009)
3.1.5 Daylighting & Artificial Lighting Daylighting is usually utilized as a design features in building to create a more aesthetically pleasing and interesting atmosphere for the users within, it usually provides a link upwards or sideward to the outdoor environment while distributing a dynamic share of natural light. (Ander, 2003) Although the result of daylighting is always visually rich, it is hard to ignore the fact that natural daylighting may bring in an excessive amount of heat in the process. Besides, it is almost impossible for architects to design without taking artificial lighting into consideration as a building is compulsory to be able to function day and night. It is more than adding skylights and large perforation to building envelope to succeed in daylighting design, it involves thoughtful integrations of design strategies in which heat gain, glare, variation of light availability and direct light penetration are taken into account. (Ander, 2003) It is essential in the art and science of daylighting to provide enough daylighting without its possible undesirable effects. Artificial lighting on the other hand is usually employed in specific spaces as it is best used to create a constant ambience when daylight is absent. It is essential for architects to consider the brightness of artificial lighting as it is a major factor which influences the quality of space illumination greatly.
21 | P a g e
3.1.6 Section Aspect Ratio (SAR) The section aspect ratio affects day lighting, passive heating and cooling factors around the light well area in our site. According to Ander, a high SAR effectively eliminates the amount of solar radiation that will reach the lower portions of the space. However in our case study, the height of the courtyard is not as tall as one in an atrium, therefore its lower SAR is ideal for day lighting and radiative cooling.
3.1.7 Daylight Factor The concept of Daylight Factor (DF) was developed in the United Kingdom in the early 20th century. Daylight Factor is a ratio that represents the amount of illumination available indoors relative to the illumination present outdoors at the same time under overcast skies.
Figure 12: Daylight factor and distribution. (Source: MS1525, 2007)
22 | P a g e
3.1.8 LUMEN METHOD Lumen Method is used to determine the number of lamps that should be installed for a given or particular room to achieve uniform light distribution. The number of lamps is determined by the following formula.
Figure 13: Typical
23 | P a g e
lumen maintenance and lamp survival data. (Source: SSL code for lighting, 2013)
Figure 14: Luminaire categories and a list of typical locations where the various environmental conditions may be found (Source: SSL code for lighting, 2013)
24 | P a g e
Figure 15: Typical changes in light output from a luminaire caused by dirt deposition, for a number of luminaire and environment categories. (Source: SSL code for lighting, 2013)
Figure 16: Typical changes in the illuminance from an installation that occur with time due to dirt deposition on the room surfaces. (Source: SSL code for lighting, 2013)
25 | P a g e
3.1.9 Lighting standards Lighting must proving a suitable visual environment within a particular space conforming to the Code of Practice on Energy Efficiency and Use of Energy. 26 | P a g e
Sufficient and suitable lighting should be provided to a restaurant in order to achieve the desired atmosphere and appearance.
Figure 17: Recommended average luminance levels. (Source: MS1525, 2007)
3.2 Research Methodology 3.2.1 Light Analysis 27 | P a g e
The day lighting and artificial lighting in a space can be analyzed and studied to create a space with good and comfortable lighting quality. With the data collected from the site with specific equipment, the data is tabulated and translated into analysis information. 3.2.2 Description of Equipment (a) Light Measuring Equipment (Digital Lux Meter)
Figure 18: Electronic device for light measuring An electronic device which measures luminous flux per unit area and illuminance level. The device picks up accurate reading as it is sensitive to illuminance. FEATURES Sensor with exclusive photo diode, multi-colour correction filters and spectrum meeting C.I.E. standard Sensor COS correction factor meets standard Separate light sensor allows user to take measurements of an optimum position Precise, easy read out and wide range High accuracy in measuring Built-in low battery indicator LSI-circuit provides high reliability and durability LCD display provides low power consumption Compact, light-weight and excellent operation LCD display can clearly read out even with high ambient light GENERAL SPECIFICATIONS Display
13mm (0.5�) LCD 28 | P a g e
Ranges
0-50,000 Lux w/ 3 ranges
Zero Adjustment
Internal adjustment
Over-input
Indication of “1”
Sampling Time
0.4 second
Sensor Structure
Exclusive photo diode and colour correction filter
Operating Temperature Operating Humidity
0 to 50c (32 to 122 F)
Power Supply
DC 9V battery. 006P MN1604 (PP3) or equivalent
Power Consumption
Approximately DC 2 mA
Dimension Weight
Main Instrument : 108 x 73 x 23 mm Sensor Probe : 82 x 55 x 7 mm 160g (0.36 LB) with batteries
Accessories
1 instruction manual and 1 carrying case
Less than 80% R.H.
