Arch672 System Studio Project: D-tow(n)er

Page 1































CODE REVIEW

D-Tow(n)er JAMILLA AFANDI ADAM BRACH DAIMEI WANG WESLEY WU Dowdell + Vance Studio

1 Building Height

Project Summary 25 stories above grade max. 305’

2 Areas / Occupancy Groups SECTION 303

Residential Lounges- at the landing of residential elevators floors 2-6

Group A-2 per § 303.3 is for assembly areas where food and drink are consumed. The requirements for these occupancies presume that alcoholic beverages may be served, thus potentially impairing the occupants’ responses to an emergency. It also presumes that chairs and tables will be loose and may obstruct or make unclear egress pathways for patrons. The requirements also recognize the poor fire history of such occupancies. Group A-3 occupancies per § 303.4 are assembly areas that do not fit into the other Group A categories. It also includes spaces used for worship, recreation, or amusement. The intent of this classification is that any use that seems to be an assembly occupancy and does not fit the criteria of the other four Group A categories should be classified as an A-3 occupancy. Group A-5 occupancies per § 303.6 are assembly areas for the participation or viewing of outdoor sporting events. The occupancy group includes incidental storage, which will be regulated per the mixed use provisions in § 508. Accessory occupancies are regulated by § 508.2 and must still be individually classified. Larger storage areas would be classified as Group S. Typically for larger combinations of M and S occupancies, the non separated provisions of § 508.3 are used. Group R-2 occupants are permanent, sleeping in buildings containing more than two dwelling units for more than 30 days. These include apartments, dormitories, and long-term residential boarding houses. Congregate living facilities with 16 or fewer occupants (note the cutoff is 16 or less) are permitted to comply with requirements for R-3 occupancies. § 406.4 classifies public parking garages into open parking garages and enclosed parking garages.

Group A-2

Indoor Recreation Centers- on levels 24, 6, 4, and 3 Group A-3 Outdoor Recreation Areas- at northeast edge of site above parking garage Group A-5

grade

Retail- on floors 1 and 2

Group M

Apartment Residences- on floors 3-25 Underground parking garage- 2 floors below

Group R-2 Group S-2

3 Construction Types

Indoor Recreation Areas residential lounges

Type I-A Type I-A

Retail

Type I-A

Parking Garage

Type I-A

R Apartment Residences 4

Overall Description of building and its use and site location. Describe basic structural system and cladding system. Note Construction Type. Note Occupancy Groups. Note Required Separations between Occupancies. Reference Table 503 from Code to determine this. Note Construction Type(s) and allowable areas for your 5 specific Occupancy Group(s)

Type I-A The building is a 27 story residential tower with multiple indoor recreation centers on a 1.5 acre site in Detroit’s Old Redford Neighborhood. It has a concrete frame and a stone rain screen veneer. The construction type is I-A. The building is a mixture of separated uses including primarily R-2 apartments on levels 3-27, large A-3 recreation areas without assembly, public spaces A-2 on levels 2-6 and M retail on levels 1 and 2. These are separated by a 2 hour use separation, which allows the area and height limitations from Table 503 to overlap. The overall building construction Type is I-A, which allows for unlimited floor plate size and height for all occupancy groups See section 302.3

A-2

unlimited

A-3

unlimited

A-5 M R-2

unlimited unlimited unlimited

Note any areas which are Unrated Construction Types. 6 Reference Table 602.

Type I buildings are unconsidered combustible since the code allows their interior building elements to be of combustible materials and also to be of unprotected construction if allowed by the building Walls facing the courtyard do not require to be fire-rated as it height and area allowances based on occupancy. abuts a large courtyard space.

What is the fire rating of the perimeter walls due to 7 building location on site? Reference Table 603.

As per Table 602 the exterior wall is required to be rated for 1 hour on all sides except those facing the courtyard, as the Fire Separation Distance is 5<x<10 feet using Type I Construction

Describe any fire sprinkler systems used. Reference Section 506 for any allowable area increase and note 8 here.

Installation of an automatic sprinkler allows for an increase in maximum height by 20 ft or 1 story, allows for unlimited per floor area, and allows for only one required means of egress for group R-@ occupancy apart units. The automatic sprinkler system also allows for decreases in minimum requirements for egress width, clear space between handrails for degree, etc.

1


As per Table 602, the building elements are required to be rated for 3 hours in Type 1 construction, and in the case of concrete construction, the structural members must follow the dimensions as per Table 602.4

9 Additonal Summary Line Items as Needed Chapter 3

Use and Occupancy Classification Section 302 Classification Residential Lounges- at the landing of residential elevators floors 2-6 Indoor Recreation Centers- on levels 24, 6, 4, and 3 Outdoor Recreation Areas- at northeast edge of site above parking garage

Group A occupancies are typically defined as having 50 or more occupants. Per § 303.1.1, assembly areas with fewer than 50 occupants are to be classified as Group B Occupancies. Assembly areas of less than 750 sf (69.68 m2) that are accessory to other uses are also not considered as Group A areas per § 303.1.2 Item 2.

Group A

Retail- on floors 1 and 2

Uses in these groups are fairly self-explanatory. The occupancy group includes incidental storage, which will be regulated per the mixed use provisions in § 508. Accessory occupancies are regulated by § 508.2 and must still be individually classified. Larger storage areas would be classified as Group S. Typically for larger combinations of M and S occupancies, the non separated provisions of § 508.3 are used. Residential occupancies include typical housing units, distinguished mainly by the total number of occupants. A key criterion for this type of occupancy is that the occupants sleep in the building. This group also includes smaller-scale institutional occupancies that fall below certain thresholds for the number of occupants. Storage for materials with quantities or characteristics not considered hazardous enough to be considered a Group H occupancy is classified as Group S.

Group M

Group R Group S

Apartment Residences- on floors 3-25

Underground Parking- 2 floors below grade

Section 302.3 Mixed Occupancies Where a building is occupied by two or more uses not included in the same occupancy classification, the building or portion thereof shall comply with Section 302.3.1 or 302.3.2 or a PROGRAMS: Large public gathering spaces adjacent to smaller noncombination of these sections. assembly public spaces, Each portion of the building shall be individually classified as to use and shall be completely separated from adjacent areas by fire barrier wall or horizontal assemblies or both having a fireresistance rating determined in accordance with Table 302.3.2 for uses being separated. Each fire area shall comply with this code based on the use of that space. Each fire area shall comply with the height limitations based on the use of of that space and the type of construction classification. In each story, the building area shall be such that the sum of the ratios of the floor area of each use divided by the allowable area for each use shall not exceed one. Section 302.3.2 Required Separation of Occupancies A,E/ A,E: No sepaation required A,E/ R:1 hour A,E/ F-2: NO SEPARATION REQUIRED A,E/B: 1HOUR R/R: NO SEPARATION REQUIRED R/ F-2: 1 HOUR R/B : 1 HOUR B/B/: NO SEPARATION REQUIRED Summary of Rated Separations Rating Separation 0 Hours All building elements including concrete roof framing Exterior walls based on fire separation distance of 10~30 feet 1/2 Hours All floor/ceiling assemblies separating sleeping units Corridor walls Horizontal separation between differing uses 1 Hour described in 302.3.2. 2 Hours All shafts connecting 4 stories. Chapter 4

