Installation Instruction Type-PI 1/1-GS; ACDC Surge Protectors (http://shop.acdc-dcac.eu/)

Page 1

MULTI-STAGE SURGE PROTECTION

SurGe

Installation and Operating Instruction ACDC Surge Protectors Type - PI (780; 7100; 7125; 7200) 1/1 - GS EIGHT (8) STAGES SERIES PROTECTOR 1/1 & 3/3 Single Phase & Three Phase CLASS I+II+III Hard Wire Installation on Rail 35mm - Modular System Cascade bi-directional EMI-RFI filtering of phase (L) and neutral (N) wire Indication for bed grounding, remote alarm CLASS

LPZ

I+II+III

0 1 2 3

IP

20

home

telecom

IT center

industry

SurGe Protection

Type - PI (780; 7100; 7125; 7200) 1/1 - GS

Empowered by Innovation

www.acdc-dcac.eu


Mounting of Protectors

SurGe

MULTI-STAGE SURGE PROTECTION

Mounting of ACDC Surge Protectors ACDC Surge Protectors Type - PI 1/1 - GS have to be installed at ENTRY POINT at the the Main Power Distribution Boards (MDB) or in internal Sub Distribution Boards (SDB) or right in front of the input power to the device that should be protected. The ACDC Surge Protector could be install in series or parallel configuration depending of total load per phase (>100A<). - If the load per phase is <100A the ACDC Surge Protector have to be install ed in SERIES configuration. - If the load per phase is >100A the ACDC Surge Protector must be installed in PARALLEL configuration. ! If the the load per phase is <100A, our RECOMMENDATION is to install the surge protector in SERIES configuration because only in this state your electrical devices will be fully protected. ! If the total load per phase is >100A and ACDC Surge Protector is installed in PARALLEL configuration our RECOMMENDATION is to install another ACDC Surge Protector in SERIES configuration (in Sub Distribution Board), downstream power grid where the load per phase drops bellow 100A. ! CAUTION Only in SERIES configuration all eight (8) protection stages are in function.

Condition for Installations: ACDC Surge Protectors must be installed in an enclosure or panel that: - provides adequate electrical and safety protection - Prevents the ingress of moisture and water - Allows operating diagnostic status to be inspected . Mounting: ACDC Surge Protectors are designed to clip to horizontal 35mm DIN rail (standard En50022).

.

Terminal and Wire size: Each terminal is designed to accept wire sizes from 4mm2 to 25mm2 solid or stranded conductor. The wire insulation should be stripped back 8mm ! DANGER THIS UNIT SHOULD BE INSTALLED AND SERVICED ONLY BY QUALIFIED PERSONNEL.

Before installing the ACDC Surge Protector, AC power must be OFF. : During the installation please check: 1. The voltage of the ACDC Surge Protector matches actual system voltage. 2. All conductors are in accordance with the appropriate installation drawings. ! CAUTION CORRECT INSTALLATION - THE LIGHTS GREEN AND YELLOW ARE LIT ! CAUTION TROUBLESHOOTING - IF THE RED LED IS BLINKING THE GROUND WIRE IS NOT CONNECTED OR THE GROUND OF THE

POWER GRID SYSTEM IN NOT WELL PERFORMED

acdc-dcac@acdc-dcac.eu

New materials, New design, New approach to Surge Protection Industry


MULTI-STAGE SURGE PROTECTION

SurGe

Installation Instruction

Installation Instruction for Type - PI (780; 7100; 7125; 7200) 1/1- GS SERIES - Single Phase Installation with phase (L) and neutral (N) filtering

Fuse

L

SERIES - Three Phase Installation with phase (L) and neutral (N) filtering L1

Fuse

L2

Fuse

L3

Fuse

N

N

PE

PE

LIN

L

PARALLEL

L LOUT

LIN

PARALLEL

L

PARALLEL

L LOUT LIN

PARALLEL

MULTI-STAGE

Type - PI Green Series Load Rating: 230VAC @ 100A

GND II IV,VI

Type - PI Green Series Load Rating: 230VAC @ 100A

SURGE

GND II IV,VI

PROTECTION

Series

Type - PI Green Series Load Rating: 230VAC @ 100A

GND II IV,VI

Fuse

L LOUT

LIN

L

PARALLEL

L LOUT LIN

PARALLEL

MULTI-STAGE

L

PARALLEL

L LOUT LIN

PARALLEL

MULTI-STAGE

SURGE

Type - PI Green Series Load Rating: 230VAC @ 100A

GND II IV,VI

MULTI-STAGE

SURGE

PROTECTION

Series

ACDC SURGE PROTECTOR

L LOUT

PARALLEL

SURGE

PROTECTION

Series

Green

L

PARALLEL

MULTI-STAGE

SURGE

PROTECTION

Type - PI Green Series Load Rating: 230VAC @ 100A

GND II IV,VI

PROTECTION

Series

ACDC SURGE PROTECTOR

Green

Type - PI Green Series Load Rating: 230VAC @ 100A

GND II IV,VI

CORRECT

CORRECT

mark

FAULT

CLASS I+II+III

CORRECT

C1'

