Magnecraft TDR Section 5

Page 1

Section

SECTION 5

5

Relays - Time Delay & Sensor

www.magnecraft.com

847-441-2540


Time Delay Relays – Application Data

Definition: Time Delay is defined as the controlled period between the functioning of two events. A Time Delay relay is a combination of an electromechanical output relay and a control circuit. The control circuit is comprised of solid state components and timing circuits that control operation of the relay and timing range. Typical time delay functions include On-Delay, Repeat cycle (starting off), Interval, Off-Delay, Retriggerable One Shot, Repeat cycle (starting on), Pulse Generator, One Shot, On/Off Delay, and Memory Latch. Each function is explained in the table below. Time delay relays have a broad choice of timing ranges from less than one second to many days. There are many choices of timing adjustments from calibrated external knobs, DIP switches, thumbwheel switches, or recessed potentiometer. The output contacts on the electromechanical output relay are direct wired to the output terminals. The contact load ratings are specified for each specific type of time delay relay. Understanding the differences between all the functions available in time delay relays can sometimes be a daunting task. When designing circuits using time delay relays questions such as: “What initiates a time delay relay?” “Does the timing start with the application or release of voltage?” “When does the output relay come on?”

SECTION 5

must be asked. Time delay relays are simply control relays with a time delay built in. Their purpose is to control an event based on time. The difference between relays and time delay relays is when the output contacts open & close: on a control relay, it happens when voltage is applied and removed from the coil; on time delay relays, the contacts will open or close before or after a pre-selected, timed interval. Typically, time delay relays are initiated or triggered by one of two methods: • application of input voltage (On Delay, Interval On, Flasher, Repeat Cycle, Delayed Interval & Interval/Flasher). • opening or closing of a trigger signal (Off Delay, Single Shot & Watchdog). These trigger signals can be one of two designs: • a control switch (dry contact), i.e., limit switch, push button, float switch, etc. • voltage (commonly known as a power trigger). To help understand, some definitions are important: Input Voltage: Control voltage applied to the input terminals (see wiring diagrams below). Depending on the function, input voltage will either initiate the unit or make it ready to initiate when a trigger signal is applied. Trigger Signal: On certain timing functions, a trigger signal is used to initiate the unit after input voltage has been applied. As noted above, this trigger signal can either be a control switch (dry contact switch) or a power trigger (voltage). Output (Load): Every time delay relay has an internal relay (usually mechanical) with contacts that open & close to control the load. They are represented by the dotted lines in the wiring diagrams. Note that the user must provide the voltage to power the load being switched by the output contacts of the time delay relay. The following tables contain both written and visual descriptions on how the common timing functions operate. A Timing Chart shows the relationship between Input Voltage, Trigger Signal (if present) and Output Contacts.

5/2

Magnecraft Solution Guide 105A


FUNCTION DEFINITION TABLES Function

Operation

Timing Chart

A. ON DELAY Power On

When the input voltage U is applied, timing delay t begins. Relay contacts R change state after time delay is complete. Contacts return to their shelf state when power U is removed. Control switch is not used in this mode.

U

B. REPEAT CYCLE Starting Off

When input voltage U is applied, time delay t begins. When time delay t is complete, relay contact R change state for time delay t. This cycle will repeat until input voltage U is removed. Control switch is not used in this mode.

U

When input voltage U is applied, relay contacts R change state immediately and timing cycle begins. When time delay is complete, contacts return to shelf state. When input voltage U is removed, contacts return to their shelf state. Control switch is not used in this mode.

D. OFF DELAY S Break

Input voltage U must be applied continuously. When control S is closed, relay contacts R change state. When control S is opened delay t begins. When delay t is complete, contact R return to their shelf state. If signal S is closed before time delay t is complete, then time is reset, the delay begins again, and relay contacts remain in their energized state If input voltage U is removed, relay contact R return to their shelf state.

E. RETRIGGERABLE ONE SHOT

Upon application of input voltage U, the time delay relay is ready to accept trigger signals S. Upon application of the trigger signal S, the relay contacts R transfer and the preset time t begins. At the end of the preset time t, the relay contacts R return to their normal condition unless the trigger signal S is opened and closed prior to time out t (before preset time elapses). Continuous cycling of the trigger signal S at a rate faster than the preset time will cause the relay contacts R to remain closed.

R

S

close open

R

on off

S

close open

R

on off

Upon application of input voltage U, the time delay relay is ready to accept trigger signals S. Upon application of the trigger signal S, the relay contacts R transfer and the preset time t begins. During time-out, the trigger signal S is ignored. The time delay relay resets by applying the trigger signal S when the relay is not energized.

U

Input voltage U must be applied continuously. When control S is closed, time delay t begins. When time delay t is complete, relay contacts R change state and remain transferred until control S is opened. If input power U is removed relay contacts R return to their shelf state.

U

Magnecraft Solution Guide 105A

R = Relay Contacts

t = Time Delay

t

t

t

t

t

t

t

t

U

H. ONE SHOT

S = Control Switch

t

U

Upon application of input voltage U, a single output pulse of 0.5 seconds long is delivered to relay after time delay t. Power must be removed and reapplied to repeat pulse. Control switch S is not used in the mode.

U = Input Voltage

t

t

G. PULSE GENERATOR

Input voltage U must be applied continuously. Output changes state with every control S closure. Returned to rest condition when power is removed.

on off

t

R

When input voltage U is applied, relay contacts R change state immediately and time delay t begins. When time delay t is complete, contacts return to their shelf state for time delay t. This cycle will repeat until input voltage U is removed. Control switch is not used in this mode.

J. MEMORY LATCH S Make

t

U

F. REPEAT CYCLE Starting On

I. ON/OFF DELAY S Make/Break

on off

t

SECTION 5

C. INTERVAL Power On

R

t

U R

on off

t

t

t

t

t

U R

on off

S

close open

R

on off

S

close open

R

on off

Pulse

t

t

t

Pulse

t

t

t

t

t

U S

close open

R

on off

5/3


Advantages of the 820 Series Time Delay Relays

Output Indication Red LED Light. Time Setting Select Between 10 Different Time Scales. Input Indication Green LED Light.

Fine Time Setting Ultimate Control in Accuracy.

Function Choose Between 10 Different Functions.

SECTION 5

Input Terminals Accepts up to a 14 AWG Wire.

DIN Rail Mounting Mounts Directly On a DIN Rail.

