MULTI-STAGE SURGE PROTECTION
SurGe
Installation and Operating Instruction ACDC Surge Protectors Type - PI (780; 7100; 7125; 7200) 3/3 - M - BS EIGHT (8) STAGES SERIES PROTECTOR 1/1 & 3/3 Single Phase & Three Phase CLASS I+II+III Hard Wire Installation - Modular System Cascade bi-directional EMI-RFI filtering of phase (L) and ground (GND) wire Indication for bed grounding, remote alarm CLASS
LPZ
I+II+III
0 1 2 3
IP
20
home
telecom
IT center
industry
SurGe Protection
Type - PI (780; 7100; 7125; 7200) 3/3 - M - BS
Empowered by Innovation
www.acdc-dcac.eu
Mounting of Protectors
SurGe
MULTI-STAGE SURGE PROTECTION
Mounting of ACDC Surge Protectors ACDC Surge Protectors Type-PI 3/3 - M - Blue Series have to be installed at ENTRY POINT before the Main Power Distribution Boards (MDB) or internal Sub Distribution Boards (SDB) or right in front of the input power to the device that should be protected. The ACDC Surge Protector could be install in series or parallel configuration depending of total load per phase (>100A<). - If the load per phase is <100A the ACDC Surge Protector have to be install ed in SERIES configuration. - If the load per phase is >100A the ACDC Surge Protector must be installed in PARALLEL configuration. ! If the the load per phase is <100A, our RECOMMENDATION is to install the surge protector in SERIES configuration because only in this state your electrical devices will be fully protected. ! If the total load per phase is >100A and ACDC Surge Protector is installed in PARALLEL configuration our RECOMMENDATION is to install another ACDC Surge Protector in SERIES configuration ( before Sub Distribution Board), downstream power grid where the load per phase drops bellow 100A, ! CAUTION Only in SERIES configuration all eight (8) protection stages are in function.
Condition for Installations: - provides adequate electrical and safety protection - Prevents the ingress of moisture and water - Allows operating diagnostic status to be inspected . Mounting: ACDC Surge Protectors are designed to fixed to the wall with screws.
.
Terminal and Wire size: Each terminal is designed to accept wire sizes from 4mm2 to 25mm2 solid or stranded conductor. The wire insulation should be stripped back 8mm ! DANGER THIS UNIT SHOULD BE INSTALLED AND SERVICED ONLY BY QUALIFIED PERSONNEL.
Before installing the ACDC Surge Protector, AC power must be OFF. : During the installation please check: 1. The voltage of the ACDC Surge Protector matches actual system voltage. 2. All conductors are in accordance with the appropriate installation drawings. ! CAUTION CORRECT INSTALLATION - THE LIGHTS GREEN AND YELLOW ARE LIT ! CAUTION TROUBLESHOOTING - IF THE RED LED IS BLINKING THE GROUND WIRE IS NOT CONNECTED OR THE GROUND OF THE
POWER GRID SYSTEM IN NOT WELL PERFORMED .
