CLEVELAND LED IP65 NON-CORROSIVE LUMINAIRE INSTRUCTIONS
Issue 07 7th February2023
THANK YOUfor buying this product. To helpensure it gives complete satisfaction pleaseinstall it according totheseinstructions, andthen pass the instructions to theappropriateperson for retention and futurereference.
SAFETY This is amains powered product. It is designedto beinstalled by suitably qualifiedpersonnel only and in accordance with theapplicable buildingand electrical regulations. Beforeinstallation ormaintenancetheelectricalsupply to the product must be isolated.
INSTALLATIONSUPPORT If installation advice or accessories are required, pleasecontact us at theaboveaddress. We will do our best tohelp. When reporting a suspectedfault or seekinginstallationsupport, theproblem is likely to be resolved most quickly if you have full product details to-hand, as wellas details of when and whereit was purchased.
LUMINAIRE INSTALLATION
1. Undo theclips on each side& hinge open the diffuser. The hingeisformed by two clips on onesideremainingclippedtothe diffuser.
2. Removethe gear tray fromthe base by squeezingtogether the plastic retainingclip. Repeat at the other end. If you needto fully remove from the body thendisconnect thewhere the strap meets thebracket inthe base.
3. Providemains supply cable& decide best entry positionon thebase. Drill points are providedat various points (base& ends). IP65 gland is fittedat oneend.
4. Fix the base. The base is able tobe fixedviathefollowing methods; oncechosen, prepare theceiling/mounting points ensuring thefixing surface/mechanism is sufficient to support the luminaire weight & its application–
Surface fixing (using mountingclips*):Mount thetwostainlesssteel surfacemount fixingclips provided (in accessory pack)tothe ceiling at the specifiedfixing centres (see diagram). Offer thebaseup to theclips & pushto snap fit.
Surface fixing (withoutmounting clips): As the base is PC then it is possibleto drillthroughthe base & fix directly tothemounting surface. Only usethe pre-mouldedstrengthened fixingpoints & caremust be takentodrill a clean holeso as to not remove any of the reinforced wallaround the hole.
Chain or Wire suspension: Mount thetwostainless steel surfacemount fixingclips to the base. Then add a V hook (provided inthe accessory pack)to each of the surface mount clips. This willprovide connection points for chain or wire suspensionat thespecifiedfixingcentres (seediagram).
ConduitSuspension*: Thebasecomes withspecific 20mm diameter drill out points at various centres (see diagram above). Thesepoints are reinforced forconduit suspension purposes. Care must betaken to drillaclean hole& not to remove any of the reinforced wall around the hole. Werecommendthe followingcombination of parts for connection tothebase(see assembly diagram to right). These parts will be availablefrom your electrical wholesaler.
* Safety screws are provided inthe accessory pack. These can befed through theclips & tightened tofix inaclosed position.
5. Route themains supply cableintothe base. It is theinstaller’s responsibility to ensuretheIP65 rating is maintained. AnIP65cable gland is provided.
6. If gear tray was fully removed, refit on tothe retainingstraps on to the gear tray brackets inthebase.
7. Route themains supply cabletothe terminal block & terminate, ensuring correct polarity is observed.
NOTE! THIS LUMINAIRE MUST BE EARTHED.
8. Fully locatethe gear tray into the base by aligning the slots withthe clips in the base& pushinginsecure.
9. Fit thecontroller by hinging back into position& securing using the snap-fit clips.
10. NOTE! THIS IS NON-SELV FITTING please make sure at least on oneof the clips are secured in place using oneof thesmall screws to prevent the diffuser from being opened
11. If vandal resistance is required, fit all thesmall screws provided (inthe accessory pack) into eachclip.
12. Reconnect power supply & check for correct operation.
Note! Luminaires fitted with electronic drivers are exempt frominsulation resistancetests, as this maycauseirreparable damage & would void warranty.
MAINTENANCE
Cleaning should becarried out at regular intervals so as not impair photometric performance or thermalsafety of theluminaire.
GENERAL MAINTAINED EMERGENCY LUMINAIRE INSTRUCTIONS
These instructions should be followed in conjunction with the standard luminaire instructions. Please read carefully and pass to the end user/responsible person for retention and future reference.
INSTALLATION
1. Following the installation of the luminaire in accordance withthe standard luminaire installation instructions, a separate permanentlive supply should be terminated in the incoming supply terminal block in the luminaire, in the connection marked ‘L PERM’. The permanent supply MUST be taken from the same phase as the corresponding switched supply and MUST be wired at the switchboard so that upon instances of tests, it is isolated at the same time as the switched supply.
2. Once the permanent live supply is connected, connect the battery to the module via the ‘plug and mate’ connector, ensuring correct polarity is observed. Failure to observe correct battery polarity will result inpermanent damage to the emergency module/driver.
3. N.B. to avoid potential damage to the battery please ensurethe permanent live is energized as soon as possible following connection of the battery to the module.
4. Upon restoration of the power supply to the luminaire, check that the indicatorLED fitted within the luminaire illuminates green. This indicates that the batteries are charging and that the charging circuit is healthy.
5. Allow the battery to charge for an uninterrupted period of not less than24 hours prior to carrying out a full discharge test.
MAINTENANCE
6. The battery pack in this luminaire must be replaced when it is no longerable to satisfy its full rated duration.
7. In emergency mode the light levelof the luminaire will be at a reduced output. Regular maintenance and gentle cleaning are recommended so as to ensure that the Emergency Output Factor (E.O.F)remains at specified levels.
8. Isolate the supply before servicing.
9. Please ensurethat the emergency flux is not compromised at any time throughout the luminaires design life.
10. DO NOT INSULATION TEST
Caution:
The battery pack in this luminaire is a Lithium Iron Phosphate (LiFePO4) type whichincludes a dedicated protection circuit. Ifreplacing the battery pack, the specification and chemistry must be identical to thatdetailed on the battery label.
TESTING OF EMERGENCY LUMINAIRES:
Recommended routine test procedures in line with BS 5266-1:2016 & BS EN 50172:2004.