General catalogue 2011

Page 1

RIELLO ELETTRONICA RIELLO ELETTRONICA

G E N E R A L C A T A L O G U E 2 0 1 1 - 1 2


RIELLO ELETTRONICA

The complete range of power solutions

1


CONTENTS

The Company Riello Elettronica and Riello UPS Our roots and our history

p.4

Riello UPS Aros The Union

p.6

Riello UPS Brand values

p.8

Riello UPS The product range p.12

2


THE UPS SYSTEMS

www.riello-ups.com

UPS rack line

p.16

UPS tower line

p.18

iPlug

p.22

iDialog

p.26

Win Dialog Plus

p.28

Net Dialog

p.30

Vision

p.32

Dialog Vision

p.36

Sentinel Pro

p.40

Sentinel Dual Low Power

p.44

Sentinel Dual High Power

p.48

Sentinel Power

p.54

Multi Sentry

p.58

Multi Guard

p.64

Master MPS

p.68

Master HP

p.78

Master Industrial

p.82

Master FC400

p.84

Multi Switch

p.86

Multi Switch ATS

p.88

Master Switch

p.90

Flywheels

p.94

Emergency devices

p.98

Connectivity

p.100

Maintenance Bypass

p.108

Services and contacts Services and Consultancy

p.110

Operating Offices

p.112

3


Riello Elettronica and Riello UPS Our roots and our history

As part of the Riello Industries Group, Riello Elettronica is an Italian model of a global company. Today, the Riello UPS brand is a world leader in the supply of Uninterruptible Power Supplies (UPS)

Riello Elettronica and Riello Industries Riello Elettronica is part of the Riello Industries Group, the operational structure of the Riello family Company. Since 1922, the Riello famil has been an innovative, entrepreneurial force in Italy. The group employs a diverse range of modern business strategies, often exceeding the limitations of a traditional parent company model. This flexible approach, combined with the traditional values of an Italian business, provides the whole group with the strength to succeed in continuously expanding markets A Family Company Agreement, defines and structures decisions related to both stock options and operational management.

4


Riello Industries, is the operational arm of the Family Company, whose entrepreneurial structure is lead by Pilade Riello, together with sons Pierantonio, Andrea, Giuseppe and Nicola. Riello Industries consists of a group of autonomous manufacturing activities, revolving around a central catalytic core, and joined together by the common goals and objectives of the family. Established in 1986, Riello Elettronica is the parent company of a group of businesses operating within the Energy, and Automation and Security sectors. The company started manufacturing switching power supplies for information technology applications, before moving into the manufacture of Uninterruptible Power Supplies (UPS). In 1995 Riello Elettronica became a holding company with operations within civil and industrial electronics, plant engineering and information technology sectors, security and intelligent home systems, and its established UPS manufacturing business. Also part of this strategic development was the restructuring of its energy-related activities under a new organisation - Riello UPS. This structure has been consolidated

COMPANY

Riello Elettronica: the headquarter.

over time thanks to the acquisition of other companies operating within the sector (e.g. Aros); creating an International company with branches across the globe.

Riello UPS The main activities of Riello UPS are the research & development, design, manufacture, sale and service of Uninterruptible Power Supplies. These are used throughout the world to provide a guaranteed continuous supply of electrical energy to information technology systems, used within data centres and IT network operations within finance, transportation, industrial manufacturing, health and other critical sectors. The Riello UPS product range includes over 60 single-phase and three-phase systems from 400VA up to 6.4MVA; providing solutions for powering the smallest desktop PCs to the latest supercomputers used within the most advanced data centre operations Riello UPS also provides a wide range of stabilisers, emergency devices for security and emergency applications, rack cabinets and connectivity accessories.

Energy area The Riello Industries Group

Safety and Automation Area

www.riello-ups.com

5


Riello UPS and Aros The Union

A GLOBAL BRANDING INITIATIVE THAT JOINS TOGETHER ALL RIELLO UPS AND AROS PRODUCTS

RIELLO ELETTRONICA’S entire UPS PORTFOLIO CONSOLIDATED UNDER RIELLO UPS Riello Elettronica, the world’s largest producer of energy transformation and power continuity systems is entirely Italian-owned. The group is a world leader in this sector and at the start of 2011 implemented a branding initiative aimed at strengthening and focusing global marketing and sales in support of its UPS and Solar Inverter portfolios. From January 1, 2011 all UPS products within the group will be branded ‘Riello UPS’, including those previously sold under the AROS brand. Solar Inverters are now marketed under the AROS Solar Technology brand. Both the UPS and solar inverter sectors have achieved considerable growth in their markets, and by unifying each sector under one dedicated brand, Riello Elettronica is creating a solid marketing platform to support its growth on a global level.

6


COMPANY

2011 Press Campaign Presentation of the fusion of the two brands

Riello UPS and AROS. Now Energy beats faster.

Unification under the Riello UPS brand successfully concludes 14 years of integration of the design, production and marketing resources of Riello UPS and AROS into a single UPS supplier; producing a global leader. The unification benefits clients and partners for both sectors in terms of stronger product portfolios, engineering, manufacturing, sales, marketing and service teams.

www.riello-ups.com

Clients and partners will benefit from the increased focused and investment in UPS related activities with a dedicated team, a stronger product portfolio, better assistance and support combined with greater brand visibility and communication. There are also advantages for clients and partners of the solar inverter sector, as the AROS Solar Technology team will concentrate its attention and resources exclusively on this rapidly growing sector.

RIELLO ELETTRONICA

www.riello-ups.com

7


Riello UPS Brand values

RIELLO UPS: AS A GLOBAL PLAYER IN THE UPS SECTOR, CONTINUED INNOVATION AND ECO-COMPATIBILITY ARE THE FOUNDATION OF ITS BUSINESS STRATEGY.

POWER QUALITY Riello UPS is committed to the supply of power solutions providing the very highest levels of efficiency, resilience and power quality on a global basis and for any application requiring continuous energy. Power Quality can be defined using two parameters: • Continuity - the availability of the power supply and its resilience • Waveform - the purity of the waveform in terms of its voltage and current characteristics The Riello UPS product range is extensive, ensuring the availability of a power solution for any critical application requiring a single UPS or turn-key solution combining UPS, Static Transfer Switches, and other power products.

8


COMPANY

An International Vision, An All-Italian Product In a world where many companies are choosing to locate manufacturing based on labour costs, often sacrificing product and service quality, Riello UPS continues to invest in a European production system. This creates two positive effects: the Riello UPS product range is highly reliable, benefiting from an integrated approach to research & development, manufacturing, distribution and service. Secondly, the process strengthens a culture of ‘continuous improvement’, with the flexibility to adapt and enhance the product even during manufacture and assembly. The end result is a superior product range that further enhances the reputation that Riello UPS enjoys for efficiency, resilience and quality.

Business Continuity and Connectivity Riello UPS products represent ‘state-ofthe-art’ developments within the energy management sector. There are currently 16 UPS product ranges offering various operating topologies and configurations, with principle applications within ‘Business Continuity’. Here Riello UPS guarantee the power quality supplied to critical applications, to allow them to function during partial or complete mains power supply failures. This quality concept is central to the Riello UPS corporate culture and every aspect (including products, personnel and services) revolves around this. Whilst product quality is a prerequisite, it is the human element that can also differentiate a company and deliver true added value. All Riello UPS personnel are actively encouraged, wherever they are within the organisation, to contribute towards improvements, whether this relates to products, systems or services. Teamwork is an essential aspect of this

www.riello-ups.com

approach to quality, and the certifications received from numerous external bodies and our many customer endorsements are proof that Riello UPS is achieving its quality objectives.

CONTINUOUS INNOVATION Riello UPS operates two research centres in Italy: one in Legnago (near Verona) for transformerless UPS up to 120kVA; and the other in Cormano (Milan) for transformer-based systems up to 800KVA and custom-design products.The research centres are separated into three distinct areas of activity within the new product development process: • Projects: concerned with concept design • Experimental: for concept testing, analysis and evaluation within laboratory conditions • Testing: prototype validation Each phase is part of a continuous innovation and development process that is designed to deliver world-class power solutions to solve today’s energy issues.

9


Brand values

Eco-friendly Solutions With a concern for the environment, Riello UPS has taken an active role in creating a culture of sustainable development and reduced energy consumption. It has established a number of environmentally friendly projects and made substantial R&D investments into new technologies; specifically focused on a generation of ‘clean energy’ products and the development of even more efficient UPS. The Riello UPS Environmental Management System is also accredited to ISO14001; as a demonstration of a social commitment, which will benefit the present and have a positive impact on the future In addition to achieving the highest possible operating efficiencies, Riello UPS has also focused its research and development efforts on other aspects that impact the environment. • Adaptive battery management to prolong battery life, and reduce wear on other consumables such as fans and capacitors. • Low Total Harmonic Distortion on the input side (THDi) of (3%) to reduce the impact on upstream equipment and a high input power factor (0.99). • Adaptive “Smart Mode” operation in which the UPS selects the best mode of operation to match the electrical characteristics of the mains power supply with the power protection performance required by the load. As a company, Riello UPS is a major contributor to the European Commission – Code of Conduct on Energy Efficiency and Quality of AC Uninterruptible Power Supplies - and the first European manufacturer to rate its products for ECO Energy Level effciency. The European Commission Code of Conduct is a document signed by the major UPS manufacturers in Europe which defines the efficiency goals for specific size bands from 10-800kVA, from 25% to 100% loading.

10

Efficiency and Eco-compatibility: the Challenge of Modern Data Centres


COMPANY

Eco LINE Riello UPS exceeds the specifications of the European Code of Conduct (on Energy Efficiency and Quality of Uninterruptible Power Supplies) and has now introduced energy savings products below 3kVA – known as the

‘ECO LINE’. Again the focus is on energy efficiency and savings – for instance by ensuring that power is not consumed by the UPS when it is connected to the mains power supply, with no load or output voltage.

Eco Energy Levels Riello UPS powers some of the most critical data centres in use today. Within these environments, energy management is critical. Running costs must be minimised without compromising resilience or the ability to withstand a mains power supply disruption. Equipment must operate at the highest possible levels to reduce the stress on critical power supplies and minimise the effect on local ambients.

Riello UPS is the first UPS manufacturer to differentiate its products using the ECO Energy Levels guide. The rating system has been applied from 3kVA (below the 10kVA threshold limit applied by the European Commission) because Riello UPS is committed to the environmental impact of its entire product range. Importantly, Riello UPS ECO Energy Levels is more than a concept. As well as playing a part in the wider corporate initiative, the system demonstrates how Riello UPS can achieve capital payment periods that are up to half the industry standard, and with a reduced ‘carbon-footprint’ - both important benefits in an environmentally and energy challenged world.

To further demonstrate commitment to the environment and promote a clear method for users to identify potential cost-savings from reduced operational energy usage, lower heat outputs and carbon-footprints. Riello UPS developed the unique ECO Energy Levels rating system - a clear method of identifying how Riello UPS products comply with the European Commission Code of Conduct. There are six levels, with level 6 being the highest that can be achieved by a UPS in full on-line mode as defined by VFI-SS-111. ‘Smart Mode’ is an intelligent economy mode at which even higher levels of efficiency can be achieved.

1

www.riello-ups.com

2

On the Riello UPS website (www.riello-ups. com) is an Energy Savings Calculator that can be used to show the energy and money saved using Riello ECO Energy level 6 products. The calculator also shows the reductions in CO2 available per model.

3

4

5

6

“Smart Mode” Availability

Energy Level

Efficiency comparison of UPS with CoC

ECO 6

Greater

YES

ECO 5

Greater

-

ECO 4

Equal

YES

ECO 3

Equal

-

ECO 2

Lower

YES

ECO 1

Lower

-

11


Riello UPS The product range

A range of power solutions for every client FROM DOMESTIC USERS TO LARGE COMPANIES, FROM DATA CENTRES TO INDUSTRIAL SYSTEMS

Riello UPS offices throughout the world

THE PRODUCT RANGE For years, Riello UPS has dedicated its best resources to the continuous development of its core business: uninterruptible power supplies (UPS). The result is the growth of a formidable market presence with a comprehensive product portfolio able to satisfy any requirement from small home/office solutions to large industrial systems and data centres.

12


Power (KVA) 0.5

iPlug

1/1

iDialog

1/1

Win Dialog Plus

1/1

Net Dialog

1/1

Dialog Vision

1/1

Vision

1/1

Sentinel Pro

1/1

Sentinel Dual

1/1 3/1

Sentinel Power

1/1 3/1

Multi Sentry

1/1 3/1 3/3

Multi Guard

3/3

Master MPS

3/3 3/1

Master HP

3/3

Master Industrial

3/1

Master 400 Hz

3/3

0.75

1

2

4

5

10

400

800

0.5-3 0.5-2 0.7-3 1-3

3.3-10 6.5-10 5-10 6.5-10 10-20 10-20 10-120 15-120 10-800 10-100 100-140 30-80 30-120

• Monitoring software

• Rack and tower configurations

• Communications options

• Modular, centralised and

• Environmental sensors • Customised solutions • Pre-sales technical consultancy (TEC)

• Static Transfer Switches (STS)

• Post-sales technical service

• Power Distribution Units (PDU)

• Hire and rental

www.riello-ups.com

200

0.8-2

• Flywheels for dc energy storage

bypasses

100

0.4-0.8

• 16 UPS ranges, from 400VA to

• Centralised and distributed

80

0.4-1.6

• Extended runtime battery packs

distributed

40

0.6-0.8

The Riello UPS portfolio includes: 6400KVA

20

COMPANY

Phase

13


14


UPS

The UPS Systems

www.riello-ups.com

15


UPS rack line portfolio

MODELS

DIALOG VISION

SENTINEL DUAL Low Power

SENTINEL DUAL High Power

POWER

500 - 800 - 1100 1500 - 2200 - 3000 VA

1100 - 1500 - 2000 - 3000 VA

3300 - 4000 - 5000 - 6000 8000 - 10000 VA

Line Interactive

On Line double conversion

On Line double conversion

Sinusoidal

Sinusoidal

Sinusoidal

Input voltage

Single-phase 230V

Single-phase 230V

Three-phase 400V (1) and Single-phase 230V

Output voltage

Single-phase 230V

Single-phase 230V

Single-phase 230V

Automatic Bypass

Manual Bypass

Inverter output transformer

Automatic battery test

RS232 serial port

Dry contacts

USB port

Eco-mode function

Smart-active function

Emergency function

Type Output waveform

Frequency converter function

Display

Basic software version

Runtime expandability 

16

Standard / compatible

 

Optional

(2200 - 3000)

(1) Only on 6.5-8-10kVA


UPS

Software and accessories compatibility

MODELS

DIALOG VISION

SENTINEL DUAL Low Power

SENTINEL DUAL High Power

POWER

500 - 800 - 1100 1500 - 2200 - 3000 VA

1100 - 1500 - 2000 - 3000 VA

3300 - 4000 - 5000 - 6000 8000 - 10000 VA

SOFTWARE POWERSHIELD3

SOFTWARE POWERNETGUARD

NETMAN 101 PLUS

NETMAN 102 PLUS

MULTICOM 301

MULTICOM 302

MULTICOM 351

MULTICOM 352

MULTICOM 362

MULTICOM 372

MULTICOM 382

MULTICOM 401

MULTI I/O

MULTISWITCH IRMS (with NetMan plus)

MULTISWITCH IRMS (with serial)

AS400 INTERFACE KIT

External MANUAL BYPASS 16A

up to 4kVA

External RACK MANUAL BYPASS 16A

up to 4kVA

56k EXTERNAL MODEM

GSM MODEM

SOFTWARE

ACCESSORIES

REMOTE SIGNAL PANEL 

Compatible

www.riello-ups.com

17


UPS tower line portfolio

MODELS

IPLUG

IDIALOG

WIN DIALOG PLUS

NET DIALOG

DIALOG VISION

VISION

SENTINEL PRO

POWER

600-800VA

400-600-800 1200-1600VA

400-600 800VA

800-1000 1500-2000VA

500-800-1100 1500-22003000VA

800-1100 1500-2200VA

700-1000 1500-2200 3000VA

Type Output waveform

On-line double Conversion

Step-wave

Step-wave

Step-wave

Step-wave

Sinusoidal

Sinusoidal

Sinusoidal

Input voltage

Single-phase 230V

Single-phase 230V

Single-phase 230V

Single-phase 230V

Single-phase 230V

Single-phase 230V

Single-phase 230V

Output voltage

Single-phase 230V

Single-phase 230V

Single-phase 230V

Single-phase 230V

Single-phase 230V

Single-phase 230V

Single-phase 230V

Automatic Bypass

Manual Bypass

Inverter output transformer

Automatic battery test

RS232 serial port

(2)

Dry contacts

USB port

Eco-mode function

Smart-active function

Emergency function

Frequency converter function

Display

Basic software version

downloadable via internet

downloadable via internet

downloadable via internet

downloadable via internet

Runtime expandability

(6)

 

18

Line Interactive Line Interactive Line Interactive Line Interactive Line Interactive Line Interactive

Standard Optional

(1) Only on 6.5-8-10kVA (2) Only on 1200-1600VA (3) From 10 to 40kVA / from 100 to 120kVA (4) From 10 to 20kVA (5) From 8 to 20kVA (6) 2200-3000VA


UPS

SENTINEL DUAL (Low Power) 1000-1500 2200-3000VA

SENTINEL DUAL (High Power)

SENTINEL POWER

MULTI SENTRY

MULTI SENTRY

3300-4000 10-12-15-20kVA (1ph) 10-12-15-20kVA (1ph) 10-12-15-20-40-60 5000-6000-6500 5000-6000-6500 8000-10000VA 10-15-20kVA (3ph) 8000-10000VA 80-100-120kVA (3ph)

MASTER MPS 3/1 10-15-20 30-40-60 80-100kVA

MASTER MPS 3/3

MASTER HP

10-15-20-30-40-60 100-120-160-200 80-100-120-160 250-300-400 200-600-800kVA 500kVA

On-line On-line On-line On-line On-line On-line On-line On-line double conversion double conversion double conversion double conversion double conversion double conversion double conversion double conversion Sinusoidal Single-phase 230V

Sinusoidal

Sinusoidal

Sinusoidal

Sinusoidal

Sinusoidal

Sinusoidal

Sinusoidal

Three-phase 400V

Three-phase 400V

Three-phase 400V

Three-phase 400V (3) Three-phase 400V (4) Single-phase 230V Three-phase 400V Single-phase 230V Single-phase 230V (5)

Three-phase 400V

Three-phase 400V ( ) Three-phase 400V ( ) Three-phase 400V ( ) Three-phase 400V Single-phase 230V Single-phase 230V Single-phase 230V 1

1

Single-phase 230V Single-phase 230V Single-phase 230V

3

www.riello-ups.com

19


UPS tower line

Software and accessories compatibility

MODELS

IPLUG

IDIALOG

WIN DIALOG PLUS

NET DIALOG

DIALOG VISION

VISION

SENTINEL PRO

POWER

600-800VA

400-600-800 1200-1600VA

400-600 800VA

800-1000 1500-2000VA

500-800-1100 1500-2200 3000VA

800-1100 1500-2200VA

700-1000 1500-2200 3000VA

SOFTWARE POWERSHIELD3

SOFTWARE POWERNETGUARD

NETMAN 102 PLUS

NETMAN 202 PLUS

MULTICOM 352

MULTICOM 362

MULTICOM 372

SOFTWARE COMPATIBILITY

ACCESSORIES NETMAN 101 PLUS

MULTICOM 301

MULTICOM 302 MULTICOM 351

MULTICOM 382 MULTICOM 401 MULTI I/O

I/O expansion board MULTISWITCH IRMS (with NetMan plus) MULTISWITCH IRMS (with serial)

AS400 INTERFACE KIT

INTERFACE BOX 3 DRY CONTACTS 250V / 5A External MANUAL BYPASS 16A

External RACK MANUAL BYPASS 16A

56k EXTERNAL MODEM

GSM MODEM

REMOTE SIGNAL PANEL 

20

Compatible


UPS

SENTINEL DUAL 1000-1500 2200-3000VA

SENTINEL DUAL

SENTINEL POWER

MULTI SENTRY

MULTI SENTRY

3300-4000 10-12-15-20kVA (1ph) 10-12-15-20kVA (1ph) 10-12-15-20-40-60 5000-6000-6500 5000-6000-6500 8000-10000VA 10-15-20kVA (3ph) 8000-10000VA 80-100-120kVA (3ph)

MASTER MPS 3/1 10-15-20 30-40-60 80-100kVA

MASTER MPS 3/3

MASTER HP

10-15-20-30-40-60 100-120-160-200 80-100-120-160 250-300-400 200-600-800kVA 500kVA

3300 - 4000 VA

3300 - 4000 VA

www.riello-ups.com

21


PERSONAL COMPUTERs

iPlug 600-800 VA Single-phase

Highlights

ECO LINE

• Compact • Versatile • Robust • Contemporary design • Advanced communication • Auto restart • Battery swap • ECO line environmental protection

The iPLUG series is the ideal solution for household, and small office systems. Its compact size and versatility, push-button operation, LED status panel and user replaceable batteries – make iPlug easy to install within a domestic environment to protect systems from surges and blackouts. When mains power fails, the load is powered by the pseudo-sinewave inverter and built-in battery. PowerShield3 UPS monitoring and control software can be used for an orderly 22

unattended shutdown of IT systems. PowerShield3 can be downloaded free of charge from www.riello-ups.com Versatile, robust and a contemporary design iPlug’s compact and ergonomic design allow the UPS to be easily used within professional and domestic environments. iPlug is extremely versatile and its innovative cable management feature ensures a clean, easy to manage installation.