Notes

Table 601 with type IIB Table 602 with type IIB

Entire building evenlope is setback from adjacentt buildings 20 ft

Section 711.3

Fully sprinklered with NFPA 13 system per exception in 302.3.2 Section 707.4

Residences above public gathering spaces, corridors above retail, corridors above/below residences All stairs in design connect a minimum of 4 stories

Special uses and occupancies The definition of a high-rise building in §403 is based on the height that typical fire-department extension ladders and hose streams can effectively fight a fire. Thus a building with an occupied floor more than 75’ (22 860) above the lowest level of fire-department access is defined as a high-rise. Firefighting in a high-rise assumes that the firefighters must enter the building and go up inside the building to fight a fire. BUILDING EXCEEDS 75’ (305’)

Section 403 High Rise Building

Section 406

Motor-Vehicle-Related Occupancies

Enclosed parking garages are similar to open parking garages except that the amount of wall enclosure relative to the building area does not allow them to be considered as open garages. Because they do not meet the criteria for open parking garages and are considered enclosed, mechanical ventilation is required to 2 story underground enclosed parking compensate for the lack of cross-ventilation. structure

Chapter 5

General Building Heights and Areas

Notations and Calculations

Section 503 General Height and Area Limitations

Table 503 Type I A construction / R-2 allows unlimited stories

503.1.3 states that Type I buildings, permitted to be of unlimited height and area per § 504 and § 506, do not require the mitigations for unlimited-area building imposed on other construction types by other sections of this chapter. Note, however, that certain Group H occupancies have height and area restrictions even for Type I buildings. no group H occupancies

Table 503 Type I A construction / A-2 allows unlimited stories

Section 506 Area Modifications

General. The areas limited by Table 503 shall be permitted to be increased due to frontage and automatic sprinkler system protection, in accordance with the 506.1 following: Chapter 6

Types of Construction

The building has frontage of at least 30 feet on all sides and fully sprinkled. The sprinklers are not being used for a rating substitution in accordance with Table 601. The allowable area for A-2 use in Type I-B construction is 9,500 sf. With the use of Equation 5-1, this area increases to 35,625. Using the equation with only the sprinkler increase results in an allowable area of 28,500 sf - which is over the area of the ground level (26,250). Comments

2


Fire resistance rating requirements for building Table 601 elements A building may only be classified as a single type of construction unless a fire wall divides it into separate structures, or it falls into the special provisions for mixed construction permitted under § 510.

Type I-A

Section 602

no fire separation required

Construction Classification Fire resistance rating requirements for exterior walls Table 602 based on separation All the sides of the building have a separation distance greater fire separation distance >10<30 / group A-2 and R-2 / than 10 0 hours feet; the required rating for the exterior walls is 0 hours.

Chapter 7

Fire Resistance Rated Construction Section 702 Definitions 702 Fire Separation Distance The distance measured from the building face to the closest interior lot line, to the centerline of a street, alley or public way, or to an imaginary line between two buildings on the lot. The distance shall be measured at right angles from the face of the wall.

All the sides of the building have a separation distance greater than 30 feet; the required rating for the exterior walls is 0 hours.

Section 704 Exterior Walls Table 704.8 Allowable Opening Area for Exterior Walls § 704.8 prohibits inclusion of service elements such as pipes or conduits into the fire-protection covering. This recognizes that such elements can conduct heat through the fire protection to the structural member and thus potentially compromise the time rating for fireresistance. 704.8.1 Automatic Sprinkler System In buildings equipped throughout with an automatic sprinkler system in accordance with Section 903.3.1.1, the maximum allowable area of unprotected openings in occupancies other than Groups H-1, H-2, and H-3 shall be the same as the tabulated limitations for protected openings.

Chapter 10

The buildings are fully sprinklered and the openings in the rated perimeter walls will be unprotected. All areas of the building perimeter have a fire separation distance of greater than 20 feet. Per Table 704.8, there is no limit to the area of openings on the building.

Means of Egress Comments § 1003.7 does not permit any of these modes of transportation to be used as components of a means of egress. The only exception is for elevators used as an accessible means of egress per § 1009.4, where they are provided with standby power and also with operation and signal devices per § 2.27 of ASME A17.1. § 1004.1 specifies that means-of-egress facilities for a building are to be designed to accommodate Section 1004 Occupant Load the number of occupants as computed in accordance with § 1004.1.2 and Table 1004.1.2. Max. Floor Area Allowances per Occupant by Table 1004.1.2 Occupancy Group bowling center: 7 net 5630 sqft @ 7 net= 804 max occupancy exercise room: 50 gross 9000 sqft total= 180 max capacity

rm 1=1900sqft= 38 max occupancy rm 2= 2700 sqft=54 max occupancy rm 3= 3050 sqft= 61 max capacity rm 4= 1350 sqft= 27 max capacity

Assembly - unconcentrated: 15 sf net library reading room: 50 gross

7860 sqft total @ 15 net= 524 max capacity 2870 sqft total @ 50 gross= 57 max capacity

rm 1= 1110 sqft= 22 max acpacity rm 2=1760 sqft=35 max capacity

locker rooms: 50 gross merchantile (main floor): 30 gross mercantile (other floors): 60 gross parking garages : 200 gross residential: 200 gross

1004.2

1004.1.1.2

1004.1.2

1004.3

1004.5

1004.6

3200 sqft total@50 gross= 64 max capacity 18200 sqft total@ 30 gross= 606 max occupancy 12900 sqft total@ 60 gross= 215 max capacity 86500 sqft total @ 200 gross= 432 max capacity 206600 sqft total @ 200 gross= 1033 max capacity

Per § 1004.2 occupant loads may be increased beyond those listed in Table 1004.1.2 as long as the means of egress system is sized to accommodate the occupant load. In no case may the occupant load calculated under this provision exceed one occupant per 7 sf (0.65 m2) of occipiable floor area. § 1004.1.1.2 applies the principle of convergence to the means of egress from a mezzanine, based on the assumption that some of the occupants of the mezzanine will pass through the floor below to get to a common set of exit paths and thus are added to the occupant load. When other egress paths are provided, those occupants need not be added. Mercantile space occupant load factors in Table 1004.1.2 have been revised so that the same factor is to be used for these spaces no matter what floor they are on. The factor is 60 sf (5.6 m2) per occupant, gross. § 1004.3 requires assembly occupancies to have signs posted in a conspicuous place showing the occupant load. This is to prevent overloading of the spaces, which could impair exiting in a panic situation. § 1004.5 states that outdoor areas, such as dining patios behind restaurants, are to be included in occupant-load calculations and provided with exits. When it can be anticipated that the occupants of an outdoor area would be in addition to those occupants inside the building, this occupant load must be added to the egress capacity calculations. When the occupants can be expected to be either inside or outside, but not both, the capacity need not be additive. § 1004.6 covers the means-of-egress requirements that apply to buildings housing multiple occupancies. When there are special egress requirements based on occupancy, they apply in that portion of the building housing that occupancy. When different occupancies share common egress paths, the most stringent requirements for each occupancy will govern the design of the means-of-egress system.