CORRECT

NIN NOUT NOUT GND

FAULT

CLASS I+II+III

CORRECT

CORRECT

FAULT

CORRECT

CLASS I+II+III

EIGHT PROTECTION STAGES 1, 3 and 7 Stage: Filter (bi-directional wave tracking); 3dB-3kHz,38dB-100kHz,50dB-300kHz; 50bB-500kHz 2, 4 and 5 Stage: Surge Limiter (L-N) 150kA (8x20μs); 22kA (10/350μs) 6. Stage: MOSFET Limiter-500A (8x20μs)(RT<1ns) 8. Stage: Surge Limiter (N-Gnd) 125kA (8x20μs); 20kA (10/350μs)

CORRECT

EIGHT PROTECTION STAGES 1, 3 and 7 Stage: Filter (bi-directional wave tracking); 3dB-3kHz,38dB-100kHz,50dB-300kHz; 50bB-500kHz 2, 4 and 5 Stage: Surge Limiter (L-N) 150kA (8x20μs); 22kA (10/350μs) 6. Stage: MOSFET Limiter-500A (8x20μs)(RT<1ns) 8. Stage: Surge Limiter (N-Gnd) 125kA (8x20μs); 20kA (10/350μs)

FAULT

CLASS I+II+III

EIGHT PROTECTION STAGES 1, 3 and 7 Stage: Filter (bi-directional wave tracking); 3dB-3kHz,38dB-100kHz,50dB-300kHz; 50bB-500kHz 2, 4 and 5 Stage: Surge Limiter (L-N) 150kA (8x20μs); 22kA (10/350μs) 6. Stage: MOSFET Limiter-500A (8x20μs)(RT<1ns) 8. Stage: Surge Limiter (N-Gnd) 125kA (8x20μs); 20kA (10/350μs)

mark

Green

GND II IV,VI

EIGHT PROTECTION STAGES

mark

Series

ACDC SURGE PROTECTOR

Green

1, 3 and 7 Stage: Filter (bi-directional wave tracking); 3dB-3kHz,38dB-100kHz,50dB-300kHz; 50bB-500kHz 2, 4 and 5 Stage: Surge Limiter (L-N) 150kA (8x20μs); 22kA (10/350μs) 6. Stage: MOSFET Limiter-500A (8x20μs)(RT<1ns) 8. Stage: Surge Limiter (N-Gnd) 125kA (8x20μs); 20kA (10/350μs)

N

CORRECT

Fuse

L3

PARALLEL

Fuse

CORRECT

Fuse

L2

PE

PARALLEL - Single Phase Installation ( for current > 100A per phase )

FAULT

CLASS I+II+III

CORRECT

CORRECT

FAULT

L1

PE

ACDC SURGE PROTECTOR Type - PI Green Series Load Rating: 230VAC @ 100A

CLASS I+II+III

SERIES - Three Phase Installation with phase (L) and without neutral (N) filtering

N

L

mark

NIN NOUT NOUT GND NIN NOUT NOUT GND NIN NOUT NOUT GND

N

PARALLEL

CORRECT

CORRECT

Fuse

LIN

CORRECT

1, 3 and 7 Stage: Filter (bi-directional wave tracking); 3dB-3kHz,38dB-100kHz,50dB-300kHz; 50bB-500kHz 2, 4 and 5 Stage: Surge Limiter (L-N) 150kA (8x20μs); 22kA (10/350μs) 6. Stage: MOSFET Limiter-500A (8x20μs)(RT<1ns) 8. Stage: Surge Limiter (N-Gnd) 125kA (8x20μs); 20kA (10/350μs)

FAULT

1, 3 and 7 Stage: Filter (bi-directional wave tracking); 3dB-3kHz,38dB-100kHz,50dB-300kHz; 50bB-500kHz 2, 4 and 5 Stage: Surge Limiter (L-N) 150kA (8x20μs); 22kA (10/350μs) 6. Stage: MOSFET Limiter-500A (8x20μs)(RT<1ns) 8. Stage: Surge Limiter (N-Gnd) 125kA (8x20μs); 20kA (10/350μs)

CLASS I+II+III

1, 3 and 7 Stage: Filter (bi-directional wave tracking); 3dB-3kHz,38dB-100kHz,50dB-300kHz; 50bB-500kHz 2, 4 and 5 Stage: Surge Limiter (L-N) 150kA (8x20μs); 22kA (10/350μs) 6. Stage: MOSFET Limiter-500A (8x20μs)(RT<1ns) 8. Stage: Surge Limiter (N-Gnd) 125kA (8x20μs); 20kA (10/350μs)