5/4

Magnecraft Solution Guide 105A


The new 820 Series Time Delay Relays are DIN rail mountable products offering 10 different timing functions, 2 status LEDs, ultra-wide timing range (0.1 sec to 10 days) and a universal voltage input (12-240 VAC/VDC) all in one modular package. The 821 is available as a 15 amp SPDT timer while its counterpart 822 is available as a DPDT timer also capable of switching up to 15 amps per pole.

• Offers a “one stop solution” for your power management system. • Available in both SPDT and DPDT contact configuration.

Solid State Circuitry Used for Time and function Control.

• The two LED status indicators indicate status at a glance. SECTION 5

• The Green LED is on when power is applied to the input terminals. The Red LED blinks during time-out, and is ON when the output is energized. • Color and appearance designed for high visibility in all environments. • Only 17.5 mm wide making it ideal for tight spaces.

Output Terminals Accepts up to a 14 AWG Wire.

• Engineering availability allows for customized relay solutions.

Optional Panel Adapter (16-788C1) See Section 3 p.18

www.magnecraft.com Magnecraft Solution Guide 105A

847-441-2540

5/5


820 Series Time Delay Relays/SPDT, DPDT 15 Amp Rating Input Indication Green LED

Output Indication Red LED Time Setting Fine Time Setting

Supply Terminals

Function

UL Listed File No. E234203

WHITE

Output Terminals DPDT (822 Version Only)

WHITE

Output Terminals DIN Mount

General Specifications Output Characteristics Number and type of Contacts Contact Material Current rating Switching voltage

Minimum Switching Requirement Indication

SECTION 5

Input Characteristics Voltage Range Operating Range Maximum consumption Indication Timing Characteristics Functions Available Time Scales Time Ranges Available

(UL 508) 821TD10H-UNI SPDT Silver Alloy 15 240 AC, 50/60 Hz 24 DC 1/2 @ 120VAC 1 @ 240 VAC B300 100 Red

822TD10H-UNI DPDT Silver Alloy 15 240 AC, 50/60 Hz 24 DC 1/2 @ 120VAC 1 @ 240 VAC B300 100 Red

12….240 85% to 110% 3 1.7 Green

12….240 85% to 110% 3 1.7 Green

day % % ms ms

A,B,C,D,E,F,G,H,I,J 10 0.1….1 1….10 0.1….1 1….10 0.1….1 1….10 0.1….1 1….10 5 0.2 150 50

A,B,C,D,E,F,G,H,I,J 10 0.1….1 1….10 0.1….1 1….10 0.1….1 1….10 0.1….1 1….10 5 0.2 150 50

V V AWG (mm2) in lb (Nm)

100,000 10,000,000 2500 AC 1000 AC 14 (2.1) 7.1 (0.8)

100,000 10,000,000 2500 AC 1000 AC 14 (2.1) 7.1 (0.8)

UL, CE -30…+70 -20…+55 IP 20 65

UL, CE -30…+70 -20…+55 IP 20 65

Units @ 240 VAC, 24 VDC

A V V HP HP Pilot Duty mA Blinks = Timing On = Energized

LED

% of Nominal LED

VAC / VDC AC DC

VA W

(See page 5/3) sec min hr

Tolerance Repeatability Reset Time Trigger Pulse Length Performance Characteristics Electrical Life Mechanical Life Dielectric strength Terminal Wire Capacity Terminal Torque (maximum) Environment Product certifications Ambient air temperature around the device Degree of protection Weight

5/6

Mechanical Setting Constant Voltage and Temperature Maximum Minimum Operations @ Rated Current (Resistive) Unpowered Input to Contacts Between Open Contacts

Standard version Storage Operation

°C °C grams

Magnecraft Solution Guide 105A


www.magnecraft.com

847-441-2540

Optional Panel Adapter (16-788C1) See Section 3 p.18

821

822

Standard Part Numbers Part Number 821TD10H-UNI 822TD10H-UNI

Input Voltage 12...240 VAC/VDC 12...240 VAC/VDC

Timing Range 0.1s...10d 0.1s...10d

BOLD-FACED PART NUMBERS ARE NORMALLY STOCKED Functions Available Contact Configuration Rated Load Current A,B,C,D,E,F,G,H,I,J SPDT 15 Amps A,B,C,D,E,F,G,H,I,J DPDT 15 Amps

FUNCTION DEFINITIONS See Section 5 p.3

Series 821 = SPDT 822 = DPDT

0.63 (16)

Relay Style TD - Time Delay

1.35 (34.2)

Number of Functions 10H = 10 Functions

2.6 MAX (65)

0.7 (17.6)

Input Voltage UNI = 12...240 VAC/VDC

0.6 (14.2)

0.13 (3.4)

SECTION 5

Part Number Builder

0.2 (5)

3.5 (90)

1.8 (45.3)

INPUT VOLTAGE Un + -

1.4 (35)

EXTERNAL 0.7 CONTROL (16.71) SWITCH A1 S A2

2.7 (67.5) 0.3 (7.4)

INPUT VOLTAGE Un + A1 S A2 R 25 26 28

R

WIRING DIAGRAMS

0.236 (6)

0.6 (16)

INPUT VOLTAGE Un + A1 S A2

INPUT15 16 18 VOLTAGE 821TD10H-UNI Un + -

EXTERNAL CONTROL SWITCH

A1 S A2 R 25 26 28

1.3 (34)

Magnecraft Solution Guide 105A

R

R

R

822TD10H-UNI

15 - COMMON 16 - NORMALLY CLOSED 18 - NORMALLY OPEN 25 - COMMON 26 - NORMALLY CLOSED 28 - NORMALLY OPEN

15 16 18

15 16 18

821TD10H-UNI

822TD10H-UNI

15 - COMMON

15 16 18

5/7


831 Voltage Sensing Relay/SPDT 15 Amp Rating Input Indication Green LED

Output Indication Red LED

Umax Time Setting Umin

Supply Terminals UL Listed File No. E234203

WHITE

Output Terminals

WHITE

DIN Mount

General Specifications Output Characteristics Number and type of Contacts Contact Material Current rating Switching voltage

SECTION 5

Minimum Switching Requirement Indication Input/Sensing Characteristics Voltage Range Absolute Input Voltage Maximum Upper Sensing Voltage Range Lower Sensing Voltage Range Maximum consumption Indication Timing Characteristics Time Scales Time Ranges Available Tolerance Repeatability Operate Time Release Time Performance Characteristics Electrical Life Mechanical Life Dielectric strength Terminal Wire Capacity Terminal Torque (maximum) Environment Product certifications Ambient air temperature around the device Degree of protection Weight