ELECTRICAL SPECIFICATIONS Range
Resolution
Accuracy
2,000 Lux
1 Lux
± (5% + 2d)
20,000 Lux
10 Lux
± (5% + 2d)
50,000 Lux
100 Lux
± (5% + 2d)
Note: Accuracy tested by a standard parallel light tungsten of 2856k temperature
(b) Smartphone [OnePlus One]
29 | P a g e
An additional recording device is used as a result comparison with the digital Lux meter. A median result is then obtained and will be averaged in the recordings table. (b) Measuring Tape
The tape is used to measure a constant height of the position of the sound meter, which is at 1m. The height is taken on one person as reference to obtain an accurate reading. (c) Camera [a7ii Sony]
The camera is used to record pictures on the source of sound in the cafe and its surrounding.
3.2.3 Data Collection Method 30 | P a g e
We placed the flux meter at the same height of 1m and 1.5m for each point in order to obtain an accurate reading. The readings were recorded on a plotted plan with 1.5m x 1.5m gridlines.
Figure 19: Position of Lux Meter at 1m & 1.5m 3.2.4 Procedure 1. Push the Power Switch to switch on the device. 2. Select the desired measuring range (10 LUX). 3. Record the Lux by holding the Sensor Probe at the desired height of measurement (1m and 1.5m). 4. Record the data displayed on the LCD of the device. 5. Repeat steps 3 & 4 until all data are completed.
Top: A smart phone is used to also record additional Lux results for comparison reasons. Left: Artificial lighting can be seen being used on the ceiling while natural lighting can be seen entering the space from the clerestory windows and the glass doors and windows.# 4. CASE STUDY 31 | P a g e
4.1 LIGHTING_PHYSIOLOGICAL ROOM 4.1.1 Site Study & Zoning
Figure 20: Grid Line & Colour Zoning of Physiological Room
Artificial Lighting & Day Lighting Site Study 32 | P a g e
Figure 21: Section A – A’ to show artificial lighting Above section illustrated the type of lighting applied in the physiological room. The selection of light fixtures was based on its method of light distribution to accommodate the functions of spaces. Recessed Ceiling Light give the direct lighting to the stuffs and patients activities level and provide clear view for the environment.
Figure 22: Section B – B’ to show daylight The above section indicates the sources of daylight to illuminate the interior spaces. Daylight intensity is higher in the zone (blue & green). This is due to the placement of glass windows at the facade. Daylight provides an alternative light source for interior space.
4.1.2 Tabulation & Interpretation of Data
33 | P a g e
Reading of light data were measured and recorded at the level of 1.0M and 1.5M respectively. The colors indicate zoning of the spaces as shown in the legend.
Table 23: Light Data of Operation Hour The light data collected above show the data during operation hour, 12pm to 2.40pm is the lunch hour. Staff of the Physiological Room will turns out to lunch and the room will be closed. The zoning is separated by patient’s activities zone and stuff working zone.
4.1.3 Lighting Fixtures & Specifications Product Brand Lamp Luminous Flux (lm) Light Outputs (lm) Rated Colour Temperature Colour Rendering Index Beam Width Wattage Placement
Philips Lighting 322.4 2500 3000k 30 Recessed Louver
4.1.4 Daylight Factor Analysis 34 | P a g e
Daylight Factor Calculation Zone
Type
Daylight Level in Malaysia E ˳ (Lux)
Average Lux Reading based on collected data, Ex (Lux)
Daylight Factor, DF = (Ex / E˳) x 100%
1 Yellow
Patient Activities Area
32000
334.53
DF = (Ex / E˳) x 100% = (334.53 / 32000) x 100% = 1.05%
2 Red
Stuff Working Area
32000
338.5
DF = (Ex / E˳) x 100% = (338.5 / 32000) x 100% = 1.06%
3 Blue
Patient Activities Area
32000
804.22
DF = (Ex / E˳) x 100% = (804.22 / 32000) x 100% = 2.51%
4 Green
Patient Activities Area
32000
1002.13
DF = (Ex / E˳) x 100% = (1002.13 / 32000) x 100% = 3.13%
DAYLIGHT SIMULATION ANALYSIS 35 | P a g e
Figure 4.1.4a: Daylight Contour Diagram
Discussion From the calculation, illuminance of zone 3 & zone 4 are higher than zone 1 & zone 2. Zone 3 and zone 4 are near to windows which allow daylight to illuminate the spaces. Based on the MS 1525, Daylight Factor of Physiological Room is in average performance.
