Telect Data Center Rack

Page 1

data center rack Ordering & Installation Guide

we simplify networks. TM


we simplify networks

racks


tough secure cool

Applies to : DR750-84430 :: DR750-84424 :: DR-84830 :: DR-84824 :: DR-84442 :: DR-84436 :: DR-84430 :: DR-84424

DR2000-84442 :: DR2000-84436 :: DR2000-84430 :: DR2000-84424 :: DR-84842 :: DR-84836 :: DR1250-84430 DR1250-84424 :: DR2000-84842 :: DR2000-84836 :: DR2000-84830 :: DR2000-84824 :: DR1250-84842 :: DR750-84830

DR1250-84836 :: DR1250-84830 :: DR1250-84824 :: DR1250-84442 :: DR1250-84436 :: DR750-84842 DR750-84442 :: DR750-84436 DR750-84430 :: DR750-84842

Patents Pending

:: DR750-84824


data center rack

we’re tough Telect’s new Earthquake-Safe Data Center Rack is a product to take pride in. Through its strength, seismic security and sheer good looks, you’ll be sure to demonstrate to the world that you do excellent work. Imagine walking into a data center and seeing your name displayed proudly and prominently amongst rows and rows of blank, no name racks. Telect wants you to serve the cloud in style. Through its rack-customizing program, you’ll be able to get private labels, custom color accents and unique configurations.

© Telect, Inc., All Rights Reserved, 142359 A0 1.509.926.6000 :: telect.com


data center rack

we’re secure Primary Benefits • Zone 4 certified • 2,000 lbs., 1,250 lbs. and 750 lbs. • Industry leading airflow doors above 80% • Compatible with OEM cooling solutions • Highly versatile and configurable • Ensuring safety of core equipment • Adjustable front and rear rails • Flexible equipment mounting • Robust design ensures reliable, long-term performance • Compatible with: - standard rack-mount equipment - a wide range of cable management solutions - Telect’s energy management strip

REV

ECO

DESCRIPTION

drawing no

customer drawing

End Panel Assem

USER MANUAL VIEWS

DATE

BY rev

A0

units

inch

designed by

B. Fuller drawn by

G. HILBERT

© Telect, Inc., All Rights Reserved, 142359 A0 1.509.926.6000 :: telect.com

date

6/2/2011 date

3/20/2012


data center rack

we’re cool The new rack offers earthquake protection accompanied by more options for cable management, more working room than other deployed cabinets, and industry leading airflow. The Telect team worked to ensure that the new cabinet would exceed current specifications and projected future requirements. Tested in switch offices and by stringent independent labs. This highly durable and versatile platform is sure not to disappoint the most veteran telecom engineers. Designed to accommodate servers, routers, batteries, and other crucial network components, each cabinet is independently Zone 4 seismic certified to hold up to 2,000 lbs., 1,250 lbs. and 750 lbs. of network equipment.

Š Telect, Inc., All Rights Reserved, 142359 A0 1.509.926.6000 :: telect.com


Data Center Racks Racks :: tough. secure. cool.

Ordering Guide 1.1 Introduction The ultimate equipment rack solution for core data center equipment, Telect’s Data Center Racks provide a seismic certified, highly durable and versatile platform for mounting equipment such as servers, routers, batteries and other crucial network components. The Data Center Rack features enhanced durability and the ability to hold a broad range of network equipment. Each rack is independently Zone 4 seismic certified to hold up to 2,000 lbs,1250 lbs and 750 lbs of network equipment. Battery shelves are also compatible, making the rack ideal for core equipment or as a heavy duty battery rack.

‣ REV

Design the perfect rack

ECO

DESCRIPTION

drawing no

customer drawing

End Panel Assem

USER MANUAL VIEWS

© Telect, Inc., All Rights Reserved, 142359 A0 1.509.926.6000 :: telect.com

DATE

BY rev

A0

units

inch

designed by

6/2/2011

drawn by

date

G. HILBERT

1

date

B. Fuller

3/20/2012

toleranc

.X .X .X


Data Center Racks

Racks :: 750 lb earthquake safe

1.3 750 Data Center Rack Rack • 84ʺ fixed height • 24ʺ & 28ʺ width (supporting 19ʺ & 23ʺ rack, respectively) • 24ʺ, 30ʺ, 36ʺ, 42ʺ depth

Panels • Removable side panels • Six-post design, seismic Zone 4 rating, 750 lb certified • Multiple side entry points • Compatible with all standard rack-mount equipment

Options • Adjustable cable management panels −6ʺ W x 24ʺ- 42ʺ D panel −10ʺ W x 24ʺ- 42ʺ D panel • Power accessories:

−Grounding package—wiring, buss bar, vertical power lacing bar −Vertical lacing bar for power cables −PDU mounting

Mounting

750 lb Rack with cable management

• Optional, adjustable front and rear mounting rails • Isolation pad

1.4 Specifications Item

Specification

Seismic certification

750 lbs (340 kg)

Physical specs, rack for 23" equipment mtg.

28ʺ W x 42" D x 84ʺ H (711 mm x 1067 mm x 2134 mm) 98 lbs (44kg)- 380 lbs (172 kg) *Additional Depths available

Physical specs, rack for 19" equipment mtg.