5/8

(UL 508) 831VS-120A SPDT Silver Alloy 15 240 AC, 50/60 Hz 24 DC 1/2 @ 120VAC 1 @ 240 VAC B300 100 Red

831VS-240A SPDT Silver Alloy 15 240 AC, 50/60 Hz 24 DC 1/2 @ 120VAC 1 @ 240 VAC B300 100 Red

120 AC 200 AC 80….150 AC 30….99 1.2 Green

240 AC 280 AC 160….276 AC 30….99 1.2 Green

sec % % ms ms

1 0….10 5 1 25 20

1 0….10 5 1 25 20

V V AWG (mm2) in lb (Nm)

100,000 10,000,000 2500 AC 1000 AC 14 (2.1) 7.1 (0.8)

100,000 10,000,000 2500 AC 1000 AC 14 (2.1) 7.1 (0.8)

UL, CE -30…+70 -20…+55 IP 20 71

UL, CE -30…+70 -20…+55 IP 20 71

Units @ 240 VAC, 24 VDC

A V V HP HP Pilot Duty mA Blinks = Timing On = Energized

LED

LED

AC/DC

Mechanical Setting Constant Voltage and Temperature Maximum Maximum Operations @ Rated Current (Resistive) Unpowered Input to Contacts Between Open Contacts

Standard version Storage Operation

V V V % VA

°C °C grams

Magnecraft Solution Guide 105A


www.magnecraft.com

847-441-2540

The 831 voltage sensor is a single phase AC voltage sensing device that is capable of monitoring and reacting to over and under voltage conditions. This product is designed to be wired across terminals A1 and A2 with the voltage that is being monitored. The two LED lamps indicate both when the input voltage is present (Green LED) and also when the output is energized (Red LED). The Umax dial is used to set the upper trip-point for the voltage sensor. The Umin dial is a percentage of the Umax dial and is used to set the lower trip-point for the voltage sensor. The timing dial is used to delay the transfer of the contacts, from 0 to 10 seconds, when a set point has been violated.

Optional Panel Adapter (16-788C1) See Section 3 p.18

Standard Part Numbers Part Number 831VS-120A

Input Voltage 120 VAC

Timing Range 0s...10s

831VS-240A

240 VAC

0s...10s

BOLD-FACED PART NUMBERS ARE NORMALLY STOCKED Sensing Voltage Range Contact Configuration Rated Load Current Upper: 80...150 VAC SPDT 15 Amps Lower: 30...99% Upper: 160...276 VAC SPDT 15 Amps Lower: 30...99%

Part Number Builder

0.63 (16)

1.35 (34.2)

Relay Style VS = Voltage Sensor

2.6 MAX (65)

Input Voltage 120A = 120 VAC 240A = 240 VAC

0.7 (17.6)

0.6 (14.2)

0.13 (3.4)

SECTION 5

Series 831 = SPDT

WIRING DIAGRAM INPUT VOLTAGE

0.2 (5)

3.5 (90)

1.8 (45.3)

Un +

A1

A2

1.4 (35)

2.7 (67.5) 0.3 (7.4)

15

0.236 (6)

Magnecraft Solution Guide 105A

0.6 (16)

16

18

15 - COMMON 16 - NORMALLY CLOSED 18 - NORMALLY OPEN

5/9


Advantages of the 841 Current Sensing Relay

Output Indication Red LED Light. Input Indication Green LED Light. Current Sensing Adjustment Knob Sense Anywhere from 10% to 100% of the Rated Sensing Current.

Time delay Delay the Transfer of Contacts from 0 to 10 Secs.

SECTION 55 SECTION

Input Terminals Accepts up to a 14 AWG Wire.

DIN Rail Mounting Mounts Directly On a DIN Rail.

5/10

Magnecraft Solution Guide 105A


The 841 Current Sensor Series is a complete current sensing solution in one modular package which mounts directly to a DIN rail. This product allows the user to monitor the current of one circuit (1 to 8 amps) and switch another circuit in case of an over current or under current condition. The built in time delay feature allows the user to accurately switch the output anytime between 0 to 10 seconds after the preset current monitoring condition is violated. Also, the 841 has the capability to extend the sensing range up to 600 A through the use of current transformers.

Solid State Circuitry Used for Sensing and Timing Control.

• The variable trip point feature allows the user to accurately sense over/under loads. • Offers a “one stop solution” for your power management system.

• The Green LED is on when power is applied to the input terminals. The Red LED blinks during time-out, and is ON when the output is generized. • Color and appearance designed for high visibility in all environments. Output Terminals Accepts up to a 14 AWG wire.

SECTION 5

• Two LED status indicators; indicate status at a glance.

• The wide input voltage range of 24 to 240 AC enables the device to work with all popular AC voltages. • Only 17.5 mm wide making it ideal for tight spaces. • Engineering availability allows for customized relay solutions.

Optional Panel Adapter (16-788C1) See Section 3 p.18

www.magnecraft.com Magnecraft Solution Guide 105A

847-441-2540

5/11


841 Current Sensing Relay/SPDT 15 Amp Rating Input Indication Green LED

Output Indication Red LED

Current Sensing Adjustment Knob Time Delay

Supply Terminals

WHITE

UL Listed File No. E234203

Output Terminals

WHITE

DIN Rail Mounting

General Specifications Output Characteristics Number and type of Contacts Contact Material Current rating Switching voltage

841CS1-UNI SPDT Silver Alloy 15 240 AC, 50/60 Hz 24 DC 1/2 @ 120VAC 1 @ 240 VAC B300 100 Red

841CS2-UNI SPDT Silver Alloy 15 240 AC, 50/60 Hz 24 DC 1/2 @ 120VAC 1 @ 240 VAC B300 100 Red

841CS5-UNI SPDT Silver Alloy 15 240 AC, 50/60 Hz 24 DC 1/2 @ 120VAC 1 @ 240 VAC B300 100 Red

841CS8-UNI SPDT Silver Alloy 15 240 AC, 50/60 Hz 24 DC 1/2 @ 120VAC 1 @ 240 VAC B300 100 Red

V VA

24….240 AC 1.5 Green

24….240 AC 1.5 Green

24….240 AC 1.5 Green

24….240 AC 1.5 Green

Sensing Characteristics Sensing Range

A

0.1….1

0.2….2

0.5….5

0.8….8

Timing Characteristics Time Scales Time Ranges Available Tolerance Repeatability

sec % %

1 0….10 5 1

1 0….10 5 1

1 0….10 5 1

1 0….10 5 1

ms ms

25 20

25 20

25 20

25 20

V V AWG (mm2) in lb (Nm)