Section 1005 Egress Sizing

3


§ 1005 specifies that the capacity of exit pathways be governed by: the occupant load, the hazard of the occupancy, whether the building is sprinklered, and whether the path is a stair or other component of a means of egress. 1005.1 Minimum Required Egress Width The means of egress shall not be less than required by this section. The total width of means of egress in inches shall not beless than the total occupant load served by the means of egress multiplied by the factors in Table 1005.1 and not less than specified elsewhere in this code.Multiple means of egress shall be sized such that the loss of any one means of egress shall not reduce the availible capacity to less than 50 percent of the required capacity. The maximum capacity required from any story of a building shall be maintained to termination of the means of eqress. 1005.1 Egress Width Per Occupant Served Occupancies other than H and I Stairways: 0.3 inches per occupant. Other egress: 0.2 inches per occupant.

1005.3.1

1005.4

1005.7

Section 1007 1007.2.1

§ 1005.3.1 states that stairs are to be sized based on the occupant load of the invidual story served by the stair. Thus the highest occupant load of any story served by a stair will determine the minimum size of the stair. This is based on observations of the time factor, along with their directional nature, in determining how people move through egress systems. The occupants of the floor below are assumed to exit that level before those behind them get to the same point in the egress system. § 1005.4 states that the capacity of the egress paths shall not decrease in exit capacity in the direction of egress travel. This corresponds to the watercourse analogy as well. This is further supported by § 1005.6, which requires that when egress paths merge, the capacity of the egress paths serves both tributary areas. Because exit doors typically swing in the direction of exit travel, doors from rooms will often swing into paths of egress travel, such as corridors. § 1005.7 requires that in such situations: • The door should project a maximum of 7” (178) into the required width when fully opened against the wall of the passage, and • The opening of the door should not reduce the required width by more than one-half. • Along narrow corridors, doors should be recessed. Minimum recess for a 36” (914) door would be: 36”– 7” = 29” (914 – 178 = 736) • Nonstructural provisions, such as trim and similar decorative features, can project into the required corridor width a maximum of 1 1/2” (38) on each side. Handrail projections are to be per § 1014.8. Accessible Means of Egress Buildings with four or more stories. In buildings where a required accessible floor is four or more stories above or below a level of exit discharge, at least one required accessible means of egress shall be an elevator complying with Section 1007.4.

1007.3 Enclosed Exit Stairways An enclosed exit stairway, to be considered part of an accessible means of egress, shall have a clear width of 48 inches minimum between handrails and shall either incorporate an area of refuge within an enlarged floor-level landing or shall be accessed from either an area of refuge complying with Section 1007.6 or a horizontal exit.

1008.1.1 Size of Doors Size of doors. The minimum width of each door opening shall be sufficient for the occupant load thereof and shall provide a clear width of not less than 32 inches. Clear openings of doorways with swinging doors shall be measured between the face of the door and the stop, with the door open 90 degrees. Where this section requires a minimum clear width of 32 inches and a door opening includes two door leaves without a mullion, one leaf shall provide a clear opening width of 32 inches. The maximum width of a swinging door leaf shall be 48 inches nominal. Means of egress doors in an occupancy in Group I-2 used for the movement of beds shall provide a clear width not less than 41 1/2 The most common door type on the project is the door described in inches. The height of doors shall not be less than 80 exception 8 - which would cover all the doors in the dorm suites 36” door used for all doors outside of inches. except the door to the corridor. units. min.32” used in units. Exceptions 1. The minimum and maximum width shall not apply to door openings that are not part of the required means of egress in occupancies in Groups R-2 and R-3 as applicable in Section 101.2. 5. Door openings within a dwelling unit or sleeping unit shall not be less than 78 inches in height. 7. Interior egress doors within a dwelling unit or sleeping unit which is not require 8. Door openings required to be accessible within Type B dwelling units shall have Section 1009 Stairways and Handrails 1009.1 Stairway Width

4


Stairway width. The width of stairways shall be determined as specified in Section 1005.1, but such width shall not be less than 44 inches. See Section 1007.3 for accessible means of egress stairways.

804 max occupancy bowling= 241” total 38 max occupancy rm 1 exercise= 36” minimum 54 max occupancy rm 2 exercise= 36” minimum 61 max capacity rm 3 exercise= 36” minimum 27 max occupancy rm 4 exercise= 36” minimum 524 max capacity unconcentrated gym= 157.2” total 22 max capacity rm 1 library= 36” minimum 35 max capacity rm 2 library= 36” minimum 64 max capacity locker room= 36” minimum 606 max occupancy mercantile main= 182” total 215 max capacity merchantile other floor= 64.5” total 432 max capacity parking garage= 129.6” total Exception: 1. Stairways serving an occupant load of 50 or less shall 1033 max capacity residences= 309” have a width of not less than 36 inches. total

1009.2 Headrooom Stairways shall have a minimum headroom clearance of 80 inches measured vertically from a line connecting the edge of the nosings. Such headroom shall be continuous above the stairway to the point where the line intersects the landing below, one tread depth beyond the bottom riser. The minimum clearance shall be maintained the full width of the stairway and landing. all stars ways in compliance with 1009.2 1009.3 Stair Treads and Risers Stair riser heights shall be 7 inches maximum and 4 inches minimum. Stair tread depths shall be 11 inches minimum. The riser height shall be measured vertically between the leading edges of adjacent treads. (continues...) 1009.6 Vertical Rise A flight of stairs shall not have a vertical rise greater than 12 feet between floor levels or landings.

all stars ways in compliance with 1009.2

All stairs require a landing considering the floor to floor heigh is between 12-15’

1009.11 Handrails Stairways shall have handrails on each side. Handrails shall be adequate in strength adn attachment in accordance with Section 1607.7. Handrails for ramps, where required by Section 1010.8, shall comply with this At areas of refuge and areas for assisted section. rescue, signage shall be provided in accordance with § 1009.11. 1009.11.1 Handrail Height Handrail height, measured above stair tread nosings, or finish surface of ramp slope, shall be uniform, not less than 34 inches and not more than 38 inches. Section 1012 Guards 1012.1 Where Required Guards shall be located along open-sided walking surfaces, mezzanines, industrial equipment platforms, stairways, ramps and landings which are located more than 30 inches above the floor or grade below. Guards shall be adequate in strength and attachment in accordance with Section 1607.7. Guards shall also be located along glazed sides of stairways, ramps and landings that are located more than 30 inches above the floor or grade below where the glazing provided does not meet the strength and attachment requirements in Section 1607.7.

all stairs in compliance with 1009.6

all areas of rescue in compliance with 1009.11

all handrails in compliance with 1009.11.1

exceptions: 1. On the loading side of loading docks or piers.