24ʺ W x 42ʺ D x 84ʺ H (610 mm x 2134 mm) 90 lbs (41 kg) - 340 lbs (154 kg) *Additional Depths available

Hole spacing

EIA Wide RMU=1-¾ʺ (1/2ʺ, 1-¼ʺ), 44 RU EIA Narrow RMU=1-¾ʺ (1/2ʺ, 5/8ʺ, 5/8ʺ), 44 RU Universal RMU=1/2ʺ, 1/2ʺ, 1/2ʺ, 44 RU

Color

Standard black, others available

Compliance

GR-63-CORE, NEBS compliant, Zone 4 certified.

NEBS tested Zone 4. Earthquake tested and ready if Seismic Anchor Kit is installed properly © Telect, Inc., All Rights Reserved, 142359 A0 1.509.926.6000 :: telect.com

2


Data Center Racks Racks :: tough. secure. cool.

Figure 1 - 19"Dimensions for 750 lb and part number DR750-84442, Front and Side View Diagram

Weight

Part Number

Dimensions

B

750 lb

DR750-84842

28.000

A

750 lb

Š Telect, Inc., All Rights Reserved, 142359 A0 1.509.926.6000 :: telect.com

DR750-84842

3

23.500


Data Center Racks

Racks :: 750 lb earthquake safe Design the perfect rack

Pick Model

Data Rack DR750

Model

84842 84836 84830 84824 84442 84436 84430 84424

A

B C D E F

G H

Dimensions

End Panel

Width

Depth

DREP-42

28"

42"

DREP-36

28"

36"

DREP-30

28"

30"

DREP-24

28"

24"

24"

42"

24"

36"

24"

30"

24"

24"

Data Rack Mounting Rails 44RU DR-MRCGP DR-MRGP-A DR-MRCG-A DR-MRCGP-A DR-MRGP-A DR-MRCG-A

Models

DR-MRGCTZ DR-MRGTTZ DR-MRGCTZP

ACCE-DR10 ACCE-DR6TS ACCE-DR10TS ACCE-DR6TD ACCE-DR10TD

12-24 EIA-D (Qty 2) 23"-19" Dimensions CN/12-24

All Models

12-24/12-24

All Models

Models

ACCE-DR6

Cage Nut EIA-D (Qty 2) 23"-19"

All Models

Adustable Cable Manager

CN/12-24 Plated 12-24/12-24 Plated Dimensions

All Models

6" Front and Rear Only

All Models

10" Front and Rear Only

C, D, G, H

6" Through 24"-30" W/ HW (Qty2)

C, D, G, H

10" Through 24"-30" W/ HW (Qty2)

A, B, E, F

6" Through 36"-42" W/ HW (Qty2)

A, B, E, F

Š Telect, Inc., All Rights Reserved, 142359 A0 1.509.926.6000 :: telect.com

24"

12-24 Tapped Zinc Plated EIA-D (Qty 2) 23"-19"

A, B, C, D

All Models

30"

Cage Nut Zinc Plated EIA-D (Qty 2) 23"-19"

A, B, C, D

DR-MRGTTZP

D, H

36"

Cage Nut EIA-D (Qty 2) 23"-19"

A, B, C, D

Models

C, G

42"

12-24 Tapped Zinc Plated EIA-D (Qty 2) 23"-19"

A, B, C, D

Data Rack Mounting Rail EIA D

B, F

Cage Nut Zinc Plated EIA-D (Qty 2)

All Models

A, B, C, D

A, E

Depth

Dimensions

All Models

DR-MRG-A

Models

10" Through 36"-42" W/ HW (Qty2) 4


Data Center Racks Racks :: tough. secure. cool. Part Number DRDP-28 DRDBP-28 DRDDP-28 DRDDBP-28 DRDP-24 DRDBP-24 DRDDP-24

Model

A, B, C, D A, B, C, D A, B, C, D A, B, C, D E, F, G, H E, F, G, H E, F, G, H

DRDDBP-24

E, F, G, H

Part Numbers

Model

DR-TC28 DR-HGB-23 DR-TC24 DR-TCC DR-TCB DRMR-AC DRMR-ACD DR-GANG DR-HGB-19 DR-ANCS DR-CN50 DR-CN100 04500-50 04500-100

DRISO-2442 DRISO-2436 DRISO-2430 DRISO-2424 ACCE-DR6ISO ACCE-DR10ISO

Black Perforated Door

28"

Chrome Perforated Dual Door

28"

Black Perforated Dual Door

24"

Chrome Perforated Door

24"

Black Perforated Door

24"

Chrome Perforated Dual Door

24"

Black Perforated Dual Door Product Data Rack Top Cap 28" Horizontal Ground Bar 23" Data Rack Top Cap 24"

All Models

Data Rack Top Cap Center Label Holder

All Models

Data Rack Top Cap Border Qty 2

All Models

Data Rack AC Power Bracket

All Models

Data Rack AC Power Bracket Dual

All Models

Data Rack Ganging Hardware

All Models

Horizontal Ground Bar 19"

All Models

Seismic Anchor Data Center Rack

All Models

Data Rack Cage Nut Qty 50

All Models

Data Rack Cage Nut Qty 100

All Models

12-24 Mounting Screws Qty 50

All Models

Model

DRISO-2824

Chrome Perforated Door

28"