CORRECT

1, 3 and 7 Stage: Filter (bi-directional wave tracking); 3dB-3kHz,38dB-100kHz,50dB-300kHz; 50bB-500kHz 2, 4 and 5 Stage: Surge Limiter (L-N) 150kA (8x20μs); 22kA (10/350μs) 6. Stage: MOSFET Limiter-500A (8x20μs)(RT<1ns) 8. Stage: Surge Limiter (N-Gnd) 125kA (8x20μs); 20kA (10/350μs)

FAULT

CLASS I+II+III

EIGHT PROTECTION STAGES

mark

Green

GND II IV,VI

EIGHT PROTECTION STAGES

mark

Series

ACDC SURGE PROTECTOR

Green

EIGHT PROTECTION STAGES

SERIES - Single Phase Installation with phase (L) and without neutral (N) filtering

C1

MULTI-STAGE

PROTECTION

ACDC SURGE PROTECTOR

Green

EIGHT PROTECTION STAGES

mark

L

L LOUT

PARALLEL

SURGE

Series

ACDC SURGE PROTECTOR

L

PARALLEL

MULTI-STAGE

PROTECTION

Series

Green

NIN NOUT NOUT GND

L

L LOUT LIN

PARALLEL

SURGE

PROTECTION

ACDC SURGE PROTECTOR Type - PI Green Series Load Rating: 230VAC @ 100A

L

PARALLEL

MULTI-STAGE

SURGE

mark

NIN NOUT NOUT GND NIN NOUT NOUT GND NIN NOUT NOUT GND

PARALLEL - Three Phase Installation ( for current > 100A per phase ) L1

C1

Fuse

L2

C2

Fuse

L3

C3

Fuse

N PE

PE

C1'

LIN

L

PARALLEL

L LOUT

LIN

PARALLEL

C2'

L

PARALLEL

L LOUT LIN

PARALLEL

MULTI-STAGE

PARALLEL

L LOUT LIN

PARALLEL

MULTI-STAGE

SURGE

Type - PI Green Series Load Rating: 230VAC @ 100A

GND II IV,VI

MULTI-STAGE

SURGE

PROTECTION

Series

ACDC SURGE PROTECTOR

L LOUT

PARALLEL

SURGE

PROTECTION

Series

Green

L

PARALLEL

MULTI-STAGE

SURGE

PROTECTION

ACDC SURGE PROTECTOR Type - PI Green Series Load Rating: 230VAC @ 100A

C3'

L

Type - PI Green Series Load Rating: 230VAC @ 100A

GND II IV,VI

PROTECTION

Series

ACDC SURGE PROTECTOR

Green

Type - PI Green Series Load Rating: 230VAC @ 100A

GND II IV,VI

CORRECT

CORRECT

FAULT

CORRECT

CLASS I+II+III

CORRECT

mark

FAULT

CORRECT

Integrated Multi-Stage Protection

NIN NOUT NOUT

CLASS I+II+III

NIN NOUT NOUT G

CORRECT

mark

FAULT

CLASS I+II+III

EIGHT PROTECTION STAGES 1, 3 and 7 Stage: Filter (bi-directional wave tracking); 3dB-3kHz,38dB-100kHz,50dB-300kHz; 50bB-500kHz 2, 4 and 5 Stage: Surge Limiter (L-N) 150kA (8x20μs); 22kA (10/350μs) 6. Stage: MOSFET Limiter-500A (8x20μs)(RT<1ns) 8. Stage: Surge Limiter (N-Gnd) 125kA (8x20μs); 20kA (10/350μs)

CORRECT

EIGHT PROTECTION STAGES 1, 3 and 7 Stage: Filter (bi-directional wave tracking); 3dB-3kHz,38dB-100kHz,50dB-300kHz; 50bB-500kHz 2, 4 and 5 Stage: Surge Limiter (L-N) 150kA (8x20μs); 22kA (10/350μs) 6. Stage: MOSFET Limiter-500A (8x20μs)(RT<1ns) 8. Stage: Surge Limiter (N-Gnd) 125kA (8x20μs); 20kA (10/350μs)

CORRECT

EIGHT PROTECTION STAGES 1, 3 and 7 Stage: Filter (bi-directional wave tracking); 3dB-3kHz,38dB-100kHz,50dB-300kHz; 50bB-500kHz 2, 4 and 5 Stage: Surge Limiter (L-N) 150kA (8x20μs); 22kA (10/350μs) 6. Stage: MOSFET Limiter-500A (8x20μs)(RT<1ns) 8. Stage: Surge Limiter (N-Gnd) 125kA (8x20μs); 20kA (10/350μs)