1012.2 Height Guards shall form a protective barrier not less than 42 inches hight, measured vertically above the leading edge of the tread, adjacent walking surface or adjacent seatboard.

all walkways over large public spaces in compliance with 1012.1

all guards in compliance with 1012.2

Section 1013 Exit Access 1013 Egress Through Intervening Spaces Egress from a room or space shall not pass through adjoining or intervening rooms or areas, except where such adjoining rooms or areas are accessory to the area served; are not high-hazard occupancy and provide a discernible path of egress travel to an exit. Egress shall not pass through kitchens, storage rooms, closets or spaces used for similar purposes. An exit access shall not pass through a room that can be locked to prevent access. Means of egress from dwelling units or sleeping units shall not lead through All path of travel that pass through public spaces can not be other sleeping areas, toilet rooms or bathrooms. obstructed of limited by locked doorways

all exit egress in complance with 1013

1013.3 Common Path of Egress Travel

In occupancies other than Groups H-1, H-2, and H-3, the common path of egress travel shall not exceed 75 feet. In occupancies in Groups H-1, H-2, and H-3, the common path of egress travel shall not exceed 25 feet.

“Common path of egress travel" is: that portion of exit access which the occupants are required to traverse before two separate and distinct paths of egress travel to two exits are available. Paths that merge are common paths of travel. Common paths of egress travel shall be included within the permitted travel distance. In no areas do the common paths of egress travel - when added to the distances between exits on any level - result in an overall travel distance which exceeds those permitted in Table 1015.1.

115’ max. travel distance for M occupancy group. 112’ max travel distance for A occupancy group. 63’ max travel distance for R-1 occupancy group.

Section 1014 Exit and Exit Access Doorways 1014.1 Exit or Exit Access Doorways Required Two exits or exit access doorways from Table 1014.1 shows a maximum occupant load for an R use of 10. any space shall be provided where one of the The following conditions exits: occupant load - from table 1004.1.2 (dorms) is 50 gross. So any 1. The occupant load of the space exceeds the values residential space which is larger than 500 sf is required to have two all residential levels have at least 2 in Table 1014.1. exit access doors. means of exit access at min. 36” Table 1014.1 Spaces with One Means of Egress-List if Necessary Occupancy

5

Max Occupant Load


Group A

50

Group B

50

Group R

10

at 15 sf per occupant = 750 square foot area at 100 sf per occupant = 5000 square foot area at 50 sf per occupant = 500 square foot area

1014.2.1 Two Exits or Exit Access Doorways-Location and Separation East Part diagonal distance =192’, required separation distance (sprinkled)=1/3*diagonal distance=64’, exit distance= 66’ West Part diagonal distance=178’, required separation distance (sprinkled)=1/3* diagonal distance=59’, exit distance: 80’ North Part diagonal distance = 176’, required separation distance (sprinkled)=1/3*diagonal distance=58’, exit distance =79’

Where two exits or exit access doorways are required from any portion of the exit access, the exit doors or exit access doorways shall be placed a distance apart equal to not less than one-half of the length of the maximum overall diagonal dimension of the building or area to be served measured in a straight line between exit doors or exit access doorways. Interlocking or scissor stairs shall be counted as one exit stairway. Exceptions 2. Where a building is equipped throughout with an automatic sprinkler system in accordance with Section 903.3.1.1 or 903.3.1.2, the separation distance of the exit doors or exit access doorways shall not be less than one-third of the length of the maximum overall diagonal dimension of the area served.

The entire building is equipped with an automatic sprinkler system 180’^2+50’^2=186’^2 Maximum diagonal in accordance with 903, and the separation distance may be 1/3 of building= 186/2= 93> 120’= in the diagonal. compliance

Section 1015 Exit Access Travel Distance max travel distance per occupancy group 1015.1 Travel Distance Limitations Exits shall be located on each story such that the maximum length of exit access travel, measured from the most remote point within a story to the entrance to an exit along the natural and unobstructed path of egress travel, shall not exceed the distances given in Table 1015.1. Where the path of exit access includes unenclosed stairways or ramps within the exit access or includes unenclosed exit ramps or stairways as permitted in Section 1019.1, the distance of travel on such means of egress components shall also be included in the travel distance measurement. Table 1015.1 Exit Access Travel Distance A,E,R occupancies 200 (no sprinkler) 250 (with) B occupancy 200 (no sprinkler) 300 (with) Section 1016 Corridors 1016.1 Corridor Fire-Resistance Rating R Occupancy / greater than 10 per floor / sprinkler required / 0.5 hour rating 1016.3 Dead End Corridors Where more than one exit or exit access doorway is required, the exit access shall be arranged such that there are no dead ends in the corridors more than 20 feet in length.

The entire building is equipped with an automatic sprinkler system in accordance with 903, so the longer distances apply. all areas in compliance, total travel The entire building is equipped with an automatic sprinkler system distance less than 250’ through the in accordance with 903, so the longer distances apply. building.

Corridors serving residential uses would require a 1/2 hour rating.

all corridors have a 1 hour fire rating

All levels of the building are required to have 2 exits.

no dead ends exist > 20 ft

Section 1018 Number of Exits and Continuity 1018.1 Minimum Number of Exits All rooms and spaces within each story shall be provided with and have access to the minimum number of approved independent exits as required by Table 1018.1 based on the occupant load, except as modified in Section 1014.1 or 1018.2. For the purposes of this chapter, occupied roofs shall be provided with exits as required for stories. The required number of exits from any story, basement or individual space shall be maintained until arrival at grade or the public way.

All occupied spaces in compliance with 1018.1 having at least 2 means of exit egress based on section 1013.3

10182 Number of Exits An occupant in a basement and on a story above the first story shall have access to not less than two separate exits from the basement or story.

Chapter 11

Accessibility § 1103.1 states that the requirements for accessibility apply both to buildings and to the sites where they are located. The accessible route is 1103.1 typically considered to extend to the boundaries of the site. Every path of travel may not need to be accessible, but a readily located accessible route must be provided inside and outside of the building and on the site.

1104 § 1104 requires that at least one accessible route be provided at site arrival points, from public transportation stops, accessible parking and loading zones, public streets, and sidewalks within the site. 1104.4 Multilevel Buildings and Facilitiies At least one accessible route shall connect each accessible level, including mezzanines, in multilevel buildings and facilities. 1107.6.2.1.1 Type A Units In occupancies in Group R-2 containing more than 20 dwelling units or sleeping units, at least 2 percent, but not less than one, of the units shall be a Type A unit. All units on a site shall be considered to determine the total number of units and the required number of Type A units. Type A units shall be dispersed among the various classes of units. § 1107.6.1.2 requires every dwelling unit to be a Type B dwelling unit in residential occupancies, 1107.6.1.2 such as Group R-2 and R-3 occupancies, where there are more than four dwelling units. See also the comment at left regarding I occupancies. Recreational facilities that serve Group R-2, R-3, 1110 and R-4 occupancies are to be accessible.