E, F, G, H

Isolation Pad

DRISO-2830

28"

A, B, C, D

All Models

DRISO-2836

Doors

A, B, C, D

DR-CDS

DRISO-2842

Width

12-24 Mounting Screws Cabinet Duct Spacer

A B C D E F

G H

All Models All Models

© Telect, Inc., All Rights Reserved, 142359 A0 1.509.926.6000 :: telect.com

5

Width

Depth

28ʺ

42ʺ

28ʺ

36ʺ

28ʺ

30ʺ

28ʺ

24ʺ

24"

42"

24"

36"

24"

30"

24"

24"

6"

6" for ACC-DR6

10"

6" for ACC-DR10


Data Center Racks

Racks :: 1250 lb earthquake safe

1.5 1250 Data Center Rack Rack • 84ʺ fixed height • 24ʺ & 28ʺ width (supporting 19ʺ & 23ʺ rack, respectively) • 24ʺ, 30ʺ, 36ʺ, 42ʺ depth

Panels • Removable side panels • Six-post design, seismic Zone 4 rating, 1250 lb certified • Multiple side entry points • Compatible with all standard rack-mount equipment

Options • Adjustable cable management panels −6ʺ W x 24ʺ- 42ʺ D panel −10ʺ W x 24ʺ- 42ʺ D panel • Power accessories:

−Grounding package—wiring, buss bar, vertical power lacing bar −Vertical lacing bar for power cables −PDU mounting

Mounting • Optional, adjustable front and rear mounting rails

Rear View, Seismic Data CenterRack

• Isolation pad

1.6 Specifications Item

Specification

Seismic certification

1,250 lbs (567 kg)

Physical specs, rack for 23" equipment mtg.

28ʺ W x 42ʺ D x 84ʺ H (711 mm x 1067 mm x 2134 mm) 98 lbs (44kg) - 380 lbs (172 kg) *Additional Depths available

Physical specs, rack for 19" equipment mtg.

24" W x 42" D x 84" H (610 mm x 2134 mm) 90 lbs (41 kg) - 340 lbs (154 kg) *Additional Depths available

Hole spacing

EIA Wide RMU=1-¾ʺ (1/2ʺ, 1-¼ʺ), 44 RU EIA Narrow RMU=1-¾ʺ (1/2ʺ, 5/8ʺ, 5/8ʺ), 44 RU Universal RMU=1/2ʺ, 1/2ʺ, 1/2ʺ, 44 RU

Color

Standard black, others available

Compliance

GR-63-CORE, NEBS compliant, Zone 4 certified.

NEBS tested Zone 4. Earthquake tested and ready if Seismic Anchor Kit is installed properly © Telect, Inc., All Rights Reserved, 142359 A0 1.509.926.6000 :: telect.com

6


Data Center Racks Racks :: tough. secure. cool.

Figure 2 - 19ʺ Dimensions for 1250 lb and part number DR1250-84442, Front and Side View Diagram

Weight

Part Number

Dimensions

B

1250 lb

DR1250-84842

28.000

A

1250 lb

© Telect, Inc., All Rights Reserved, 142359 A0 1.509.926.6000 :: telect.com

DR1250-84842

7

23.500


Data Center Racks

Racks :: 1250 lb earthquake safe Design the perfect rack

Pick Model

Data Rack DR1250

Model

84842 84836 84830 84824 84442 84436 84430 84424

A

B C D E F

G H

Dimensions

End Panel

Width

Depth

DREP-42

28"

42"

DREP-36

28"

36"

DREP-30

28"

30"

DREP-24

28"

24"

24"

42"

24"

36"

24"

30"

24"

24"

Data Rack Mounting Rails 44RU DR-MRCGP DR-MRGP-A DR-MRCG-A DR-MRCGP-A DR-MRGP-A DR-MRCG-A

Models

DR-MRGCTZ DR-MRGTTZ DR-MRGCTZP

ACCE-DR10 ACCE-DR6TS ACCE-DR10TS ACCE-DR6TD ACCE-DR10TD

12-24 EIA-D (Qty 2) 23"-19" Dimensions CN/12-24

All Models

12-24/12-24

All Models

Models

ACCE-DR6

Cage Nut EIA-D (Qty 2) 23"-19"

All Models

Adustable Cable Manager

CN/12-24 Plated 12-24/12-24 Plated Dimensions

All Models

6" Front and Rear Only

All Models

10" Front and Rear Only

C, D, G, H

6" Through 24"-30" W/ HW (Qty2)

C, D, G, H

10" Through 24"-30" W/ HW (Qty2)

A, B, E, F

6" Through 36"-42" W/ HW (Qty2)

A, B, E, F

Š Telect, Inc., All Rights Reserved, 142359 A0 1.509.926.6000 :: telect.com

24"

12-24 Tapped Zinc Plated EIA-D (Qty 2) 23"-19"

A, B, C, D

All Models

30"

Cage Nut Zinc Plated EIA-D (Qty 2) 23"-19"

A, B, C, D

DR-MRGTTZP

D, H

36"

Cage Nut EIA-D (Qty 2) 23"-19"

A, B, C, D

Models

C, G

42"

12-24 Tapped Zinc Plated EIA-D (Qty 2) 23"-19"

A, B, C, D

Data Rack Mounting Rail EIA D

B, F

Depth

Cage Nut Zinc Plated EIA-D (Qty 2)

All Models

A, B, C, D

A, E

Dimensions

All Models

DR-MRG-A

Models

10" Through 36"-42" W/ HW (Qty2) 8


Data Center Racks Racks :: tough. secure. cool.