• Available with French (2P+T), English, Shuko and Italian outlets. • PowerShield3 supervision and shutdownsoftware for Windows operating systems 7, 2008, Vista, 2003, XP, Linux, Mac OS X and Sun Solaris • Plug and Play function 2-YEAR WARRANTY

Automatic Restart The UPS automatically restarts when the mains power supply is restored, after auto power.

configurator for model selection Load type

Power VA *

Personal computer

250

LCD Monitor

70

15” Monitor

150

Scanner, printer

200

Modem, TV, DVD players, PlayStation, Hi-Fi, telephone, Fax

50

Laser printer **

200

* Average estimated value ** Use of the iPLUG filtered power output is recommended.

ECO Line environmental protection iPlug features a unique shut-off button to reduce energy consumption during periods of prolonged inactivity.

Available sockets

Applications LCD monitors, personal computers, VDUs, printers, scanners and faxes. Features • ECO LINE product • Compact and ergonomic • 5 Battery runtime protected sockets • 3 Surge protected sockets for powering larger absorption loads such as laser printers • Ability to switch on the UPS without a mains power supply (Cold Start) • User replaceable batteries (Battery Swap) • USB Interface • Can be placed on a desktop or the floor • Power cable included • Short-circuit protection • Auto restart (when mains power is restored, after a battery discharge) • GS/Nemko Safety mark

www.riello-ups.com

Schuko SOCKET

FRENCH SOCKET

ITALIAN SOCKET

ENGLISH SOCKET

CEE 7/7P

CEE 7/5

CEI 23/16

BS1363A

details IPG 600 - IPG 800

SOCKET WITH UPS PROTECTION (NO BREAK IN POWER IF MAINS FAILS) FILTERED SOCKETS: OVERVOLTAGE PROTECTION ONLY

IEC SOCKETS WITH UPS PROTECTION SAFETY FUSE USB COMMUNICATION PORT

23

UPS

Advanced communication PowerShield3 software for the safe and unattended shutdown of connected IT systems on mains power supply failure. PowerShield3 provides efficient and intuitive UPS management through bar chart displays of important operating information.


MODELS

IPG 600

IPG 800

POWER

600VA/360W

800VA/480W

INPUT Nominal voltage

220-240 Vac

Input voltage tolerance

230 Vac (+20/-25%)

Frequency

50/60 Hz with automatic selection

OUTPUT Voltage during mains operation

230 Vac (+20/-25%)

Voltage during battery operation

230 Vac (+/- 10%)

Frequency during battery operation

50 or 60 Hz (+/- 1%)

Waveform

Pseudo-sine

BATTERIES Type

VRLA AGM lead acid maintenance free batteries

Charging time

6-8 hours

OTHER FEATURES Net weight (kg) Gross weight (kg)

4.1

4

4.4

Dimensions (hwd) (mm)

99 x 175 x 313

Packaging dimensions (hwd) (mm)

260 x 380 x 140

Communication

USB

Output socket

6 sockets (Shuko or Italian or French or English) + 2 IEC 320 C13

Regulations

EN 62040-1-1 and Directive EN 62040-3 EN 62040-2 and Directive 2004/108 EC

Trademarks

CE; GS/NEMKO on Shuko version

Ambient temperature Colour

24

3.7

0째C / +40째C Black

Altitude and relative humidity

6000 m max altitude, < 95% non-condensing

Standard equipment provided

power cable, user guide


UPS www.riello-ups.com

25


PERSONAL COMPUTERs

SMALL INFORMATION NETWORKS

iDialog 400-1600 VA Single-phase

Highlights

ECO LINE

• Compact • Silent • Contemporary design • Advanced ommunication • Auto restart • ECO Line environmental protection • Very low energy consumption

The iDialog range is the ideal solution for the protection of PCs and peripheral devices in domestic and office environments. iDialog is an easy-to-install and economical solution for protecting: • equipment such as PCs, Media Centres and peripheral devices, TVs, Home Cinemas, Satellite and Digital Terrestrial Receivers, DVD players and writers; • Modems and xDSL routers; • Small household appliances. Silent Operation Thanks to the use of high-frequency components and the absence of moving 26

parts, the noise produced by the UPS is equal to 0dbA. Advanced communication PowerShield3 software for the safe and unattended shutdown of connected IT systems on mains power supply failure. PowerShield3 provides efficient and intuitive UPS management through bar chart displays of important operating information. Automatic restart The UPS automatically restarts when the mains power supply is restored, after auto power.


IDG 400

IDG 600

IDG 800

IDG 1200

IDG 1600

POWER

400VA/240W

600VA/360W

800VA/480W

1200VA/720W

1600VA/960W

UPS

MODELS INPUT Nominal voltage

220-240 Vac

Input voltage tolerance

230 Vac (+20/-25%)

Frequency

50 or 60 Hz with automatic selection

OUTPUT Voltage during mains operation

230 Vac (+20/-25%)

Voltage during battery operation

230 Vac (+/- 10%)

Frequency during battery operation

50 or 60 Hz (+/- 1%)

Waveform

Pseudo-sine

BATTERIES Type

VRLA AGM lead acid maintenance free batteries

Charging time

6-8 h

OTHER FEATURES Net weight (kg)

3.2

3.4

6.6

7

Gross weight (kg)

3.7

4.1

8.1

8.6

Dimensions (hwd) (mm)

192 x 90 x 232

275 x 97 x 315

Packaging dimensions (hwd) (mm)

278 x 300 x 138

370 x 400 x 170

Communication Output socket

USB

USB + RS232

4 IEC 320 C13

6 IEC 320 C13

Regulations

EN 62040-1-1 and Directive EN 62040-3 EN 62040-2 and Directive 2004/108 EC

Trademarks

CE; GS/Nemko

Ambient temperature

0°C / +40°C

Colour

Black

Altitude and relative humidity

6000 m max altitude, <95% non-condensing

Standard equipment provided

2 output supply cables, 1 USB cable, user’s manual

ECO Line environmental protection iDialog features a unique shut-off button to reduce energy consumption during periods of prolonged inactivity. Features • ECO LINE product • Reduced energy consumption, operating at 99% efficiency • Maximum reliability and protection thanks to PowerShield3 supervision and shutdownsoftware, downloadable free of charge from www.riello-ups.com • Can be installed on PCs Windows operating systems 7, 2008, Vista, 2003,

www.riello-ups.com

XP, Linux, Mac OSX and Sun Solaris • With its compact shape iDialog can be placed on a desk or floor within a home or office environment. • Silent operation, iDialog is also suitable for protecting domestic digital equipment such as Home Cinemas, DVD writers, Satellite and Digital Terrestrial Receivers.

details IDG 400 IDG 600 IDG 800

IDG 1200 IDG 1600

SOCKET WITH UPS PROTECTION (NO BREAK IN POWER IF MAINS FAILS) RS232 SERIAL PORT

COMMUNICATION PORT SAFETY FUSE

2-YEAR WARRANTY

MAINS INPUT SOCKET FILTERED SOCKETS: OVERVOLTAGE PROTECTION ONLY

27


PERSONAL COMPUTERs

SMALL INFORMATION NETWORKS

Win Dialog Plus 400-800 VA Single-phase

Highlights • Automatic Voltage Regulator (AVR) • Advanced communication • Automatic battery test

The WIN DIALOG PLUS series includes the 400-600-800VA models and uses digital technology. The load is powered from the mains through an AVR to stabilise brownouts, sags, and surge voltages, and EMI filters to suppress spikes and transients. When the mains fails, the load is powered from a pseudo-sinewave inverter, to provide sufficient runtime for computer system shutdown using PowerShield3. PowerShield3, software, is downloadable free of charge from www.riello-ups.com.

28

Features • Stabilisation and filtering of the mains power supply using a built-in AVR and EMI filters for the elimination of atmospheric disturbances • Cold Start capability: the UPS can power up without a mains supply present • High reliability with built-in battery test • Auto restart (when mains power is restored, after discharge of the batteries) • Supplied with two IEC cables for powering the loads


WPG 400

WPG 600

WPG 800

POWER

400VA/240W

600VA/360W

800VA/480W

UPS

MODELS INPUT Nominal voltage

220-230-240 Vac

Input voltage tolerance

230 Vac (±25%)

Frequency

50 or 60 Hz with automatic selection

OUTPUT Voltage during mains operation

230 Vac (-8%, +10%)

Voltage during battery operation

230 Vac (+/- 5%)

Frequency during battery operation

50 or 60 Hz (+/- 0.5%)

Battery waveform

Pseudo sine wave

BATTERIES Type

VRLA AGM lead acid maintenance-free

Charging time

6-8 h

OTHER FEATURES Net weight (kg)

5.8

Gross weight (kg)

6.9

6.2 7.3

Dimensions (hwd) (mm)

152 x 110 x 325

Packaging dimensions (hwd) (mm)

140 x 380 x 230

Communication Output socket

USB 3 IEC SOCKET 320 C13

Regulations

EN 62040-1-1 and Directive EN 62040-3 EN 62040-2 and Directive 2004/108 EC

Trademarks

CE

Ambient temperature Colour

0°C / +40°C Dark grey RAL 7016

Altitude and relative humidity

6000 m max altitude, <95% non-condensing

Standard equipment provided

2 output supply cables, communications software; user manual

details

Advanced communication • Advanced communication, multiplatform, for all operating systems and network environments: PowerShield3 supervision and shutdownsoftware for Windows operating systems 7, 2008, Vista, 2003, XP, Linux, Mac OS X and Sun Solaris • Standard USB interface

WPG 400 - WPG 600 WPG 800

USB

MAINS INPUT Output socket

2-YEAR WARRANTY

www.riello-ups.com

29


PERSONAL COMPUTERs

SMALL INFORMATION NETWORKS

Net Dialog 800-2000 VA Single-phase

Highlights • Automatic Voltage Regulator (AVR) • Advanced communication • Automatic battery test

The NET DIALOG series includes the 800-1000 1500-2000VA models and uses digital technology: the load is powered from the mains through an AVR to stabilise brownouts, sags, and surge voltages, and EMI filters to suppress spikes and transients. When the mains fails, the load is powered from a pseudo-sinewave inverter, to provide sufficient runtime for computer system shutdown using PowerShield3. PowerShield3, software, is downloadable free of charge from www.riello-ups.com. The UPS also includes telephone line protection, with filtering. 30

For advanced communication and high performance, NET DIALOG, is the ideal solution for users who require total control over the power supply systems. Features • Stabilisation and filtering of the mains power supply using a built-in AVR • Cold Start capability: the UPS can power up without a mains supply present • Auto restart when mains power is restored • Integrated protection for telephone line/ RJ11/45 modem connection. • High reliability with automatic battery testing


NDG 800

NDG 1000

NDG 1500

NDG 2000

POWER

800VA/480W

1000VA/600W

1500VA/900W

2000VA/1200W

UPS

MODELS INPUT Nominal voltage

220-230-240 Vac

Input voltage tolerance

230 Vac (±25%)

Frequency

50 or 60 Hz with automatic selection

OUTPUT Voltage during mains operation

230 Vac (-8%, +10%)

Voltage during battery operation

230 Vac (+/- 5%)

Frequency during battery operation

50 or 60 Hz (+/- 0.5%)

Intervention time

usually 2 ms

Battery waveform

Pseudo-sine

BATTERIES Type

VRLA AGM lead acid maintenance free batteries

Charging time

4-6 h

OTHER FEATURES Net weight (kg) Gross weight (kg)

14

14.5

15

20

15.3

15.8

16.3

21.4

Dimensions (hwd) (mm)

180 x 140 x 375

214 x 140 x 410

Packaging dimensions (hwd) (mm)

260 x 480 x 300

270 x 520 x 320

Circuit protection devices

Excessive low battery - overvoltage - short-circuit

NET/Tel/Modem PC Protection

RJ11/45 connectors

Communication

RS232 serial port

Output socket Regulations

4 IEC SOCKET 320 C13 EN 62040-1-1 and Directive EN 62040-3 EN 62040-2 and Directive 2004/108 EC

Immunity to lightning

IEC 801-5

Ambient temperature

0°C / +40°C

Storage temperature

-15°C / 45°C

Relative humidity

< 95% non-condensing

Noise level

< 40 dBA a 1 m

Colour

Advanced communication • Advanced communication, multi-platform, for all operating systems and network environments: Supervision and shutdown PowerShield3 software for Windows operating systems 7, 2008, Vista, 2003, XP, Linux, Mac OS X, Sun Solaris, Linux, Novell and other Unix operating systems • UPS is supplied with a cable for direct connection to the PC 2-YEAR WARRANTY

Dark grey RAL 7016

details NDG 800 NDG 1000 NDG 1500

NDG 2000

RS232 SERIAL PORT

TELEPHONE/ LINE MODEM PROTECTION

Output socket MAINS INPUT

www.riello-ups.com

31


SMALL INFORMATION NETWORKS

Local Area Networks (LAN)

WORK STATIONS

ServerS

POINT oF SALES SYSTEMS (PoS)

Vision 800-2000 VA Single-phase

Highlights

ECO LINE

• Superior protection • Compact and contemporary design • High availability • Versatility • LCD Display • Advanced communication • Automatic Voltage Regulator (AVR)

The VISION series is available in a Tower version (VST) from 800VA to 2000VA with digital sinewave technology. The VISION series, thanks to its connectivity and advanced communications, is the ideal solution for users who require a power solution offering superior protection and versatility. VISION is the best protection for peripheral network devices, servers, and network back-up systems.

32

High protection The Vision series uses Line Interactive technology and provides a sinewave output. The UPS is 98% efficient with a low energy consumption. The UPS also provides a high level of protection against mains power disturbances. An AVR (Automatic Voltage Regulator provides protection from brownouts, surges, overvoltages and undervoltage without battery intervention.


UPS

Reduced battery usage ensures that the battery set is 100% available for mains power failures. EMI filters provide further protection from surges and transients. When the mains power supply fails, the load is powered by the inverter, providing a perfect sinewave for maximum power continuity and reliability. High availability A EnergyShare socket allows loadshedding and the shutdown of less critical peripheral devices to extend the battery runtime. “Hot Swap” batteries can be removed from the front panel for easy and safe UPS maintenance. Battery test facility to detect deteriorating battery performance and failure. Deep discharge protection to reduce general battery ageing. Versatility “Cold start” function allowing the UPS to be powered up without a mains power supply present. LCD Display Vision UPS have a backlit LCD display providing UPS status information including the load and battery charge percentages. Advanced communication • Advanced communication, multiplatform, for all operating systems and network environments: PowerShield3 supervision and shutdownsoftware for Windows operating systems 7, 2008, Vista, 2003, XP, Linux, Mac OS X, Sun Solaris, Linux, Novell and other Unix operating systems. • USB or RS232 (selectable) • Expansion slot for SNMP network adapter card • Status, measurements, alarms, and input, output and battery parameters available on the LCD display. Features • ECO LINE product • EnergyShare socket • Surge protected sockets for powering larger absorption loads such as laser printers • Ability to switch on the UPS without a mains power supply (Cold Start) www.riello-ups.com

• User replaceable batteries (Battery Swap) • USB Interface and RS232 • Slot for communication boards • Maximum reliability and protection of PCs and file serversrunning PowerShield3 supervision and shutdownsoftware, downloadable free from www.riello-ups.com

• Short circuit proctection • Auto restart (when mains power is restored, after battery discharge) • GS/Nemko Safety mark 2-YEAR WARRANTY

• Fully configurable using UPS Tools configuration software • High reliability (automatic and manually activated battery test)

details VST 800 VST 1100

VST 1500 VST 2000

USB RS232 SERIAL PORT SLOT FOR COMMUNICATION BOARDS SAFETY FUSE Output socket MAINS INPUT ENERGYSHARE

33


MODELS

VST 800

VST 1100

VST 1500

VST 2000

POWER

800VA/640W

1100VA/880W

1500VA/1200W

2000VA/1600W

INPUT Nominal voltage

230 Vac (200, 208, 220, 240 V selectable)

Voltage tolerance

160 - 294 Vac

Frequency

50 or 60 Hz with automatic selection

Frequency tolerance

±5%

OUTPUT Nominal voltage

230 Vac (200, 208, 220, 240 V selectable)

Frequency

50 or 60 Hz with automatic selection

Waveform

Sinusoidal

BATTERIES Type

VRLA AGM lead acid maintenance free batteries

Charging time

4-6 h

OTHER FEATURES Net weight (kg)

10.5

11.3

16.5

18.5

Gross weight (kg)

12.2

13

18.4

20.4

Dimensions (hwd) (mm) Packaging dimensions (hwd) (mm) Protection devices

247 x 120 x 443

247 x 160 x 443

342 x 208 x 530

354 x 250 x 540

Overcurrent - short-circuit - overvoltage - undervoltage - temperature - excessive low battery

Communication

USB / RS232 / slot for communications interface

Input sockets Output socket Regulations

4 IEC 320 C13

6 IEC 320 C13 EN 62040-1-1 e direttiva 2006/95/EC EN 62040-2 e direttiva 2004/108 EC

Ambient temperature

0°C / +40°C

Storage temperature

-15°C / 45°C

Colour Relative humidity Noise level

34

1IEC 320 C14

Dark grey RAL 7016 <95% non-condensing < 50 dBA


UPS www.riello-ups.com

35


SMALL INFORMATION NETWORKS

Local Area Networks (LAN)

WORK STATIONS

ServerS

POINT oF SALES SYSTEMS (PoS)

Dialog Vision 500-3000 VA Single-phase

ECO LINE

Highlights • Superior protection • High availability • Versatility • LCD Display • Advanced communication • Automatic Voltage Regulator (AVR)

The DIALOG VISION series includes the DVR (Rack version) and DVD (Dual Rack/ Tower version) with models from 500VA to 3000VA and uses sinewave digital technology. The DIALOG VISION range, with its advanced communications and connectivity options, is the ideal solution for the most demanding of customers looking for superior protection and versatility. DIALOG VISION is the best protection for network devices, rackmounted servers, conventional rack-mounted or tower servers, network storage systems. Very high protection An Automatic Voltage Regulator (AVR) 36

provides stabilisation from brownouts, sag and surge voltages. EMI filters then provide further protection from spikes and transients. When the mains power supply fails, the load is powered by the inverter and receives a true sinewave supply for maximum power continuity and reliability. The UPS also incorporates protection for PC and network, telephone line/modem connections (RJ45-RJ11). High availability One EnergyShare socket for loadshedding of the least critical loads to maximise back up time for the most critical servers. Hot swappable battery (front access) for


Versatility Dialog Vision Dual (DVD 1500, 2200 and 3000) can be placed directly onto the floor or mounted in 19’’ rackmount cabinets. The front panel digital display can be easily pulled out and rotated to suit the installation format. Dialog Vision includes an Emergency Power Off (EPO) input contact. Cold Start function to allow a Dialog Vision to power up with no mains power supply present.

down software included, with SNMP agent, for Windows 7, 2008, Vista, 2003, XP, Linux, Mac OS X, Sun Solaris, Linux, VMWare ESX operating systems and other Unix operating systems • USB or RS232 serial port (selectable) • Slot-in SNMP network adapter card • LCD Display. Features • ECO LINE product • EnergyShare socket • Surge-protected sockets for powering strong impulsive absorption loads (laser printers, etc) • Ability to switch on the UPS in the absence of mains power (Cold Start)

Advanced communication • Advanced communication, multiplatform, for all operating systems and network environments: Powershield3 supervision and shut-

• User-replaceable batteries (Battery Swap) • USB Interface AND RS232 • Slot for communication boards • Maximum reliability in PC protection thanks to the PowerShield3 supervision and shutdown software, downloadable free of charge from www.riello-ups.com • Highly reliable batteries (automatic and manually activated battery test) • Protected against short-circuits • Auto restart (when mains power is restored, after discharge of the batteries) • EPO

UPS

simple and risk-free UPS maintenance. Additional Battery Boxes (with chargers) are available for the DVD 2200 and 3000 for long back up time applications. Battery Test facility to detect deteriorating battery performance and failure. Deep discharge protection: in the case of low load long discharge periods, the end-of-discharge voltage threshold is increased as recommended by battery manufacturers, in order to avoid damaging the battery

2-YEAR WARRANTY

details

DVR 500/800/1100

ENERGYSHARE SOCKET

IEC OUTPUT SOCKET

INPUT PLUG RETE IEC

DVD 1500

battery box MODELS DVD MODELS

RS232 SERIAL INTERFACE

BB DVD 96-A5

USB PORT

EPO

THERMAL OUTPUT PROTECTION

IEC OUTPUT SOCKET

TELEPHONE/ MODEM PROTECTION

DVD 2200 - DVD 3000 DVD 2200/3000

88

Dimensions (mm)

43

8

1. Remove the mimic panel by pressing the appropriate button

BATTERY EXPANSION CONNECTOR

2

58

2. Rotate the mimic panel and insert it into position

ENERGYSHARE SOCKET

3. Rotate the UPS 90°

IEC 16° OUTPUT SOCKET

4. Insert the UPS into the rack

90°

90°

www.riello-ups.com

37


MODELS

DVR 500

DVR 800

DVR 1100

DVD 1500

DVD 2200

DVD 3000

POWER

500VA/350W

800VA/540W

1100VA/740W

1500VA/1050W

2200VA/1540W

3000VA/2100W

INPUT Nominal voltage

230 Vac (200, 208, 220, 240 V selectable)

Voltage tolerance

160 - 294 Vac

Frequency

50 or 60 Hz with automatic selection

Frequency tolerance

±5%

OUTPUT Nominal voltage

230 Vac (200, 208, 220, 240 V selectable)

Frequency

50 or 60 Hz with automatic selection

Waveform

Sinusoidal

BATTERIES Type

VRLA AGM lead acid maintenance free batteries

Charging time

4-6 h

OTHER FEATURES Net weight (kg)

12

13.5

15.6

28.7

31

32.8

Gross weight (kg)

16

18

20

32.5

36

38

Dimensions (hwd) (mm) Packaging dimensions (hwd) (mm) Protection devices

1U x 19” x 460

T 88 x 438 x 582 - R 2U x 19” x 582

200 x 605 x 623

260 x 726 x 623

Overcurrent - short-circuit - overvoltage - undervoltage - temperature - excessive low battery

Communication Input sockets Output socket Regulations

1 IEC 320 C14 4 IEC 320 C13

1 IEC 320 C20 8 IEC 320 C13

0°C / +40°C

Storage temperature

-15°C / 45°C

Relative humidity Noise level

8 IEC 320 C13 - 1 IEC 320 C19

EN 62040-1-1 and Directive 2006/95/EC EN 62040-2 and Directive 2004/108 EC

Ambient temperature Colour

38

USB / RS232 / slot for communications interface

Dark grey RAL 7016 <95% non-condensing < 50 dBA


UPS www.riello-ups.com

39


SMALL INFORMATION NETWORKS

Local Area Networks (LAN)

WORK STATIONS

ServerS

POINT OF SALES SYSTEMS (EPO)

Sentinel Pro 700-3000 VA Single-phase

Highlights

ECO LINE

• Operating flexibility • Emergency function • Battery optimisation • Runtime Expandability • Reduced noise • On-line (VFI)

After years of success with the Dialog series, Riello UPS introduces its evolution: the Sentinel Pro series. Customers will appreciate Premium Pro for its unique, modern design and for improvements in performance made possible by the continuous technological research carried out in the Riello UPS research centres. Sentinel PRO uses On-line double conversion technology, resulting in the highest levels of reliability and maximum protection for critical loads such as servers, and IT and Voice/Data applications.

