Cables for BUILDING INFRASTRUCTURE SYSTEMS
Edition 1 2015
www.btcables.com
CONTENTS CABLE FINDER BT CABLES – BELDEN EQUIVALENTS SECTION 1
BT BMS-TECTM - Paired Cables
SECTION 2
BT BMS-TECTM - Multi-Conductor Cables
SECTION 3
BT FIREPRO-TEC™ – Fire Detection and Alarm System Cables
SECTION 4
BT FIREPRO-TEC™ – Fire Resistant Cables
SECTION 5
BT Security-Tec ™– Coaxial Cables
SECTION 6
BT Data-Tec™ - Category LAN Cables
SECTION 7
BT Industrial-Tec™ - DEF Standard Cables
SECTION 8
BT Industrial-Tec™ - Industrial Cables
SECTION 9
BT Industrial-Tec™ – Control Cables
GENERALTECHNICAL INFORMATION COMPARISON BETWEEN EUROPEAN AND UNITED STATES CABLE DESIGN BASICS CONVERSIONS GLOSSARY BT CABLES PART NUMBER INDEX
info.btcables@bt.com
2
TM
BT BMS-TEC Application
RS-485 RS-422 G.P. Bus RS-232 Lon Works
Cable Finder - Paired Cables
Cond.Size ↓ 24 AWG 24 AWG 22 AWG 22AWG 24 AWG 22 AWG 22 AWG 24 AWG 0.64 mm 0.64 mm
KNX
0.8 mm 0.8 mm
Security & Alarm
18 AWG
BMS
0.6 mm²
Application
G.P Bus
No. of pairs ↓ 1 1 1 1
No. of pairs → Screen Sheath
Foil+ braid every pair a foil Foil no scrn every pair a foil Foil Foil Foil + Braid Foil
1
2
3
4
PVC HFFR PVC HFFR PVC PVC HFFR PVC HFFR
C1189 C1318 C1080 C1401
C1191 C1320 C1296 C1403 C1383 C1197 C1282 C1183
C1192 C1321 C1297 C1404 C1384 C1298
C1299
C1181 C1346
C1190 C1319 C1295 C1402 C1382 C1196 C1281 C1182 C1347
C1184
C1185
HFFR
C1348
C1349
1.5
PVC HFFR HFFR
C1219 C1220 C1171
C1217 C1218 C1172
C1173
C1174
C1175
C1176
1.4 1.4 1.8
HFFR
C1418
C1419
C1420
C1421
C1422
C1423
1.8
PVC
C1381
AWG conductor size → Screen ↓ Sheath ↓ Yes PVC Yes HFFR No PVC No HFFR
5
6
7
C1386 C1214 C1314 C1186
C1187
8
Page
§
C1188
1.1 1.1 1.1 1.1 1.2 1.6 1.6 1.3 1.5
1.9
22
20
18
16
14
12
Section
C1199 C1310 C1301 C1311
C1195 C1308 C1300 C1309
C1193 C1272 C1203 C1271
C1213 C1270 C1198 C1307
C1224 C1305 C1222 C1306
C1313 C1303 C1302 C1304
1.7 1.7 1.7 1.7
Page
BT BMS-TECTM - Multi-Conductor Cables Cond. Size AWG↓ 22
20
18
16
14
12
No. of conductors 3
No. of conductors → Sheath ↓ Screen Yes PVC No Yes HFFR No Yes PVC No Yes HFFR No Yes PVC No Yes HFFR No UV-HFFR Yes Yes PVC No Yes HFFR No UV-HFFR Yes Yes PVC No Yes HFFR No Yes PVC No Yes HFFR No Conductor size → Sheath ↓ Screen PVC Yes
2
3
4
6
8
Section
C1226 C1227 C1741 C1742 C1019 C1020 C1731 C1732 C1013 C1014 C1721 C1722 C1351 C1007 C1008 C1711 C1712 C1391 C1001 C1002 C1701 C1702 C1322 C1323 C1334 C1335
C1228 C1278 C1743 C1744 C1021 C1022 C1733 C1734 C1015 C1016 C1723 C1724 C1352 C1009 C1010 C1713 C1714 C1392 C1003 C1004 C1703 C1704 C1324 C1325 C1336 C1337
C1230 C1231 C1745 C1746 C1023 C1024 C1735 C1736 C1017 C1018 C1725 C1726 C1353 C1011 C1012 C1715 C1716 C1393 C1005 C1006 C1705 C1706 C1326 C1327 C1338 C1339
C1264 C1265 C1747 C1748 C1260 C1261 C1737 C1738 C1211 C1212 C1727 C1728 C1354 C1252 C1253 C1717 C1718 C1394 C1248 C1249 C1707 C1708 C1330 C1331 C1342 C1343
C1232 C1233 C1749 C1750 C1262 C1263 C1739 C1740 C1258 C1259 C1729 C1730 C1355 C1254 C1255 C1719 C1720 C1395 C1250 C1251 C1709 C1710 C1332 C1333 C1344 C1345
2.1 2.1 2.2 2.2 2.1 2.1 2.2 2.2 2.1 2.1 2.2 2.2 2.3 2.1 2.1 2.2 2.2 2.3 2.1 2.1 2.2 2.2 2.1 2.1 2.2 2.2
22 AWG
20 AWG
18 AWG
Section
C1215
C1245
C1225
?
Page
Page
Multi-Conductor Power Limited Tray Cables (PLTC) are available on request
info.btcables@bt.com
3
BT FIREPRO-TEC™ – Fire Detection and Alarm System Cables Cond. size → Screen ↓ Sheath ↓ Yes PVC No PVC
No. of pairs ↓ 1 1
Application
Fire Alarm
AWG 18 C1040 C1135
AWG 16 C1041 C1136
AWG 14 C1042 C1137
AWG 12 C1043 C1138
Section
Page
3 3
BT FIREPRO-TEC™ – Fire Resistant Cables Application
Circuit integrity
No. of cores ↓ 1 2 2 3 3
Cond. size → Screen ↓ Sheath ↓ No HFFR Yes HFFR No HFFR Yes HFFR No HFFR
0.75 mm2
1.0 mm2
C1284 C1139 C1159 C1149
C1283 C1140 C1160 C1150
1.5 mm2 C1760 C1044 C1141 C1161 1151
2.5 mm2 C1761 C1045 C1142 C1162 C1152
4.0 mm2
Section
Page
4 4 4 4 4
C1289 C1143 C1163 C1153
BT Security-Tec ™– Coaxial Cables Application CCTV SMATV CATV HDTV
Inner Conductor Solid BC Solid BC Flex BC CCS CCS Solid BC Solid BC
Screen
Sheath
RG-59
RG-6
RG-11
Section
Braid BC Braid BC Braid BC Foil+Alu Braid Quad screen Foil+TC Braid Foil+TC Braid
PVC HFFR PVC PVC PVC PVC HFFR
C1028 C1428 C1275 C1025 C1256 C1229 C1378
C1029 C1429 C1276 C1026 C1257 C1279 C1379
C1030 C1430 C1277 C1027 C1241 C1280 C1380
5.1 5.1 5.1 5.2 5.2 5.3 5.3
Page
50 Ohm Coaxial cables are available on request
BT Data-Tec™ - Category LAN Cables Cat. type Cat 3
Sheath PVC
Cat. types
Sheath PVC HFFR PVC HFFR PVC HFFR PVC HFFR PVC HFFR HFFR HFFR
Cat 5e Cat 5epatch Cat 6 Cat 6-patch Cat 6a Cat 7 Cat 7a
2 pairs C1031 UTP C1035 C1235 C1500 C1510 C1037 C1237 C1540 C1550 C1055 C1200
6 prs C1266
12 prs C1267
UTP-UL C1285
C1287
25 prs C1032 FTP C1036 C1236 C1520 C1530 C1038 C1238 C1560 C1570 C1056 C1052
50 prs C1033 FTP-UL C1286
100 prs C1034
150 prs C1268
U-FTP
200 prs C1269 S-FTP
C1288
C1057 C1053 C1039 C1201
info.btcables@bt.com
section 6.4
Page
Section 6.1 6.1 6.3 6.3 6.1 6.1 6.3 6.3 6.2 6.2 6.2 6.2
Page
4
BT Industrial-Tec™ - DEF Standard Cables Conductor No. of cores Screened Unscreened Conductor No. of cores Screened Unscreened Conductor No. of cores Screened Unscreened
2 C1164 C1360
3 C1165 C1361
2
3
C1366
C1367
4
6
C1362
C1144
4 C1171 C1368
2
3
C1158
C1370
7 x 0.1 mm = 0.055 mm² 9 15 25 C1166 C1168 C1147 C1145 C1146
6 C1172 C1369
4 C1177 C1371
7 x 0.2mm = 0.22 mm² 8 12 C1173 C1174 C1154 C1155
36 C1169 C1148
20 C1175 C1156
16 x 0.2mm = 0.5 mm² 6 12 C1178 C1375 C1372 C1373
50 C1365 C1364
section 7 7
Page
36 C1176 C1157
section 7 7
Page
section 7 7
Page
18 C1180 C1374
BT Industrial-Tec™ - Industrial Cables BS(PAS) 5308 – Part 2 – Type 1 – Collectively Screened – Unarmoured cables No. of pairs 1 2 5 10 20 Conductor 0.5 mm² (16x0.2 mm) C1081 C1082 C1083 C1084 C1085 Conductor 0.75 mm² (24x0.2 mm) C1086 C1087 C1088 C1089 C1090 Conductor 1.5 mm² (7x0.53 mm) C1091 C1092 C1093 C1094 C1095
section 8 8 8
Page
BS(PAS) 5308 – Part 2 – Type 1 – Collectively Screened – Armoured cables No. of pairs 1 2 5 10 20 Conductor 0.5 mm² (16x0.2 mm) C1097 C1098 C1099 C1100 C1096 Conductor 0.75 mm² (24x0.2 mm) C1101 C1102 C1103 C1104 C1105 Conductor 1.5 mm² (7x0.53 mm) C1106 C1107 C1108 C1109 C1110
section 8 8 8
Page
BS(PAS) 5308 – Part 2 – Type 1 – Individually & Collectively Screened – Unarmoured cables No. of pairs 2 5 10 20 Conductor 0.5 mm² (16x0.2 mm) C1111 C1112 C1113 C1114 Conductor 0.75 mm² (24x0.2 mm) C1115 C1116 C1117 C1118 Conductor 1.5 mm² (7x0.53 mm) C1119 C1120 C1121 C1122
section 8 8 8
Page
BS(PAS) 5308 – Part 2 – Type 1 – Individually & Collectively Screened – Armoured cable No. of pairs 2 5 10 20 Conductor 0.5 mm² (16x0.2 mm) C1123 C1124 C1125 C1126 Conductor 0.75 mm² (24x0.2 mm) C1127 C1128 C1129 C1130 Conductor 1.5 mm² (7x0.53 mm) C1131 C1132 C1133 C1134
section 8 8 8
Page
info.btcables@bt.com
5
BT Industrial-Tec™ - Control Cables No. of cores Conductor 0.75 mm² (24x0.2 mm) Conductor 1.0 mm² (32x0.2 mm) Conductor 1.5 mm² (30x0.24 mm) Conductor 2.5 mm² (50x0.24 mm)
3 C1631 C1632 C1633 C1634
YY Series (N stranded cores surrounded by a PVC sheath) 5 7 8 12 18 section C1645 C1648 9 9 C1639 C1641 C1643 C1646 C649 9 C1640 C1642 C1644 C1647 C1650 9
CY Series (N stranded cores surrounded by a braiding plus a PVC sheath) 3 4 5 section C1620 C1624 9 C1621 C1625 9 C1622 C1626 C1628 9 C1623 C1627 C1629 9
No. of cores Conductor 0.75 mm² (24x0.2 mm) Conductor 1.0 mm² (32x0.2 mm) Conductor 1.5 mm² (30x0.24 mm) Conductor 2.5 mm² (50x0.24 mm)
No. of cores Conductor 0.75 mm² (24x0.2 mm) Conductor 1.0 mm² (32x0.2 mm) No. of cores Conductor 1.5 mm² (30x0.24 mm) Conductor 2.5 mm² (50x0.24 mm) Conductor 4.0 mm² (56x0.29 mm) Conductor 6.0 mm² (84x0.29 mm)
4 C1635 C1636 C1637 C1638
Page
Page
SY Series (N stranded cores surrounded by Steel Wire Armouring plus a PVC sheath) 3 4 5 7 12 18 25 section Page C1655 9 C1651 C1656 C1660 C1665 C1669 C1671 C1673 C1675 9 2 3 4 5 6 7 12 18 C1652 C1657 C1661 C1666 C1668 C1670 C1672 C1674 9 C1658 C1662 9 C1659 C1663 9 C1664 9 2
info.btcables@bt.com
6
BT Cables - Belden equivalents
Belden P/N BT Cables P/N 1030A 1043A 1044A 1064A 1067A 1467A 1505A 1523A 1583A 1617A 1633E 1694A 1885ENH 3079E 3105A 3107A 3108A 3109A 4000FE 4000UE 4001UE 4100FE 4100UE 4101UE 4102UE 4200FE 4200UE 4201FE 4201UE 4202FE 4202UE 4300FE 4300UE 4301FE 4301UE 4302FE 4302UE 4304FE 4304UE 4306FE 4306UE 4400FE 4400UE 4401FE 4402FE 4402UE 4500FE 4500UE 4501FE 4501UE 4502FE 4502UE 4504FE 4504UE 4506FE 4506UE 5100FE 5100UE 5101FE 5101UE 5102FE 5102UE 5200FE 5200UE 5201FE 5201UE 5202FE 5202UE 5300FE 5300UE 5301FE 5301UE 5302FE 5302UE 5305FE 5400FE 5400UE 5401FE 5401UE 5402FE 5402UE 7731A 7860E 7965E 8205 8205NH 8259 8442 8442NH 8471 8471NH 8473 8473NH
C1223 C1078 C1077 C1076 C1074 C1075 C1229 C1027 C1035 C1241 C1036 C1279 C1039 C1315 C1080 C1295 C1296 C1297 C1334 C1335 C1337 C1701 C1702 C1704 C1706 C1711 C1712 C1713 C1714 C1715 C1716 C1721 C1722 C1723 C1724 C1725 C1726 C1727 C1728 C1729 C1730 C1731 C1732 C1733 C1735 C1736 C1741 C1742 C1743 C1744 C1745 C1746 C1747 C1748 C1749 C1750 C1001 C1002 C1003 C1004 C1005 C1006 C1007 C1008 C1009 C1010 C1011 C1012 C1013 C1014 C1015 C1016 C1017 C1018 C1239 C1019 C1020 C1021 C1022 C1023 C1024 C1280 C1038 C1037 C1300 C1415 C1046 C1301 C1416 C1198 C1307 C1222 C1306
Conductor Size 16(7*24) AWG 16 (7*24) AWG 16 (7*24) AWG 18 (7*26) AWG 18 (7*26) AWG 18 (7*26) AWG 20 AWG 14 AWG 24 AWG 14 AWG 24 AWG 18 AWG 23 AWG 22 (7*30) AWG 22 (7*30) AWG 22 (7*30) AWG 22 (7*30) AWG 22 (7*30) AWG 12 (19*25) AWG 12 (19*25) AWG 12 (19*25) AWG 14 (19*27) AWG 14 (19*27) AWG 14 (19*27) AWG 14 (19*27) AWG 16 (19*29) AWG 16 (19*29) AWG 16 (19*29) AWG 16 (19*29) AWG 16 (19*29) AWG 16 (19*29) AWG 18 (7*26) AWG 18 (7*26) AWG 18 (7*26) AWG 18 (7*26) AWG 18 (7*26) AWG 18 (7*26) AWG 18 (7*26) AWG 18 (7*26) AWG 18 (7*26) AWG 18 (7*26) AWG 20 (7*28) AWG 20 (7*28) AWG 20 (7*28) AWG 20 (7*28) AWG 20 (7*28) AWG 22 (7*30) AWG 22 (7*30) AWG 22 (7*30) AWG 22 (7*30) AWG 22 (7*30) AWG 22 (7*30) AWG 22 (7*30) AWG 22 (7*30) AWG 22 (7*30) AWG 22 (7*30) AWG 14 (19*27) AWG 14 (19*27) AWG 14 (19*27) AWG 14 (19*27) AWG 14 (19*27) AWG 14 (19*27) AWG 16 (19*29) AWG 16 (19*29) AWG 16 (19*29) AWG 16 (19*29) AWG 16 (19*29) AWG 16 (19*29) AWG 18 (7*26) AWG 18 (7*26) AWG 18 (7*26) AWG 18 (7*26) AWG 18 (7*26) AWG 18 (7*26) AWG 18 (7*26) AWG 20 (7*28) AWG 20 (7*28) AWG 20 (7*28) AWG 20 (7*28) AWG 20 (7*28) AWG 20 (7*28) AWG 14 AWG 23 AWG 23 AWG 20 (7*28) AWG 20 (7*28) AWG 20 (10*33) AWG 22 (7*30) AWG 22 (7*30) AWG 16 (19*29) AWG 16 (19*29) AWG 14 (19*27) AWG 14 (19*27) AWG
No. of Conductors
No. of Pairs 1 16 20 4 16 8
1 1
Individually Collective shielded shield pairs Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes
Jacket PVC PVC PVC PVC PVC PVC PVC PVC
4 1 4 1 4 1 2 2 3 4 2 2 3 2 3 3 4 2 2 3 3 4 4 2 2 3 3 4 4 6 6 8 8 2 2 3 4 4 2 2 3 3 4 4 6 6 8 8 2 2 3 3 4 4 2 2 3 3 4 4 2 2 3 3 4 4 7 2 2 3 3 4 4 1
Yes
Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes
Yes Yes Yes
4 4 1 1 1
Yes Yes
Yes 1 1 1 1
2 2
Yes
Yes yes Yes Yes Yes Yes Yes Yes Yes Yes
PVC PVC PVC PVC PVC PVC PVC PVC PVC HFFR HFFR HFFR HFFR HFFR HFFR HFFR HFFR HFFR HFFR HFFR HFFR HFFR HFFR HFFR HFFR HFFR HFFR HFFR HFFR HFFR HFFR HFFR HFFR HFFR HFFR HFFR HFFR HFFR HFFR HFFR HFFR HFFR HFFR HFFR HFFR HFFR HFFR PVC PVC PVC PVC PVC PVC PVC PVC PVC PVC PVC PVC PVC PVC PVC PVC PVC PVC PVC PVC PVC PVC PVC PVC PVC PVC
PVC HFFR PVC PVC HFFR PVC HFFR PVC HFFR