Part Number DRDP-28 DRDBP-28 DRDDP-28 DRDDBP-28 DRDP-24 DRDBP-24 DRDDP-24

Model

A, B, C, D A, B, C, D A, B, C, D A, B, C, D E, F, G, H E, F, G, H E, F, G, H

DRDDBP-24

E, F, G, H

Part Numbers

Model

DR-TC28 DR-HGB-23 DR-TC24 DR-TCC DR-TCB DRMR-AC DRMR-ACD DR-GANG DR-HGB-19 DR-ANCS DR-CN50 DR-CN100 04500-50 04500-100

DRISO-2442 DRISO-2436 DRISO-2430 DRISO-2424 ACCE-DR6ISO ACCE-DR10ISO

28"

Black Perforated Door

28"

Chrome Perforated Dual Door

28"

Black Perforated Dual Door

24"

Chrome Perforated Door

24"

Black Perforated Door

24"

Chrome Perforated Dual Door

24"

Black Perforated Dual Door Product Data Rack Top Cap 28" Horizontal Ground Bar 23" Data Rack Top Cap 24"

All Models

Data Rack Top Cap Center Label Holder

All Models

Data Rack Top Cap Border Qty 2

All Models

Data Rack AC Power Bracket

All Models

Data Rack AC Power Bracket Dual

All Models

Data Rack Ganging Hardware

All Models

Horizontal Ground Bar 19"

All Models

Seismic Anchor Data Center Rack

All Models

Data Rack Cage Nut Qty 50

All Models

Data Rack Cage Nut Qty 100

All Models

12-24 Mounting Screws Qty 50

All Models

Model

DRISO-2824

Chrome Perforated Door

E, F, G, H

Isolation Pad

DRISO-2830

28"

A, B, C, D

All Models

DRISO-2836

Doors

A, B, C, D

DR-CDS

DRISO-2842

Width

12-24 Mounting Screws Cabinet Duct Spacer

A B C D E F

G H

All Models All Models

© Telect, Inc., All Rights Reserved, 142359 A0 1.509.926.6000 :: telect.com

9

Width

Depth

28ʺ

42ʺ

28ʺ

36ʺ

28ʺ

30ʺ

28ʺ

24ʺ

24"

42"

24"

36"

24"

30"

24"

24"

6"

6" for ACC-DR6

10"

6" for ACC-DR10


Data Center Racks

Racks :: 2000 lb earthquake safe

1.7 2000 Data Center Rack Rack • 84ʺ fixed height • 24ʺ & 28ʺ width (supporting 19ʺ & 23ʺ rack, respectively) • 24ʺ, 30ʺ, 36ʺ, 42ʺ depth

Panels • Removable side panels • Six-post design, seismic Zone 4 rating, 2000 lb certified • Multiple side entry points • Compatible with all standard rack-mount equipment

Options • Adjustable cable management panels −6ʺ W x 24ʺ- 42ʺ D panel −10ʺ W x 24ʺ- 42ʺ D panel • Power accessories:

−Grounding package—wiring, buss bar, vertical power lacing bar −Vertical lacing bar for power cables −PDU mounting

Mounting • Optional, adjustable front and rear mounting rails

Data Center Rack with cable management

• Isolation pad

1.8 Specifications Item

Specification

Seismic certification

2,000 lbs (907 kg)

Physical specs, rack for 23" equipment mtg.

28" W x 42" D x 84" H (711 mm x 1067 mm x 2134 mm) 98 lbs (44kg) - 380 lbs (172 kg) *Additional Depths available

Physical specs, rack for 19" equipment mtg.

24" W x 42" D x 84" H (610 mm x 2134 mm) 90 lbs (41 kg) - 340 lbs (154 kg) *Additional Depths available

Hole spacing

EIA Wide RMU=1-¾ʺ (1/2ʺ, 1-¼ʺ), 44 RU EIA Narrow RMU=1-¾ʺ (1/2ʺ, 5/8ʺ, 5/8ʺ), 44 RU Universal RMU=1/2ʺ, 1/2ʺ, 1/2ʺ, 44 RU

Color

Standard black, others available

Compliance

GR-63-CORE, NEBS compliant, Zone 4 certified.

NEBS tested Zone 4. Earthquake tested and ready if Seismic Anchor Kit is installed properly © Telect, Inc., All Rights Reserved, 142359 A0 1.509.926.6000 :: telect.com

10


Data Center Racks Racks :: tough. secure. cool.