40

In business continuity applications that require long battery operation times, it is possible to extend runtimes by several hours using ER versions equipped with more powerful battery chargers. The front mimic panel has been entirely redesigned, adding an LCD display that shows the input and output voltages, and battery readings in addition to the UPS operating status. The inverter and the microprocessor control stage has been completely redesigned to provide increased efficiency and greater configuration options.


UPS

Another feature of the Sentinel Pro series is its maximum expandability. The UPS is supplied with a USB port and an expansion slot for protocol conversion or relay contacts boards. Sentinel PRO features a unique shut-off button to reduce energy consumption during periods of prolonged inactivity (ECO LINE). Sentinel PRO is available in 700VA, 1000VA, 1500VA, 2200VA and 3000VA models. Operating flexibility Different operating modes, programmable depending on user requirements and the load to be powered, have been introduced in order to reduce energy consumption. • Economy Mode: the UPS can operate in line interactive mode, with the load powered by the mains, reducing consumption and thus improving efficiency (up to 98%). • Smart Active Mode: the UPS automatically selects on-line or line interactive operation, depending on the quality of the mains supply, checking the number, frequency and the type of disturbances present. • Stand by Off (emergency back-up): the UPS powers the loads only in the event of mains failure. The inverter begins working with a progressive start-up sequence to prevent inrush currents. • Operation as a frequency converter (50 or 60 Hz) Emergency function This configuration ensures the operation of those devices that must be powered during mains failure, including emergency lighting systems, fire detection/exit systems, alarms etc. When the mains supply fails, the inverter begins powering the load with a progressive start (Soft Start) in order to prevent overloading. Battery optimisation The Sentinel PRO series is equipped with deep discharge protection to help optimise battery life. Periodically the UPS carries out a battery efficiency test (also manually activated) and its wide input voltage range, helps to reduce battery usage.

www.riello-ups.com

Runtime expandability Optional battery extension packs can be connected to increase UPS runtime. In addition the Sentinel PRO range includes ER versions with more powerful battery chargers in place of the internal batteries to enable fast recharge times.

• Highly reliable batteries (automatic and manually activated battery test) • High level of UPS reliability (total microprocessor control) • Low impact on the mains (sinusoidal absorption) • Input protection with resettable fuse.

Reduced noise Thanks to the use of high-frequency components and load-based fan speed control, the noise produced by the UPS is reduced to less than 40dB.

Advanced communication • Multi-platform communication for all operating systems and network environments; supervision and shutdown PowerShield3 software for Windows operating systems 7, 2008, Vista, 2003, XP, Linux, Mac OS X, Sun Solaris, VMware ESX and other Unix operating systems • Standard supplied UPS Tools configuration and customisation software • RS232 serial port and opto-isolated contacts • USB Port • Slot for communication boards

Features • Filtered, stabilised and reliable voltage: double conversion On-line technology (VFI compliant with IEC 62040-3) standard with filters for the suppression of atmospheric disturbances. • High overload (up to 150%) • Programmable Auto-restart when mains is restored • Battery start-up (cold start) • Power factor correction (UPS input power factor, close to 1) • Wide input voltage range (from 140V to 276V) without battery intervention. • Runtime can be extended up to several hours • Fully configurable using UPS Tools configuration software

2-YEAR WARRANTY

41


details SEP 2200 SEP 2200 ER

SEP 3000 SEP 3000 ER USB PORT

SEP 700 SEP 1500

COMMUNICATION SLOT

SERIAL INTERFACE

SEP 1000 SEP 1000 ER

BATTERY EXPANSION CONNECTOR OUTPUT THERMAL PROTECTION Output socket INPUT THERMAL PROTECTION INPUT SOCKET

MODELS

BB SEP 36-A3 / BB SEP 36-M1

BB SEP 72-A3 / BB SEP 72-M1

SEP 1000

SEP 2200-3000 / ER

SEP MODELS

333

235

Dimensions (mm)

6

2

158

42

44

42

190


SEP 700

POWER

700VA/560W

SEP 1000

SEP 1000 ER

1000VA/800W

SEP 1500

SEP 2200

1500VA/1200W

SEP 2200 ER

SEP 3000

2200VA/1760W

UPS

MODELS

SEP 3000 ER

3000VA/2400W

INPUT Nominal voltage

220-230-240 Vac

Voltage range without battery intervention

140 Vac < Vin < 276 Vac @50% LOAD / 184 Vac < Vin < 276 Vac @ 100% LOAD

Max allowable voltage

300 Vac

Nominal frequency

50 or 60 Hz

Frequency range

50 Hz ± 5% / 60 Hz ± 5%

Power factor

> 0.99

Current distortion

≤7%

BY PASS Voltage tolerance

180 - 264 Vac

Frequency tolerance

Selectable from ±1.5Hz to ±5Hz

OUTPUT Voltage distortion with linear load / with non-linear load

< 2% / < 4%

Frequency

Selectable: 50 Hz or 60 Hz or automatic selection

Static variation

± 1%

Dynamic variation

≤ 5% in 20 msec.

Waveform

Sinusoidal

Current crest factor

3:1

ECO Mode and Smart Active Output

98%

BATTERIES Type Charging time

VRLA AGM lead acid maintenance free batteries 2-4 hours

N.A.

2-4 hours

N.A.

2-4 hours

N.A.

OVERLOAD TIMES 100% < Load < 110%

2 minutes

110% < Load < 150%

5 seconds

Load > 150%

1 second

OTHER FEATURES Net weight (kg)

10,9

13,3

7

14,8

25,6

10,6

28

14

Gross weight (kg)

12,5

14,9

8,6

15,5

28,8

13,8

31,2

17,2

Dimensions (hwd) (mm)

235 x 158 x 422

333 x 190 x 446

Packaging dimensions (hwd) (mm)

340 x 245 x 500

470 x 325 x 585

Surge protection Protection devices Communication

300 joule Overcurrent - short-circuit - overvoltage - undervoltage - thermal - excessive low battery protection devices USB / DB9 con RS232 e contatti / Slot for communications interface

Input sockets Output socket Regulations Ambient temperature Relative humidity Colour Noise level Standard equipment provided standard

www.riello-ups.com

1 iEC 320 C14

1 iEC 320 C20

4 iEC 320 C13

8 iEC 320 C13

8 iEC 320 C13 + 1 iEC 320 C19

Safety: EN 62040-1 and Directive 2006/95/EL; EMC: EN 620040-2 category C2 and Directive 2004/108/EL 0°C / +40°C < 95% non-condensing Black < 40 dBA @ 1 m Power cable, serial cable, USB cable, safety manual, quick start, software on CD-ROM

43


Local Area Networks (LAN)

ServerS

DATA CENTRES

CASH REGISTERS

TELECOMMUNICATIONS DEVICES

INDUSTRIAL PLCs

EMERGENCY DEVICES (Lights/Alarms)

Sentinel Dual Low Power 1-3 kVA

Single-phase 6

Highlights • Simplified Installation • Installation Versatility • Reduced management costs • Runtime Expandability • Reduced noise • On-line (VFI)

Sentinel Dual is a new range of high density double conversion on-line UPS, suitable for powering a wide range of devices including servers, storage systems, telephony equipment - VoIP, network, medical and industrial systems. The Sentinel Dual rating are ideal for powering and protecting Blade Server systems with high input power factor. Its height of only 2U makes Sentinel ideal for 19” rack cabinets. Customers will appreciate Sentinel Dual for its practical, modern design and for 44

improvements in performance made possible by the continuous technological research carried out by Riello UPS research and development team. The newly-designed inverter is one of the best energy conversion systems on the market, thanks its 0.9 output power factor and its 92% efficiency rate in On-line operation mode. In business continuity applications that require long battery operation times, it is possible to extend runtime by several hours by using ER versions equipped with more powerful battery chargers.


Simplified Installation • Sentinel Dual can be installed as a tower or in 19” rack cabinets, by simply removing and rotating the mimic panel • Low noise (<40dBA) for installation in any environment thanks to PWM digitally-controlled ventilation, depending on the load applied on the use of the high frequency switching inverter. • Features guaranteed up to 40° C (the components are designed for high temperatures and thus subject to less stress at normal temperatures) • On Sentinel Dual models, the output plugs can be programmed to disconnect less critical loads during blackouts (EnergyShare function). Installation Versatility Sentinel Dual can be used in tower or rack version, by simply turning the display and adding the supplied handles (optional runners). Reduced management costs The functions can be programmed using software or manually set by the mimic panel, making this UPS range very flexible and easy to use. Sentinel Dual can be configured in the following operating modes: • On-line, maximum power protection and output voltage waveform quality • ECO Mode, to increase output (up to to 98%) , allows Line Interactive technology to be selected • Smart Active, the UPS automatically decides upon the operating mode based on the quality of the network. 1. Remove the mimic panel

• Back-up, the UPS can be selected to function only when mains power fails (emergency mode only) • Frequency converter (50 or 60 Hz). Sentinel Dual offers maximum flexibility for integration with any communication system. • Multi-platform communication for all operating systems and network environments; supervision and shutdown PowerShield3 software for Windows operating systems 7, 2008, Vista, 2003, XP, Linux, Mac OS X, Sun Solaris, VMware ESX and other Unix operating systems. • Standard supplied UPS Tools configuration and customisation software • RS232 serial port and opto-isolated contacts • USB Port • Slot for communication boards such as Modbus/Jbus, TCP/IP, SNMP and relay contacts Emergency function This configuration ensures the operation of those devices that must be powered during mains failure, including emergency lighting systems, fire detection/exit systems, alarms etc. In case of a black-out, the inverter begins powering the load with a progressive start (Soft start) in order to prevent overloading. High quality output voltage • Even with non-linear loads (loads with a crest factor of up to 3:1) • High short circuit current on Bypass • High overload capacity 150% by inverter (even with mains failure • Filtered, stabilised and reliable voltage (double conversion On-line technology (VFI compliant with EN62040-2 class C1) with filters for the suppression of atmospheric disturbances.

2. Rotate the mimic panel and insert it into position

• Power factor correction: UPS input power factor, close to 1 and sinewave current absorption

UPS

Having always been sensitive to energy savings, Riello UPS has introduced a shutoff button in the Sentinel Dual series to reduce energy consumption to zero during prolonged periods of inactivity.

High battery reliability • Automatic and manual battery test • Batteries are user replaceable without interruption to the load (Hot Swap) • Unlimited extendible runtime via dedicated Battery Boxes with the same appearance as the UPS. Reduced noise Thanks to the use of high frequency components and load-based fan speed control, the noise produced by the UPS is less than 40dB. Other features • Output voltage can be selected using software (220-230-240V) • Auto-restart when mains power is restored (programmable via software) • Stand-by on Bypass: when the UPS is switched off, it automatically goes into bypass and battery charge mode • Minimum load switch-off • Battery discharge warning • Start-up delay • Total microprocessor control • Automatic bypass without interruption • Status, measurements and alarms available on standard, backlit display. • UPS firmware updating via PC • Input protection through resettable thermal switch (versions up to 1500VA) • Standard Back-feed protection: to prevent energy from being fed back to the network • Manual switching to bypass. 2-YEAR WARRANTY

3. Rotate the UPS 90°

4. Attach the rack supports

90°

90°

www.riello-ups.com

45


particulars

INPUT SOCKET

THERMAL INPUT PROTECTION

EMERGENCY

SDH 1000

SDH 1500 SWITCH DEVICE (ESD)

BBX

SDH 2200/2200ER 3000/3000 ER

OUTPUT SOCKET

BATTERY EXPANSION OUTLET

Serial RS232

MAINS INPUT

USB PORT

battery box MODELS

BB SDH 36-A3 / BB SDH 36-M1

BB SDH 72-A3 / BB SDH 72-M1

SDH 1000

SDH 2200-3000

MODELS SDH Dimensions (mm)

450

450

OPTIONS • Universal rails for installation in rack cabinets • Multipass 16 bypass (mm/kg): 2U x 438 x 360 - rack 6.8 version weight

5

62

5

42 87

46

87


SDH 1000

SDH 1500

SDH 2200

SDH 2200 ER

SDH 3000

SDH 3000 ER

POWER

1000VA/900W

1500VA/1350W

2200VA/1980W

2200VA/1760W

3000VA/2700W

3000VA/2400W

UPS

MODELS INPUT Nominal voltage

220-230-240 Vac

Voltage range without battery intervention

140 Vac < Vin < 276 Vac @50% LOAD / 184 Vac < Vin < 276 Vac @ 100% LOAD

Max allowable voltage

300 V

Nominal frequency

50 or 60 Hz ±5Hz

Frequency range

50 Hz ± 5% / 60 Hz ± 5%

Power factor

> 0.98

Current distortion

≤7%

BY PASS Voltage tolerance

200 - 253 Vac

Frequency tolerance

Frequency selected (from ±0.5Hz to ±5Hz configurable)

OUTPUT Voltage distortion with linear load / with non-linear load

< 2%

Frequency

Selectable: 50 Hz or 60 Hz or automatic selection

Static variation

± 1%

Dynamic variation

≤ 5% in 20 msec.

Waveform

Sinusoidal

Current crest factor

3:1

ECO Mode and Smart Active Output

98%

BATTERIES Type

VRLA AGM lead acid maintenance free batteries

Charging time

2-4 hours

OVERLOAD TIMES 100% < Load < 110%

1 minute

110% < Load < 150%

4 seconds

Load > 150%

0.5 seconds

OTHER FEATURES Net weight (kg) Gross weight (kg)

17.5

18

30.5

15

31

15

21

21.5

35

19.5

35.5

19.5

Dimensions (hwd) (mm)

87x450x425 (2Ux19”x425)

87x450x625 (2Ux19”x625)

Packaging dimensions (hwd) (mm)

245x550x600

245x600x760

Surge protection Protection devices

300 joule Overcurrent - short-circuit - overvoltage - undervoltage - thermal - excessive low battery protection devices

Communication Input sockets Output socket Compliance with Standards Ambient temperature Relative humidity Colour Noise level Standard equipment provided

www.riello-ups.com

USB / DB9 con RS232 e contatti / Slot for communications interface 1 iEC 320 C14

1 iEC 320 C20

8 iEC 320 C13

8 iEC 320 C13 + 1 iEC 320 C19

Safety: EN 62040-1 and Directive 2006/95/EL; EMC: EN 620040-2 category C2 and Directive 2004/108/EL 0°C / +40°C < 95% non-condensing Black < 40 dBA @ 1 m Power cable, serial cable, USB cable, safety manual, quick start, software on CD-ROM

47


Local Area Networks (LAN)

ServerS

DATA CENTRES

CASH REGISTERS

INDUSTRIAL PLCs

ELECTROMEDICAL DEVICES

EMERGENCY DEVICES (Lights/Alarms)

Sentinel Dual High Power 3.3-10 kVA

single/single-phase and three/single-phase 6

Highlights • Simplified Installation • Operation selection • High quality output voltage • High battery reliability • Emergency Back-up function • Battery optimisation • EnergyShare • Reduced noise • On-line (VFI)

48

SENTINEL DUAL is the best solution for powering sensitive and vital “mission critical” utilities and safety devices (electro-medical), ensuring maximum power reliability. The flexibility of installation and use (digital display, user-removable batteries) and the many communication options, make SENTINEL DUAL a UPS suitable for many applications, from information technology to security. SENTINEL DUAL can be installed on the floor or in rack cabinets for networking applications. The SENTINEL DUAL is available in 3.3-4 5-6-8-10 kVA models and uses double conversion On-line technology (VFI): the load is powered continuously by the inverter which supplies sinusoidal voltage

that is filtered and stabilised in terms of voltage, form and frequency; in addition, the input and output filters significantly increase the load’s immunity to network disturbances and lightning strikes. Technology and performance: selectable Economy Mode and Smart Active Mode functions Diagnostics: standard digital display, RS232 and USB interface with PowerShield3 software included, and communication slot for connectivity accessories.

Simplified Installation • May be installed on the floor (tower version) or in rackmount cabinets (rack version). The mimic panel can be rotated (using the key supplied)


Operation selection The functions may be programmed using software or manually via the mimic panel • On-line • ECO Mode, to increase output (up to 98%), allows for selection of Line Interactive technology (VI) to power low priority loads from the mains. • Smart Active, the UPS automatically decides upon the operating mode (VI or VFI) based on the quality of the network. • Back-up, the UPS can be selected to function only when mains power fails (emergency mode only) • Frequency converter (50 or 60 Hz).

High quality output voltage • Even with non-linear loads (loads with a rest factor of up to 3:1) • High short circuit current on Bypass • High overload capacity 150% by inverter (even with mains failure 1. Release the mimic panel by applying pressure to the catch

• Filtered, stabilised and reliable voltage (double conversion On-line technology (VFI compliant with IEC 62040-3) with filters for the suppression of atmospheric disturbances. • Power factor correction: UPS input power factor, close to 1 and sinewave current absorption High battery reliability • Automatic and manual battery test • Reduced ripple component (detrimental to the batteries) thanks to the “LRCD” system (Low Ripple Current Discharge) • Batteries are user replaceable without interruption to the power to the load (Hot Swap) • Unlimited extendible runtime via dedicated modular design Battery Boxes • The batteries are not activated during mains failure of <40 ms (high hold up time) or when there are variations in input voltage (from 84V to 276V). Emergency Back-up function This configuration ensures the operation of those devices that require continuous and lasting power during mains failure, such as emergency lighting systems, fire detection/ extinction systems, alarms etc. In case of a black-out, the inverter begins powering the load with a progressive start (Soft start) in order to prevent overloading. Battery optimisation The wide input range and a high Hold Up Time value minimise battery interventions and increase efficiency and battery life; for smaller power breaks, energy is drawn from a group of appropriately-sized capacitors.

off of low priority loads; alternatively, emergency only loads, normally not powered when the mains is present, can be activated.

UPS

• Low noise (<40dBA): can be installed in any environment thanks to its PWM digitally-controlled ventilation, dependent on the load applied and on the use of a high frequency switching inverter • Can be connected to an external maintenance bypass (5-6-8-10 kVA SDLs) • Features guaranteed up to 40°C (the components are designed for high temperatures and are thus subject to less stress at normal temperatures) • Availability of two built-in IEC output sockets with thermal protection (5-68-10 kVA SDLs) • On the 5-6-8-10 kVA models it is possible to programme two 10A output sockets (EnergyShare function) to turn off when the mains power supply fails.

Reduced noise Thanks to the digital PWM control, the speed of the fans is adjusted depending on the temperature of the two internal heatsyncs, ensuring extended life and a reduction in noise to less than 45dB. Other features • Output voltage can be selected using software (220-230-240V) • Auto-restart when mains power is restored (programmable via software) • Bypass on: when the machine is switched off, it automatically goes into bypass and battery charge mode • Minimum load switch-off • Low battery warning • Start-up delay • Total microprocessor control • Automatic bypass without interruption • Use of IMS modules (Insulated Metallic Substrates) • Statuses, measurements and alarms available on standard, backlit display. • UPS digital updating (flash upgradable) • Input protection through resettable thermal switch • Standard Back-feed protection: to prevent energy from being fed back to the network • Manual switching to bypass.