4.1.5 Artificial Lighting Analysis 36 | P a g e
Zone 1: Patient Activities Area
Figure 24: Lighting Fixtures in Zone 1
Fixture Properties Indicatio n
Image
Light Type
Unit(s )
Philips lighting Brightboost TLF T-8 Fluorescen t Tube
20
Light Distributio n
Light Distribution Description -Offer long life and energy savings in an environmentall y responsible light bulb. -Come in Natural light.
Material Properties 37 | P a g e
Component
Material
Colour
Surface Finish
Reflectanc e Value (%)
Surface Area (m2)
Wall
Plastered Brick Wall
Light blue
Matte
80
73.5
Floor
Terrazzo Flooring
Blue
Gloss
20
101.25
Sliding Door
Glass Panel Transluc ent
Transparen t
8
5
Window
Aluminium Frame
Matte
80
Glass Panel Transluc ent
Transparen t
8
Gypsum Ceiling
White
Matte
80
Robotic Gait
White
Gloss
80
Robotic
White
Gloss
80
White
Ceiling 45
Furniture
38 | P a g e
Gait Bed
Sink
White
Gloss
90
Chair
Black
Matte
10
Table & cupboard
Gray
Matte
80
Lumen Method Calculation 39 | P a g e
Dimensions of Space (L x W) (m) Total Floor Area (m²) Standard Illumination Required (lux) Type of Lighting Fixture Number of Lighting Fixture / N Lumen of Lighting Fixture / F (lm) Height of Luminaries (m) Height of Working Plan (m) Mounting Height / H (m) Reflection Factors
13.5 x 7.5 101.25 200 Philips Lighting 24 2500 3.1 0.8 2.3 Ceiling : 0.8 Wall : 0.8 Floor : 0.2
Room Index RI =
LxW H x ( L+W )
Utilisation Factor / Refer Chart Maintenance Factor Illuminance Level / E (lux) N x F x UF x MF E= A
= 13.5 x 7.5 / 2.3 x (13.5 + 7.5) = 2.10
0.46 0.8 E=
24 x 2500 x 0.46 x 0.8 101.25
E=218.07
Discussion According to MS 1525, standard illuminance for the physiological room is 200 lux. Illuminance level for our site from calculation is 218.07 lux which met the standard requirement.
40 | P a g e
Zone 2: Stuff Working Area
Figure 25: Lighting Fixtures in Zone 2
Fixture Properties Indicatio n
Image
Light Type
Unit(s )
Philips lighting Brightboost TLF T-8 Fluorescen t Tube
8
Light Distributio n
Light Distribution Description -Offer long life and energy savings in an environmentall y responsible light bulb. -Come in Natural light.
41 | P a g e
Material Properties Component
Material
Color
Surface Finish
Reflectance Value (%)
Surface Area (M2)
Wall
Plastered Brick Wall
Light blue
Matte
80
32
Floor
Terrazzo Flooring
Blue
Gloss
20
33.75
Ceiling
Gypsum Ceiling
White
Matte
80
33.75
Furniture
Chair
Orange Matte
50
Working desk
White
80
Matte
42 | P a g e
Door
Gray
Matte
80
Lumen Method Calculation Dimensions of Space (L x W) (m) Total Floor Area (m²) Standard Illumination Required (lux) Type of Lighting Fixture Number of Lighting Fixture / N Lumen of Lighting Fixture / F (lm) Height of Luminaries (m) Height of Working Plan (m) Mounting Height / H (m) Reflection Factors
4.5 x 7.5 33.75 300 - 400 Philips Lighting 8 322.4 3.1 0.8 2.3 Ceiling : 0.8 Wall : 0.8 Floor : 0.2
Room Index LxW RI = H x ( L+W )
Utilisation Factor / Refer Chart Maintenance Factor Illuminance Level / E (lux) N x F x UF x MF E= A
= 4.5 x 7.5 / 2.3 x (4.5 + 7.5) = 1.22
0.40 0.8 E=
8 x 2500 x 0.4 x 0.8 33.75
E=¿ 189.63
Discussion According to MS 1525, standard illuminance for the physiological room is 200 lux. Illuminance level for our site from calculation is 189.63 lux which met the standard requirement.
