Types 1301F and 1301G
Instruction Manual Form 1111 February 2009
1301 Series High-Pressure Regulators !
WARNING
Failure to follow these instructions or to properly install and maintain this equipment could result in an explosion, fire and/or chemical contamination causing property damage and personal injury or death. Fisher速 regulators must be installed, operated, and maintained in accordance with federal, state, and local codes, rules and regulations, and Fisher instructions. If the regulator vents gas or a leak develops in the system, service to the unit may be required. Failure to correct trouble could result in a hazardous condition.
P1025
Figure 1. Type 1301F High-Pressure Regulator
Scope of the Manual
Types 1301F and 1301G regulators can also be used in many other applications due to their rugged design as high-pressure reducing regulators for various fluids such as air, gas, water, and other liquids.
This Instruction Manual provides instructions for the installation, adjustment, maintenance, and parts ordering of the Types 1301F and 1301G high-pressure regulators.
The Type 1301F can handle outlet pressures from 10 to 225 psig (0,69 to 15,5 bar) in three ranges and the Type 1301G can handle outlet pressures from 200 to 500 psig (13,8 to 34,5 bar) in one range.
Product Description
Specifications
Types 1301F and 1301G regulators are direct-operated, high-pressure regulators, which can be used where high-pressure gas must be reduced for use as pilot supply pressure in pilot-operated regulators or as loading pressure in pressure-loaded regulators.
Specifications section lists the specifications for Types 1301F and 1301G high-pressure regulators on page 2. The maximum outlet pressure for a given regulator as it comes from the factory is stamped on the regulator nameplate.
Introduction
www.emersonprocess.com/regulators
D100341X012
Installation, operation, and maintenance procedures performed by unqualified personnel may result in improper adjustment and unsafe operation. Either condition may result in equipment damage or personal injury. Use qualified personnel when installing, operating, and maintaining the 1301 Series high-pressure regulator.