EnergyShare (5÷10kVA) The presence of two configurable IEC output sockets, allows for runtime optimisation, programming the switch-

2. Rotate the mimic panel counter clockwise and then secure it back in place

3. Rotate the UPS 90°

4. Attach the rack supports

90°

90°

www.riello-ups.com

49


details

Advanced communication • Advanced multi-platform communication for all operating systems and network environments; supervision and shutdown PowerShield3 software for Windows operating systems 7, 2008, Vista, 2003, XP, Linux, Mac OS X, Sun Solaris, VMware ESX and other Unix operating systems. • Plug and Play function • USB Port • RS232 serial port • Slot for installation of communications boards

SDL 3300 SDL 4000

SDL 8000 SDL 10000 SDL 6500 TM SDL 8000 TM SDL 10000 TM

SDL 5000 SDL 6000

USB PORT SERIAL PORT COMMUNICATION SLOT

THERMAL INPUT PROTECTION INPUT SOCKET

Output socket BATTERY EXPANSION CONNECTOR

2-YEAR WARRANTY

INPUT CABLE ACCESS

Options • Battery cabinets for extended runtimes, with or without batteries • Telescopic rails for rack cabinet mounting

OUTPUT CABLE ACCESS

battery box MODELS

BB SDL 108-A4 / BB SDL 108-M1

BB SDL 192-A3/ BB SDL 192-A6

BC SDL 108-B1

SDL 3300-4000

SDL 5000-6000 SDL 6500TM-8000-8000TM-10000-10000TM

SDL 3300-4000 Tower

MODELS SDL

19 ’’ 17 5

520

19 ’’

0

52

17 5

660

630

4U

455

4U

455

Dimensions (mm)

0

66

21 5

655

4U = 176 mm; 19” = 438 mm

50


SDL 3300

SDL 4000

SDL 5000

SDL 6000

SDL 8000

SDL 10000

POWER

3300VA/2300W

4000VA/2400W

5000VA/3500W

6000VA/4200W

8000VA/6400W

10000VA/8000W

UPS

MODELS INPUT Nominal voltage

220-230-240 Vac

Minimum voltage

164 Vac @ load 100% / 84 Vac @ load 50%

Nominal frequency

50 or 60 Hz ±5Hz

Power factor

> 0.98

Current distortion

≤7%

BY PASS Voltage tolerance

180 - 264 Vac (selectable in Economy Mode and Smart Active Mode)

Frequency tolerance

Selected frequency ±5% (selectable by user)

OUTPUT Nominal voltage

220-230-240 Vac selectable

Voltage distortion

< 3% with linear load / < 6% with non-linear load

Frequency

50 or 60 Hz selectable

Static variation

1.5%

Dynamic variation

≤ 5% in 20 ms

Waveform

Sinusoidal

Crest factor

3:1

BATTERIES Charging time

4-6 hours

OVERLOAD TIMES 100% < Load < 110%

1 minute

110% < Load < 150%

4 seconds

Load > 150%

0.5 seconds

OTHER FEATURES Net weight (kg) Gross weight (kg)

38

40

62

64

94

95

42.5

44.5

70

72

102

103

Dimensions (hwd) (mm)

455 x 175 x 520 tower 175(4U)x19”x483 rack

455 x 175 x 660 tower 175(4U)x19”x660 rack

2 x 455 x 175 x 660 tower 2 x 175(4U)x19”x660 rack

Packaging dimensions (hwd) (mm)

540 x 620 x 280

720 x 530 x (270+15)

780 x 555 x (270+15)

Line-Interactive/ Smart Active output

98%

Protection devices

Overcurrent - short-circuit - overvoltage - undervoltage - thermal - excessive low battery protection devices

Communication

USB / RS232 + slot for communications interface

Input sockets

1 iEC 320 C20

Terminal board

Output socket

2 IEC 320 C13 + 1 iEC 320 C20

Terminal board + 2 IEC 320 C13

Regulations

EN 62040-1 EMC EN 62040-2 Directive 73/23 - 93/68 - 2004/108 EC EN 62040-3

Ambient temperature

0°C / +40°C

Relative humidity

< 95% non-condensing

Colour Noise level Standard equipment provided standard

www.riello-ups.com

Dark grey RAL 7016 < 40 dBA a 1 m

< 45 dBA a 1 m

Two 10A cables; One IEC-16A plug; software; serial cable; keys to release mimic panel; handles kit

Two cable guides; terminal board connections; One IEC-16A plug; software; serial cable; keys to release mimic panel; handle kit

51


MODELS

SDL 6500 TM

SDL 8000 TM

SDL 10000 TM

POWER

6500VA/5200W

8000VA/6400W

10000VA/8000W

INPUT Nominal voltage

400 Vac Three-phase + N

Minimum voltage (F + N)

164 Vac @ load 100% / 84 Vac @ load 50%

Nominal frequency

50 or 60 Hz ±5Hz

Power factor

> 0.95

BY PASS Voltage tolerance

180 - 264 Vac (selectable in Economy Mode or Smart Active Mode)

Frequency tolerance

Selected frequency ±5% (selectable by user)

OUTPUT Nominal voltage

220-230-240 Vac selectable

Voltage distortion

< 3% with linear load / < 6% with non-linear load

Frequency

50 or 60 Hz selectable

Static variation

1.5%

Dynamic variation

≤ 5% in 20 ms

Waveform

Sinusoidal

Crest factor

3:1

BATTERIES Charging time

4-6 hours

OVERLOAD TIMES 100% < Load < 110%

1 minute

110% < Load < 150%

4 seconds

Load > 150%

0.5 seconds

OTHER FEATURES Net weight (kg)

91

94

95

Gross weight (kg)

99

102

103

Dimensions (hwd) (mm)

2 x 660x175x455 / 2 x 4Ux19”x660

Packaging dimensions (hwd) (mm)

780 x 555 x (270+15)

Smart Active Output

up to 98%

Protection devices

Overcurrent - short-circuit - overvoltage - undervoltage - thermal - excessive low battery protection devices

Communication Input sockets Output socket Regulations Ambient temperature Relative humidity Colour Noise level Standard equipment provided standard

52

USB / RS232 + slot for communications interface Terminal board Terminal board + 2 IEC 320 C13 EN 62040-1 EMC EN 62040-2 Directive 73/23 - 93/68 - 2004/108 EC EN 62040-3 0°C / +40°C < 95% non-condensing Dark grey RAL 7016 < 45 dBA a 1 m Two cable guides; terminal board connections; One IEC-16A plug; software; serial cable; keys to release mimic panel; handle kit


UPS www.riello-ups.com

53


Local Area Networks (LAN)

ServerS

DATA CENTRES

CASH REGISTERS

TELECOMMUNICATIONS DEVICES

INDUSTRIAL PLCs

ELECTROMEDICAL DEVICES

EMERGENCY DEVICES (Lights/Alarms)

Sentinel Power 5-6 kVA

single/single-phase

6.5-10 kVA

6

single/single-phase and three/single-phase

Highlights • High UPS reliability • Operation Mode selection • High quality output voltage • Simplified Installation • High battery reliability • EnergyShare • Low impact on mains network

Sentinel Power is the ideal solution for powering sensitive and vital “mission critical” utilities such as safety devices (electro-medical), ensuring maximum power reliability. The series includes 5-6kVA single/singlephase and 6.5-8-10kVA single/singlephase and three/three-phase models with double conversion On-line technology (VFI); the load is always powered by the inverter which provides a sinusoidal voltage, filtered and stabilised in terms of 54

voltage, form and frequency. Moreover, the input and output filters significantly increase the load’s immunity against network disturbances and lightning strikes. Sentinel Power stands for technology, performance (selectable Economy Mode and Smart Active Mode) and diagnostics (LCD custom display, RS232 and USB interfaces with Powershield3 software included, ESD input, slot for interfacing with optional boards).


Operation selection The operating mode may be programmed using software or manually via the mimic panel. • On-line • ECO Mode, to increase output (up to to 98%), allows for selection of Line Interactive technology (VI) to power low priority loads from the mains supply. • Smart Active, the UPS automatically decides upon the operating mode (VI or VFI) based on the quality of the network. • Back-up, the UPS can be selected to function only when mains power fails (emergency mode only) • Frequency converter (50 or 60 Hz). High quality output voltage • Even with non-linear loads (loads with a crest factor of up to 3:1) • High short circuit current on Bypass • High overload capacity 150% by inverter (even with mains failure). • Filtered, stabilised and reliable voltage (double conversion On-line technology (VFI compliant with IEC 62040-3) with filters for the suppression of atmospheric disturbances. • Power factor correction: UPS input power factor, close to 1 and sinewave current absorption

• The batteries are not activated during mains failure of <40 ms (high hold up time) or when there are variations in input voltage (from 84V to 276V).

UPS

High UPS reliability • Total microprocessor control • Static and manual bypass without interruption • Features guaranteed up to 40° C (the components are designed to work at high temperatures and thus are subject to less stress at normal temperatures)

EnergyShare The presence of two 10A configurable IEC output sockets, allows for runtime optimisation, programming the switchoff of low priority loads; alternatively, emergency only loads, normally not powered when the mains is present, can be activated. Low impact on mains network • Sinusoidal absorption of input current on single-phase/single-phase series. Other features • Advanced diagnostics: status, measurements, alarms available on custom LDC display • Low noise (<40dBA) for installation in any environment thanks to PWM digitally-controlled ventilation, depending on the load applied and on the use of a high frequency switching inverter (>20kHz, value greater than the audible range) • Auto restart (automatic when mains supply is restored, programmable via software or mimic panel) • Emergency back-up function, the UPS can be selected to function only when mains power fails (emergency lighting only) • Back feed protection standard: to prevent energy from being feed back into the main supply • UPS digital updating (flash upgradable)

Advanced communication • Compatible with Riello UPS TeleNetGuard teleassistance • Advanced multi-platform communication for all operating systems and network environments: PowerShield3 supervision and shutdown software for Windows operating systems 7, 2003, Vista, 2003, XP, Linux, Mac OS X, Sun Solaris, Linux, Novell and other Unix operating systems. • RS232 serial port • Plug and Play function • Slot for installation of communications boards.

Simplified Installation • UPS can be installed on single-phase or three-phase distribution network • Output terminal board + 2 IEC sockets for powering local utilities (computers, modems, etc.) • Simplified positioning (built-in wheels). High battery reliability • Automatic and manual battery test • Reduced ripple component (detrimental to the batteries) thanks to the “LRCD” system (Low Ripple Current Discharge) • Unlimited extendible runtime via dedicated modular design Battery Boxes www.riello-ups.com

55


details

SPW 5000 - SPW 6000 SPW 6500 - SPT 8000 SPW 10000 ON/OFF Switch

battery box MODELS

BB SPW 240-A3 / BB SPW 240-A6 BC SPW 240-M1/ BC SPW 240-M4

Dimensions (mm)

Slot for communications interface Emergency SWITCH DEVICE (ESD)

RS232 SERIAL PORT IEC SOCKET

INPUT SWITCH (SWIN)

USB PORT

MAINTENANCE BYPASS (SWMB) OUTPUT SWITCH (SWOUT)

615

BATTERY FUSE PORT (SWBT)

785

28

2

56


SPW 5000

SPW 6000

SPT 6500

SPT 8000

SPT 10000

POWER

5000VA/4000W

6000VA/4800W

6500VA/5200W

8000VA/6400W

10000VA/8000W

UPS

MODELS INPUT Nominal voltage

220-230-240 Vac single-phase or 380-400-415 Vac three-phase with neutral

220-230-240 Vac Single-phase

Minimum voltage without battery intervention

170 Vac @ load 100% / 140 Vac @ load 50%

Nominal frequency

50 or 60 Hz ±5Hz

BY PASS Voltage tolerance

180 - 264 Vac (selectable in Economy Mode e Smart Active Mode)

Frequency tolerance

Selected frequency ±5%

OUTPUT Nominal voltage

220 - 230 - 240 Vac selectable

Voltage distortion

< 3% with linear load / < 6% with non-linear load

Frequency

50 or 60 Hz selectable o with automatic selection

Static variation

± 1.5 %

Dynamic variation

≤ 5% in 20 ms

Waveform

Sinusoidal

Crest factor

≥3:1

BATTERIES Charging time

6-8 hours

OVERLOAD TIMES 100% < Carico < 125%

1 minute

125% < Carico < 150%

4 seconds

Load > 150%

0.5 seconds

OTHER FEATURES Net weight (kg)

91

92

105

106

Gross weight (kg)

99

100

110

111

Dimensions (hwd) (mm)

615 x 282 x 785

Packaging dimensions (hwd) (mm)

863 x 388 x (650+15)

Smart Active Output

up to 98%

Protection devices

Overcurrent - short-circuit - overvoltage - undervoltage - thermal - excessive low battery protection devices

Communication

USB / RS232 + slot for communications interface

Input sockets

Terminal board

Output socket

Terminal board + 2 IEC 320 C13

Regulations

EN 62040-1 EMC EN 62040-2 directive 2006/95/EC - 2004/108 EC EN 62040-3

Ambient temperature

0°C / +40°C

Relative humidity

< 95% non-condensing

Colour

Dark grey RAL 7016

Noise level

< 45 dBA a 1 m

OPTIONS Battery cabinets for extended runtimes Isolation transformer (hlp) mm/kg

www.riello-ups.com

yes (with and without battery charger) 500 x 400 x 265 / 80

57


Local Area Networks (LAN)

ServerS

DATA CENTRES

CASH REGISTERS

TELECOMMUNICATIONS DEVICES

e-business

(Servers Farms, ISP/ASP/POP)

INDUSTRIAL PLCs

ELECTROMEDICAL DEVICES

EMERGENCY DEVICES (Lights/Alarms)

Multi Sentry 10-20 kVA Single-phase

10-120 kVA

6

Three-phase

Highlights • Complete power range from 10 up to 120 kVA • Small footprint • High efficiency up to 96,5% • Zero Impact Source • Advanced communication

The MULTI SENTRY series is ideal for protecting data centre and telecommunications systems, IT networks and critical systems where poor power quality can lead to a loss of operations and service. The MULTI SENTRY series is available in 10-12 15-20 kVA models with three-phase and single-phase input and single-phase output, and 10-12-15- 20-30-40-60-80100-120 kVA models with three-phase input and output with On-line double conversion technology, according to the 58

VFI-SS-111 classification, as defined in IEC EN 62040-3. MULTI SENTRY: designed and built using state of the art technology and components, and controlled by the DSP (Digital Signal Processor) microprocessor, to provide maximum protection to the powered loads with no impact on downsteam systems and optimise energy savings. Its highly flexible design allows full compatibility both with three-phase and single-phase power supplies.


High output Using state-of-the-art technologies three-level NPC inverters have been designed which ensure a high output of up to 96.5%. These technology solutions allow for a saving of more than 50% of the energy dissipated in a year, compared to a similar product on the market with 92% output. The exceptional performance makes it possible to recover the initial investment cost in less than three years of operation. Battery care system Proper battery care is critical to ensuring the correct operation of a UPS in emergency conditions. The Riello UPS Battery Care System consists of a series of features and capabilities that allow for battery management in order to obtain the best performance possible and extend their operating life. Battery charging: MULTI SENTRY is suitable for use with hermetically sealed lead-acid (VRLA), AGM and GEL batteries and Open Cup and Nickel Cadmium batteries. Depending on the battery type, different charging methods are available. • One-level voltage recharge, typically used for more common VRLA AGM www.riello-ups.com

UPS

MST 40 Traditional UPS 40kVA

% Efficiency

Zero impact source Thanks to the technology used, MULTI SENTRY solves installation problems in systems where the power supply has limited installed power, where the UPS is also powered by a generator or where there are compatibility problems with loads that generate harmonic currents; MULTI SENTRY has zero impact on its power source, being either the mains power supply or a generator: • input current distortion of less than 3% • Input power factor 0.99 • power walk-in function that ensures a progressive start-up of the rectifier • start-up delay function, to restart the rectifiers when mains power is restored if there are several UPS in the system. In addition, MULTI SENTRY plays a filter and power factor correction role in the power network upstream of the UPS, as it eliminates harmonic components and the reactive power, generated by the powered utilities.

100 98 96 94 92 90 88 86 84 82 80 78 76 0

20 30 40

60

80

100

120

% load batteries • Two-level voltage recharge according to IU characteristic • Charge block system to reduce electrolyte consumption and further extend the life of VRLA batteries. Compensation of recharge voltage as a function of the temperature in order to prevent excessive charges or battery overheating. Battery tests to quickly diagnose any reduction in performance or problems with the batteries. Protection against deep discharges: during extended low-load discharges, the end-of-discharge voltage is increased as recommended by the battery manufacturers, to prevent damage to or decreased performance of the batteries. Ripple current: the recharge ripple

(residual AC component) current is one of the most important causes of a reduction in reliability and battery life. Thanks to a high frequency battery charger, MULTI SENTRY reduces this value to negligible levels, prolonging battery life and maintaining high performance over a long period of time. Wide voltage range: the rectifier is designed for operation with a wide range of input voltage values (up to - 40% at half load), reducing the need for battery discharge and thus helping to battery extend life. Maximum reliability and availability Connect up to 6 units in redundant (N+1) or parallel configuration. The UPS continues to operate in parallel even in

59


the event of an interruption in the connection cable (closed loop). Low management cost The technology and the choice of high performance components, allows MULTI SENTRY to achieve exceptional performance and output, with an extremely compact overall size • smallest overall footprint is only 0.26sqm for MULTI SENTRY 20kVA with batteries • the type of input stage ensures a power factor close to 1 and low current distortion without adding bulky and expensive filters • output power at 0.9 power factor that provides up to 15% more active power than a standard UPS on the market, guaranteeing a greater margin in UPS sizing for potential load increases. Flexibility MULTI SENTRY is suitable for use in a wide range of applications, thanks to its configuration flexibility, accessories and options, and performance: • suitable for powering capacitive loads, such as Blade servers, without any reduction in active power from 0.9 lead to 0.9 lag

(% PA UPS) P Q

CAPACITIVE

100 80

PF 0.9

60

e.g.: 10 kVA UPS powers 9 kW load

40

PF 1

20

e.g.: 10 kVA UPS powers 9 kW load

% PA 0 25

50

75

100

(% P UPS) P

20 40 60

PF 0.9

e.g.: 10 kVA UPS powers 9 kW load

80

INDUCTIVE 100

(% PA UPS) P Q

60

• On-line, Eco, Smart Active and Stand By Off operating modes that are compatible with compatible with applications for centralised power systems (CSS). • frequency converter mode • configurable EnergyShare sockets to ensure backup for the most critical loads or those programmed to operate only when mains power fails • Cold Start to switch on the UPS even when there is no mains power • MST/MSM version: cabinet (1320x440x850mm HLW) for optimised solutions when medium to long-term runtime is required. • optional temperature sensor for external battery cabinets, to assist the recharge voltage compensation • additional battery chargers to optimise charge time • optional dual input to mains power supply • isolation transformers to vary neutral connectivity in the event of separate power sources or for galvanic isolation between input and output • battery cabinets of different sizes and capacities, for providing extended runtimes. Advanced communication MULTI SENTRY is equipped with a graphic display (240x128 pixel backlit) that provides UPS information, measurements, status, and alarms in different languages and displays wave forms and voltage/current. The default screen shows the status of the UPS graphically indicating the status of the various blocks (rectifier, batteries, inverter, bypass).

• Advanced multi-platform, communication for all operating systems and network environments: PowerShield3 supervision and shutdown software for Windows operating systems 7, 2008, Vista, 2003, XP, Linux Mac OS X, Sun Solaris, Linux, Novell and other Unix operating systems. • Compatible with the Riello TeleNetGuard service • RS232 serial port or USB • 3 slots for the installation of optional communications accessories like network adapters, voltage-free contacts etc. • REPO Remote Emergency Power Off for switching off the UPS with the remote emergency button •Input for the connection of the auxiliary contact of an external manual bypass • Input for synchronisation from an external source • Graphic mimic panel display for remote connection.