100,000 10,000,000 2500 AC 1000 AC 14 (2.1) 7.1 (0.8)

100,000 10,000,000 2500 AC 1000 AC 14 (2.1) 7.1 (0.8)

100,000 10,000,000 2500 AC 1000 AC 14 (2.1) 7.1 (0.8)

100,000 10,000,000 2500 AC 1000 AC 14 (2.1) 7.1 (0.8)

UL, CE -30…+70 -20…+55 IP 20 60

UL, CE -30…+70 -20…+55 IP 20 60

UL, CE -30…+70 -20…+55 IP 20 60

UL, CE -30…+70 -20…+55 IP 20 60

Minimum Switching Requirement Indication

SECTION 5

Input Characteristics Voltage Range Maximum consumption Indication

Operate Time Release Time Performance Characteristics Electrical Life Mechanical Life Dielectric strength Terminal Wire Capacity Terminal Torque (maximum) Environment Product certifications Ambient air temperature around the device Degree of protection Weight

5/12

(UL 508) Units

@ 240 VAC, 24 VDC

LED

LED

Mechanical Setting Constant Voltage and Temperature Maximum Maximum Operations @ Rated Current (Resistive) Unpowered Input to Contacts Between Open Contacts

Standard version Storage Operation

A V V HP HP Pilot Duty mA Blinks = Timing On = Energized

°C °C grams

Magnecraft Solution Guide 105A


www.magnecraft.com

847-441-2540

Optional Panel Adapter (16-788C1) See Section 3 p.18

Standard Part Numbers Part Number 841CS1-UNI 841CS2-UNI 841CS5-UNI 841CS8-UNI

Input Voltage 24...240 VAC 24...240 VAC 24...240 VAC 24...240 VAC

Timing Range 0.1s...10s 0.1s...10s 0.1s...10s 0.1s...10s

BOLD-FACED PART NUMBERS ARE NORMALLY STOCKED Sensing Current Range Contact Configuration Rated Load Current 0.1...1A SPDT 15 Amps 0.2...2A SPDT 15 Amps 0.5...5A SPDT 15 Amps 0.8...8A SPDT 15 Amps

Part Number Builder

0.63 (16)

Relay Style CS = Current Sensor

1.35 (34.2)

Sensing Current 1 = 0.1...1 Amp 2 = 0.2...2 Amp 5 = 0.5...5 Amp 8 = 0.8...8 Amp

2.6 MAX (65)

0.7 (17.6) 0.13 (3.4)

Input Voltage UNI = 24...240 VAC

0.6 (14.2)

0.2 (5)

3.5 (90)

1.8 (45.3)

1.4 (35)

0.3 (7.4)

Magnecraft Solution Guide 105A

WIRING DIAGRAM

INPUT VOLTAGE

2.7 (67.5)

0.236 (6)

SECTION 5

Series 841 = SPDT

0.6 (16)

SENSING CIRCUIT

A1

B1

A2

15

16

18

15 - COMMON 16 - NORMALLY CLOSED 18 - NORMALLY OPEN

5/13


Advantages of the TDR782 Time Delay Relay

Time Setting Select Between 7 Different Time Scales.

Marked with Both IEC and NEMA Markings Universal Socket Compatibility.

SECTION 5

Socket Compatible Mounts Directly On a DIN Rail or Panel.

Time Adjustment Dial Fine Tune the Time Setting.

Mating Hold-Down Clip Available Secures Relay to Socket.

Output Indication Status at a Glance.

Excellent Immunity to Interference Conforms to IEC 61812-1/A11. Input Indication Status at a Glance.

5/14

Magnecraft Solution Guide 105A


The miniature TDR782 series is a single-function, single-voltage time delay relay with multiple time ranges for the ultimate in packaging the most within the smallest space possible in a panel or on the DIN rail. The TDR782 features a screw driver adjustable knob which allows the user to choose 1 of 7 timing ranges and a large knob on top for fine tuning the timing setting. This dual adjustment design allows for supreme flexibility and timing accuracy. The dual LEDs allow the user to know when power is present at the coil and when the output is energized. When mated with the Magnecraft sockets and accessories, these ROHS compliant timers provide a complete modular system that will meet all your control relay requirements in a package that is both visually appealing and functionally outstanding.

• • • • • •

Offers a “one stop solution” for your power management system. Available as a DPDT and 4PDT to meet your individual needs. Switching capabilities of either 3 or 5 amps. The two LED status indicators; indicate status at a glance. Color and appearance designed to high visibility in all environments. Engineering availability allows for customized control system solutions.

www.magnecraft.com Magnecraft Solution Guide 105A

SECTION 5

The Complete System Solution!

847-441-2540

5/15


TDR782 Time Delay Relay/DPDT, 4PDT, 3 or 5 Amp Rating

Socket Compatible

WHITE

Time Adjustment Dial

UL Recognized File No. E191122

Input Indication Output Indication

General Specifications Output Characteristics Number and type of Contacts Contact Material Current rating Maximum permissible current Minimum Switching Requirement Indication

(UL 508) Units A A mA On = Energized

< 0.01 s LED

Input Characteristics Standard Voltage Operating Range

SECTION 5

Maximum consumption

Indication Timing Characteristics Functions Available Time Scales Time Ranges Available

% of Nominal % of Nominal

LED

24 AC 120 AC 230 AC 12 DC 24 DC

VAC VDC VAC VDC VA VA VA W W

(See page 5/3) sec min hr

Tolerance Repeatability Temperature Drift Reset Time

Mechanical Setting Constant Voltage and Temperature Maximum

% % % / °C ms

Performance Characteristics Electrical Life Mechanical Life Dielectric strength

Operations @ Rated Current Unpowered Input to Contacts

(Resistive)

Environment Product certifications Ambient air temperature around the device Degree of protection Weight

5/16

Standard version Storage Operation

V

°C °C grams

TDR782XBX DPDT Silver Alloy 5 10 100 Amber

TDR782XDX 4PDT Silver Alloy 3 10 100 Amber

24, 120, 230 12, 24 85% to 115% 90% to 110% 1.7 2.6 3 1.5 1.2 Green

24, 120, 230 12, 24 85% to 115% 90% to 110% 1.7 2.6 3 1.5 1.2 Green

A (On Delay) 7 0.1….1 1….10 0.1….1 1….10 0.1….1 1….10 10….100 5 0.5 0.05 50

A (On Delay) 7 0.1….1 1….10 0.1….1 1….10 0.1….1 1….10 10….100 5 0.5 0.05 50

100,000 10,000,000 2000 AC

100,000 10,000,000 2000 AC

UR, CE, CSA -40…+70 -20…+60 IP 50 43

UR, CE, CSA -40…+70 -20…+60 IP 50 43

Magnecraft Solution Guide 105A


www.magnecraft.com Function

Operation

A.