4.739

84.000

4.739

19.500

16.000

24.000

42.000

Front View

Side View

79.656

Figure 3 - 19ʺ Dimensions for 2000 lb and part number DR2000-84442, Front and Side View

gned by

SITTON

wn by

HILBERT

date

tolerances (unless otherwise specified)

2/21/2012

.X ±.060 .XX ±.020 date Diagram .XXX ±.010 3/20/2012

A B

sheet

hole size: ±.005 angularity: ±1°

Weight

sheet size

B

1 of 1

2000 lb

NTS

project

R118

11

projection

Part Number

Dimensions

DR2000-84842

28.000

DR2000-84842

2000 lb

© Telect, Inc., All Rights Reserved, 142359 A0 1.509.926.6000 :: telect.com

scale

23.500


Data Center Racks

Racks :: 2000 lb earthquake safe Design the perfect rack

Pick Model

Data Rack DR2000

Model

84842 84836 84830 84824 84442 84436 84430 84424

A

B C D E F

G H

Dimensions

End Panel

Width

Depth

DREP-42

28"

42"

DREP-36

28"

36"

DREP-30

28"

30"

DREP-24

28"

24"

24"

42"

24"

36"

24"

30"

24"

24"

Data Rack Mounting Rails 44RU DR-MRCGP DR-MRGP-A DR-MRCG-A DR-MRCGP-A DR-MRGP-A DR-MRCG-A

Models

DR-MRGCTZ DR-MRGTTZ DR-MRGCTZP

ACCE-DR10 ACCE-DR6TS ACCE-DR10TS ACCE-DR6TD ACCE-DR10TD

12-24 EIA-D (Qty 2) 23"-19" Dimensions CN/12-24

All Models

12-24/12-24

All Models

Models

ACCE-DR6

Cage Nut EIA-D (Qty 2) 23"-19"

All Models

Adustable Cable Manager

CN/12-24 Plated 12-24/12-24 Plated Dimensions

All Models

6" Front and Rear Only

All Models

10" Front and Rear Only

C, D, G, H

6" Through 24"-30" W/ HW (Qty2)

C, D, G, H

10" Through 24"-30" W/ HW (Qty2)

A, B, E, F

6" Through 36"-42" W/ HW (Qty2)

A, B, E, F

Š Telect, Inc., All Rights Reserved, 142359 A0 1.509.926.6000 :: telect.com

24"

12-24 Tapped Zinc Plated EIA-D (Qty 2) 23"-19"

A, B, C, D

All Models

30"

Cage Nut Zinc Plated EIA-D (Qty 2) 23"-19"

A, B, C, D

DR-MRGTTZP

D, H

36"

Cage Nut EIA-D (Qty 2) 23"-19"

A, B, C, D

Models

C, G

42"

12-24 Tapped Zinc Plated EIA-D (Qty 2) 23"-19"

A, B, C, D

Data Rack Mounting Rail EIA D

B, F

Depth

Cage Nut Zinc Plated EIA-D (Qty 2)

All Models

A, B, C, D

A, E

Dimensions

All Models

DR-MRG-A

Models

10" Through 36"-42" W/ HW (Qty2) 12


Data Center Racks Racks :: tough. secure. cool. Part Number DRDP-28 DRDBP-28 DRDDP-28 DRDDBP-28 DRDP-24 DRDBP-24 DRDDP-24

Model

A, B, C, D A, B, C, D A, B, C, D A, B, C, D E, F, G, H E, F, G, H E, F, G, H

DRDDBP-24

E, F, G, H

Part Numbers

Model

DR-TC28 DR-HGB-23 DR-TC24 DR-TCC DR-TCB DRMR-AC DRMR-ACD DR-GANG DR-HGB-19 DR-ANCS DR-CN50 DR-CN100 04500-50 04500-100

DRISO-2442 DRISO-2436 DRISO-2430 DRISO-2424 ACCE-DR6ISO ACCE-DR10ISO

Black Perforated Door

28"

Chrome Perforated Dual Door

28"

Black Perforated Dual Door

24"

Chrome Perforated Door

24"

Black Perforated Door

24"

Chrome Perforated Dual Door

24"

Black Perforated Dual Door Product Data Rack Top Cap 28" Horizontal Ground Bar 23" Data Rack Top Cap 24"

All Models

Data Rack Top Cap Center Label Holder

All Models

Data Rack Top Cap Border Qty 2

All Models

Data Rack AC Power Bracket

All Models

Data Rack AC Power Bracket Dual

All Models

Data Rack Ganging Hardware

All Models

Horizontal Ground Bar 19"

All Models

Seismic Anchor Data Center Rack

All Models

Data Rack Cage Nut Qty 50

All Models

Data Rack Cage Nut Qty 100

All Models

12-24 Mounting Screws Qty 50

All Models

Model

DRISO-2824

Chrome Perforated Door

28"

E, F, G, H

Isolation Pad

DRISO-2830

28"

A, B, C, D

All Models

DRISO-2836

Doors

A, B, C, D

DR-CDS

DRISO-2842

Width

12-24 Mounting Screws Cabinet Duct Spacer

A B C D E F

G H

All Models All Models

© Telect, Inc., All Rights Reserved, 142359 A0 1.509.926.6000 :: telect.com

13

Width

Depth

28ʺ

42ʺ

28ʺ

36ʺ

28ʺ

30ʺ

28ʺ

24ʺ

24"

42"

24"

36"

24"

30"

24"

24"

6"

6" for ACC-DR6

10"

6" for ACC-DR10


Data Center Racks Racks :: Non-Seismic

1.9 Non-Seismic Data Rack Rack • 84ʺ fixed height • 24ʺ & 28ʺ width (supporting 19ʺ & 23ʺ rack, respectively) • 24ʺ, 30ʺ, 36ʺ, 42ʺ depth

Panels • Removable side panels • Six-post design, seismic Zone 4 rating, 2000 lb certified • Multiple side entry points • Compatible with all standard rack-mount equipment

Options • Adjustable cable management panels −6ʺ W x 24ʺ- 42ʺ D panel −10ʺ W x 24ʺ- 42ʺ D panel • Power accessories:

−Grounding package—wiring, buss bar, vertical power lacing bar −Vertical lacing bar for power cables −PDU mounting

Mounting Data Center Rack with no cable management

• Optional, adjustable front and rear mounting rails • Isolation pad

1.10 Specifications Item

Specification

Non-Seismic Physical specs, rack for 23" equipment mtg.

28" W x 42" D x 84" H (711 mm x 1067 mm x 2134 mm) 98 lbs (44kg)- 380 lbs (172 kg) *Additional Depths available

Physical specs, rack for 19" equipment mtg.

24" W x 42" D x 84" H (610 mm x 2134 mm) 90 lbs (41 kg) - 340 lbs (154 kg) *Additional Depths available

Hole spacing

EIA Wide RMU=1-¾" (1/2", 1-¼"), 44 RU EIA Narrow RMU=1-¾" (1/2", 5/8", 5/8"), 44 RU Universal RMU=1/2", 1/2", 1/2", 44 RU

Color

Standard black, others available

Compliance

GR-63-CORE, NEBS compliant, Zone 4 certified.

© Telect, Inc., All Rights Reserved, 142359 A0 1.509.926.6000 :: telect.com

14


Data Center Racks Racks :: tough. secure. cool.

Figure 4 - 19" Non-Seismic Dimensions for DR-84442, Front and Side Views Diagram

Part Number

Dimensions

B

DR-84842

28.000

A

Š Telect, Inc., All Rights Reserved, 142359 A0 1.509.926.6000 :: telect.com

DR-84842

23.500

15


Data Center Racks Racks :: Non-Seismic Design the perfect rack

Pick Model

Data Rack DR

Model

84842 84836 84830 84824 84442 84436 84430 84424

A

B C D E F

G H

Dimensions

End Panel

Width

Depth

DREP-42

28"

42"

DREP-36

28"

36"

DREP-30

28"

30"

DREP-24

28"

24"

24"

42"

24"

36"

24"

30"

24"

24"

Data Rack Mounting Rails 44RU DR-MRCGP DR-MRGP-A DR-MRCG-A DR-MRCGP-A DR-MRGP-A DR-MRCG-A

Models

DR-MRGCTZ DR-MRGTTZ DR-MRGCTZP

ACCE-DR10 ACCE-DR6TS ACCE-DR10TS ACCE-DR6TD ACCE-DR10TD

12-24 EIA-D (Qty 2) 23"-19" Dimensions CN/12-24

All Models

12-24/12-24

All Models

Models

ACCE-DR6

Cage Nut EIA-D (Qty 2) 23"-19"

All Models

Adustable Cable Manager

CN/12-24 Plated 12-24/12-24 Plated Dimensions

All Models

6" Front and Rear Only

All Models

10" Front and Rear Only

C, D, G, H

6" Through 24"-30" W/ HW (Qty2)

C, D, G, H

10" Through 24"-30" W/ HW (Qty2)

A, B, E, F

6" Through 36"-42" W/ HW (Qty2)

A, B, E, F

Š Telect, Inc., All Rights Reserved, 142359 A0 1.509.926.6000 :: telect.com

24"

12-24 Tapped Zinc Plated EIA-D (Qty 2) 23"-19"

A, B, C, D

All Models

30"

Cage Nut Zinc Plated EIA-D (Qty 2) 23"-19"

A, B, C, D

DR-MRGTTZP

D, H

36"

Cage Nut EIA-D (Qty 2) 23"-19"

A, B, C, D

Models

C, G

42"

12-24 Tapped Zinc Plated EIA-D (Qty 2) 23"-19"

A, B, C, D

Data Rack Mounting Rail EIA D

B, F

Cage Nut Zinc Plated EIA-D (Qty 2)

All Models

A, B, C, D

A, E

Depth

Dimensions

All Models

DR-MRG-A

Models

10" Through 36"-42" W/ HW (Qty2) 16


Data Center Racks Racks :: tough. secure. cool.

Part Number DRDP-28 DRDBP-28 DRDDP-28 DRDDBP-28 DRDP-24 DRDBP-24 DRDDP-24

Model

A, B, C, D A, B, C, D A, B, C, D A, B, C, D E, F, G, H E, F, G, H E, F, G, H

DRDDBP-24

E, F, G, H

Part Numbers

Model

DR-TC28 DR-HGB-23 DR-TC24 DR-TCC DR-TCB DRMR-AC DRMR-ACD DR-GANG DR-HGB-19 DR-ANCS DR-CN50 DR-CN100 04500-50 04500-100

DRISO-2442 DRISO-2436 DRISO-2430 DRISO-2424 ACCE-DR6ISO ACCE-DR10ISO

Black Perforated Door

28"

Chrome Perforated Dual Door

28"

Black Perforated Dual Door

24"

Chrome Perforated Door

24"

Black Perforated Door

24"

Chrome Perforated Dual Door

24"