MODELS

BB 1320 480-T4 / BB 1320 480-T5 BB 1320 480-T2 / AB 1320 480-T5

BB 1600 480-S5 / AB 1600 480-S5

BB 1900 480-V6 / BB 1900 480-V7 / BB 1900 480-V8 BB 1900 480-V9 / AB 1900 480-V9

up to 60 kVA

up to 80 kVA

up to 120 kVA

MODELS UPS

UPS

battery box

1600

1320 815

400

1900

Dimensions (mm)

650

860

750

0

80

details MST 100 - 120 (front) EnergyShare SOCKET

PARALLEL CONNECTORS

SLOT FOR COMMUNICATION INTERFACE

REPO CONNECTORS - AS400 USB - RS232 PARALLEL CONNECTORS

MST 60 - 80 (front) SLOT FOR COMMUNICATION INTERFACE REPO CONNECTORS AS400 USB - RS232

MSM 10 - 20 MST 10 - 40 (front) SLOT FOR COMMUNICATION INTERFACE

EnergyShare SOCKETS BATTERY FUSES

REMOTE CONNECTOR AND CONTACTS

MCM 10 - 12 - 15 - 20 MCT 10 - 12 - 15 - 20 (rear) SLOT FOR COMMUNICATION INTERFACE PARALLEL CONNECTORS SERIAL PORT RS232

USB PORT INPUT SWITCH OUTPUT SWITCH MANUAL BYPASS BYPASS SWITCH

INPUT SWITCH

BYPASS SWITCH (OPTIONAL)

OUTPUT SWITCH MANUAL BYPASS

OUTPUT SWITCH MANUAL BYPASS

MULTICOM 382 AUXILIARY BOARD SLOT

www.riello-ups.com

IEC AUXILIARY SOCKETS

BYPASS SWITCH (OPTIONAL)

61


MODELS

MCM/MSM 10

MCM/MSM 12

MCM/MSM 15

MCM/MSM 20

INPUT Nominal voltage

380-400-415 Vac three-phase with neutral / 220-230-240 single-phase

Nominal frequency

50 or 60 Hz

Frequency tolerance

40 ÷ 72 Hz

Power factor at full load

0.99

Current distortion

thdi ≤ 3%

BY PASS Nominal voltage

220-230-240 Vac

Number of phases

1

Voltage tolerance

180 ÷ 264 V (selectable)

Nominal frequency

50 or 60 Hz (selectable)

Frequency tolerance

±5 (selectable)

OUTPUT Nominal power (kVA)

10

12

15

20

Active power (kW)

8

9.6

12

16

Power factor

0.8

Number of phases

1

Nominal voltage (V)

220-230-240 Vac (selectable)

Static variation

± 1%

Dynamic variation

± 3%

Crest factor (Ipeak/Irms)

3:1

Voltage distortion

< 1% with linear load / < 3% with non-linear load

Frequency

50 or 60 Hz

Frequency stability during battery operation

0.01%

Overload at Pf 0.8

110% for 10 minutes, 133% for 1 minute, 150% for 5 seconds

BATTERIES Type

VRLA AGM/GEL

Charging time

6 hours

INFO FOR INSTALLATION Weight without internal batteries (kg) (MCM/MSM) Dimensions (hwd) (mm) Communication Ambient temperature

82/110

90/115

3 slot for communications interface /RS232/USB 0°C / +40°C

Relative humidity

90% non-condensing Dark grey RAL 7016

Protection level Smart Active Output

Regulations

95/120

930 x 320 x 840 (MCM version) 1320 x 440 x 850 (MSM version)

Colour Noise level

62

80/105

< 52 dBA a 1 m IP20 up to 98% Directive EMC 2004/108/CE Electromagnetic Compatibility Directive Standards: Safety IEC EN 62040-1; EMC IEC EN 62040-2 C2 Classification according to IEC 62040-3 (Voltage Frequency Independent) VFI - SS – 111


MCT/MST MCT/MST MCT/MST MCT/MST 10 12 15 20

MST 30

MST 40

MST 60

MST 80

MST 100

MST 120

UPS

MODELS INPUT Nominal voltage

380-400-415 Vac three-phase with neutral

Nominal frequency

50 or 60 Hz

Frequency tolerance

40 ÷ 72 Hz

Power factor at full load

0.99

Current distortion

thdi ≤ 3%

BY PASS Nominal voltage

380-400-415 Vac three-phase with neutral

Number of phases

3+N

Voltage tolerance

180 ÷ 264 V (selectable)

Nominal frequency

50 or 60 Hz (selectable)

Frequency tolerance

±5 (selectable)

OUTPUT Nominal power (kVA)

10

12

15

20

30

40

60

80

100

120

Active power (kW)

9

10.8

13.5

18

27

36

54

72

90

108

370

380

Power factor

0.9

Number of phases

3+N

Nominal voltage (V)

380-400-415 Vac (selectable)

Static variation

± 1%

Dynamic variation

± 3%

Crest factor (Ipeak/Irms)

3:1

Voltage distortion

≤ 1% with linear load / ≤ 3% with non-linear load

Frequency

50 or 60 Hz

Frequency stability during battery operation

0.01%

Overload at Pf 0.8

115% unlimited, 125% for 10 minutes, 150% for 1 minute, 168% for 5 seconds

BATTERIES Type

VRLA AGM/GEL

Charging time

6 hours

INFO FOR INSTALLATION Weight without internal batteries (kg) (MCT/MST) Dimensions (hwd) (mm)

80/105

82/110

90/115

90/115

930 x 320 x 840 (versione MCT) 1320 x 440 x 850 (versione MST)

Communication

135

145

1320 x 440 x 850

Relative humidity

90% non-condensing Dark grey RAL 7016

Smart Active Output

Regulations

www.riello-ups.com

1600 x 500 x 850

1900 x 750 x 855

0°C / +40°C

Colour Protection level

200

3 slot for communications interface /RS232/USB

Ambient temperature

Noise level

190

< 52 dBA a 1 m

< 48 dBA a 1 m

< 52 dBA a 1 m

< 65 dBA a 1 m

IP20 up to 99% European directives L V 2006/95/CE Low Voltage Directive EMC 2004/108/CE Electromagnetic Compatibility Directive Standards: Safety IEC EN 62040-1; EMC IEC EN 62040-2 C2 Classification according to IEC 62040-3 (Voltage Frequency Independent) VFI - SS – 111

63


Local Area Networks (LAN)

ServerS

DATA CENTRES

TELECOMMUNICATIONS DEVICES

e-business (Server Farms, ISP/ASP/POP)

EMERGENCY DEVICES (Lights/Alarms)

Multi Guard

Highlights • Power flexibility 15-120 KVA • UPS module with hot-swap function • Modular power and runtime • Intelligent battery charging system • High MTBF and low MTTR

The Multi Guard 15-120 kVA modular UPS is a scalable 3 Phase / 3 phase with double conversion Uninterruptible Power Supply system. Its power capacity ranges from 15kVA to 120kVA, delivering the best combination of reliability, functionality and flexibility. The Multi Guard 15-120 N+X parallel architecture adopts a drawer-style, highly intelligent design to achieve maximum power availability and redundancy. It is specially designed to meet the protection demands of mission critical 64

loads in Datacentres or other important applications. Each module has an individual power capacity of 15 kVA, and a standard cabinet can be fitted with up to 8 modules to reach 120 kVA. If the load is within limits, modules can be hotswapped to enable true power continuity without any interruptions. System features • Maximum 120kVA capacity in a 19“ rack. • 15kVA per module with hot-swappable feature


Other advantage • The Multi Guard 15-120 UPS power modules use the latest DSP microchip technology. This reduces hardware components, increases UPS reliability and also makes it convenient to upgrade and maintain using the remote software. • The UPS operates with load sharing technology. Should any of the UPS modules fail, the load will be taken over by the rest of the modules without interruption. This increases the real time operation and power availability compared to other standby UPS. • The Multi Guard 15-120 UPS is designed to connect to external battery banks without limiting the battery run time. The 19” racks in black color design can blend easily into most Data Centres, Computer or Power Rooms. N+X Parallel Redundancy UPS The N+X parallel redundant configuration of the Multi Guard 15-120 increases the reliability of the UPS system. Advanced Modular Design The Multi Guard 15-120 system contains UPS modules, LCD Display module, PDU and other accessories. Each UPS module is a fully functionable 15kVA UPS. Through the advanced wireless parallel control technology and smart communication modulation, the UPS modules or LCD display module can www.riello-ups.com

be replaced easily at any time without affecting the operation of the UPS. The user friendly “plug & play” design simplifies UPS service and maintenance.

UPS

• the LCD display on the front panel displays unit status and important information such as input and output rating, capacity and temperature. This is available in a number of languages, and can include after sales contact details. • Communication port is available for RS232, RS485, SNMP & AS400. • Regular battery strings for the DC power without using particular battery modules. • DSP Technology. • Charging current is up to 36 DC Amp constant current on 90kVA system, suitable for several hours of battery back up. • High output power availability up to 99.999%, MTBF more than 1,000,000 hours & MTTR<5mins Input power factor >0.99 and THDi <5%

The most reliable N+X parallel redundancy The Multi Guard 15-120 de-centralises its controller in each UPS Module. The LCD Display module is for display and communication purposes only, so even if the LCD Display module fails, the UPS system would still function and support the load without any interruption. High MTBF ability Each UPS module in the 15-120 UPS system is a fully functional UPS. There is no additional controlling module for parallel and load sharing. System MTBF for two modules in parallel is more than 1,000,000 hours and power availability is above 99.999%. MTTR < 5 mins In a parallel redundant 15-120 UPS system, the UPS will keep working even one of the modules fails. The module replacement procedure only needs 5 minutes for full system recovery, minimizing expensive downtime. Superior Electrical Characteristic Pure Sine Wave input current with THDi ≤5% and unity input power (≥0.99). The output voltage distortion is ≤1.5%. Intelligent charging system The Multi Guard 15-120 UPS system applies a two-step intelligent charging system. The first stage is a constant charging current that can recharge the battery capacity to 90% in a short time. The system then transfers to a constant voltage mode to complete the charging and guarantee the battery can be fully

GMT 30kVA charged all the time. This intelligent charging system not only reduces the battery recharging time, but can also extend runtime by using plug-in battery packs. Modular back up time The Multi Guard 30 and 60 versions are designed to build up autonomy time using a single battery mode brick. Saving: • Installation costs • electricity costs • cooling costs • expansions costs • maintenance costs

Redundancy

Ease of Maintenance Scalability 65


UPS Power selection The Multi Guard 15-120 can be configured from 1 up to 8 modules in its cabinet to form the most suitable N+ X configuration. The Multi Guard grows as business grows by simply adding further UPS modules to the to exhisting frame. The initial investment is minimised, while future expansion is easy, cost-effective and efficient to complete.

Multi Guard 30 Multi Guard 30 is the Entry Level to the Multi Guard Range. It is the ideal solution to supply a medium load that requires redundancy with the ability to expand the capacity in the future. Its flexibility and expandability give it an advantage over any stand alone ups solution. The solution is very compact, with the possibility to also expand the autonomy by adding up to 3 battery banks in the

same cabinet. Power ranges from 15 kVA to 30 kVA (2 modules); 19’’ rack mounted with the internal battery pack. NO. OF POWER MODULES

kVA

Typical runtime (min)(*)

1

15

90

2

30

42

(*) The autonomy refers to the max number of installed batteries.

Multi Guard 60 Modular three phase UPS system ranging from 15 kVA to 60 kVA, 19’’ rack mounted with the internal battery pack. This solution can include 4 x 15 kVA modules providing the following back up time at 75% of nominal load. If redundancy is requested (N+1 modules) the max output power will be 45 kVA.

NO. OF POWER MODULES

kVA

Typical runtime (min)(*)

15

113

30

54

45

30

60

21

(*) The autonomy refers to the max number of installed batteries.

Multi Guard 120 Modular three phase UPS system ranging from 15 kVA to 120 kVA, 19’’ rack mounted and designed for an external battery cabinet. The maximum output power of the Multi Guard cabinet is 120 kVA (8 x 15 kVA modules). If redundancy is requested ( N+1 modules) the max output power is 105 kVA.

66


UPS

MODELS

GMT - da 15kVA a 120kVA

INPUT Voltage Voltage range Frequency range

380V/ 400V/ 415V, 4-wire three-phase + E from 294Vac to 520Vac from 40 Hz to 70 Hz

Power factor

>0.99

thdi

< 5%

BY PASS Voltage Voltage range Transfer time from On-line to Off-Line or vice versa

380V/ 400V/ 415V, 4-wire three-phase + E from 323Vac to 437Vac 0 sec

OUTPUT Voltage Voltage stability Frequency

380V/ 400V/ 415V, 4-wire three-phase + E ≤ 1.5% 50 Hz / 60 Hz

MODULE Power Output power

15kVA / 13,5kW 15kVA x number of modules (up to 8 modules)

TECHNICAL SPECIFICATIONS Noise level (measured at 1m from UPS) Operating temperature Humidity Storage temperature Module weight

from ≤ 60dBA to ≤62dBA O°C / +40°C 20% - 90% non-condensing -15° +55° 35 kg

Module dimensions (hwd) (mm)

131 x 440 x 700

GMT 30 Dimensions (hwd) (mm)

1500 x 600 x 1000

GMT 60 Dimensions (hwd) (mm)

2000 x 600 x 1000

GMT 120 Dimensions (hwd) (mm)

2000 x 600 x 1000

Eco Mode efficiency

up to 99%

Standards

www.riello-ups.com

Safety: IEC 62040-1-1 EMC: IEC 62040-2

67


Local Area Networks (LAN)

ServerS

DATA CENTRES

TELECOMMUNICATIONS DEVICES

e-business

(Servers Farms, ISP/ASP/POP)

INDUSTRIAL PROCESSES

INDUSTRIAL PLCs

ELECTROMEDICAL DEVICES

EMERGENCY DEVICES (Lights/Alarms)

Master MPS 10-800 kVA

Three-phase/Three-phase

10-100 kVA

6

Three-phase/Single-phase

Highlights • Efficiency Control System (ECS) • Galvanic Separation • High overload capacity • LCD Display • Numerous parallel solutions

Absolute protection Master MPS series UPS devices ensure maximum protection and power quality for any type of load, especially for mission critical applications, security systems and electro-medical equipment, industrial processes and telecommunications. Master Plus is an on-line double conversion UPS (class VFI SS 68

111 in accordance with IEC EN 62040-3) with a transformer isolated inverter. The Master Plus range includes threephase input and single-phase output versions from 10 to 100kVA, and threephase input and output versions 10 to 800kVA. The three-phase versions are available from 10 to 200 kVA with a 6-pulse thyristor rectifier and, for some


Easy source Master MPS makes powering UPS devices by power generators and MV/LV transformers easier and more efficient, reducing loss in systems and coils and correcting the power factor and eliminating harmonics by the loads powered by the UPS itself. In addition to this, the progressive start-up of the rectifier and the possibility of reducing the recharge current of the batteries, allow for the containment of the input current absorbed and therefore do not overload the source, especially when the source is a generator. Power continuity For years, Riello UPS has been developing and offering various solutions for dealing with the different requirements and the problems that inevitably arise in the most critical applications. Riello UPS offers flexible, high-availability solutions that are able to adapt to the different system structures and different criticality levels. Riello UPS creates UPS systems can tolerate a number of component or subsystem failures, while continuing to operate normally and to provide service without interruption. This is achieved by installing carefully designed redundant elements, eliminating the common failure nodes, scheduling maintenance activities and through the control and supervision of the operating parameters of the system and the environment. The TEC service staff is ready to provide guidance and advice on projects. Flexibility Master Plus is suited to all types of applications, from computers to the most demanding industrial environments. Thanks to the broad range of accessories www.riello-ups.com

and options, complex architectures and configurations can be created to ensure maximum power to critical loads: expansions (in redundancy or power) may be made in already-operating parallel systems, even without having to switch off any UPS that are already operating and thus, maintaining power to utilities. UGS and PSJ devices also ensure redundancy in the downstream distribution of the parallel system, creating a “selective” system that provides power to other connected utilities even when there are failures on one utility. Battery care system: maximum battery care Normally the batteries are kept charged by the rectifier; when mains power fails, the UPS uses this energy source to power its utilities. Therefore, proper battery care is critical to ensuring correct UPS operation in emergency conditions. Battery Care System consists of a series of features and capabilities that allow for battery management in order to obtain the best performance possible and extend their operating life. • Dual level charging regime to optimise recharge currents and reduce charge times • Temperature compensation and deep discharge protection to reduce overall battery ageing • Charge blocking system to reduce electrolyte consumption and lengthen the life of VRLA batteries • Battery tests to diagnose, in advance, any reduction in performance or problems with the batteries. Master Plus is also compatible with different battery technologies: vented open lead acid, VRLA AGM and NiCd. Ease of Installation Master MPS requires only a very small space for installation (only 0.64 sqm for a 200KVA system); in addition, front access allows servicing of all major components from the front panel, making side access unnecessary. Given the upwards ventilation, Master Plus can be placed up against a wall, reducing the space to be left free, necessary in event the flow of hot air coming out the rear.

Specific solutions The UPS can be adapted to meet your requirements. Contact TEC to discuss the feasibility of specific solutions and options not listed in the catalogue.

UPS

powers, with 12-pulses. From 100kVA to 500kVA, the HP versions with IGBT rectifiers offer the best solution for low harmonic distortion of input current THDi and for the single input power factor (see Master HP chapter); products with 12-pulse thyristor rectifiers in the same power range are available upon request. From 600 to 800kVA, the solutions are offered are equipped with a 12-pulse rectifier with and without a filter to reduce harmonics (optional)

Advanced communication • Compatible with Teleguard for teleassistance. • Advanced communication, multiplatform, for all operating systems and network environments: Supervision and shutdown PowerShield3 software for Windows operating systems 7, 2008, Vista, 2003, XP, Linux, Mac OS X, Sun Solaris, Linux, Novell and other Unix operating systems. • UPS is supplied with a cable for direct PC connection (Plug and PLay) • RS232 double serial port • Slot for network adapter installation; ESD contact (Emergency Switching Device) for switching off the UPS by remote emergency button. • Remote led mimic panel or graphic display. Maximum reliability and availability Distributed or centralised parallel up to 8 units per redundant (N+1) or powerparallel. A parallel between models with different power levels is possible. Hot System Expansion (HSE): HSE allows the insertion of a new UPS within an existing system, without the need to switch off the UPSs which are already operating or switch them to bypass mode. This guarantees maximum load protection, even during maintenance and enlargement. Maximum levels of availability also in the event of an interruption to the parallel bus cable: the system is “FAULT TOLERANT”. It is not affected by connection cable faults and continues powering the load without a continuity solution, signalling the anomaly with an alarm. Efficiency Control System (ECS): is a system that optimises the efficiency of parallel systems, according to the power required by the load in that moment. However, N +1 redundancy is guaranteed, but every UPS working in parallel operates at the best load level possible in order to achieve the highest overall output.

69


OPTIONS • UGS - UPS Group Synchroniser Allows 2 or more non-parallel UPS devices to remain synchronised even during mains power failure. The UGS also enables a Riello UPS to be synchronised with another power source that is independent and of a different power rating. • PSJ - Parallel Systems Joiner Connects two UPS groups in parallel, hot (without output discontinuity) through a power coupling switch. A UPS group (slave) is is permanently synchronised to the Master group both

when the mains supply is present or not present (thanks to the UGS synchronising device) . If there is a failure on one of the UPS devices in parallel, it is cut-off. The PSJ will automatically connect the remaining UPS to the other group in parallel via an external bypass, in order to ensure the redundancy of the load.

Bypass mains

Bypass mains

Mains

UPS1

UPS8

Mains UPS3...

UPS2

Battery

Battery

UPS3...

Battery

UPS2

Battery

UPS1

Mains

Mains

UPS8

Common BY PASS

Battery

Mains

Battery

Mains

Maintenance Bypass Cabinet

Load

Load

Parallel configuration of up to 8 units with distributed bypass

Parallel configuration of up to 8 units with common bypass

Parallel architecture that ensures the redundancy of the power source. +Flexibility and modularity

Parallel architecture that ensures the redundancy of the power source, with autonomous bypass management. + Selectivity of downstream faults in bypass mode

UPS2B

Mains

UPS1A

Bypass 2

Mains

UPS2A

Mains

UPS1B

UPS2B

Battery

UPS1B

Mains

Battery

Mains

System B

Bypass 1

Battery

UPS2A

Battery

UPS1A

Mains

Battery

Mains

System A

Bypass 2

Battery

Mains

Battery

System B

Bypass 1

Battery

System A

UGS Sinchroniser

PSJ

Static Transfer SWITCH

SWITCH

Load 3 Load 1

Static Transfer SWITCH

Load 2

Load 1

Load 2

Load 4

70

Dynamic dual bus configuration

Dual bus system configuration

Solution that ensures redundancy until the distribution of the powersupply to the loads + Downstream fault discrimination

Solution that ensures the redundancy of the power supply evenduring maintenance + High availability and redundancy


555

740

MPT 100 - MPT 120 MPT 160- MPT 200

740

800

1900

1900

1400

800

MPT 800

MPT 600

1900

MPM/MPT 60รท80

1400

MPM/MPT 10รท40

0

80

UPS

dimensions (mm)

4400

0

98

3200

0

100

battery box MODELS MODELS UPS

BB 1900 396-L6 / BB 1900 396-L7 BB 1900 396-L8 / BB 1900 396-L9

BB 1900 480-L6 / BB 1900 480-L7 BB 1900 480-L8 / BB 1900 480-L9

BB 1400 384-B1

BB 1400 384-B2 / BB 1400 384-B3 BB 1400 384-B4 / BB 1400 384-B5

MPT 100-200 MPM 100

MPT 600-800 MHT 100-500

MPT 10-60

MPT 10-80

86

0

80

0

55

5

1400 86

740

740

0

TCE 270

TCE 400

TLE 400

MPT 100-200 / MPM 100

MHT 100-250

MPT D 600-800 / MHT 300-500

MODELS MODELS UPS

1400

1900

Dimensions (mm)

27 0

www.riello-ups.com

0

80

400

0

85

1900

1900

1900

Dimensions (mm)

400

0

100

71


isolation transformers MODELS

TI 10 T / TI 15 T / TI 20 T TI 30 T / TI 40 T

TI 60 T / TI 80 T

TI 100 T / TI 120 T TI 160 T

TI 200 T / TI 250 T

TI 300 T / TI 400 T TI 500 T / TI 600 T

5

720

64 0

OPTIONS • Isolation transformer • Synchronisation device (see UGS) • Hot connection device (see PSJ) • Interface for generator • Closed Loop parallel kit option (Closed loop: to be ordered with the UPS) • Empty battery cabinets or for prolonged runtimes

72

720

65

0

0

80

1900

1900

1400

1200 55

1900

Dimensions (mm)

80

0

0

80

120 0

0

100


MPM 10 *

MPM 15 *

MPM 20 *

MPM 30

MPM 40

MPM 60

MPM 80

MPM 100

POWER

10

15

20

30

40

60

80

100

UPS

MODELS INPUT Nominal voltage

380 - 400 - 415 Vac Three-phase

Voltage tolerance

400 V + 20% /- 25%

Frequency

45 - 65 Hz

Soft start

0 ÷ 100% in 30’’ (selectable)

Permissible frequency tolerance

± 2% (selectable from ± 1% to ± 5% from front panel)

Standard equipment provided standard

Back Feed protection; separable bypass line

BATTERIES Type

open lead acid and VRLA AGM / GEL; NiCd.

Residual ripple voltage

< 1%

Temperature compensation

-0.5 Vx°C

Typical charge current

0.2 x C10

OUTPUT Nominal power (kVA)

10

15

20

30

40

60

80

100

Active power (kW)

9

13,5

18

27

36

54

72

90

520

650

Number of phases

1

Nominal voltage

220 - 230 - 240 Vac Single-phase

Static stability

± 1%

Dynamic stability

± 5% in 10 ms

Voltage distortion

< 1% with linear load / < 3% with non-linear load

Crest factor (lpeack/lrms)

3:1

Frequency stability on battery

0.05%

Frequency

50 or 60 Hz (selectable)

Overload

110% for 60’; 125% for 10’; 150% for 1’

INFO FOR INSTALLATION Net weight

200

220

Dimensions (hwd) (mm)

230

290

340

1400 x 555 x 740

Remote signals

440

1400 x 800 x 740 voltage-free contacts

Remote controls

ESD and bypass

Communication

Double RS232 + remote contacts + 2 slots for communications interface

Ambient temperature

0°C / +40°C

Relative humidity

< 95% non-condensing

Colour Noise level at 1 m (dBA) Protection level Smart Active Output Regulations Classification according to IEC 62040-3

1900 x 800 x 800

Dark grey RAL 7016 54

62

62

63

IP20 up to 98% Regulatory Directives LV 2006/95/EC - 2004/108/EC; IEC Safety EN 62040-1; EMC IEC EN 62040-2; IEC Performance EN 62040-3 (Voltage Frequency Independent) VFI - SS - 111

* Also available with internal batteries

www.riello-ups.com

73


MODELS

MPT 10 *

MPT 15 *

MPT 20 *

MPT 30

MPT 40

MPT 60

MPT 80

POWER

10

15

20

30

40

60

80

INPUT Nominal voltage

380 - 400 - 415 Vac Three-phase

Voltage tolerance

400 V + 20% /- 25%

Frequency

45 ÷ 65 Hz

Soft start

0 ÷ 100% in 30’’ (selectable)

Permissible frequency tolerance

± 2% (selectable from ± 1% to ± 5% from front panel)

Standard equipment provided standard

Back Feed protection; separable bypass line

BATTERIES Type

open lead acid and VRLA AGM / GEL; NiCd.

