Cables for BUILDING INFRASTRUCTURE SYSTEMS

Edition 1 2015

www.btcables.com


CONTENTS CABLE FINDER BT CABLES – BELDEN EQUIVALENTS SECTION 1

BT BMS-TECTM - Paired Cables

SECTION 2

BT BMS-TECTM - Multi-Conductor Cables

SECTION 3

BT FIREPRO-TEC™ – Fire Detection and Alarm System Cables

SECTION 4

BT FIREPRO-TEC™ – Fire Resistant Cables

SECTION 5

BT Security-Tec ™– Coaxial Cables

SECTION 6

BT Data-Tec™ - Category LAN Cables

SECTION 7

BT Industrial-Tec™ - DEF Standard Cables

SECTION 8

BT Industrial-Tec™ - Industrial Cables

SECTION 9

BT Industrial-Tec™ – Control Cables

GENERALTECHNICAL INFORMATION COMPARISON BETWEEN EUROPEAN AND UNITED STATES CABLE DESIGN BASICS CONVERSIONS GLOSSARY BT CABLES PART NUMBER INDEX

info.btcables@bt.com

2


TM

BT BMS-TEC Application

RS-485 RS-422 G.P. Bus RS-232 Lon Works

Cable Finder - Paired Cables

Cond.Size ↓ 24 AWG 24 AWG 22 AWG 22AWG 24 AWG 22 AWG 22 AWG 24 AWG 0.64 mm 0.64 mm

KNX

0.8 mm 0.8 mm

Security & Alarm

18 AWG

BMS

0.6 mm²

Application

G.P Bus

No. of pairs ↓ 1 1 1 1

No. of pairs → Screen Sheath

Foil+ braid every pair a foil Foil no scrn every pair a foil Foil Foil Foil + Braid Foil

1

2

3

4

PVC HFFR PVC HFFR PVC PVC HFFR PVC HFFR

C1189 C1318 C1080 C1401

C1191 C1320 C1296 C1403 C1383 C1197 C1282 C1183

C1192 C1321 C1297 C1404 C1384 C1298

C1299

C1181 C1346

C1190 C1319 C1295 C1402 C1382 C1196 C1281 C1182 C1347

C1184

C1185

HFFR

C1348

C1349

1.5

PVC HFFR HFFR

C1219 C1220 C1171

C1217 C1218 C1172

C1173

C1174

C1175

C1176

1.4 1.4 1.8

HFFR

C1418

C1419

C1420

C1421

C1422

C1423

1.8

PVC

C1381

AWG conductor size → Screen ↓ Sheath ↓ Yes PVC Yes HFFR No PVC No HFFR

5

6

7

C1386 C1214 C1314 C1186

C1187

8

Page

§

C1188

1.1 1.1 1.1 1.1 1.2 1.6 1.6 1.3 1.5

1.9

22

20

18

16

14

12

Section

C1199 C1310 C1301 C1311

C1195 C1308 C1300 C1309

C1193 C1272 C1203 C1271

C1213 C1270 C1198 C1307

C1224 C1305 C1222 C1306

C1313 C1303 C1302 C1304

1.7 1.7 1.7 1.7

Page

BT BMS-TECTM - Multi-Conductor Cables Cond. Size AWG↓ 22

20

18

16

14

12

No. of conductors 3

No. of conductors → Sheath ↓ Screen Yes PVC No Yes HFFR No Yes PVC No Yes HFFR No Yes PVC No Yes HFFR No UV-HFFR Yes Yes PVC No Yes HFFR No UV-HFFR Yes Yes PVC No Yes HFFR No Yes PVC No Yes HFFR No Conductor size → Sheath ↓ Screen PVC Yes

2

3

4

6

8

Section

C1226 C1227 C1741 C1742 C1019 C1020 C1731 C1732 C1013 C1014 C1721 C1722 C1351 C1007 C1008 C1711 C1712 C1391 C1001 C1002 C1701 C1702 C1322 C1323 C1334 C1335

C1228 C1278 C1743 C1744 C1021 C1022 C1733 C1734 C1015 C1016 C1723 C1724 C1352 C1009 C1010 C1713 C1714 C1392 C1003 C1004 C1703 C1704 C1324 C1325 C1336 C1337

C1230 C1231 C1745 C1746 C1023 C1024 C1735 C1736 C1017 C1018 C1725 C1726 C1353 C1011 C1012 C1715 C1716 C1393 C1005 C1006 C1705 C1706 C1326 C1327 C1338 C1339

C1264 C1265 C1747 C1748 C1260 C1261 C1737 C1738 C1211 C1212 C1727 C1728 C1354 C1252 C1253 C1717 C1718 C1394 C1248 C1249 C1707 C1708 C1330 C1331 C1342 C1343

C1232 C1233 C1749 C1750 C1262 C1263 C1739 C1740 C1258 C1259 C1729 C1730 C1355 C1254 C1255 C1719 C1720 C1395 C1250 C1251 C1709 C1710 C1332 C1333 C1344 C1345

2.1 2.1 2.2 2.2 2.1 2.1 2.2 2.2 2.1 2.1 2.2 2.2 2.3 2.1 2.1 2.2 2.2 2.3 2.1 2.1 2.2 2.2 2.1 2.1 2.2 2.2

22 AWG

20 AWG

18 AWG

Section

C1215

C1245

C1225

?

Page

Page

Multi-Conductor Power Limited Tray Cables (PLTC) are available on request

info.btcables@bt.com

3


BT FIREPRO-TEC™ – Fire Detection and Alarm System Cables Cond. size → Screen ↓ Sheath ↓ Yes PVC No PVC

No. of pairs ↓ 1 1

Application

Fire Alarm

AWG 18 C1040 C1135

AWG 16 C1041 C1136

AWG 14 C1042 C1137

AWG 12 C1043 C1138

Section

Page

3 3

BT FIREPRO-TEC™ – Fire Resistant Cables Application

Circuit integrity

No. of cores ↓ 1 2 2 3 3

Cond. size → Screen ↓ Sheath ↓ No HFFR Yes HFFR No HFFR Yes HFFR No HFFR

0.75 mm2

1.0 mm2

C1284 C1139 C1159 C1149

C1283 C1140 C1160 C1150

1.5 mm2 C1760 C1044 C1141 C1161 1151

2.5 mm2 C1761 C1045 C1142 C1162 C1152

4.0 mm2

Section

Page

4 4 4 4 4

C1289 C1143 C1163 C1153

BT Security-Tec ™– Coaxial Cables Application CCTV SMATV CATV HDTV

Inner Conductor Solid BC Solid BC Flex BC CCS CCS Solid BC Solid BC

Screen

Sheath

RG-59

RG-6

RG-11

Section

Braid BC Braid BC Braid BC Foil+Alu Braid Quad screen Foil+TC Braid Foil+TC Braid

PVC HFFR PVC PVC PVC PVC HFFR

C1028 C1428 C1275 C1025 C1256 C1229 C1378

C1029 C1429 C1276 C1026 C1257 C1279 C1379

C1030 C1430 C1277 C1027 C1241 C1280 C1380

5.1 5.1 5.1 5.2 5.2 5.3 5.3

Page

50 Ohm Coaxial cables are available on request

BT Data-Tec™ - Category LAN Cables Cat. type Cat 3

Sheath PVC

Cat. types

Sheath PVC HFFR PVC HFFR PVC HFFR PVC HFFR PVC HFFR HFFR HFFR

Cat 5e Cat 5epatch Cat 6 Cat 6-patch Cat 6a Cat 7 Cat 7a

2 pairs C1031 UTP C1035 C1235 C1500 C1510 C1037 C1237 C1540 C1550 C1055 C1200

6 prs C1266

12 prs C1267

UTP-UL C1285

C1287

25 prs C1032 FTP C1036 C1236 C1520 C1530 C1038 C1238 C1560 C1570 C1056 C1052

50 prs C1033 FTP-UL C1286

100 prs C1034

150 prs C1268

U-FTP

200 prs C1269 S-FTP

C1288

C1057 C1053 C1039 C1201

info.btcables@bt.com

section 6.4

Page

Section 6.1 6.1 6.3 6.3 6.1 6.1 6.3 6.3 6.2 6.2 6.2 6.2

Page

4


BT Industrial-Tec™ - DEF Standard Cables Conductor No. of cores Screened Unscreened Conductor No. of cores Screened Unscreened Conductor No. of cores Screened Unscreened

2 C1164 C1360

3 C1165 C1361

2

3

C1366

C1367

4

6

C1362

C1144

4 C1171 C1368

2

3

C1158

C1370

7 x 0.1 mm = 0.055 mm² 9 15 25 C1166 C1168 C1147 C1145 C1146

6 C1172 C1369

4 C1177 C1371

7 x 0.2mm = 0.22 mm² 8 12 C1173 C1174 C1154 C1155

36 C1169 C1148

20 C1175 C1156

16 x 0.2mm = 0.5 mm² 6 12 C1178 C1375 C1372 C1373

50 C1365 C1364

section 7 7

Page

36 C1176 C1157

section 7 7

Page

section 7 7

Page

18 C1180 C1374

BT Industrial-Tec™ - Industrial Cables BS(PAS) 5308 – Part 2 – Type 1 – Collectively Screened – Unarmoured cables No. of pairs 1 2 5 10 20 Conductor 0.5 mm² (16x0.2 mm) C1081 C1082 C1083 C1084 C1085 Conductor 0.75 mm² (24x0.2 mm) C1086 C1087 C1088 C1089 C1090 Conductor 1.5 mm² (7x0.53 mm) C1091 C1092 C1093 C1094 C1095

section 8 8 8

Page

BS(PAS) 5308 – Part 2 – Type 1 – Collectively Screened – Armoured cables No. of pairs 1 2 5 10 20 Conductor 0.5 mm² (16x0.2 mm) C1097 C1098 C1099 C1100 C1096 Conductor 0.75 mm² (24x0.2 mm) C1101 C1102 C1103 C1104 C1105 Conductor 1.5 mm² (7x0.53 mm) C1106 C1107 C1108 C1109 C1110

section 8 8 8

Page

BS(PAS) 5308 – Part 2 – Type 1 – Individually & Collectively Screened – Unarmoured cables No. of pairs 2 5 10 20 Conductor 0.5 mm² (16x0.2 mm) C1111 C1112 C1113 C1114 Conductor 0.75 mm² (24x0.2 mm) C1115 C1116 C1117 C1118 Conductor 1.5 mm² (7x0.53 mm) C1119 C1120 C1121 C1122

section 8 8 8

Page

BS(PAS) 5308 – Part 2 – Type 1 – Individually & Collectively Screened – Armoured cable No. of pairs 2 5 10 20 Conductor 0.5 mm² (16x0.2 mm) C1123 C1124 C1125 C1126 Conductor 0.75 mm² (24x0.2 mm) C1127 C1128 C1129 C1130 Conductor 1.5 mm² (7x0.53 mm) C1131 C1132 C1133 C1134

section 8 8 8

Page

info.btcables@bt.com

5


BT Industrial-Tec™ - Control Cables No. of cores Conductor 0.75 mm² (24x0.2 mm) Conductor 1.0 mm² (32x0.2 mm) Conductor 1.5 mm² (30x0.24 mm) Conductor 2.5 mm² (50x0.24 mm)

3 C1631 C1632 C1633 C1634

YY Series (N stranded cores surrounded by a PVC sheath) 5 7 8 12 18 section C1645 C1648 9 9 C1639 C1641 C1643 C1646 C649 9 C1640 C1642 C1644 C1647 C1650 9

CY Series (N stranded cores surrounded by a braiding plus a PVC sheath) 3 4 5 section C1620 C1624 9 C1621 C1625 9 C1622 C1626 C1628 9 C1623 C1627 C1629 9

No. of cores Conductor 0.75 mm² (24x0.2 mm) Conductor 1.0 mm² (32x0.2 mm) Conductor 1.5 mm² (30x0.24 mm) Conductor 2.5 mm² (50x0.24 mm)

No. of cores Conductor 0.75 mm² (24x0.2 mm) Conductor 1.0 mm² (32x0.2 mm) No. of cores Conductor 1.5 mm² (30x0.24 mm) Conductor 2.5 mm² (50x0.24 mm) Conductor 4.0 mm² (56x0.29 mm) Conductor 6.0 mm² (84x0.29 mm)

4 C1635 C1636 C1637 C1638

Page

Page

SY Series (N stranded cores surrounded by Steel Wire Armouring plus a PVC sheath) 3 4 5 7 12 18 25 section Page C1655 9 C1651 C1656 C1660 C1665 C1669 C1671 C1673 C1675 9 2 3 4 5 6 7 12 18 C1652 C1657 C1661 C1666 C1668 C1670 C1672 C1674 9 C1658 C1662 9 C1659 C1663 9 C1664 9 2

info.btcables@bt.com

6


BT Cables - Belden equivalents

Belden P/N BT Cables P/N 1030A 1043A 1044A 1064A 1067A 1467A 1505A 1523A 1583A 1617A 1633E 1694A 1885ENH 3079E 3105A 3107A 3108A 3109A 4000FE 4000UE 4001UE 4100FE 4100UE 4101UE 4102UE 4200FE 4200UE 4201FE 4201UE 4202FE 4202UE 4300FE 4300UE 4301FE 4301UE 4302FE 4302UE 4304FE 4304UE 4306FE 4306UE 4400FE 4400UE 4401FE 4402FE 4402UE 4500FE 4500UE 4501FE 4501UE 4502FE 4502UE 4504FE 4504UE 4506FE 4506UE 5100FE 5100UE 5101FE 5101UE 5102FE 5102UE 5200FE 5200UE 5201FE 5201UE 5202FE 5202UE 5300FE 5300UE 5301FE 5301UE 5302FE 5302UE 5305FE 5400FE 5400UE 5401FE 5401UE 5402FE 5402UE 7731A 7860E 7965E 8205 8205NH 8259 8442 8442NH 8471 8471NH 8473 8473NH

C1223 C1078 C1077 C1076 C1074 C1075 C1229 C1027 C1035 C1241 C1036 C1279 C1039 C1315 C1080 C1295 C1296 C1297 C1334 C1335 C1337 C1701 C1702 C1704 C1706 C1711 C1712 C1713 C1714 C1715 C1716 C1721 C1722 C1723 C1724 C1725 C1726 C1727 C1728 C1729 C1730 C1731 C1732 C1733 C1735 C1736 C1741 C1742 C1743 C1744 C1745 C1746 C1747 C1748 C1749 C1750 C1001 C1002 C1003 C1004 C1005 C1006 C1007 C1008 C1009 C1010 C1011 C1012 C1013 C1014 C1015 C1016 C1017 C1018 C1239 C1019 C1020 C1021 C1022 C1023 C1024 C1280 C1038 C1037 C1300 C1415 C1046 C1301 C1416 C1198 C1307 C1222 C1306

Conductor Size 16(7*24) AWG 16 (7*24) AWG 16 (7*24) AWG 18 (7*26) AWG 18 (7*26) AWG 18 (7*26) AWG 20 AWG 14 AWG 24 AWG 14 AWG 24 AWG 18 AWG 23 AWG 22 (7*30) AWG 22 (7*30) AWG 22 (7*30) AWG 22 (7*30) AWG 22 (7*30) AWG 12 (19*25) AWG 12 (19*25) AWG 12 (19*25) AWG 14 (19*27) AWG 14 (19*27) AWG 14 (19*27) AWG 14 (19*27) AWG 16 (19*29) AWG 16 (19*29) AWG 16 (19*29) AWG 16 (19*29) AWG 16 (19*29) AWG 16 (19*29) AWG 18 (7*26) AWG 18 (7*26) AWG 18 (7*26) AWG 18 (7*26) AWG 18 (7*26) AWG 18 (7*26) AWG 18 (7*26) AWG 18 (7*26) AWG 18 (7*26) AWG 18 (7*26) AWG 20 (7*28) AWG 20 (7*28) AWG 20 (7*28) AWG 20 (7*28) AWG 20 (7*28) AWG 22 (7*30) AWG 22 (7*30) AWG 22 (7*30) AWG 22 (7*30) AWG 22 (7*30) AWG 22 (7*30) AWG 22 (7*30) AWG 22 (7*30) AWG 22 (7*30) AWG 22 (7*30) AWG 14 (19*27) AWG 14 (19*27) AWG 14 (19*27) AWG 14 (19*27) AWG 14 (19*27) AWG 14 (19*27) AWG 16 (19*29) AWG 16 (19*29) AWG 16 (19*29) AWG 16 (19*29) AWG 16 (19*29) AWG 16 (19*29) AWG 18 (7*26) AWG 18 (7*26) AWG 18 (7*26) AWG 18 (7*26) AWG 18 (7*26) AWG 18 (7*26) AWG 18 (7*26) AWG 20 (7*28) AWG 20 (7*28) AWG 20 (7*28) AWG 20 (7*28) AWG 20 (7*28) AWG 20 (7*28) AWG 14 AWG 23 AWG 23 AWG 20 (7*28) AWG 20 (7*28) AWG 20 (10*33) AWG 22 (7*30) AWG 22 (7*30) AWG 16 (19*29) AWG 16 (19*29) AWG 14 (19*27) AWG 14 (19*27) AWG

No. of Conductors

No. of Pairs 1 16 20 4 16 8

1 1

Individually Collective shielded shield pairs Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes

Jacket PVC PVC PVC PVC PVC PVC PVC PVC

4 1 4 1 4 1 2 2 3 4 2 2 3 2 3 3 4 2 2 3 3 4 4 2 2 3 3 4 4 6 6 8 8 2 2 3 4 4 2 2 3 3 4 4 6 6 8 8 2 2 3 3 4 4 2 2 3 3 4 4 2 2 3 3 4 4 7 2 2 3 3 4 4 1

Yes

Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes

Yes Yes Yes

4 4 1 1 1

Yes Yes

Yes 1 1 1 1

2 2

Yes

Yes yes Yes Yes Yes Yes Yes Yes Yes Yes

PVC PVC PVC PVC PVC PVC PVC PVC PVC HFFR HFFR HFFR HFFR HFFR HFFR HFFR HFFR HFFR HFFR HFFR HFFR HFFR HFFR HFFR HFFR HFFR HFFR HFFR HFFR HFFR HFFR HFFR HFFR HFFR HFFR HFFR HFFR HFFR HFFR HFFR HFFR HFFR HFFR HFFR HFFR HFFR HFFR PVC PVC PVC PVC PVC PVC PVC PVC PVC PVC PVC PVC PVC PVC PVC PVC PVC PVC PVC PVC PVC PVC PVC PVC PVC PVC

PVC HFFR PVC PVC HFFR PVC HFFR PVC HFFR

BT Cables Brand and Additional Data 300V PL Tray Cable 600V Tray Cable 600V Tray Cable 600V Tray Cable 600V Tray Cable 300V PL Tray Cable RG-59 Coaxial Cable (BC) RG11 Coaxial Cable (CCS) CAT 5E UTP Cable RG-11 Quad Shield Coaxial Cable (CCS) CAT 5E FTP Cable RG-6 Coaxial Cable (BC) CAT 7 ISTP Cable Profibus DP RS-485 Computer Cable RS-485 Low Cap Computer Cable RS-485 Computer Cable RS-485 Computer Cable BMS-HFFR cables BMS-HFFR cables BMS-HFFR cables BMS-HFFR cables BMS-HFFR cables BMS-HFFR cables BMS-HFFR cables BMS-HFFR cables BMS-HFFR cables BMS-HFFR cables BMS-HFFR cables BMS-HFFR cables BMS-HFFR cables BMS-HFFR cables BMS-HFFR cables BMS-HFFR cables BMS-HFFR cables BMS-HFFR cables BMS-HFFR cables BMS-HFFR cables BMS-HFFR cables BMS-HFFR cables BMS-HFFR cables BMS-HFFR cables BMS-HFFR cables BMS-HFFR cables BMS-HFFR cables BMS-HFFR cables BMS-HFFR cables BMS-HFFR cables BMS-HFFR cables BMS-HFFR cables BMS-HFFR cables BMS-HFFR cables BMS-HFFR cables BMS-HFFR cables BMS-HFFR cables BMS-HFFR cables BMS-PVC cables BMS-PVC cables BMS-PVC cables BMS-PVC cables BMS-PVC cables BMS-PVC cables BMS-PVC cables BMS-PVC cables BMS-PVC cables BMS-PVC cables BMS-PVC cables BMS-PVC cables BMS-PVC cables BMS-PVC cables BMS-PVC cables BMS-PVC cables BMS-PVC cables BMS-PVC cables BMS-PVC cables BMS-PVC cables BMS-PVC cables BMS-PVC cables BMS-PVC cables BMS-PVC cables BMS-PVC cables RG-11 Coaxial Cable (BC) CAT6 FTP Cable CAT 6 UTP Cable High Conductivity Speaker and BMS-PVC-TC Cable High Conductivity Speaker and BMS-PVC-TC Cable RG-58 Coaxial Cable High Conductivity Speaker and BMS-PVC-TC Cable BMS-HFFR cables High Conductivity Speaker and BMS-PVC-TC Cable BMS-HFFR cables High Conductivity Speaker and BMS-PVC-TC Cable BMS-HFFR cables

info.btcables@bt.com

7


BT Cables - Belden equivalents

Belden P/N BT Cables P/N 8477 8477NH 8718NH 8719 8719NH 8720 8720NH 8723 8723NH 8723PE 8760 8760NH 8761 8761NH 8762 8762NH 8770 8772 8777 8777NH 8777PE 8778 8778NH 9100 9116 9259 9463F 9501 9501NH 9501PE 9502 9502NH 9502PE 9503 9503NH 9503PE 9504 9504NH 9504PE 9505 9505NH 9505PE 9506 9506NH 9506PE 9507 9507NH 9507PE 9508 9508NH 9508PE 9510NH 9510NH 9536 NH 9536 9538 9538NH 9540 9571 9572 9574 9575 9580 9581 9582 9583 9728 9729 9730 9740 9740NH 9773 9774 9841 9841NH 9841PE 9842 9842NH 9843 9843NH 9844 9844NH 9913 1227A1 1232A1 43051 43113 513945 533945 543945 9842NH 9842PE 9843NH

C1302 C1417 C1303 C1213 C1270 C1224 C1305 C1196 C1281 C1316 C1193 C1272 C1199 C1310 C1195 C1308 C1225 C1245 C1197 C1282 C1317 C1214 C1314 C1025 C1026 C1275 C1079 C1181 C1441 C1451 C1182 C1442 C1452 C1183 C1443 C1453 C1184 C1444 C1454 C1185 C1445 C1455 C1186 C1446 C1456 C1187 C1447 C1457 C1188 C1448 C1458 C1206 C1449 C1358 C1398 C1399 C1359 C1400 C1135 C1136 C1040 C1041 C1137 C1042 C1138 C1043 C1384 C1382 C1383 C1203 C1271 C1298 C1299 C1189 C1318 C1409 C1190 C1319 C1191 C1320 C1192 C1321 C1047 C1031 C1032 C1208 C1207 C1030 C1029 C1028 C1319 C1410 C1320

Conductor Size 12 (19*25) AWG 12 (19*25) AWG 12 (19*25) AWG 16 (19*29) AWG 16 (19*29) AWG 14 (19*27) AWG 14 (19*27) AWG 22 (7*30) AWG 22 (7*30) AWG 22 (7*30) AWG 18 (7*26) AWG 18 (7*26) AWG 22 (7*30) AWG 22 (7*30) AWG 20 (7*28) AWG 20 (7*28) AWG 18 (7*26) AWG 20 (7*28) AWG 22 (7*30) AWG 22 (7*30) AWG 22 (7*30) AWG 22 (7*30) AWG 22 (7*30) AWG 20 AWG 18 AWG 20 (19*33) 20 (42*36) AWG 24 (7*32) AWG 24 (7*32) AWG 24 (7*32) AWG 24 (7*32) AWG 24 (7*32) AWG 24 (7*32) AWG 24 (7*32) AWG 24 (7*32) AWG 24 (7*32) AWG 24 (7*32) AWG 24 (7*32) AWG 24 (7*32) AWG 24 (7*32) AWG 24 (7*32) AWG 24 (7*32) AWG 24 (7*32) AWG 24 (7*32) AWG 24 (7*32) AWG 24 (7*32) AWG 24 (7*32) AWG 24 (7*32) AWG 24 (7*32) AWG 24 (7*32) AWG 24 (7*32) AWG 24 (7*32) AWG 24 (7*32) AWG 24 (7*32) AWG 24 (7*32) AWG 24 (7*32) AWG 24 (7*32) AWG 24 (7*32) AWG 18 AWG 16 AWG 18 AWG 16 AWG 14 AWG 14 AWG 12 AWG 12 AWG 24 (7*32) AWG 24 (7*32) AWG 24 (7*32) AWG 18 (7*26) AWG 18 (7*26) AWG 22 (7*30) AWG 22 (7*30) AWG 24 (7*32) AWG 24 (7*32) AWG 24 (7*32) AWG 24 (7*32) AWG 24 (7*32) AWG 24 (7*32) AWG 24 (7*32) AWG 24 (7*32) AWG 24 (7*32) AWG 10 AWG 24 AWG 24 AWG 0.4 mm 26 AWG 14 AWG 18 AWG 20 AWG 24 (7*32) AWG 24 (7*32) AWG 24 (7*32) AWG

No. of Conductors

No. of Pairs

Individually Collective shielded shield pairs

1 1 1

Yes Yes

2 2 2 2

Yes Yes 2 2 2 1 1 1 1 1 1

Yes Yes Yes

3 3 3 6 6

Yes Yes Yes Yes Yes

Yes Yes Yes Yes Yes Yes Yes Yes

3 3

1 1 1

Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes

1 1 1 1 2 2 2 3 3 3 4 4 4 5 5 5 6 6 6 7 7 7 8 8 8 10 10 6 6 8 8 10 1 1 2 2

Yes Yes 1

2

Yes 1

2

Yes 4 2 1 1 1 4 5 1 1 1 2 2 3 3 4 4

1

Yes Yes Yes

Yes Yes

Yes 2 25 8

1 1 1 1 2 2 3

Yes Yes Yes Yes Yes Yes Yes Yes

Jacket PVC HFFR HFFR PVC HFFR PVC HFFR PVC HFFR PE PVC HFFR PVC HFFR PVC HFFR PVC PVC PVC HFFR PE PVC HFFR PVC PVC PVC PVC PVC HFFR PE PVC HFFR PE PVC HFFR PE PVC HFFR PE PVC HFFR PE PVC HFFR PE PVC HFFR PE PVC HFFR PE PVC HFFR HFFR PVC PVC HFFR PVC PVC PVC PVC PVC PVC PVC PVC PVC PVC PVC PVC PVC HFFR PVC PVC PVC HFFR PE PVC HFFR PVC HFFR PVC HFFR PVC PVC PVC PVC HFFR PVC PVC PVC HFFR PE HFFR

BT Cables Brand and Additional Data High Conductivity Speaker and BMS-PVC-TC Cable BMS-HFFR cables BMS-HFFR cables High Conductivity Speaker and BMS-PVC-TC Cable BMS-HFFR cables High Conductivity Speaker and BMS-PVC-TC Cable BMS-HFFR cables Individually Shielded TP BMS-PVC-TC Cable Individually Shielded TP BMS-HFFR-TC Cable Individually Shielded TP BMS-PE-TC Cable High Conductivity Speaker and BMS-PVC-TC Cable BMS-HFFR cables High Conductivity Speaker and BMS-PVC-TC Cable BMS-HFFR cables High Conductivity Speaker and BMS-PVC-TC Cable BMS-HFFR cables High Conductivity Speaker and BMS-PVC-TC Cable High Conductivity Speaker and BMS-PVC-TC Cable Individually Shielded TP BMS-PVC-TC Cable Individually Shielded TP BMS-HFFR-TC Cable Individually Shielded TP BMS-PE-TC Cable Individually Shielded TP BMS-PVC-TC Cable Individually Shielded TP BMS-HFFR-TC Cable RG-59 Coaxial Cable (CCS) RG-6 Coaxial Cable (CCS) RG-59 Coaxial CCTV cable Twinax - Blue Hose cable RS-232 Computer Cable RS-232 Computer Cable RS-232 Computer Cable RS-232 Computer Cable RS-232 Computer Cable RS-232 Computer Cable RS-232 Computer Cable RS-232 Computer Cable RS-232 Computer Cable RS-232 Computer Cable RS-232 Computer Cable RS-232 Computer Cable RS-232 Computer Cable RS-232 Computer Cable RS-232 Computer Cable RS-232 Computer Cable RS-232 Computer Cable RS-232 Computer Cable RS-232 Computer Cable RS-232 Computer Cable RS-232 Computer Cable RS-232 Computer Cable RS-232 Computer Cable RS-232 Computer Cable RS-232 Computer Cable RS-232 Computer Cable RS-232 Computer Cable RS-232 Computer Cable RS-232 Computer Cable RS-232 Computer Cable RS-232 Computer Cable Fire Detection and Alarm System Cable, FPLR rated 105°C, UL listed Fire Detection and Alarm System Cable, FPLR rated 105°C, UL listed Fire Detection and Alarm System Cable, FPLR rated 105°C, UL listed Fire Detection and Alarm System Cable, FPLR rated 105°C, UL listed Fire Detection and Alarm System Cable, FPLR rated 105°C, UL listed Fire Detection and Alarm System Cable, FPLR rated 105°C, UL listed Fire Detection and Alarm System Cable, FPLR rated 105°C, UL listed Fire Detection and Alarm System Cable, FPLR rated 105°C, UL listed Low Cap Computer Cable Low Cap Computer Cable Low Cap Computer Cable High Conductivity Speaker and BMS-PVC-TC Cable BMS-HFFR cables Individually Shielded TP BMS-PVC-TC Cable Individually Shielded TP BMS-PVC-TC Cable RS-485 Low Cap Computer Cable RS-485 Low Cap Computer Cable RS-485 Low Cap Computer Cable RS-485 Low Cap Computer Cable RS-485 Low Cap Computer Cable RS-485 Low Cap Computer Cable RS-485 Low Cap Computer Cable RS-485 Low Cap Computer Cable RS-485 Low Cap Computer Cable RG-8 Series Coaxial Cable CAT 3 UTP Cable CAT 3 UTP Cable 8 Pair/0.4 Braided Telecoms Cable TELCO 75 Ohm Coaxial Cable RG-11 Coaxial Cable (BC) RG6 Series Coaxial Cable (BC) RG-59 Coaxial Cable (BC) 2 Pair 24AWG RS485 Low Cap Computer Cable HFFR Jacket 2 Pair 24AWG RS485 Low Cap Computer Cable HFFR Jacket 3 Pair 24AWG RS485 Low Cap Computer Cable HFFR Jacket

info.btcables@bt.com

8


BT Cables - Belden equivalents

Belden P/N BT Cables P/N 9843PE 9844NH 9844PE MRG2130 MRG214 YE00819 YE00820 YE00905 YE00906

C1411 C1321 C1412 C1048 C1049 C1219 C1217 C1220 C1218

Conductor Size 24 (7*32) AWG 24 (7*32) AWG 24 (7*32) AWG 2.25 (7*0.75) mm 2.25 (7*0.75) mm 0.8 0.8 0.8 0.8

No. of Conductors

No. of Pairs 3 4 4

1 1 1 2 1 2

Individually Collective shielded shield pairs Yes Yes Yes Yes Yes Yes Yes Yes Yes

Jacket PE HFFR PE PVC PVC PVC PVC HFFR HFFR

BT Cables Brand and Additional Data 3 Pair 24AWG RS485 Low Cap Computer Cable HFFR Jacket 4 Pair 24AWG RS485 Low Cap Computer Cable HFFR Jacket 4 Pair 24AWG RS485 Low Cap Computer Cable HFFR Jacket RG213 Series Coaxial cable RG214 Series Coaxial Cable KNX (was EIB) CABLE KNX (was EIB) CABLE KNX (was EIB) CABLE KNX (was EIB) CABLE

info.btcables@bt.com

9


Section 1 - BT BMS-TECTM - Paired Cables or HFFR sheathed cables for BUS and Interface Systems PVC, PE

1. Application RS-232, RS-422, RS-485, KNX (EIB or Instabus), LonWorks, ModBus, M-Bus, CAN-bus, BACnet, BMS (Building Management Systems) or general interface systems. 2. Basic Construction of the cables Wire = conductor without or with insulation. With insulation sometimes also indicated as core. Conductor: may be solid = one single rod or flexible = twisted bare or tinned copper strands, ranging from 12 to 24AWG. Conductor (AWG) 24 22 20 18 16 14 12

Configuration (AWG) 7 x 32 7 x 30 7 x 28 7 x 26 19 x 29 19 x 27 19 x 25

Configuration (mm) 7 x 0.20 7 x 0.25 7 x 0.32 7 x 0.40 19 x 0.28 19 x 0.36 19 x 0.45

DC Resistance (Ohm/km) ≤ 88 ≤ 57.4 ≤ 32.16 ≤ 22.7 ≤ 15.47 ≤ 9.36 ≤ 5.61

Insulation: Polyethylene (PE) or Foam PE (FPE) for PVC (Polyvinyl Chloride) or Halogen-Free (HFFR) sheathed cables. And Halogen-Free (HFFR) for HFFR sheathed cables. All insulations are in accordance with BS EN 50290-2, good strippable and coloured. The colours are not interchangeable. Pair = two twisted – colour coded – wires. Individually screened pair (if applicable): one pair wrapped with an Aluminium/Polyester foil under which a drain wire. Cable core: two or more (individually screened) pairs stranded. Good twisting (lay-length < 30 ~ 40D) is necessary otherwise the cable can hardly be bending and will break after a few bends. Drain wire (only in combination with a screen): stranded tinned copper wires. In order to avoid corrosion, it is recommended that drain wires are tinned. Screen (if applicable): Helically applied (= as a spiral) Aluminium/Polyester (Alpet) foil. For the flexibility of a cable a helically applied foil is to be preferred. A longitudinally applied foil act more as a stiff tube = more difficult to bend. Braiding (if applicable): tinned copper wires. Sheath: grey PVC , black PE or purple HFFR, all in accordance with BS EN 50290-2. Cable Configuration Insulation Sheath PE, FPE or PVC

PVC

PE, FPE or PVC

PE

PE, FPE or HFFR

HFFR

Cable Retardancy according to IEC 60332-1 No according to IEC 60332-3-24

Low Smoke

Halogen-free (non acid, non toxic)

RoHS compliant

No

No

Yes

No according to IEC 61034-1-2

Only with (F)PE insulation according to IEC 60754-1 & 2

Yes Yes

Operating temperature range: -25 to +75 °C and Rated Voltage: 300 Vrms

info.btcables@bt.com

10


RS-232: Hand shake interface used for low data rates. Computer to printer or to modem or to another device. RS-422: Balanced digital circuit. Medium speed data exchange. Long line modems and Daisy chain configuration. RS-485: Balanced digital circuit. Medium speed fieldbus interfaces. RS-232

RS-422

RS-485

Differential Max. number of drivers Max. number of receivers Modes of operation Network topology Max. distance acc. to standard Max. speed at 12 m. Max. speed at 1200 m.

no 1 1 full duplex point-to-point 15 m 20 kbs 1 kbs

yes 1 10 half duplex multidrop 1200 m 10 Mbs 100 kbs

yes 1 32 half duplex multidrop 1200 m 35 Mbs 100 kbs

Conductor size Number of conductors Impedance BT Cables main part numbers see

mainly 24 AWG 6 to 25 not defined section 1.3

mainly 24 AWG 2 pairs or more 100 Ohm section 1.2

mainly 24 AWG 1 pair or more 120 Ohm section 1.1

Cables used

KNX is a standardised (EN 50090, ISO/IEC 14543), OSI-based network communications protocol for intelligent buildings. KNX is the successor to, and convergence of, three previous standards: the European Home Systems Protocol (EHS), BatiBUS, and the European Installation Bus (EIB or Instabus).

BT Cables main part numbers for KNX cables: C1217 (quad – PVC) – C1218 (quad – HFFR) – C1219 (1 pair – PVC) – C1220 (1 pair – HFFR).

LonWorks is a networking platform specifically created to address the needs of control applications. The platform is built on a protocol created by Echelon Corporation for networking devices over media such as twisted pair, power lines, fibre optics, and RF. It is used for the automation of various functions within buildings such as lighting and HVAC.

BT Cables main part numbers for LonWorks: C1198 (PVC) - C1203 (PVC) – C1307 (HFFR) – C1271 (HFFR) – C1346 (HFFR) – C1347 (HFFR) – C1348 (HFFR) and C1349 (HFFR).

Modbus is a serial communications protocol published by Modicon in 1979 for use with its programmable logic controllers (PLCs). Simple and robust, it has since become one of the de facto standard communications protocols in the industry.

BT Cables main part numbers for Modbus: C1197 (PVC) - C1193 (PVC) – C1282 (HFFR) – C1272 (HFFR).

M-Bus (Meter-Bus) is a European standard (EN 13757-2 physical and link layer, EN 13757-3 application layer) for the remote reading of gas or electricity meters. M-Bus is also usable for other types of consumption meters.

BT Cables main part number for M-bus: C1020 – C1193.

Controller–area network (CAN or CAN-bus) is a vehicle bus standard designed specifically for automotive applications but now also used in other areas such as industrial automation and medical equipment. CAN bus utilize TIA/EIA-485 cables.

BT Cables main part numbers for CAN-bus: C1080 - C1189 – C1190 – C1191 – C1192 – C1295 – C1296 – C1297 and HFFR cables C1318 – C1319 – C1320 – C1321.

BACnet is a communications protocol for building automation and control networks. It is was designed to allow communication of building automation and control systems for applications such as heating, ventilating, and air-conditioning control, lighting control, access control, and fire detection systems and their associated equipment. BACnet over IP can utilize Cat 6.

BT Cables main part numbers for BACnet: C1228 (PVC) – C1189 (PVC) – C1190 (PVC) - C1318 (HFFR) and C1319 (HFFR).

info.btcables@bt.com

11


Section 1.1 Paired Cables for TIA/EIA-485 = RS-485 applications 22 and 24AWG conductors – PE or FPE insulation – Dual Screen - PVC or HFFR sheath CABLE DESCRIPTION 1. Conductor Flexible Tinned Copper

5. Screen Aluminium/Polyester

Standard Put Up Length 305 or 500 meters

2. Insulation Polyethylene (PE) or Foam PE (FPE)

6. Braiding Tinned Copper wires

Standard References TIA/EIA-485 (BS) EN 50290-2 IEC 60332-1 (PVC sheath) or IEC 60332-3-24 (3C) (HFFR sheath) IEC 61034 (HFFR sheath) IEC 60754-1 & 2 (HFFR sheath) RoHS directives

3. Pair Impedance 120 Ω

7. Sheath Material Grey PVC or Purple HFFR

4. Tinned Copper Drain Wire 24 AWG(7 x 32)

Cables with 24 AWG conductors – PE insulation - PVC sheath

24 (7 x 32) 24 (7 x 32) 24 (7 x 32) 24 (7 x 32)

Max. DC Resistance Conductor (Ω/km) 88 88 88 88

Coverage braiding (%) 90 90 90 90

24 (7 x 32) 24 (7 x 32) 24 (7 x 32) 24 (7 x 32)

88 88 88 88

90 90 90 90

BTCL Part Number

No of pairs

Conductor (AWG)

C1189 C1190 C1191 C1192

1 2 3 4

C1318 C1319 C1320 C1321

1 2 3 4

Capacitance

Weight

PVC PVC PVC PVC

Overall Diameter (mm) 5.9 8.5 9.0 9.9

(pF/m) 41 41 41 41

(kg/km) 49 80.5 92.6 114.4

HFFR HFFR HFFR HFFR

5.9 8.5 9.0 9.9

41 42 42 42

49 80.5 92.6 114.4

Capacitance

Weight

PVC PVC PVC PVC

Overall Diameter (mm) 6.1 9.1 10.5 11.4

(pF/m) 36 37 38 38

(kg/km) 63.7 75.6 97 119.1

HFFR HFFR HFFR HFFR

6.1 9.1 10.5 11.4

36 37 38 38

63.7 75.6 97 119.1

Sheath

Cables with 22 AWG conductors – Foam PE insulation - Halogen-free (HFFR) sheath

22 (7 x 30) 22 (7 x 30) 22 (7 x 30) 22 (7 x 30)

Max. DC Resistance Conductor (Ω/km) 57.4 57.4 57.4 57.4

Coverage braiding (%) 65 65 65 65

22 (7 x 30) 22 (7 x 30) 22 (7 x 30) 22 (7 x 30)

57.4 57.4 57.4 57.4

65 65 65 65

BTCL Part Number

No of pairs

Conductor (AWG)

C1080 C1295 C1296 C1297

1 2 3 4

C1401 C1402 C1403 C1404

1 2 3 4

Colour scheme

Sheath

Pair 1

Pair 2

Pair 3

Pair 4

Wire a (insulation colour / colour of stripe)

White / blue

White / orange

White / green

White / brown

Wire b (insulation colour / colour of stripe)

Blue / white

Orange / white

Green / white

Brown /white

For more details, please see the respective detailed datasheet(s)

info.btcables@bt.com

12


Section 1.2 Cables with 2 to 6 pairs for RS-422 applications 24AWG conductors – FPE insulation – every pair screened - PVC sheath CABLE DESCRIPTION 1. Conductor Flexible Tinned Copper 2. Insulation Foam Polyethylene (FPE) 3. Pair Two twisted wires 4. Drain Wire Flexible Tinned Copper 24 AWG (7 x 32)

Standard Put Up Length 305 or 500 metres

5. Screen Aluminium/Polyester Wrapped around each Pair

Standard References ANSI/TIA/EIA-422-B (BS) EN 50290-2 IEC 60332-1 RoHS directives

6. Cable core 2 or more individually screened pairs stranded 7. Sheath Material Grey PVC

Cables with 24 AWG conductors – PE insulation – PVC sheath BTCL Part Number

No. of Pairs

C1382 C1383 C1384 C1386

2 3 4 6

Colour scheme C1382 to C1386

Conductor and Drain Wire (AWG) 24 (7 x 32) 24 (7 x 32) 24 (7 x 32) 24 (7 x 32)

Max. DC Resistance Conductor (Ω/km) 88 88 88 88

Pair 1 Black/Red

Overall Diameter (mm) 6.7 8.4 9.2 10.6

Pair 2 Black/White

Capacitance

Impedance

Weight

(pF/m) 41 41 41 41

(Ohm) 100 100 100 100

(kg/km) 41.8 59.4 75.5 104.8

Pair 3 Black/Green

Pair 4 Black/Blue

Pair 5 Black/Yellow

Pair 6 Black/Brown

For more details, please see the respective detailed datasheet(s)

info.btcables@bt.com

13


Section 1.3 Cables with 2 to 8 pairs for RS-232 applications 24AWG conductors – PVC insulation – overall screen – PVC, PE or HFFR sheath CABLE DESCRIPTION 1. Conductor Flexible Tinned Copper 24AWG(7x32) 2. Insulation PVC or HFFR

4. Cable core 2 or more pairs stranded

C1441 C1442 C1443 C1444 C1445 C1446 C1447 C1448 C1449 BTCL Part Number C1451 C1452 C1453 C1454 C1455 C1456 C1457 C1458

6. Screen Aluminium/Polyester

Standard References ANSI/TIA/EIA-232-F (BS) EN 50290-2 IEC 60332-1 (PVC sheath) IEC 60332-3-24 (3C) (HFFR sheath) IEC 61034 (HFFR sheath) RoHS directives

No. of Pairs

Insulation

Sheath

1 2 3 4 5 6 7 8

PVC PVC PVC PVC PVC PVC PVC PVC

PVC PVC PVC PVC PVC PVC PVC PVC

No. of Pairs

Insulation

Sheath

1 2 3 4 5 6 7 8 10

HFFR HFFR HFFR HFFR HFFR HFFR HFFR HFFR HFFR

HFFR HFFR HFFR HFFR HFFR HFFR HFFR HFFR HFFR

No. of Pairs

Insulation

Sheath

1 2 3 4 5 6 7 8

PVC PVC PVC PVC PVC PVC PVC PVC

PE PE PE PE PE PE PE PE

C1181 C1182 C1183 C1184 C1185 C1186 C1187 C1188 BTCL Part Number

Standard Put Up Length 305 or 500 metres

7. Sheath Material Grey PVC Purple HFFR Black PE

3. Pair Two twisted wires

BTCL Part Number

5. Tinned Copper Drain Wire 24 AWG(7 x 32)

Conductor and Drain Wire 24 (7 x 32) 24 (7 x 30) 24 (7 x 30) 24 (7 x 30) 24 (7 x 30) 24 (7 x 30) 24 (7 x 30) 24 (7 x 30)

Max. DCR Conductor (Ω/km) 88 88 88 88 88 88 88 88

Overall Diameter 4.0 5.6 5.9 6.7 7.3 7.4 7.5 8.3

Capacitance

Weight

135 76 76 80 80 80 80 80

18 28 39 48 57 65 68 76

Conductor and Drain Wire 24 (7 x 32) 24 (7 x 30) 24 (7 x 30) 24 (7 x 30) 24 (7 x 30) 24 (7 x 30) 24 (7 x 30) 24 (7 x 30) 24 (7 x 30)

Max. DCR Conductor (Ω/km) 88 88 88 88 88 88 88 88 88

Overall Diameter 4.0 5.6 5.9 6.7 7.3 7.4 7.5 8.3 9.2

Capacitance

Conductor and Drain Wire 24 (7 x 32) 24 (7 x 30) 24 (7 x 30) 24 (7 x 30) 24 (7 x 30) 24 (7 x 30) 24 (7 x 30) 24 (7 x 30)

Max. DCR Conductor (Ω/km) 88 88 88 88 88 88 88 88

Overall Diameter 4.0 5.6 5.9 6.7 7.3 7.4 7.5 8.3

Capacitance

Weight

95 55 55 60 60 60 60 60 60

18 28 39 48 57 65 73 85 95

Weight

135 76 76 80 80 80 80 80

14.5 24.5 31 39 47 55 59 67

Colour scheme of the pairs Pair number

Pair 1

Wire a

Black

Wire b

Red

Pair 2

Pair 3

Pair 4

Pair 5

Pair 6

Pair 7

Pair 8

Pair 10

Black

Black

Black

Black

Black

Black

Red

Red

White

Green

Blue

Yellow

Brown

Orange

White

Blue

For more details, please see the respective detailed datasheet(s)

info.btcables@bt.com

14


Section 1.4 Cables for KNX (was EIB or Instabus) applications 0.8 mm conductors – PE insulation – overall screen - PVC or HFFR sheath CABLE DESCRIPTION 1. Conductor Solid Bare Copper 0.8 mm = 0.5 mm2

5. Drain Wire 0.4 mm Tinned Copper

2. Insulation Polyethylene (PE) Black-RedWhite-Green

C1217 C1218 C1219 C1220

BTCL Part Number C1217 C1218 C1219 C1220

Standard References EN 50090 (BS) EN 50290-2 IEC 60332-1 (PVC sheath) or IEC 60332-3-24 (3C) (HFFR sheath) IEC 61034 (HFFR sheath) IEC 60754-1 & 2 (HFFR sheath) RoHS directives

6. Screen Aluminium/Polyester 7 Sheath Material Green PVC or Green HFFR

3. Cable Core Quad or Pair

BTCL Part Number

Standard Put Up Length 305 or 500 metres

4. Polyester tape

No. of wires 1x4 1x4 1x2 1x2

Lay-Up quad quad pair pair

Sheath Material PVC HFFR PVC HFFR

Diameter Insulation (mm) 1.45 1.45 1.45 1.45

Wire a

Wire b

Wire c

Wire d

Black Black Black Black

White White White White

Red Red

Green Green

Overall Diameter (mm) 6.1 6.1 5.5 5.5

Max. DC Resistance Conductor (Ω/km) 37 37 37 37

Capacitance

Weight

(pF/m) ≤ 100 ≤ 100 ≤ 100 ≤ 100

(kg/km) 51 53 37 39

For more details, please see the respective detailed datasheet(s)

info.btcables@bt.com

15


Section 1.5 Cables for LonWorks applications 0.64 mm conductors – PE or FPE insulation Individually screened pairs or unscreened pairs - HFFR sheath CABLE DESCRIPTION 1. Conductor Solid Bare Copper 0.64 mm = 0.32 mm²

5. Cable core one pair or two pairs stranded

2. Insulation Polyethylene (PE) or Foam Polyethylene (FPE)

6 Sheath Material Purple HFFR

3. Pairs with no screen two twisted wires 4. Individually screened pair two twisted wires plus drain wire wrapped with an Aluminium/Polyester foil

BTCL Part Number

No. of pairs

Insulation Material

Indiv. screened pairs

C1346 C1347 C1348 C1349

1 2 1 2

Solid PE Solid PE Foam PE Foam PE

No No Yes Yes

Overall Diameter (mm) 3.5 5.2 4.6 7.6

Standard Put Up Length 305 or 500 metres Standard References EN 50090 (BS) EN 50290-2 IEC 60332-3C IEC 61034 IEC 60754-1 & 2 RoHS directives

Max. DC Resistance Conductor (Ω/km) 61 61 61 61

Capacitance

Weight

(pF/m) 46 46 46 46

(kg/km) 17.1 27.7 24.2 56.1

For more details, please see the respective detailed datasheet(s)

info.btcables@bt.com

16


Section 1.6 Cables for General Interface applications 2 to 6 pairs – 22AWG conductors – PE or HFFR insulation Individually screened pairs – PVC or HFFR sheath CABLE DESCRIPTION 1. Conductor Flexible Tinned Copper 22AWG(7 x 30)

5. Screen Aluminium/Polyester foil wrapped around each pair

2. Insulation Polyethylene (PE) or Halogen-free (HFFR)

6. Cable core 2 or more individually screened pairs stranded

3. Pair Two twisted wires

7. Sheath Material Grey PVC or Purple HFFR

4. Tinned Copper Drain Wire 24 AWG(7 x 32)

BTCL Part Number C1196 C1281 C1197 C1282 C1298 C1299 C1214 C1314

No. of pairs

Insulation Material

Sheath Material

2 2 3 3 4 5 6 6

PE HFFR PE HFFR PE PE PE HFFR

PVC HFFR PVC HFFR PVC PVC PVC HFFR

Colour scheme

Pair 1

Overall Diameter (mm) 6.0 6.5 6.5 7.5 7.0 7.7 8.9 9.5

Pair 2

Pair 3

Standard Put Up Length 305 or 500 metres Standard References (BS) EN 50290-2 IEC 60332-1 (PVC sheath) IEC 60332-3-24 (3C) (HFFR sheath) IEC 61034 (HFFR sheath) IEC 60754-1 & 2 (HFFR sheath) RoHS directives

Max. DC Resistance Conductor (Ω/km) 57.4 57.4 57.4 57.4 57.4 57.4 57.4 57.4

Pair 4

Capacitance

Weight

(pF/m) 90 150 98 155 98 99 99 155

(kg/km) 36.1 50.8 49.1 67.4 62 74.2 87.2 115.6

Pair 5

C1196 and C1281

Black/ Red

Green/White

C1197 and C1282

Black/ Red

Black/White

Black/Green

C1298

Black/ Red

Black/White

Black/Green

Black/Blue

C1299

Black/ Red

Black/White

Black/Green

Black/Blue

Black/Yellow

C1214 and C1314

Black/ Red

Black/White

Black/Green

Black/Blue

Black/Yellow

Pair 6

Black/Brown

For more details, please see the respective detailed datasheet(s)

info.btcables@bt.com

17


Section 1.7 Cables for General Interface applications One pair – 22 to 12AWG conductors – PE insulation Collective (overall) screen – PVC or HFFR sheath CABLE DESCRIPTION 1. Conductor Flexible Tinned Copper

Standard Put Up Length 305 or 500 metres

4. T.C. Drain Wire (only with screen) 24 AWG(7 x 32)

2. Insulation PVC or Polyethylene (PE) or Halogen-free (HFFR)

Standard References (BS) EN 50290-2 IEC 60332-1 (PVC sheath) IEC 60332-3-24 (3C) (HFFR sheath) IEC 61034 (HFFR sheath) IEC 60754-1 & 2 (HFFR sheath) RoHS directives

5. Screen (if applicable) Aluminium/Polyester 6. Sheath Material Grey PVC or Purple HFFR

3. Pair Two wires twisted

DC Resistance 12 to 22 AWG conductors Conductor

AWG

22

20

18

16

14

12

No. of strands x gauge

AWG

7 x 30

7 x 28

7 x 26

19 x 29

19 x 27

19 x 25

No. of strands x mm

Mm

7 x 0.25

7 x 0.32

7 x 0.40

19 x 0.28

19 x 0.36

19 x 0.45

Ω/km

57.4

35.75

22.7

15.47

9.36

5.61

Max. DC resistance conductor

One pair cables with PE insulation and PVC sheath Screened BTCL Part Number

C1199 C1195 C1193 C1213 C1224 C1313

Cond.

Capacity

Weight

(AWG)

(pF/m)

(kg/km)

22 20 18 16 14 12

4.4 5.0 5.6 7.9 9.0 10.2

75 75 75 60 76 77

25 36.4 43.2 75.7 104.9 124.7

Screened BTCL Part Number

C1310 C1308 C1272 C1270 C1305 C1303

Unscreened

Overall Diameter (mm)

Cond.

BTCL Part Number

C1301 C1300 C1203 C1198 C1222 C1302

Cond.

Capacity

Weight

(AWG)

Overall Diameter (mm)

(pF/m)

(kg/km)

22 20 18 16 14 12

4.0 4.3 5.1 6.9 8.6 9.8

70 80 85 90 108 115

19.5 23 38.6 63.3 91.8 115

Capacity

Weight

(AWG)

Overall Diameter (mm)

(pF/m)

(kg/km)

22 20 18 16 14 12

4.7 5,2 5.9 7.7 8.7 9.7

48 52 65 48 55 57

24.7 34.7 45.9 71.8 95.3 128.2

One pair cables with HFFR insulation and HFFR sheath Unscreened Capacity

Weight

(AWG)

Overall Diameter (mm)

(pF/m)

(kg/km)

22 20 18 16 14 12

4.8 5.3 6.0 7.8 8.8 9.8

140 158 165 150 180 195

27.1 37.2 48.4 74.3 97.9 132.6

BTCL Part Number

C1311 C1309 C1271 C1307 C1306 C1304

Cond.

For more details, please see the respective detailed datasheet(s)

info.btcables@bt.com

18


Section 1.8 Cables for Security & Alarm applications 1 to 6 pairs – 18AWG conductors – polyolefin insulation foil or foil + braid overall screen –HFFR sheath CABLE DESCRIPTION Design 1. Conductor Flexible Bare Copper 2. Insulation Polyolefin

5. Drain Wire Flexible Tinned Copper 24 AWG (7 x 32)

Standard Put Up Length 305 or 500 metres

6. Overall Screen 1 Aluminium/Polyester foil

Standard References (BS) EN 50290-2 IEC 60332-3-24 IEC 61034 IEC 60754-1 & 2 RoHS directives

7. Overall Screen 2 braid coverage

3. Pair Two twisted wires 4. Cable core N pairs stranded

8. Sheath Material Purple Halogen-free (HFFR)

Cables with 18AWG conductors – Polyolefin insulation – Collective Screen and HFFR sheath BTCL Part Number

No. of Pairs

C1171 C1172 C1173 C1174 C1175 C1176

1 2 3 4 5 6

BTCL Part Number

No. of Pairs

Conductor (AWG)

Screen

C1418 C1419 C1420 C1421 C1422 C1423

1 2 3 4 5 6

18 (7 x 26) 18 (7 x 26) 18 (7 x 26) 18 (7 x 26) 18 (7 x 26) 18 (7 x 26)

foil + braid foil + braid foil + braid foil + braid foil + braid foil + braid

Colour scheme C1171 to C1176

Conductor (AWG) 18 (7 x 26) 18 (7 x 26) 18 (7 x 26) 18 (7 x 26) 18 (7 x 26) 18 (7 x 26)

Screen foil foil foil foil foil foil

Pair 1 Black/Red

Max. DC Resistance Conductor (Ω/km) 22.7 22.7 22.7 22.7 22.7 22.7

Overall Diameter (mm) 5.1 7.7 8.1 8.9 9.9 10.2

Max. DC Resistance Conductor (Ω/km) 22.7 22.7 22.7 22.7 22.7 22.7

Pair 2 Black/White

Capacitance

Weight

(pF/m) 115 115 115 115 115 115

(kg/km) 4.1 7.41 9.64 12.37 14.92 17.11

Overall Diameter (mm)

Capacitance (pF/m)

Weight (kg/km)

5.8 8.4 8.8 9.6 10.5 10.9

115 115 115 115 115 115

4.7 10.5 11.6 13.7 16.5 18.6

Pair 3 Black/Green

Pair 4 Black/Blue

Pair 5 Black/Yellow

Pair 6 Black/Brown

For more details, please see the respective detailed datasheet(s)

info.btcables@bt.com

19


Section 1.9 Building Management Systems Cable for 1 pair – 0.6 mm² conductors – polyolefin insulation Collective overall screen –PVC sheath

CABLE DESCRIPTION 1. Conductor Flexible Bare Copper 7 x 0.35 mm = 0.6 mm²

5. Screen Aluminium/Polyester foil

2. Insulation Polyolefin Core 1: Black Core 2: Red

6 Sheath Material Grey PVC

Standard Put Up Length 305 or 500 metres Standard References (BS) EN 50290-2 IEC 60332-1 RoHS directives

3. Pairs two twisted wires 4. Tinned Copper Drain Wirer 7 x 0.20 mm

BTCL Part Number

No. of pairs

C1381

1

Overall Diameter (mm) 3.9

Max. DC Resistance Conductor (Ω/km) 61

Capacitance (pF/m)

Weight (kg/km)

110

14.6

For more details, please see the respective detailed datasheet(s)

info.btcables@bt.com

20


Section 2 - BT BMS-TECTM - Multi-Conductor Cables

Application and Construction 1. Application All PVC and HFFR sheathed multi-conductor cables are suitable for Building Management Systems (BMS), Sound, Audio, Security, Safety, Control and Instrumentation. 2. Basic Construction of the cables Wire = Conductor without or with insulation. With insulation sometimes also indicated as core. Conductor: flexible = twisted bare or tinned copper strands, ranging from 12 to 22AWG. Conductor (AWG) 24 22 20 18 16 14 12

configuration (AWG) 7 x 32 7 x 30 7 x 28 7 x 26 19 x 29 19 x 27 19 x 25

configuration (mm) 7 x 0.2 7 x 0.25 7 x 0.32 7 x 0.40 19 x 0.28 19 x 0.36 19 x 0.45

DC Resistance (Ohm/km) ≤ 88 ≤ 57.4 ≤ 32.16 ≤ 22.7 ≤ 15.47 ≤ 9.36 ≤ 5.61

Insulation: Polypropylene (PP) for PVC (Polyvinyl Chloride) sheathed cables and Halogen-Free (HFFR) for HFFR sheathed cables. Both insulations are in accordance with BS EN 50290-2. Good strippable and coloured insulation. The colours are not interchangeable. Colour scheme of wires with 12 or 14 AWG conductors: black-white-red-green-brown-blue-orange-yellow-purlpe-grey-pinktan. Colour scheme of wires with ≥ 16AWG conductors: black-red-white-green-brown-blue-orange-yellow-purlpe-grey-pink-tan. Cable core: two or more wires, twisted. Good twisting (lay-length < 30 – 40D) is necessary otherwise the cable can hardly be bending and will break after a few bends. Drain wire (only in combination with a screen): stranded tinned copper wires. In order to avoid corrosion, it is recommended that drain wires are tinned. Screen (if applicable): Helically applied (= as a spiral) Aluminium/Polyester (Alpet) foil. For the flexibility of a cable a helically applied foil is to be preferred. A longitudinally applied foil act more as a stiff tube = more difficult to bend. Sheath: grey PVC or purple HFFR or black UV-resistant HFFR, all in accordance with BS EN 50290-2. Cable configurations Insulation Sheath Retardancy Retardant acc. to Low Smoke emission acc. to Halogen-free acc. to RoHS compliant

Cables with PVC sheath PP acc. to (BS)EN 50290-2 PVC acc. to (BS)EN 50290-2 Flame Retardant IEC 60332-1 / UL1581 Not applicable Not applicable Yes

Halogen-Free cables HFFR acc. to (BS)EN 50290-2 HFFR acc. to (BS)EN 50290-2 Fire Retardant IEC 60332-3-24 / UL 1685 IEC 61034 IEC 60754 yes

Operating temperature range: -25 to +75 °C and Rated Voltage: 300 Vrms.

Non-standard cable constructions, colours, details and/or additional information are available on request. For more details, please see the respective detailed datasheet(s). Please note that technical specifications are subject to change without notice.

info.btcables@bt.com

21


Section 2.1 – Multi-Conductor Cables

PVC sheathed cables with 12AWG to 22AWG conductors for Audio, Control, Instrumentation and Building Management Systems (BMS) CABLE DESCRPTION Design 1. Conductor Stranded Bare Copper

4 Drain Wire (only with screen) 24 AWG (7 x 32) Tinned Copper 5 Screen (if applicable) Aluminium/Polyester > 100% Coverage

2. Insulation Polypropylene (PP) 3 Cable Core Two or more wires stranded

Standard References (BS) EN 50290-2 IEC 60332-1 RoHS directives

6. Sheath Material Grey PVC

2 3 4 6 8

(AWG) 22 22 22 22 22

BT Cables Part Number C1226 C1228 C1230 C1264 C1232

Yes Yes Yes Yes Yes

(mm) 3.3 3.5 3.8 4.5 4.9

(kg/km) 16.5 21.4 26 35.7 45.1

BT Cables Part Number C1227 C1278 C1231 C1265 C1233

2 3 4 6 8

20 20 20 20 20

C1019 C1021 C1023 C1260 C1262

Yes Yes Yes Yes Yes

3.5 3.7 4.1 5.0 5.4

22 28.5 35.4 49.9 62.9

C1020 C1022 C1024 C1261 C1263

No No No No No

3.4 3.6 4.0 4.9 5.3

19.7 26.2 33.1 47.9 60.6

2 3 4 6 8

18 18 18 18 18

C1013 C1015 C1017 C1211 C1258

Yes Yes Yes Yes Yes

4.0 4.2 4.6 5.75 6.0

29.6 39.2 49.4 70.9 89.5

C1014 C1016 C1018 C1212 C1259

No No No No No

3.9 4.1 4.55 5.7 5.9

27.3 36.9 47.2 68.2 87

2 3 4 6 8

16 16 16 16 16

C1007 C1009 C1011 C1252 C1254

Yes Yes Yes Yes Yes

4.6 4.9 5.3 6.8 7.6

37.3 50 63.5 91.6 120.8

C1008 C1010 C1012 C1253 C1255

No No No No No

4.5 4.75 5.25 6.7 7.5

35 47.7 61.1 89 118.1

2 3 4 6 8

14 14 14 14 14

C1001 C1003 C1005 C1248 C1250

Yes Yes Yes Yes Yes

6.0 6.5 6.9 8.6 9.8

57 77.9 102.5 151 197.3

C1002 C1004 C1006 C1249 C1251

No No No No No

5.75 6.35 6.75 8.4 9.7

53.3 72.5 97.1 148.2 194.5

2 3 4 6 8

12 12 12 12 12

C1322 C1324 C1326 C1330 C1332

Yes Yes Yes Yes Yes

6.9 7.4 8.2 9.8 10.7

85.7 118.1 151.1 215.5 279.5

C1323 C1325 C1327 C1331 C1333

No No No No No

6.7 7.2 8.0 9.6 10.5

79.8 112.1 145.3 209.7 273.7

No of wires

Cond.

Standard Put Up Length 305 and 500 metres

Diam.

Weight

Scrn

Diam.

Weight

No No No No No

(mm) 3.3 3.5 3.8 4.5 4.9

(kg/km) 14.6 19.7 23.9 33.6 43

Scrn

Scrn = Screen, Diam. = overall diameter. For more details, please see the respective detailed datasheet(s

info.btcables@bt.com

22


Section 2.2 – Multi-Conductor Cables

Halogen-Free (HFFR) cables with 12AWG to 22AWG conductors for Audio, Control, Instrumentation and Building Management Systems (BMS) CABLE DESCRIPTION Design 1. Conductor Stranded Bare Copper

4. Screen (if applicable) Aluminium/Polyester > 100% Coverage

2. Insulation HFFR

5. Ripcord

Standard References (BS) EN 50290-2 IEC 60332-3C IEC 61034 IEC 60754-1 & 2 RoHS directives

6. Sheath Material Purple Halogen-Free (HFFR)

3. Drain Wire (only with screen) 24 AWG (7 x 32) Tinned Copper

2 3 4 6 8

(AWG) 22 22 22 22 22

BT Cables Part Number C1741 C1743 C1745 C1747 C1749

Yes Yes Yes Yes Yes

(mm) 3.9 4.1 4.4 5.2 5.6

(kg/km) 22.4 27.6 33.7 45.8 56.4

BT Cables Part Number C1742 C1744 C1746 C1748 C1750

2 3 4 6 8

20 20 20 20 20

C1731 C1733 C1735 C1737 C1739

Yes Yes Yes Yes Yes

4.7 4.9 5.3 6.2 6.7

32.6 40.2 48.7 66.2 81.9

C1732 C1734 C1736 C1738 C1740

No No No No No

4.6 4.8 5.2 6.1 6.6

30.1 37.7 46.2 63.7 79.4

2 3 4 6 8

18 18 18 18 18

C1721 C1723 C1725 C1727 C1729

Yes Yes Yes Yes Yes

5.1 5.4 5.8 6.8 7.3

41.0 52.3 64.1 88.6 110.8

C1722 C1724 C1726 C1728 C1730

No No No No No

5.0 5.3 5.7 6.7 7.2

38.5 49.8 61.6 86.1 108.2

2 3 4 6 8

16 16 16 16 16

C1711 C1713 C1715 C1717 C1719

Yes Yes Yes Yes Yes

5.4 5.7 6.2 7.3 7.9

49.3 63.8 79.3 108.2 137.0

C1712 C1714 C1716 C1718 C1720

No No No No No

5.4 5.7 6.2 7.3 7.9

46.8 61.3 78.2 107.0 135.9

2 3 4 6 8

14 14 14 14 14

C1701 C1703 C1705 C1707 C1709

Yes Yes Yes Yes Yes

6.5 6.9 7.5 8.9 9.6

67.7 92.8 115.4 163.7 210.8

C1702 C1704 C1706 C1708 C1710

No No No No No

6.4 6.8 7.4 8.8 9.5

65.2 89.1 112.9 162.8 208.3

2 3 4 6 8

12 12 12 12 12

C1334 C1336 C1338 C1342 C1344

Yes Yes Yes Yes Yes

7.7 8.1 8.9 10.6 11.6

102.2 135.0 170.9 243.3 314.6

C1335 C1337 C1339 C1343 C1345

No No No No No

7.5 7.9 8.7 10.4 11.4

97.0 129.7 165.7 237.1 306.2

No of wires

Cond.

Standard Put Up Length 305 metres

Diam.

Weight

Scrn

Diam.

Weight

No No No No No

(mm) 3.9 4.1 4.4 5.2 5.6

(kg/km) 20.5 26.0 31.7 43.9 54.4

Scrn

Scrn = Screen, Diam. = overall diameter. For more details, please see the respective detailed datasheet(s

info.btcables@bt.com

23


Section 2.3 – Multi-Conductor Cables

UV-Resistant Halogen-Free (HFFR) cables with 12AWG to 22AWG conductors for Audio, Control, Instrumentation and Building Management Systems (BMS) CABLE DESCRIPTION Design

Standard Put Up Length 305 metres

1. Conductor Stranded Bare Copper

4. Screen (if applicable) Aluminium/Polyester > 100% Coverage

2. Insulation HFFR

5. Ripcord

Standard References (BS) EN 50290-2 IEC 60332-3C IEC 61034 IEC 60754-1 & 2 RoHS directives

6. Sheath Material Black UV-resistant Halogen-Free (HFFR)

3. Drain Wire (only with screen) 24 AWG (7 x 32) Tinned Copper

(AWG)

BT Cables Part Number

(mm)

(kg/km)

2

18

C1351

Yes

5.1

41.0

3

18

C1352

Yes

5.4

52.3

4

18

C1353

Yes

5.8

64.1

6

18

C1354

Yes

6.8

88.6

8

18

C1355

Yes

7.3

110.8

10

18

C1356

Yes

8.4

135.7

20

18

C1357

Yes

10.7

249.6

Cond.

BT Cables Part Number C1391 C1392 C1393 C1394 C1395 C1396 C1397

Diameter

Weight

(mm) 5.5 5.8 6.3 7.4 8.0 9.5 12.1

(kg/km) 49.3 63.8 79.3 108.2 137.0 173.1 316.6

No of wires

No of wires

Cond.

(AWG)

2

16

3

16

4

16

6

16

8

16

10

16

20

16

Screen

Diameter

Weight

Screen Yes Yes Yes Yes Yes Yes Yes

For more details, please see the respective detailed datasheet(s)

info.btcables@bt.com

24


Section 3 - BT FIREPRO-TEC™ – Fire Detection and Alarm System Cables

Bare Copper 12 to 18AWG, one pair, PVC insulation and Sheath, Screened and Unscreened ©UL Certification: type FPLR rated 105°C - ©UL listed APPLICATION Fire Detection and Alarm Systems Fire Retardancy: UL 1666 Operating temperature range: -40 to +105 °C and Rated Voltage: 300 Vrms

CABLE DESCRIPTION 1. Conductor Solid Bare Copper

4. TC Drain Wire (only under screen) 22 AWG (7 x 30)

2. Insulation PVC acc. to UL444 Black and Red

No. of Pairs

C1040 C1135 C1041 C1136 C1042 C1137 C1043 C1138

1 1 1 1 1 1 1 1

Standard References UL1424 UL444 UL1666 RoHS directives

5. Screen (if applicable) Aluminium/Polyester > 100% Coverage

3. Pair Two wires twisted

BT Cables Part Number

Standard Put Up Length 305 metres

6. Sheath Material Red PVC acc. to UL444

Conductor ( AWG) 18 18 16 16 14 14 12 12

Screen Yes No Yes No Yes No Yes No

POWER-LIMITED CIRCUIT CABLE NO. 000001 1000 FEET F ORM 3

Overall Diameter (mm)

Max. DC Resistance Conductor (Ω/km)

5.9 5.8 6.1 6.0 7.8 7.7 8.7 8.6

22.7 22.7 15.47 15.47 9.36 9.36 5.61 5.61

Capacitance

Weight

(pF/m)

(kg/km)

160 60 189 71 160 69 216 65

19.2 16.0 28.5 25.0 43.0 40.0 66.0 63.0

Non-standard cable constructions, colours, details and/or additional information are available on request. For more details, please see the respective detailed datasheet(s). Please note that technical specifications are subject to change without notice.

info.btcables@bt.com

25


Section 4 - BT FIREPRO-TEC™ – Fire Resistant Cables

Bare and Flexible Copper Conductors 0.75 to 4.0 mm2, Silicon insulation and Halogen-free Sheath, Screened and Unscreened 1. Application All Fire Resistant cables are suitable for Security, Safety, Control and Instrumentation with special requirements for circuit integrity in case of a fire. 2. Fire Resistance confirming with BS6387 CWZ: Fire Resistant to BS 6387, Cat. C: exposed to fire at 950°C for 3 hours Fire Resistant to BS 6387, Cat. W: exposed to fire at 650°C for 15 minutes, then exposed to fire at 650°C with water for 15 minutes Fire Resistant to BS 6387, Cat. Z: exposed to fire at 650°C for 15 minutes, then exposed to fire at 650°C with mechanical shock for 15 minutes 3. Fire Retardancy confirming with IEC 60332-3-24 (was 3C) 4. Basic Construction of the cables Wire = Conductor with Insulation Conductor: solid bare copper wires, ranging from 0.75 to 2.5 mm² and the 4.0 mm² conductor consists of stranded bare copper wires = flexible

Cross Section (mm²) 0.75 1.0 1.5 2.5 4.0

Diameter (mm) 1 x 1.0 1 x 1.13 1 x 1.4 1 x 1.8 7 x 0.85 = 2.55

DC Resistance (Ohm/km) ≤ 24.5 ≤ 18.1 ≤ 12.1 ≤ 7.41 ≤ 4.61

Recommended Current (Amp) ≤ 12 ≤ 18 ≤ 21 ≤ 30 ≤ 40

Insulation: Silicon Rubber blends acc. to BS 7655. Good strippable and coloured insulation. The colours are not interchangeable. Colour scheme: 2 cores: brown – blue, 3 cores: brown – black – grey, 4 and more cores: brown – blue – black – grey – others black numbered. Cable core: two or more cores, twisted. Good twisting is necessary otherwise the cable can hardly be bending and will break after a few bends. Drain wire (only in combination with a screen): solid bare copper. Screen (if applicable): Helically applied (= as a spiral) Aluminium/Polyester (Alpet) foil. For the flexibility of a cable a helically applied foil is to be preferred. A longitudinally applied foil act more as a stiff tube = more difficult to bend. Sheath: red HFFR in accordance with BS EN 50290-2 Operating temperature range: -20 to +90 °C. Rated Voltage: 300/500 Vrms

Non-standard cable constructions, colours, details and/or additional information are available on request. For more details, please see the respective detailed datasheet(s). Please note that technical specifications are subject to change without notice.

info.btcables@bt.com

26


Section 4 - BT FIREPRO-TEC™ – Fire Resistant Cables

CABLE DESCRIPTION 1. Conductor Solid or Flexible Bare Copper 2. Insulation Silicon Rubber blend 3. Cable core Two or three wires Twisted

BT Cables Part Number C1284 C1139 C1159 C1149 C1283 C1140 C1160 C1150 C1044 C1141 C1161 C1151 C1045 C1142 C1162 C1152 C1289 C1143 C1163 C1153

No. of wires 2 2 3 3 2 2 3 3 2 2 3 3 2 2 3 3 2 2 3 3

4. BC Drain Wire (only under screen)

Standard Put Up Length 305 and 500 metres

5. Screen (if applicable) Aluminium/Polyester > 100% Coverage

Standard References BS 6387 CWZ BS 7655 IEC 60332-3C IEC 60754-1 & 2 RoHS directives

6. Sheath Material Red HFFR

Conductor (mm²) 0.75 0.75 0.75 0.75 1.0 1.0 1.0 1.0 1.5 1.5 1.5 1.5 2.5 2.5 2.5 2.5 4.0 4.0 4.0 4.0

Screen

Drain Wire (mm²) 0.75

Yes No Yes No Yes No Yes No Yes No Yes No Yes No Yes No Yes No Yes No

0.75 1.0 1.0 1.5 1.5 2.5 2.5 4.0 4.0

Overall Diameter (mm) 7.5 7.4 7.9 7.8 7.8 7.7 8.1 8.0 8.7 8.6 8.95 8.85 9.9 9.8 10.3 10.2 12.0 11.9 12.95 12.85

Max. DC Resistance Conductor (Ω/km) 24.5 24.5 24.5 24.5 18.1 18.1 18.1 18.1 12.1 12.1 12.1 12.1 7.41 7.41 7.41 7.41 4.61 4.61 4.61 4.61

Weight (kg/km) 67.0 61.7 83 75 73.4 65.5 93 83 98.1 87.6 123 108 134.3 119.4 174 151 197.1 172.6 270 234

For more details, please see the respective detailed datasheet(s)

info.btcables@bt.com

27


Section 5 - BT Security-Tec ™– Coaxial Cables

Application and Construction of Coax Cables for 75 Ohm Video Systems Applications. CCTV: Closed Circuit Television is the use of video cameras to transmit a signal to a specific place, on a limited set of monitors SMATV: Satellite Master Antenna Television used to deliver signals to multiple dwelling units (e.g., apartment buildings and trailer parks). CATV: Central Antenna Television = Cable television is a system of providing television to consumers via radio frequency signals transmitted to televisions. Nowadays also used for internet and telephone. HDTV: High-definition television refers to video having resolution substantially higher than traditional television systems. Telecom and networking: a number of special cable constructions. Basic Cable Design. Coaxial cables are designed to carry radio frequency current of a much higher frequency than the 50 or 60 Hz used in low voltage cables. And this requires special construction to prevent power losses. If an ordinary wire is used to carry high frequency currents, the wire acts as an antenna, and the high frequency currents radiate off the wire as radio waves, causing power losses. To prevent this, in coaxial cable one of the conductors is formed into a tube and encloses the other conductor. This confines the radio waves from the central conductor to the space inside the tube. To prevent the outer conductor, or shield, from radiating, it is connected to electrical ground, keeping it at a constant potential. The dimensions and spacing of the conductors must be uniform throughout the length of the cable. Any abrupt change in the spacing of the two conductors along the cable tends to reflect radio frequency power back toward the source. This acts as a bottleneck, reducing the amount of power reaching the destination end of the cable. Choosing the correct 75 ohm coax cable. Most coaxial cables for video applications have a nominal impedance of 75 ohms. Their differing electrical and physical characteristics make it important to select the correct type of cable to suit the application. RG59 Analogue TV

RG6 RG11 RG59

CCTV

RG6 RG11

Acceptable performance on cable runs < 225 metres Gives superior performance on cable runs < 225 metres. Used for cable runs > 225 metres but < 545 metres. For cable runs greater than 545 metres. Acceptable performance on cable runs < 225 metres Gives for superior performance on cable runs < 225 metres. Used for cable runs > 225 metres but < 545 metres. For cable runs greater than 545 metres.

This table is for reference only. BT Cables survey of Part Numbers. Application CCTV – PVC sheath CCTV – HFFR sheath CCTV CATV / SMATV CATV / SMATV HDTV – PVC sheath HDTV – HFFR sheath

Tested 1000 MHz 1000 MHz 1000 MHz 3000 MHz 3000 MHz 4500 MHz 4500 MHz

Speciality Solid conductor Solid conductor Flexible conductor Dual screen Quad screen Dual Screen 95% Dual Screen 95%

RG-59 C1028 C1428 C1275 C1025 C1256 C1229 C1378

RG-6 C1029 C1429 C1276 C1026 C1257 C1279 C1379

RG-11 C1030 C1430 C1277 C1027 C1241 C1280 C1380

Operating temperature range: -25 to +75 °C and Rated Voltage: 300 Vrms

info.btcables@bt.com

28


Section 5.1 – BT Security-Tec ™– 75 ohm coax cables

CCTV and Video Applications, sweep tested 1to 1000 MHz CABLE DESCRIPTION 1. Conductor Solid or Flexible Bare Copper

Standard References IEC 61196 (BS) EN 50117 (BS) EN 50290-2 IEC 60332-1 (PVC sheath) or IEC 60332-3-24 (HFFR cable) IEC 61034 (only HFFR cable) IEC 60754-1 & 2 (HFFR cable) RoHS directives

4. Sheath Material Polyvinyl Chloride (PVC) or Halogen-Free (HFFR)

2. Dielectric Foamed Polyethylene (FPE)

Standard Put Up Length 305 or 500 metres

3. Braid Bare Copper

Physical Characteristics BT Cables Part Number C1028 C1428 C1275 C1029 C1429 C1276 C1030 C1480 C1277

Conductor

Diameter Dielectric (mm) 3.71 3.71 3.71 4.60 4.60 4.60 7.11 7.11 7.11

RG-Type RG-59 RG-59 RG-59 RG-6 RG-6 RG-6 RG-11 RG-11 RG-11

(mm) 0.81 solid 0.81 solid 19x0.18TC 1.02 solid 1.02 solid 19x0.22 1.63 solid 1.63 solid 19x0.34

Coverage braid (%) 95 95 95 95 95 95 90 90 90

Sheath Material PVC HFFR PVC PVC HFFR PVC PVC HFFR PVC

Overall Diameter (mm) 6.0 6.0 6.0 6.8 6.8 6.8 10.0 10.0 10.0

Weight (kg/km) 47.12 48.5 47.12 55.5 58.2 54.66 115.9 120 115.9

Electrical and Physical Characteristics (at 20°C) BT Cables Part Number

RG-Type

Impedance (Ω)

C1028 C1428 C1275 C1029 C1429 C1276 C1030 C1480 C1277

RG-59 RG-59 RG-59 RG-6 RG-6 RG-6 RG-11 RG-11 RG-11

75 ± 3 75 ± 3 75 ± 3 75 ± 3 75 ± 3 75 ± 3 75 ± 3 75 ± 3 75 ± 3

Max. DC Resistance Conductor (Ω/km) 33.5 33.5 40 21.5 21.5 30 8.8 8.8 8.8

Max. DC Resistance screen (Ω/km) 10.1 10.1 10.1 10.8 10.8 10.8 6.5 6.5 6.5

Nominal Capacitance (pF/m) 53.5 53.5 53.5 53.5 53.5 53.5 52.8 52.8 52.8

Min. Return Loss 1 to 1000 MHZ (dB) 20 20 20 20 20 20 20 20 20

Nominal Attenuation in dB/100m MHz RG-59 RG-6 RG-11

5 1.9 1.78 0.99

10 2.95 2.36 1.51

50 6.23 4.92 2.96

100 8.53 6.56 4.27

200 11.81 9.51 6.23

300 15.3 12.43 8.27

400 16.41 13.78 9.51

450 18.92 15.14 10.31

550 21.03 17.15 11.51

700 22.97 18.37 13.45

750 24.8 19.73 13.95

870 26.84 20.26 14.87

1000 27.89 21.96 17.06

For more details, please see the respective detailed datasheet(s).

info.btcables@bt.com

29


Section 5.2 – BT Security-Tec ™– 75 ohm coax cables

SMATV - CATV and Video applications, sweep tested1to 3000 MHz CABLE DESCRIPTION 1. Conductor Solid Copper Covered Steel (CCS)

5. Braid 2 (Quad scrn only) Aluminium/Polyester foil 100% coverage

2. Dielectric Foamed Polyethylene (FPE)

6. Screen 2 (Quad scrn only) Aluminium

3. Screen 1 Bonded Aluminium/ Polyester foil 100% coverage

7. Sheath Polyvinyl Chloride (PVC)

Standard References IEC 61196 (BS) EN 50117 (BS) EN 50290-2 IEC 60332-1 RoHS directives

Standard Put Up Length 305 or 500 metres

4. Braid 1 Aluminium

Physical Characteristics BT Cables Part Number C1025 C1256 C1026 C1257 C1027 C1241

Conductor RG-Type (mm) 0.81 0.81 1.02 1.02 1.63 1.63

RG-59-3 GHz RG-59-3 GHz RG-6-3 GHz RG-6-3 GHz RG-11-3 GHz RG-11-3 GHz

Diameter Dielectric (mm) 3.71 3.71 4.60 4.60 7.11 7.11

Type of Screen Dual scrn Quad scrn Dual scrn Quad scrn Dual scrn Quad scrn

Coverage braid (%) 54 54 + 46 60 60 + 40 61 60 +40

Sheath Material PVC PVC PVC PVC PVC PVC

Overall Diameter (mm) 6.0 6.73 6.8 7.52 10.0 10.3

Weight (kg/km) 32.42 39.4 41.32 49.5 86.6 90.6

Dual Screen = Screen 1 + Braid 1 Quad Screen = Screen 1 + Braid 1 + Screen 2 + Braid 2 Electrical and Physical Characteristics (at 20°C) BT Cables Part Number

RG-Type

Imped.

C1025 C1256 C1026 C1257 C1027 C1241

RG-59-3 GHz RG-59-3 GHz RG-6-3 GHz RG-6-3 GHz RG-11-3 GHz RG-11-3 GHz

(Ω) 75 ± 3 75 ± 3 75 ± 3 75 ± 3 75 ± 3 75 ± 3

Max. DC Resistance Conductor (Ω/km) 146.5 146.5 92.2 92.2 36.5 36.5

Max. DC Resistance Screen (Ω/km) 52 26 30 17 25 12

Nominal Capacitance (pF/m) 53 53 53 53 53 53

Min. Return Loss (dB) < 1000 < 2000 < 3000 MHz MHz MHz 18 16 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20

Nominal Attenuation in dB/100m MHz

5

10

50

100

200

400

550

870

1250

1750

2150

2500

3000

RG-59 RG-6 RG-11

2.92 2.2 1.25

3.45 2.48 2.03

5.40 5.15 3.75

8.21 6.6 5.01

12.56 9.56 6.85

16.01 13.12 7.05

19.36 15.45 9.65

24.74 19.69 12.6

30.62 24.25 16.66

36.71 29.26 20.28

40.82 32.88 22.93

44.72 35.88 25.12

48.64 39.83 28.08

For more details, please see the respective detailed datasheet(s)

info.btcables@bt.com

30


Section 5.3 – BT Security-Tec ™– 75 ohm coax cables

HDTV and HD Video applications, sweep tested1to 4500 MHz CABLE DESCRIPTION 1. Conductor Solid Bare Copper

4. Braid Tinned Copper

2. Dielectric Foamed Polyethylene

5. Sheath Material Polyvinyl Chloride (PVC) or Halogen-free (HFFR) Colour: Orange

3. Screen Bonded Aluminium/ Polyester foil 100% coverage

Standard References IEC 61196 (BS) EN 50117 (BS) EN 50290-2 IEC 60332-1(PVC sheath) or IEC 60332-3C ( HFFR cable) IEC 61034 (HFFR cable) IEC 60754-1 & 2 (HFFR cable) RoHS directives

Standard Put Up Length 305 or 500 metres

Physical Characteristics BT Cables Part Number C1229 c1378 C1279 c1379 C1280 C1380

Conductor RG-Type (mm) 0.81 0.81 1.02 1.02 1.63 1.63

RG-59-4.5 GHz RG-59-4.5 GHz RG-6-4.5 GHz RG-6-4.5 GHz RG-11-4.5 GHz RG-11-4.5 GHz

Diameter Dielectric (mm) 3.71 3.71 4.60 4.60 7.11 7.11

Coverage braid (%) 95 95 95 95 95 95

Sheath Material PVC HFFR PVC HFFR PVC HFFR

Overall Diameter (mm) 6.0 6.0 6.8 6.8 10.0 10.0

Weight (kg/km) 46.72 48.2 56.2 59 114.5 117

Electrical and Physical Characteristics (at 20°C) BT Cables Part Number

RG-Type

Imp.

C1229 c1378 C1279 c1379 C1280 C1380

RG-59-4.5 GHz RG-59-4.5 GHz RG-6-4.5 GHz RG-6-4.5 GHz RG-11-4.5 GHz RG-11-4.5 GHz

(Ω) 75 ± 3 75 ± 3 75 ± 3 75 ± 3 75 ± 3 75 ± 3

Max. DC Resistance Conductor (Ω/km) 33.5 33.5 21.5 21.5 8.8 8.8

Max. DC Resistance Screen (Ω/km) 12.5 12.5 10.6 10.6 6.6 6.6

Nom. Cap. (pF/m) 53 53 53 53 53 53

<1000 MHz 23 23 23 23 23 23

Min. Return Loss (dB) < 2000 < 3000 MHz MHz 22 16 22 16 22 16 22 16 22 16 22 16

< 4500 MHz 15 15 15 15 15 15

Nominal Attenuation in dB/100m MHz RG-59 RG-6 RG-11

1 0.98 0.79 0.53

5 2.07 1.71 1.12

10 2.95 2.33 1.51

50 6.23 4.57 2.96

100 7.55 6.40 4.20

300 13.68 11.96 7.49

550 18.83 15.76 10.41

750 22.23 18.05 12.38

1000 25.96 21.36 14.57

2000 38.24 31.44 21.84

3000 46.13 39.76 27.93

4500 56.50 50.46 35.98

For more details, please see the respective detailed datasheet(s).

info.btcables@bt.com

31


Section 6 – BT Data-Tec™ - Category LAN Cables Application and Construction of Category Cables Area Networks and Structured Wiring Systems for Local 1. Application Horizontal or Building Wiring for one of the following categories of twisted pair cabling systems

Cat 1 Cat 2 Cat 3 Cat 4 Cat 5

Max. data rate 1 Mbps 4 Mbps 16 Mbps 20 Mbps 100 MHz

Cat 5e

100 MHz

Cat 6

250 MHz

Cat 6a

500 MHz

Cat 7

600 MHz

As Cat 6a plus supporting 100GbE

Cat 7a

1000 MHz

CATV (862 MHz), 40GBASE-T over 50 m. 100GbE over 15 m.

Category

Usual application

Standard(s) ISO/IEC

TIA/EIA

Analogue voice Token ring of IBM Voice, 10MbE(thernet) 16 Mbps Token Ring 10/100/1000 MbE 155 Mbps ATM, 4/16 Mbps Token Ring as Cat5e plus 10Gb Ethernet over ≤ 55 m. As Cat 6 plus 10Gb Ethernet over 100 m.

EN

De facto, never a standard TIA/EIA 568-B Was only a standard briefly Replaced by 5e

TIA/EIA 568-C.2

Cat 7a is not recognised in TIA/EIA-569

ISO/IEC 11806, 2nd edition IEC 61156 ISO/IEC 11801: 2002, category 7 / class F ISO/IEC 11801, amendment 1 (2008) and amendment 2 (2010).

EN 50173-1 EN 50288

2. Basic Cable Construction of the standard cables (not being patch cables) Wire = Conductor with Insulation Insulation: will be good strippable, suitable for insulation displacement and coloured. The colours are not interchangeable. Pair = two twisted – colour coded – wires. Individually screened pair (if applicable): one pair wrapped with an Aluminium/Polyester foil under which a drain wire. Braiding (if applicable): tinned copper wires. Ripcord: to ease removal of the sheath. Sheath: PVC or Halogen-Free (HFFR). Cat 3 Type

UUTP

Conductor Insulation Cable core Core wrapping Drain wire Overall screen Sheath

Solid BC Polyolefin 6 to 200 pairs Yes No No PVC

Cat 5e UUTP

Cat 6

FUTP

Solid BC PE

No No

UUTP

FUTP

Solid BC PE 4 pairs

Yes Foil

No Yes No Foil PVC or HFFR

info.btcables@bt.com

Cat 6a Cat 7 Cat 7a UFTP & S-FTP S-FTP UUTP FUTP Solid BC Solid BC Solid BC Skin-foam-skin PE 4 Individually screened pairs No No Central drain wire Braiding HFFR

32


Section 6 – BT Data-Tec™ - Category LAN Cables 3. Basic Cable Construction of the standard patch cables

Cat 5e Cat 6 UUTP FUTP UUTP FUTP Flexible BC PE PE 4 pairs 4 pairs no yes no yes no yes no yes no foil no foil yes PVC or HFFR

Type Conductor Insulation Cable core Core wrapping Drain wire (TC) Overall Screen Rip cord Sheath 4. General Characteristics Max. DCR conductor Impedance

Cat 3 9.6 100

Ω/100m Ω

Cat 5e 9.38 100

Cat 6 9.38 100

Cat 6a 7.7 100

Cat 7 7.7 100

Standard Colour scheme of Cat 5e – 6 – 6a and 7: Pair number a-wire

Pair 1 Blue White with blue stripe

b-wire

Pair 2 Orange White with orange stripe

Pair 3 Green White with green stripe

Pair 4 Brown White with brown stripe

Operating temperature range: -20 to +80 °C and Rated Voltage: 300 Vrms. 5. Cable Range of BT Cables: Cat3 - PVC Category Type Sheath BT P/N

2 pairs C1031 Cat 5e UTP PVC C1035

6 pairs C1266

12 pairs C1267

Cat 5e UTP-UL listed PVC C1285

Category Type Sheath BT P/N

Cat 6 UUTP PVC C1037

Cat 6 UUTP-UL listed PVC C1287

Category Type Sheath BT P/N

Cat 6a U-UTP PVC C1200

Cat 6a U-FTP HFFR C1053

Category Type Sheath BT P/N

Cat 5e UTP-Patch PVC C1500

Cat 5e UTP-Patch HFFR C1510

25 pairs C1032

50 pairs C1033

Cat 5e UTP HFFR C1235

Cat 6 UUTP HFFR C1227 Cat 7 S-FTP HFFR C1039

Cat 5e FTP-Patch PVC C1520

Cat 6 FUTP PVC C1038

100 pairs C1034

150 pairs C1268

Cat 5e FTP PVC C1036

Cat 5e FTP-UL listed PVC C1286

Cat 6 FUTP-UL listed PVC C1288

Cat 6 FUTP HFFR C1238

200 pairs C1269 Cat 5e FTP HFFR C1236

Cat 7a S-FTP HFFR C1201 Cat 5e FTP-Patch HFFR C1530

Cat 6 UTP-Patch PVC C1540

Cat 6 UTP-Patch HFFR C1550

Cat 6 FTP-Patch PVC C1560

Cat 6 FTP-Patch HFFR C1570

Non-standard cable constructions, colours, details and/or additional information are available on request. For more details, please see the respective detailed datasheet(s). Please note that technical specifications are subject to change without notice.

info.btcables@bt.com

33


Section 6.1 – BT Data-Tec™ - Category LAN Cables Cat 5e and 6 UTP and FTP cables

Cat 5e cables BT Cables Part Number C1035 C1285 C1235 C1036 C1286 C1236

Type UUTP UUTP-UL UUTP FUTP FUTP-UL FUTP

Cat 5e Variants Overall Diameter Sheath (mm) 5.0 PVC 5.0 PVC 5.0 HFFR 6.3 PVC 6.3 PVC 6.3 HFFR

Weight (kg/km) 30 30 29 42 42 42

Main Transmission Characteristics of Cat 5e cables Frequency (MHz)

Min. Return Loss (dB/100m)

Maximum Attenuation (dB/100m)

Minimum NEXT (dB)

Maximum Time Delay (ns/100m)

Minimum PSNEXT (dB)

Minimum ELFEXT (dB)

Minimum PSELFEXT (dB)

1 4 8 10 16 20 25 31.25 62.5 100

20.0 23.0 24.5 25.0 25.0 25.0 24.3 23.6 21.5 20.1

2.0 4.1 5.8 6.5 8.2 9.3 10.4 11.7 17.0 22.0

65.3 56.3 51.8 50.3 47.2 45.8 44.3 42.9 38.4 35.3

570.00 552.00 546.73 545.38 543.00 542.05 541.20 540.44 538.55 537.60

62.3 53.3 48.8 47.3 44.4 42.8 41.3 39.9 35.4 32.3

64.0 52.0 45.9 44.0 39.9 38.0 35.8 34.1 28.1 24.0

61.0 49.0 42.9 41.0 36.9 35.0 33.0 31.1 25.1 21.0

Cat 6 cables Cat 6 Variant

BT Cables Part Number C1037 C1287 C1237 C1038 C1288 C1238

Type

Sheath

UUTP UUTP-UL UUTP FUTP FUTP-UL FUTP

PVC PVC HFFR PVC PVC HFFR

Overall Diameter (mm) 6.2 6.2 6.2 7.4 7.4 7.4

Weight (kg/km) 42 42 42 56 56 54.1

Main Transmission Characteristics of Cat 6 cables Frequency (MHz)

Return Loss (dB/100m)

Maximum Attenuation (dB/100m)

Minimum NEXT (dB)

Maximum Time Delay (ns/100m)

Minimum PSNEXT (dB)

Minimum ELFEXT (dB)

Minimum PSELFEXT (dB)

1 4 8 10 16 20 25 31.25 62.5 100 200 250

20.0 23.0 24.5 25.0 25.0 25.0 24.3 23.6 21.5 20.1 18.0 17.3

2.0 3.8 5.3 6.0 7.6 8.5 9.5 10.7 15.4 19.8 29.0 32.8

74.3 65.3 60.8 59.3 56.2 54.8 53.3 51.9 47.4 44.3 39.8 38.3

570.00 552.00 546.73 545.38 543.00 542.05 541.20 540.44 538.55 537.80 536.54 536.27

72.3 63.3 58.8 57.3 54.2 52.8 51.3 49.9 45.4 42.3 37.8 36.3

67.8 55.8 49.7 47.8 43.7 41.8 39.8 37.9 31.9 27.8 21.8 19.8

64.8 52.8 46.7 44.8 40.7 38.8 36.8 34.9 28.9 24.8 18.8 16.8

For more details, please see the respective detailed datasheet(s).

info.btcables@bt.com

34


Section 6.2 – BT Data-Tec™ - Category LAN Cables Cat 6a U-FTP and Cat 7 S-FTP cables Cat 6a U-FTP cables

BT Cables Part Number

Type

C1200 C1053

U-UTP U-FTP

Cat 6a Variants Overall Diameter Sheath (mm)

Weight (kg/km)

8.3 7.2

PVC HFFR

61.2 49.9

Main Transmission Characteristics of Cat 6a U-FTP cables Freq. (MHz)

Return Loss (dB/100m)

Attenuation (dB/100m)

NEXT (dB/100m)

PSNEXT (dB/100m)

ELFEXT (dB/100m)

Impedance (Ohm))

1 10 31.25 100 300 500

20.0 25.0 23.6 20.1 17.3 17.3

3.7 5.8 10.4 19.0 34.2 45.2

74.3 59.3 51.9 44.3 37.1 33.8

72.3 57.3 49.9 42.3 35.1 31.8

55.9 47.8 37.9 27.8 18.1 14.0

100 ± 15 100 ± 15 100 ± 15 100 ± 15 100 ± 25 100 ± 15

Cat 7 cables

BT Cables Part Number

Type

C1039

S-FTP

Cat 7 Variants Overall Diameter Sheath (mm)

Weight (kg/km)

7.8

HFFR

67.5

Main Transmission Characteristics of Cat 7 S-FTP cables Frequency (MHz)

Return Loss (dB/100m)

Attenuation (dB/100m)

NEXT (dB)

PSNEXT (dB)

ELFEXT (dB)

Impedance (Ohm)

1 10 20 62.5 300 600

20.0 25.0 25.0 21.5 14.5 12.5

2.5 6.5 8.9 14.9 35.2 50.1

78 78 78 75.5 65.2 60.7

75 75 75 72.5 62.2 57.7

78.0 56.5 56.5 56.8 25.0 16.0

100 ± 15 100 ± 15 100 ± 15 100 ± 15 100 ± 25 100 ± 25

Cat 7a cables

BT Cables Part Number

Type

C1201

S-FTP

Cat 7a Variants Overall Diameter Sheath (mm)

Weight (kg/km)

8.5

HFFR

71.1

Main Transmission Characteristics of Cat 7a S-FTP cables Frequency (MHz)

Return Loss (dB/100m)

Attenuation (dB/100m)

NEXT (dB)

PSNEXT (dB)

ACR (dB)

Impedance (Ohm)

4 10 20 62.5 300 600 900 1000

23.0 25.0 25.0 21.5 17.3 17.3 17.3 16.0

4.0 5.8 8.2 14.6 32.7 47.1 54.9 61.9

80.0 80.0 80.0 80.0 71.2 66.7 64.9 63.4

77.0 77.0 77.0 77.0 68.2 63.7 61.9 60.4

78.0 74.3 71.0 60.6 38.6 19.6 9.93 1.47

100 ± 15 100 ± 15 100 ± 15 100 ± 15 100 ± 25 100 ± 25 100 ± 25 100 ± 25

For more details, please see the respective detailed datasheet(s).

info.btcables@bt.com

35


Section 6.3 – BT Data-Tec™ - Category LAN Cables Cat 5e and Cat 6 UTP and FTP PATCH Cables

Cat 5e and Cat6 Patch cables

BT Cables Part Number

Type

C1500 C1510 C1520 C1530

UUTP UUTP FUTP FUTP

Cat 5e Variants Overall Diameter Sheath (mm)

Weight (kg/km)

5.2 5.2 5.1 5.1

PVC HFFR PVC HFFR

30.7 31.4 31.2 31.1

Main Transmission Characteristics of Cat 5e Patch cables Cat 5e - Patch

UTP / FTP

Frequency (MHz)

Return Loss (dB/100m)

1 4 8 10 16 20 25 31.25 62.5 100

20.0 23.0 24.5 25.0 25.0 25.0 24.2 23.3 20.7 19.0

UTP

FTP Maximum Attenuation (dB/100m)

2.4 4.9 6.9 7.8 9.9 11.1 12.5 14.1 20.4 26.4

3.1 6.1 8.6 9.7 12.4 13.9 15.6 17.6 25.5 33.0

UTP / FTP

UTP / FTP

UTP / FTP

UTP / FTP

Minimum NEXT (dB)

Minimum PSNEXT (dB)

Minimum ELFEXT (dB)

Minimum PSELFEXT (dB)

65.3 56.3 51.8 50.3 47.2 45.8 44.3 42.9 38.4 35.3

62.3 53.3 48.8 47.3 44.2 42.8 41.3 39.9 35.4 32.3

63.8 51.8 45.7 43.8 39.7 37.8 35.8 33.9 27.9 23.8

60.8 48.8 42.7 40.8 36.7 34.8 32.8 30.9 24.9 20.8

Cat 6 Patch cables

BT Cables Part number

Type

C1540 C1550 C1560 C1570

UUTP UUTP FUTP FUTP

Cat 6 Variants Overall Diameter Sheath (mm)

Weight (kg/km)

5.9 5.9 6.2 6.2

PVC HFFR PVC HFFR

31.6 32.4 34.6 35.8

Main Transmission Characteristics of Cat 6 Patch cables Cat 6 - Patch

UTP / FTP

Frequency (MHz)

Return Loss (dB/100m)

1 4 10 16 20 31.25 62.5 100 200 250

20.0 23.0 25.0 25.0 25.0 23.3 20.7 19.0 16.4 15.5

UTP

FTP Maximum Attenuation (dB/100m)

2.4 4.6 7.2 9.1 10.2 12.9 18.6 23.9 35.0 39.4

3.1 6.1 8.6 12.4 13.9 17.6 25.5 33.0 48.6 55.3

UTP / FTP

UTP / FTP

UTP / FTP

UTP / FTP

Minimum NEXT (dB)

Minimum PSNEXT (dB)

Minimum ELFEXT (dB)

Minimum PSELFEXT (dB)

74.3 65.3 59.3 56.2 54.8 51.9 47.4 44.3 39.8 38.3

72.3 63.3 57.3 54.2 52.8 49.9 45.4 42.3 37.8 36.3

67.8 56.0 48.0 43.9 42.0 38.1 32.1 28.0 22.0 20.0

64.8 53.0 45.0 40.9 39.0 35.1 29.1 25.0 19.0 17.0

For more details, please see the respective detailed datasheet(s).

info.btcables@bt.com

36


Section 6.4 – BT Data-Tec™ - Category LAN Cables Cat 3 multi pair Cables Cat 3 cables

BT Cables Part Number

No. of pairs

C1031 C1266 C1267 C1032 C1033 C1034 C1268 C1269

2 6 12 25 50 100 150 200

Cat 3 cables Nom. Nom. Diameter Diameter Conductor Insulation (mm) (mm)

0.5 0.5 0.5 0.5 0.5 0.5 0.5 0.5

Nom. Overall Diameter (mm)

0.9 0.9 0.9 0.9 0.9 0.9 0.9 0.9

3.6 5.5 7.4 11.8 15.5 21.6 26.8 29.4

Weight (kg/km)

16 39 73 154 280 530 800 1040

Electrical Characteristics Cat 3 cables at 20° Frequency

Max. Attenuation

Max. NEXT

Min. Return Loss

Impedance

MHz 1 4 8 10 16

(dB/100m) 2.6 5.6 8.5 9.7 13.1

(dB) 41.3 32.3 27.8 26.3 23.3

(dB) 12.0 12.0 12.0 12.0 10.0

(Ohm) 100 ± 15 100 ± 15 100 ± 15 100 ± 15 100 ± 15

Cable Make-Up Cat 3 cables C1031

C1266

C1267

C1032

C1033

C1034

C1268

C1269

2

6

12

25

50

100

150

200

Number of pairs per unit

25

10

25

25

25

Number of units in the centre

1

5

4

1

1

5

7

BT Cables Part Number No of pairs

Number of units in the 1e layer Pair Colour Code Cat 3 cables Pair No.

Pair Colours in 2 – 6 -12 or 25 pairs cables

Pair No.

Pair Colours in Unit of 12 or 25 pairs

Pair No.

Pair Colours in Unit of 25 pairs

1

White / Blue

11

Black / Blue

21

Purple / Blue

2

White / Orange

12

Black / Orange

22

Purple / Orange

3

White / Green

13

Black / Green

23

Purple / Green

4

White / Brown

14

Black / Brown

24

Purple / Brown

5

White / Grey

15

Black / Grey

25

Purple / Grey

6

Red / Blue

16

Yellow / Blue

7

Red / Orange

17

Yellow / Orange

8

Red / Green

18

Yellow / Green

9

Red / Brown

19

Yellow / Brown

10

Red / Grey

20

Yellow / Grey

For more details, please see the respective detailed datasheet(s).

info.btcables@bt.com

37


Section 7 – BT Industrial-Tec™ - DEF Standard Cables

DEF Standard 51-12 Parts 4 & 5 1. Application Originally developed for military use, these flexible multi-conductor cables are now widely used within the industry. They are designed for high density wiring between and within instruments and electronic equipment and/or components and especially used in process control systems, computers, data processors, sound systems and of course in military equipment. 2. Main Standard DEF standard 61-12, part 4 and 5. 2. Basic Construction of the cables Wire = Conductor with Insulation. Conductor: flexible = stranded tinned copper wires. Size configuration Max. DC Resistance Max. recommended current Rated Voltage

mm2 mm Ω/km Amps Vrms

0.055 7 x 0.1 345 0.25 250

0.22 7 x 0.2 86.2 1 440

0.5 16 x 0.20 37.7 2.5 440

Insulation: PVC (Polyvinyl Chloride). Good strippable and coloured insulation. The colours are not interchangeable. Cable core: two or more wires, stranded. Colour scheme: Core No. 1 2 3 4 5 6 7 8 9 10

Color Red Blue Green Yellow White Black Brown Violet Orange Pink

Core No. 11 12 13 14 15 16 17 18 19 20

Color Turquoise Grey RED/Blue GREEN/Red YELLOW/Red WHITE/Red RED/Black RED/Brown YELLOW/Blue WHITE/Blue

Core No. 21 22 23 24 25 26 27 28 29 30

Color BLUE/Black ORANGE/Blue GREEN/Blue GREY/Blue YELLOW/Green WHITE/Green GREEN/Black ORANGE/Green GREY/Green YELLOW/Brown

Core No. 31 32 33 34 35 36

Color

50

WHITE/Brown BROWN/Black GREY/Brown YELLOW/Violet VIOLET/Black WHITE/Violet Special scheme, on request available

Drain wire (only in combination with a screen): twisted (= flexible) tinned copper wires. Screen (if applicable): Braiding of tinned copper wires, coverage 91%. Sheath: grey PVC. Flame Retardancy: IEC 60332-1 (Vertical Wire test). Operating temperature range: -20 to +70 °C.

Non-standard cable constructions, colours, details and/or additional information are available on request. For more details, please see the respective detailed datasheet(s). Please note that technical specifications are subject to change without notice.

info.btcables@bt.com

38


Section 7 – BT Industrial-Tec™ - DEF Standard Cables

CABLE DESCRIPTION 1. Conductor Stranded Tinned Copper

4. Screen (if required) Tinned Copper 91% Coverage

Standard Put Up Length 305 metres

2. Insulation PVC

5. Ripcord

Standard References DEF standard 61-12, part 4 & 5 IEC 60332-1 RoHS directives

6. Sheath Material Flame-Retardant Polyvinyl Chloride (PVC) Standard colour: grey

3. Cable core) Two or more wires stranded

No of wires 2 3 4 6 9 15 25 36 50

BT Cables Part Number C1164 C1165

No of wires 2 3 4 6 8 12 20 36

BT Cables Part Number

No of wires 2 3 4 6 12 18

BT Cables Part Number

C1166

C1168 C1169 C1365

C1471 C1472 C1473 C1474 C1475 C1476

C1177 C1178 C1375 C1180

Conductor 7 x 0.1 mm = 0.055 mm² Diameter BT Cables Screen (mm) Part Number Yes 3.2 C1360 Yes 3.6 C1361 C1362 Yes 4.2 C1144 C1145 C1146 Yes 6.3 C1147 Yes 6.9 C1148 Yes 8.0 C1364

Conductor 7 x 0.2 mm = 0.22 mm² Diameter BT Cables Screen (mm) Part Number C1366 C1367 Yes 4.4 C1368 Yes 5.6 C1369 Yes 6.1 C1154 Yes 6.9 C1155 Yes 8.6 C1156 Yes 10.8 C1157

Conductor 16 x 0.2 mm = 0.5 mm² Diameter BT Cables Screen (mm) Part Number C1158 C1370 Yes 7.3 C1371 Yes 8.3 C1372 Yes 10.5 C1373 Yes 12.0 C1374

Screen No No No No No No No No No

Screen No No No No No No No No

Screen No No No No No No

Diameter (mm) 2.3 2.4 2.6 3.1 3.7 4.2 5.5 6.1 7.2

Diameter (mm) 3.4 3.6 3.9 4.6 5.6 6.1 7.8 9.8

Diameter (mm) 5.5 5.8 6.3 7.3 9.5 11.0

For more details, please see the respective detailed datasheet(s)

info.btcables@bt.com

39


8 – BT Industrial-Tec™ - Industrial Cables Section

Application and Construction 1. Application These cables are generally used to transmit analogue or digital signals in industrial process plants where chemical and mechanical protections are needed (chemical and petrochemical industries). The unarmoured versions (Type 1) are generally use for indoor installation. 2. Main Standard BS(PAS) 5308 – Part 2 – Type 1 & 2. 2. Basic Construction of the cables Wire = Conductor with Insulation. Conductor: flexible = stranded tinned copper wires. Pair: two twisted wires. mm2 mm Ω/km °C °C Amps pF/m μH/Ω Vrms

Conductor Size configuration Max. DC Resistance at 20°C Max. conductor temperature Min. operating temperature Max. recommended current Max. mutual capacitance at 1 kHz Max. L/R ratio Rated Voltage

0.5 16 x 0.2 39.7 65 -20 6 250 25 300 / 500

0.75 24 x 0.2 26.5 65 -20 8 250 25 300 / 500

1.5 7 x 0.53 12.3 65 -20 12 250 40 300 / 500

Insulation: PVC (Polyvinyl Chloride) in accordance with BS 7655. Good strippable and coloured insulation. The colours are not interchangeable. Cable core: two or more pairs, stranded. Colour scheme: Pair No. a-wire b-wire Pair No. a-wire b-wire

1 White Blue 11 Black Blue

2 White Orange

12 Black Orange

3 White Green 13 Black Green

4 White Brown 14 Black Brown

5 White Grey 15 Black Grey

6 Red Blue 16 Yellow Blue

7 Red Orange

17 Yellow Orange

8 Red Green 18 Yellow Green

9 Red Brown 19 Yellow Brown

10 Red Grey 20 Yellow Grey

Drain wire (only in combination with an individual or collective screen): stranded tinned copper wires. Individual Screen (if applicable): Aluminium/Polyester (Alpet) tape. Coverage ≥ 115%. Collective Screen (if applicable): Aluminium/Polyester (Alpet) tape. Coverage ≥ 115%. Bedding (if applicable): Flame Retardant PVC. Armour (if applicable): galvanised steel wires. Sheath: Flame Retardant PVC. Flame Retardancy: IEC 60332-1 (Vertical Wire test).

Non-standard cable constructions, colours, details and/or additional information are available on request. For more details, please see the respective detailed datasheet(s). Please note that technical specifications are subject to change without notice.

info.btcables@bt.com

40


8 – BT Industrial-Tec™ - Industrial Cables Section

BS(PAS) 5308 - Part 2 – Type 1 – Collectively Screened Cables Conductor 0.5 mm² (16 x 0.2 mm) No of pairs 1 2 5 10 20

BT Cables Part Number C1081 C1082 C1083 C1084 C1085

Armour No No No No No

Diameter (mm) 7.0 7.9 13.1 17.2 22.3

Weight (kg/km 50 72 170 290 500

BT Cables Part Number C1096 C1092 C1093 C1094 C1095

Armour Yes Yes Yes Yes Yes

Diameter (mm) 11.4 12.3 17.9 22.9 29.1

Weight (kg/km) 240 290 510 880 1500

Diameter (mm) 11.7 12.9 19.8 25.3 31.3

Weight (kg/km) 270 310 710 1200 1700

Diameter (mm) 12.9 14.3 22.1 28.4 35.7

Weight (kg/km) 300 390 870 1500 2400

Conductor 0.75 mm² (24 x 0.2 mm) No of pairs 1 2 5 10 20

BT Cables Part Number C1086 C1087 C1088 C1089 C1090

Armour No No No No No

Diameter (mm) 7.3 8.3 14.3 18.7 24.5

Weight (kg/km 60 100 210 350 750

BT Cables Part Number C1101 C1102 C1103 C1104 C1105

Armour Yes Yes Yes Yes Yes

Conductor 1.5 mm² (7 x 0.53 mm) No of pairs 1 2 5 10 20

BT Cables Part Number C1091 C1092 C1093 C1094 C1095

Armour No No No No No

Diameter (mm) 8.3 9.7 16.4 20.6 28.5

Weight (kg/km 90 140 330 580 1100

BT Cables Part Number C1106 C1107 C1108 C1109 C1110

Armour Yes Yes Yes Yes Yes

For more details, please see the respective detailed datasheet(s)

info.btcables@bt.com

41


8 – BT Industrial-Tec™ - Industrial Cables Section

BS(PAS) 5308 - Part 2 – Type 1 – Individually & Collectively Screened Cables Conductor 0.5 mm² (16 x 0.2 mm) No of pairs 2 5 10 20

BT Cables Part Number C1111 C1112 C1113 C1114

Armour No No No No

Diameter (mm) 12.0 15.2 21.1 27.3

Weight (kg/km 100 250 480 780

BT Cables Part Number C1123 C1124 C1125 C1126

Armour Yes Yes Yes Yes

Diameter (mm) 16.8 20.9 27.9 34.4

Weight (kg/km) 450 750 1300 1900

Diameter (mm) 17.6 22.0 29.5 37.8

Weight (kg/km) 490 801 1800 2200

Diameter (mm) 20.4 25.4 33.5 42.6

Weight (kg/km) 660 1000 1700 2800

Conductor 0.75 mm² (24 x 0.2 mm) No of pairs 2 5 10 20

BT Cables Part Number C1115 C1116 C1117 C1118

Armour No No No No

Diameter (mm) 12.8 16.3 22.7 29.8

Weight (kg/km 190 270 550 960

BT Cables Part Number C1127 C1128 C1129 C1130

Armour Yes Yes Yes Yes

Conductor 0.75 mm² (24 x 0.2 mm) No of pairs 2 5 10 20

BT Cables Part Number C1119 C1120 C1121 C1122

Armour No No No No

Diameter (mm) 14.7 18.8 26.5 34.4

Weight (kg/km 250 460 760 1350

BT Cables Part Number C1131 C1132 C1133 C1134

Armour Yes Yes Yes Yes

For more details, please see the respective detailed datasheet(s)

info.btcables@bt.com

42


Section 9 - BT Industrial-Tec™ -– Control Cables

Application and Construction 1. Application These cables are commonly used as interconnecting cables to control, measure and regulate processor aided production within the industry and also as flexible power control cables suitable for robotic and automated equipment. 2. Main Standard VDE 0250/VDE 0255 2. Basic Construction of the cables Wire = Conductor with Insulation. Conductor: flexible = stranded tinned copper wires. Conductor Size Conductor material configuration Max. DC Resistance at 20°C

mm2

0.75

1.0

mm Ω/km

24x0.2 27

32x0.2 20.2

1.5 2.5 bare copper 30x0.24 50x0.24 8.4 14

4

6

56x0.29 4.95

84x0.29 3.3

Insulation: Flame Retardant PVC (Polyvinyl Chloride). Insulation Resistance > 500 MΩ/km. Good strippable insulation. Conductor Size Radial thickness insulation

mm2 mm

0.75 0.5

1.0 0.5

1.5 0.4

2.5 0.5

4 0.8

6 0.7

Cable core: three or more wires stranded. In case of 5 wires with a central filler. Colour scheme: Green/yellow - black with printed numbers. Collective Screen (CY series): braiding of tinned copper wires with a coverage of 70%. Bedding (SY series): Flame Retardant PVC. Armour (SY series): galvanised steel wires. Sheath: Flame Retardant PVC. Flame Retardancy: IEC 60332-1 (Vertical Wire test). Operating temperature range: -20 to +70 °C. Rated Voltage: 300 V. Cable Types: YY series: three or more stranded cores, surrounded by a PVC sheath. CY series: as YY series plus a collective screen between cable core and PVC sheath. SY series: as YY series plus a Steel Wire Armouring between cable core and transparent PVC sheath.

Non-standard cable constructions, colours, details and/or additional information are available on request. For more details, please see the respective detailed datasheet(s). Please note that technical specifications are subject to change without notice.

info.btcables@bt.com

43


Section 9 - BT Industrial-Tec™ -– Control Cables

YY Series: Cable core of stranded cores surrounded by a PVC sheath No of wires

BT Cables Part Number

3 4 12 18

C1631 C1635 C1645 C1648

No of wires

BT Cables Part Number

3 4 5 7 8 12 18

C1633 C1637 C1639 C1641 C1643 C1646 C1649

Conductor (mm² / mm) 0.75 / 24x0.2 0.75 / 24x0.2 0.75 / 24x0.2 0.75 / 24x0.2

Diameter (mm) 5.6 6.6 10.4 12.4

Conductor (mm² / mm) 1.5 / 30X0.24 1.5 / 30X0.24 1.5 / 30X0.24 1.5 / 30X0.24 1.5 / 30X0.24 1.5 / 30X0.24 1.5 / 30X0.24

Diameter (mm) 6.5 7.6 8.4 9.5 10.4 12.4 14.5

BT Cables Part Number C1632 C1636

BT Cables Part Number C1634 C1638 C1640 C1642 C1644 C1647 C1650

Conductor (mm² / mm) 1.0 / 32X0.2 1.0 / 32X0.2

Diameter (mm) 6.2 7.1

Conductor (mm² / mm) 2.5 / 50X0.24 2.5 / 50X0.24 2.5 / 50X0.24 2.5 / 50X0.24 2.5 / 50X0.24 2.5 / 50X0.24 2.5 / 50X0.24

Diameter (mm) 6.5 9.1 10.3 11.8 12.6 14.9 14.5

CY Series: Cable core of stranded cores surrounded by a braiding of tinned copper wires plus a PVC sheath No of wires

BT Cables Part Number

3 4

C 1620 C1624

No of wires

BT Cables Part Number

3 4 5

C1622 C1626 C1628

Conductor (mm² / mm) 0.75 / 24x0.2 0.75 / 24x0.2

Diameter (mm) 6.0 6.7

Conductor (mm² / mm) 1.5 / 30X0.24 1.5 / 30X0.24 1.5 / 30X0.24

Diameter (mm) 6.8 7.6 8.2

BT Cables Part Number C1621 C1625 BT Cables Part Number C1623 C1627 C1629

Conductor (mm² / mm) 1.0 / 32X0.2 1.0 / 32X0.2

Diameter (mm) 6.4 7.0

Conductor (mm² / mm) 2.5 / 50X0.24 2.5 / 50X0.24 2.5 / 50X0.24

Diameter (mm) 8.0 9.0 9.8

For more details, please see the respective detailed datasheet(s)

info.btcables@bt.com

44


Section 9 - BT Industrial-Tec™ -– Control Cables

SY Series: Cable core of stranded cores surrounded by a bedding, a Steel Wire Armouring plus a PVC sheath No of wires

BT Cables Part Number

3 4

C1655

No of wires

BT Cables Part Number

2 3 4 5 6 7 12 18 25 No of wires

BT Cables Part Number

3 4

C1659 C1663

Conductor (mm² / mm) 0.75 / 24x0.2

Diameter (mm) 7.8

C1651 C1656 C1660 C1665

Conductor (mm² / mm) 1.0 / 32X0.2 1.0 / 32X0.2 1.0 / 32X0.2 1.0 / 32X0.2

Diameter (mm) 8.2 8.2 8.2 10.6

C1669 C1671 C1673 C1675

1.0 / 32X0.2 1.0 / 32X0.2 1.0 / 32X0.2 1.0 / 32X0.2

11.7 13.8 15.8 19.7

Conductor (mm² / mm) 4.0 / 56x0.29 4.0 / 56x0.29

Diameter (mm) 13.4 13.4

BT Cables Part Number C1658 C1662 BT Cables Part Number C1652 C1657 C1661 C1666 C1668 C1670 C1672 C1674

BT Cables Part Number C1664

Conductor (mm² / mm) 2.5 / 50X0.24 2.5 / 50X0.24

Diameter (mm)

Conductor (mm² / mm) 1.5 / 30X0.24 1.5 / 30X0.24 1.5 / 30X0.24 1.5 / 30X0.24 1.5 / 30X0.24 1.5 / 30X0.24 1.5 / 30X0.24 1.5 / 30X0.24

Diameter (mm) 9.4 9.4 9.4 11.2 12.3 12.4 14.3 16.8

Conductor (mm² / mm)

Diameter (mm)

6.0 / 84X0.29

16.0

For more details, please see the respective detailed datasheet(s)

info.btcables@bt.com

45


GENERAL TECHNICAL INFORMATION American Wire Gauge (AWM) Conductors (of bare or tinned copper) Flexible Conductors

AWG

24

Number of strands

22

20

18

16

14

12 19

7

7

7

7

19

19

Gauge single strand

AWG

32

30

28

26

29

27

25

Diameter single strand

mm

0.2

0.25

0.32

0.40

0.28

0.36

0.45

Solid Conductors

AWG

Diameter

mm

24 0.51

22

20

0.64

18

0.81

1.02

16

14

1.29

12

1.63

2.05

All Conductors

AWG

24

22

20

18

16

14

12

Cross section

mm²

0.20

0.32

0.52

0.82

1.37

2.08

3.31

Max. DC resistance

Ω/km

88

57.4

32.16

22.7

15.47

9.36

5.61

Max. Recommended current 2 or 3 core cable

Amps

2.7

2.8

3.75

5

6.25

8

12

Max. Recommended current 4 or 5 core cable

Amps

2.2

2.25

3

4

5

6.4

9.6

Max. Recommended current 6 to 19 core cable

Amps

1.9

1.95

2.6

3.5

4.35

5.6

8.4

Max. Recommended current 20 to 36 core cable

Amps

1.35

1.4

1.65

2.5

3.12

4

6

Metric Conductors (of bare copper according to IEC 60228) Conductor

mm²

0.75

1.0

1.5

2.5

4.0

Max. Recommended current 2 or 3 core cable

Amps

≤5

≤ 5.70

≤ 6.25

≤8

≤ 12

Flexible Conductors, class 2

mm²

0.055

0.22

0.50

0.75

1.0

1.5

2.5

4.0

6.0

7

7

7

7

7

7

7

7

7

mm

0.1

0.2

Max. DC resistance

Ω/km

345

86.2

36.0

24.5

18.1

12.1

7.41

4.61

3.08

Flexible Conductors, class 5

mm²

0.055

0.22

0.50

0.75

1.0

1.5

2.5

4.0

6.0

16

24

32

30

50

56

84

mm

0.2

0.2

0.2

0.24

0.24

0.29

0.29

Max. DC resistance

Ω/km

39.0

26.0

19.5

13.3

7.98

4.95

3.30

Max. Recommended current 2 or 3 core cable

Amps

2.7

2.8

3.75

5

6.25

8

12

Max. Recommended current 4 or 5 core cable

Amps

2.2

2.25

3

4

5

6.4

9.6

Max. Recommended current 6 to 19 core cable

Amps

1.9

1.95

2.6

3.5

4.35

5.6

8.4

Max. Recommended current 20 to 36 core cable

Amps

1.35

1.4

1.65

2.5

3.12

4

6

Number of strands Diameter single strand

Number of strands Diameter single strand

0.53

All conductors in BT Cables are in accordance with above tables unless otherwise stated in the respective section of this publication or datasheets.

info.btcables@bt.com

46


Pairs: all pairs consist of two twisted wires with a lay-length < 40 D. Cable Cores: all cable cores consist of stranded wires or pairs Foil screens for multi-core and multi-pair cables, screens or shields mostly consist of an aluminium foil laminated to polyester, broadly known as Alpet. These foils are helically (as a spiral) applied with sufficient overlap to guarantee 115 % or more coverage. . For the flexibility of a cable a helically applied foil is to be preferred. A longitudinally applied foil act more as a stiff tube = more difficult to bend. A drain wire or continuity wire, contacting the aluminium side of the foil, is used for the termination of the screen and also to ground electrostatic discharges. In case the screen of a coaxial cable where the screen may be a foil, this foil will be applied longitudinally and will also be bonded to the dielectric around the conductor. Braided screens consist of 16 or 24 groups of strands. One set of 8 or 12 strands is woven clockwise and the other set of 8 or 12 strands anti-clockwise. Strands can consist of tinned or bare copper or aluminium wires. Braided screens provide good screening efficiency and flexibility. Higher coverage provides better screening. Sheaths: grey PVC, purple HFFR or black for PE, all in accordance with BS EN 50290-2. Sheath

PVC

Physical properties Retardancy Retardancy acc. to Low Smoke Halogen-free (non acid, non toxic) RoHS compliant Installation **

BS EN 50290-2-22 Flame IEC 60332-1 Not applicable Not applicable YES INDOOR

PVC Alarm cables UL444 Fire UL1666 Not applicable Not applicable YES INDOOR

HFFR

PE

BS EN 50290-2 Fire IEC 60332-3C IEC 61034 IEC 60754 YES INDOOR

BS EN 50290-2 Not applicable Not applicable Not applicable Not applicable YES OUTDOOR

** on request cables with a sheath for in- & outdoor = universal use available.

RoHS Limits for Hazardous Substances Substance

Max. Concentration

Lead (Pb) Mercury (Hg) Cadmium (Cd) Chromium 6 PBB PBDE

0.03% 0.10% 0.01% 0.1% 0.1% 0.1%

Unless so marked, all BT Cables do not contain restricted or hazardous substances and are compliant with the European Regulations or Directives for RoHS (Restriction of Hazardous Substances), REACH (Regulation Registration, Evaluation, Authorisation and Restriction of Chemical substances), WEEE (Waste Electrical and Electronic Equipment ), ELV (End of Life Vehicles) and BFR (Brominated Flame Retardants).

RS Protocol Differential Max. number of drivers Max. number of receivers Modes of operation Network topology Max. distance acc. to standard Max. speed at 12 m. Max. speed at 1200 m. Cables used BT Cables main part numbers see

RS-232 no

RS-422 yes

RS-485 yes

1 1 full duplex point-to-point 15 m 20 kbs 1 kbs

1 10 half duplex multidrop 1200 m 10 Mbs 100 kbs mainly 24AWG conductors. Two pairs or more. 100 ohm section 1.2

1 32 half duplex multidrop 1200 m 35 Mbs 100 kbs mainly 24AWG conductors. One pair or more. 120 ohm section 1.1

6 to 25 conductors. No impedance specified section 1.3

info.btcables@bt.com

47


Nominal Attenuation in dB/100m for RG Coaxial Cables MHz RG-59 RG-6 RG-11

1 0.98 0.79 0.53

5 2.07 1.71 1.12

10 2.95 2.33 1.51

50 6.23 4.57 2.96

100 7.55 6.40 4.20

300 13.68 11.96 7.49

550 18.83 15.76 10.41

750 22.23 18.05 12.38

1000 25.96 21.36 14.57

2000 38.24 31.44 21.84

3000 46.13 39.76 27.93

4500 56.50 50.46 35.98

COMPARISON BETWEEN EUROPEAN AND UNITED STATES CABLE DESIGN BASICS Europe

USA

Focus on SAFETY = SAVING LIVES Low Voltage Directive 220 Volt, 50 Hz More radial thickness of insulation IEC-EN and National Standards Cable specs. in mm, N, etc. 70 °C (is equal to 80 °C in USA) 300 / 500 Vrms 450 / 750 Vrms IEC 60332-1 IEC 60332-3-24 (former 3C)

Focus Directives Power supply system Cable basics Standards Units Temperature Ratings Voltage Ratings Retardancy levels Environmental requirements

RoHS compliant CE Marking The CE marking certifies that a product has met EU consumer safety, health or environmental requirements. By affixing the CE marking to a product, the manufacturer – on his sole responsibility – declares that it meets EU safety, health and environmental requirements or, if stipulated in the directive(s), it had to be examined by a notified conformity assessment body.

Quality assurance

Focus on REDUCING INSURANCE CLAIMS National Electrical Code 120 Volt, 60 Hz More copper in conductors UL standards Cable specs. in inches, lbs, etc. 80 °C (Is equal to 70 °C in Europe) 300 Vrms 600 Vrms UL1581 – VW-1 UL1685 A number of states banned Hg and PBDE UL Approval / Listing UL does not approve products. Rather it evaluates products for compliance to specific requirements, and permits acceptable products to carry a UL certification mark, as long as they remain compliant with the standards. Products under its listing service are said to be “UL Listed,” identified by the distinctive UL mark.

CONVERSIONS Europe 1 mm = 0.03937 inches 1 m = 3.2808 feet (305 m = 1000 feet) 1 m = 1.0936 feet 1 km = 0.6214 miles 1 kg/km = 0.6719 lbs/1000 ft 1 ohm/km = 0.3048 ohm/1000 ft 1 N = 0.2248 lbs force -40 °C = -40 °F -30 °C = -22 °F 0 °C = 32 °F 60 °C = 90 °F 75 °C = 167 °F 90 °C = 194 °F

USA 1 inch = 25,4 mm 1 feet = 0.3048 m 1 yard = 0.9144m 1 mile = 1.6093 km 1 lbs/1000 ft = 1.488 kg/km 1 ohm/1000 ft = 3.2808 ohm/km 1 lbs force = 0.2248 N -40 °F = -40 °C -22 °F = -30 °C 32 °F = 0 °C 90 °F = -60 °C 167 °F = -75 °C 194 °F = -90 °C

info.btcables@bt.com

48


Area Conversions From Circular mils Square inches mm² Square feet

To Square inches

Multiply by 0.0000007854

To Square mils

Multiply by 0.7854

To mm²

Multiply by 0.0005067

Circular mils

1,273.240

Square mils

1,000,000.00

mm²

645.16

Square inches Square meters

0.00155 0.0929

Square mils

1550.01

Circular mils

1,973.53

Common Wire Conversions AWG Cir. mils mm²

24 404 0.205

22 640 0.324

987 0.5

20 1029 0.521

19/18 1481 0.75

18 1620 0.821

18/17 1974 1.0

AWG Cir. mils mm²

16 2580 1.371

15/16 2961 1.5

14 4110 2.082

14/13 4935 2.5

12 6530 3.309

7896 4.0

11 8230 4.170

Force, Mass and Weight Conversion From Pounds Pound per 1000 ft Pound-force

To Kilograms Kilogram per kilometre Newton

Multiply by 0.4535 1.488 4.4482

From Kilograms Kilogram per kilometre Newton

info.btcables@bt.com

To Pounds

Multiply by 2.205

Pound per 1000 ft

0.6719

Pound-force

0.2248

49


GLOSSARY Cat 8 Cable supports frequencies up to 1200 Mhz. Under development. No applications yet.

A = Amp: Ampere = unit of electric current. AC: Alternating current, e.g. 50 or 60 Hz AC power. ACR: Attenuation Crosstalk Ratio. The difference between attenuation and crosstalk. Important characteristic in transmission to assure that the transmitted signal is stronger at the receiving end of the cable than are any interference signals imposed on that same pair by crosstalk from other pairs. Alpet: aluminium foil covered with polyester.

CATV: Community Antenna Television, also often used to mean Cable TV. It is a system of providing television to consumers through or optical fibre cables. High-speed Internet, telephony, and similar non-television services may also be provided. CCTV: Closed-circuit television is the use of video cameras to transmit a signal to a specific place, on a limited set of monitors. Circuit integrity refers to the operability of electrical circuits during a fire. It is a form of fire-resistance rating.

Alu braid: braiding of woven aluminium wires ANSI: American National Standards Institute Attenuation: The gradual loss in intensity of signals in electrical circuits. AWG: American wire gauge, is a standardized wire gauge system used since 1857 predominantly in the United States and Canada for the diameters of round, solid, nonferrous, electrically conducting wire. BT Cables: a leading manufacturer of communication cables. B.C. = BC: Bare Copper, mostly referring to a conductor or braid. Bending radius: the radius that a cable can be bent without any detrimental effects on transmission performance.

Coaxial Cable or coax: an electrical cable with a centre conductor surrounded by a tubular insulating layer = the dielectric, surrounded by a tubular conducting screen = the outer conductor, surrounded by an outer sheath. The term coaxial comes from the centre conductor and the outer screen sharing the same geometric axis. Conductor: most familiar conductors are metallic. Copper or tinned copper is the most common material used for electrical wiring. Silver is also in use as a conductor and out performs copper, but is more expensive. Continuity Wire: see Drain Wire.

Braid or Braiding: is a structure or pattern formed by intertwining of commonly 16 or 24 strands of wires.

Crosstalk (XT): any phenomenon by which a signal transmitted on one circuit of a transmission system creates an undesired effect in another circuit. Crosstalk is usually caused by undesired capacitive, inductive, or conductive coupling from one circuit (mostly a pair) to another (pair).

B.S: British Standards are the standards produced by BSI Group which is incorporated under a Royal Charter (and which is formally designated as the National Standards Body (NSB) for the UK).

Current: electric current is a flow of electric charge through a medium. This flowing electric charge is typically carried by moving electrons in a conductor such as wire. The unit of current is Ampere.

Cable core: two or more wires or pairs stranded. Good twisting is necessary otherwise the cable can hardly be bent and will lose performance after a few bends.

DC Resistance: the resistance of an object is defined as the ratio of voltage across it to the direct current through it. The unit of resistance is Ohm.

Category cables: high performance twisted pair cables for local area networking = structured wiring or cabling. Cables range from Cat 3 to Cat 7a. The higher the number, the greater the bandwidth and the better the performance.

Dielectric: the insulation between centre and outer conductor (screen) of coaxial cables. Mostly solid or foam (= cellular) polyethylene (PE).

Cat 3 Cable supports 10 Base-T Standard for bandwidths up to 10 Mbps over a maximum distance of 100 meters. They can support frequencies up to 10 Mhz. Cat 5/5e Cable supports 100 Base-T Standard for bandwidths up to 100 Mbps over a maximum distance of 100 meters. They can support frequencies up to 100 Mhz. Cat 5e cables can also support 1000 Base-T. Cat 6 Cable supports 1000 Base-T Standard for bandwidths up to 1000 Mbps over a maximum distance of 100 meters. Cat 6 standard can support frequencies up to 250 Mhz. They also support 10GE (10Gig Ethernet) bandwidth over limited distances. Cat 6A Cable supports 10G Base-T standard for bandwidths up to 10 Gbps over a maximum distance of 100 meters. Cat 6A standard can support frequencies up to 500 Mhz. Cat 7 Cable supports 10G Base-T standard for bandwidths up to 10 Gbps over a maximum distance of 100 meters. Cat 7 standard can support frequencies up to 600 Mhz. It offers better performance and improved cross talk suppression over the Cat 6A cables. Cat 7A Cable supports 10G Base-T standard for bandwidths up to 10 Gbps over a maximum distance of 100 meters. In addition to this, they can also support 40 Gbps bandwidth for around 50 meters and 100 Gbps bandwidth for around 15 meters. They support frequencies up to 1000 Mhz.

Distortion: the alteration of the original shape (or other characteristic) of an object, image, sound, waveform or other form of information or representation. Distortion is usually unwanted, and often many methods are employed to minimize it in practice. Drain wire: a conductor in contact with the foil (of a screen) in order to terminate the screen. Also referred to as a Continuity Wire. The preferred drain wire is tinned copper wire or wires. Decibel (dB): is a logarithmic unit that indicates the ratio of a physical quantity (usually power or intensity) relative to a specified or implied reference level. A ratio in decibels is ten times the logarithm to base 10 of the ratio of two power quantities. ELFEXT: the Equal-Level Far-End Crosstalk (ELFEXT) test measures FarEnd Crosstalk (FEXT). FEXT is very similar to NEXT, but happens at the receiver side of the connection. Due to impedance on the line, crosstalk diminishes the signal as it gets further away from the transmitter. Because of this, FEXT is usually less detrimental to a signal than NEXT, but still important nonetheless. EIA: the Electronic Industri8es Association ceased operations on 28 February 2011. The former sectors of EIA are the Electronic Components Association (ECA), JEDEC, Government Electronics and Information Technology Association (GEIA), now part of TechAmerica, Telecommunications Industry Association (TIA), and Consumer Electronics Association (CEA).

info.btcables@bt.com

50


EN: European Norms maintained by CEN (European Committee for Standardization), CENELEC (European Committee for Electrotechnical Standardization) and ETSI (European Telecommunications Standards Institute). Farad: the unit of capacitance. FPE: Foam Polyethylene (PE) = closed cells with gas in PE in order to reduce the dielectric constant. Often used as dielectric in coaxial cables. The gas may be generated by chemical decomposition during extrusion of the insulation (dielectric) referred to as chemical foaming or blowing, or by injection into the polymer melt within the extruder (physical foaming or blowing).

Lay-length: The length measured along the axis of a wire or cable required for a single strand (in stranded wire) or conductor (in cable) to make one complete turn about the axis of the conductor or cable. In a twisted pair cable, the lay length is the distance it takes for the two wires to completely twist around each other. Lay length is also known as pitch length. Local Area Network (LAN): any communication network for connecting computers within a building or small group of buildings. m = metre: S. I. unit of measure of length.

FAS Cables: cables for fire detection and alarm systems Far end crosstalk (FEXT): Interference between two pairs of a cable measured at the other end of the cable from the transmitter. FR: can mean Flame Retardant or Fire Retardant or Fire Resistant. Flame Retardant: are cables passing the vertical wire test of IEC 60332-1 or UL 1581 VW-1). Fire Retardant: are cables passing the bundle test of IEC 60332-2-24 or UL 1685 Vertical Tray. Fire Resistant are cables with a circuit integrity of a specified time. Frequency: is the number of occurrences of a repeating event per unit time. The unit of frequency is Hertz (Hz).

MHz = MegaHertz: . 1 MHz = one million Hertz. Near End Crosstalk (NEXT): Interference between two pairs in a cable measured at the same end of the cable as the transmitter. Operating temperature (range): the temperature range at which the cable can operate. Polyolefin: is a polymer produced by polymerisation of a simple olefin (also called an alkene) as a monomer, for example Polyethylene or Polypropylene. PA = Polyamide PE = Polyethylene. PP = Polypropylene. PVC = Polyvinyl Chloride. Power Sum ELFEXT (PSELFEXT): is the sum of FEXT values from 3 wire pairs as they affect the other wire pair.

G.P. Bus: General Purpose Bus Application Headroom: in case of testing category cables this is the average of the difference between worst case margin and the specified value.

Pair: two twisted insulated wires, normally colour coded. Quad: a four conductor cable core or unit, symmetrical stranded or twisted together.

Henry (H): unit of inductance. Hertz (Hz): unit of frequency. 1 Hz means that an event repeats once per second. HFFR = Halogen-Free, Flame or Fire Retardant Impedance: the ratio of voltage applied to the current is called the input impedance. The input impedance of the infinite line is called the characteristic impedance. Insertion Loss: also referred to as attenuation, refers to the loss of signal strength at the far end of a line compared to the signal that was introduced into the line. This loss is due to the electrical resistance of the copper cable, the loss of energy through the cable insulation and the impedance caused by the connectors. Insertion loss is usually expressed in decibels dB with a minus sign. Insertion loss increases with distance and frequency. For every 6dB of loss, the original signal will be half the original amplitude. Inductance: is the property of an electrical circuit causing voltage to be generated proportional to the rate of change in current in a circuit. This property also is called self inductance to discriminate it from mutual inductance, describing the voltage induced in one electrical circuit by the rate of change of the electric current in another circuit. Insulation: insulations are coatings applied to wires to isolate the conductors. Insulation materials are applied to provide good strippable and interchangeable colour. The physical properties are in accordance with BS EN 50290-2. Individually screened pair: a pair with a helically applied (= as a spiral) Aluminium/Polyester (Alpet) foil. A drain wire is normally applied under the screen to provide continuity and ease of tern=miantion.

Jacket = sheath. This is the outer protective polymer surrounding the cable core.

Rated Temperature: the maximum continuous temperature that the cable can withstand during its lifetime. It is generally limited by the thermal aging characteristics of the plastics used to insulate and/or sheath the wire. Rated Voltage: the maximum voltage at which a cable can operate for extended periods without undue degradation or safety hazard. Resistance: the electrical resistance of a conductor measures its opposition to the passage of an electric current; the inverse quantity is electrical conductance, measuring how easily electricity flows along a certain path. The unit of electrical resistance is the ohm (Ω), while electrical conductance is measured in Siemens (S). Return Loss (RL): the Return or Reflection Loss of a line is the ratio of the power reflected back from the line to the power transmitted into the line. RL is expressed in decibels (dB). The RL of coaxial cables is the loss of signal power resulting from the reflection caused at a discontinuity in the cable. This discontinuity can be fluctuations in dimensions and/or dielectric. Return Loss is also one of many parameters regulated by the requirements established for Category 5e and onwards cables. It is a measure of the reflected energy from a transmitted signal. The larger the value, the less energy that is reflected. Poor Return Loss figures of a circuit are quite often caused by poor termination (connectors). Screen: a cable screen acts as a Faraday cage to reduce electrical noise from affecting the signals, and to reduce electromagnetic radiation that may interfere with other parts in a cable or other cables. The screen minimizes capacitive coupled noise from other electrical sources. For more info regarding screens: see also the Technical Information section.

info.btcables@bt.com

51


Sheath: the outer covering of a cable, standard in accordance with BS EN 50290-2 and grey for PVC, purple for HFFR and black for PE. Shield = screen. SMATV = Satellite Master Antenna Television, and refers to a system that uses multiple satellite and broadcast signals to create a single integrated cable signal for distribution to a cabling network Solid BC: one solid conductor of bare copper. Solid TC: one solid conductor of tinned copper T.C. = TC = Tinned Copper Conductor TIA: the Telecommunications Industry Association is accredited by the American National Standards Institute (ANSI) to develop voluntary industry standards for a wide variety of telecommunications products. Twisted pair: a type of wiring in which two conductors are twisted together for the purposes of cancelling out electromagnetic interference (EMI) from external sources; for instance, electromagnetic radiation from unshielded twisted pair (UTP) cables, and crosstalk between neighbouring pairs. Volt = Voltage = unit of electric, expressed with the symbol V. Wire = Conductor with Insulation. Sometimes also indicated as Core.

info.btcables@bt.com

52


UNITED KINGDOM

EUROPE

Delaunays Road, Blackley Manchester, M9 8FP Tel: +44 161 740 9151 Fax: +44 161 795 8393 Email: info.btcables@bt.com

Madrid 28 28027 Spain Tel: +34 611370897 Fax: +44 161 795 8393 Email: info.btcables@bt.com

MIDDLE EAST

ASIA

Rawdah - Riyadh Kingdom of Saudi Arabia Tel: +966 500333786 Fax: +44 161 795 8393 Email: info.btcables@bt.com

Shenzhen – Guangdong Province People’s Republic of China Tel: +86 13923775251 Fax: +44 161 795 8393 Email: info.btcables@bt.com

www.btcables.com