6

Comments

exception: requirements, and these exceptions are distributed among sections in other chapters of the code. The exceptions apply in general to low occupancy spaces and those where provision of access would be disproportionate to the utility of the space. exception:The only exception to this requirement is for a large site where elements are spread out along a vehicular access route that is not in itself accessible. This assumes that all people on the site are moving from one location to another by vehicle and that there is not a separate inaccessible pedestrian route for people without disabilities.

all routes on every level in compliance

50 type A R-1 units throughout the project exception: Accessible dwelling and sleeping units are to be provided per Table 1107.6.1.1. Where a building contains more than 50 dwelling units or sleeping units, the number of Accessible units are to be determined per building. exception: 1110.4.6: Raised refereeing, judging, and scoring structures used solely for refereeing, judging, or scoring a sport are not required to be accessible or be on an accessible route.


§ 1110.4.3: An accessible route is to be provided to at least 5%, but not less than one, of each type of bowling lane. Note that only seating serving the accessible bowling lanes is to be accessible and on an accessible route. Each area of sport activity is to be on an accessible route but is not required to be accessible except as provided for in § 1110.4.2 through § 1110.4.14, which set forth specific requirements or exclude some areas from accessibility requirements. § 1111.1 requires the international symbol of accessibility to be located at accessible parking spaces per § 1106.1 and 1106.2, accessible areas of refuge per § 1007.9, at accessible toilet locations, at accessible entries, accessible checkout aisles, and at accessible 1111 dressing and accessible locker rooms. Laundry Equipment: When laundry equipment is provided in spaces that are required to be accessible, § E105.2 requires that at least one of each type of equipment should be accessible per A117.1. Mailboxes: § E105.4 requires that when mailboxes are provided at an interior location that at least 5% of them be accessible per A117.1. Where mailboxes are provided at each unit then accessible mailboxes are to be provided at accessible units.

7

all accessible routes and seating arrangements in bowling alley

no stacked washers in units, all accessible side by side centrally located

all mailboxes in compliance






BUILDING SITE DIAGRAMS COMPACTNESS

D- TOW(N)ER Jamilla Afandi, Adam Brach, Daimei Wang and Shurui Wu Dowdell + Vance Studio

Site Building Data: BUILDING SITE DIAGRAM (MORE COMPACT) Gross floor area Faรงade area Roof area Area to ground Total Envelope Volume E/A A/V

330,000 ft2 90,700 ft2 55,000 ft2 55,000 ft2 200,700 ft2 4,292,000 ft3 0.61 0.04

BUILDING SITE DIAGRAM (SCHEMATIC DESIGN) Gross floor area Faรงade area Roof area Area to ground Total Envelope Volume E/A A/V Heating Energy Demand Total Energy Demand

269,130 ft2 200,500 ft2 29,500 ft2 29,500 ft2 259,500 ft2 4,051,500 ft3 0.96 0.06 10kwh/m2.year 40kwh/m2.year

BUILDING SITE DIAGRAM (LESS COMPACT) Gross floor area Faรงade area Roof area Area to ground Total Envelope Volume E/A A/V

313,600 ft2 307,200 ft2 27,200 ft2 27,200 ft2 361,600 ft2 4,000,000 ft3 1.15 0.09

269,130 ft2 /25000 m2 Gross floor area 200,500 ft2 / 18627 m2 Faรงade area 29,500 ft2 / 2740 m2 Roof area 29,500 ft2 / 2740 m2 Area to ground 259,500 ft2 / 24108 m2 Total Envelope 4,051,500 ft3/ 114725.7m3 Volume Compactness 0.96 m2/m2 E/A 0.21 m2/m3 A/V 10kwh/m2.year Heating Energy Demand 40kwh/m2.year Total Energy Demand

BUILDING SITE DIAGRAMS ORIENTATION

N

Window to wall ratio 20% all facades. High PerformanceEnvelope

N

Window to wall ratio 60% at one long facade. 10% at the others. High Performance Envelope

N

Window to wall ratio 60% at one long facade. 20% at the others. High Performance Envelope

Design Narrative: Our team select the second massing as our final scheme. The building depth of the more compact one will be very long and the central part can not gain any daylight. The less compact one is in confliction with our concept of a high-density urban community. The tower scheme is very compact and the depth is 40-50 feet so that daylight can cover most part of the room.

BUILDING SITE DIAGRAM ORIENTATION 1

BUILDING SITE DIAGRAM ORIENTATION 2

BUILDING SITE DIAGRAM ORIENTATION 3

The main orientation of our building is south/southeast so that most units can gain enough daylight by facing south. Through the calculation, we also find out that putting more windows along one long facade can save more energy.


BUILDING SITE DIAGRAMS SOLAR ORIENTATION AND DAYLIGHT

D- TOW(N)ER Jamilla Afandi, Adam Brach, Daimei Wang and Shurui Wu Dowdell + Vance Studio

Site Building Data: 269,130 ft2 /25000 m2 Gross floor area 200,500 ft2 / 18627 m2 Façade area 29,500 ft2 / 2740 m2 Roof area 29,500 ft2 / 2740 m2 Area to ground 259,500 ft2 / 24108 m2 Total Envelope 4,051,500 ft3/ 114725.7m3 Volume Compactness 0.96 m2/m2 E/A 0.21 m2/m3 A/V 10kwh/m2.year Heating Energy Demand 40kwh/m2.year Total Energy Demand

SOLAR “ENTRY”- NOON

DAYLIGHT DIAGRAM

Winter noon sun angle = 90-(42.3+23.26)=24.44 Summer noon sun angle = 90-(42.3-23.26)=70.96

The short building depth and floor to ceiling windows make it possible for all units to face south/southeast to gain equivalent daylight.

BUILDING SITE DIAGRAMS NATURAL VENTILATION

Northwest Operable Window

Design Narrative: The short building depth and floor to ceiling windows make it possible for all units to face south/southeast to gain equivalent daylight. Single corridor layout also guarantees direct access to sunlight without being blocked by other buildings. The balcony side is facing the south/south east while the corridor side is facing the north/northwest. Thus, the unit can enjoy morning and noon daylight rather than exposed to the afternoon west sunlight.

Southeast Balcony

NATURAL VENTILATION PLAN DIAGRAM Because of the short depth of the tower, most units facing the south/southcan have cross ventilation. (d/h = 50/12 <5)

NATURAL VENTILATION SECTION DIAGRAM Balcony area and floor to ceiling windows increase natural ventilation rate.

NATURAL VENTILATION ISOMETRIC Public space (void space) ventilation can help reduce the level of pollutants in “closed” corridor area.

All units have one side facing the street and one side facing public park; cross ventilation will be the main strategy. (d/h = 50/12 =4.16 <5). Big public space connects to corridors, and such void space ventilation can help reduce the level of pollutants in “closed” corridor area.


D-TOW(N)ER

20' - 0"

20' - 0"

Jamilla Afandi, Adam Brach, Daimei Wang, and Shurui Wu Dowdell + Vance Studio

Building Layout and Grid

50' - 0" 20' - 0" 10' - 0"

Structural System

20' - 0"

20' - 0"

UP

Type of Construction Site Location Seismic Rating SiteSpecific Wind Speed Floor and Roof Live Load Ground Snow Load Structural Frame Type Structural Materails Structure Fire Rating Period

UP

20' - 0"

20' - 0"

UP UP

20' - 0"

20' - 0"

20' - 0"

20' - 0"

20' - 0"

20' - 0"

140' - 0"

Building Data:

20' - 0"

20' - 0"

20' - 0" 10' - 0" 20' - 0" 10' - 0" 20' - 0"

Building Layout

20' - 0"

20' - 0"

73

20' - 0"

72

20' - 0"

71

70

69

stiffener angles are fastened to each side of a web plate to stiffen it against buckling; bearing stiffeners are placed at a point of support or under a concentrated load; intermediate stiffeners are placed between bearing stiffeners for increased resistance to diagonal compressive stresses.