Residual ripple voltage

< 1%

Temperature compensation

-0.5 Vx°C

Typical charge current

0.2 x C10

OUTPUT Nominal power (kVA)

10

15

20

Active power (kW)

9

13,5

18

Number of phases

30

40

60

80

27

36

54

72

450

600

3+N

Nominal voltage

380 - 400 - 415 Vac Three-phase + N

Static stability

± 1%

Dynamic stability

± 5% in 10 ms

Voltage distortion

< 1% with linear load / < 3% with non-linear load

Crest factor (lpeack/lrms)

3:1

Frequency stability on battery

0.05%

Frequency

50 or 60 Hz (selectable)

Overload

110% for 60’; 125% for 10’; 150% for 1’

INFO FOR INSTALLATION Weight without internal batteries (kg)

212

220

Dimensions (hwd) (mm)

230

280

1400 x 800 x 740

Remote signals

voltage-free contacts

Remote controls

ESD and bypass

Communication

Double RS232 + remote contacts + 2 slots for communications interface

Ambient temperature

0°C / +40°C

Relative humidity

< 95% non-condensing

Colour Noise level at 1 m (dBA) Protection level Smart Active Output Regulations Classification according to IEC 62040-3 * Also available with internal batteries

74

330

1400 x 555 x 740

Dark grey RAL 7016 54

60

62 IP20 up to 98%

Regulatory Directives LV 2006/95/EC - 2004/108/EC; IEC Safety EN 62040-1; EMC IEC EN 62040-2; IEC Performance EN 62040-3 (Voltage Frequency Independent) VFI - SS - 111


MPT 100

MPT 120

MPT 160

MPT 200

POWER

100

120

160

200

UPS

MODELS INPUT Nominal voltage

380 - 400 - 415 Vac Three-phase

Voltage tolerance

400 V + 20% /- 25%

Frequency

45 ÷ 65 Hz

Soft start

0 ÷ 100% in 30’’ (selectable)

Permissible frequency tolerance

± 2% (selectable from ± 1% to ± 5% from front panel)

Standard equipment provided standard

Back Feed protection; separable bypass line

BATTERIES Type

open lead acid and VRLA AGM / GEL; NiCd.

Residual ripple voltage

< 1%

Temperature compensation

-0.5 Vx°C

Typical charge current

0.2 x C10

OUTPUT Nominal power (kVA)

100

120

160

200

Active power (kW)

90

96

144

180

Number of phases

3+N

Nominal voltage

380 - 400 - 415 Vac Three-phase + N

Static stability

± 1%

Dynamic stability

± 5% in 10 ms

Voltage distortion

< 1% with linear load / < 3% with non-linear load

Crest factor (lpeack/lrms)

3:1

Frequency stability on battery

0.05%

Frequency

50 or 60 Hz (selectable)

Overload

110% for 60’; 125% for 10’; 150% for 1’

INFO FOR INSTALLATION Weight (kg) Dimensions (hwd) (mm) Remote signals

640

650

770 1900 x 800 x 800 voltage-free contacts

Remote controls

ESD and bypass

Communication

Double RS232 + remote contacts + 2 slots for communications interface

Ambient temperature Relative humidity Colour Noise level at 1 m (dBA) Protection level Smart Active Output Regulations Classification according to IEC 62040-3

www.riello-ups.com

810

0°C / +40°C < 95% non-condensing Dark grey RAL 7016 63 ÷ 68 IP20 up to 98% Regulatory Directives LV 2006/95/EC - 2004/108/EC; IEC Safety EN 62040-1; EMC IEC EN 62040-2; IEC Performance EN 62040-3 (Voltage Frequency Independent) VFI - SS - 111

75


MODELS

MPT 600

MPT 800

POWER

600

800

INPUT Nominal voltage

380 - 400 - 415 Vac Three-phase

Voltage tolerance

400 V ± 20%

Frequency

45 ÷ 65 Hz

Power factor

> 0.93 in HC version

Current distortion

< 3% in HC version

Soft start

0 ÷ 100% in 30’’ (selectable)

Permissible frequency tolerance

± 2% (selectable from ± 1% to ± 5% from front panel)

Standard equipment provided standard

Back Feed protection; separable bypass line

BATTERIES Type

open lead acid and VRLA AGM / GEL; NiCd.

Residual ripple voltage

< 1%

Temperature compensation

-0.5 Vx°C

Typical charge current

0.2 x C10

OUTPUT Nominal power (kVA)

600

800

Active power (kW)

480

640

Number of phases

3+N

Nominal voltage

380 - 400 - 415 Vac Three-phase + N

Static stability

± 1%

Dynamic stability

± 5% in 10 ms

Voltage distortion

< 1% with linear load / < 3% with non-linear load

Crest factor (lpeack/lrms)

3:1

Frequency stability on battery

0.05%

Frequency

50 or 60 Hz (selectable)

Overload

110% for 60’; 125% for 10’; 150% for 1’

INFO FOR INSTALLATION Weight (kg) Dimensions (hwd) (mm)

4000

5300

1900 x 3200 x 1000

1900 x 4400 x 1000

Remote signals

voltage-free contacts

Remote controls

ESD and bypass

Communication

Double RS232 + remote contacts + 2 slots for communications interface

Ambient temperature

0°C / +40°C

Relative humidity

< 95% non-condensing

Colour Noise level at 1 m (dBA) Protection level Smart Active Output Regulations Classification according to IEC 62040-3

76

Dark grey RAL 7016 < 75

< 78 IP20 up to 98%

Regulatory Directives LV 2006/95/EC - 2004/108/EC; IEC Safety EN 62040-1; EMC IEC EN 62040-2; IEC Performance EN 62040-3 (Voltage Frequency Independent) VFI - SS - 111


UPS www.riello-ups.com

77


Local Area Networks (LAN)

ServerS

DATA CENTRES

TELECOMMUNICATIONS DEVICES

e-business

(Servers Farms, ISP/ASP/POP)

INDUSTRIAL PROCESSES

INDUSTRIAL PLCs

ELECTROMEDICAL DEVICES

EMERGENCY DEVICES (Lights/Alarms)

Master HP 100-500 kVA

Three-phase/Three-phase 6

Highlights • Input stage with IGBT technology • Galvanic Separation • High overload capacity • LCD Display

Master MPS range has been enhanced with the HP version in sizes from 100 to 500kVA Thanks to the on-line, double conversion technology achieved entirely with IGBT and DSP (Digital Signal Processor), the Master HP series ensures maximum protection and power quality for any type of data processing or industrial load, particularly for 78

“mission critical” applications, and classified as VFI SS 11. (Voltage and Frequency Independent) in accordance with IEC EN 62040-3. This series has been designed using a new configuration that includes an IGBT sinewave input rectifier rather than the more conventional thyristors.


www.riello-ups.com

Main features • High output • Compact size: only 0.85 m2 a for 250kVA UPS • Light weight • Double load protection, both electronic and galvanic, for the battery. The entire HP Master range is suited for use in the broadest spectrum of applications; thanks to the flexibility of configuration, accessories and options available, it is suited for powering capacitive loads such as blade

UPS

servers, etc. Power supply reliability and availability for critical applications are guaranteed by the parallel distributed or centralised parallel up to 8 units, per redundant (N +1) or power parallel and by all the different configurations available in the Master MPS range.

Options • Input isolation transformer • Synchronisation device (see UGS Master MPS) • Hot connection device (see PSJ Master MPS) • Interface for generator • Closed Loop parallel kit option (Closed loop: to be ordered with the UPS) • Empty battery cabinets or for runtimes

dimensions (mm)

800

0

85

MHT 300 MHT 400

MHT 500

1000

0

85

1900

MHT 160 - MHT 200 MHT 250

1900

MHT 100 MHT 120

1900

Battery care system: maximum battery care Master HP features the same Battery Care System as the Master series. The conventional MPS takes care of battery operating status, in order to maintain service conditions for as long as possible. Flexibility The configuration with the output

transformer, a feature of both the Master HP and conventional series, is characterised by the galvanic isolation of the load and the battery for greater versatility in system configurations. As a matter of fact it allows for two network inputs (main and emergency) separate, and coming from two different power sources; this is particularly suited to parallel systems in order to ensure the selectivity between the two sources, thus improving the reliability of the entire installation.

1900

Zero impact source The HP version offers the benefits summarised in the Zero Impact Source formula, thanks to the IGBT rectifier, solves all integration problems in systems where the power supply has a limited installed power, where the UPS is also powered by a generator, or where there are compatibility problems with loads that generate harmonic currents,; as a matter of fact, Master HP has zero impact on the power source, either network or generator: • less than 3% input current distortion • Input power factor 0.99 • power walk-in function that ensures a progressive start-up of the rectifier • start-up delay function, to restart the rectifiers when mains power is restored if there are several UPSs in the system. In addition, MASTER HP plays a filter and power factor correction role in the power network upstream of the UPS, since it eliminates harmonic components and the reactive power, generated by the powered utilities.

1500

0

100

2100

0

100

79


MODELS

MHT 100

MHT 120

MHT 160

MHT 200

MHT 250

MHT 300

MHT 400

MHT 500

POWER

100

120

160

200

250

300

400

500

INPUT Nominal voltage

380 - 400 - 415 Vac Three-phase

Frequency

45 ÷ 65 Hz

Power factor

> 0.99

Harmonic current distortion

<3% THDi

Soft start

0 ÷ 100% in 30’’ (selectable)

Frequency tolerance

± 2% (selectable from ± 1% to ± 5% from front panel)

Standard equipment provided standard

Back Feed protection; separable bypass line

BATTERIES Type

open lead acid and VRLA AGM / GEL; NiCd.

Ripple current

Zero

Charge voltage compensation

-0.5 Vx°C

OUTPUT Nominal power (kVA)

100

120

160

200

Active power (kW)

90

108

144

180

Number of phases

250

300

400

500

225

270

360

450

3+N

Nominal voltage

380 - 400 - 415 Vac Three-phase + N

Static stability

± 1%

Dynamic stability

± 5% in 10 ms

Voltage distortion

< 1% with linear load / < 3% with non-linear load

Crest factor (lpeack/lrms)

3:1

Frequency stability on battery

0.05%

Frequency

50 or 60 Hz (selectable)

Overload

110% for 60’; 125% for 10’; 150% for 1’

INFO FOR INSTALLATION Weight (kg)

656

Dimensions (hwd) (mm)

1900 x 800 x 850

700

800

910

1400

voltage-free contacts (configurabile)

Remote controls

ESD and bypass (configurabile)

Communication

Double RS232 + remote contacts + 2 slots for communications interface < 95% non-condensing

Colour Protection level Smart Active Output Regulations Classification according to IEC 62040-3

2100 1900 x 2100 x 1000

0°C / +40°C

Relative humidity Noise level (1 m)

1700

1900 x 1500 x 1000

Remote signals

Ambient temperature

80

1000

1900 x 1000 x 850

Dark grey RAL 7016 63 ÷ 68 dBA

70 ÷ 72 dBA IP20 (others upon request) up to 98,5%

Safety: EN 62040-1-1 (directive 2006/95/EC); EMC: EN 62040-2 (directive 2004/108/EC) (Voltage Frequency Independent) VFI - SS - 111

70 dBA


UPS www.riello-ups.com

81


INDUSTRIAL PROCESSES

INDUSTRIAL PLCs

Master Industrial 30-80 kVA

Three-phase/Single-phase DC BUS 220 Vdc

Highlights • Battery voltage: 220 Vdc • Galvanic Separation • High short-circuit current • Redundant ventilation

Protection for Industrial Applications The Master Industrial series UPS devices ensure maximum protection and power quality for any type of load, especially for industrial applications, industrial and petrochemical processes, and electrical and power plants etc. Master Industrial is an on-line double conversion UPS that belongs to class VFI SS 111 according to IEC EN 62040-3 with input and inverter transformers.

82

Industrial Environment Master Industrial is suited to demanding installation environments where there are vibrations, mechanical stress, dust and in general where operating conditions are unfavourable to products created for the market standard (different levels of IP protection available upon request). High ICC The high short-circuit current (Icc = 3) makes it suitable for loads that require high current peaks; during switch-on or during normal operation.


The Easy Source input feature, the Battery Care System, and the flexibility and communication capabilities are the same as those available in the traditional Master MPS series.

MIM 60 MIM 80

1900

Redundant ventilation Particular attention was dedicated to redundant ventilation at 100%, which ensures operation with a normal load with half of the fans operating; in addition,

MIM 30 MIM 40

0

80

800

UPS

dimensions (mm)

each fan is checked and an alarm signal is provided in cases of stoppage or failure.

1900

Continuous voltage 220V The input and inverter transformers guarantee the isolation of the AC side and also the batteries, which are sized for a voltage of 220 Vdc (from 108 to 114 elements), the standard industrial value.

0

80

1600

MODELS

MIM 30

MIM 40

MIM 60

MIM 80

POWER

30

40

60

80

INPUT Nominal voltage

380 - 400 - 415 Vac Three-phase

Voltage tolerance

400 V ± 20%

Frequency

45 ÷ 65 Hz

Power factor

≥ 0.93

Current distortion

< 5%

Soft start

0 - 100% in 30’’ configurable

Permissible frequency tolerance

± 2% (selectable from ± 1% to ± 5% from front panel)

Standard equipment

Back Feed protection; separable bypass line; battery isolation

BATTERIES Number of cells

108 ÷ 114

Max charge voltage

274 V

Temperature compensation

-0.5 Vx°C

OUTPUT Nominal power (kVA)

30

40

Active power (kW)

24

32

Nominal voltage

60

80

48

64

230 Vac Single-phase

Static stability

± 1%

Dynamic stability

± 5%

Voltage distortion

< 1% with linear load / < 3% with non-linear load

Frequency

50 or 60 Hz (selectable)

Crest factor (lpeack/lrms)

3:1

Overload

110% for 60’; 125% for 10’; 150% for 1’

Short circuit current

3 I nom.

INFO FOR INSTALLATION Weight (kg) Dimensions (hwd) (mm)

850

900

1400

1900 x 800 x 800

1500 1900 x 1600 x 800

Remote signals

voltage-free contacts

Remote controls

ESD and bypass

Communication

Double RS232 + remote contacts + 2 slots for communications interface

Ambient temperature Relative humidity

0°C / +40°C < 95% non-condensing

Colour

Dark grey RAL 7016

Noise level

63 ÷ 68 dBA a 1 m

Ventilation

Redundant fans

Protection level

IP20

Rendimento

up to 94%

Regulations

Regulatory Directives LV 2006/95/EC - 2004/108/EC; IEC Safety EN 62040-1; EMC IEC EN 62040-2; IEC Performance EN 62040-3

Classification according to IEC 62040-3 www.riello-ups.com

(Voltage Frequency Independent) VFI - SS - 111 83


INDUSTRIAL PROCESSES

INDUSTRIAL PLCs

Master FC400 30-120 kVA

Three-phase/Three-phase

Highlights • Frequency converter 50/400 Hz • Output voltage: 208 V - 3F • Galvanic Separation • Two versions to rduce input harmonics • Applications:airport, military and naval

The Master FC400 series static frequency converters are available from 30 to 120kVA, with a 50 or 60Hz input and a 400Hz output. The product of extended experience acquired in the UPS industry, the MP FC 400 series is distinguished by the use of technologically advanced components and for excellent reliability, ease of maintenance and easy of operation. The Master FC400 series uses double conversion technology (VFI SS 111 voltage and frequency independent compliant with IEC EN 62040-3) with an output transformer inside in order to ensure the isolation of the load from network disturbances in all 84

conditions. The output voltage is 208Vca three-phase (200/115V versions upon request). Thanks to high frequency, digitallycontrolled IGBT technology, the Master FC400 static converters are ideal for airport, military and naval applications. Minimum impact on network – easy source Master FC400 was designed to reduce to a minimum the impact on the network or a generator located upstream, thanks to the low harmonic content input and the progressive start of the rectifier.


Options • Input isolation transformer • 2 Programmable relay contact boards • Remote LCD mimic panel • Remote Graphic Panel • Higher protection level than IP20 • Parallel.

740

550

UPS

MFC 60 - MFC 80 MFC 100 - MFC 120

MFC 30

1900

Ease of Installation and Maintenance Master FC400 only requires a small space for installation (only 0.86m2 for 120kVA). Ordinary and extraordinary maintenance operations are facilitated by frontal access to the main subsets of the frequency converter. The fans in the upper part of the UPS allow for its placement against the wall, eliminating side and rear access.

dimensions (mm)

Applications Master Plus FC provides additional protection for a wide range of applications, including: • Powering planes in airports • Radar and flight-control systems • Naval applications • Military applications • Power for test benches

1200

These features make the frequency converters of the Master FC400 especially compatible with generators.

0

80

800

MODELS

MFC 30

MFC 60

MFC 80

MFC 100

MFC 120

POWER

30

60

80

100

120

INPUT Nominal voltage

380 - 400 - 415 Vac Three-phase

Voltage tolerance

400 V ± 20%

Frequency

45 ÷ 65 Hz

Power factor

≥ 0.93 (HC Version)

Current distortion

< 5% C (HC Version)

Soft start

0 - 100% in 120’’ configurable

OUTPUT Nominal power (kVA)

30

60

80

100

120

Active power (kW)

24

48

64

80

96

Nominal voltage

208 Vac Three-phase + Neutro

Static stability

± 1%

Dynamic stability

± 5%

Voltage distortion

< 3% with linear load / < 4% with non-linear load

Frequency

400 Hz

Crest factor (lpeack/lrms)

3:1

Overload

110% for 60’; 125% for 10’; 150% for 1’

INFO FOR INSTALLATION Weight (kg) Dimensions (hwd) (mm) Remote signals

330 1200 x 550 x 740

480

500

530 1900 x 800 x 800

voltage-free contacts

Remote controls

ESD and ON/OFF

Communication

Double RS232 + remote contacts + 2 slots for communications interface

Ambient temperature Relative humidity

0°C / +40°C (50°C @ 75% load) < 95% non-condensing

Colour

Dark grey RAL 7016

Noise level

61 ÷ 63 dBA a 1 m

Protection level

560

IP20 (others upon request)

Rendimento

up to 92%

Regulations

Regulatory Directives LV 2006/95/EC - 2004/108/EC; IEC Safety EN 62040-1; EMC IEC EN 62040-2; IEC Performance EN 62040-3

Classification according to IEC 62040-3 www.riello-ups.com

(Voltage Frequency Independent) VFI - SS - 111 85


ServerS

Multi Switch 16A

Single-phase

Highlights • Redundant power supply • Load protection • Versatility of use

Ouput 1 Max 4 A

Ouput 2

Multi-SWITCH allows for extreme power supply continuity to the installation. Its operating principle ensures higher reliability than a single UPS or one with a bypass.

Max 4 A

Ouput 3 Max 4 A

Ouput 4 Input 1

Max 4 A

Ouput 5 Input 2

Max 4 A

Ouput 6 Max 4 A

Ouput 7 Max 4 A

Ouput 8 Max 4 A

86

Operating principle Multi-Switch allows for the remote distribution and management of 8 utilities in a system with two power supply lines of any type (two mains inputs, or two UPS devices). Multi-Switch is able to connect each of the 8 loads (each with a maximum absorption of 4A) to one of the two power lines, while simultaneously monitoring absorption. Protection against load faults If the event of a load fault (for example due to a short circuit or overload) the Multi-switch disconnects the load, in order to prevent disturbing


Protection against power supply faults In the event one of the two power sources is not within the tolerances, Multi-Switch will switch the other utilities to the second power source (switching is instantaneous if the two sources are in phase). Features • Full utilities protection against mains and load failures • Versatility of use: Multi-SWITCH can be powered with 2 different power supplies (2 UPS devices even of different sizes/ types) • Wiring on 19” cabinet • LCD display for monitoring measurements / alarms / statuses • Can be connected to PowerNetGuard

supervision software (Ethernet version) • No signal connection between the Multi Switch and the power sources or utilities is necessary. • Visualisation software • Network interface.

