Unit Cooler TC Series (AU)

Page 1

Dual Discharge Cabinet Coolers

n Optimised 3/8” Rifle Bore Tube Coils n Easy clean white ABS tray and colour steel case n Extremely low profile n Factory Applied “Blue Coil Coat” Corrosion Protection n 15mm PVC Drain Connection

TC

0.4 1.7 kW

SERIES

MODELS Capacity kW @ 6 KTD -4°C SST

T.X Valve

TCM

04

06

08

10

12

16

R404A

0.48

0.69

0.84

0.99

1.29

1.65

R407F

0.51

0.72

0.90

1.02

1.35

1.74

R22

0.45

0.66

0.81

0.96

1.26

1.62

R134a

0.45

0.60

0.75

0.90

1.17

1.50

R404A

X-SW

X-SW

0-SW

E-0-SW

E-0-SW

E-1-SW

R407F

X-VW

X-VW

0-VW

E-0-VW

E-0-VW

E-0-VW

R22

X-VW

X-VW

0-VW

E-0-VW

E-0-VW

E-0-VW

R134a

X-JW

X-JW

0-JW

E-0-JW

E-0-JW

E-1-JW

J8*S

TC SERIES

MEDIUM TEMP


DIMENSIONS

2

100 (MIN. FOR AIRFLOW

A

4

3

6

5

100 (MIN. FOR AIRFLOW

L (OVERALL LENGTH)

7

8

50 (NOM. FOR DRAIN TRAY REMOVAL)

D (OVERALL DEPTH)

H (OVERALL HEIGHT)

1

AIR FLOW

AIR FLOW

B

21 DRAIN HOLE FOR SPIGOT

AIR FLOW

FRONT ELEVATION

A

B

25

SIDE ELEVATION

C

C

NTS (mm)

MODELS

TCM03

TCM04, 06, 08

TCM10

TCM12, 16

DIMENSIONS

D

L

604

604

604

804

D

386

386

386

466

H

156

178

200

208

D

ISOMETRIC VIEWS

E

MEDIUM TEMP

TCM

Air Volume

l/sec

Fan Motors RAY K.

-

REVISED BY

REV

-

Coil

Dimensions

ECN -

DD-MM-YY

ECN NO.

DATE

2

THE DRAWING AND INFORMATION CONTAINED HEREIN ARE THE EXCLUSIVE PROPERTIES OF PATTON LIMITED. IT SHALL BE RETURNED UPON DEMAND AND SHALL NOT BE REPRODUCED IN WHOLE OR IN PART, DISCLOSE TO ANYONE ELSE OR USED WITHOUT THE WRITTEN CONSENT OF PATTON LIMITED

3

1

UNLESS OTHERWISE SPECIFIED: DIMENSIONS ARE IN MILLIMETERS SURFACE FINISH: TOLERANCES: LINEAR: ANGULAR: NAME DRAWN

CAMERON W.

CHK'D

RAY K.

APPV'D

CRAIG P.

MFG

DEBUR AND BREAK SHARP EDGES

FINISH:

08 SIGNATURE

200 1

Q.A

REFER TO TC SERIES DETAIL DRAWINGS DATE

230 MATERIAL:

DO NOT SCALE DRAWING

10

12 TITLE:

TC SERIES260 GA

-

16 300

1 DWG NO.

REFER TO TC SERIES DETAIL DRAWINGS

4

REVISION:

APPROX WEIGHT: 6.0-13.5Kg

PL01-ASM-TC01

1

SCALE:

CUT SIZE:

A3

1

17-JAN-2012 SHEET 1 OF 1

Watts

16

16

16

16

25

25

Amps

0.45

0.45

0.45

0.45

0.68

0.68

Circuit Vol.

dm

0.49

0.61

0.81

0.98

1.53

1.83

Connection

Dist Inlet

3/8"

3/8"

3/8"

1/2"

1/2"

1/2"

F.Sw

Suct Outlet

3/8"

3/8"

3/8"

1/2"

1/2"

1/2"

fpi

8

8

8

8

8

8

L

604

604

604

604

804

804

D

386

386

386

386

466

466

H

178

178

178

200

208

208

kg

7.4

7.5

8.5

9.2

12.5

13.5

mm

Net Weight

1

DESCRIPTION

1

06

220 PROPRIETARY AND CONFIDENTIAL 220

Num.

Ø 254mm Ø 300mm

04

CAPACITY CORRECTION TCM @ °C SST

3

RELATIVE HUMIDITY GUIDE Temp Diff

R.H %

Temp Diff

R.H %

1.17

2K

94

10K

77

1.07

4K

89

12K

73

-5°

0.99

6K

84

14K

70

-10°

0.93

8K

81

16K

66

Specifications subject to change without notice

NOTES: 1. Fan motors 220-240V/1/50Hz

The company reserves the right to make specification changes without notice. AU 01/01/2017