43 | P a g e
Zone 3: Patient Activities Area
Figure 26: Lighting Fixtures in Zone 3
Fixture Properties Indicatio n
Image
Light Type
Unit(s )
Philips lighting Brightboost TLF T-8 Fluorescen t Tube
15
Light Distributio n
Light Distribution Description -Offer long life and energy savings in an environmentall y responsible light bulb. -Come in Natural light.
44 | P a g e
Material Properties Component
Material
Color
Surface Finish
Reflectanc Surface e Value (%) Area (M2)
Wall
Plastered Brick Wall
Light blue
Matte
80
68.25
Floor
Terrazzo Flooring
Blue
Gloss
20
81
Sliding door
Glass Panel Transluc ent
Transparen t
8
5
Window
Aluminum Frame
Matte
80
8
Glass Panel Transluc ent
Transparen t
8
Gypsum Ceiling
Matte
80
Ceiling
White
White
36
45 | P a g e
Furniture
Chair
Orange
Matte
50
Table
Brown
Matte
50
Stool #1
Gray
Matte
80
Stool #2
Black
Matte
10
Bed
Blue
Matte
10
46 | P a g e
Rehab Walking Devices
Black
Matte
10
Rehab Stair Black Devices
Matte
10
47 | P a g e
Lumen Method Calculation Dimensions of Space (L x W) (m) Total Floor Area (m²) Standard Illumination Required (lux) Type of Lighting Fixture Number of Lighting Fixture / N Lumen of Lighting Fixture / F (lm) Height of Luminaries (m) Height of Working Plan (m) Mounting Height / H (m) Reflection Factors
13.5 x 6 81 300 - 400 Philips Lighting 18 322.4 3.1 0.8 2.3 Ceiling : 0.8 Wall : 0.8 Floor : 0.2
Room Index RI =
LxW H x ( L+W )
Utilisation Factor / Refer Chart Maintenance Factor Illuminance Level / E (lux) E=
N x F x UF x MF A
= 13.5 x 6 / 2.3 x (13.5 + 6) = 1.8
0.46 0.8 E=
18 x 2500 x 0.46 x 0.8 81
E=Âż 204.44
Discussion According to MS 1525, standard illuminance for the physiological room is 200 lux. Illuminance level for our site from calculation is 204.44 lux which met the standard requirement.
48 | P a g e
Zone 4: Patient Activities Area
Figure 27: Lighting Fixtures in Zone 4
Fixture Properties Indicatio n
Image
Light Type
Unit(s )
Philips lighting Brightboost TLF T-8 Fluorescen t Tube
6
Light Distributio n
Light Distribution Description -Offer long life and energy savings in an environmentall y responsible light bulb. -Come in Natural light.
49 | P a g e
Material Properties Component
Material
Color
Surface Finish
Reflecta nce Value (%)
Surface Area (M2)
Wall
Plastered Brick Wall
Light blue
Matte
80
36.75
Floor
Terrazzo Flooring
Blue
Gloss
20
27
Window
Aluminum Frame
White
Matte
80
4
Glass Panel Transluce nt
Transpare nt
8
Gypsum Ceiling
Matte
80
Ceiling
White
27
50 | P a g e
Furniture
Chair
Orange
Matte
50
Yoga Mat
Red
Matte
40
Computer Desk
Brown
Matte
50
51 | P a g e
Lumen Method Calculation Dimensions of Space (L x W) (m) Total Floor Area (m²) Standard Illumination Required (lux) Type of Lighting Fixture Number of Lighting Fixture / N Lumen of Lighting Fixture / F (lm) Height of Luminaries (m) Height of Working Plan (m) Mounting Height / H (m) Reflection Factors
6 x 4.5 27 300 - 400 Philips Lighting 6 322.4 3.1 0.8 2.3 Ceiling : 0.8 Wall : 0.8 Floor : 0.2
Room Index RI =
LxW H x ( L+W )
Utilisation Factor / Refer Chart Maintenance Factor Illuminance Level / E (lux) E=
N x F x UF x MF A
= 6 x 4.5 / 2.3 x (6 + 4.5) = 1.12
0.37 0.8 E=
6 x 2500 x 0.37 x 0.8 27
E=¿ 164.44
Discussion According to MS 1525, standard illuminance for the physiological room is 200 lux. Illuminance level for our site from calculation is 164.44 lux which do not met the standard requirement. Therefore, to meet the standard requirements, additional number of Philips Lighting is required to make up the insufficient illuminance. N=
ExA F x UF x MF
N=
(200−164.44) x 27 2500 x 0.37 x 0.8
N=1.29( 2)
52 | P a g e
Hence, an additional two (2) number of Philips Lighting are required to meet the standard illuminance for Zone 4.