MSW (2 inputs - 8 outputs) FRONT

Output socket

BACK

MODELS

MSW

POWER

16A

UPS

the operation of the other loads (in case of poor protection selectivity).

version “N” ETHERNET

THERMAL INPUT PROTECTIONS

version “S” Serial E RS232

INPUT SOCKETS

INPUT Nominal voltage Nominal frequency Max load for every input (A) Input sockets

180 - 276 Vac 50 or 60 Hz 16 2 IEC 320 (16A)

OUTPUT Nominal voltage Max load for every output (A) Output socket

choice between the two input power sources 4 8 IEC 320 10A

INFO FOR INSTALLATION Weight (kg) Dimensions (hwd) (mm) Ambient temperature

10 2U x 19” x 360 0°C / +40°C

Relative humidity

< 95% non-condensing

Protection devices

Overcurrent - overvoltage - undervoltage - thermal - protection against energy back-feed

Max altitude Max altitude (in storage conditions) Communication Colour Protection level Noise level

www.riello-ups.com

3000 m 6000 m; 45 °C RS232 in MSW-S / Ethernet in MSW-N Dark grey RAL 5004 IP20 < 35 dBA a 1 m

87


ServerS

Multi Switch ATS 16A

Single-phase

Highlights • Load protection • Versatility of use • Only 1U

Ouput 1 Max 10 A

Input 1

Input 2

Ouput 2 Max 10 A

Ouput 3 Max 16 A

88

Multi-SWITCH ATS provides extreme power supply continuity to the installation. Its operating principle ensures higher reliability than a single UPS or one with a bypass. Operating principle Multi Switch ATS provides direct distribution of eight 10A IEC utilities or one 16A IEC utility in a system with two power supply lines of any type (two mains inputs, or two UPS). Multi Switch ATS is able to connect to either of the two power supply lines, while also monitoring absorption. Protection against load faults In case one of the loads fails (e.g. short


Protection against power supply faults In the event one of the two power sources does not fall not within the tolerances, Multi-Switch ATS will switch the other loads to the second power source (this occurs instantaneously if the two sources are in phase). Features • Full utilities protection against mains and load failures • Versatility of use: Multi Switch ATS can be powered with 2 different power supplies (2 UPS devices even of different sizes/types) • Wiring on 19” cabinet • Mimic panel

• Can be connected to PowerNetGuard supervision software • No signal connection between the Multi Switch ATS and the power sources or utilities is necessary. • Compatible with Powershield3 software • Slot for communication boards

UPS

circuit) the Multi Switch ATS disconnects the group of sockets where the load itself is connected, thus preventing other loads from being switched off (e.g. in case of poor protection selectivity) .

particulars MTA FRONT

ON/OFF Switches

REAR

USB

Serial RS232

THERMAL INPUT PROTECTIONS

SLOT FOR COMMUNICATION INTERFACE

TERMINAL BOARD CONTACTS

Output socket

MODELS

MTA

CORRENTE

16A

INPUT SOCKETS

INPUT Nominal voltage Nominal frequency Max load for every input (A) INPUT SOCKETS

180 - 276 Vac 50 or 60 Hz 16 2 IEC-320 C20 (16A)

OUTPUT Nominal voltage

choice between the two input power sources

Max load for every output (A)

10A su IEC-320 C13 - 16A su IEC-320 C19

Output socket

4+4 IEC-320 C13 (10A) + 1 IEC-320 C19 (16A)

INFO FOR INSTALLATION Weight (kg) Dimensions (hwd) (mm) Ambient temperature

6 1U x 19” x 330 0°C / +40°C

Relative humidity

< 95% non-condensing

Protection devices

Overcurrent - overvoltage - undervoltage - thermal - protection against energy back-feed

Max altitude Max altitude (in storage conditions) Communication Colour Protection level Noise level

www.riello-ups.com

3000 m 6000 m; 45 °C DB con RS232, USB, slot for communications interface, porta a contatti a relé Dark grey RAL 5004 IP20 < 35 dBA a 1 m

89


ServerS

Master Switch STS

Highlights • High reliability • “Hot Replacement” function • 3- or 4-pole version • Advanced communication

Installing a Master Switch static transfer switch provides additional resilience and protection from the disruption that can be caused by the failure of a single power source The result is the absolute protection of industrial utilities and critical information technology against power supply and load faults. 90

Operating principle Master Switch guarantees a source of redundant power, allowing the load to be switched between to alternative and independent power sources. Switching can be automatic (when a supply source falls outside of acceptable tolerances) or manually done by an operator from the front panel or remotely.


Total microprocessor control Microprocessor control logic ensures: • Fast and safe switching between power sources • Monitoring of all parameters via LCD display • Constant control of the SCRs • Advanced remote diagnostics (RS232 and TCP/IP)

High protection In the event of an output short circuit, MASTER SWITCH will block the transfer between the two power sources eliminating the risk of propagating the short circuit and its effects on the other loads. A backfeed control circuit ensures the automatic intervention of protection devices when a return of energy to one of the two MASTER SWITCH inputs is detected. Accessibility The layout of the moving components and parts is designed to ensure easy frontal access: • power cable connections that are easily accessed with entry from below • boards housed in a dedicated area for rapid diagnosis / replacement • all parts subject to controls, maintenance and/or replacement.

FUNCTION

L1

S1 Priority Source

L2

S2 Priority Source

L3

S1 Present

L4

S2 Present

L5

Static transfer switch SS1 closed

L6

Static transfer switch SS2 closed

L7

Alarm indicator

L8

Output selector ON/OFF

UPS

3P + N Source 2 Input

Input MCCB 1

Input MCCB 2

S2

S1

Maintenance Switch 2

Maintenance Switch 1

S4-2

SS2

SS1

S4-1

Output Switch 1

S3

3P + N Output

Redundant Design Power is supplied to the internal logic by two, separate supply circuits that are fully independent and that can be replaced in “hot replacement” mode without causing power supply interruptions to the load. In the event that the power supplied by both sources fails, full system operation is guaranteed by the Power Supply Backup function that provides auxiliary power supply to the circuit through an external, independent power source. MASTER SWITCH is equipped with dual redundant ventilation defined as: “fan LED

3P + N Source 1 Input

dimensions (mm) MTS 100 MTS 150

MTS 200 - MTS 250 MTS 300 - MTS 400

1500

685

0

53

MTS 600

685

0

58

1900

Protection against environmental disturbances Load overloads and faults In the event of an overload, the user can decide the level of intervention of the internal protections in order to block the supply of energy. In the extreme case a downstream short circuit, MASTER SWITCH disconnects the load, in order to prevent jeopardising the operation of other loads (e.g.. in case of poor protection selectivity).

Advanced communication Master Switch provides information, measurements, statuses, and alarms via the LCD display. The STS is compatible with Powershield3 supervision and shutdown software for Windows operating systems 7, 2008, Vista, 2003, XP, Linux, Mac OS X, and Sun Solaris.

1770

Protection against power supply faults In the event that one of the two power sources does not fall within accepted tolerance values, MASTER SWITCH will transfer the other loads over to the second power source (this happens instantly if the two sources are in phase).

redundancy plus”. Thanks to this feature, and in the unlikely event that two fans fail at the same time, those remaining would still be able to dissipate the heat generated at rated load and with an ambient temperature up to 40° C. The fans can be replaced in “hot replacement” mode, ensuring continuity during the intervention.

950

0 73

L1 L3

L5

L7 L4

L6

L8

L2

5 function keys and LCD operation www.riello-ups.com

91


MASTER SWITCH in REDUNDANT mode The secondary source [AS], although highly reliable, only powers the load power in the event of a failure with the priority source [PS], ensuring maximum redundancy and power quality to the loads.

UPS

UPS

[PS]

[AS]

USER 1

MASTER SWITCH in CROSS FEEDING Mode The two sources power critical loads using MASTER SWITCHES configured to selected one of the two power sources as the priority source (PS). In case of a failure in one of two sources, the other will be able to supply power to all the loads connected to the system).

[AS] = Secondary [PS] = Priority

UPS

UPS

[PS]

[AS]

USER 1 [AS]

[PS]

[AS] = Secondary [PS] = Priority

USER 2 MASTER SWITCH in BACK-UP mode MASTER SWITCHES power utilities via the priority energy source [PS]; the secondary energy source [AS] is made up of independent, separate power sources and to make up for any faults in the priority power source. [PS]

Independent separate lines

UPS

[PS]

[AS]

USER 1 [PS]

[AS]

[AS] = Secondary [PS] = Priority

USER 2

The flexibility of the UGS system ensures synchronism between the sources even when one of the two systems is not a Riello UPS model but rather is made by another manufacturer or when the input sources are not UPSs.

Sse

ss ins

ins

ins U S

US

UGS Sinchroniser

S ic r ns er S

o o

S ic r ns er S

o

92

ins

Battery

US

Battery

US

ss

Battery

Sse

Battery

DYNAMIC DUAL BUS CONFIGURATION The Riello UPS solution guarantees maximum reliability and ensures continuity of power supply in all operating conditions thanks to the UGS option that keeps the two systems, A and B, perfectly synchronised.

o


RATED CURRENT (A)

MTS 100

MTS 150

MTS 200

MTS 250

MTS 300

MTS 400

MTS 600

100

150

200

250

300

400

600

55

57

UPS

MODELS INPUT Nominal voltage sources S1/S2

380 - 400 - 415 Vac three-phase with neutral

Input voltage tolerance

180÷264 Vac (selectable)

Switched input phases

3+N (4-pole) - 3 (3-pole)

Nominal frequency

50 or 60 Hz

Input frequency tolerance range

+/-10% (selectable)

Distribution compatibility

IT, TT, TNS, TNC

OPERATING FEATURES Transfer type

“Break Before Make” (no overlapping sources)

Available transfer methods

Automatic / Manual / Remote

Transfer time for source failure

< 4 msec (S1/S2 synchronised) 10 msec (S1/S2 NON synchronised)

ENVIRONMENTAL Efficiency at full load (%) Noise level at 1 m from front (dBA) (from 0 to full load) - (dBA)

> 99% 55

55

55

55

Storage temperature

-10°C up to +50°C

Ambient temperature

O°C - 40°C

Relative humidity

55

95% non-condensing

Max installation height

1000 m at rated power (-1% power for every 100 m above 1000 m) - Max 4000 m

Reference Standards

EN 62310-1 (safety) EN 62310-2 (electro-magnetic compatibility)

INFO FOR INSTALLATION Weight (kg) Dimensions (hwd) (mm) Colour Protection level

www.riello-ups.com

155

175

1500 x 685 x 530

205

210

220

1770 x 685 x 580

240

375 1900 x 950 x 730

RAL 7016 IP 20

93


Local Area Networks (LAN)

ServerS

DATA CENTRES

TELECOMMUNICATIONS DEVICES

e-business

(Servers Farms, ISP/ASP/POP)

INDUSTRIAL PROCESSES

INDUSTRIAL PLCs

ELECTROMEDICAL DEVICES

EMERGENCY DEVICES (Lights/Alarms)

Flywheels Energy Storage

Highlights • High reliability • Very low TCO • Life expectancy of more than 20 years • High energy density • Parallelability with identical units or batteries • Green Energy • High efficiency Model with touch screen (optional)

The VDC series of flywheel energy storage systems provide Riello Master Plus UPS with a source of dc power that can be used to ride through short mains power supply 94

failures. The length of supply available can be used to cover the start-up time of a standby generator or prevent the initial discharge of a locally connected battery set.


UPS

The VDC flywheel connects directly to the UPS DC busbar and is a standalone device supplied in a matching cabinet. The VDC series of flywheels has been designed for UPS applications within datacentres, hospitals and industrial installations. The patented flywheel concept is a form of energy storage and provides a green, clean source of back up power by converting the kinetic energy stored within a rotating mass to electrical power through a built-in IGBTbased converter. Two sizes are available (VDC and VDCXE) with a loadrelated back-up autonomy.

Benefits • High reliability • Lowest cost of ownership (TCO) • High power density • Small footprint • High efficiency - 99.4% • Minimal maintenance • Simple installation

Battery hardening For applications without Gensets or for those who still want to use batteries, the VDC and VDCXE can operate in parallel with batteries. In this configuration, the VDC is the first line of defense against power anomalies – saving the batteries for prolonged power outages. By being first to provide the necessary energy to ride-through power glitches, www.riello-ups.com

UPS

Backup Generator

Bypass

ATS

Rectifier AC/DC

Inverter AC/DC

Critical Loads

Utility 208-600v AC VDC Series flyweehls DC Energy Storage

the VDC system significantly increases battery life by absorbing over 98% of the discharges that would normally cause the batteries to be cycled. This innovative patented technology enables the flywheel to charge and discharge at high rates for countless cycles without degradation throughout its 20 year life – unlike traditional batteries.

Options The following options are available: • Colour Touch Screen panel • Remote Emergency Power Off (EPO) board • Modbus communication board • Dry contacts interface board

dimensions (mm) VDC / VDC-XE

1872

VDC flywheel concept The Riello UPS VDC-series flywheel stores kinetic energy in the form of a rotating mass (spinning at 36,000 RPM) within a sealed container. The patented technology includes the flywheel hub, formed from aerospace-grade steel, a high speed permanent magnet motor generator, contact-free magnetic bearings that levitate and sustain the rotor during operation, and a superior touchscreen control system that provides vital information on system performance. A flywheel is also known as a ‘mechanical battery’ and energy storage system, and is used to perform the traditional role of battery sets within a standby power application.

762

762

95


Configurations Backup during auxiliary generator start-up phase Genset Ride-Through: Generators must be able to assume critical loads quickly. While batteries can carry out this function, Riello UPS VDC series systems provide reliable energy storage instantaneously; assuring a predictable transition to the stand-by generator, all in a compact footprint.

Utility Power

Auto Transfer Switch

Critical Loads

UPS

Critical Power

DC Bus

Backup Generator

VDC Flywheels Non Critical Loads

Aid to batteries For applications without Generators or for those who still want to use batteries, the VDC and VDC-XE can operate in parallel. In this configuration, the VDC is the first line of defense against power fluctuations – saving the batteries for prolonged power outages. By being first to provide the necessary energy to ride through power glitches, the Riello UPS VDC series significantly increases battery life by absorbing over 98% of the discharges that would have normally caused the batteries to be cycled.

Utility Power

Auto Transfer Switch

UPS

Critical Loads

Critical Power

DC Bus

Backup Generator

VDC Flywheels Non Critical Loads

Protection for industrial applications For applications in industrial markets where power disturbances can shut down sensitive process control equipment leading to lost productivity, the Riello UPS VDC series is the perfect solution. 98% of all power disruptions and outages are less than 10 seconds in duration; all of which can be covered by the energy stored in the flywheel. Because the VDC series can operate in harsh environments and occupies a compact space, it is also the ideal solution for industrial applications where space is limited.

Utility Power

Auto Transfer Switch

Critical Loads

UPS

Critical Power

DC Bus

VDC Flywheels Non Critical Loads

96


VDC

UPS

Run times * UPS OUTPUT POWER RATING (kVA)

Number of flywheels 1

40

60

80

100

120

160

225

275

99.8

67.0

50.3

40.3

33.6

21.9

11.7

6.4

80.0

65.0

48.8

34.8

72.3

51.5

2 3 4

450

550

26.6

11.3

6.2

42.2

23.2

16.8

8.5

55.6

34.1

26.1

16.0

6.0

34.8

23.0

11.7

450

550

750

1100

5

750

1100

Runtime in seconds VDC-XE

UPS OUTPUT POWER RATING (kVA)

Number of flywheels 1

40

60

80

100

120

160

225

275

133.3

88.9

66.7

53.3

44.4

32.9

20.5

14.1

102.4

85.3

64.0

45.5

37.3

19.7

13.6

6.7

95.0

67.6

55.3

33.6

26.3

16.2

6.9

72.9

44.6

36.5

25.3

13.3

45.6

33.3

20.0

2 3 4 5 Runtime in seconds

(*) Backup Times are typical using 0.9 Output Power Factor, 80% Power Full Load Rating, 96% Inverter Efficiency

MODELS

VDC

VDC-XE

POWER Max Power Max Energy Storage Flywheel rotation speed

215 kW

300 kW

3000kWsec@100kW

4000kWsec@100kW

from 18500 to 36000 rpm

from 14500 to 36750 rpm

INPUT Input Voltage

400-600 Vdc

Recharge Rate Efficiency

15-50 A Adjustable for application 99.2% at max. power

99.4% at max. power

OUTPUT Voltage Discharge

400-520 Vdc Adjustable for application

Voltage Regulation

+/- 1%

DC Ripple

≤ 2%

INFO FOR INSTALLATION Operating Temperature

-2O°C / +40°C

Humidity

95% non-condensing

Colour

Dark grey RAL 7016

Noise level Dimensions (hwd) (mm) Weight (kg) Protection level Regulations

www.riello-ups.com

≤ 68dBA a 1 m 1872 x 762 x 762 705 IP 20 EMC EN 61000-6-4:2001; EMC EN 61000-6-2:2001; Safety EN 60204-1; Directives: 2004/108/EC; 98/37/EC

97


Emergency devices

Highlights • High reliability • “Hot Replacement” function • Advanced communication

Riello UPS systems are also designed and built to be used in applications such as centralised power supply systems for emergency lighting, alarms, and electro-medical equipment. Regulatory standards CEI 64-8 V2, EN 50171 and other guidelines, define the features and capabilities that the systems must have; below the main features/capabilities are summarised: • Runtime of up to 3 h • Battery recharge time under 12 hours • Galvanic isolation input/output • Advanced diagnostics (information on equipment’s mimic panel) • Interface device to provide information remotely (usually via voltage free contacts) • High short circuit current These applications require a UPS configured as follows: • Standard UPS with high capacity battery charger • Isolation transformer (when required) • Ability to communicate with remote peripheral device.

Features • Total microprocessor control: for reduced overall size and superior reliability • Use of IGBT technology (Isolated Gate Bipolar Transistor) has been used in UPS devices for over 10 years to optimise electrical performance including overload management and small size. • Advanced communications interface(UPS devices equipped with free contact interfaces, RS232/485 serial interface for communication with local PC or network PC) • “Telenetguard” teleassistance for remote equipment control and diagnostics. • LCD display for complete control of equipment (statuses/alarms/ measurements/event logs) • Option of expanding the power and/or of increasing reliability through the parallel connection of several models (8kVA models and higher)

CSS CONFIGURATIONS Model

98

Sentinel Pro

Sentinel Dual

Sentinel Power

Multi Sentry

Runtime up to 3 hours: Power

1.600 W

2.000 W

3.000 W

30.000 W

Runtime up to 1 hour: Power

2.100 W

3.500 W

7.000 W

64.000 W


Advanced communication Multi-platform communication for all operating systems and network environments: PowerShield3 supervision and shutdown software for Windows operating systems 7, 2008, Vista, 2003, XP, Linux, Mac OS X and Sun Solaris, VMware ESX and other Unix operating systems. Regulatory Compliance Riello UPS systems comply with European and available national guidelines.

power supply. In the “always powered” operating mode, the CSS load is always powered by the inverter and is only switched onto the mains via the bypass circuit in the event of a failure In the “powered from the mains” mode, the load is powered and only switched onto the inverter when there is no mains power. In “emergency only” mode the load is only powered by the inverter if there is no mains power. The inverter has a soft-start feature, to handle current surges when powered utilities are switched on, and limit the value of the power required. In “always powered/emergency only” mode two outputs can be used: one always powered (such as for powering computer loads) and one that is only powered when there is no mains power (such as for powering emergency lights that by law

A full range of CSS, from 700VA to 200kVA The CSS range is comprised of the following blocks: Rectifier: converts the alternating current input voltage, coming from the mains power supply or from an alternative source (generator) into continuous current voltage. Inverter: converts the continuous current voltage supplied by the rectifier into alternating current voltage: in this way, the voltage is reconstructed,filtered and stabilised compared to the input voltage.

must switch on within 0.5 seconds of a mains failure).

UPS

Options • Communications interfaces: see accessories table of individual models • Isolation transformers

Batteries: used to power the inverter for a period of time required by law (up to 3 hours if there is no generator). The batteries used are generally valveregulated, lead-acid batteries, and do not require maintenance or a special installation environment as they have very low gas emissions.

Diagrams of the various system solutions 1. ALWAYS POWERED

2. POWERED BY MAINS

3. ONLY EMERGENCY

4. ALWAYS POWERED/ONLY EMERGENCY

By-pass: allows switching between the inverter and the mains

www.riello-ups.com

99


Connectivity PowerShield3 Communications Software

All the trademarks indicated are the property of their respective owners.

GRAPHIC MONITORING OF UPS AND Environmental Sensors STATUS PowerShield3 is a simple but powerful RIELLO UPS management tool. There are various graphic versions for all the operating systems. DETAILED UPS PARAMETER DISPLAY AND Environmental Sensors PowerShield3 provides all the information required for first level diagnostics. EVENTS LOG AND GRAPHICAL DISPLAY All changes in UPS operating status are logged and displayed in a graphical format from which the user can monitor trends in the mains electrical parameters monitored. PROGRAMMING OF UPS PARAMETERS The user can select several options remotely: turn the UPS on or off, restart after a power loss and instigate a battery test. GRAPHIC MONITORING OF UPS STATUS VERSION FOR MAC OS X RIELLO UPS PowerShield3 software is the only UPS control and shut-down software running under Macintosh with a client-server cross platform architecture. It allows integration in TCP/IP networks with Windows, Novell, IBM OS/2 and the most widely used UNIX operating systems. PowerShield3 supports the Netman Plus series of network agents and provides multi-language support. BLOCK AND FUNCTIONAL DIAGRAMS PowerShield3 also displays the UPS in block format providing the user with information regarding operating status. NOTIFICATION OF ALARMS VIA E-MAIL, SMS, FAX AND VOICE PowerShield3 can be configured to forward alarm messages automatically via e-mail, SMS, fax and voice.

PowerShield3 can be downloaded free of charge from www.riello-ups.com

PowerShield3 software guarantees efficient and intuitive UPS management, displaying all the most important information such as input voltage, applied load, and battery capacity. In the event of a failure, it is able to provide detailed information on the status of the UPS. Its client/server architecture makes it an ideal tool for managing multiplatform network systems. Features • Sequential and priority-based shutdown: PowerShield3 carries out unattended shutdowns of all network PCs, saving any work in progress by the most common applications. Users can define the shutdown priority of the various computers connected to the network and customise the procedure. • Multi-platform compatibilty, PowerShield ensures multi-platform interoperability using the standard TCP/IP as a communications protocol. This makes it possible to monitor computers with different operating systems from a single console,for 100

example monitoring a UNIX server from a Windows PC or connecting to a UPS located indifferent geographical areas using dedicated networks (intranets) or the Internet. • Event scheduling: PowerShield3 allows users to define their own shutdown and start-upprocedures for powered systems, thereby increasing system security and providing significant energy savings. • Message management: PowerShield3 keeps users constantly informed of the status of both the UPS and the environmental sensors, both locally and by sending messages via the network. In addition, it also is possible to define a list of users that will receive e-mails, faxes, voice mails and SMS in the event of failures or black-outs. • Integrated SNMP agent: PowerShield3 features an integrated SNMP agent for UPS management allows sending all information pertaining to the UPS using the standard RFC 1628 and related trap ,and environmental sensors. This feature makes it possible to manage the UPS in compatible SNMP management stations such as HP Open View, Novell Managewise and IBM NetView • Integrated wap server integrated:

PowerShield3 allows the user to remotely monitor the UPS via aWAP mobile phone UPS diagnostics has never been so easy and immediate. • Security and communication is now password protected for increased security in UPS management. Thanks to the discovery/browsing function, all the UPS devices connected to a computer and/or via LAN are immediately displayed in list format in order to be monitored. In the absence of a LAN connection, communication is supported via modem.