BT Cables Brand and Additional Data 300V PL Tray Cable 600V Tray Cable 600V Tray Cable 600V Tray Cable 600V Tray Cable 300V PL Tray Cable RG-59 Coaxial Cable (BC) RG11 Coaxial Cable (CCS) CAT 5E UTP Cable RG-11 Quad Shield Coaxial Cable (CCS) CAT 5E FTP Cable RG-6 Coaxial Cable (BC) CAT 7 ISTP Cable Profibus DP RS-485 Computer Cable RS-485 Low Cap Computer Cable RS-485 Computer Cable RS-485 Computer Cable BMS-HFFR cables BMS-HFFR cables BMS-HFFR cables BMS-HFFR cables BMS-HFFR cables BMS-HFFR cables BMS-HFFR cables BMS-HFFR cables BMS-HFFR cables BMS-HFFR cables BMS-HFFR cables BMS-HFFR cables BMS-HFFR cables BMS-HFFR cables BMS-HFFR cables BMS-HFFR cables BMS-HFFR cables BMS-HFFR cables BMS-HFFR cables BMS-HFFR cables BMS-HFFR cables BMS-HFFR cables BMS-HFFR cables BMS-HFFR cables BMS-HFFR cables BMS-HFFR cables BMS-HFFR cables BMS-HFFR cables BMS-HFFR cables BMS-HFFR cables BMS-HFFR cables BMS-HFFR cables BMS-HFFR cables BMS-HFFR cables BMS-HFFR cables BMS-HFFR cables BMS-HFFR cables BMS-HFFR cables BMS-PVC cables BMS-PVC cables BMS-PVC cables BMS-PVC cables BMS-PVC cables BMS-PVC cables BMS-PVC cables BMS-PVC cables BMS-PVC cables BMS-PVC cables BMS-PVC cables BMS-PVC cables BMS-PVC cables BMS-PVC cables BMS-PVC cables BMS-PVC cables BMS-PVC cables BMS-PVC cables BMS-PVC cables BMS-PVC cables BMS-PVC cables BMS-PVC cables BMS-PVC cables BMS-PVC cables BMS-PVC cables RG-11 Coaxial Cable (BC) CAT6 FTP Cable CAT 6 UTP Cable High Conductivity Speaker and BMS-PVC-TC Cable High Conductivity Speaker and BMS-PVC-TC Cable RG-58 Coaxial Cable High Conductivity Speaker and BMS-PVC-TC Cable BMS-HFFR cables High Conductivity Speaker and BMS-PVC-TC Cable BMS-HFFR cables High Conductivity Speaker and BMS-PVC-TC Cable BMS-HFFR cables
info.btcables@bt.com
7
BT Cables - Belden equivalents
Belden P/N BT Cables P/N 8477 8477NH 8718NH 8719 8719NH 8720 8720NH 8723 8723NH 8723PE 8760 8760NH 8761 8761NH 8762 8762NH 8770 8772 8777 8777NH 8777PE 8778 8778NH 9100 9116 9259 9463F 9501 9501NH 9501PE 9502 9502NH 9502PE 9503 9503NH 9503PE 9504 9504NH 9504PE 9505 9505NH 9505PE 9506 9506NH 9506PE 9507 9507NH 9507PE 9508 9508NH 9508PE 9510NH 9510NH 9536 NH 9536 9538 9538NH 9540 9571 9572 9574 9575 9580 9581 9582 9583 9728 9729 9730 9740 9740NH 9773 9774 9841 9841NH 9841PE 9842 9842NH 9843 9843NH 9844 9844NH 9913 1227A1 1232A1 43051 43113 513945 533945 543945 9842NH 9842PE 9843NH
C1302 C1417 C1303 C1213 C1270 C1224 C1305 C1196 C1281 C1316 C1193 C1272 C1199 C1310 C1195 C1308 C1225 C1245 C1197 C1282 C1317 C1214 C1314 C1025 C1026 C1275 C1079 C1181 C1441 C1451 C1182 C1442 C1452 C1183 C1443 C1453 C1184 C1444 C1454 C1185 C1445 C1455 C1186 C1446 C1456 C1187 C1447 C1457 C1188 C1448 C1458 C1206 C1449 C1358 C1398 C1399 C1359 C1400 C1135 C1136 C1040 C1041 C1137 C1042 C1138 C1043 C1384 C1382 C1383 C1203 C1271 C1298 C1299 C1189 C1318 C1409 C1190 C1319 C1191 C1320 C1192 C1321 C1047 C1031 C1032 C1208 C1207 C1030 C1029 C1028 C1319 C1410 C1320
Conductor Size 12 (19*25) AWG 12 (19*25) AWG 12 (19*25) AWG 16 (19*29) AWG 16 (19*29) AWG 14 (19*27) AWG 14 (19*27) AWG 22 (7*30) AWG 22 (7*30) AWG 22 (7*30) AWG 18 (7*26) AWG 18 (7*26) AWG 22 (7*30) AWG 22 (7*30) AWG 20 (7*28) AWG 20 (7*28) AWG 18 (7*26) AWG 20 (7*28) AWG 22 (7*30) AWG 22 (7*30) AWG 22 (7*30) AWG 22 (7*30) AWG 22 (7*30) AWG 20 AWG 18 AWG 20 (19*33) 20 (42*36) AWG 24 (7*32) AWG 24 (7*32) AWG 24 (7*32) AWG 24 (7*32) AWG 24 (7*32) AWG 24 (7*32) AWG 24 (7*32) AWG 24 (7*32) AWG 24 (7*32) AWG 24 (7*32) AWG 24 (7*32) AWG 24 (7*32) AWG 24 (7*32) AWG 24 (7*32) AWG 24 (7*32) AWG 24 (7*32) AWG 24 (7*32) AWG 24 (7*32) AWG 24 (7*32) AWG 24 (7*32) AWG 24 (7*32) AWG 24 (7*32) AWG 24 (7*32) AWG 24 (7*32) AWG 24 (7*32) AWG 24 (7*32) AWG 24 (7*32) AWG 24 (7*32) AWG 24 (7*32) AWG 24 (7*32) AWG 24 (7*32) AWG 18 AWG 16 AWG 18 AWG 16 AWG 14 AWG 14 AWG 12 AWG 12 AWG 24 (7*32) AWG 24 (7*32) AWG 24 (7*32) AWG 18 (7*26) AWG 18 (7*26) AWG 22 (7*30) AWG 22 (7*30) AWG 24 (7*32) AWG 24 (7*32) AWG 24 (7*32) AWG 24 (7*32) AWG 24 (7*32) AWG 24 (7*32) AWG 24 (7*32) AWG 24 (7*32) AWG 24 (7*32) AWG 10 AWG 24 AWG 24 AWG 0.4 mm 26 AWG 14 AWG 18 AWG 20 AWG 24 (7*32) AWG 24 (7*32) AWG 24 (7*32) AWG
No. of Conductors
No. of Pairs
Individually Collective shielded shield pairs
1 1 1
Yes Yes
2 2 2 2
Yes Yes 2 2 2 1 1 1 1 1 1
Yes Yes Yes
3 3 3 6 6
Yes Yes Yes Yes Yes
Yes Yes Yes Yes Yes Yes Yes Yes
3 3
1 1 1
Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes
1 1 1 1 2 2 2 3 3 3 4 4 4 5 5 5 6 6 6 7 7 7 8 8 8 10 10 6 6 8 8 10 1 1 2 2
Yes Yes 1
2
Yes 1
2
Yes 4 2 1 1 1 4 5 1 1 1 2 2 3 3 4 4
1
Yes Yes Yes
Yes Yes
Yes 2 25 8
1 1 1 1 2 2 3
Yes Yes Yes Yes Yes Yes Yes Yes
Jacket PVC HFFR HFFR PVC HFFR PVC HFFR PVC HFFR PE PVC HFFR PVC HFFR PVC HFFR PVC PVC PVC HFFR PE PVC HFFR PVC PVC PVC PVC PVC HFFR PE PVC HFFR PE PVC HFFR PE PVC HFFR PE PVC HFFR PE PVC HFFR PE PVC HFFR PE PVC HFFR PE PVC HFFR HFFR PVC PVC HFFR PVC PVC PVC PVC PVC PVC PVC PVC PVC PVC PVC PVC PVC HFFR PVC PVC PVC HFFR PE PVC HFFR PVC HFFR PVC HFFR PVC PVC PVC PVC HFFR PVC PVC PVC HFFR PE HFFR
BT Cables Brand and Additional Data High Conductivity Speaker and BMS-PVC-TC Cable BMS-HFFR cables BMS-HFFR cables High Conductivity Speaker and BMS-PVC-TC Cable BMS-HFFR cables High Conductivity Speaker and BMS-PVC-TC Cable BMS-HFFR cables Individually Shielded TP BMS-PVC-TC Cable Individually Shielded TP BMS-HFFR-TC Cable Individually Shielded TP BMS-PE-TC Cable High Conductivity Speaker and BMS-PVC-TC Cable BMS-HFFR cables High Conductivity Speaker and BMS-PVC-TC Cable BMS-HFFR cables High Conductivity Speaker and BMS-PVC-TC Cable BMS-HFFR cables High Conductivity Speaker and BMS-PVC-TC Cable High Conductivity Speaker and BMS-PVC-TC Cable Individually Shielded TP BMS-PVC-TC Cable Individually Shielded TP BMS-HFFR-TC Cable Individually Shielded TP BMS-PE-TC Cable Individually Shielded TP BMS-PVC-TC Cable Individually Shielded TP BMS-HFFR-TC Cable RG-59 Coaxial Cable (CCS) RG-6 Coaxial Cable (CCS) RG-59 Coaxial CCTV cable Twinax - Blue Hose cable RS-232 Computer Cable RS-232 Computer Cable RS-232 Computer Cable RS-232 Computer Cable RS-232 Computer Cable RS-232 Computer Cable RS-232 Computer Cable RS-232 Computer Cable RS-232 Computer Cable RS-232 Computer Cable RS-232 Computer Cable RS-232 Computer Cable RS-232 Computer Cable RS-232 Computer Cable RS-232 Computer Cable RS-232 Computer Cable RS-232 Computer Cable RS-232 Computer Cable RS-232 Computer Cable RS-232 Computer Cable RS-232 Computer Cable RS-232 Computer Cable RS-232 Computer Cable RS-232 Computer Cable RS-232 Computer Cable RS-232 Computer Cable RS-232 Computer Cable RS-232 Computer Cable RS-232 Computer Cable RS-232 Computer Cable RS-232 Computer Cable Fire Detection and Alarm System Cable, FPLR rated 105°C, UL listed Fire Detection and Alarm System Cable, FPLR rated 105°C, UL listed Fire Detection and Alarm System Cable, FPLR rated 105°C, UL listed Fire Detection and Alarm System Cable, FPLR rated 105°C, UL listed Fire Detection and Alarm System Cable, FPLR rated 105°C, UL listed Fire Detection and Alarm System Cable, FPLR rated 105°C, UL listed Fire Detection and Alarm System Cable, FPLR rated 105°C, UL listed Fire Detection and Alarm System Cable, FPLR rated 105°C, UL listed Low Cap Computer Cable Low Cap Computer Cable Low Cap Computer Cable High Conductivity Speaker and BMS-PVC-TC Cable BMS-HFFR cables Individually Shielded TP BMS-PVC-TC Cable Individually Shielded TP BMS-PVC-TC Cable RS-485 Low Cap Computer Cable RS-485 Low Cap Computer Cable RS-485 Low Cap Computer Cable RS-485 Low Cap Computer Cable RS-485 Low Cap Computer Cable RS-485 Low Cap Computer Cable RS-485 Low Cap Computer Cable RS-485 Low Cap Computer Cable RS-485 Low Cap Computer Cable RG-8 Series Coaxial Cable CAT 3 UTP Cable CAT 3 UTP Cable 8 Pair/0.4 Braided Telecoms Cable TELCO 75 Ohm Coaxial Cable RG-11 Coaxial Cable (BC) RG6 Series Coaxial Cable (BC) RG-59 Coaxial Cable (BC) 2 Pair 24AWG RS485 Low Cap Computer Cable HFFR Jacket 2 Pair 24AWG RS485 Low Cap Computer Cable HFFR Jacket 3 Pair 24AWG RS485 Low Cap Computer Cable HFFR Jacket
info.btcables@bt.com
8
BT Cables - Belden equivalents
Belden P/N BT Cables P/N 9843PE 9844NH 9844PE MRG2130 MRG214 YE00819 YE00820 YE00905 YE00906
C1411 C1321 C1412 C1048 C1049 C1219 C1217 C1220 C1218
Conductor Size 24 (7*32) AWG 24 (7*32) AWG 24 (7*32) AWG 2.25 (7*0.75) mm 2.25 (7*0.75) mm 0.8 0.8 0.8 0.8
No. of Conductors
No. of Pairs 3 4 4
1 1 1 2 1 2
Individually Collective shielded shield pairs Yes Yes Yes Yes Yes Yes Yes Yes Yes
Jacket PE HFFR PE PVC PVC PVC PVC HFFR HFFR
BT Cables Brand and Additional Data 3 Pair 24AWG RS485 Low Cap Computer Cable HFFR Jacket 4 Pair 24AWG RS485 Low Cap Computer Cable HFFR Jacket 4 Pair 24AWG RS485 Low Cap Computer Cable HFFR Jacket RG213 Series Coaxial cable RG214 Series Coaxial Cable KNX (was EIB) CABLE KNX (was EIB) CABLE KNX (was EIB) CABLE KNX (was EIB) CABLE
info.btcables@bt.com
9
Section 1 - BT BMS-TECTM - Paired Cables or HFFR sheathed cables for BUS and Interface Systems PVC, PE
1. Application RS-232, RS-422, RS-485, KNX (EIB or Instabus), LonWorks, ModBus, M-Bus, CAN-bus, BACnet, BMS (Building Management Systems) or general interface systems. 2. Basic Construction of the cables Wire = conductor without or with insulation. With insulation sometimes also indicated as core. Conductor: may be solid = one single rod or flexible = twisted bare or tinned copper strands, ranging from 12 to 24AWG. Conductor (AWG) 24 22 20 18 16 14 12
Configuration (AWG) 7 x 32 7 x 30 7 x 28 7 x 26 19 x 29 19 x 27 19 x 25
Configuration (mm) 7 x 0.20 7 x 0.25 7 x 0.32 7 x 0.40 19 x 0.28 19 x 0.36 19 x 0.45
DC Resistance (Ohm/km) ≤ 88 ≤ 57.4 ≤ 32.16 ≤ 22.7 ≤ 15.47 ≤ 9.36 ≤ 5.61
Insulation: Polyethylene (PE) or Foam PE (FPE) for PVC (Polyvinyl Chloride) or Halogen-Free (HFFR) sheathed cables. And Halogen-Free (HFFR) for HFFR sheathed cables. All insulations are in accordance with BS EN 50290-2, good strippable and coloured. The colours are not interchangeable. Pair = two twisted – colour coded – wires. Individually screened pair (if applicable): one pair wrapped with an Aluminium/Polyester foil under which a drain wire. Cable core: two or more (individually screened) pairs stranded. Good twisting (lay-length < 30 ~ 40D) is necessary otherwise the cable can hardly be bending and will break after a few bends. Drain wire (only in combination with a screen): stranded tinned copper wires. In order to avoid corrosion, it is recommended that drain wires are tinned. Screen (if applicable): Helically applied (= as a spiral) Aluminium/Polyester (Alpet) foil. For the flexibility of a cable a helically applied foil is to be preferred. A longitudinally applied foil act more as a stiff tube = more difficult to bend. Braiding (if applicable): tinned copper wires. Sheath: grey PVC , black PE or purple HFFR, all in accordance with BS EN 50290-2. Cable Configuration Insulation Sheath PE, FPE or PVC
PVC
PE, FPE or PVC
PE
PE, FPE or HFFR
HFFR
Cable Retardancy according to IEC 60332-1 No according to IEC 60332-3-24
Low Smoke
Halogen-free (non acid, non toxic)
RoHS compliant
No
No
Yes
No according to IEC 61034-1-2
Only with (F)PE insulation according to IEC 60754-1 & 2
Yes Yes
Operating temperature range: -25 to +75 °C and Rated Voltage: 300 Vrms
info.btcables@bt.com
10
RS-232: Hand shake interface used for low data rates. Computer to printer or to modem or to another device. RS-422: Balanced digital circuit. Medium speed data exchange. Long line modems and Daisy chain configuration. RS-485: Balanced digital circuit. Medium speed fieldbus interfaces. RS-232
RS-422
RS-485
Differential Max. number of drivers Max. number of receivers Modes of operation Network topology Max. distance acc. to standard Max. speed at 12 m. Max. speed at 1200 m.
no 1 1 full duplex point-to-point 15 m 20 kbs 1 kbs
yes 1 10 half duplex multidrop 1200 m 10 Mbs 100 kbs
yes 1 32 half duplex multidrop 1200 m 35 Mbs 100 kbs
Conductor size Number of conductors Impedance BT Cables main part numbers see
mainly 24 AWG 6 to 25 not defined section 1.3
mainly 24 AWG 2 pairs or more 100 Ohm section 1.2
mainly 24 AWG 1 pair or more 120 Ohm section 1.1
Cables used
KNX is a standardised (EN 50090, ISO/IEC 14543), OSI-based network communications protocol for intelligent buildings. KNX is the successor to, and convergence of, three previous standards: the European Home Systems Protocol (EHS), BatiBUS, and the European Installation Bus (EIB or Instabus).
BT Cables main part numbers for KNX cables: C1217 (quad – PVC) – C1218 (quad – HFFR) – C1219 (1 pair – PVC) – C1220 (1 pair – HFFR).