acdc-dcac@acdc-dcac.eu
New materials, New design, New approach to Surge Protection Industry
MULTI-STAGE SURGE PROTECTION
SurGe
Installation Instruction
Installation Instruction for Type - PI (780; 7100; 7125; 7200) 3/3 - M - BS The model could be installed in series configuration with or without ground filtering or in parallel configuration
- SERIES - Three Phase Installation with phase (L) and ground (GND) filtering
Installation Instruction
Input Ground Rail
L1IN L1OUT
L2IN L2OUT
Output Ground Rail
L3IN L3OUT
L1
Fuse
L2
Fuse
L3
Fuse
N PE
L
LIN
PARALLEL
L LOUT LIN
L
PARALLEL
PARALLEL
L LOUT LIN MULTI-STAGE
PROTECTION
SURGE
Type - PI Blue Series Load Rating: 230VAC @ 100A
PARALLEL
L LOUT
L
PARALLEL
MULTI-STAGE
PROTECTION
PROTECTION
Type - PI Blue Series Load Rating: 230VAC @ 100A
mark
GIN GOUT N
N
CORRECT
N
CORRECT
N
CORRECT
GIN GOUT
FAULT
1, 3 and 7 Stage: Filter (bi-directional wave tracking); 3dB-3kHz,38dB-100kHz,50dB-300kHz; 50bB-500kHz 2, 4 and 5 Stage: Surge Limiter (L-N) 150kA (8x20μs); 22kA (10/350μs) 6. Stage: MOSFET Limiter-500A (8x20μs)(RT<1ns) 8. Stage: Surge Limiter (N-Gnd) 125kA (8x20μs); 20kA (10/350μs)
CLASS I+II+III
1, 3 and 7 Stage: Filter (bi-directional wave tracking); 3dB-3kHz,38dB-100kHz,50dB-300kHz; 50bB-500kHz 2, 4 and 5 Stage: Surge Limiter (L-N) 150kA (8x20μs); 22kA (10/350μs) 6. Stage: MOSFET Limiter-500A (8x20μs)(RT<1ns) 8. Stage: Surge Limiter (N-Gnd) 125kA (8x20μs); 20kA (10/350μs)
CORRECT
1, 3 and 7 Stage: Filter (bi-directional wave tracking); 3dB-3kHz,38dB-100kHz,50dB-300kHz; 50bB-500kHz 2, 4 and 5 Stage: Surge Limiter (L-N) 150kA (8x20μs); 22kA (10/350μs) 6. Stage: MOSFET Limiter-500A (8x20μs)(RT<1ns) 8. Stage: Surge Limiter (N-Gnd) 125kA (8x20μs); 20kA (10/350μs)
FAULT
N
N
Series
Blue
GND II IV,VI
EIGHT PROTECTION STAGES
CLASS I+II+III
GIN GOUT N
SURGE
Type - PI Blue Series Load Rating: 230VAC @ 100A
EIGHT PROTECTION STAGES CORRECT
N
MULTI-STAGE
ACDC SURGE PROTECTOR
Blue
GND II IV,VI
EIGHT PROTECTION STAGES CORRECT
mark
Type - PI Blue Series Load Rating: 230VAC @ 100A
mark
GIN GOUT N
L LOUT
PARALLEL
PROTECTION
Series
ACDC SURGE PROTECTOR
Blue
GND II IV,VI
FAULT
CLASS I+II+III
CORRECT
CORRECT
FAULT
CLASS I+II+III
CORRECT
CORRECT
FAULT
CLASS I+II+III
CORRECT
CORRECT
EIGHT PROTECTION STAGES 1, 3 and 7 Stage: Filter (bi-directional wave tracking); 3dB-3kHz,38dB-100kHz,50dB-300kHz; 50bB-500kHz 2, 4 and 5 Stage: Surge Limiter (L-N) 225kA (8x20μs); 32kA (10/350μs) 6. Stage: MOSFET Limiter-500A (8x20μs)(RT<1ns) 8. Stage: Surge Limiter (N-Gnd) 200kA (8x20μs); 30kA (10/350μs)
FAULT
CLASS I+II+III
EIGHT PROTECTION STAGES
N
L
PARALLEL
SURGE
Series
ACDC SURGE PROTECTOR
1, 3 and 7 Stage: Filter (bi-directional wave tracking); 3dB-3kHz,38dB-100kHz,50dB-300kHz; 50bB-500kHz 2, 4 and 5 Stage: Surge Limiter (L-N) 225kA (8x20μs); 32kA (10/350μs) 6. Stage: MOSFET Limiter-500A (8x20μs)(RT<1ns) 8. Stage: Surge Limiter (N-Gnd) 200kA (8x20μs); 30kA (10/350μs)