Supported operating systems • Windows 2000, 2003 Server, XP, Vista, 2008 Server, 7, on X86, X86_64 and IA64 processors • Linux on X86, X86_64 and IA64 processors • Novell Netware 3.x, 4.x, 5.x, 6 • Mac OS X • The most common UNIX operating systems such as: IBM AIX, HP, SUN Solaris INTEL and SPARC, SCO Unixware and Open Server, Silicon Graphics IRIX, Compaq Tru64 UNIX and DEC UNIX, Open BSD UNIX and FreeBSD UNIX, NCR UNIX • HP OPEN VMS • VMWare ESX, VSPHERE.


UPS

PowerNETGuard Supervision software PowerNETGuard is a programme for the centralised management of UPS devices through SNMP communication protocol and is the ideal tool for EDP Managers in Data Centres and medium and large networks. Using the Management Information Base (MIB) described with RFC1628 it is able to homogeneously manage all the UPSs conforming to this world standard.

Features • Centralised control of remote UPSs via Ethernet with SNMP protocol • Multi-level display of geographical areas, building plans, maps, etc. • Multi-user access with various security levels • Compatible with Netman and Standard SNMP RFC1628 interfaces • Creation of graphs of UPS input and output values and data back-up on files • Alarm notification via e-mail and SMS • Integrated Wap Server for alarm display • For Windows operating systems (2008 Server, Vista, 2003 and XP), Linux, Mac OS X, Solaris 8, 9 and 10, and Silicon Graphics IRIX

Centralised control of remote UPS devices 1. CONNECTION VIA NETMAN PLUS 2. NETWORK AGENTS FOR THIRD PARTY UPS 1. Netman 1. Netman

2. Network agent

1. Netman

NetMan 101/102 Plus Network agent The NetMan Plus network agent allows for the management of the UPS directly connected on LAN 10/100 Mb using the main network communication protocols (TCP/IP, HTTP andSNMP). It was developed to integrate the UPS into medium and large networks, in order to provide a high degree of communications reliability between the UPS and its management systems. Features • Compatible with 10/100Mbps Ethernet and IPv4/6 network • Compatible with PowerShield3 and TeleNetGuard www.riello-ups.com

• SNMP with RFC1628 for PowerNETGuard and NMS connection • SNMP with RFC 3433 for managing environmental sensors • HTTP for UPS control via web browser • SMTP for emailing alarm notification or UPS status • Serial port for UPS control • Modem management for TeleNetGuard and PowerShield3 • Events log management • Wake-on Lan management for starting computer via TCP/IP network • Other standards: DHCP, DNS, RARP, FTP, NTP, ICMP, IGMP • Configured via TELNET or serial terminal with data import/export • Firmware upgradeable through the serial port and TFTP server. 101


NetMan 202 Plus Network agent

The NetMan 202 network agent allows for the management of UPSs directly connected to LAN 10/100 Mb using the main network communication protocols (TCP/IP, HTTP andSNMP). It was developed to integrate the UPS into medium and large networks, in order to provide a high degree of communications reliability between the UPS and its management systems. Features • 32bit RISC processor • Compatible with 10/100Mbps Ethernet and IPv4/6 network

Environmental sensors With Netman environmental sensors it is possible to monitor and record environmental conditions and activities in protected areas and at premises where the UPS is installed. Environmental sensors allow extending the control and management of the environment surrounding the UPS, monitoring temperature, humidity and allowing the operation of devices such as fans or locks, providing the values via Web, SNMP, and through PowerShield3 software.

Application diagram

Air conditioner

Smoke detector Temperature sensor Temperature sensor + digital control

Netman

102

• Compatible with PowerShield3 and TeleNetGuard • SNMP v1 and v3 with RFC1628 for PowerNETGuard and NMS connection • SNMP v1 and v3 with RFC3433 for the management of environmental sensors • HTTP for UPS control via web browser • SMTP for emailing alarm notification or UPS status • Maximum expandability • USB host for Pendrive USB connection • Events log and data management • Wake-on Lan management for starting computer via TCP/IP network • Other standards: DHCP, DNS, RARP, FTP, NTP, ICMP, IGMP • Management of environmental sensors • Configurable via Telnet, SSH, and serial terminal sessions with data export/import. • Firmware upgradeable via USB port FTP and http.

Using the PowerShield3 software it is possible to manage the status of sensors for sending messages. For further information, refer to the PowerShield3 software. NetMan plus can handle up to a maximum of 6 separate sensors. The environmental sensors can be installed quickly, thanks to their small size, and do not require external power. In addition, configuration is quick and intuitive thanks to the self-learning of the connected sensors. The following sensors are available: - Sensor for temperature: -55 +125 °C - Sensor for temperature: -55 +125 °C and humidity: 0- 100% - Sensor for temperature: -55 +125 °C and digital I/O: 0-12Vdc. In, 1A max Out 48Vdc

Application diagram Temperature sensor

Netman


UPS

Multicom 301/302 Protocol converter The MultiCOM 301/302 protocol converter allows monitoring the UPS using the MODBUS/JBUS protocol on RS232 or RS485 serial lines. In addition, it manages a second independent RS232 serial line that can be used to connect to other devices such as the Netman 101 or a PC that uses PowerShield3 software.

Features • Port configuration for MODBUS/JBUS as RS232 or RS485 • Management of two independent serial lines • Suited for integration with main BMS systems.

Multicom 351/352 Serial duplicator The MultiCOM 351/352 serial duplicator is an accessory that allows two devices to be connected to a single UPS communication serial port. It can be used in all cases where several serial connections and multiple UPS polling are required, and is ideal for LAN networks with a firewall, where a high level of security is required or for the management of separate LAN networks powered by a singe UPS.

Features • Cascading configuration to obtain a maximum of 4 serial communication ports • LED communication flow indicator • Firmware can be updated via the serial port

Multicom 362 Serial Port / USB The Multicom 362 accessory allows the UPS to communicate via the RS232 serial line or alternatively via the USB port through the auxiliary communication port. It allows UPSs not equipped with a USB communication port to be connected to Apple Macintosh computers or computers with Windows and Linux operating systems.

www.riello-ups.com

Features • Compatible with USB 1.2 • Compatible with PowerShield3. For compatibility, refer to the Compatibility table on pg. 17 and 20

103


Multicom 372 SERIAL PORT / ESD The Multicom 372 allows an additional communication port to be added to the UPS to control and monitor the UPS via the RS232 serial line. The board is supplied with an ESD input (emergency UPS shutdown) and an RSD (Remote Shut-down) input, both available on a removable terminal board and directly connectible to emergency buttons or other buttons.

Features

MultiCOM 382 provides a set of relay contacts for the management of UPS statuses and alarms. The board is equipped with two removable terminal boards. The ESD signal (emergency UPS shutdown) and the RSD signal (Remote shutdown) are found on one of these terminal boards. Using this board, Battery Working, Bypass, Alarm and Low Battery

signals can be associated with SPDT dry contacts or normally open contacts.

• Management of EPO and UPS Shut-down • Powering of devices up to 12V 80mA max. For compatibility, refer to the Compatibility table on pg. 17 and 20

Multicom 382 Contacts /ESD board

Features • Max power 3A to 250Vac • Ability to configure the association of the signals on the contacts. For compatibility, refer to the Compatibility table on pg. 17 and 20

Multi I/O Protocol and contacts converter The Multi I/O is a device that integrates the UPS with a control system, via input and output relay signals, that is fully configurable. It allows two devices to be connected to a single UPS communication serial port. It can be used in all cases where there is a real need for several serial connections for the multiple interrogation of the UPS. It is also able to communicate on RS485 lines via the MODBUS/JBUS protocol.

104

Features • 8 analog/digital inputs • 8 relay outputs (3A to 250Vac), configurable using the input and UPS statuses. • Communicate with the UPS via RS232 • It can control two independent RS232/ RS485 serial lines to monitor the UPS and its statuses with the MODBUS/JBUS protocol. • Firmware can be updated via the serial port


UPS

I/O Expansion board The I/O expansion board for the Master Plus range is equipped with: • 6 outputs with NC/NO voltage-free contacts (250V/5A), electrically isolated from each other and from other circuits • 2 self-powered inputs

Each output or input can be configured with different meanings, using the relative menu.

Multicom 401 is an accessory that allows the UPS to be connected to a Profibus DP network. The device combines UPS management and monitoring in a control system based on a field bus that is among the most widely used in the industrial sector and in communication between control / automation and I/O distributed systems.

Features

For compatibility, refer to the Compatibility table on pg. 17 and 20

Multicom 401 Protocol converter • PROFIBUS DP-V1 protocol • Configurable addresses from 0 to 99 • Data format: Profidrive V2 PP05 • Communication speed configurable from 9.6kBit/s to 12 MBit/s • Led displaying the communication flow

Kit for AS400 and i-Series Communications kit The IBM AS/400 system, due to single level memory management, requires the almost-mandatory connection to a UPS as any drop in voltage resulting in a power shutdown, causes long, if not very long, restoration times as well as possible

hardware damage due to even simple disturbances in electrical power signal. The AS/400 systems connection kit, allows for the correct closure of the OS/400 operating system, during a black-out.

Features • Compatible with all AS/400 and i-Series Systems • Supports all UPSs in the Riello UPS range.

Multi Panel is a remote control panel that allows users to remotely monitor the UPS and to have a detailed overview of operating conditions in real time. Using this type of device, network power, output, and battery measurements as well as UPS statuses can be viewed. The high-visibility graphic display is available in English, Italian, German, French, Spanish, Russian, Chinese and many other languages. Multi Panel is equipped with three independent serial ports, one of which permits monitoring the UPS via the MODBUS

/ JBUS or on RS485 or RS232 serial lines. The other independent serial lines allow other other devices to be connected, such as Netman 101 or a PC that uses PowerShield3 software.

Multi Panel

www.riello-ups.com

• High visibility LCD with graphic functions • Management of three independent serial lines • Port configuration for MODBUS/JBUS as RS232 or RS485 • Suited for integration with main BMS management systems. • Firmware can be updated via the serial port

105


Connectivity: some solutions Powershield3 Software free

RS232 USB

Point-to-point connections with serial lines

Local position

Multicom 362

Powershield3 Software full license

RS232 USB

Local position

Powershield3 Software free

RS232 USB

Local position

Multicom 301/302

Connections with field bus with serial lines

MODBUS RS485 MODBUS

PLC

Multicom 301/302

Management PC

Multicom 301/302

Local position

Multicom 401

PROFIBUS Multicom 401 PLC Profibus DP

106

Management PC


UPS

Ethernet TCP/IP LAN/WAN CONNECTIONS

Netman 101/202 plus

Powershield3 Software full license

Netman 101/202 plus Server

SWITCH

LAN

Netman 101/202 plus

WAN

internet

Software PowerNetGuard RS232

Remote position

USB

Remote position

Powershield3 Software free

Netman 101/102 plus

Ethernet TCP/IP WAN CONNECTIONS SWITCH

Netman 101/102 plus

internet

Netman 101/102 plus

WAN

PowerNetGuard Software Remote position

SWITCH Netman 101/102 plus

Connection with PLC to contacts Multicom 372

Management PC

PLC

www.riello-ups.com

Local position

107


Maintenance Bypass Multi Pass 10, 16 e 16-R Multi PASS 16 Box version

Multi PASS 16-R Rack version

The MultiPASS manual bypass cuts out the UPS in the event of malfunction or breakage. MultiPASS ensures that the connected utilities are automatically switched to the main power line if the UPS is switched off or is blocked. MultiPASS 16 is provided for rack or wall installations (box).

Features

Available in a 32A single-phase configuration, enables to service UPS up to 6kVA in a quick and safe manner, and meanwhile ensuring power continuity.

MBB32A is equipped with a metal support for wall mounting metal support.

Available in a 100A configuration, can be used as manual bypass for 10-20kVA single-phase UPS and 10-40kVA threephase UPS.

Riello UPS offers a wide range of external bypasses and static switches for its UPSs up to 800kVA, for parallel systems up to 6.4 MVA.

• Rack or wall version • Standard back-feed protection • Automatic switching during mains failure • Mains power present LED indicator • Available with sockets of different standards (IEC, english socket, terminal boards).

MBB32A MAINS LOAD OUT UPS

MBB100A SWIN

MAINS

TO UPS INPUT or UPS BYPASS INPUT

AUX SWMB

REMOTE MAINTENANCE bypass (normal close contact)

AUX

LOAD

108

SWOUT

FROM UPS BYPASS


SERVICES AND CONTACTS

Services and contacts

www.riello-ups.com

109


Services and consultancy Pre-sales consultancy

TEC is the RIELLO UPS pre-sales advisory service. Our TEC (Technical Energy Consultant) experts have been working in the power sector for years, and come from backgrounds with technical experience in industry and power plants. Consultancy On Standards TEC personnel can provide advice on the relevant standards affecting: • RIELLO UPS product ranges • Batteries • Installation • Applications - such as emergency lighting, security and electro-medical Work tools TEC training and information is provided in the form of: • UPS sizing • Official technical guides • Installation and specification manuals • TEC newsletters • Technical specifications Technical consultancy tEC personnel can provide advise and guidance on the selection, sizing and installation of RIELLO UPS products. Support in design tEC personnel can provide assistance in the design of a UPS system to completely satisfy customer specifications, including bespoke designs.

Technical Assistance Services

The Team UPService, our technical assistance facility uses highly trained engineers to provide a reliable and competent technical support and after-sales service. The services UPService can provide customers with: • A dedicated CALL CENTRE for connection to the UPService organisation.UPService personnel are always available and ready to provide advice and assistance regarding UPS installation, maintenance, fault finding and repair. • The free SWAP assistance service.

• On request, UPService can provide assistance during installation and initial startup of the UPS and train onsite personnel. UPService engineers can also verify site suitability, analyse and advise on rental solutions and disconnect and relocate equipment. • MAINTENANCE CONTRACTS can be provided by UPService to minimise response times and repair costs. Contracts range from periodic inspections to comprehensive cover including labour and materials. • UPService organises regular TECHNICAL TRAINING COURSES for UPS operators and installers.

• ON SITE a site based service for larger UPS that cannot be transported back to the UPService facility, either inside or outside warranty. A fast repair on site is guaranteed through the use of state-of-the-art UPS technology and the professionalism of the UPService personnel and Authorised Assistance Centres. UPService guarantees that failed parts are replaced with functioning ones, tested and updated in order to maintain the safety, reliability and operating characteristics of the UPS.

Help desk tEC is available 24-7 around the world and may be reached by phone, fax or e-mail to answer your requests immediately.

tec@riello-ups.com 110

upservice@riello-ups.com


SERVICES AND CONTACTS

TeleNETGuard 24 hour Teleassistance

Teleassistance The teleassistance service consists of a modem connection (GSM or dedicated telephone line) between your UPS and Riello UPS’s Service Centre. In case of failure your UPS will automatically call the Service Centre, which analyses the parameters sent and determines the importance of the call, distinguishing between a real failure and a simple alarm, and simultaneously transmits the alarm via fax, email or SMS to the customer. Advantages With TeleNetGuard, our Service Centres are able to intervene, already knowing the nature of the problem, thus shortening the time required for its resolution, while the regular transmission of more than 500 UPS parameters,

helps to prevent any problems due to the ageing of electronic components. With this service, your UPS is controlled 24 hours a day, all year round. The teleassistance service is free for the first year ( with the exception of the initial modem cost) To renew the TeleNETGuard service after the first 12 months, a maintenance contract must be stipulated, whose cost is included in the Teleservice.

Renting as an energy solution

Why renting? • Renting the UPS protects the original investment, while avoiding risks associated with technological obsolescence and limitations related to property ownership. • Renting does not require any minimum duration obligations and the fees are considered operating costs and therefore, are tax deductible. • By renting the UPS, the customer enjoys the benefits of using the latest technologies, without having to deal with the disadvantages of property ownership. Advantages • Immediate UPS availability. • Maintenance and assistance for the entire duration of the rental lease. • Variable and flexible lease periods: from 36 to 60 months. • Increased reliability due to the presence of constantly updated UPS devices. • All Risk insurance. Guaranteed services • Dedicated toll-free number • Dedicated e-mail. • Assistance in selecting the UPS. • Priority intervention thanks to the extensive network of Riello Service Centres. • Teleassistance. • Removal of old UPS.

www.riello-ups.com

111


Operating Offices UK RIELLO UPS Ltd Unit 50 - Clywedog Road North Wrexham Industrial Estate - Wrexham LL13 9XN Tel.: +44 (0)1978 729 297 - Fax: +44 (0)1978 729 290 www.riello-ups.co.uk / riello@riello-ups.co.uk ITALIA LEGNAGO, Headquarters Production and Sales Management Viale Europa, 7 37045 Legnago (VR) Tel.: +39 0442 635811 Fax: +39 0442 629098 www.riello-ups.com riello@riello-ups.com MILANO, Production and Sales Office Via Somalia, 20 20032 Cormano (MI) Tel.: +39 02 663271 Fax: +39 02 66327351 www.riello-ups.com riello@riello-ups.com ROMA, Sales Office Via Fosso della Magliana, 34/G 00148 Roma Tel.: +39 06 65192125 Fax: +39 06 65192247 www.riello-ups.com rielloroma@riello-ups.com

CONSTANT POWER SERVICES Ltd Unit 3 - Trust Industrial Estate, Wilbury Way Hitchin, Herts, SG4 0UZ Tel.: +44 (0)1462 422 955 - Fax: +44 (0)1462 422 754 www.cps4ups.co.uk / info@cps4ups.co.uk FRANCE RIELLO ONDULEURS s.a.r.l. SIEGE SOCIAL: 2/4 Rue du Bois Chaland, ZAC du Bois Chaland - 91090 Lisses Tel.: +33 (0)1 60 875454 - Fax: +33 (0)1 60 875450 www.riello-onduleurs.com - ventes@riello-onduleurs.com SALES SUD 147 Avenue M. Mérieux, Parc de Sacuny, Park Avenir 1 - 69530 Brignais Tel.: +33 (0)4 72 177108 - Fax: +33 (0)4 78 351422 www.riello-onduleurs.com - contact@riello-onduleurs.com ESPAÑA RIELLO ENERDATA s.l. C/ Labradores, 13 Urb. Prado del Espino 28660 Boadilla del Monte, Madrid Tel.: +34 (0)91 63 33 000 - Fax: +34 (0)91 63 21 793 www.riello-enerdata.es / enerdata@riello-enerdata.es RIELLO ENERDATA s.l. C/Aviacion 18 Edificio Morena y Vallejo 1 1º planta pol. Ind. Calonge 41007 Sevilla ESPANA Tel. +34 955 040044 Fax +34 955 040041 www.riello-enerdata.es / enerdata@riello-enerdata.es RIELLO TDL s.l. c/ Terra Alta, 88 - P.I. “Can Carner” 08211 Castellar Del Vallès, Barcelona Tel.: +34 (0)93 74 71 210 - Fax: +34 (0)93 71 46 562 www.riello-tdl.com / comercial@riello-tdl.com DEUTSCHLAND RIELLO UPS GmbH Siemensstr. 12 21465 Reinbek bei Hamburg Tel.: +49 (0)40 727 57-06 - Fax: +49 (0)40 727 57-189 www.riello-ups.de / info@riello-ups.de

112

INDIA Riello PCI India Pvt. Ltd. Prime Group Building, 11/5B, Pusa Road, New Delhi - 110 005. Phones: 91-11-41 888 999 (30 lines), 41 888 888, 2576 2562-64, 2576 2552-53, 2581 3338 Fax: 91-11-2575 5815, 2582 1623 PEOPLE’S REPUBLIC OF CHINA Riello UPS (Asia) Co., Ltd 28F, No. 500, Fute Dong Er Road, Waigaoqiao Free Trade Zone, Pudong District 200131 Shanghai Tel: +86-21-50464748 - Fax: +86-21-50464648 www.riello-ups.com - info@riello-ups.cn Riello UPS Asia Beijing Office No.418, 4F, Block A, Gaode Platza, No.10, Huayuan Dong Road, Haidian District Beijing Tel: +86-10-82038861 / 8862 Fax: +86-10-82038863 Riello UPS Asia Guangzhou Office Address Unit 1507 East Building, Dongshan Square, No. 65, Xianlie Zhong Road, Yuexiu District, 510095, Guangzhou. Tel: +86-20-28848001 Fax: +86-20-28848002 ASIA PACIFIC Singapore Representative office No. 138, Robinson Road - The corporate office #14-06 068906 Singapore Tel. +65 6323 4131 - Fax. +65 6323 4212 www.riello-ups.com - info@riello-ups.sg


Official Sponsor


CATGENX0111RUGB

www.riello-ups.com riello@riello-ups.com

- In the interest of product improvement Riello UPS reserves the right to change specifications without notice.

RIELLO ELETTRONICA


Turn static files into dynamic content formats.

Create a flipbook
Issuu converts static files into: digital portfolios, online yearbooks, online catalogs, digital photo albums and more. Sign up and create your flipbook.