LIGHTING ANALYSIS DIAGRAM
The above lighting analysis showed how installation of various types of luminaires in each space affects the light levels obtained. The lux reading is quite average in zone 1 and zone 2 but zone 3 and zone 4 is higher because it is near to the windows and affected by day lighting.
53 | P a g e
4.1.6 Analysis & Evaluation Physiological Room provides comfortable patient activities spaces with thoughtful planning of spatial ambience quality. The luminaire is used to enhance the spaces experience, which gives sufficient lumen for patient and stuff activities and yet achieving the ambience. The quality of space will increase the comfortable of patient experience. Zoning Based on our observations and data collection in site visit, artificial lighting for the physiological room is design according to the function of the space. Zoning of spaces allows energy efficiency in terms of energy usage according to the placement of various luminaires. Various luminaires were distributed based on the functional requirement of the spaces. The analyze area will have the hospital standards luminaire to provide sufficient lumen to the space. Day Lighting According to the calculations of Daylight Factor, daylight penetrates into the interior during the morning and afternoon time is actually creating glazing, where the windows are used to inviting the glazing and allows day light to illuminate the patient activities space. However, only zone 3 and zone 4 patient activities area that are located near the windows are getting stronger day light luminance. Hence, based on data collection, the illuminance in zone 3 and zone 4 are higher than zone 1 and zone 2.
54 | P a g e
4.2 LIGHTING_GYMNASIUM 4.2.1 SITE STUDY AND ZONING
Figure 28: Grid Line & Color Zoning of Gymnasium
55 | P a g e
ARTIFICIAL LIGHTING & DAYLIGHTING SITE STUDY
Figure 29: Section A-A’ to show artificial lighting Section above show the type of lighting applied in the gymnasium room. The selection of light fixtures was based on it’s light distribution to function in the spaces. Recessed Ceiling Light give the direct lighting to the working level and provide clear view for the user.
Figure 30: Section B-B’ to show day lighting The section above indicates the sources of day lighting penetrate in the interior spaces. Daylight intensity is higher in the one site of the gymnasium. This is due to the placement of full height glass panel. Daylight provide an alternative light source for interior space
56 | P a g e
4.2.2 Tabulation & Interpretation of Data Reading of light data were measured and recorded at the level of 1.0M and 1.5M respectively. The colors indicate zoning of the spaces as shown in the legend.
A
C
D
E
F
G
1
60 917 800
68 834 752
54 883 758
57 1071 911
62 1074 1063
63 1079 970
66 1225 1000
2
65 1233 1097
66 1187 967
57 1193 1015
59 1162 977
65 1465 1050
67 1435 1013
68 1305 955
3
68 975 661
68 1225 1037
63 1140 1130
55 1243 951
69 1441 1067
72 1239 1065
70 1142 1040
4
71 1029 943
69 1073 1144
59 1199 1030
67 1208 1052
74 1280 933
77 1238 969
64 1122 1025
5
68 1126 1072
68 1162 1060
58 1064 1095
59 1110 1027
63 1228 1040
68 1188 1028
77 1065 966
6
67 1770 1330
64 1134 1110
68 1099 750
64 1012 1005
73 1095 1103
72 1166 1208
63 1106 1135
7
65 1282 1431
58 1015 1045 LEGENDS
67 775 730
74 676 818
68 1475 1550
64 1150 1666
65 1550 1900
Standing Sitting
Standing Sitting
Standing Sitting
Standing Sitting
Standing Sitting
Standing Sitting
Standing Sitting
B
ZONE 1 ZONE 2
ZONE 3 ZONE 4
Figure 31: Light Data of Operation Hour
57 | P a g e
The light data collected above show the data during operation hour, 12pm to 2.40pm is the lunch hour. Staff of the Rehab Gym Room will turns out to lunch and the room will be closed.
