EMERGENCY RECESSED INSTRUCTIONS
Issue 07 21st January 2025
THANK YOU for buying this product. To help ensure itgivescomplete satisfaction please install it according to theseinstructions and then pass the instructionsto the appropriate person for retention and futurereference.
SAFETY. This is a mains powered product. It is designedtobe installed by suitably qualified personnel only and in accordance with the applicable building and electrical regulations. Before installation or maintenance the electrical supply to the product must be isolated.

WARRANTY This product is warrantedto be free of defects in materials, design and workmanship for 5 years from the date of purchase. If a suspected faultshould develop in this time, please call our helpline on +44 (0)800 783 6909. This warranty does not include batteries or consumable items such as fuses.
INSTALLATION SUPPORT If installation advice or accessories are required please also contactus on the number above We will do our best to help. When reporting a suspected fault or seeking installation support the problem is likely to be resolved most quickly if you have fullproductdetails to-hand, as well as details of when and where it was purchased.
LUMINAIRE INSTALLATION

1. Decide mounting position in ceiling & cut 60mm diameter hole. Care should be taken to:
o avoid structures, wiring orpipe work that may be in the ceiling void
o not exceed the specified cutting diameter so as not to expose the cut edge
o remove any thermal insulationfrom the area, so the luminaire is not covered
2. Pass the mains supply cable down through the hole& route to the module canister. This luminaire requires an UNSWITCHED live supply.
3. Unscrew &removethe termination cover on both ends of the module canister.
4. Terminatethe mains supply cable ensuring correct polarity is observed. THIS FITTING MUST BE EARTHED
5. Plug in the battery pack using the connector provided.
6. Enter the “Installation Date” inthe appropriate place on the label.
7. Refit the termination covers & clamp the outer sheathing of the cable to restrain in position. Tighten screws to secure.
8. Fit the luminaire into the ceiling by:
o Inserting the module canister into the ceiling void by passing it through the hole & laying it in position, ensuring stable location onto the ceiling.
o Insert the top of the lamp head into the hole & push to engage the springs so retains in position
9. Reconnectthe power supply & check the green indicator LED illuminates.
10. The batteries shouldbe allowed to charge forat least 24 hours before carrying out a full discharge test to check batteries are charging correctly & the maintained duration is being achieved.
OPERATION / MAINTENANCE
1. Nominal battery life is 4years, after whichtime they shouldbe replaced with a suitable equivalent.
2. This luminaire MUST be disconnected before the circuit itis installed on is subjected to any high voltage or insulation resistance testing, otherwise irreparable damage will occur toluminaire components.
3. Ensure cleanliness of luminaires is maintained so as not to affect performance.


WARNING ****************************
The luminaire uses Lithium Iron Phosphate cells (LiFeP04) in itsbatterypack. These batteries include overcharge protection circuitry and a Negative Temperature Co-efficient (NTC) third lead to control thermal runaway. When the battery is no longer able to provide its full rated duration, itmust be replaced with an identical type. Please consult the manufacturer if in doubt.
TESTING FOR EMERGENCY LUMINAIRES
Recommended routine test procedures in line with BS 5266 & BS EN 50172:
Monthly Functional Test
Simulate a mains supply failure by isolating the circuit(ensuring if it is safe to do so) orby way of a test key switch if fitted into the circuit.
Do this for a period of time sufficient to check that the light source illuminates from the battery supply – We recommend 30 seconds.
Once complete, ensure the normal supply is restored & that the green LED charge indicatorilluminates.
Log result/comments in the Testing Log Book (below).
Annual Discharge Test
Simulate a mains supply failure by isolating the circuit(ensuring if it is safe to do so) orby way of a test key switch if fitted into the circuit.
This should be for the full 3-hour rated duration.
Check thatthe light source illuminates & remains illuminated for the full rated duration period.
Once complete, ensure the normal supply is restored & that the green LED charge indicatorilluminates.
Log result/comments in the Testing Log Book (below).
TESTING LOG BOOK
LuminaireType: