SOLUTION
1
CONTROL TRIM OPTION OVERVIEW 54-60 46th Street, Maspeth NY 11378
800.622.LOCK
local: 718.392.9000
fax: 718.392.8944
www.securitech.com
Securitech Control Trim meets today’s system integration needs.
INTERIOR
EXTERIOR
EGRESS FUNCTION
KEY FUNCTION
Free Egress At All Times (Fail-Safe Exiting)
Single Entry Classroom Function Key Usage Switch ELECTRIC TYPE & FUNCTION 24vDC Fail-Secure
Lock Body Switch Options
24vDC Fail-Safe
Latch Position Switch
24vAC Fail-Secure
Door Position Switch
Mechanical Fail-Secure
LEVER ACTIVATED SWITCH
LEVER ACTIVATED SWITCH
No Switch
No Switch
Electromagnetic Release Switch
Electromagnetic Release Switch
Request-To-Exit (R-T-E) Switch
Lever Position Switch
LEVER TYPE Vandal-Resistant Slip-Clutch Lever
Classroom: Lever remains unlocked until relocked by key.
Fail-Secure Lever remains locked with loss of power. (DC Release, AC Release, Mechanical) Fail-Safe For re-entry applications; lever unlocks with loss of power. (Re-Entry)
Power Options
Single Use - Store Room: Lever relocks when key is removed. (Standard)
Electric Release
Key Function
Exterior Operation Options 24vDC Used for Fail-Secure or Fail-Safe. 24vAC(30VA) Used when “Buzzing” sound is required. Fail-Secure only. Mechanical Only Use Storeroom or Classroom Function
E1.0
Key Usage Switch Indicates key is used to bypass access control systems
Lock Body
Request-To-Exit Moving lever sends signal for exiting; Eliminates need for R-E-X or P-I-R switches
Exterior
Interior
Signaling Options Latch Position Switch Indicates that latch is fully extended Door Position Switch Indicates that the door is in the frame
General Solutions Binder 2012 V9.2
SOLUTION
1
FUNCTION CHART 54-60 46th Street, Maspeth NY 11378 800.622.LOCK local: 718.392.9000 fax: 718.392.8944 Use this Function Chart in reference to LEXI, ELECTRA and ACCED electric lock models.
24vDC Electric Release
24R
24A
ON OFF
24R
24R
24R
24R
24R
24D
24D
24D
24D
24D
24D
24D
24D
24vDC Electric Release
24vDC Re-Entry Function
24R
24vDC Re-Entry Function
24vAC “Buzzing” Release
24A
24vAC “Buzzing” Release
Key Usage Switch
Key Usage Switch
Latch Position Switch
Latch Position Switch
ON OFF
Key On/Off Switch
CF
CF
Classroom Function
ON OFF
ON OFF
Key On/Off Switch Single Entry
Single Entry
AC “Buzz”
Fail-Secure
Fail-Safe
Fail-Safe
Entry By Key 24vDC Electric Release
24R
24A
24vDC Electric Release
24vDC Re-Entry Function
24R
24vDC Re-Entry Function
24vAC “Buzzing” Release
24A
24vAC “Buzzing” Release
24D
24D
24D
24D
24D
24D
24D
Key Usage Switch
Key Usage Switch
Latch Position Switch
Latch Position Switch
ON OFF
Classroom Function Key On/Off Switch
24A
24A
Entry By Key 24D
24D
Request-To-Exit Signal CF
A2 1
DESCRIPTIONS
Fail-Secure
A1 1
7
FUNCTIONS
D4
1 D4
7 D2
6 D2
5 D2
4 D2
3 D2
D2
FUNCTIONS
1
DC Release With Request-To-Exit
24D
24R
Request-To-Exit Signal CF
Classroom Function
DESCRIPTIONS
R2 7
24R
Entry By Key 24D
Request-To-Exit Signal CF
R2 4
24D
R2 3
Fail-Safe
Entry By Key
R2 1
Fail-Secure
Fail-Safe
R1 7
Fail-Secure
R1 3
DESCRIPTIONS
R1 1
7
FUNCTIONS
D3
1
Re-Entry
D3
7
6
D1
D1
D1
5
4 D1
3 D1
DESCRIPTIONS
D1
FUNCTIONS
1
DC Release
www.securitech.com
Request-To-Exit Signal CF ON OFF
ON OFF
Single Entry
CF
CF ON OFF
Classroom Function Key On/Off Switch Single Entry
Door Handing
How to determine the swing of the door The door handing is determined by looking at the door from the exterior (key) side of the door. Look at the hinges and determine if the door swings in to the room or out of the room.
Key/Lock Side of the door
E1.1 General Solutions Binder 2012 V9.2
SOLUTION
1
ELECTRICAL WIRING DATA 54-60 46th Street, Maspeth NY 11378
800.622.LOCK
fax: 718.392.8944
www.securitech.com
These recommended, minimum wire sizes are for reference only. Verify compliance with the local codes before installation.
EXAMPLE: 24vDC POWER SUPPLY 82 Ft.
JUNCTION BOX
local: 718.392.9000
54 Ft.
The charts are base of the following criteria:
FIRE-ALARM PANEL
Current The amount of current from the power supply to the control switches, contacts and the electrical product.
26 Ft.
CONTROL TRIM
In the example above, 4 items are being connected: a 24vDC power supply; a junction box; a fire-alarm panel, for emergency release of the door in case of fire; and a control trim.
Distance The distance, in feet, that the current travels from the power supply to the control switches, contacts and the electrical product.
First, determine the distance between each of the items: The 24vDC power supply is connected to the junction box. The distance is 82 feet.
Wire Size Minimum size required for controlling the electrical product. Larger sizes can be used to meet code.
The junction box is connected to the fire-alarm panel and the control trim. The distance between the junction box and firealarm is 54 feet. The distance between the junction box and the control trim is 26 feet.
Wire Length Length of wire in one direction.
Next add the distances (82, 54, 26) together. The total distance is 162 feet.
Solenoid Providing sufficient voltage to the solenoid of one product. If more products are used, the distance should be multiplied by the number of products used. Our electric release solenoid has a low current draw allowing easy access control system integration without requiring special power supplies.
Refer to the chart for 24vDC. Locate the nearest distance (250 feet). The recommended wire size is 18 AWG. NOTE: For more wiring information, please contact Securitech for assistance
DISTANCE (in feet) VOLTAGE
25
50
100
150
250
500
750
1000
24vAC (30VA)
18 AWG
18 AWG
18 AWG
18 AWG
16 AWG
14 AWG
12 AWG
10 AWG
24vDC
18 AWG
18 AWG
18 AWG
18 AWG
18 AWG
18 AWG
16 AWG
14 AWG
TRANSFORMER Solenoid
E1.2
Resistance
Draw
AC
5 OHMS
2 AMPS
DC
90 OHMS
.003 AMPS
General Solutions Binder 2012 V9.2