LonWorks is a networking platform specifically created to address the needs of control applications. The platform is built on a protocol created by Echelon Corporation for networking devices over media such as twisted pair, power lines, fibre optics, and RF. It is used for the automation of various functions within buildings such as lighting and HVAC.
BT Cables main part numbers for LonWorks: C1198 (PVC) - C1203 (PVC) – C1307 (HFFR) – C1271 (HFFR) – C1346 (HFFR) – C1347 (HFFR) – C1348 (HFFR) and C1349 (HFFR).
Modbus is a serial communications protocol published by Modicon in 1979 for use with its programmable logic controllers (PLCs). Simple and robust, it has since become one of the de facto standard communications protocols in the industry.
BT Cables main part numbers for Modbus: C1197 (PVC) - C1193 (PVC) – C1282 (HFFR) – C1272 (HFFR).
M-Bus (Meter-Bus) is a European standard (EN 13757-2 physical and link layer, EN 13757-3 application layer) for the remote reading of gas or electricity meters. M-Bus is also usable for other types of consumption meters.
BT Cables main part number for M-bus: C1020 – C1193.
Controller–area network (CAN or CAN-bus) is a vehicle bus standard designed specifically for automotive applications but now also used in other areas such as industrial automation and medical equipment. CAN bus utilize TIA/EIA-485 cables.
BT Cables main part numbers for CAN-bus: C1080 - C1189 – C1190 – C1191 – C1192 – C1295 – C1296 – C1297 and HFFR cables C1318 – C1319 – C1320 – C1321.
BACnet is a communications protocol for building automation and control networks. It is was designed to allow communication of building automation and control systems for applications such as heating, ventilating, and air-conditioning control, lighting control, access control, and fire detection systems and their associated equipment. BACnet over IP can utilize Cat 6.
BT Cables main part numbers for BACnet: C1228 (PVC) – C1189 (PVC) – C1190 (PVC) - C1318 (HFFR) and C1319 (HFFR).
info.btcables@bt.com
11
Section 1.1 Paired Cables for TIA/EIA-485 = RS-485 applications 22 and 24AWG conductors – PE or FPE insulation – Dual Screen - PVC or HFFR sheath CABLE DESCRIPTION 1. Conductor Flexible Tinned Copper
5. Screen Aluminium/Polyester
Standard Put Up Length 305 or 500 meters
2. Insulation Polyethylene (PE) or Foam PE (FPE)
6. Braiding Tinned Copper wires
Standard References TIA/EIA-485 (BS) EN 50290-2 IEC 60332-1 (PVC sheath) or IEC 60332-3-24 (3C) (HFFR sheath) IEC 61034 (HFFR sheath) IEC 60754-1 & 2 (HFFR sheath) RoHS directives
3. Pair Impedance 120 Ω
7. Sheath Material Grey PVC or Purple HFFR
4. Tinned Copper Drain Wire 24 AWG(7 x 32)
Cables with 24 AWG conductors – PE insulation - PVC sheath
24 (7 x 32) 24 (7 x 32) 24 (7 x 32) 24 (7 x 32)
Max. DC Resistance Conductor (Ω/km) 88 88 88 88
Coverage braiding (%) 90 90 90 90
24 (7 x 32) 24 (7 x 32) 24 (7 x 32) 24 (7 x 32)
88 88 88 88
90 90 90 90
BTCL Part Number
No of pairs
Conductor (AWG)
C1189 C1190 C1191 C1192
1 2 3 4
C1318 C1319 C1320 C1321
1 2 3 4
Capacitance
Weight
PVC PVC PVC PVC
Overall Diameter (mm) 5.9 8.5 9.0 9.9
(pF/m) 41 41 41 41
(kg/km) 49 80.5 92.6 114.4
HFFR HFFR HFFR HFFR
5.9 8.5 9.0 9.9
41 42 42 42
49 80.5 92.6 114.4
Capacitance
Weight
PVC PVC PVC PVC
Overall Diameter (mm) 6.1 9.1 10.5 11.4
(pF/m) 36 37 38 38
(kg/km) 63.7 75.6 97 119.1
HFFR HFFR HFFR HFFR
6.1 9.1 10.5 11.4
36 37 38 38
63.7 75.6 97 119.1
Sheath
Cables with 22 AWG conductors – Foam PE insulation - Halogen-free (HFFR) sheath
22 (7 x 30) 22 (7 x 30) 22 (7 x 30) 22 (7 x 30)
Max. DC Resistance Conductor (Ω/km) 57.4 57.4 57.4 57.4
Coverage braiding (%) 65 65 65 65
22 (7 x 30) 22 (7 x 30) 22 (7 x 30) 22 (7 x 30)
57.4 57.4 57.4 57.4
65 65 65 65
BTCL Part Number
No of pairs
Conductor (AWG)
C1080 C1295 C1296 C1297
1 2 3 4
C1401 C1402 C1403 C1404
1 2 3 4
Colour scheme
Sheath
Pair 1
Pair 2
Pair 3
Pair 4
Wire a (insulation colour / colour of stripe)
White / blue
White / orange
White / green
White / brown
Wire b (insulation colour / colour of stripe)
Blue / white
Orange / white
Green / white
Brown /white
For more details, please see the respective detailed datasheet(s)
info.btcables@bt.com
12
Section 1.2 Cables with 2 to 6 pairs for RS-422 applications 24AWG conductors – FPE insulation – every pair screened - PVC sheath CABLE DESCRIPTION 1. Conductor Flexible Tinned Copper 2. Insulation Foam Polyethylene (FPE) 3. Pair Two twisted wires 4. Drain Wire Flexible Tinned Copper 24 AWG (7 x 32)
Standard Put Up Length 305 or 500 metres
5. Screen Aluminium/Polyester Wrapped around each Pair
Standard References ANSI/TIA/EIA-422-B (BS) EN 50290-2 IEC 60332-1 RoHS directives
6. Cable core 2 or more individually screened pairs stranded 7. Sheath Material Grey PVC
Cables with 24 AWG conductors – PE insulation – PVC sheath BTCL Part Number
No. of Pairs
C1382 C1383 C1384 C1386
2 3 4 6
Colour scheme C1382 to C1386
Conductor and Drain Wire (AWG) 24 (7 x 32) 24 (7 x 32) 24 (7 x 32) 24 (7 x 32)
Max. DC Resistance Conductor (Ω/km) 88 88 88 88
Pair 1 Black/Red
Overall Diameter (mm) 6.7 8.4 9.2 10.6
Pair 2 Black/White
Capacitance
Impedance
Weight
(pF/m) 41 41 41 41
(Ohm) 100 100 100 100
(kg/km) 41.8 59.4 75.5 104.8
Pair 3 Black/Green
Pair 4 Black/Blue
Pair 5 Black/Yellow
Pair 6 Black/Brown
For more details, please see the respective detailed datasheet(s)
info.btcables@bt.com
13
Section 1.3 Cables with 2 to 8 pairs for RS-232 applications 24AWG conductors – PVC insulation – overall screen – PVC, PE or HFFR sheath CABLE DESCRIPTION 1. Conductor Flexible Tinned Copper 24AWG(7x32) 2. Insulation PVC or HFFR
4. Cable core 2 or more pairs stranded
C1441 C1442 C1443 C1444 C1445 C1446 C1447 C1448 C1449 BTCL Part Number C1451 C1452 C1453 C1454 C1455 C1456 C1457 C1458
6. Screen Aluminium/Polyester
Standard References ANSI/TIA/EIA-232-F (BS) EN 50290-2 IEC 60332-1 (PVC sheath) IEC 60332-3-24 (3C) (HFFR sheath) IEC 61034 (HFFR sheath) RoHS directives
No. of Pairs
Insulation
Sheath
1 2 3 4 5 6 7 8
PVC PVC PVC PVC PVC PVC PVC PVC
PVC PVC PVC PVC PVC PVC PVC PVC
No. of Pairs
Insulation
Sheath
1 2 3 4 5 6 7 8 10
HFFR HFFR HFFR HFFR HFFR HFFR HFFR HFFR HFFR
HFFR HFFR HFFR HFFR HFFR HFFR HFFR HFFR HFFR
No. of Pairs
Insulation
Sheath
1 2 3 4 5 6 7 8
PVC PVC PVC PVC PVC PVC PVC PVC
PE PE PE PE PE PE PE PE
C1181 C1182 C1183 C1184 C1185 C1186 C1187 C1188 BTCL Part Number
Standard Put Up Length 305 or 500 metres
7. Sheath Material Grey PVC Purple HFFR Black PE
3. Pair Two twisted wires
BTCL Part Number
5. Tinned Copper Drain Wire 24 AWG(7 x 32)
Conductor and Drain Wire 24 (7 x 32) 24 (7 x 30) 24 (7 x 30) 24 (7 x 30) 24 (7 x 30) 24 (7 x 30) 24 (7 x 30) 24 (7 x 30)
Max. DCR Conductor (Ω/km) 88 88 88 88 88 88 88 88
Overall Diameter 4.0 5.6 5.9 6.7 7.3 7.4 7.5 8.3
Capacitance
Weight
135 76 76 80 80 80 80 80
18 28 39 48 57 65 68 76
Conductor and Drain Wire 24 (7 x 32) 24 (7 x 30) 24 (7 x 30) 24 (7 x 30) 24 (7 x 30) 24 (7 x 30) 24 (7 x 30) 24 (7 x 30) 24 (7 x 30)
Max. DCR Conductor (Ω/km) 88 88 88 88 88 88 88 88 88
Overall Diameter 4.0 5.6 5.9 6.7 7.3 7.4 7.5 8.3 9.2
Capacitance
Conductor and Drain Wire 24 (7 x 32) 24 (7 x 30) 24 (7 x 30) 24 (7 x 30) 24 (7 x 30) 24 (7 x 30) 24 (7 x 30) 24 (7 x 30)
Max. DCR Conductor (Ω/km) 88 88 88 88 88 88 88 88
Overall Diameter 4.0 5.6 5.9 6.7 7.3 7.4 7.5 8.3
Capacitance
Weight
95 55 55 60 60 60 60 60 60
18 28 39 48 57 65 73 85 95
Weight
135 76 76 80 80 80 80 80
14.5 24.5 31 39 47 55 59 67
Colour scheme of the pairs Pair number
Pair 1
Wire a
Black
Wire b
Red
Pair 2
Pair 3
Pair 4
Pair 5
Pair 6
Pair 7
Pair 8
Pair 10
Black
Black
Black
Black
Black
Black
Red
Red
White
Green
Blue
Yellow
Brown
Orange
White
Blue
For more details, please see the respective detailed datasheet(s)
info.btcables@bt.com
14
Section 1.4 Cables for KNX (was EIB or Instabus) applications 0.8 mm conductors – PE insulation – overall screen - PVC or HFFR sheath CABLE DESCRIPTION 1. Conductor Solid Bare Copper 0.8 mm = 0.5 mm2
5. Drain Wire 0.4 mm Tinned Copper
2. Insulation Polyethylene (PE) Black-RedWhite-Green
C1217 C1218 C1219 C1220
BTCL Part Number C1217 C1218 C1219 C1220
Standard References EN 50090 (BS) EN 50290-2 IEC 60332-1 (PVC sheath) or IEC 60332-3-24 (3C) (HFFR sheath) IEC 61034 (HFFR sheath) IEC 60754-1 & 2 (HFFR sheath) RoHS directives
6. Screen Aluminium/Polyester 7 Sheath Material Green PVC or Green HFFR
3. Cable Core Quad or Pair
BTCL Part Number
Standard Put Up Length 305 or 500 metres
4. Polyester tape
No. of wires 1x4 1x4 1x2 1x2
Lay-Up quad quad pair pair
Sheath Material PVC HFFR PVC HFFR
Diameter Insulation (mm) 1.45 1.45 1.45 1.45
Wire a
Wire b
Wire c
Wire d
Black Black Black Black
White White White White
Red Red
Green Green
Overall Diameter (mm) 6.1 6.1 5.5 5.5
Max. DC Resistance Conductor (Ω/km) 37 37 37 37
Capacitance
Weight
(pF/m) ≤ 100 ≤ 100 ≤ 100 ≤ 100
(kg/km) 51 53 37 39
For more details, please see the respective detailed datasheet(s)
info.btcables@bt.com
15
Section 1.5 Cables for LonWorks applications 0.64 mm conductors – PE or FPE insulation Individually screened pairs or unscreened pairs - HFFR sheath CABLE DESCRIPTION 1. Conductor Solid Bare Copper 0.64 mm = 0.32 mm²
5. Cable core one pair or two pairs stranded
2. Insulation Polyethylene (PE) or Foam Polyethylene (FPE)
6 Sheath Material Purple HFFR
3. Pairs with no screen two twisted wires 4. Individually screened pair two twisted wires plus drain wire wrapped with an Aluminium/Polyester foil
BTCL Part Number
No. of pairs
Insulation Material
Indiv. screened pairs
C1346 C1347 C1348 C1349
1 2 1 2
Solid PE Solid PE Foam PE Foam PE
No No Yes Yes
Overall Diameter (mm) 3.5 5.2 4.6 7.6
Standard Put Up Length 305 or 500 metres Standard References EN 50090 (BS) EN 50290-2 IEC 60332-3C IEC 61034 IEC 60754-1 & 2 RoHS directives
Max. DC Resistance Conductor (Ω/km) 61 61 61 61
Capacitance
Weight
(pF/m) 46 46 46 46
(kg/km) 17.1 27.7 24.2 56.1
For more details, please see the respective detailed datasheet(s)
info.btcables@bt.com
16
Section 1.6 Cables for General Interface applications 2 to 6 pairs – 22AWG conductors – PE or HFFR insulation Individually screened pairs – PVC or HFFR sheath CABLE DESCRIPTION 1. Conductor Flexible Tinned Copper 22AWG(7 x 30)
5. Screen Aluminium/Polyester foil wrapped around each pair
2. Insulation Polyethylene (PE) or Halogen-free (HFFR)
6. Cable core 2 or more individually screened pairs stranded
3. Pair Two twisted wires
7. Sheath Material Grey PVC or Purple HFFR
4. Tinned Copper Drain Wire 24 AWG(7 x 32)
BTCL Part Number C1196 C1281 C1197 C1282 C1298 C1299 C1214 C1314
No. of pairs
Insulation Material
Sheath Material
2 2 3 3 4 5 6 6
PE HFFR PE HFFR PE PE PE HFFR
PVC HFFR PVC HFFR PVC PVC PVC HFFR
Colour scheme
Pair 1
Overall Diameter (mm) 6.0 6.5 6.5 7.5 7.0 7.7 8.9 9.5
Pair 2
Pair 3
Standard Put Up Length 305 or 500 metres Standard References (BS) EN 50290-2 IEC 60332-1 (PVC sheath) IEC 60332-3-24 (3C) (HFFR sheath) IEC 61034 (HFFR sheath) IEC 60754-1 & 2 (HFFR sheath) RoHS directives
Max. DC Resistance Conductor (Ω/km) 57.4 57.4 57.4 57.4 57.4 57.4 57.4 57.4
Pair 4
Capacitance
Weight
(pF/m) 90 150 98 155 98 99 99 155
(kg/km) 36.1 50.8 49.1 67.4 62 74.2 87.2 115.6
Pair 5
C1196 and C1281
Black/ Red
Green/White
C1197 and C1282
Black/ Red
Black/White
Black/Green
C1298
Black/ Red
Black/White
Black/Green
Black/Blue
C1299
Black/ Red
Black/White
Black/Green
Black/Blue
Black/Yellow
C1214 and C1314
Black/ Red
Black/White
Black/Green
Black/Blue
Black/Yellow
Pair 6
Black/Brown
For more details, please see the respective detailed datasheet(s)
info.btcables@bt.com
17
Section 1.7 Cables for General Interface applications One pair – 22 to 12AWG conductors – PE insulation Collective (overall) screen – PVC or HFFR sheath CABLE DESCRIPTION 1. Conductor Flexible Tinned Copper
Standard Put Up Length 305 or 500 metres
4. T.C. Drain Wire (only with screen) 24 AWG(7 x 32)
2. Insulation PVC or Polyethylene (PE) or Halogen-free (HFFR)
Standard References (BS) EN 50290-2 IEC 60332-1 (PVC sheath) IEC 60332-3-24 (3C) (HFFR sheath) IEC 61034 (HFFR sheath) IEC 60754-1 & 2 (HFFR sheath) RoHS directives
5. Screen (if applicable) Aluminium/Polyester 6. Sheath Material Grey PVC or Purple HFFR
3. Pair Two wires twisted
DC Resistance 12 to 22 AWG conductors Conductor
AWG
22
20
18
16
14
12
No. of strands x gauge
AWG
7 x 30
7 x 28
7 x 26
19 x 29
19 x 27
19 x 25
No. of strands x mm
Mm
7 x 0.25
7 x 0.32
7 x 0.40
19 x 0.28
19 x 0.36
19 x 0.45
Ω/km
57.4
35.75
22.7
15.47
9.36
5.61
Max. DC resistance conductor
One pair cables with PE insulation and PVC sheath Screened BTCL Part Number
C1199 C1195 C1193 C1213 C1224 C1313
Cond.
Capacity
Weight
(AWG)
(pF/m)
(kg/km)
22 20 18 16 14 12
4.4 5.0 5.6 7.9 9.0 10.2
75 75 75 60 76 77
25 36.4 43.2 75.7 104.9 124.7
Screened BTCL Part Number
C1310 C1308 C1272 C1270 C1305 C1303
Unscreened
Overall Diameter (mm)
Cond.
BTCL Part Number
C1301 C1300 C1203 C1198 C1222 C1302
Cond.
Capacity
Weight
(AWG)
Overall Diameter (mm)
(pF/m)
(kg/km)
22 20 18 16 14 12
4.0 4.3 5.1 6.9 8.6 9.8
70 80 85 90 108 115
19.5 23 38.6 63.3 91.8 115
Capacity
Weight
(AWG)
Overall Diameter (mm)
(pF/m)
(kg/km)
22 20 18 16 14 12
4.7 5,2 5.9 7.7 8.7 9.7
48 52 65 48 55 57
24.7 34.7 45.9 71.8 95.3 128.2
One pair cables with HFFR insulation and HFFR sheath Unscreened Capacity
Weight
(AWG)
Overall Diameter (mm)
(pF/m)
(kg/km)
22 20 18 16 14 12
4.8 5.3 6.0 7.8 8.8 9.8
140 158 165 150 180 195
27.1 37.2 48.4 74.3 97.9 132.6
BTCL Part Number
C1311 C1309 C1271 C1307 C1306 C1304
Cond.