FAULT

CLASS I+II+III

EIGHT PROTECTION STAGES

ND

Green

GND II IV,VI

1, 3 and 7 Stage: Filter (bi-directional wave tracking); 3dB-3kHz,38dB-100kHz,50dB-300kHz; 50bB-500kHz 2, 4 and 5 Stage: Surge Limiter (L-N) 150kA (8x20μs); 22kA (10/350μs) 6. Stage: MOSFET Limiter-500A (8x20μs)(RT<1ns) 8. Stage: Surge Limiter (N-Gnd) 125kA (8x20μs); 20kA (10/350μs)

mark

Series

ACDC SURGE PROTECTOR

Green

mark

GND NIN NOUT NOUT GND NIN NOUT NOUT GND

www.acdc-dcac.eu


Operation

MULTI-STAGE SURGE PROTECTION

SurGe

Diagnostic System

Operation Diagnostic System Normal:

Red

Yellow

Green Led Indication for correct stage no. 2,4 and 6. The stages no. 1,3 and 7 (high garde bi-directional filtering) are always in function along with ultimate (5-th) protection stage.

Continuous yellow and green

Fault: Led Indication for correct stage no. 4,6 and un correct no 2. The stages no. 1,3 and 7 (bi-directional filtering) are always in function along with ultimate (5-th) protection stage.

Continuous green

Fault: Led Indication for bed grounding (Low impedance equipotential ground is not provided)

Blinking red

Fault: Continuous red

Only stages 1,3 and 7 are still in function along with ultimate (5-th) protection stage.

Connections for common contact alarm

LIN

L LOUT LIN

L

PARALLEL

PARALLEL

L

PARALLEL

L LOUT LIN

PARALLEL

L LOUT

PARALLEL

MULTI-STAGE

MULTI-STAGE

MULTI-STAGE

PROTECTION

PROTECTION

PROTECTION

Series

Series

SURGE

ACDC SURGE PROTECTOR

Type - PI Green Series Load Rating: 230VAC @ 100A

L

PARALLEL

SURGE

ACDC SURGE PROTECTOR

Green

Type - PI Green Series Load Rating: 230VAC @ 100A

GND II IV,VI

SURGE

Series

ACDC SURGE PROTECTOR

Green

Type - PI Green Series Load Rating: 230VAC @ 100A

GND II IV,VI

GND II IV,VI

CORRECT

CORRECT

FAULT

CORRECT

CLASS I+II+III

CORRECT

1, 3 and 7 Stage: Filter (bi-directional wave tracking); 3dB-3kHz,38dB-100kHz,50dB-300kHz; 50bB-500kHz 2, 4 and 5 Stage: Surge Limiter (L-N) 150kA (8x20μs); 22kA (10/350μs) 6. Stage: MOSFET Limiter-500A (8x20μs)(RT<1ns) 8. Stage: Surge Limiter (N-Gnd) mark 125kA (8x20μs); 20kA (10/350μs)

FAULT

1, 3 and 7 Stage: Filter (bi-directional wave tracking); 3dB-3kHz,38dB-100kHz,50dB-300kHz; 50bB-500kHz 2, 4 and 5 Stage: Surge Limiter (L-N) 150kA (8x20μs); 22kA (10/350μs) 6. Stage: MOSFET Limiter-500A (8x20μs)(RT<1ns) 8. Stage: Surge Limiter (N-Gnd) mark 125kA (8x20μs); 20kA (10/350μs)

CLASS I+II+III

1, 3 and 7 Stage: Filter (bi-directional wave tracking); 3dB-3kHz,38dB-100kHz,50dB-300kHz; 50bB-500kHz 2, 4 and 5 Stage: Surge Limiter (L-N) 150kA (8x20μs); 22kA (10/350μs) 6. Stage: MOSFET Limiter-500A (8x20μs)(RT<1ns) 8. Stage: Surge Limiter (N-Gnd) mark 125kA (8x20μs); 20kA (10/350μs)

CORRECT

EIGHT PROTECTION STAGES

CORRECT

EIGHT PROTECTION STAGES FAULT

CLASS I+II+III

EIGHT PROTECTION STAGES

Green

NIN NOUT NOUT GND NIN NOUT NOUT GND NIN NOUT NOUT GND

-

+ 13

Free Contact Alarm Every ACDC Surge Protector Type -PI (740; 780; 7125; 7200) Green Series have free contact alarm as basic option. The alarm is activate in two cases: 1. When some of the protection stages (2, 4 or 6) are damaged or burned and Red Led is ON. Alarm contacts 1-3 are permanently closed. 2. When the ground of the power grid system is not well performed (pour grounding). Alarm contacts1-3 are closing with frequency of 2Hz (0,5s) Red led is blinking. . Free contacts are on the cover of the protector with contact no. 1 and 3. (see picture) . The contact is a optocoupler with maximum value of voltage 70VDC and current of 10mA. In normal condition it is open.