When the input voltage U is applied, timing delay t begins. Relay contacts R change state after time delay is complete. Contacts return to their shelf state when power U is removed. Control switch is not used in this mode.

ON DELAY Power On

847-441-2540

Timing Chart

TDR782 Relay with the 70-782EL14-1 Socket

U t

R

t

Standard Part Numbers Input Voltage

BOLD-FACED PART NUMBERS ARE NORMALLY STOCKED Functions Available Contact Configuration Rated Load Current

Timing Range

TDR782XBXA-12D TDR782XBXA-24D TDR782XBXA-24A TDR782XBXA-110A TDR782XBXA-230A

12 VDC 24 VDC 24VAC 110 VAC 230 VAC

0.1s 0.1s 0.1s 0.1s 0.1s

to to to to to

100h 100h 100h 100h 100h

A A A A A

(On (On (On (On (On

Delay) Delay) Delay) Delay) Delay)

DPDT DPDT DPDT DPDT DPDT

5 5 5 5 5

Amps Amps Amps Amps Amps

TDR782XDXA-12D TDR782XDXA-24D TDR782XDXA-24A TDR782XDXA-110A TDR782XDXA-230A

12 VDC 24 VDC 24VAC 110 VAC 230 VAC

0.1s 0.1s 0.1s 0.1s 0.1s

to to to to to

100h 100h 100h 100h 100h

A A A A A

(On (On (On (On (On

Delay) Delay) Delay) Delay) Delay)

4PDT 4PDT 4PDT 4PDT 4PDT

3 3 3 3 3

Amps Amps Amps Amps Amps

Part Number Builder Contact Configuration XBX = DPDT XDX = 4PDT

0.8 (21)

1.0 (27)

2

3

4

5

6

7

8

9

10 11

3.5 (89.3)

4

1

2

3

2 41

8

5

6

7

8

12 14

9

10

11

13

5 6 7

R

12

1

4

5

8

14

1.1 (27)

4

1

2

5

8

5

6

9

12

13

14 NEMA

14

WIRING DIAGRAMS 8 TERMINAL SQUARE Bottom View BASE DPDT (ON DELAY) Magnecraft Solution Guide 105A

0.2 (5.6)

1

12

NEMA 13

0.14 (3.5)

TDR782XBX

8 9 10

Un

9

0.74 (19)

14

14 TERMINAL SQUARE BASE 4PDT (ON DELAY)

TDR782XDX 34

70-782EL8-1, 70-782EL14-1 SOCKETS

2.4 (61)

12

13

Input Voltage 12D = 12 VDC 24D = 24 VDC 24A = 24 VAC 110A = 110 VAC 230A = 230 VAC

Other mating sockets see Section 2: 70-782E14-1, 70-782D14-1, 70-461-1, 70-378-1, 70-379-1

NOTE: Terminal size is 0.105 x 0.020 (2.68 x 0.508)

1

– –

Functions A = ON Delay

9

2.6 (6.5) 1.54 (39.1)

SECTION 5

Series TDR782 = 782 Miniature Timer

4 .02 (0.5) 8

12 10 16-TDR782SC Metal Hold-Down Clip

See Section 3 14 p.8-11

13

2.3 NEMA .24 (6.0) (59.4)

.83 (21)

41

11

41

31

21

12

9

12

11

10

9

44

14

44

34

24

14

8

5

8

7

6

5

42

12

42

32

22

12

4

1

4

3

2

1

3.3 (85) 1 5 9

2 6 1.1 (27.9) 10

3

4 3.1

7

8

11

13

.83 (21) .02 (0.5)

1.1 (27.9)

1.5 (38) A2

14 NEMA

.83 (21)

(79)

12

1.4 (35.5)

11

IEC: NEMA:

A1

2.6 INPUT (6.5) 13 1.54 .24 (39.1) (6.0) 14

DPDT

A2

IEC: NEMA:

A1

14 INPUT 13

.24 (6.0)

4PDT

5/17


Advantages of the TDRPRO-5100 Series Time Delay Relays

Output Indication Red LED Light.

Input Indication Green LED Light.

Panel Mount Adapter Included Panel Mountable.

Transparent Cover Dust and Splatter Proof Retains Timer Settings.

SECTION 5

Mating Hold-Down Clip Available Secures Relay to Socket.

Industry Standard 8 or 11 Pin Octal Socket Compatible.

Finger Safe Sockets Available Protect Operators from Live Circuits.

Flexible Mounting Mounts Directly on a DIN Rail or Panel.

5/18 Magnecraft Solution Guide 105A


The Complete System Solution!

*See Application Data (p. 5/2-5/3) for Function Definition.

• Offers a “one stop solution” for your power management system. • Several configurations available to meet your individual needs.

SECTION 5

The TDRPRO-5100 Series is a programmable multi-function, multi-voltage time delay relay with multiple time ranges for the ultimate in flexibility. The TDRPRO-5100 features thumb wheel adjustment for impeccable accuracy. The two indicator LEDs allow the user to know when power is present at the coil, output is energized or if the relay is performing one of its 10 timing functions.

• Switching capabilities up to 12 amps. • The broad timing range meets most timing requirements. • The 12 to 240 VAC/VDC input voltage range enables this timer to work with all popular voltages. • The two LED status indicators; indicate status at a glance. The green LED is on when power is applied to the input terminals. The red LED blinks during timeout and is on when the output is energized. • The tamper proof dust cover retains the settings and keeps the dust out. • The thumb wheel adjustment for function and timing ensures accuracy and eliminates mechanical deviation. • Color and appearance designed to high visibility in all environments. • Engineering availability allows for customized control system solutions.

www.magnecraft.com Magnecraft Solution Guide 105A

847-441-2540

5/19


TDRPRO-5100 Series Time Delay Relays/SPDT, DPDT 12 Amp Rating Output Indication Red LED Panel Mount Adapter Included

Input Indication Green LED

UL Recognized File No. E43641

General Specifications Output Characteristics Number and type of Contacts Contact Material Current rating Switching voltage

@ 240 VAC, 30 VDC

Minimum Switching Requirement Indication Input Characteristics Voltage Range Operating Range Maximum consumption