For more details, please see the respective detailed datasheet(s)
info.btcables@bt.com
18
Section 1.8 Cables for Security & Alarm applications 1 to 6 pairs – 18AWG conductors – polyolefin insulation foil or foil + braid overall screen –HFFR sheath CABLE DESCRIPTION Design 1. Conductor Flexible Bare Copper 2. Insulation Polyolefin
5. Drain Wire Flexible Tinned Copper 24 AWG (7 x 32)
Standard Put Up Length 305 or 500 metres
6. Overall Screen 1 Aluminium/Polyester foil
Standard References (BS) EN 50290-2 IEC 60332-3-24 IEC 61034 IEC 60754-1 & 2 RoHS directives
7. Overall Screen 2 braid coverage
3. Pair Two twisted wires 4. Cable core N pairs stranded
8. Sheath Material Purple Halogen-free (HFFR)
Cables with 18AWG conductors – Polyolefin insulation – Collective Screen and HFFR sheath BTCL Part Number
No. of Pairs
C1171 C1172 C1173 C1174 C1175 C1176
1 2 3 4 5 6
BTCL Part Number
No. of Pairs
Conductor (AWG)
Screen
C1418 C1419 C1420 C1421 C1422 C1423
1 2 3 4 5 6
18 (7 x 26) 18 (7 x 26) 18 (7 x 26) 18 (7 x 26) 18 (7 x 26) 18 (7 x 26)
foil + braid foil + braid foil + braid foil + braid foil + braid foil + braid
Colour scheme C1171 to C1176
Conductor (AWG) 18 (7 x 26) 18 (7 x 26) 18 (7 x 26) 18 (7 x 26) 18 (7 x 26) 18 (7 x 26)
Screen foil foil foil foil foil foil
Pair 1 Black/Red
Max. DC Resistance Conductor (Ω/km) 22.7 22.7 22.7 22.7 22.7 22.7
Overall Diameter (mm) 5.1 7.7 8.1 8.9 9.9 10.2
Max. DC Resistance Conductor (Ω/km) 22.7 22.7 22.7 22.7 22.7 22.7
Pair 2 Black/White
Capacitance
Weight
(pF/m) 115 115 115 115 115 115
(kg/km) 4.1 7.41 9.64 12.37 14.92 17.11
Overall Diameter (mm)
Capacitance (pF/m)
Weight (kg/km)
5.8 8.4 8.8 9.6 10.5 10.9
115 115 115 115 115 115
4.7 10.5 11.6 13.7 16.5 18.6
Pair 3 Black/Green
Pair 4 Black/Blue
Pair 5 Black/Yellow
Pair 6 Black/Brown
For more details, please see the respective detailed datasheet(s)
info.btcables@bt.com
19
Section 1.9 Building Management Systems Cable for 1 pair – 0.6 mm² conductors – polyolefin insulation Collective overall screen –PVC sheath
CABLE DESCRIPTION 1. Conductor Flexible Bare Copper 7 x 0.35 mm = 0.6 mm²
5. Screen Aluminium/Polyester foil
2. Insulation Polyolefin Core 1: Black Core 2: Red
6 Sheath Material Grey PVC
Standard Put Up Length 305 or 500 metres Standard References (BS) EN 50290-2 IEC 60332-1 RoHS directives
3. Pairs two twisted wires 4. Tinned Copper Drain Wirer 7 x 0.20 mm
BTCL Part Number
No. of pairs
C1381
1
Overall Diameter (mm) 3.9
Max. DC Resistance Conductor (Ω/km) 61
Capacitance (pF/m)
Weight (kg/km)
110
14.6
For more details, please see the respective detailed datasheet(s)
info.btcables@bt.com
20
Section 2 - BT BMS-TECTM - Multi-Conductor Cables
Application and Construction 1. Application All PVC and HFFR sheathed multi-conductor cables are suitable for Building Management Systems (BMS), Sound, Audio, Security, Safety, Control and Instrumentation. 2. Basic Construction of the cables Wire = Conductor without or with insulation. With insulation sometimes also indicated as core. Conductor: flexible = twisted bare or tinned copper strands, ranging from 12 to 22AWG. Conductor (AWG) 24 22 20 18 16 14 12
configuration (AWG) 7 x 32 7 x 30 7 x 28 7 x 26 19 x 29 19 x 27 19 x 25
configuration (mm) 7 x 0.2 7 x 0.25 7 x 0.32 7 x 0.40 19 x 0.28 19 x 0.36 19 x 0.45
DC Resistance (Ohm/km) ≤ 88 ≤ 57.4 ≤ 32.16 ≤ 22.7 ≤ 15.47 ≤ 9.36 ≤ 5.61
Insulation: Polypropylene (PP) for PVC (Polyvinyl Chloride) sheathed cables and Halogen-Free (HFFR) for HFFR sheathed cables. Both insulations are in accordance with BS EN 50290-2. Good strippable and coloured insulation. The colours are not interchangeable. Colour scheme of wires with 12 or 14 AWG conductors: black-white-red-green-brown-blue-orange-yellow-purlpe-grey-pinktan. Colour scheme of wires with ≥ 16AWG conductors: black-red-white-green-brown-blue-orange-yellow-purlpe-grey-pink-tan. Cable core: two or more wires, twisted. Good twisting (lay-length < 30 – 40D) is necessary otherwise the cable can hardly be bending and will break after a few bends. Drain wire (only in combination with a screen): stranded tinned copper wires. In order to avoid corrosion, it is recommended that drain wires are tinned. Screen (if applicable): Helically applied (= as a spiral) Aluminium/Polyester (Alpet) foil. For the flexibility of a cable a helically applied foil is to be preferred. A longitudinally applied foil act more as a stiff tube = more difficult to bend. Sheath: grey PVC or purple HFFR or black UV-resistant HFFR, all in accordance with BS EN 50290-2. Cable configurations Insulation Sheath Retardancy Retardant acc. to Low Smoke emission acc. to Halogen-free acc. to RoHS compliant
Cables with PVC sheath PP acc. to (BS)EN 50290-2 PVC acc. to (BS)EN 50290-2 Flame Retardant IEC 60332-1 / UL1581 Not applicable Not applicable Yes
Halogen-Free cables HFFR acc. to (BS)EN 50290-2 HFFR acc. to (BS)EN 50290-2 Fire Retardant IEC 60332-3-24 / UL 1685 IEC 61034 IEC 60754 yes
Operating temperature range: -25 to +75 °C and Rated Voltage: 300 Vrms.
Non-standard cable constructions, colours, details and/or additional information are available on request. For more details, please see the respective detailed datasheet(s). Please note that technical specifications are subject to change without notice.
info.btcables@bt.com
21
Section 2.1 – Multi-Conductor Cables
PVC sheathed cables with 12AWG to 22AWG conductors for Audio, Control, Instrumentation and Building Management Systems (BMS) CABLE DESCRPTION Design 1. Conductor Stranded Bare Copper
4 Drain Wire (only with screen) 24 AWG (7 x 32) Tinned Copper 5 Screen (if applicable) Aluminium/Polyester > 100% Coverage
2. Insulation Polypropylene (PP) 3 Cable Core Two or more wires stranded
Standard References (BS) EN 50290-2 IEC 60332-1 RoHS directives
6. Sheath Material Grey PVC
2 3 4 6 8
(AWG) 22 22 22 22 22
BT Cables Part Number C1226 C1228 C1230 C1264 C1232
Yes Yes Yes Yes Yes
(mm) 3.3 3.5 3.8 4.5 4.9
(kg/km) 16.5 21.4 26 35.7 45.1
BT Cables Part Number C1227 C1278 C1231 C1265 C1233
2 3 4 6 8
20 20 20 20 20
C1019 C1021 C1023 C1260 C1262
Yes Yes Yes Yes Yes
3.5 3.7 4.1 5.0 5.4
22 28.5 35.4 49.9 62.9
C1020 C1022 C1024 C1261 C1263
No No No No No
3.4 3.6 4.0 4.9 5.3
19.7 26.2 33.1 47.9 60.6
2 3 4 6 8
18 18 18 18 18
C1013 C1015 C1017 C1211 C1258
Yes Yes Yes Yes Yes
4.0 4.2 4.6 5.75 6.0
29.6 39.2 49.4 70.9 89.5
C1014 C1016 C1018 C1212 C1259
No No No No No
3.9 4.1 4.55 5.7 5.9
27.3 36.9 47.2 68.2 87
2 3 4 6 8
16 16 16 16 16
C1007 C1009 C1011 C1252 C1254
Yes Yes Yes Yes Yes
4.6 4.9 5.3 6.8 7.6
37.3 50 63.5 91.6 120.8
C1008 C1010 C1012 C1253 C1255
No No No No No
4.5 4.75 5.25 6.7 7.5
35 47.7 61.1 89 118.1
2 3 4 6 8
14 14 14 14 14
C1001 C1003 C1005 C1248 C1250
Yes Yes Yes Yes Yes
6.0 6.5 6.9 8.6 9.8
57 77.9 102.5 151 197.3
C1002 C1004 C1006 C1249 C1251
No No No No No
5.75 6.35 6.75 8.4 9.7
53.3 72.5 97.1 148.2 194.5
2 3 4 6 8
12 12 12 12 12
C1322 C1324 C1326 C1330 C1332
Yes Yes Yes Yes Yes
6.9 7.4 8.2 9.8 10.7
85.7 118.1 151.1 215.5 279.5
C1323 C1325 C1327 C1331 C1333
No No No No No
6.7 7.2 8.0 9.6 10.5
79.8 112.1 145.3 209.7 273.7
No of wires
Cond.
Standard Put Up Length 305 and 500 metres
Diam.
Weight
Scrn
Diam.
Weight
No No No No No
(mm) 3.3 3.5 3.8 4.5 4.9
(kg/km) 14.6 19.7 23.9 33.6 43
Scrn
Scrn = Screen, Diam. = overall diameter. For more details, please see the respective detailed datasheet(s
info.btcables@bt.com
22
Section 2.2 – Multi-Conductor Cables
Halogen-Free (HFFR) cables with 12AWG to 22AWG conductors for Audio, Control, Instrumentation and Building Management Systems (BMS) CABLE DESCRIPTION Design 1. Conductor Stranded Bare Copper
4. Screen (if applicable) Aluminium/Polyester > 100% Coverage
2. Insulation HFFR
5. Ripcord
Standard References (BS) EN 50290-2 IEC 60332-3C IEC 61034 IEC 60754-1 & 2 RoHS directives
6. Sheath Material Purple Halogen-Free (HFFR)
3. Drain Wire (only with screen) 24 AWG (7 x 32) Tinned Copper
2 3 4 6 8
(AWG) 22 22 22 22 22
BT Cables Part Number C1741 C1743 C1745 C1747 C1749
Yes Yes Yes Yes Yes
(mm) 3.9 4.1 4.4 5.2 5.6
(kg/km) 22.4 27.6 33.7 45.8 56.4
BT Cables Part Number C1742 C1744 C1746 C1748 C1750
2 3 4 6 8
20 20 20 20 20
C1731 C1733 C1735 C1737 C1739
Yes Yes Yes Yes Yes
4.7 4.9 5.3 6.2 6.7
32.6 40.2 48.7 66.2 81.9
C1732 C1734 C1736 C1738 C1740
No No No No No
4.6 4.8 5.2 6.1 6.6
30.1 37.7 46.2 63.7 79.4
2 3 4 6 8
18 18 18 18 18
C1721 C1723 C1725 C1727 C1729
Yes Yes Yes Yes Yes
5.1 5.4 5.8 6.8 7.3
41.0 52.3 64.1 88.6 110.8
C1722 C1724 C1726 C1728 C1730
No No No No No
5.0 5.3 5.7 6.7 7.2
38.5 49.8 61.6 86.1 108.2
2 3 4 6 8
16 16 16 16 16
C1711 C1713 C1715 C1717 C1719
Yes Yes Yes Yes Yes
5.4 5.7 6.2 7.3 7.9
49.3 63.8 79.3 108.2 137.0
C1712 C1714 C1716 C1718 C1720
No No No No No
5.4 5.7 6.2 7.3 7.9
46.8 61.3 78.2 107.0 135.9
2 3 4 6 8
14 14 14 14 14
C1701 C1703 C1705 C1707 C1709
Yes Yes Yes Yes Yes
6.5 6.9 7.5 8.9 9.6
67.7 92.8 115.4 163.7 210.8
C1702 C1704 C1706 C1708 C1710
No No No No No
6.4 6.8 7.4 8.8 9.5
65.2 89.1 112.9 162.8 208.3
2 3 4 6 8
12 12 12 12 12
C1334 C1336 C1338 C1342 C1344
Yes Yes Yes Yes Yes
7.7 8.1 8.9 10.6 11.6
102.2 135.0 170.9 243.3 314.6
C1335 C1337 C1339 C1343 C1345
No No No No No
7.5 7.9 8.7 10.4 11.4
97.0 129.7 165.7 237.1 306.2
No of wires
Cond.
Standard Put Up Length 305 metres
Diam.
Weight
Scrn
Diam.
Weight
No No No No No
(mm) 3.9 4.1 4.4 5.2 5.6
(kg/km) 20.5 26.0 31.7 43.9 54.4
Scrn
Scrn = Screen, Diam. = overall diameter. For more details, please see the respective detailed datasheet(s
info.btcables@bt.com
23
Section 2.3 – Multi-Conductor Cables
UV-Resistant Halogen-Free (HFFR) cables with 12AWG to 22AWG conductors for Audio, Control, Instrumentation and Building Management Systems (BMS) CABLE DESCRIPTION Design
Standard Put Up Length 305 metres
1. Conductor Stranded Bare Copper
4. Screen (if applicable) Aluminium/Polyester > 100% Coverage
2. Insulation HFFR
5. Ripcord
Standard References (BS) EN 50290-2 IEC 60332-3C IEC 61034 IEC 60754-1 & 2 RoHS directives
6. Sheath Material Black UV-resistant Halogen-Free (HFFR)
3. Drain Wire (only with screen) 24 AWG (7 x 32) Tinned Copper
(AWG)
BT Cables Part Number
(mm)
(kg/km)
2
18
C1351
Yes
5.1
41.0
3
18
C1352
Yes
5.4
52.3
4
18
C1353
Yes
5.8
64.1
6
18
C1354
Yes
6.8
88.6
8
18
C1355
Yes
7.3
110.8
10
18
C1356
Yes
8.4
135.7
20
18
C1357
Yes
10.7
249.6
Cond.
BT Cables Part Number C1391 C1392 C1393 C1394 C1395 C1396 C1397
Diameter
Weight
(mm) 5.5 5.8 6.3 7.4 8.0 9.5 12.1
(kg/km) 49.3 63.8 79.3 108.2 137.0 173.1 316.6
No of wires
No of wires
Cond.
(AWG)
2
16
3
16
4
16
6
16
8
16
10
16
20
16
Screen
Diameter
Weight
Screen Yes Yes Yes Yes Yes Yes Yes
For more details, please see the respective detailed datasheet(s)
info.btcables@bt.com
24
Section 3 - BT FIREPRO-TEC™ – Fire Detection and Alarm System Cables
Bare Copper 12 to 18AWG, one pair, PVC insulation and Sheath, Screened and Unscreened ©UL Certification: type FPLR rated 105°C - ©UL listed APPLICATION Fire Detection and Alarm Systems Fire Retardancy: UL 1666 Operating temperature range: -40 to +105 °C and Rated Voltage: 300 Vrms
CABLE DESCRIPTION 1. Conductor Solid Bare Copper
4. TC Drain Wire (only under screen) 22 AWG (7 x 30)
2. Insulation PVC acc. to UL444 Black and Red
No. of Pairs
C1040 C1135 C1041 C1136 C1042 C1137 C1043 C1138
1 1 1 1 1 1 1 1
Standard References UL1424 UL444 UL1666 RoHS directives
5. Screen (if applicable) Aluminium/Polyester > 100% Coverage
3. Pair Two wires twisted
BT Cables Part Number
Standard Put Up Length 305 metres
6. Sheath Material Red PVC acc. to UL444
Conductor ( AWG) 18 18 16 16 14 14 12 12
Screen Yes No Yes No Yes No Yes No
POWER-LIMITED CIRCUIT CABLE NO. 000001 1000 FEET F ORM 3
Overall Diameter (mm)
Max. DC Resistance Conductor (Ω/km)
5.9 5.8 6.1 6.0 7.8 7.7 8.7 8.6
22.7 22.7 15.47 15.47 9.36 9.36 5.61 5.61
Capacitance
Weight
(pF/m)
(kg/km)
160 60 189 71 160 69 216 65
19.2 16.0 28.5 25.0 43.0 40.0 66.0 63.0
Non-standard cable constructions, colours, details and/or additional information are available on request. For more details, please see the respective detailed datasheet(s). Please note that technical specifications are subject to change without notice.
