RECESSED EMERGENCY PACK V2 - SELF TEST - Instructions

Page 1

RECESSED EMERGENCY PACK V2 SELFTEST INSTRUCTIONS

Issue 05 13th May 2022

THANKYOU for purchasing this product. To help ensure itgives complete satisfaction please installit according to these instructions and then pass theinstructions to the appropriate person for retention and futurereference.

SAFETY This is a mains voltage powered product. It is designed to be installed by suitably qualified personnel only and in accordance with the applicable building and electrical regulations. Before installation or maintenance, the electrical supply to the product must be isolated. N.B. TheproductisclassII.

INSTALLATIONSUPPORT If installation advice or accessories are required, please contact us at the above address. When reporting a suspected fault or seeking installation support the problem is likely to be resolved more quickly if you have full product details to-hand, as well as details of when and where it was purchased.

INSTALLATION

The Recessed Emergency Pack has been designed to work with certain NVC luminaires. Please enquire for compatibility to product ranges.

1. Pass the switched & permanent mains supply cable down through the chosen aperture in the ceiling.

2. On the Emergency pack, unclip the terminal block cover to exposethe terminal block.

3. Route the switched & permanent live supply to the terminal block and terminate ensuring correct polarity is observed. Note: There is an earth terminal provided to enable the use of twin & earth cable for earth continuity on the circuit.

4. Restrain the cable (on outerinsulation) using the cable clamp provided & then clip the terminal block cover back in position.

5. Disconnect the LED driver from the LED luminaire by unplugging thetwist lock connector (rotate and pull apart) and re-connect to the driver connection lead on the emergency pack as shown on the wiring diagram.

6. Wire the switched Live supply out from the emergency pack to the LED driver observing correct polarity

7. Connect the LED luminaire to the LED luminaire connection lead on the emergency pack by using the twistlock connectors (push fit and rotate).

8. Install the Bi-colour indicator LED next to the fitting aperture, using the bezel provided (fits to 20mm diameterhole).

9. Locate the LED Driver & Emergency pack into the ceiling void.

10. Offer the chosen luminaire up to the aperture, then finish installing the luminaire in line with the installation instructions provided.

Note!– When used with LED panels, locate the main driver and the M3 pack away from the edge of the panel and keep a gap of approximately 10cm between them.

11. Reconnect power supply & check for correct operation.

Note!DONOTINSULATIONTEST.

12. When the power supply is reconnected, check that the Bi-colour indicator LED illuminates green to ensure the battery is charging.

******************************IMPORTANTWARNING****************************

This unit is usingLithium-IronPhosphate cells (LiFePO4) in its battery pack.These batteries require close monitoringand protectioncircuitryto operate safely.

The batteryisnon-replaceable, please replace thefull product when itis nolonger able toprovide its fullratedduration of 3hours.

MAINTENANCE

1. Nominal battery design life is at least 4 years, after which time should be checked to ensurefull duration. Replaced at suitable time with a similar equivalent battery pack.

2. When the lamp operates from the battery supply it will be at a reduced light level, so ensure cleanliness of luminaires is maintained so as not to affect performance.

Page 1 of 2

SELF-TESTFUNCTION

This product includes a built-in self-test facility. Once given a permanent mains supply, the luminairewillautomatically carry out a monthly functional check & an annual full duration test, in line with the testing procedures to BS 5266 and BS EN 50172:2004.

Pre-Commissioning

 Product must be left to charge, uninterrupted for not less than 24 hours.

 Upon completion of the 24-hour charge cycle, a full 3-hour Discharge Test is automatically undertaken (this is to commission the product). During this time the Bi-colour indicator LED will remain in the offstate.

 Once the full 3-hour Discharge Testhas completed the product will go into normal charge mode and the Bi-colour LED indicator will illuminate green (no faults).

MonthlyFunctionTest

 At some point between 15-30 days the productwillundertake a 30-second Function Test, the Bi-colour LED indicator will remain in theoff state.

 On completion of the monthlyFunction Test theBi-colour LED indicatorwillilluminate green (no faults)

 The Function Tests will be repeated on amonthly basis.

 The Function Tests will be undertaken atrandomly selected times to avoid luminaires testing at the same time.

AnnualDischargeTest

 At the end of the year a full 3-hour Discharge Test will be undertaken. During this time the Bi-colour indicator LED will remain in the off state.

 On completion of the annual Discharge Test the Bi-colour indicator LED will illuminate green (no faults)

If there is a power outage, the luminaire will continue its cycle afterpower is restored.

FAULTINDICATORS

Notes:

 The faultindicator will continue to flash until the fault is fixed.

Page 2 of 2
SELFTEST-FAULTINDICATION MODE Method Cause LEDIndication MAINSON NoAction Nofaults Green(on) NoAction Batteryfault (openorshort) Red(Flashingevery1s)+bleep every45s NoAction Ledfault Yellow(flashingevery1s)+bleep every45s MONTHLYSELF TESTMODE NoAction Emergencyok Green(on) Batteryfault Red(Flashingevery1s)+bleep every45s Ledfault Yellow(flashingevery1s)+bleep every45s YEARLYSELF-TEST MODE NoAction Emergency>3hr. Green(on) Batteryopenorshort,or discharge<3hr. Red(Flashingevery1s)+bleep every45s Ledfault Yellow(flashingevery1s)+bleep every45s MAINSFAILURE Goesinto3-hour emergencydischarge modeofoperation Discharge>3hr Green(on)whenpowerrestored Discharge<3hr Red(Flashingevery1s)+bleep every45s

MANUALTESTINGisnotrecommended.

A manual test can stillbe initiated by isolating the permanent live supply (e.g., viaa key-switch) for as long as required to check function/duration, choosing to do this may affect the life of the batteries & may resultin them not meeting full rated duration.

This would void any warranty with NVC.

Page 3 of 2

Turn static files into dynamic content formats.

Create a flipbook