mark
SURGE
GND II IV,VI
EIGHT PROTECTION STAGES
N
L LOUT LIN
PARALLEL
MULTI-STAGE
Series
Blue
Type - PI Blue Series Load Rating: 230VAC @ 100A
GND II IV,VI
1, 3 and 7 Stage: Filter (bi-directional wave tracking); 3dB-3kHz,38dB-100kHz,50dB-300kHz; 50bB-500kHz 2, 4 and 5 Stage: Surge Limiter (L-N) 225kA (8x20μs); 32kA (10/350μs) 6. Stage: MOSFET Limiter-500A (8x20μs)(RT<1ns) 8. Stage: Surge Limiter (N-Gnd) 200kA (8x20μs); 30kA (10/350μs)
mark
L LOUT LIN
PARALLEL
SURGE
PROTECTION
ACDC SURGE PROTECTOR
Blue
Type - PI Blue Series Load Rating: 230VAC @ 100A
GND II IV,VI
L
PARALLEL
MULTI-STAGE
Series
ACDC SURGE PROTECTOR
Blue
LIN
PARALLEL
SURGE
Series
ACDC SURGE PROTECTOR
L
PARALLEL
MULTI-STAGE
PROTECTION
mark
GIN GOUT N
N
GIN GOUT
N
- SERIES - Three Phase Installation with phase (L) and without ground (GND) filtering
Installation Instruction
Ground Rail
L1IN L1OUT
L2IN L2OUT
Ground Rail
L3IN L3OUT
L1
Fuse
L2
Fuse
L3
Fuse
N PE
L
LIN
PARALLEL
L LOUT LIN
PARALLEL
L
PARALLEL
L LOUT LIN MULTI-STAGE
PROTECTION
Series
Series
SURGE
ACDC SURGE PROTECTOR
Type - PI Blue Series Load Rating: 230VAC @ 100A
L
PARALLEL
MULTI-STAGE
PROTECTION
PARALLEL
L LOUT
ACDC SURGE PROTECTOR
Blue
Type - PI Blue Series Load Rating: 230VAC @ 100A
GND II IV,VI
L
PARALLEL
L LOUT LIN
PARALLEL
L
PARALLEL
MULTI-STAGE
MULTI-STAGE
Series
PROTECTION
PROTECTION
Series
Series
SURGE
ACDC SURGE PROTECTOR Type - PI Blue Series Load Rating: 230VAC @ 100A
GND II IV,VI
N
GIN GOUT N
L
L LOUT LIN
CORRECT
N
CORRECT
GIN GOUT
CORRECT
N
N
mark
Series
Blue
GND II IV,VI
FAULT
1, 3 and 7 Stage: Filter (bi-directional wave tracking); 3dB-3kHz,38dB-100kHz,50dB-300kHz; 50bB-500kHz 2, 4 and 5 Stage: Surge Limiter (L-N) 150kA (8x20μs); 22kA (10/350μs) 6. Stage: MOSFET Limiter-500A (8x20μs)(RT<1ns) 8. Stage: Surge Limiter (N-Gnd) 125kA (8x20μs); 20kA (10/350μs)
CLASS I+II+III
1, 3 and 7 Stage: Filter (bi-directional wave tracking); 3dB-3kHz,38dB-100kHz,50dB-300kHz; 50bB-500kHz 2, 4 and 5 Stage: Surge Limiter (L-N) 150kA (8x20μs); 22kA (10/350μs) 6. Stage: MOSFET Limiter-500A (8x20μs)(RT<1ns) 8. Stage: Surge Limiter (N-Gnd) 125kA (8x20μs); 20kA (10/350μs)
CORRECT
1, 3 and 7 Stage: Filter (bi-directional wave tracking); 3dB-3kHz,38dB-100kHz,50dB-300kHz; 50bB-500kHz 2, 4 and 5 Stage: Surge Limiter (L-N) 150kA (8x20μs); 22kA (10/350μs) 6. Stage: MOSFET Limiter-500A (8x20μs)(RT<1ns) 8. Stage: Surge Limiter (N-Gnd) 125kA (8x20μs); 20kA (10/350μs)
FAULT
EIGHT PROTECTION STAGES
CLASS I+II+III
GIN GOUT N
SURGE
EIGHT PROTECTION STAGES CORRECT
N
MULTI-STAGE
PROTECTION
ACDC SURGE PROTECTOR Type - PI Blue Series Load Rating: 230VAC @ 100A
Blue
GND II IV,VI
EIGHT PROTECTION STAGES CORRECT
mark
ACDC SURGE PROTECTOR Type - PI Blue Series Load Rating: 230VAC @ 100A
Blue
mark
GIN GOUT N
