SAN DIEGO COMMUNITY COLLEGE DISTRICT
Gymnasium y Daylighting y g g Retrofit Harry West Gym – SD City College UC/CSU/CCC Sustainability Conference - June 22 22, 2009
David Umstot, PE Vice Chancellor Facilities Management 1
Learning Objective
The learner will identify y means to correct lighting illumination deficiencies with daylight harvesting and energy efficient lighting.
2
San Diego City College San Diego City College is uniquely situated nextt to t the th heart h t off downtown d t San S Diego, Di with close proximity to freeway access, public transportation and residential neighborhoods
3
San Diego City College Harry West Gymnasium The Harry West Gym first opened in October 2005. It h th has three regulation l ti b basketball k tb ll courts, t six i b badminton d i t courts, and three volleyball courts. It can accommodate up to 2 2,000 000 spectators spectators.
4
Harry West Gymnasium Existing Conditions The footcandle lighting at the floor level was half of what was needed for collegiate sports.
5
Harry West Gymnasium Proposed Corrections To achieve recommended lighting levels, a daylighting retrofit was proposed to replace 400-watt High Intensity Discharge (HID) fixtures with six-bulb T-5 High Output fi t fixtures and d install i t ll natural t ld daylight li ht h harvesting ti fifixtures. t
6
Harry West Gymnasium Proposed Corrections Daylighting Project
Remove 40 750-watt HID fixtures
Replace with 20 sixbulb T-5 fixtures and 20 daylight harvesting fixtures
Annual kWh Savings 116 316 kWh 116,316 7
Harry West Gymnasium Retrofit Advantages
Savings of between $17 – 18K annually for electricity
Significantly improve lighting levels and lighting quality during both daytime and evening hours
Reduction of replacement costs for materials and labors by approximately 50%
Ability to take advantage of $12K in incentive rebates offered by San Diego Gas & Electric for this energy efficient solution energy-efficient 8
Harry West Gymnasium Daylighting Retrofit Retrofit efforts began in November 2008 with installation of the T-5 lights and electronic ballasts.
9
Harry West Gymnasium Daylighting Retrofit The installation of 20 skylights was completed in April 2009.
10
Harry West Gymnasium Retrofit Energy Savings
11
Harry West Gymnasium Lighting Levels Pre-existing lighting conditions using 400-watt High Intensity Discharge (HID) fixtures
12
Harry West Gymnasium Lighting Levels Footcandle reading using daylight harvest fixtures only
13
Harry West Gymnasium Lighting Levels Footcandle reading after retrofit of 6L-T5 fixtures only
14
Harry West Gymnasium Lighting Levels How do they compare? Pre-existing levels
Daylight Harvest
Retrofit of T5 fixtures
15
Harry West Gymnasium Cost of Implementation
16
Harry West Gymnasium Projected Cost Savings Annually
17
Harry West Gymnasium CO2 Savings Estimated 261,427 lbs. of CO2 reduced annually That’s the equivalent of removing 22 cars from San Diego roads every year, or about 440 cars over the 20-year life-cycle of each daylight harvesting fixture
18
Copyright Materials