SECTION 5

LED

Timing Characteristics Functions Available Time Scales Time Ranges Available

A V V HP HP Pilot Duty mA Blinks = Timing On = Energized

LED

% of Nominal

Indication

AC DC

0.1 sec sec 0.1 min min 0.1 hr hr 10 hr % % ms ms ms

Operations @ Rated Current (Resistive) Unpowered Input to Contacts Between Open Contacts

Environment Product certifications Ambient air temperature around the device Degree of protection Weight

TDRPRO-5101 TDRPRO-5001

TDRPRO-5102 TDRPRO-5002

DPDT Silver Alloy 12 240 AC, 50/60 Hz 30 DC 1/3 @ 120VAC 1/2 @ 240 VAC B300 100 Red

SPDT Silver Alloy 12 240 AC, 50/60 Hz 30 DC 1/3 @ 120VAC 1/2 @ 240 VAC B300 100 Red

DPDT Silver Alloy 12 240 AC, 50/60 Hz 30 DC 1/3 @ 120VAC 1/2 @ 240 VAC B300 100 Red

12….240 85% to 115% 2.5 2 Green

12….240 85% to 115% 2.5 2 Green

12….240 85% to 115% 2.5 2 Green

A,B,C,D,E,F,G,H,I,J 7 0….999 0….999 0….999 0….999 0….999 0….999 0….999 0 0.1 25 25 150

A,B,C,D,E,F,G,H,I,J 7 0….999 0….999 0….999 0….999 0….999 0….999 0….999 0 0.1 25 25 150

A,B,C 7 0….999 0….999 0….999 0….999 0….999 0….999 0….999 0 0.1 25 25 150

100,000 10,000,000 2500 AC 1000 AC

100,000 10,000,000 2500 AC 1000 AC

100,000 10,000,000 2500 AC 1000 AC

UR, CE -30…+70 -20…+55 IP 40 133

UR, CE -30…+70 -20…+55 IP 40 133

UR, CE -30…+70 -20…+55 IP 40 133

VA W

Mechanical Setting Constant Voltage and Temperature Maximum Maximum

Performance Characteristics Electrical Life Mechanical Life Dielectric strength

TDRPRO-5100 TDRPRO-5000

VAC / VDC

(See page 5/3)

Tolerance Repeatability Operate Time Release Time Reset Time

V V

Standard version Storage Operation

°C °C grams

EXTERNAL CONTROL SWITCH 5

4

6

7

3 2

5/20

New Part Number: Legacy Part Number: Units

(UL 508)

1 11

WIRING DIAGRAMS 4

8

3

9 10

2

INPUT OFF DELAY

5100

EXTERNAL CONTROL SWITCH

5 6

8

INPUT

5 6

2

7 1

4 3

5101

7 1

8

5102

INPUT Magnecraft Solution Guide 105A

ON DELAY


www.magnecraft.com

847-441-2540

TDRPRO Relay with the 70-750DL8-1 Socket

Standard Part Numbers New Part Number TDRPRO-5100 TDRPRO-5101 TDRPRO-5102

Supercedes TDRPRO-5000 TDRPRO-5001 TDRPRO-5002

Input Voltage 12...240 VAC/VDC 12...240 VAC/VDC 12...240 VAC/VDC

BOLD-FACED PART NUMBERS ARE NORMALLY STOCKED Functions Available Contact Configuration Rated Load Current A,B,C,D,E,F,G,H,I,J DPDT 12 Amps A,B,C,D,E,F,G,H,I,J SPDT 12 Amps A,B,C DPDT 12 Amps

Timing Range 0.1s...9990h 0.1s...9990h 0.1s...9990h

FUNCTION DEFINITIONS See Section 5 p.3

Part Number Builder Series TDRPRO = 48 X 48 Time Delay Relay

Contact Configuration/ # of Functions 5100 = DPDT, 10 Functions 5101 = SPDT, 10 Functions 5102 = DPDT, 3 Functions

SECTION 5

1.9 (48)

Other mating sockets see Section 2: 70-750E8-1, 70-750E11-1, 70-169-1, 70-170-1, 70-465-1,70-464-1

1.9 (48)

70-750DL8-1, 70-750DL11-1 SOCKETS 1.45 (37) 2.8 (72)

0.23 (6)

3.0 (76)

11

32

22

24

12

22

8

7

5

1

4

5

24

21

14

31 11

6

8

0.2 (5.1)

2.9 (72) 0.06 (1.52)

0.25 (6.35)

16-TDRPROSC Metal Hold-Down Clip

See Section 3 p.8-11 4.3 (109.2)

Magnecraft Solution Guide 105A

1.5 (38)

1.4 (36)

1.1 (28)

3.18 3 (81)

1.6 (40)

12 4 11

21

1

6

34

14

9

3

1.6 (40) IEC: NEMA:

IEC: NEMA:

A2

INPUT

7

A1

A2

2

10

INPUT

1.2 (30)

A1

INPUT

INPUT

2

1.35 (34.2)

5/21


Advantages of the TDRSOX/SRX Time Delay Relays

Time Adjustment Dial Fine Tune the Time Setting.

Output Indication Red LED Light.

Integrated DIP Switch Simplifies the Programming of the Functions and Timing.

Removable Knob Prevents Tampering.

Input Indication Green LED Light.

SECTION 5

Optional Side and Top Flange Mounting Flexibility in Mounting Techniques.

Socket Compatible Makes for Easy Installation and Replacement.

Flexible Mounting Mounts Directly on a DIN Rail or Panel.

5/22

Magnecraft Solution Guide 105A


The Complete System Solution!

The SOX series features both On Delay and Interval functions, in contrast the SRX series has the capability of handling the Off Delay and Retriggerable One Shot functions. Please see the Application Data at the beginning of this section for a complete description of the above four functions. Combining all of this into one affordable package is the reason Magnecraft continues to be a leader in providing the most comprehensive line of control and timing relays.

SECTION 5

The TDRSOX/SRX series is a dual-function, dual-voltage time delay relay that offers a wide timing range. This cost sensitive timer features DIP switches that allow the user to set the function modes and choose between eight separate time scales. The knob on top is used for fine tuning the time setting. This dual adjustment design allows for supreme flexibility and timing accuracy. The dual LEDs allow the user to know when power is present at the coil and when the output is energized.

• • • • • •

Offers a “one stop solution” for your power management system. Several configurations available to meet your individual needs. Switching capabilities up to 12 amps. The broad timing range meets most timing requirements. Dual voltage coils eliminate the need to specify AC or DC. (AC only for 240). The two LED status indicators; indicate status at a glance. The green LED is on when power is applied to the input terminals. The red LED blinks during timeout and is on when the output is energized. • Integrated DIP switch simplifies the programming of the functions and timing. • Color and appearance designed for high visibility in all environments. • Engineering availability allows for customized control system solutions.

www.magnecraft.com Magnecraft Solution Guide 105A

847-441-2540

5/23


TDRSOX/SRX Time Delay Relays/DPDT 12 Amp Rating C

UL US

UL Listed When Used With Magnecraft Sockets.

UL Recognized File No. E43641

Recessed Potentiometer for Fine Tuning the Timing Setting

Input Indication Green LED

SELECTING TIME RANGES

Output Indication Red LED

TIME RANGE 0.1 sec - 1 sec 1 sec - 10 sec 10 sec - 100 sec 0.1 min - 1 min 1 min - 10 min 10 min - 100 min 0.1 hr - 1 hr 1hr - 10 hr

DIP Switch for Function/Timing WHITE

General Specifications Output Characteristics Number and type of Contacts Contact Material Current rating Switching voltage

Minimum Switching Requirement Indication

12, 24, 120 240 80% to 110% 5 2.5 Green

12, 24, 120 240 80% to 110% 5 2.5 Green

sec sec sec min min min hr hr % % ms ms

A, C 8 0.1….1 1….10 10….100 0.1….1 1….10 10….100 0.1….1 1….10 10 1 150 50

D, E 8 0.1….1 1….10 10….100 0.1….1 1….10 10….100 0.1….1 1….10 10 1 150 50

Operations @ Rated Current (Resistive) Unpowered Input to Contacts Between Open Contacts

V V

100,000 10,000,000 2500 AC 1000 AC

100,000 10,000,000 2500 AC 1000 AC

Standard version Storage Operation

°C °C

UR, CE -20…+85 -20…+55 IP 40 85

UR, CE -20…+85 -20…+55 IP 40 85

@ 240 VAC, 24 VDC

A V V HP HP Pilot Duty mA

LED

SECTION 5

Indication

LED

Environment Product certifications Ambient air temperature around the device Degree of protection Weight

5/24

IV OFF ON OFF ON OFF ON OFF ON

TDRSRX DPDT Silver Alloy 12 240 AC, 50/60 Hz 30 DC 1/3 @ 120VAC 1/2 @ 240 VAC B300 100 Red

% of Nominal

Performance Characteristics Electrical Life Mechanical Life Dielectric strength

III OFF OFF ON ON OFF OFF ON ON

TDRSOX DPDT Silver Alloy 12 240 AC, 50/60 Hz 30 DC 1/3 @ 120VAC 1/2 @ 240 VAC B300 100 Red

Units

Operating Range Maximum consumption

Tolerance Repeatability Reset Time Trigger Pulse Length

II OFF OFF OFF OFF ON ON ON ON

(UL 508)

Input Characteristics Voltage Range

Timing Characteristics Functions Available Time Scales Time Ranges Available

DIGITAL SWITCH POSITION

VAC / VDC VAC AC DC

VA W

(See page 5/3)

Mechanical Setting Constant Voltage and Temperature Maximum Minimum

grams

Magnecraft Solution Guide 105A


TERNAL ONTROL WITCH

www.magnecraft.com

847-441-2540

FUNCTION DEFINITIONS See Section 5 p.3

SELECTING FUNCTION FUNCTION SOX

DIGITAL SWITCH POSITION OFF ON

ON DELAY INTERVAL FUNCTION SRX

OFF ON

TDRSOX/SRXB Standard Part Numbers

TDRSOX/SRXP

BOLD-FACED PART NUMBERS ARE NORMALLY STOCKED Timing Range Contact Configuration Rated Load Current

Part Number

Input Voltage

8 Pin Octal Base - On Delay/Interval TDRSOXP-12V TDRSOXP-24V TDRSOXP-120V TDRSOXP-240A

12 VAC/VDC 24 VAC/VDC 120 VAC/VDC 240 VAC

0.1s...10h 0.1s...10h 0.1s...10h 0.1s...10h

DPDT DPDT DPDT DPDT

12 12 12 12

Amps Amps Amps Amps

11 Pin Octal Base - Off Delay/Retriggerable One Shot TDRSRXP-12V TDRSRXP-24V TDRSRXP-120V TDRSRXP-240A

12 VAC/VDC 24 VAC/VDC 120 VAC/VDC 240 VAC

0.1s...10h 0.1s...10h 0.1s...10h 0.1s...10h

DPDT DPDT DPDT DPDT

12 12 12 12

Amps Amps Amps Amps

8 Blade Square Base - On Delay/Interval TDRSOXB-12V TDRSOXB-24V TDRSOXB-120V TDRSOXB-240A

12 VAC/VDC 24 VAC/VDC 120 VAC/VDC 240 VAC

0.1s...10h 0.1s...10h 0.1s...10h 0.1s...10h

DPDT DPDT DPDT DPDT

12 12 12 12

Amps Amps Amps Amps

11 Blade Square Base - Off Delay/Retriggerable One Shot TDRSRXB-12V TDRSRXB-24V TDRSRXB-120V TDRSRXB-240A

12 VAC/VDC 24 VAC/VDC 120 VAC/VDC 240 VAC

0.1s...10h 0.1s...10h 0.1s...10h 0.1s...10h

DPDT DPDT DPDT DPDT

12 12 12 12

Amps Amps Amps Amps

SECTION 5

OFF DELAY RETRIGGERABLE ONE SHOT

Part Number Builder Function SOX = On Delay/Interval SRX = Off Delay/Retriggerable One Shot

Series TDR = Time Delay Relay

Terminal Style P = Pins Octal B = Blade Square

Input Voltage 12V = 12 VAC/VDC 24V = 24 VAC/VDC 120V = 120 VAC/VDC 240A = 240 VAC

WIRING DIAGRAMS EXTERNAL CONTROL SWITCH

1

4

12 4 14 5 4 37

5 6

3 2

7 1

8

2

SOXP

INPUT

ON DELAY

Magnecraft Solution Guide 105A

32 5 6 7 34

8

9 10

EXTERNAL 3 CONTROL 22 SWITCH 6 24 9

112 21 A 1 11 B SRXP A2 A1 INPUT OFF DELAY NEMA OFF DELAY IEC

EXTERNAL CONTROL SWITCH

1 12 4 4 14 3 7 211

5 6 7

8 A1 A1 INPUT ON DELAY NEMA IEC

3 22 6 24 9 21 B A2

EXTERNAL CONTROL SWITCH

1

2

3

12 4 14

32 5 4 34 3

22 6 5 24

7 11

SOXB

A A1

2

9

6

21 7 8B SRXB A2 INPUT

1

OFF DELAY NEMA ON DELAY IEC

5/25


TDRSOX/SRX Time Delay Relays continued C

UL US

Input Indication Green LED

UL Listed When Used With Magnecraft Sockets.