Type II-B Zone I 120 mph 50 psf 20 psf Concrete Frame Concrete 120 Minutes

68

Structural Grid

Structural Spanning System

Structural Schematics

4” minimum slab depth, rule of thumb for slab depth tensile reinforcement Two-way slabs are most efficient when spanning square or nearly square bays, and suitable for carrying intermediate heavy loads over 15’ to 40’ spans

Green Roof

Schematic Design For the schematic design, we chosed 20’ by 20’ grid system for building structure so that each living unit is 20’ by 40’. Three structure options are concrete structure with two-way slab and beam, concrete structure with two-way waffle slab, and steel structure.

19” domes and 5” ribs create a 2’ module 3” to 4-1/2” slab depth; rule of thumb for total depth: span/24=10” square metal or fiberglass dome forms are available in 19” and 30”

Considering we have green roofs on the top and roof live load will be much heavier than regular roof. Concrete structure may be more reasonable for this superstructure. Rule of thumb calculations Span: 20’ 1. Concrete column (1F-8F) 16”X16” (9F-25F) 12”X12” 2. Concrete beam minimum depth: span/16=15” beam width should be equal or greater than column width width: 1/3 to 1/2 of beam depth = 12” depth: 24” to 36” 3. Two-way slab and beam 4” minimum slab depth, rule of thumb for slab depth: slab perimeter/180 depth = 6”

Structural Scheme Option 1 Steel, Two-way Beam System

Structural Scheme Option 2 Concrete, Two-way Slab and Beam

Structural Scheme Option 3 Concrete, Two-way Waffle Slab

two-way slabs are most efficient when spanning square or nearly square bays and suitable for carring intermediate to heavy loads over 15’ to 40’ spans.


Jamilla Afandi, Adam Brach, Daimei Wang, and Shurui Wu Dowdelll + Vance Studio

poured in place concrete slab

3/4” hardwood floor finishing

Structural System

1/2” insulation foam

rebar

6 mil vapor barrier

Building Data:

floor reactions become forces on beams

Type of Construction Site Location Seismic Rating SiteSpecific Wind Speed Floor and Roof Live Load Ground Snow Load Structural Frame Type Structural Materails Structure Fire Rating Period

concrete slab

68

3/4” plywood subfloor 2X4” @16” sleepers

two-way conceret beampoured in place

20' - 0"

reinforced concrete column

12”

9F-25F Rule of thumb calculations

12”

Span: 20’

UP

20' - 0" 20' - 0"

20' - 0"

20' - 0"

UP UP

20' - 0"

20' - 0"

73

20' - 0" 10' - 0" 20' - 0" 10' - 0" 20' - 0"

72

71

70

69

Typical Floor plan with all structural sizes and grids dimensioned UP UP

20' - 0"

20' - 0"

20' - 0" 10' - 0" 20' - 0" 10' - 0" 20' - 0"

20' - 0"

68

20' - 0"

73 20' - 0"

20' - 0"

72

20' - 0"

20' - 0"

71

20' - 0"

UP

70

20' - 0"

20' - 0"

20' - 0"

UP

3. Two-way slab and beam 4” minimum slab depth, rule of thumb for slab depth: slab perimeter/180 depth = 6”

69 UP

20' - 0" 20' - 0"

20' - 0"

2. Concrete beam minimum depth: span/16=15” beam width should be equal or greater than column width width: 1/3 to 1/2 of beam depth = 12” depth: 24” to 36” 20' - 0"

UP

20' - 0"

UP

140' - 0" UP

20' - 0" 10' - 0" 20' - 0" 10' - 0" 20' - 0"

70

1. Concrete column (1F-8F) 16”X16” (9F-25F) 12”X12”

lateral support system

UP

20' - 0"

concrete shear wall

UP

50' - 0" 20' - 0" 10' - 0"

UP

20' - 0" 140' - 0"

20' - 0"

71

We use concrete shear walls at each end of the masing as lateral support system.

12”

16” UP 1F-8F

72

20' - 0" 10' - 0" 20' - 0" 10' - 0" 20' - 0"

50'16” - 0" 20' - 0" 10' - 0"

20' - 0"

50' - 0" 20' - 0" 10' - 0"

9F-25F

140' - 0"

20' - 0" 20' - 0" 20' 20'- -0"0" 20' - 0" 20'20' - 0"- 0" 20'20' - 0"- 0" 20' 20' 20' - -0"0" - 0" 20' 20' 20' - -0"0" - 0" 20' 20' 20' - -0"0" - 0" 20' 20' 20' - -0"0" - 0" 20' 20'20' - -0"0" - 0" 20' 20'- -0"0"

20' - 0" 140' - 0"

20' - 0" 20' - 0" 20' - 0" 20' - 0" 20' - 0" 20' - 0" 20' - 0"

12”

UP 1F-8F

20' - 0"

20' - 0"

High-rise buildings that are assigned to Risk Category III or IV. As there is a high-rise residential building in our project, we decided to use concrete frame structure. The grid is 20’ by 20’ and we used two-way slab and beam system. For the floor detail, we consider using reinforced concrete slab and it’s cast-in-place concrete.

reinforced concrete beam

20' - 0"

UP

16”

27”

20' - 0"

UP

50' - 0" 20' - 0" 10' - 0"

20' - 0"

20' - 0"

20' - 0"

20' - 0"

20' - 0"

UP

20' - 0"

Isometric view of structural assembly with lateral support system

Detail Design 27”

20' - 0"

lateral support system: concrete core bracing system at each end of the building

50' - 0" 20' - 0" 10' - 0"

20' - 0"

20' - 0"

20' - 0"

Structural Assembly and Lateral Support System

73

20' - 0" 20' - 0"

20' - 0"

Typical flooring system and finishes

20' - 0"

Typical anatomy of structure and construction

140' - 0"

Typical module force exploded diagrams

UP

Column reactions become forces on foundations

69

columns are in compression

Type II-B Zone I 120 mph 50 psf 20 psf Concrete Frame Concrete 120 Minutes

20' - 0"

conceret slab carries roof loads uniformly distributed

D-TOW(N)ER

Floor Details

20' - 0"

68


D-TOW(N)ER

Constructional Systems Layouts

Jamilla Afandi, Adam Brach, Daimei Wang, and Shurui Wu Dowdelll + Vance Studio 6” thick reinforced concrete slab

Structural System Building Data:

12”X 27” two-way poured in place concrete beam

1” thick bluestone hung on the facade

west facade with double panel sliding windows

Type of Construction Site Location Seismic Rating SiteSpecific Wind Speed Floor and Roof Live Load Ground Snow Load Structural Frame Type Structural Materails Structure Fire Rating Period

Type II-B Zone I 120 mph 50 psf 20 psf Concrete Frame Concrete 120 Minutes

12”X 12” poured in place concrete column double panel Low E glaze store front system Integrated Design concrete staircase

Integrated floor: the floor is integrated with per unit Air Handling Unit and conduit. As we are using two-way concrete frame structure, the AHU system is located beneath the concrete beam and inside the dropped ceiling. The electricity pipe is integrated in the slab. The floor has sound insulation and vapor barrier.

8” thick internal wall 12” thick concrete shear wall

12”X 27” two-way poured in place concrete beam

12” thick concrete shear wall between units balcony with sandstone panel, sliding door, tilt window, and railing

finishing floor

Construction rendered exploded views

Integrated wall: the internal wall is constructed by CMU blocks as fire separation. It has sound insulation. The exterier wall is rapped with thermal insulation.


D-TOW(N)ER

Integrated Systems Details 3/4” hardwood floor finishing

interior

exterior balcony

3/4” plywood subfloor 2X4” @16” sleepers rebar

1/2” insulation foam 6 mil vapor barrier

12”X27”reinforced concrete beam

1/4” per foot sloped concrete balcony double panel sliding door

6” rigid insulation

thermal break

6” thick reinforced concrete slab

12”X27”reinforced concrete beam

2 layers gypsum-based board

Jamilla Afandi, Adam Brach, Daimei Wang, and Shurui Wu Dowdelll + Vance Studio

railing

Structural System Building Data: Type of Construction Site Location Seismic Rating SiteSpecific Wind Speed Floor and Roof Live Load Ground Snow Load Structural Frame Type Structural Materails Structure Fire Rating Period

Type II-B Zone I 120 mph 50 psf 20 psf Concrete Frame Concrete 120 Minutes

reinforced concrete slab

8” CMU

one layer of gypsum-based board

2X4” wood framing /Fiber glass insulation

interior

2 layers gypsum-based board

Integrated Design

Typical internal wall structure floor junction

Typical external wall structure floor junction concrete column sliding door

conduit in the slab 4’X4’ sandstone panel glass and metal railing

per unit AHU

dropped ceiling 6” air vent below the beam

concrete slab with sandstone on the facade reinforced concrete beam

Typical Isometric cut away structure integrated detail

tructural detail with finishies

Integrated floor: the floor is integrated with per unit Air Handling Unit and conduit. As we are using two-way concrete frame structure, the AHU system is located beneath the concrete beam and inside the dropped ceiling. The electricity pipe is integrated in the slab. The floor has sound insulation and vapor barrier. Integrated wall: the internal wall is constructed by CMU blocks as fire separation. It has sound insulation. The exterier wall is rapped with thermal insulation.



D- TOW(N)ER Jamilla Afandi, Adam Brach, Daimei Wang, Shurui Wu Dowdell + Vance Studio

Active Environmental Design Systems ENERGY DISTRIBUTION

AIR HANDLING

ENERGY CONVERSION

domestic hot water usage

WARM WATER

hot water tank (centrally located)

RESOURCES

ground water supply

heat exchanger

natural gas condenser unit split down flow air handling unit

return

supply

pv panels

electricity

Active Energy concept

Active Systems


D- TOW(N)ER Jamilla Afandi, Adam Brach, Daimei Wang, Shurui Wu Dowdell + Vance Studio

Active Environmental Design Systems

Active Systems Energy Conversion Heating system:

In unit natural gas furnace equipped with electric AHU with heat exchanger.

per unit AHU with Condenser Unit

Cooling System:

Return Supply Return Return

per unit AHU with Condenser Unit

Supply

Supply

Return Return 3 panel sliding glass door Supply

operable tilt window 3 panel sliding glass door

Supply

operable tilt window

Energy Conversion Type of energy conversion

3 panel sliding glass door

Heat exchanger

operable tilt window

Domestic Warm Water Heating Type of WW heating Single Bedroom Apartment 2 supply vents- 2 return vents

Double Bedroom Apartment 3 supply vents- 3 return vents

Central hot water boiler located near top of building

Renewable Energy Sources

PV panels incorporated into the design of rooftop grey water management system with the height of buildings increasing northward to allow for optimal collection of solar rays by pv panels.

Isometric illustration of energy distribution


D- TOW(N)ER Jamilla Afandi, Adam Brach, Daimei Wang, Shurui Wu Dowdell + Vance Studio

Active Environmental Design Systems

Active Systems

Return

Return

To circulate the cooled and heated air a air handling unit is installed in every residence unit. To improve AHU efficiency a heat exchanger is also installed. All mean of power are of natural gas.

Return

Return

Gyp. Board Soffit

Mechanical Ventilation

Gyp. Board Soffit

Return Supply

Supply Supply

Supply

Supply

Single Bedroom Apartment Energy Distribution

Double Bedroom Apartment Energy Distribution

Integration of Ventilation and Energy Distribution





306’ - 0’’

294’ - 0’’ 282’ - 0’’

D-TOW(N)ER Jamilla Afandi, Adam Brach, Daimei Wang, and Shurui Wu Dowdell + Vance Studio

270’ - 0’’

258’ - 0’’

Building Elevations

246’ - 0’’

Building Data: 234’ - 0’’

222’ - 0’’ 210’ - 0’’

Gross Building SF Total Elevation SF Total Glass SF Total Percentage of Glass Elevation

331344SF 169002SF 100278SF 59.3%

198’ - 0’’

186’ - 0’’ 174’ - 0’’

Facade Design Narrative: 162’ - 0’’

150’ - 0’’ 138’ - 0’’ 126’ - 0’’

114’ - 0’’ 102’ - 0’’ 90’ - 0’’ 78’ - 0’’

66’ - 0’’ 54’ - 0’’ 42’ - 0’’ 30’ - 0’’

15’ - 0’’

Grand River Ave

Grand River Ave

Overall Building Elevation: Primary Site Facade

0’ - 0’’

South Elevation SCALE:

1/32” = 1’-0”

There are three types of facades in this project based on diferent programs and plan layout. The fisrt one is on the bacony side of the living units. As the bacony is a triangle shape, the facade that faces to the bacony is composed of fixed glass, tilt window and glass sliding door. The solid area of the facade is covered with sandstone panels, which is a local material in Michigan. The percentage of glass in this facade is 75% and they are facing to south as well as north, which is intended to increase the sunlight into living room and bedroom. The second type of facade is located in the corridor side of the living units. It’s primary located on the west elevation of the highrise. The facade is basically a curtain wall system with 4’ by 4’ bluestone panels hanging on the outside of the glass. Both the stone panels and the solar control glazing function as shading elements. The third type of facade is store-front curtain wall system for all of the public space that includes sports court, restaurant, commercial and other types of community space.