info.btcables@bt.com
25
Section 4 - BT FIREPRO-TEC™ – Fire Resistant Cables
Bare and Flexible Copper Conductors 0.75 to 4.0 mm2, Silicon insulation and Halogen-free Sheath, Screened and Unscreened 1. Application All Fire Resistant cables are suitable for Security, Safety, Control and Instrumentation with special requirements for circuit integrity in case of a fire. 2. Fire Resistance confirming with BS6387 CWZ: Fire Resistant to BS 6387, Cat. C: exposed to fire at 950°C for 3 hours Fire Resistant to BS 6387, Cat. W: exposed to fire at 650°C for 15 minutes, then exposed to fire at 650°C with water for 15 minutes Fire Resistant to BS 6387, Cat. Z: exposed to fire at 650°C for 15 minutes, then exposed to fire at 650°C with mechanical shock for 15 minutes 3. Fire Retardancy confirming with IEC 60332-3-24 (was 3C) 4. Basic Construction of the cables Wire = Conductor with Insulation Conductor: solid bare copper wires, ranging from 0.75 to 2.5 mm² and the 4.0 mm² conductor consists of stranded bare copper wires = flexible
Cross Section (mm²) 0.75 1.0 1.5 2.5 4.0
Diameter (mm) 1 x 1.0 1 x 1.13 1 x 1.4 1 x 1.8 7 x 0.85 = 2.55
DC Resistance (Ohm/km) ≤ 24.5 ≤ 18.1 ≤ 12.1 ≤ 7.41 ≤ 4.61
Recommended Current (Amp) ≤ 12 ≤ 18 ≤ 21 ≤ 30 ≤ 40
Insulation: Silicon Rubber blends acc. to BS 7655. Good strippable and coloured insulation. The colours are not interchangeable. Colour scheme: 2 cores: brown – blue, 3 cores: brown – black – grey, 4 and more cores: brown – blue – black – grey – others black numbered. Cable core: two or more cores, twisted. Good twisting is necessary otherwise the cable can hardly be bending and will break after a few bends. Drain wire (only in combination with a screen): solid bare copper. Screen (if applicable): Helically applied (= as a spiral) Aluminium/Polyester (Alpet) foil. For the flexibility of a cable a helically applied foil is to be preferred. A longitudinally applied foil act more as a stiff tube = more difficult to bend. Sheath: red HFFR in accordance with BS EN 50290-2 Operating temperature range: -20 to +90 °C. Rated Voltage: 300/500 Vrms
Non-standard cable constructions, colours, details and/or additional information are available on request. For more details, please see the respective detailed datasheet(s). Please note that technical specifications are subject to change without notice.
info.btcables@bt.com
26
Section 4 - BT FIREPRO-TEC™ – Fire Resistant Cables
CABLE DESCRIPTION 1. Conductor Solid or Flexible Bare Copper 2. Insulation Silicon Rubber blend 3. Cable core Two or three wires Twisted
BT Cables Part Number C1284 C1139 C1159 C1149 C1283 C1140 C1160 C1150 C1044 C1141 C1161 C1151 C1045 C1142 C1162 C1152 C1289 C1143 C1163 C1153
No. of wires 2 2 3 3 2 2 3 3 2 2 3 3 2 2 3 3 2 2 3 3
4. BC Drain Wire (only under screen)
Standard Put Up Length 305 and 500 metres
5. Screen (if applicable) Aluminium/Polyester > 100% Coverage
Standard References BS 6387 CWZ BS 7655 IEC 60332-3C IEC 60754-1 & 2 RoHS directives
6. Sheath Material Red HFFR
Conductor (mm²) 0.75 0.75 0.75 0.75 1.0 1.0 1.0 1.0 1.5 1.5 1.5 1.5 2.5 2.5 2.5 2.5 4.0 4.0 4.0 4.0
Screen
Drain Wire (mm²) 0.75
Yes No Yes No Yes No Yes No Yes No Yes No Yes No Yes No Yes No Yes No
0.75 1.0 1.0 1.5 1.5 2.5 2.5 4.0 4.0
Overall Diameter (mm) 7.5 7.4 7.9 7.8 7.8 7.7 8.1 8.0 8.7 8.6 8.95 8.85 9.9 9.8 10.3 10.2 12.0 11.9 12.95 12.85
Max. DC Resistance Conductor (Ω/km) 24.5 24.5 24.5 24.5 18.1 18.1 18.1 18.1 12.1 12.1 12.1 12.1 7.41 7.41 7.41 7.41 4.61 4.61 4.61 4.61
Weight (kg/km) 67.0 61.7 83 75 73.4 65.5 93 83 98.1 87.6 123 108 134.3 119.4 174 151 197.1 172.6 270 234
For more details, please see the respective detailed datasheet(s)
info.btcables@bt.com
27
Section 5 - BT Security-Tec ™– Coaxial Cables
Application and Construction of Coax Cables for 75 Ohm Video Systems Applications. CCTV: Closed Circuit Television is the use of video cameras to transmit a signal to a specific place, on a limited set of monitors SMATV: Satellite Master Antenna Television used to deliver signals to multiple dwelling units (e.g., apartment buildings and trailer parks). CATV: Central Antenna Television = Cable television is a system of providing television to consumers via radio frequency signals transmitted to televisions. Nowadays also used for internet and telephone. HDTV: High-definition television refers to video having resolution substantially higher than traditional television systems. Telecom and networking: a number of special cable constructions. Basic Cable Design. Coaxial cables are designed to carry radio frequency current of a much higher frequency than the 50 or 60 Hz used in low voltage cables. And this requires special construction to prevent power losses. If an ordinary wire is used to carry high frequency currents, the wire acts as an antenna, and the high frequency currents radiate off the wire as radio waves, causing power losses. To prevent this, in coaxial cable one of the conductors is formed into a tube and encloses the other conductor. This confines the radio waves from the central conductor to the space inside the tube. To prevent the outer conductor, or shield, from radiating, it is connected to electrical ground, keeping it at a constant potential. The dimensions and spacing of the conductors must be uniform throughout the length of the cable. Any abrupt change in the spacing of the two conductors along the cable tends to reflect radio frequency power back toward the source. This acts as a bottleneck, reducing the amount of power reaching the destination end of the cable. Choosing the correct 75 ohm coax cable. Most coaxial cables for video applications have a nominal impedance of 75 ohms. Their differing electrical and physical characteristics make it important to select the correct type of cable to suit the application. RG59 Analogue TV
RG6 RG11 RG59
CCTV
RG6 RG11
Acceptable performance on cable runs < 225 metres Gives superior performance on cable runs < 225 metres. Used for cable runs > 225 metres but < 545 metres. For cable runs greater than 545 metres. Acceptable performance on cable runs < 225 metres Gives for superior performance on cable runs < 225 metres. Used for cable runs > 225 metres but < 545 metres. For cable runs greater than 545 metres.
This table is for reference only. BT Cables survey of Part Numbers. Application CCTV – PVC sheath CCTV – HFFR sheath CCTV CATV / SMATV CATV / SMATV HDTV – PVC sheath HDTV – HFFR sheath
Tested 1000 MHz 1000 MHz 1000 MHz 3000 MHz 3000 MHz 4500 MHz 4500 MHz
Speciality Solid conductor Solid conductor Flexible conductor Dual screen Quad screen Dual Screen 95% Dual Screen 95%
RG-59 C1028 C1428 C1275 C1025 C1256 C1229 C1378
RG-6 C1029 C1429 C1276 C1026 C1257 C1279 C1379
RG-11 C1030 C1430 C1277 C1027 C1241 C1280 C1380
Operating temperature range: -25 to +75 °C and Rated Voltage: 300 Vrms
info.btcables@bt.com
28
Section 5.1 – BT Security-Tec ™– 75 ohm coax cables
CCTV and Video Applications, sweep tested 1to 1000 MHz CABLE DESCRIPTION 1. Conductor Solid or Flexible Bare Copper
Standard References IEC 61196 (BS) EN 50117 (BS) EN 50290-2 IEC 60332-1 (PVC sheath) or IEC 60332-3-24 (HFFR cable) IEC 61034 (only HFFR cable) IEC 60754-1 & 2 (HFFR cable) RoHS directives
4. Sheath Material Polyvinyl Chloride (PVC) or Halogen-Free (HFFR)
2. Dielectric Foamed Polyethylene (FPE)
Standard Put Up Length 305 or 500 metres
3. Braid Bare Copper
Physical Characteristics BT Cables Part Number C1028 C1428 C1275 C1029 C1429 C1276 C1030 C1480 C1277
Conductor
Diameter Dielectric (mm) 3.71 3.71 3.71 4.60 4.60 4.60 7.11 7.11 7.11
RG-Type RG-59 RG-59 RG-59 RG-6 RG-6 RG-6 RG-11 RG-11 RG-11
(mm) 0.81 solid 0.81 solid 19x0.18TC 1.02 solid 1.02 solid 19x0.22 1.63 solid 1.63 solid 19x0.34
Coverage braid (%) 95 95 95 95 95 95 90 90 90
Sheath Material PVC HFFR PVC PVC HFFR PVC PVC HFFR PVC
Overall Diameter (mm) 6.0 6.0 6.0 6.8 6.8 6.8 10.0 10.0 10.0
Weight (kg/km) 47.12 48.5 47.12 55.5 58.2 54.66 115.9 120 115.9
Electrical and Physical Characteristics (at 20°C) BT Cables Part Number
RG-Type
Impedance (Ω)
C1028 C1428 C1275 C1029 C1429 C1276 C1030 C1480 C1277
RG-59 RG-59 RG-59 RG-6 RG-6 RG-6 RG-11 RG-11 RG-11
75 ± 3 75 ± 3 75 ± 3 75 ± 3 75 ± 3 75 ± 3 75 ± 3 75 ± 3 75 ± 3
Max. DC Resistance Conductor (Ω/km) 33.5 33.5 40 21.5 21.5 30 8.8 8.8 8.8
Max. DC Resistance screen (Ω/km) 10.1 10.1 10.1 10.8 10.8 10.8 6.5 6.5 6.5
Nominal Capacitance (pF/m) 53.5 53.5 53.5 53.5 53.5 53.5 52.8 52.8 52.8
Min. Return Loss 1 to 1000 MHZ (dB) 20 20 20 20 20 20 20 20 20
Nominal Attenuation in dB/100m MHz RG-59 RG-6 RG-11
5 1.9 1.78 0.99
10 2.95 2.36 1.51
50 6.23 4.92 2.96
100 8.53 6.56 4.27
200 11.81 9.51 6.23
300 15.3 12.43 8.27
400 16.41 13.78 9.51
450 18.92 15.14 10.31
550 21.03 17.15 11.51
700 22.97 18.37 13.45
750 24.8 19.73 13.95
870 26.84 20.26 14.87
1000 27.89 21.96 17.06
For more details, please see the respective detailed datasheet(s).
info.btcables@bt.com
29
Section 5.2 – BT Security-Tec ™– 75 ohm coax cables
SMATV - CATV and Video applications, sweep tested1to 3000 MHz CABLE DESCRIPTION 1. Conductor Solid Copper Covered Steel (CCS)
5. Braid 2 (Quad scrn only) Aluminium/Polyester foil 100% coverage
2. Dielectric Foamed Polyethylene (FPE)
6. Screen 2 (Quad scrn only) Aluminium
3. Screen 1 Bonded Aluminium/ Polyester foil 100% coverage
7. Sheath Polyvinyl Chloride (PVC)
Standard References IEC 61196 (BS) EN 50117 (BS) EN 50290-2 IEC 60332-1 RoHS directives
Standard Put Up Length 305 or 500 metres
4. Braid 1 Aluminium
Physical Characteristics BT Cables Part Number C1025 C1256 C1026 C1257 C1027 C1241
Conductor RG-Type (mm) 0.81 0.81 1.02 1.02 1.63 1.63
RG-59-3 GHz RG-59-3 GHz RG-6-3 GHz RG-6-3 GHz RG-11-3 GHz RG-11-3 GHz
Diameter Dielectric (mm) 3.71 3.71 4.60 4.60 7.11 7.11
Type of Screen Dual scrn Quad scrn Dual scrn Quad scrn Dual scrn Quad scrn
Coverage braid (%) 54 54 + 46 60 60 + 40 61 60 +40
Sheath Material PVC PVC PVC PVC PVC PVC
Overall Diameter (mm) 6.0 6.73 6.8 7.52 10.0 10.3
Weight (kg/km) 32.42 39.4 41.32 49.5 86.6 90.6
Dual Screen = Screen 1 + Braid 1 Quad Screen = Screen 1 + Braid 1 + Screen 2 + Braid 2 Electrical and Physical Characteristics (at 20°C) BT Cables Part Number
RG-Type
Imped.
C1025 C1256 C1026 C1257 C1027 C1241
RG-59-3 GHz RG-59-3 GHz RG-6-3 GHz RG-6-3 GHz RG-11-3 GHz RG-11-3 GHz
(Ω) 75 ± 3 75 ± 3 75 ± 3 75 ± 3 75 ± 3 75 ± 3
Max. DC Resistance Conductor (Ω/km) 146.5 146.5 92.2 92.2 36.5 36.5
Max. DC Resistance Screen (Ω/km) 52 26 30 17 25 12
Nominal Capacitance (pF/m) 53 53 53 53 53 53
Min. Return Loss (dB) < 1000 < 2000 < 3000 MHz MHz MHz 18 16 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20
Nominal Attenuation in dB/100m MHz
5
10
50
100
200
400
550
870
1250
1750
2150
2500
3000
RG-59 RG-6 RG-11
2.92 2.2 1.25
3.45 2.48 2.03
5.40 5.15 3.75
8.21 6.6 5.01
12.56 9.56 6.85
16.01 13.12 7.05
19.36 15.45 9.65
24.74 19.69 12.6
30.62 24.25 16.66
36.71 29.26 20.28
40.82 32.88 22.93
44.72 35.88 25.12
48.64 39.83 28.08
For more details, please see the respective detailed datasheet(s)
info.btcables@bt.com
30
Section 5.3 – BT Security-Tec ™– 75 ohm coax cables
HDTV and HD Video applications, sweep tested1to 4500 MHz CABLE DESCRIPTION 1. Conductor Solid Bare Copper
4. Braid Tinned Copper
2. Dielectric Foamed Polyethylene
5. Sheath Material Polyvinyl Chloride (PVC) or Halogen-free (HFFR) Colour: Orange
3. Screen Bonded Aluminium/ Polyester foil 100% coverage
Standard References IEC 61196 (BS) EN 50117 (BS) EN 50290-2 IEC 60332-1(PVC sheath) or IEC 60332-3C ( HFFR cable) IEC 61034 (HFFR cable) IEC 60754-1 & 2 (HFFR cable) RoHS directives
Standard Put Up Length 305 or 500 metres
Physical Characteristics BT Cables Part Number C1229 c1378 C1279 c1379 C1280 C1380
Conductor RG-Type (mm) 0.81 0.81 1.02 1.02 1.63 1.63
RG-59-4.5 GHz RG-59-4.5 GHz RG-6-4.5 GHz RG-6-4.5 GHz RG-11-4.5 GHz RG-11-4.5 GHz
Diameter Dielectric (mm) 3.71 3.71 4.60 4.60 7.11 7.11
Coverage braid (%) 95 95 95 95 95 95
Sheath Material PVC HFFR PVC HFFR PVC HFFR
Overall Diameter (mm) 6.0 6.0 6.8 6.8 10.0 10.0
Weight (kg/km) 46.72 48.2 56.2 59 114.5 117
Electrical and Physical Characteristics (at 20°C) BT Cables Part Number
RG-Type
Imp.
C1229 c1378 C1279 c1379 C1280 C1380
RG-59-4.5 GHz RG-59-4.5 GHz RG-6-4.5 GHz RG-6-4.5 GHz RG-11-4.5 GHz RG-11-4.5 GHz
(Ω) 75 ± 3 75 ± 3 75 ± 3 75 ± 3 75 ± 3 75 ± 3
Max. DC Resistance Conductor (Ω/km) 33.5 33.5 21.5 21.5 8.8 8.8
Max. DC Resistance Screen (Ω/km) 12.5 12.5 10.6 10.6 6.6 6.6
Nom. Cap. (pF/m) 53 53 53 53 53 53
<1000 MHz 23 23 23 23 23 23
Min. Return Loss (dB) < 2000 < 3000 MHz MHz 22 16 22 16 22 16 22 16 22 16 22 16
< 4500 MHz 15 15 15 15 15 15
Nominal Attenuation in dB/100m MHz RG-59 RG-6 RG-11
1 0.98 0.79 0.53
5 2.07 1.71 1.12
10 2.95 2.33 1.51
50 6.23 4.57 2.96
100 7.55 6.40 4.20
300 13.68 11.96 7.49
550 18.83 15.76 10.41
750 22.23 18.05 12.38
1000 25.96 21.36 14.57
2000 38.24 31.44 21.84
3000 46.13 39.76 27.93
4500 56.50 50.46 35.98
For more details, please see the respective detailed datasheet(s).
info.btcables@bt.com
31
Section 6 – BT Data-Tec™ - Category LAN Cables Application and Construction of Category Cables Area Networks and Structured Wiring Systems for Local 1. Application Horizontal or Building Wiring for one of the following categories of twisted pair cabling systems
Cat 1 Cat 2 Cat 3 Cat 4 Cat 5
Max. data rate 1 Mbps 4 Mbps 16 Mbps 20 Mbps 100 MHz
Cat 5e
100 MHz
Cat 6
250 MHz
Cat 6a
500 MHz
Cat 7
600 MHz
As Cat 6a plus supporting 100GbE
Cat 7a
1000 MHz
CATV (862 MHz), 40GBASE-T over 50 m. 100GbE over 15 m.
Category
Usual application
Standard(s) ISO/IEC
TIA/EIA
Analogue voice Token ring of IBM Voice, 10MbE(thernet) 16 Mbps Token Ring 10/100/1000 MbE 155 Mbps ATM, 4/16 Mbps Token Ring as Cat5e plus 10Gb Ethernet over ≤ 55 m. As Cat 6 plus 10Gb Ethernet over 100 m.
EN
De facto, never a standard TIA/EIA 568-B Was only a standard briefly Replaced by 5e
TIA/EIA 568-C.2
Cat 7a is not recognised in TIA/EIA-569
ISO/IEC 11806, 2nd edition IEC 61156 ISO/IEC 11801: 2002, category 7 / class F ISO/IEC 11801, amendment 1 (2008) and amendment 2 (2010).