4.2.3 Lighting Fixtures & Specifications Product Brand Lamp Luminous Flux (lm) Light Outputs (lm) Rated Colour Temperature Colour Rendering Index Beam Width Wattage Placement
Philips Lighting 322.4 2500 3000k 30 Recessed Louver
58 | P a g e
4.2.4 Daylight Factor Analysis Daylight Factor Calculation Zone
Daylight Level in Malaysia E ˳ (Lux)
Average Lux Reading based on collected data, Ex (Lux)
Daylight Factor, DF = (Ex / E˳) x 100%
1 Blue
32000
952
DF = (Ex / E˳) x 100% = (952 / 32000) x 100% = 2.98%
2 Yellow
32000
1039
DF = (Ex / E˳) x 100% = (1039 / 32000) x 100% = 3.25%
3 Orange
32000
1254
DF = (Ex / E˳) x 100% = (1254 / 32000) x 100% = 3.92%
4 Green
32000
1103
DF = (Ex / E˳) x 100% = (1103 / 32000) x 100% = 3.45%
59 | P a g e
DAYLIGHT SIMULATION ANALYSIS
Figure 4.2.4a: Daylight Contour Diagram
Discussion From the calculation, illuminance of zone 3 & zone 4 are higher than zone 1 & zone 2. Zone 3 and zone 4 are near to windows which allow daylight to illuminate the spaces. Based on the MS 1525, Daylight Factor of Gymnasium is in average performance. 60 | P a g e
4.2.5 Artificial Lighting Analysis Zone 1: Lifting Zone
Figure 32: Lighting Fixtures in Zone 1
Fixture Properties Indicatio n
Image
Light Type
Unit(s )
Light Distributio n
Light Distribution Description
61 | P a g e
Philips lighting Brightboost TLF T-8 Fluorescen t Tube
6
-Offer long life and energy savings in an environmentall y responsible light bulb. -Come in Natural light.
Material Properties Component
Material
Color
Surface Finish
Reflecta nce Value (%)
Surface Area (M2)
Wall
Plastered Brick Wall
White
Matte
80
72
Floor
Terrazzo Flooring
Blue
Gloss
20
24
Sliding door
Glass Panel
Transluc ent
Transpare nt
8
5
Window
Aluminum Frame
White
Matte
80
0.8
Glass Panel
Transluc ent
Transpare nt
8
Gypsum Ceiling
White
Matte
80
Ceiling
24
62 | P a g e
Furniture
Hexagon workout machine
Grey
Gloss
15
Chair
Orange
Matte
50
Lumen Method Calculation Dimensions of Space (L x W) (m) Total Floor Area (m²) Standard Illumination Required (lux) Type of Lighting Fixture Number of Lighting Fixture / N Lumen of Lighting Fixture / F (lm) Height of Luminaries (m) Height of Working Plan (m) Mounting Height / H (m) Reflection Factors
4.7 x 6.2 29.14 300 - 400 Philips Lighting 4 2500 5.0 0.8 4.2 Ceiling : 0.8 Wall : 0.8 Floor : 0.2
Room Index RI =
LxW H x ( L+W )
Utilisation Factor / Refer Chart Maintenance Factor Illuminance Level / E (lux) E=
N x F x UF x MF A
= 4.7x 6.2 / 4.2 x (4.7 + 6.2) = 0.64
0.28 0.8 E=
4 x 2500 x 0.28 x 0.8 29.14
E=76.87
Discussion
63 | P a g e
According to MS 1525, standard illuminance for the gymnasium room is 300 lux. Illuminance level for our site from calculation is 76.87 lux which doesn’t met the standard requirement.