306’ - 0’’

294’ - 0’’ 282’ - 0’’ 270’ - 0’’

D-TOW(N)ER Jamilla Afandi, Adam Brach, Daimei Wang, and Shurui Wu Dowdell + Vance Studio

Building Elevations

258’ - 0’’ 246’ - 0’’ 234’ - 0’’

222’ - 0’’

Building Data: Gross Building SF Total Elevation SF Total Glass SF Total Percentage of Glass in Elevation

331344SF 169002SF 100278SF 59.3%

210’ - 0’’ 198’ - 0’’

186’ - 0’’ 174’ - 0’’ 162’ - 0’’

150’ - 0’’ 138’ - 0’’ 126’ - 0’’

114’ - 0’’

Facade Design Narrative: There are three types of facades in this project based on diferent programs and plan layout. The fisrt one is on the bacony side of the living units. As the bacony is a triangle shape, the facade that faces to the bacony is composed of fixed glass, tilt window and glass sliding door. The solid area of the facade is covered with sandstone panels, which is a local material in Michigan. The percentage of glass in this facade is 75% and they are facing to south as well as north, which is intended to increase the sunlight into living room and bedroom.

102’ - 0’’ 90’ - 0’’ 78’ - 0’’

66’ - 0’’ 54’ - 0’’ 42’ - 0’’ 30’ - 0’’

15’ - 0’’

0’ - 0’’

Overall Building Elevation: Courtyard Elevation

East Elevation SCALE:

1/32” = 1’-0”

The second type of facade is located in the corridor side of the living units. It’s primary located on the west elevation of the highrise. The facade is basically a curtain wall system with 4’ by 4’ bluestone panels hanging on the outside of the glass. Both the stone panels and the solar control glazing function as shading elements. The third type of facade is store-front curtain wall system for all of the public space that includes sports court, restaurant, commercial and other types of community space.


D-TOW(N)ER Jamilla Afandi, Adam Brach, Daimei Wang, and Shurui Wu Dowdell + Vance Studio 4’X4’ sandstone panel t=1”

Building Elevations Unit Data:

glass and metal railing

Gross Building Net Building Number of Floors Number of Units

concrete slab t=6” covered with 5’ X3’ sandstone panel t=1”

269,130SF 152,486SF overground:25 underground:2 152

sliding door 8’10”height 2’7” width

Facade Design Narrative:

tilt window 3’ height 3’6” width t=1”&1/2”gas fill

There are three types of facades in this project based on diferent programs and plan layout. The fisrt one is on the bacony side of the living units. As the bacony is a triangle shape, the facade that faces to the bacony is composed of fixed glass, tilt window and glass sliding door. The solid area of the facade is covered with sandstone panels, which is a local material in Michigan. The percentage of glass in this facade is 75% and they are facing to south as well as north, which is intended to increase the sunlight into living room and bedroom.

2’X4’ bluestone panel t=1” solar control glass t=1”&1/2”gas fill

concrete slab t=6” covered with 5’ X3’ sandstone panel t=1”

The second type of facade is located in the corridor side of the living units. It’s primary located on the west elevation of the highrise. The facade is basically a curtain wall system with 4’ by 4’ bluestone panels hanging on the outside of the glass. Both the stone panels and the solar control glazing function as shading elements.

tilt window 5’6” height t=1”&1/2”gas fill

The third type of facade is store-front curtain wall system for all of the public space that includes sports court, restaurant, commercial and other types of community space.

East Elevation SCALE:

3/16” = 1’-0”

Enlarged Elevation Study

Wall Section SCALE:

3/16” = 1’-0”


D-TOW(N)ER

DETAIL 1

DETAIL 1

DETAIL 2

FIXED

FIXED

Jamilla Afandi, Adam Brach, Daimei Wang, and Shurui Wu Dowdell + Vance Studio

DETAIL 1

SLIDE

Building Elevations Unit Data:

DETAIL 2

Total Building Elevation SF Total Building Glass SF Total Percentage of Glass for All Building Elevations

331344SF 169002SF 59.3%

DETAIL 2

Window for public space

Window for bacony

Window for bedroom

FG 623 inside glazed Thermal (1”&1/4” infill), Solar Control Glass

AA 3200 HP Thermal sliding door

CW-GLASSvent UT window TRIFAB 451UT Framing system

Window Elevation SCALE:

1/4” = 1’-0”

Window Design Narrative. Detail1

Detail1

Detail1

Head 1” infill

Head at sliding panel

Head of fixed glass

The glass of window for public space is solar control glass so that it functions as part of shading system. We chose full height window from ceiling to floor for the facade on the balcony side to maximize the daylight for living room and bedroom. Dimension of the window is chosen according to the modular of the facade.

Detail2

Detail2

Detail2

Intermediate horizontal 1” over 1” infill

Sill at sliding panel

Head of window

Window Details SCALE:3”

Window Type Diagram / Schedule

= 1’-0”













D-TOW(N)ER

Jamilla Afandi, Adam Brach, Daimei Wang, Shurui Wu Dowdell + Vance Studio

Passive and Active Environmental Systems and Facades

Details

Wall Construction Calculation Components

Thickness

Outdoor Air Film

n/a

Rigid Foam Insulation

0.33'

Indoor Air Film

n/a

Plywood

k

c

r 0.3

0.018

0.05

0.04'

0.69

17.25

0.06

Gypsum Board

0.04'

0.26

6.5

0.15

Concrete Wall

1'

1.4

1.4

0.72

18.33 0.72

TOTAL

20.28

U-VALUE

0.04930966469

Floor Construction Table Components

Thickness

Outdoor Air Film

n/a

Rigid Foam Insulation

0.33'

Indoor Air Film

n/a

Oakwood

0.04'

Concrete Slab

1 + 0.25'

k

c

r 0.3

0.018

0.15

18.33

0.69

6.5

0.06

1.4

1.12

0.89

0.72

TOTAL

20.3

U-VALUE

0.04926108374

Green Roof Table Components

Thickness

Rigid Foam Insulation

0.33'

Concrete Slab

2'

Rigid Foam Insulation

k

c 0.05

1.4

0.7

1.43

0.33'

0.018

0.05

18.33

Plywood

0.04'

0.69

17.25

0.06

Gypsom Board

0.04'

0.26

6.5

0.15

Insulation Layer

Weather Wrap Vapor Barrier

18.33

38.3

U-VALUE

r

0.018

TOTAL

0.02610966057

Calculation U Value SI or IP units

Insulation U-value Roof (R-Value) .02611 (38.3) U-Value Wall (R-Value) .04931 (20.3) U-Value Floor (R-Value) .04926 (20.3) Weather Wrap TYVEK Commercial @ 28 perms 1. Air Penetration: 0.001 cfm/ft2 at 75 Pa 2. Water Vapor Transmission: 28 perms 3. Water Penetration Resistance: Minimum 280 cm 4. Basis Weight: Minimum 2.7 oz/yd2, 5. Air Resistance: Air infiltration at >1500 seconds 6. Tensile Strength: Minimum 38/35 lbs/ in. 7. Tear Resistance: 12/10 lbs. 8. Surface Burning Characteristics: Class A


Turn static files into dynamic content formats.

Create a flipbook
Issuu converts static files into: digital portfolios, online yearbooks, online catalogs, digital photo albums and more. Sign up and create your flipbook.