Recessed Potentiometer for Fine Tuning the Timing Setting

Output Indication Red LED

UL Recognized File No. E43641

DIP Switch for Function/Timing WHITE

NOTE: Terminal size is 0.187 x 0.020 (4.75 x 0.508) 1.42 (36)

2.6 (65)

0.8 (2)

0.7 (17)

1.73 (44)

SECTION 5

TDRSOX/SRXB

3.0 (77)

0.13 (3.3) 3.4 (86) 1.4 (36)

TDRSOX/SRXP

2.6 (65)

0.8 (2.0)

0.7 (17)

1.73 (44)

0.13 (3.3)

Relay Adapters

16-711C1

5/26

Section 3 p.14-16

16-711C4

Section 3 p.14-16 Magnecraft Solution Guide 105A


www.magnecraft.com

TDRSOX/SRXB

847-441-2540

TDRSOX/SRXP

Other mating sockets see Section 2: 70-750E8-1, 70-750E11-1, 70-169-1, 70-170-1, 70-465-1, 70-464-1

6

5

3

2

70-463-1 SOCKET

1.4 (35)

1

1.7 (43)

0.4 (10)

4

1.0 (26)

0.2 (5.1)

B

1.5 (38)

SECTION 5

3.1 (80)

3.0 (76)

A

9

8

7

3.7 (93)

16-1344 Metal Hold-Down Clip See Section 3 p.8-11

1.5 (37)

1.5 (38)

1.4 (36)

1.1 (28)

3.0 (76)

22

11

12

5

1

4

24

21

14

6

8

3

0.2 (5.1)

2.9 (72)

1.6 (40)

4.2 (106)

Magnecraft Solution Guide 105A

24

22

8

7

5

31 11

3.18 (81)

12 4 11

21

1

6

34

14

9

3

1.6 (40) IEC: NEMA:

70-750DL8-1, 70750DL11-1 SOCKETS

32

IEC: NEMA:

A2

INPUT

7

A1

A2

2

10

INPUT

1.2 (30)

A1

INPUT

INPUT

2

1.35 (34.2)

5/27


SECTION 5

Section

5/28

5

C r os s Re fe r e n c e Gu i d e

Magnecraft

Carlo Gavazzi

Finder

Omron

NCC

821TD10H-UNI

EAACT231M EAACT2310H

H3DS-M-L H3DS-S-L H3DS-A-L

DMM-9999M-24M

822TD10H-UNI

EAADT231M EAADT2310H

81.01 81.11 82.01 82.11 82.21 82.31 82.41 87.01 87.11 87.21 87.31 87.41 87.91 82.82 87.02 87.61 87.62 87.82

Magnecraft

NAIS

Finder

Omron

TDR782XBXA-12D

S1DX-A2C

85.02

TDR782XBXA-24D

S1DX-A2C

85.02

TDR782XBXA-24A

S1DX-A2C

85.02

TDR782XBXA-110A

S1DX-A2C

85.02

TDR782XBXA-230A

S1DX-A2C

85.02

H3YN-2 H3YN-21 H3YN-2 H3YN-21 H3YN-2 H3YN-21 H3YN-2 H3YN-21 H3YN-2 H3YN-21

TDR782XDXA-12D

S1DX-A4C

85.04

TDR782XDXA-24D

S1DX-A4C

85.04

TDR782XDXA-24A

S1DX-A4C

85.04

TDR782XDXA-110A

S1DX-A4C

85.04

TDR782XDXA-230A

S1DX-A4C

85.04

H3DE-M-2

H3YN-4 H3YN-41 H3YN-4 H3YN-41 H3YN-4 H3YN-41 H3YN-4 H3YN-41 H3YN-4 H3YN-41

www.magnecraft.com

IDEC

Fuji

Allen Bradley

ST7P-2DE

700HS12

GT5Y-2SN1D24 GT5Y-2SN3D24

ST7P-2DE

700HS12

ST7P-2A

700HS12

GT5Y-2SN3A100 GT5Y-2SN6A100 GT5Y-2SN1A200 GT5Y-2SN3A200 GT5Y-2SN6A200 GT5Y-4SN1D12

ST7P-2A

700HS12

ST7P-2A

700HS12

GT5Y-4SN1D24 GT5Y-4SN3D24 GT5Y-4SN1A100 GT5Y-4SN3A100 GT5Y-4SN6A100

847-441-2540 Magnecraft Solution Guide 105A


Magnecraft

Supercedes Magnecraft

Potter & Brumfield

Square D

Omron

CNM5 CNS-35-96 CNS-35-76

9050JCK70V14

H3CA-A

TDRPRO-5100

TDRPRO-5000

TDRPRO-5101 TDRPRO-5102

TDRPRO-5001 TDRPRO-5102

Magnecraft

Allen Bradley

NCC

IDEC

TDRSOXP-24 TDRSOXP-120 TDRSOXP-240 TDRSRXP-12 TDRSRXP-24 TDRSRXP-120 TDRSOXB-12 TDRSOXB-24 TDRSOXB-120 TDRSRXB-12 TDRSRXB-24 TDRSRXB-120

700HRM12TU24 700HRM12TA17 700HRM12TA17

T2K-xxxxx-466 T2K-xxxxx-467/462 T2K-xxxxx-461

RTE-P1AD24 RTE-P1AF20 RTE-P1AF20 RTE-P2D12 RTE-P2AD24 RTE-P1AF20 RTE-B1D12 RTE-B1AD24 RTE-B1AF20 RTE-B2D12 RTE-B2AD24 RTE-B2AF20

H3CA-8H H3CA-8

SECTION 5

CN1 CNS-35-92 CNS-35-72

www.magnecraft.com Magnecraft Solution Guide 105A

847-441-2540

5/29


www.magnecraft.com

847-441-2540

SECTION 5

NOTES:

5/30

Magnecraft Solution Guide 105A


Turn static files into dynamic content formats.

Create a flipbook
Issuu converts static files into: digital portfolios, online yearbooks, online catalogs, digital photo albums and more. Sign up and create your flipbook.