Zone 2: Treadmill Zone
Figure 33: Lighting Fixtures in Zone 2
Fixture Properties Indicatio n
Image
Light Type
Unit(s )
Light Distributio n
Light Distribution Description
64 | P a g e
Philips lighting Brightboost TLF T-8 Fluorescen t Tube
6
-Offer long life and energy savings in an environmentall y responsible light bulb. -Come in Natural light.
Material Properties Component
Material
Color
Surface Finish
Reflecta nce Value (%)
Surface Area (M2)
Wall
Plastered Brick Wall
White
Matte
80
90
Floor
Terrazzo Flooring
Blue
Gloss
20
31.5
Window
Aluminum Frame
White
Matte
80
4.4
Glass Panel
Transluc ent
Transpare nt
8
Gypsum Ceiling
White
Matte
80
Ceiling
31.5
65 | P a g e
Furniture
Treadmills
Grey
Gloss
15
Chair
Orange
Matte
50
Lumen Method Calculation Dimensions of Space (L x W) (m) Total Floor Area (m²) Standard Illumination Required (lux) Type of Lighting Fixture Number of Lighting Fixture / N Lumen of Lighting Fixture / F (lm) Height of Luminaries (m) Height of Working Plan (m) Mounting Height / H (m) Reflection Factors
7.5 x 6.2 46.50 300 - 400 Philips Lighting 8 2500 5.0 0.8 4.2 Ceiling : 0.8 Wall : 0.8 Floor : 0.2
Room Index LxW RI = H x ( L+W )
Utilisation Factor / Refer Chart Maintenance Factor Illuminance Level / E (lux) N x F x UF x MF E= A
= 7.5x 6.2 / 4.2 x (7.5 + 6.2) = 0.80
0.34 0.8 E=
8 x 2500 x 0.34 x 0.8 46.50
66 | P a g e
E=116.99
Discussion According to MS 1525, standard illuminance for the gymnasium room is 300 lux. Illuminance level for our site from calculation is 116.99 lux which doesn’t met the standard requirement.
Zone 3: Rest Zone
Figure 34: Lighting Fixtures in Zone 3
Fixture Properties 67 | P a g e
Indicatio n
Image
Light Type
Unit(s )
Philips lighting Brightboost TLF T-8 Fluorescen t Tube
6
Light Distributio n
Light Distribution Description -Offer long life and energy savings in an environmentall y responsible light bulb. -Come in Natural light.
Material Properties Component
Material
Color
Surface Finish
Reflecta nce Value (%)
Surface Area (M2)
Wall
Plastered Brick Wall
White
Matte
80
72
Floor
Terrazzo Flooring
Blue
Gloss
20
24
Ceiling
Gypsum Ceiling
White
Matte
80
24
68 | P a g e
Furniture
Hexagon workout machine
Grey
Gloss
15
Low Roll machine
Grey
Gloss
15
Lumen Method Calculation Dimensions of Space (L x W) (m) Total Floor Area (m²) Standard Illumination Required (lux) Type of Lighting Fixture Number of Lighting Fixture / N Lumen of Lighting Fixture / F (lm) Height of Luminaries (m) Height of Working Plan (m) Mounting Height / H (m) Reflection Factors
4.7 x 6.3 29.61 300 - 400 Philips Lighting 4 2500 5.0 0.8 4.2 Ceiling : 0.8 Wall : 0.8 Floor : 0.2
Room Index RI =
LxW H x ( L+W )
Utilisation Factor / Refer Chart
= 4.7 x 6.3 / 4.2 x (4.7 + 6.3) = 0.64
0.28 69 | P a g e
Maintenance Factor Illuminance Level / E (lux) E=
0.8 E=
N x F x UF x MF A
4 x 2500 x 0.28 x 0.8 29.61
E=75.65
Discussion According to MS 1525, standard illuminance for the gymnasium room is 300 lux. Illuminance level for our site from calculation is 75.65 lux which doesn’t met the standard requirement.
Zone 4: Cycle Zone
Figure 35: Lighting Fixtures in Zone 4 70 | P a g e
Fixture Properties Indicatio n
Image
Light Type
Unit(s )
Philips lighting Brightboost TLF T-8 Fluorescen t Tube
6
Light Distributio n
Light Distribution Description -Offer long life and energy savings in an environmentall y responsible light bulb. -Come in Natural light.