Black Perforated Dual Door Product Data Rack Top Cap 28" Horizontal Ground Bar 23" Data Rack Top Cap 24"

All Models

Data Rack Top Cap Center Label Holder

All Models

Data Rack Top Cap Border Qty 2

All Models

Data Rack AC Power Bracket

All Models

Data Rack AC Power Bracket Dual

All Models

Data Rack Ganging Hardware

All Models

Horizontal Ground Bar 19"

All Models

Seismic Anchor Data Center Rack

All Models

Data Rack Cage Nut Qty 50

All Models

Data Rack Cage Nut Qty 100

All Models

12-24 Mounting Screws Qty 50

All Models

Model

DRISO-2824

Chrome Perforated Door

28"

E, F, G, H

Isolation Pad

DRISO-2830

28"

A, B, C, D

All Models

DRISO-2836

Doors

A, B, C, D

DR-CDS

DRISO-2842

Width

12-24 Mounting Screws Cabinet Duct Spacer

A B C D E F

G H

All Models All Models

© Telect, Inc., All Rights Reserved, 142359 A0 1.509.926.6000 :: telect.com

17

Width

Depth

28ʺ

42ʺ

28ʺ

36ʺ

28ʺ

30ʺ

28ʺ

24ʺ

24ʺ

42ʺ

24ʺ

36ʺ

24ʺ

30ʺ

24ʺ

24ʺ

6ʺ for ACC-DR6

10ʺ

6ʺ for ACC-DR10


Data Center Racks Racks :: tough. secure. cool.

Figure 5 - 23ʺ Data Center Dimensions for DR-ISO2847, Top and Bottom Views

© Telect, Inc., All Rights Reserved, 142359 A0 1.509.926.6000 :: telect.com

18


Data Center Racks Racks :: tough. secure. cool.

Figure 6 - 19ʺ Data Center Dimensions for DR-ISO2442, Top and Bottom Views

© Telect, Inc., All Rights Reserved, 142359 A0 1.509.926.6000 :: telect.com

19


SPECIFIED)

N ACCORDANCE WITH ALL DARDS

Data Center Racks

MOVE BURRS

Racks :: tough. secure. cool.

36.00 2.00

23.25

10.00

8.50

23.25

28.00

2.38

30.48

2.76

Figure 7 - Data Center Isolation Pad 28ʺW 36ʺD, part number DRISO-2836 Product

Dimensions

Data Center Rack Isolation Pad

28"W 42"D

Finish:

Data Center Rack Isolation Pad

24"W 42"D GP03-RED FIBERGLASS

Material:

Data Center Rack Isolation Pad

24"W 36"DUnless Otherwise Specified Tolerances 28"W 36"D

Data Center Rack Isolation Pad

24"W 30"D

Data Center Rack Isolation Pad 7

6

Data Center Rack Isolation Pad

© Telect, Inc., All Rights Reserved, 142359 A0 1.509.926.6000 :: telect.com

DESIGNED BY

DRISO-2442DATE

S. SITTON DRISO-2842

DRAWN BY

DATE

DRISO-2436 S. SITTON

1/11/2012 1/31/2012

THE 3D MODEL IS THE MASTER FILE. THE GEOMETRY NOT FOR REPRODUCTION COPYRIGHT: 2012 WITHIN THE MASTER FILE MUST BE USED TO FABRICATE This document contains proprietary information that is THIS PART. DIMENSIONS SHOWN ARE DEEMED CRITICAL property of TELECT, INC., Spokane, Washington. It is AND WILL BE USED AS INSPECTION/PROCESS DIMENSIONS. intended for the exclusive use of our customer for APPLY THE FOLLOWING TOLERANCES TO THE 3D CAD FILE information, installation, and/or service. The recipient agrees not to reproduce or copy this document or its GEOMETRY TO FABRICATE THIS PART. contents in whole or in part without prior written permission .X ±.060 HOLE SIZE: ±.005 from TELECT, INC. This document must be returned .XX ±.020 ANGULARITY: ±1° promptly if no longer needed or upon written request from .XXX ±.010 TELECT, INC.

Data Center Rack Isolation Pad

Data Center Rack Isolation Pad

Part Number

5

24"W 24"D 28"W 24"D

20

DRISO-2836 DRISO-2430

28"W 30"D

 TITLE

DRAWING NO

DRISO-2830

4

DRISO-2424 3

DRISO-2824

2


Data Center Racks Racks :: tough. secure. cool.

Installation Guide 2.1 Installation Please read these instructions carefully and completely before beginning installation. For assistance, contact Technical Support at 1.509.926.6000, www.telect.com, or support@telect.com. These instructions presume you have verified that the Telect equipment being installed is compatible with the rest of the system, including power, ground, circuit protection, signal characteristics, equipment from other vendors, and local codes or ordinances.

2.1 Inspecting the shipment Telect, Inc., is not liable for shipping damage. Telect is not responsible for any equipment damage or poor operating performance when you do not follow these guidelines or when you use non-certified installers. Keep the container until you have checked equipment operation. If you experience any kind of problem, call Telect’s Customer Service Department at 1-509-926-6000. Use the original, undamaged container if you are instructed to return the enclosure to Telect. If a shipping container is damaged, keep it for the carrier’s inspection. Notify the carrier and call Telect’s Customer Service Department at 1-509-926-6000. Other than this installation guide, the cabinet ships with no other components. Optional concrete and raised floor anchoring kits discussed in this guide are shown on page 18.