L LOUT
PARALLEL
SURGE
GND II IV,VI
FAULT
CLASS I+II+III
CORRECT
CORRECT
FAULT
CLASS I+II+III
CORRECT
CORRECT
FAULT
CLASS I+II+III
CORRECT
1, 3 and 7 Stage: Filter (bi-directional wave tracking); 3dB-3kHz,38dB-100kHz,50dB-300kHz; 50bB-500kHz 2, 4 and 5 Stage: Surge Limiter (L-N) 225kA (8x20μs); 32kA (10/350μs) 6. Stage: MOSFET Limiter-500A (8x20μs)(RT<1ns) 8. Stage: Surge Limiter (N-Gnd) 200kA (8x20μs); 30kA (10/350μs)
CORRECT
1, 3 and 7 Stage: Filter (bi-directional wave tracking); 3dB-3kHz,38dB-100kHz,50dB-300kHz; 50bB-500kHz 2, 4 and 5 Stage: Surge Limiter (L-N) 225kA (8x20μs); 32kA (10/350μs) 6. Stage: MOSFET Limiter-500A (8x20μs)(RT<1ns) 8. Stage: Surge Limiter (N-Gnd) 200kA (8x20μs); 30kA (10/350μs)
FAULT
CLASS I+II+III
1, 3 and 7 Stage: Filter (bi-directional wave tracking); 3dB-3kHz,38dB-100kHz,50dB-300kHz; 50bB-500kHz 2, 4 and 5 Stage: Surge Limiter (L-N) 225kA (8x20μs); 32kA (10/350μs) 6. Stage: MOSFET Limiter-500A (8x20μs)(RT<1ns) 8. Stage: Surge Limiter (N-Gnd) 200kA (8x20μs); 30kA (10/350μs)
mark
PROTECTION
Blue
Type - PI Blue Series Load Rating: 230VAC @ 100A
GND II IV,VI
EIGHT PROTECTION STAGES
N
L
PARALLEL
SURGE
EIGHT PROTECTION STAGES
N
L LOUT LIN
PARALLEL
MULTI-STAGE
ACDC SURGE PROTECTOR
Blue
EIGHT PROTECTION STAGES
mark
LIN
PARALLEL
SURGE
mark
N
GIN GOUT N
L
L LOUT LIN
N
GIN GOUT
N
- PARALLEL - Three Phase Installation (for current > 100A per phase) Ground Rail
Installation Instruction L1
L2
Ground Rail
L3
L1
C1
Fuse
L2
C2
Fuse
L3
C3
Fuse
N PE
LIN
L
PARALLEL
L LOUT LIN
PARALLEL
L
PARALLEL
L LOUT LIN
PARALLEL
MULTI-STAGE
L LOUT SURGE
PROTECTION
Series
ACDC SURGE PROTECTOR
Type - PI Blue Series Load Rating: 230VAC @ 100A
Type - PI Blue Series Load Rating: 230VAC @ 100A
L
PARALLEL
L LOUT
PARALLEL
ACDC SURGE PROTECTOR Type - PI Blue Series Load Rating: 230VAC @ 100A
GND II IV,VI
SURGE
PROTECTION
Series
ACDC SURGE PROTECTOR Type - PI Blue Series Load Rating: 230VAC @ 100A
Blue
GND II IV,VI
CORRECT
GIN GOUT N
CORRECT
mark
N
Series
Blue
GND II IV,VI
FAULT
GIN GOUT N
CORRECT
mark
N
CORRECT
EIGHT PROTECTION STAGES 1, 3 and 7 Stage: Filter (bi-directional wave tracking); 3dB-3kHz,38dB-100kHz,50dB-300kHz; 50bB-500kHz 2, 4 and 5 Stage: Surge Limiter (L-N) 150kA (8x20μs); 22kA (10/350μs) 6. Stage: MOSFET Limiter-500A (8x20μs)(RT<1ns) 8. Stage: Surge Limiter (N-Gnd) 125kA (8x20μs); 20kA (10/350μs)
CLASS I+II+III
EIGHT PROTECTION STAGES 1, 3 and 7 Stage: Filter (bi-directional wave tracking); 3dB-3kHz,38dB-100kHz,50dB-300kHz; 50bB-500kHz 2, 4 and 5 Stage: Surge Limiter (L-N) 150kA (8x20μs); 22kA (10/350μs) 6. Stage: MOSFET Limiter-500A (8x20μs)(RT<1ns) 8. Stage: Surge Limiter (N-Gnd) 125kA (8x20μs); 20kA (10/350μs)
FAULT
EIGHT PROTECTION STAGES CORRECT
GIN GOUT
MULTI-STAGE
SURGE
Series
CORRECT
Integrated Multi-Stage Protection
MULTI-STAGE