EN 50173-1 EN 50288
2. Basic Cable Construction of the standard cables (not being patch cables) Wire = Conductor with Insulation Insulation: will be good strippable, suitable for insulation displacement and coloured. The colours are not interchangeable. Pair = two twisted – colour coded – wires. Individually screened pair (if applicable): one pair wrapped with an Aluminium/Polyester foil under which a drain wire. Braiding (if applicable): tinned copper wires. Ripcord: to ease removal of the sheath. Sheath: PVC or Halogen-Free (HFFR). Cat 3 Type
UUTP
Conductor Insulation Cable core Core wrapping Drain wire Overall screen Sheath
Solid BC Polyolefin 6 to 200 pairs Yes No No PVC
Cat 5e UUTP
Cat 6
FUTP
Solid BC PE
No No
UUTP
FUTP
Solid BC PE 4 pairs
Yes Foil
No Yes No Foil PVC or HFFR
info.btcables@bt.com
Cat 6a Cat 7 Cat 7a UFTP & S-FTP S-FTP UUTP FUTP Solid BC Solid BC Solid BC Skin-foam-skin PE 4 Individually screened pairs No No Central drain wire Braiding HFFR
32
Section 6 – BT Data-Tec™ - Category LAN Cables 3. Basic Cable Construction of the standard patch cables
Cat 5e Cat 6 UUTP FUTP UUTP FUTP Flexible BC PE PE 4 pairs 4 pairs no yes no yes no yes no yes no foil no foil yes PVC or HFFR
Type Conductor Insulation Cable core Core wrapping Drain wire (TC) Overall Screen Rip cord Sheath 4. General Characteristics Max. DCR conductor Impedance
Cat 3 9.6 100
Ω/100m Ω
Cat 5e 9.38 100
Cat 6 9.38 100
Cat 6a 7.7 100
Cat 7 7.7 100
Standard Colour scheme of Cat 5e – 6 – 6a and 7: Pair number a-wire
Pair 1 Blue White with blue stripe
b-wire
Pair 2 Orange White with orange stripe
Pair 3 Green White with green stripe
Pair 4 Brown White with brown stripe
Operating temperature range: -20 to +80 °C and Rated Voltage: 300 Vrms. 5. Cable Range of BT Cables: Cat3 - PVC Category Type Sheath BT P/N
2 pairs C1031 Cat 5e UTP PVC C1035
6 pairs C1266
12 pairs C1267
Cat 5e UTP-UL listed PVC C1285
Category Type Sheath BT P/N
Cat 6 UUTP PVC C1037
Cat 6 UUTP-UL listed PVC C1287
Category Type Sheath BT P/N
Cat 6a U-UTP PVC C1200
Cat 6a U-FTP HFFR C1053
Category Type Sheath BT P/N
Cat 5e UTP-Patch PVC C1500
Cat 5e UTP-Patch HFFR C1510
25 pairs C1032
50 pairs C1033
Cat 5e UTP HFFR C1235
Cat 6 UUTP HFFR C1227 Cat 7 S-FTP HFFR C1039
Cat 5e FTP-Patch PVC C1520
Cat 6 FUTP PVC C1038
100 pairs C1034
150 pairs C1268
Cat 5e FTP PVC C1036
Cat 5e FTP-UL listed PVC C1286
Cat 6 FUTP-UL listed PVC C1288
Cat 6 FUTP HFFR C1238
200 pairs C1269 Cat 5e FTP HFFR C1236
Cat 7a S-FTP HFFR C1201 Cat 5e FTP-Patch HFFR C1530
Cat 6 UTP-Patch PVC C1540
Cat 6 UTP-Patch HFFR C1550
Cat 6 FTP-Patch PVC C1560
Cat 6 FTP-Patch HFFR C1570
Non-standard cable constructions, colours, details and/or additional information are available on request. For more details, please see the respective detailed datasheet(s). Please note that technical specifications are subject to change without notice.
info.btcables@bt.com
33
Section 6.1 – BT Data-Tec™ - Category LAN Cables Cat 5e and 6 UTP and FTP cables
Cat 5e cables BT Cables Part Number C1035 C1285 C1235 C1036 C1286 C1236
Type UUTP UUTP-UL UUTP FUTP FUTP-UL FUTP
Cat 5e Variants Overall Diameter Sheath (mm) 5.0 PVC 5.0 PVC 5.0 HFFR 6.3 PVC 6.3 PVC 6.3 HFFR
Weight (kg/km) 30 30 29 42 42 42
Main Transmission Characteristics of Cat 5e cables Frequency (MHz)
Min. Return Loss (dB/100m)
Maximum Attenuation (dB/100m)
Minimum NEXT (dB)
Maximum Time Delay (ns/100m)
Minimum PSNEXT (dB)
Minimum ELFEXT (dB)
Minimum PSELFEXT (dB)
1 4 8 10 16 20 25 31.25 62.5 100
20.0 23.0 24.5 25.0 25.0 25.0 24.3 23.6 21.5 20.1
2.0 4.1 5.8 6.5 8.2 9.3 10.4 11.7 17.0 22.0
65.3 56.3 51.8 50.3 47.2 45.8 44.3 42.9 38.4 35.3
570.00 552.00 546.73 545.38 543.00 542.05 541.20 540.44 538.55 537.60
62.3 53.3 48.8 47.3 44.4 42.8 41.3 39.9 35.4 32.3
64.0 52.0 45.9 44.0 39.9 38.0 35.8 34.1 28.1 24.0
61.0 49.0 42.9 41.0 36.9 35.0 33.0 31.1 25.1 21.0
Cat 6 cables Cat 6 Variant
BT Cables Part Number C1037 C1287 C1237 C1038 C1288 C1238
Type
Sheath
UUTP UUTP-UL UUTP FUTP FUTP-UL FUTP
PVC PVC HFFR PVC PVC HFFR
Overall Diameter (mm) 6.2 6.2 6.2 7.4 7.4 7.4
Weight (kg/km) 42 42 42 56 56 54.1
Main Transmission Characteristics of Cat 6 cables Frequency (MHz)
Return Loss (dB/100m)
Maximum Attenuation (dB/100m)
Minimum NEXT (dB)
Maximum Time Delay (ns/100m)
Minimum PSNEXT (dB)
Minimum ELFEXT (dB)
Minimum PSELFEXT (dB)
1 4 8 10 16 20 25 31.25 62.5 100 200 250
20.0 23.0 24.5 25.0 25.0 25.0 24.3 23.6 21.5 20.1 18.0 17.3
2.0 3.8 5.3 6.0 7.6 8.5 9.5 10.7 15.4 19.8 29.0 32.8
74.3 65.3 60.8 59.3 56.2 54.8 53.3 51.9 47.4 44.3 39.8 38.3
570.00 552.00 546.73 545.38 543.00 542.05 541.20 540.44 538.55 537.80 536.54 536.27
72.3 63.3 58.8 57.3 54.2 52.8 51.3 49.9 45.4 42.3 37.8 36.3
67.8 55.8 49.7 47.8 43.7 41.8 39.8 37.9 31.9 27.8 21.8 19.8
64.8 52.8 46.7 44.8 40.7 38.8 36.8 34.9 28.9 24.8 18.8 16.8
For more details, please see the respective detailed datasheet(s).
info.btcables@bt.com
34
Section 6.2 – BT Data-Tec™ - Category LAN Cables Cat 6a U-FTP and Cat 7 S-FTP cables Cat 6a U-FTP cables
BT Cables Part Number
Type
C1200 C1053
U-UTP U-FTP
Cat 6a Variants Overall Diameter Sheath (mm)
Weight (kg/km)
8.3 7.2
PVC HFFR
61.2 49.9
Main Transmission Characteristics of Cat 6a U-FTP cables Freq. (MHz)
Return Loss (dB/100m)
Attenuation (dB/100m)
NEXT (dB/100m)
PSNEXT (dB/100m)
ELFEXT (dB/100m)
Impedance (Ohm))
1 10 31.25 100 300 500
20.0 25.0 23.6 20.1 17.3 17.3
3.7 5.8 10.4 19.0 34.2 45.2
74.3 59.3 51.9 44.3 37.1 33.8
72.3 57.3 49.9 42.3 35.1 31.8
55.9 47.8 37.9 27.8 18.1 14.0
100 ± 15 100 ± 15 100 ± 15 100 ± 15 100 ± 25 100 ± 15
Cat 7 cables
BT Cables Part Number
Type
C1039
S-FTP
Cat 7 Variants Overall Diameter Sheath (mm)
Weight (kg/km)
7.8
HFFR
67.5
Main Transmission Characteristics of Cat 7 S-FTP cables Frequency (MHz)
Return Loss (dB/100m)
Attenuation (dB/100m)
NEXT (dB)
PSNEXT (dB)
ELFEXT (dB)
Impedance (Ohm)
1 10 20 62.5 300 600
20.0 25.0 25.0 21.5 14.5 12.5
2.5 6.5 8.9 14.9 35.2 50.1
78 78 78 75.5 65.2 60.7
75 75 75 72.5 62.2 57.7
78.0 56.5 56.5 56.8 25.0 16.0
100 ± 15 100 ± 15 100 ± 15 100 ± 15 100 ± 25 100 ± 25
Cat 7a cables
BT Cables Part Number
Type
C1201
S-FTP
Cat 7a Variants Overall Diameter Sheath (mm)
Weight (kg/km)
8.5
HFFR
71.1
Main Transmission Characteristics of Cat 7a S-FTP cables Frequency (MHz)
Return Loss (dB/100m)
Attenuation (dB/100m)
NEXT (dB)
PSNEXT (dB)
ACR (dB)
Impedance (Ohm)
4 10 20 62.5 300 600 900 1000
23.0 25.0 25.0 21.5 17.3 17.3 17.3 16.0
4.0 5.8 8.2 14.6 32.7 47.1 54.9 61.9
80.0 80.0 80.0 80.0 71.2 66.7 64.9 63.4
77.0 77.0 77.0 77.0 68.2 63.7 61.9 60.4
78.0 74.3 71.0 60.6 38.6 19.6 9.93 1.47
100 ± 15 100 ± 15 100 ± 15 100 ± 15 100 ± 25 100 ± 25 100 ± 25 100 ± 25
For more details, please see the respective detailed datasheet(s).
info.btcables@bt.com
35
Section 6.3 – BT Data-Tec™ - Category LAN Cables Cat 5e and Cat 6 UTP and FTP PATCH Cables
Cat 5e and Cat6 Patch cables
BT Cables Part Number
Type
C1500 C1510 C1520 C1530
UUTP UUTP FUTP FUTP
Cat 5e Variants Overall Diameter Sheath (mm)
Weight (kg/km)
5.2 5.2 5.1 5.1
PVC HFFR PVC HFFR
30.7 31.4 31.2 31.1
Main Transmission Characteristics of Cat 5e Patch cables Cat 5e - Patch
UTP / FTP
Frequency (MHz)
Return Loss (dB/100m)
1 4 8 10 16 20 25 31.25 62.5 100
20.0 23.0 24.5 25.0 25.0 25.0 24.2 23.3 20.7 19.0
UTP
FTP Maximum Attenuation (dB/100m)
2.4 4.9 6.9 7.8 9.9 11.1 12.5 14.1 20.4 26.4
3.1 6.1 8.6 9.7 12.4 13.9 15.6 17.6 25.5 33.0
UTP / FTP
UTP / FTP
UTP / FTP
UTP / FTP
Minimum NEXT (dB)
Minimum PSNEXT (dB)
Minimum ELFEXT (dB)
Minimum PSELFEXT (dB)
65.3 56.3 51.8 50.3 47.2 45.8 44.3 42.9 38.4 35.3
62.3 53.3 48.8 47.3 44.2 42.8 41.3 39.9 35.4 32.3
63.8 51.8 45.7 43.8 39.7 37.8 35.8 33.9 27.9 23.8
60.8 48.8 42.7 40.8 36.7 34.8 32.8 30.9 24.9 20.8
Cat 6 Patch cables
BT Cables Part number
Type
C1540 C1550 C1560 C1570
UUTP UUTP FUTP FUTP
Cat 6 Variants Overall Diameter Sheath (mm)
Weight (kg/km)
5.9 5.9 6.2 6.2
PVC HFFR PVC HFFR
31.6 32.4 34.6 35.8
Main Transmission Characteristics of Cat 6 Patch cables Cat 6 - Patch
UTP / FTP
Frequency (MHz)
Return Loss (dB/100m)
1 4 10 16 20 31.25 62.5 100 200 250
20.0 23.0 25.0 25.0 25.0 23.3 20.7 19.0 16.4 15.5
UTP
FTP Maximum Attenuation (dB/100m)
2.4 4.6 7.2 9.1 10.2 12.9 18.6 23.9 35.0 39.4
3.1 6.1 8.6 12.4 13.9 17.6 25.5 33.0 48.6 55.3
UTP / FTP
UTP / FTP
UTP / FTP
UTP / FTP
Minimum NEXT (dB)
Minimum PSNEXT (dB)
Minimum ELFEXT (dB)
Minimum PSELFEXT (dB)
74.3 65.3 59.3 56.2 54.8 51.9 47.4 44.3 39.8 38.3
72.3 63.3 57.3 54.2 52.8 49.9 45.4 42.3 37.8 36.3
67.8 56.0 48.0 43.9 42.0 38.1 32.1 28.0 22.0 20.0
64.8 53.0 45.0 40.9 39.0 35.1 29.1 25.0 19.0 17.0
For more details, please see the respective detailed datasheet(s).
info.btcables@bt.com
36
Section 6.4 – BT Data-Tec™ - Category LAN Cables Cat 3 multi pair Cables Cat 3 cables
BT Cables Part Number
No. of pairs
C1031 C1266 C1267 C1032 C1033 C1034 C1268 C1269
2 6 12 25 50 100 150 200
Cat 3 cables Nom. Nom. Diameter Diameter Conductor Insulation (mm) (mm)
0.5 0.5 0.5 0.5 0.5 0.5 0.5 0.5
Nom. Overall Diameter (mm)
0.9 0.9 0.9 0.9 0.9 0.9 0.9 0.9
3.6 5.5 7.4 11.8 15.5 21.6 26.8 29.4
Weight (kg/km)
16 39 73 154 280 530 800 1040
Electrical Characteristics Cat 3 cables at 20° Frequency
Max. Attenuation
Max. NEXT
Min. Return Loss
Impedance
MHz 1 4 8 10 16
(dB/100m) 2.6 5.6 8.5 9.7 13.1
(dB) 41.3 32.3 27.8 26.3 23.3
(dB) 12.0 12.0 12.0 12.0 10.0
(Ohm) 100 ± 15 100 ± 15 100 ± 15 100 ± 15 100 ± 15
Cable Make-Up Cat 3 cables C1031
C1266
C1267
C1032
C1033
C1034
C1268
C1269
2
6
12
25
50
100
150
200
Number of pairs per unit
25
10
25
25
25
Number of units in the centre
1
5
4
1
1
5
7
BT Cables Part Number No of pairs
Number of units in the 1e layer Pair Colour Code Cat 3 cables Pair No.
Pair Colours in 2 – 6 -12 or 25 pairs cables
Pair No.
Pair Colours in Unit of 12 or 25 pairs
Pair No.
Pair Colours in Unit of 25 pairs
1
White / Blue
11
Black / Blue
21
Purple / Blue
2
White / Orange
12
Black / Orange
22
Purple / Orange
3
White / Green
13
Black / Green
23
Purple / Green
4
White / Brown
14
Black / Brown
24
Purple / Brown
5
White / Grey
15
Black / Grey
25
Purple / Grey
6
Red / Blue
16
Yellow / Blue
7
Red / Orange
17
Yellow / Orange
8
Red / Green
18
Yellow / Green
9
Red / Brown
19
Yellow / Brown
10
Red / Grey
20
Yellow / Grey
For more details, please see the respective detailed datasheet(s).
info.btcables@bt.com
37
Section 7 – BT Industrial-Tec™ - DEF Standard Cables
DEF Standard 51-12 Parts 4 & 5 1. Application Originally developed for military use, these flexible multi-conductor cables are now widely used within the industry. They are designed for high density wiring between and within instruments and electronic equipment and/or components and especially used in process control systems, computers, data processors, sound systems and of course in military equipment. 2. Main Standard DEF standard 61-12, part 4 and 5. 2. Basic Construction of the cables Wire = Conductor with Insulation. Conductor: flexible = stranded tinned copper wires. Size configuration Max. DC Resistance Max. recommended current Rated Voltage
mm2 mm Ω/km Amps Vrms
0.055 7 x 0.1 345 0.25 250
0.22 7 x 0.2 86.2 1 440
0.5 16 x 0.20 37.7 2.5 440
Insulation: PVC (Polyvinyl Chloride). Good strippable and coloured insulation. The colours are not interchangeable. Cable core: two or more wires, stranded. Colour scheme: Core No. 1 2 3 4 5 6 7 8 9 10
Color Red Blue Green Yellow White Black Brown Violet Orange Pink
Core No. 11 12 13 14 15 16 17 18 19 20
Color Turquoise Grey RED/Blue GREEN/Red YELLOW/Red WHITE/Red RED/Black RED/Brown YELLOW/Blue WHITE/Blue
Core No. 21 22 23 24 25 26 27 28 29 30
Color BLUE/Black ORANGE/Blue GREEN/Blue GREY/Blue YELLOW/Green WHITE/Green GREEN/Black ORANGE/Green GREY/Green YELLOW/Brown
Core No. 31 32 33 34 35 36
Color
50
WHITE/Brown BROWN/Black GREY/Brown YELLOW/Violet VIOLET/Black WHITE/Violet Special scheme, on request available
Drain wire (only in combination with a screen): twisted (= flexible) tinned copper wires. Screen (if applicable): Braiding of tinned copper wires, coverage 91%. Sheath: grey PVC. Flame Retardancy: IEC 60332-1 (Vertical Wire test). Operating temperature range: -20 to +70 °C.
Non-standard cable constructions, colours, details and/or additional information are available on request. For more details, please see the respective detailed datasheet(s). Please note that technical specifications are subject to change without notice.
info.btcables@bt.com
38
Section 7 – BT Industrial-Tec™ - DEF Standard Cables
CABLE DESCRIPTION 1. Conductor Stranded Tinned Copper
4. Screen (if required) Tinned Copper 91% Coverage
Standard Put Up Length 305 metres
2. Insulation PVC
5. Ripcord
Standard References DEF standard 61-12, part 4 & 5 IEC 60332-1 RoHS directives
6. Sheath Material Flame-Retardant Polyvinyl Chloride (PVC) Standard colour: grey
3. Cable core) Two or more wires stranded
No of wires 2 3 4 6 9 15 25 36 50
BT Cables Part Number C1164 C1165
No of wires 2 3 4 6 8 12 20 36
BT Cables Part Number
No of wires 2 3 4 6 12 18
BT Cables Part Number
C1166
C1168 C1169 C1365
C1471 C1472 C1473 C1474 C1475 C1476
C1177 C1178 C1375 C1180
Conductor 7 x 0.1 mm = 0.055 mm² Diameter BT Cables Screen (mm) Part Number Yes 3.2 C1360 Yes 3.6 C1361 C1362 Yes 4.2 C1144 C1145 C1146 Yes 6.3 C1147 Yes 6.9 C1148 Yes 8.0 C1364
Conductor 7 x 0.2 mm = 0.22 mm² Diameter BT Cables Screen (mm) Part Number C1366 C1367 Yes 4.4 C1368 Yes 5.6 C1369 Yes 6.1 C1154 Yes 6.9 C1155 Yes 8.6 C1156 Yes 10.8 C1157
Conductor 16 x 0.2 mm = 0.5 mm² Diameter BT Cables Screen (mm) Part Number C1158 C1370 Yes 7.3 C1371 Yes 8.3 C1372 Yes 10.5 C1373 Yes 12.0 C1374
Screen No No No No No No No No No
Screen No No No No No No No No
Screen No No No No No No
Diameter (mm) 2.3 2.4 2.6 3.1 3.7 4.2 5.5 6.1 7.2
Diameter (mm) 3.4 3.6 3.9 4.6 5.6 6.1 7.8 9.8
Diameter (mm) 5.5 5.8 6.3 7.3 9.5 11.0
For more details, please see the respective detailed datasheet(s)
info.btcables@bt.com
39
8 – BT Industrial-Tec™ - Industrial Cables Section
Application and Construction 1. Application These cables are generally used to transmit analogue or digital signals in industrial process plants where chemical and mechanical protections are needed (chemical and petrochemical industries). The unarmoured versions (Type 1) are generally use for indoor installation. 2. Main Standard BS(PAS) 5308 – Part 2 – Type 1 & 2. 2. Basic Construction of the cables Wire = Conductor with Insulation. Conductor: flexible = stranded tinned copper wires. Pair: two twisted wires. mm2 mm Ω/km °C °C Amps pF/m μH/Ω Vrms
Conductor Size configuration Max. DC Resistance at 20°C Max. conductor temperature Min. operating temperature Max. recommended current Max. mutual capacitance at 1 kHz Max. L/R ratio Rated Voltage
0.5 16 x 0.2 39.7 65 -20 6 250 25 300 / 500
0.75 24 x 0.2 26.5 65 -20 8 250 25 300 / 500
1.5 7 x 0.53 12.3 65 -20 12 250 40 300 / 500
Insulation: PVC (Polyvinyl Chloride) in accordance with BS 7655. Good strippable and coloured insulation. The colours are not interchangeable. Cable core: two or more pairs, stranded. Colour scheme: Pair No. a-wire b-wire Pair No. a-wire b-wire
1 White Blue 11 Black Blue
2 White Orange
12 Black Orange
3 White Green 13 Black Green
4 White Brown 14 Black Brown
5 White Grey 15 Black Grey
6 Red Blue 16 Yellow Blue
7 Red Orange
17 Yellow Orange
8 Red Green 18 Yellow Green
9 Red Brown 19 Yellow Brown
10 Red Grey 20 Yellow Grey
Drain wire (only in combination with an individual or collective screen): stranded tinned copper wires. Individual Screen (if applicable): Aluminium/Polyester (Alpet) tape. Coverage ≥ 115%. Collective Screen (if applicable): Aluminium/Polyester (Alpet) tape. Coverage ≥ 115%. Bedding (if applicable): Flame Retardant PVC. Armour (if applicable): galvanised steel wires. Sheath: Flame Retardant PVC. Flame Retardancy: IEC 60332-1 (Vertical Wire test).
Non-standard cable constructions, colours, details and/or additional information are available on request. For more details, please see the respective detailed datasheet(s). Please note that technical specifications are subject to change without notice.
info.btcables@bt.com
40
8 – BT Industrial-Tec™ - Industrial Cables Section
BS(PAS) 5308 - Part 2 – Type 1 – Collectively Screened Cables Conductor 0.5 mm² (16 x 0.2 mm) No of pairs 1 2 5 10 20
BT Cables Part Number C1081 C1082 C1083 C1084 C1085
Armour No No No No No
Diameter (mm) 7.0 7.9 13.1 17.2 22.3
Weight (kg/km 50 72 170 290 500
BT Cables Part Number C1096 C1092 C1093 C1094 C1095
Armour Yes Yes Yes Yes Yes
Diameter (mm) 11.4 12.3 17.9 22.9 29.1
Weight (kg/km) 240 290 510 880 1500
Diameter (mm) 11.7 12.9 19.8 25.3 31.3
Weight (kg/km) 270 310 710 1200 1700
Diameter (mm) 12.9 14.3 22.1 28.4 35.7
Weight (kg/km) 300 390 870 1500 2400
Conductor 0.75 mm² (24 x 0.2 mm) No of pairs 1 2 5 10 20
BT Cables Part Number C1086 C1087 C1088 C1089 C1090
Armour No No No No No
Diameter (mm) 7.3 8.3 14.3 18.7 24.5
Weight (kg/km 60 100 210 350 750
BT Cables Part Number C1101 C1102 C1103 C1104 C1105
Armour Yes Yes Yes Yes Yes
Conductor 1.5 mm² (7 x 0.53 mm) No of pairs 1 2 5 10 20
BT Cables Part Number C1091 C1092 C1093 C1094 C1095
Armour No No No No No
Diameter (mm) 8.3 9.7 16.4 20.6 28.5
Weight (kg/km 90 140 330 580 1100
BT Cables Part Number C1106 C1107 C1108 C1109 C1110
Armour Yes Yes Yes Yes Yes
For more details, please see the respective detailed datasheet(s)
info.btcables@bt.com
41
8 – BT Industrial-Tec™ - Industrial Cables Section
BS(PAS) 5308 - Part 2 – Type 1 – Individually & Collectively Screened Cables Conductor 0.5 mm² (16 x 0.2 mm) No of pairs 2 5 10 20
BT Cables Part Number C1111 C1112 C1113 C1114
Armour No No No No
Diameter (mm) 12.0 15.2 21.1 27.3
Weight (kg/km 100 250 480 780
BT Cables Part Number C1123 C1124 C1125 C1126
Armour Yes Yes Yes Yes
Diameter (mm) 16.8 20.9 27.9 34.4
Weight (kg/km) 450 750 1300 1900
Diameter (mm) 17.6 22.0 29.5 37.8
Weight (kg/km) 490 801 1800 2200
Diameter (mm) 20.4 25.4 33.5 42.6
Weight (kg/km) 660 1000 1700 2800
Conductor 0.75 mm² (24 x 0.2 mm) No of pairs 2 5 10 20
BT Cables Part Number C1115 C1116 C1117 C1118
Armour No No No No
Diameter (mm) 12.8 16.3 22.7 29.8
Weight (kg/km 190 270 550 960
BT Cables Part Number C1127 C1128 C1129 C1130
Armour Yes Yes Yes Yes
Conductor 0.75 mm² (24 x 0.2 mm) No of pairs 2 5 10 20
BT Cables Part Number C1119 C1120 C1121 C1122
Armour No No No No
Diameter (mm) 14.7 18.8 26.5 34.4
Weight (kg/km 250 460 760 1350
BT Cables Part Number C1131 C1132 C1133 C1134
Armour Yes Yes Yes Yes
For more details, please see the respective detailed datasheet(s)
info.btcables@bt.com
42
Section 9 - BT Industrial-Tec™ -– Control Cables
Application and Construction 1. Application These cables are commonly used as interconnecting cables to control, measure and regulate processor aided production within the industry and also as flexible power control cables suitable for robotic and automated equipment. 2. Main Standard VDE 0250/VDE 0255 2. Basic Construction of the cables Wire = Conductor with Insulation. Conductor: flexible = stranded tinned copper wires. Conductor Size Conductor material configuration Max. DC Resistance at 20°C
mm2
0.75
1.0
mm Ω/km
24x0.2 27
32x0.2 20.2
1.5 2.5 bare copper 30x0.24 50x0.24 8.4 14
4
6
56x0.29 4.95
84x0.29 3.3
Insulation: Flame Retardant PVC (Polyvinyl Chloride). Insulation Resistance > 500 MΩ/km. Good strippable insulation. Conductor Size Radial thickness insulation
mm2 mm
0.75 0.5
1.0 0.5
1.5 0.4
2.5 0.5
4 0.8
6 0.7
Cable core: three or more wires stranded. In case of 5 wires with a central filler. Colour scheme: Green/yellow - black with printed numbers. Collective Screen (CY series): braiding of tinned copper wires with a coverage of 70%. Bedding (SY series): Flame Retardant PVC. Armour (SY series): galvanised steel wires. Sheath: Flame Retardant PVC. Flame Retardancy: IEC 60332-1 (Vertical Wire test). Operating temperature range: -20 to +70 °C. Rated Voltage: 300 V. Cable Types: YY series: three or more stranded cores, surrounded by a PVC sheath. CY series: as YY series plus a collective screen between cable core and PVC sheath. SY series: as YY series plus a Steel Wire Armouring between cable core and transparent PVC sheath.
Non-standard cable constructions, colours, details and/or additional information are available on request. For more details, please see the respective detailed datasheet(s). Please note that technical specifications are subject to change without notice.
info.btcables@bt.com
43
Section 9 - BT Industrial-Tec™ -– Control Cables
YY Series: Cable core of stranded cores surrounded by a PVC sheath No of wires
BT Cables Part Number
3 4 12 18
C1631 C1635 C1645 C1648
No of wires
BT Cables Part Number
3 4 5 7 8 12 18
C1633 C1637 C1639 C1641 C1643 C1646 C1649
Conductor (mm² / mm) 0.75 / 24x0.2 0.75 / 24x0.2 0.75 / 24x0.2 0.75 / 24x0.2
Diameter (mm) 5.6 6.6 10.4 12.4
Conductor (mm² / mm) 1.5 / 30X0.24 1.5 / 30X0.24 1.5 / 30X0.24 1.5 / 30X0.24 1.5 / 30X0.24 1.5 / 30X0.24 1.5 / 30X0.24
Diameter (mm) 6.5 7.6 8.4 9.5 10.4 12.4 14.5
BT Cables Part Number C1632 C1636
BT Cables Part Number C1634 C1638 C1640 C1642 C1644 C1647 C1650
Conductor (mm² / mm) 1.0 / 32X0.2 1.0 / 32X0.2
Diameter (mm) 6.2 7.1
Conductor (mm² / mm) 2.5 / 50X0.24 2.5 / 50X0.24 2.5 / 50X0.24 2.5 / 50X0.24 2.5 / 50X0.24 2.5 / 50X0.24 2.5 / 50X0.24
Diameter (mm) 6.5 9.1 10.3 11.8 12.6 14.9 14.5
CY Series: Cable core of stranded cores surrounded by a braiding of tinned copper wires plus a PVC sheath No of wires
BT Cables Part Number
3 4
C 1620 C1624
No of wires
BT Cables Part Number
3 4 5
C1622 C1626 C1628
Conductor (mm² / mm) 0.75 / 24x0.2 0.75 / 24x0.2
Diameter (mm) 6.0 6.7
Conductor (mm² / mm) 1.5 / 30X0.24 1.5 / 30X0.24 1.5 / 30X0.24
Diameter (mm) 6.8 7.6 8.2
BT Cables Part Number C1621 C1625 BT Cables Part Number C1623 C1627 C1629
Conductor (mm² / mm) 1.0 / 32X0.2 1.0 / 32X0.2
Diameter (mm) 6.4 7.0
Conductor (mm² / mm) 2.5 / 50X0.24 2.5 / 50X0.24 2.5 / 50X0.24
Diameter (mm) 8.0 9.0 9.8
For more details, please see the respective detailed datasheet(s)
info.btcables@bt.com
44
Section 9 - BT Industrial-Tec™ -– Control Cables
SY Series: Cable core of stranded cores surrounded by a bedding, a Steel Wire Armouring plus a PVC sheath No of wires
BT Cables Part Number
3 4
C1655
No of wires
BT Cables Part Number
2 3 4 5 6 7 12 18 25 No of wires
BT Cables Part Number
3 4
C1659 C1663
Conductor (mm² / mm) 0.75 / 24x0.2
Diameter (mm) 7.8
C1651 C1656 C1660 C1665
Conductor (mm² / mm) 1.0 / 32X0.2 1.0 / 32X0.2 1.0 / 32X0.2 1.0 / 32X0.2
Diameter (mm) 8.2 8.2 8.2 10.6
C1669 C1671 C1673 C1675
1.0 / 32X0.2 1.0 / 32X0.2 1.0 / 32X0.2 1.0 / 32X0.2
11.7 13.8 15.8 19.7
Conductor (mm² / mm) 4.0 / 56x0.29 4.0 / 56x0.29
Diameter (mm) 13.4 13.4
BT Cables Part Number C1658 C1662 BT Cables Part Number C1652 C1657 C1661 C1666 C1668 C1670 C1672 C1674
BT Cables Part Number C1664
Conductor (mm² / mm) 2.5 / 50X0.24 2.5 / 50X0.24
Diameter (mm)
Conductor (mm² / mm) 1.5 / 30X0.24 1.5 / 30X0.24 1.5 / 30X0.24 1.5 / 30X0.24 1.5 / 30X0.24 1.5 / 30X0.24 1.5 / 30X0.24 1.5 / 30X0.24
Diameter (mm) 9.4 9.4 9.4 11.2 12.3 12.4 14.3 16.8
Conductor (mm² / mm)
Diameter (mm)
6.0 / 84X0.29
16.0
For more details, please see the respective detailed datasheet(s)
info.btcables@bt.com
45
GENERAL TECHNICAL INFORMATION American Wire Gauge (AWM) Conductors (of bare or tinned copper) Flexible Conductors
AWG
24
Number of strands
22
20
18
16
14
12 19
7
7
7
7
19
19
Gauge single strand
AWG
32
30
28
26
29
27
25
Diameter single strand
mm
0.2
0.25
0.32
0.40
0.28
0.36
0.45
Solid Conductors
AWG
Diameter
mm
24 0.51
22
20
0.64
18
0.81
1.02
16
14
1.29
12
1.63
2.05
All Conductors
AWG
24
22
20
18
16
14
12
Cross section
mm²
0.20
0.32
0.52
0.82
1.37
2.08
3.31
Max. DC resistance
Ω/km
88
57.4
32.16
22.7
15.47
9.36
5.61
Max. Recommended current 2 or 3 core cable
Amps
2.7
2.8
3.75
5
6.25
8
12
Max. Recommended current 4 or 5 core cable
Amps
2.2
2.25
3
4
5
6.4
9.6
Max. Recommended current 6 to 19 core cable
Amps
1.9
1.95
2.6
3.5
4.35
5.6
8.4
Max. Recommended current 20 to 36 core cable
Amps
1.35
1.4
1.65
2.5
3.12
4
6
Metric Conductors (of bare copper according to IEC 60228) Conductor
mm²
0.75
1.0
1.5
2.5
4.0
Max. Recommended current 2 or 3 core cable
Amps
≤5
≤ 5.70
≤ 6.25
≤8
≤ 12
Flexible Conductors, class 2
mm²
0.055
0.22
0.50
0.75
1.0
1.5
2.5
4.0
6.0
7
7
7
7
7
7
7
7
7
mm
0.1
0.2
Max. DC resistance
Ω/km
345
86.2
36.0
24.5
18.1
12.1
7.41
4.61
3.08
Flexible Conductors, class 5
mm²
0.055
0.22
0.50
0.75
1.0
1.5
2.5
4.0
6.0
16
24
32
30
50
56
84
mm
0.2
0.2
0.2
0.24
0.24
0.29
0.29
Max. DC resistance
Ω/km
39.0
26.0
19.5
13.3
7.98
4.95
3.30
Max. Recommended current 2 or 3 core cable
Amps
2.7
2.8
3.75
5
6.25
8
12
Max. Recommended current 4 or 5 core cable
Amps
2.2
2.25
3
4
5
6.4
9.6
Max. Recommended current 6 to 19 core cable
Amps
1.9
1.95
2.6
3.5
4.35
5.6
8.4
Max. Recommended current 20 to 36 core cable
Amps
1.35
1.4
1.65
2.5
3.12
4
6
Number of strands Diameter single strand
Number of strands Diameter single strand
0.53
All conductors in BT Cables are in accordance with above tables unless otherwise stated in the respective section of this publication or datasheets.
info.btcables@bt.com
46
Pairs: all pairs consist of two twisted wires with a lay-length < 40 D. Cable Cores: all cable cores consist of stranded wires or pairs Foil screens for multi-core and multi-pair cables, screens or shields mostly consist of an aluminium foil laminated to polyester, broadly known as Alpet. These foils are helically (as a spiral) applied with sufficient overlap to guarantee 115 % or more coverage. . For the flexibility of a cable a helically applied foil is to be preferred. A longitudinally applied foil act more as a stiff tube = more difficult to bend. A drain wire or continuity wire, contacting the aluminium side of the foil, is used for the termination of the screen and also to ground electrostatic discharges. In case the screen of a coaxial cable where the screen may be a foil, this foil will be applied longitudinally and will also be bonded to the dielectric around the conductor. Braided screens consist of 16 or 24 groups of strands. One set of 8 or 12 strands is woven clockwise and the other set of 8 or 12 strands anti-clockwise. Strands can consist of tinned or bare copper or aluminium wires. Braided screens provide good screening efficiency and flexibility. Higher coverage provides better screening. Sheaths: grey PVC, purple HFFR or black for PE, all in accordance with BS EN 50290-2. Sheath
PVC
Physical properties Retardancy Retardancy acc. to Low Smoke Halogen-free (non acid, non toxic) RoHS compliant Installation **
BS EN 50290-2-22 Flame IEC 60332-1 Not applicable Not applicable YES INDOOR
PVC Alarm cables UL444 Fire UL1666 Not applicable Not applicable YES INDOOR
HFFR
PE
BS EN 50290-2 Fire IEC 60332-3C IEC 61034 IEC 60754 YES INDOOR
BS EN 50290-2 Not applicable Not applicable Not applicable Not applicable YES OUTDOOR
** on request cables with a sheath for in- & outdoor = universal use available.
RoHS Limits for Hazardous Substances Substance
Max. Concentration
Lead (Pb) Mercury (Hg) Cadmium (Cd) Chromium 6 PBB PBDE
0.03% 0.10% 0.01% 0.1% 0.1% 0.1%
Unless so marked, all BT Cables do not contain restricted or hazardous substances and are compliant with the European Regulations or Directives for RoHS (Restriction of Hazardous Substances), REACH (Regulation Registration, Evaluation, Authorisation and Restriction of Chemical substances), WEEE (Waste Electrical and Electronic Equipment ), ELV (End of Life Vehicles) and BFR (Brominated Flame Retardants).
RS Protocol Differential Max. number of drivers Max. number of receivers Modes of operation Network topology Max. distance acc. to standard Max. speed at 12 m. Max. speed at 1200 m. Cables used BT Cables main part numbers see
RS-232 no
RS-422 yes
RS-485 yes
1 1 full duplex point-to-point 15 m 20 kbs 1 kbs
1 10 half duplex multidrop 1200 m 10 Mbs 100 kbs mainly 24AWG conductors. Two pairs or more. 100 ohm section 1.2
1 32 half duplex multidrop 1200 m 35 Mbs 100 kbs mainly 24AWG conductors. One pair or more. 120 ohm section 1.1
6 to 25 conductors. No impedance specified section 1.3
info.btcables@bt.com
47
Nominal Attenuation in dB/100m for RG Coaxial Cables MHz RG-59 RG-6 RG-11
1 0.98 0.79 0.53
5 2.07 1.71 1.12
10 2.95 2.33 1.51
50 6.23 4.57 2.96
100 7.55 6.40 4.20
300 13.68 11.96 7.49
550 18.83 15.76 10.41
750 22.23 18.05 12.38
1000 25.96 21.36 14.57
2000 38.24 31.44 21.84
3000 46.13 39.76 27.93
4500 56.50 50.46 35.98
COMPARISON BETWEEN EUROPEAN AND UNITED STATES CABLE DESIGN BASICS Europe
USA
Focus on SAFETY = SAVING LIVES Low Voltage Directive 220 Volt, 50 Hz More radial thickness of insulation IEC-EN and National Standards Cable specs. in mm, N, etc. 70 °C (is equal to 80 °C in USA) 300 / 500 Vrms 450 / 750 Vrms IEC 60332-1 IEC 60332-3-24 (former 3C)
Focus Directives Power supply system Cable basics Standards Units Temperature Ratings Voltage Ratings Retardancy levels Environmental requirements
RoHS compliant CE Marking The CE marking certifies that a product has met EU consumer safety, health or environmental requirements. By affixing the CE marking to a product, the manufacturer – on his sole responsibility – declares that it meets EU safety, health and environmental requirements or, if stipulated in the directive(s), it had to be examined by a notified conformity assessment body.
Quality assurance
Focus on REDUCING INSURANCE CLAIMS National Electrical Code 120 Volt, 60 Hz More copper in conductors UL standards Cable specs. in inches, lbs, etc. 80 °C (Is equal to 70 °C in Europe) 300 Vrms 600 Vrms UL1581 – VW-1 UL1685 A number of states banned Hg and PBDE UL Approval / Listing UL does not approve products. Rather it evaluates products for compliance to specific requirements, and permits acceptable products to carry a UL certification mark, as long as they remain compliant with the standards. Products under its listing service are said to be “UL Listed,” identified by the distinctive UL mark.
CONVERSIONS Europe 1 mm = 0.03937 inches 1 m = 3.2808 feet (305 m = 1000 feet) 1 m = 1.0936 feet 1 km = 0.6214 miles 1 kg/km = 0.6719 lbs/1000 ft 1 ohm/km = 0.3048 ohm/1000 ft 1 N = 0.2248 lbs force -40 °C = -40 °F -30 °C = -22 °F 0 °C = 32 °F 60 °C = 90 °F 75 °C = 167 °F 90 °C = 194 °F
USA 1 inch = 25,4 mm 1 feet = 0.3048 m 1 yard = 0.9144m 1 mile = 1.6093 km 1 lbs/1000 ft = 1.488 kg/km 1 ohm/1000 ft = 3.2808 ohm/km 1 lbs force = 0.2248 N -40 °F = -40 °C -22 °F = -30 °C 32 °F = 0 °C 90 °F = -60 °C 167 °F = -75 °C 194 °F = -90 °C
info.btcables@bt.com
48
Area Conversions From Circular mils Square inches mm² Square feet
To Square inches
Multiply by 0.0000007854
To Square mils
Multiply by 0.7854
To mm²
Multiply by 0.0005067
Circular mils
1,273.240
Square mils
1,000,000.00
mm²
645.16
Square inches Square meters
0.00155 0.0929
Square mils
1550.01
Circular mils
1,973.53
Common Wire Conversions AWG Cir. mils mm²
24 404 0.205
22 640 0.324
987 0.5
20 1029 0.521
19/18 1481 0.75
18 1620 0.821
18/17 1974 1.0
AWG Cir. mils mm²
16 2580 1.371
15/16 2961 1.5
14 4110 2.082
14/13 4935 2.5
12 6530 3.309
7896 4.0
11 8230 4.170
Force, Mass and Weight Conversion From Pounds Pound per 1000 ft Pound-force
To Kilograms Kilogram per kilometre Newton
Multiply by 0.4535 1.488 4.4482
From Kilograms Kilogram per kilometre Newton
info.btcables@bt.com
To Pounds
Multiply by 2.205
Pound per 1000 ft
0.6719
Pound-force
0.2248
49
GLOSSARY Cat 8 Cable supports frequencies up to 1200 Mhz. Under development. No applications yet.
A = Amp: Ampere = unit of electric current. AC: Alternating current, e.g. 50 or 60 Hz AC power. ACR: Attenuation Crosstalk Ratio. The difference between attenuation and crosstalk. Important characteristic in transmission to assure that the transmitted signal is stronger at the receiving end of the cable than are any interference signals imposed on that same pair by crosstalk from other pairs. Alpet: aluminium foil covered with polyester.
CATV: Community Antenna Television, also often used to mean Cable TV. It is a system of providing television to consumers through or optical fibre cables. High-speed Internet, telephony, and similar non-television services may also be provided. CCTV: Closed-circuit television is the use of video cameras to transmit a signal to a specific place, on a limited set of monitors. Circuit integrity refers to the operability of electrical circuits during a fire. It is a form of fire-resistance rating.
Alu braid: braiding of woven aluminium wires ANSI: American National Standards Institute Attenuation: The gradual loss in intensity of signals in electrical circuits. AWG: American wire gauge, is a standardized wire gauge system used since 1857 predominantly in the United States and Canada for the diameters of round, solid, nonferrous, electrically conducting wire. BT Cables: a leading manufacturer of communication cables. B.C. = BC: Bare Copper, mostly referring to a conductor or braid. Bending radius: the radius that a cable can be bent without any detrimental effects on transmission performance.
Coaxial Cable or coax: an electrical cable with a centre conductor surrounded by a tubular insulating layer = the dielectric, surrounded by a tubular conducting screen = the outer conductor, surrounded by an outer sheath. The term coaxial comes from the centre conductor and the outer screen sharing the same geometric axis. Conductor: most familiar conductors are metallic. Copper or tinned copper is the most common material used for electrical wiring. Silver is also in use as a conductor and out performs copper, but is more expensive. Continuity Wire: see Drain Wire.
Braid or Braiding: is a structure or pattern formed by intertwining of commonly 16 or 24 strands of wires.
Crosstalk (XT): any phenomenon by which a signal transmitted on one circuit of a transmission system creates an undesired effect in another circuit. Crosstalk is usually caused by undesired capacitive, inductive, or conductive coupling from one circuit (mostly a pair) to another (pair).
B.S: British Standards are the standards produced by BSI Group which is incorporated under a Royal Charter (and which is formally designated as the National Standards Body (NSB) for the UK).
Current: electric current is a flow of electric charge through a medium. This flowing electric charge is typically carried by moving electrons in a conductor such as wire. The unit of current is Ampere.
Cable core: two or more wires or pairs stranded. Good twisting is necessary otherwise the cable can hardly be bent and will lose performance after a few bends.
DC Resistance: the resistance of an object is defined as the ratio of voltage across it to the direct current through it. The unit of resistance is Ohm.
Category cables: high performance twisted pair cables for local area networking = structured wiring or cabling. Cables range from Cat 3 to Cat 7a. The higher the number, the greater the bandwidth and the better the performance.
Dielectric: the insulation between centre and outer conductor (screen) of coaxial cables. Mostly solid or foam (= cellular) polyethylene (PE).
Cat 3 Cable supports 10 Base-T Standard for bandwidths up to 10 Mbps over a maximum distance of 100 meters. They can support frequencies up to 10 Mhz. Cat 5/5e Cable supports 100 Base-T Standard for bandwidths up to 100 Mbps over a maximum distance of 100 meters. They can support frequencies up to 100 Mhz. Cat 5e cables can also support 1000 Base-T. Cat 6 Cable supports 1000 Base-T Standard for bandwidths up to 1000 Mbps over a maximum distance of 100 meters. Cat 6 standard can support frequencies up to 250 Mhz. They also support 10GE (10Gig Ethernet) bandwidth over limited distances. Cat 6A Cable supports 10G Base-T standard for bandwidths up to 10 Gbps over a maximum distance of 100 meters. Cat 6A standard can support frequencies up to 500 Mhz. Cat 7 Cable supports 10G Base-T standard for bandwidths up to 10 Gbps over a maximum distance of 100 meters. Cat 7 standard can support frequencies up to 600 Mhz. It offers better performance and improved cross talk suppression over the Cat 6A cables. Cat 7A Cable supports 10G Base-T standard for bandwidths up to 10 Gbps over a maximum distance of 100 meters. In addition to this, they can also support 40 Gbps bandwidth for around 50 meters and 100 Gbps bandwidth for around 15 meters. They support frequencies up to 1000 Mhz.
Distortion: the alteration of the original shape (or other characteristic) of an object, image, sound, waveform or other form of information or representation. Distortion is usually unwanted, and often many methods are employed to minimize it in practice. Drain wire: a conductor in contact with the foil (of a screen) in order to terminate the screen. Also referred to as a Continuity Wire. The preferred drain wire is tinned copper wire or wires. Decibel (dB): is a logarithmic unit that indicates the ratio of a physical quantity (usually power or intensity) relative to a specified or implied reference level. A ratio in decibels is ten times the logarithm to base 10 of the ratio of two power quantities. ELFEXT: the Equal-Level Far-End Crosstalk (ELFEXT) test measures FarEnd Crosstalk (FEXT). FEXT is very similar to NEXT, but happens at the receiver side of the connection. Due to impedance on the line, crosstalk diminishes the signal as it gets further away from the transmitter. Because of this, FEXT is usually less detrimental to a signal than NEXT, but still important nonetheless. EIA: the Electronic Industri8es Association ceased operations on 28 February 2011. The former sectors of EIA are the Electronic Components Association (ECA), JEDEC, Government Electronics and Information Technology Association (GEIA), now part of TechAmerica, Telecommunications Industry Association (TIA), and Consumer Electronics Association (CEA).
info.btcables@bt.com
50
EN: European Norms maintained by CEN (European Committee for Standardization), CENELEC (European Committee for Electrotechnical Standardization) and ETSI (European Telecommunications Standards Institute). Farad: the unit of capacitance. FPE: Foam Polyethylene (PE) = closed cells with gas in PE in order to reduce the dielectric constant. Often used as dielectric in coaxial cables. The gas may be generated by chemical decomposition during extrusion of the insulation (dielectric) referred to as chemical foaming or blowing, or by injection into the polymer melt within the extruder (physical foaming or blowing).
Lay-length: The length measured along the axis of a wire or cable required for a single strand (in stranded wire) or conductor (in cable) to make one complete turn about the axis of the conductor or cable. In a twisted pair cable, the lay length is the distance it takes for the two wires to completely twist around each other. Lay length is also known as pitch length. Local Area Network (LAN): any communication network for connecting computers within a building or small group of buildings. m = metre: S. I. unit of measure of length.
FAS Cables: cables for fire detection and alarm systems Far end crosstalk (FEXT): Interference between two pairs of a cable measured at the other end of the cable from the transmitter. FR: can mean Flame Retardant or Fire Retardant or Fire Resistant. Flame Retardant: are cables passing the vertical wire test of IEC 60332-1 or UL 1581 VW-1). Fire Retardant: are cables passing the bundle test of IEC 60332-2-24 or UL 1685 Vertical Tray. Fire Resistant are cables with a circuit integrity of a specified time. Frequency: is the number of occurrences of a repeating event per unit time. The unit of frequency is Hertz (Hz).
MHz = MegaHertz: . 1 MHz = one million Hertz. Near End Crosstalk (NEXT): Interference between two pairs in a cable measured at the same end of the cable as the transmitter. Operating temperature (range): the temperature range at which the cable can operate. Polyolefin: is a polymer produced by polymerisation of a simple olefin (also called an alkene) as a monomer, for example Polyethylene or Polypropylene. PA = Polyamide PE = Polyethylene. PP = Polypropylene. PVC = Polyvinyl Chloride. Power Sum ELFEXT (PSELFEXT): is the sum of FEXT values from 3 wire pairs as they affect the other wire pair.
G.P. Bus: General Purpose Bus Application Headroom: in case of testing category cables this is the average of the difference between worst case margin and the specified value.
Pair: two twisted insulated wires, normally colour coded. Quad: a four conductor cable core or unit, symmetrical stranded or twisted together.
Henry (H): unit of inductance. Hertz (Hz): unit of frequency. 1 Hz means that an event repeats once per second. HFFR = Halogen-Free, Flame or Fire Retardant Impedance: the ratio of voltage applied to the current is called the input impedance. The input impedance of the infinite line is called the characteristic impedance. Insertion Loss: also referred to as attenuation, refers to the loss of signal strength at the far end of a line compared to the signal that was introduced into the line. This loss is due to the electrical resistance of the copper cable, the loss of energy through the cable insulation and the impedance caused by the connectors. Insertion loss is usually expressed in decibels dB with a minus sign. Insertion loss increases with distance and frequency. For every 6dB of loss, the original signal will be half the original amplitude. Inductance: is the property of an electrical circuit causing voltage to be generated proportional to the rate of change in current in a circuit. This property also is called self inductance to discriminate it from mutual inductance, describing the voltage induced in one electrical circuit by the rate of change of the electric current in another circuit. Insulation: insulations are coatings applied to wires to isolate the conductors. Insulation materials are applied to provide good strippable and interchangeable colour. The physical properties are in accordance with BS EN 50290-2. Individually screened pair: a pair with a helically applied (= as a spiral) Aluminium/Polyester (Alpet) foil. A drain wire is normally applied under the screen to provide continuity and ease of tern=miantion.
Jacket = sheath. This is the outer protective polymer surrounding the cable core.
Rated Temperature: the maximum continuous temperature that the cable can withstand during its lifetime. It is generally limited by the thermal aging characteristics of the plastics used to insulate and/or sheath the wire. Rated Voltage: the maximum voltage at which a cable can operate for extended periods without undue degradation or safety hazard. Resistance: the electrical resistance of a conductor measures its opposition to the passage of an electric current; the inverse quantity is electrical conductance, measuring how easily electricity flows along a certain path. The unit of electrical resistance is the ohm (Ω), while electrical conductance is measured in Siemens (S). Return Loss (RL): the Return or Reflection Loss of a line is the ratio of the power reflected back from the line to the power transmitted into the line. RL is expressed in decibels (dB). The RL of coaxial cables is the loss of signal power resulting from the reflection caused at a discontinuity in the cable. This discontinuity can be fluctuations in dimensions and/or dielectric. Return Loss is also one of many parameters regulated by the requirements established for Category 5e and onwards cables. It is a measure of the reflected energy from a transmitted signal. The larger the value, the less energy that is reflected. Poor Return Loss figures of a circuit are quite often caused by poor termination (connectors). Screen: a cable screen acts as a Faraday cage to reduce electrical noise from affecting the signals, and to reduce electromagnetic radiation that may interfere with other parts in a cable or other cables. The screen minimizes capacitive coupled noise from other electrical sources. For more info regarding screens: see also the Technical Information section.
info.btcables@bt.com
51
Sheath: the outer covering of a cable, standard in accordance with BS EN 50290-2 and grey for PVC, purple for HFFR and black for PE. Shield = screen. SMATV = Satellite Master Antenna Television, and refers to a system that uses multiple satellite and broadcast signals to create a single integrated cable signal for distribution to a cabling network Solid BC: one solid conductor of bare copper. Solid TC: one solid conductor of tinned copper T.C. = TC = Tinned Copper Conductor TIA: the Telecommunications Industry Association is accredited by the American National Standards Institute (ANSI) to develop voluntary industry standards for a wide variety of telecommunications products. Twisted pair: a type of wiring in which two conductors are twisted together for the purposes of cancelling out electromagnetic interference (EMI) from external sources; for instance, electromagnetic radiation from unshielded twisted pair (UTP) cables, and crosstalk between neighbouring pairs. Volt = Voltage = unit of electric, expressed with the symbol V. Wire = Conductor with Insulation. Sometimes also indicated as Core.
info.btcables@bt.com
52
UNITED KINGDOM
EUROPE
Delaunays Road, Blackley Manchester, M9 8FP Tel: +44 161 740 9151 Fax: +44 161 795 8393 Email: info.btcables@bt.com
Madrid 28 28027 Spain Tel: +34 611370897 Fax: +44 161 795 8393 Email: info.btcables@bt.com
MIDDLE EAST
ASIA
Rawdah - Riyadh Kingdom of Saudi Arabia Tel: +966 500333786 Fax: +44 161 795 8393 Email: info.btcables@bt.com
Shenzhen – Guangdong Province People’s Republic of China Tel: +86 13923775251 Fax: +44 161 795 8393 Email: info.btcables@bt.com
www.btcables.com