Design the perfect rack

© Telect, Inc., All Rights Reserved, 142359 A0 1.509.926.6000 :: telect.com

21


Data Center Racks Racks :: tough. secure. cool.

2.1.1 Important Installation Guidelines • Elevated Operating Ambient Temperature - If installed in a closed or multi-unit rack assembly, the operating ambient temperature of the rack environment may be greater than room ambient. Therefore, consideration should be given to installing the equipment in an environment compatible with the maximum ambient temperature (Tma) specified by the manufacturer. • Reduced Air Flow - Installation of the equipment in a rack should be such that the amount of air flow required for safe operation of the equipment is not compromised. • Mechanical Loading - Mounting of the equipment in the rack should be such that a hazardous condition is not achieved due to uneven mechanical loading. • Circuit Overloading - Consideration should be given to the connection of the equipment to the supply circuit and the effect that overloading of the circuits might have on overcurrent protection and supply wiring. Appropriate consideration of equipment nameplate ratings should be used when addressing this concern. • Reliable Earthing - Reliable earthing of rack-mounted equipment should be maintained. Particular attention should be given to supply connections other than direct connections to the branch circuit (e.g. use of power strips).

!

ALERT

ALERT! Only qualified technicians may install and maintain this product. Verify all connections meet requirements specified in local electric codes or operating company guidelines. Only use components and crimping tools approved by agencies or certifying bodies recognized in your country or region, such as Underwriter’s Laboratories (UL), TUV, etc. 2.1.2 Installation Considerations 2.1.3 Location & Space The indoor cabinet requires 28" (71 cm) door clearance at the front and rear. Leave as much side clearance for panel removal and worker access as required by your application or local regulations. If you don’t require side access, you can install the cabinets with zero side clearance, and you can leave off any adjacent panels for side-by-side cabinets needing cross-access. Choose a location in compliance with your local operating company requirements. 2.1.4 Tools & Equipment You will need the following tools to install the rack: • 18-mm (or 23/32-in.) masonry bit • 40 N•m torque wrench with a 19-mm box or open end. (A 19-mm socket at least 54-mm deep will also work.) • broadblade screwdriver (~8-mm or 5/16-in. blade width) • horizontal or plumb level (optional) • isolation pad (if required at base of cabinet) • hammer • support strut mounting hardware

© Telect, Inc., All Rights Reserved, 142359 A0 1.509.926.6000 :: telect.com

22


Data Center Racks Racks :: tough. secure. cool.

Figure 8 - Mounting Hardware

2.2 Mounting

!

ALERT

ALERT! The cabinet weighs approximately 445 lbs. (202 kg) for the 19" Data Center Rack, and 475 lbs. (216 kg) for the 23", without additional equipment or shipping materials. Use the appropriate lifting equipment. 2.2.1 Concrete Floor (51005-ANCS Anchor Kit) Each Telect Anchoring Kit (sold separately) contains an isolation pad, concrete anchors, threaded studs, and fastening hardware to anchor and secure the base of one cabinet to a concrete floor. • Using the isolation pad as a template, mark the hole patterns, then move the pad aside. • Drill a 5/8" (18 mm) diameter hole, 4" (100 mm) deep, at each of the four anchor locations. Use a HEPA filter shop vacuum while drilling to prevent concrete dust contamination of adjacent equipment.

© Telect, Inc., All Rights Reserved, 142359 A0 1.509.926.6000 :: telect.com

23


Data Center Racks Racks :: tough. secure. cool.

!

ALERT

ALERT! If you drill past a reinforcing bar, you MUST use an isolation pad to isolate the cabinet from the rebar ground. Telect recommends the use of isolation pads on all cabinet and rack installations to protect against inadvertent rebar grounds. 1. Clean out the holes using a HEPA filter shop vacuum and carefully clean away all debris. Figure 9 - Isolation Pad for the Data Center Rack THREADED STUD TORQUE NUT RED PLASTIC RING ON A TORQUE NUT FLAT WASHER METAL SLEEVE NYLON SPACER SLEEVE EXPANDABLE ANCHOR SLEEVE ANCHOR CONE

Figure 10 - 51005-ANCS Anchor Kit 2. Thread the torque nut and washer onto the rod. The washer should touch the top of the metal sleeve. 3. Insert the anchor into the hole. Tap the anchor rod down with a hammer until the washer touches the concrete.

Š Telect, Inc., All Rights Reserved, 142359 A0 1.509.926.6000 :: telect.com

24


Data Center Racks Racks :: tough. secure. cool.

4. Pre-torque the anchor to approximately 30 ft-lbs. 5. Loosen the nut several turns, then remove the rod, torque nut, and washer (the rod assembly can be backed out by using the screwdriver slot; the sleeves and anchor cone remain in the hole). 6. Place the isolation pad on the mounting surface. 7. Position the cabinet over the holes; do not let debris fall into the holes. 8. Install the insulating washers that accompany the isolation pad. 9. Place the rods through the holes in the cabinet base and thread them into the anchor bodies until they are fully engaged in the threads of the bottom cones. 10. