The Input Data And Calculation Space Data Machine No FCU/1-6/60a,60b Height (ft) Space No WEP LOD-FD 134 Area ( ft2) Floor No. FIRST FLOOR Volume ( ft3) CHW Terminal Units Units Type Solar &Trans Gain Glass GLASS H W N NE E SE S SW W NW
9/14/2009 8:57
MIRDIF CITY CENTRE NORDSEE,Shop No FD134,Mirdif City Center,dubai
Plot No/ Area No : Project: Consultant: HEAT LOAD
R evised ( 2 )- 1/4/2003
Condition Data Month Yearly Range Daily Range Time Latitude Altitude
19.00 730.00 13870.00
Outdoor 115.00 85.00 30% 135.00 54 (0 to .15)
Design Data
11 50.00 21.00 16.00 25 N 26.00 External Load U
Glass Area Ft 2
dB F WB F % RH GR./LB Dew point Haze Factor SC
COLOR L
Frame Factors
Indoor 75.00 63.00 50% 62.50 53 0.15 SOLAR GAIN BTU/HR
Difference 40.00 22.00 72.50 1
TRANS GAIN BTU/HR
L
HORIZONTAL
Total Solar &Trans Gain Glass Trans Gain -Except Glass WALL H N NE E SE S SW W NW H
W
Total Wall Area Ft
2
Net Wall Area Ft
2
External Load U
Mass Ib/Ft
2
Color
TRANS GAIN
L L
W
Area Ft 2
EX OR NO
U
External Load Mass Ib/Ft2
Color
ROOF FLOOR PARTITION CEILING
Trans Gain -Wall heat to space% Exposure E
Trans Gain- Roof & Others SENSIBLE
Internal Load
ELEMENTS
LIGHTS PEOPLE
MOTORS REHEAT APPLIANCES MISC. STEAM W/FT2 4.70 FT2/ Person 73.00
HP WATT WATT WATT LB/H Watt 3431.00 Persons 10.00
VENTILATION
CFM/Person Air Change /Hr Infiltration
SAFETY FACTOR s
SH % LH % Others%
UNITS DATA Operat. Time No Of Units 24.00 1.00 TOTAL LOAD Total Grand Load Total Sensible Heat Total Latent Heat TONS 12.29
T adb 54.00 BTU/HR 147425.08 145272.58 2152.50 BTU/HR.FT2 201.95
33560.00
Light Factor 1.00 Activity Level 1
Total Watt 3431.00
Heat to space% 100%
Operat % 100% Attendance % 100%
Out Door Air Sub-Total Safety Factor
10.00% 5.00% 3.00%
Supply Air Return Air Out Door Air CFM/FT2 10.32
LATENT
114104.00
CFM No %
by-pass F(BF) 0.17
TRANS GAIN
V INF. BTU/HR
SENSIBLE 11665.40 SENSIBLE 2450.00
LATENT 2050.00
128219.40
2050.00
128219.40 12821.94
2050.00 102.50
Trm - Tsa 17.43 CFM 7535.67 7535.67 SHF 0.99
Off Coil Air T o F 54.00 THERMAL
PI
Losses 2.00 INSULATION
Duct Losses+ Fan HP
4231.24
Effective Room Heat Effective Room Total Heat
SENSIBLE LATENT 145272.58 2152.50 147425.08
Out Door Air Heat
A PERFECT SOLUTION FOR A PERFECT LIFE
Roof Load To Plenum Lights Load To Plenum Sensible Heat (Plenum)