1, 3 and 7 Stage: Filter (bi-directional wave tracking); 3dB-3kHz,38dB-100kHz,50dB-300kHz; 50bB-500kHz 2, 4 and 5 Stage: Surge Limiter (L-N) 150kA (8x20μs); 22kA (10/350μs) 6. Stage: MOSFET Limiter-500A (8x20μs)(RT<1ns) 8. Stage: Surge Limiter (N-Gnd) 125kA (8x20μs); 20kA (10/350μs)
N
N
PARALLEL
PROTECTION
CLASS I+II+III
N
PARALLEL
MULTI-STAGE
PROTECTION
Blue
FAULT
mark
GIN GOUT N
PARALLEL
ACDC SURGE PROTECTOR Type - PI Blue Series Load Rating: 230VAC @ 100A
CLASS I+II+III
CORRECT
CORRECT
mark
N
FAULT
CORRECT
CORRECT
CLASS I+II+III
FAULT
CORRECT
CORRECT
CLASS I+II+III
EIGHT PROTECTION STAGES 1, 3 and 7 Stage: Filter (bi-directional wave tracking); 3dB-3kHz,38dB-100kHz,50dB-300kHz; 50bB-500kHz 2, 4 and 5 Stage: Surge Limiter (L-N) 225kA (8x20μs); 32kA (10/350μs) 6. Stage: MOSFET Limiter-500A (8x20μs)(RT<1ns) 8. Stage: Surge Limiter (N-Gnd) 200kA (8x20μs); 30kA (10/350μs)
FAULT
CLASS I+II+III
EIGHT PROTECTION STAGES
mark
PARALLEL
SURGE
1, 3 and 7 Stage: Filter (bi-directional wave tracking); 3dB-3kHz,38dB-100kHz,50dB-300kHz; 50bB-500kHz 2, 4 and 5 Stage: Surge Limiter (L-N) 225kA (8x20μs); 32kA (10/350μs) 6. Stage: MOSFET Limiter-500A (8x20μs)(RT<1ns) 8. Stage: Surge Limiter (N-Gnd) 200kA (8x20μs); 30kA (10/350μs)
GIN GOUT N
C3'
Blue
GND II IV,VI
EIGHT PROTECTION STAGES
N
C2'
Series
ACDC SURGE PROTECTOR
Blue
GND II IV,VI
1, 3 and 7 Stage: Filter (bi-directional wave tracking); 3dB-3kHz,38dB-100kHz,50dB-300kHz; 50bB-500kHz 2, 4 and 5 Stage: Surge Limiter (L-N) 225kA (8x20μs); 32kA (10/350μs) 6. Stage: MOSFET Limiter-500A (8x20μs)(RT<1ns) 8. Stage: Surge Limiter (N-Gnd) 200kA (8x20μs); 30kA (10/350μs)
N
LIN
MULTI-STAGE
PROTECTION
Series
Blue
GND II IV,VI
C1'
PARALLEL
SURGE
PROTECTION
ACDC SURGE PROTECTOR
Type - PI Blue Series Load Rating: 230VAC @ 100A
L
PARALLEL
MULTI-STAGE
SURGE
mark
N
GIN GOUT
N
www.acdc-dcac.eu
Installation Instruction
SurGe
MULTI-STAGE SURGE PROTECTION
Installation Instruction for Type - PI (780; 7100; 7125; 7200) 3/3 - M - BS The Surge Protectors are installed in Metal Distribution board with degree of protection IP54
DANGER HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
CAUTION This equipment must only be installed and serviced by qualified electrical . personnel. Tu r n o f f a l l p o w e r supplying this equipment before working on or inside equipment. . During installation into an electrical system, it must not be energized until completely inspection. Failure to follow these instructions will result in serious injury.
acdc-dcac@acdc-dcac.eu
New materials, New design, New approach to Surge Protection Industry
MULTI-STAGE SURGE PROTECTION
Operation
SurGe
Diagnostic System
Operation Diagnostic System Normal:
Red
Yellow
Green Led Indication for correct stage no. 2,4 and 6. The stages no. 1,3 and 7 (high garde bi-directional filtering) are always in function along with ultimate (5-th) protection stage.
Continuous yellow and green
Fault: Led Indication for correct stage no. 4,6 and un correct no 2. The stages no. 1,3 and 7 (bi-directional filtering) are always in function along with ultimate (5-th) protection stage.
Continuous green
Fault: Led Indication for bed grounding (Low impedance equipotential ground is not provided)
Blinking red
Fault: Continuous red
Only stages 1,3 and 7 are still in function along with ultimate (5-th) protection stage.
Connections for common contact alarm
LIN
L LOUT LIN
L
PARALLEL
PARALLEL
L
PARALLEL
L LOUT LIN
PARALLEL
L LOUT
PARALLEL
MULTI-STAGE
MULTI-STAGE
MULTI-STAGE
PROTECTION
PROTECTION
PROTECTION
Series
Series
SURGE
ACDC SURGE PROTECTOR
Type - PI Blue Series Load Rating: 230VAC @ 100A
L
PARALLEL
SURGE
ACDC SURGE PROTECTOR
Blue
Type - PI Blue Series Load Rating: 230VAC @ 100A
GND II IV,VI
SURGE
Type - PI Blue Series Load Rating: 230VAC @ 100A
GND II IV,VI
IN
CORRECT
N
CORRECT
GOUT N
FAULT
IN
CLASS I+II+III
N
CORRECT
GOUT N
CORRECT
IN
FAULT
1, 3 and 7 Stage: Filter (bi-directional wave tracking); 3dB-3kHz,38dB-100kHz,50dB-300kHz; 50bB-500kHz 2, 4 and 5 Stage: Surge Limiter (L-N) 150kA (8x20μs); 22kA (10/350μs) 6. Stage: MOSFET Limiter-500A (8x20μs)(RT<1ns) 8. Stage: Surge Limiter (N-Gnd) mark 125kA (8x20μs); 20kA (10/350μs)
CLASS I+II+III
1, 3 and 7 Stage: Filter (bi-directional wave tracking); 3dB-3kHz,38dB-100kHz,50dB-300kHz; 50bB-500kHz 2, 4 and 5 Stage: Surge Limiter (L-N) 150kA (8x20μs); 22kA (10/350μs) 6. Stage: MOSFET Limiter-500A (8x20μs)(RT<1ns) 8. Stage: Surge Limiter (N-Gnd) mark 125kA (8x20μs); 20kA (10/350μs)
CORRECT
1, 3 and 7 Stage: Filter (bi-directional wave tracking); 3dB-3kHz,38dB-100kHz,50dB-300kHz; 50bB-500kHz 2, 4 and 5 Stage: Surge Limiter (L-N) 150kA (8x20μs); 22kA (10/350μs) 6. Stage: MOSFET Limiter-500A (8x20μs)(RT<1ns) 8. Stage: Surge Limiter (N-Gnd) mark 125kA (8x20μs); 20kA (10/350μs)
CORRECT
EIGHT PROTECTION STAGES
FAULT
CLASS I+II+III
EIGHT PROTECTION STAGES
N
Blue
GND II IV,VI
EIGHT PROTECTION STAGES
N
Series
ACDC SURGE PROTECTOR
Blue
GOUT
-
+ 13
Free Contact Alarm Every ACDC Surge Protector Type -PI (740; 780; 7125; 7200) Blue Series have free contact alarm as basic option. The alarm is activate in two cases: 1. When some of the protection stages (2, 4 or 6) are damaged or burned and Red Led is ON. Alarm contacts 1-3 are permanently closed. 2. When the ground of the power grid system is not well performed (pour grounding). Alarm contacts1-3 are closing with frequency of 2Hz (0,5s) Red led is blinking. . Free contacts are on the cover of the protector with contact no. 1 and 3. (see picture) . The contact is a optocoupler with maximum value of voltage 70VDC and current of 10mA. In normal condition it is open.
ACDC DCAC Dane Krapcev no.2/1, 1000-Skopje, Macedonia
Phone: 389 2 3216 988; Fax: 389 2 3216 993
-
+ 1
N.C
3
www.acdc-dcac.eu