Material Properties Component
Material
Color
Surface Finish
Reflecta nce Value (%)
Surface Area (M2)
Wall
Plastered Brick Wall
White
Matte
80
84.5
Floor
Terrazzo Flooring
Blue
Gloss
20
31.5
71 | P a g e
Door
Aluminum Frame
Gray
Matte
75
4
Sliding door
Glass Panel
Transluc ent
Transpare nt
8
5
Window
Aluminum Frame
White
Matte
80
0.8
Glass Panel
Transluc ent
Transpare nt
8
Ceiling
Gypsum Ceiling
White
Matte
80
Furniture
Cycling Machines
Grey
Gloss
15
31.5
Lumen Method Calculation Dimensions of Space (L x W) (m) Total Floor Area (m²) Standard Illumination Required (lux) Type of Lighting Fixture Number of Lighting Fixture / N Lumen of Lighting Fixture / F (lm) Height of Luminaries (m) Height of Working Plan (m) Mounting Height / H (m) Reflection Factors
7.5 x 6.3 46.25 300 - 400 Philips Lighting 8 2500 5.0 0.8 4.2 Ceiling : 0.8 72 | P a g e
Wall Floor
: 0.8 : 0.2
Room Index LxW RI = H x ( L+W )
Utilisation Factor / Refer Chart Maintenance Factor Illuminance Level / E (lux) E=
N x F x UF x MF A
= 7.5x 6.3 / 4.2 x (7.5 + 6.3) = 0.82
0.34 0.8 E=
8 x 2500 x 0.34 x 0.8 46.25
E=117.62
Discussion According to MS 1525, standard illuminance for the gymnasium room is 300 lux. Illuminance level for our site from calculation is 117.62 lux which doesn’t met the standard requirement.
LIGHTING ANALYSIS DIAGRAM
73 | P a g e
The above lighting analysis showed how installation of various types of luminaires in each space affects the light levels obtained. The lux reading is affected by the day lighting as well. Thus it showed higher lux reading on overall space.
4.2.6 Analysis & Evaluation Zoning Based on our observations and data collection in site visit, artificial lighting for each space is design according to the function of the space. According to MS 1525, standard illuminance for filling area is 300 lux. Average lux reading based on collected data is 1039 lux and the lighting Illuminance for our site is lower than the standard. Both of this data can show that the energy usage for the light bulb of this building is lower but the final average lux result is much higher than the standard illuminance due to wide opening window and door. Both doesn't meet the standard requirement, one is over the standard illuminance and one is much lower compare to the standard.
74 | P a g e
Therefore, this building has high energy efficiency which can reduce the cost for the electricity and achieve good illuminance level during working time. Hence, electric appliances can reduce to save more electrical energy or reduction of opening can be consider to achieve more comfort area for the user. Day Lighting Daylight penetrates into the interior during the morning and afternoon time is actually creating glazing, where the openings are used to allow the glazing and day light to illuminate the activities space. According to the calculations of Daylight Factor, zone 3 and 4 are located nearer to the entrance and opening compare to zone 1 and 2 which located more inward. Hence, zone 3 and 4 receive more light then zone 1 and 2 which affect the illuminance in zone 3 and 4 are higher.
5. REFERENCES 1. Architectural Lighting. (n.d.). Retrieved from iGuzzini: http://www.iguzzini.com/Architectural_lighting
2. D. H., & E, R. C. (2011). Architectural Lighting: Designing With Light And Space. 3. 4. 5. 6.
New York: Princeton Architectural Press. Lighting Solutions . (2014). Retrieved from MCLA Architectural Lighting Design: http://www.mcla-inc.com/ Performance in Lighting . (2015). Retrieved from PIL: http://www.pil-usa.com/ Steffy, G. (2002). Architectural Lighting Design. New York: John Wiley & Sons Sundin, J. (2008). The Lighting. Retrieved from Architectural Lighting: http://www.archlighting.com/industry/reports/the-lightingspecificationprocess_o
75 | P a g e
7. T. P., & W. M. (2011). Daylighting: Architecture and Lighting Design. New York: Routledge. 8. Wymelenberg, K. V. (2014). The Benefits of Natural Light. Retrieved from Architectural Lighting: http://www.archlighting.com/technology/the-benefitsof-naturallight_o
76 | P a g e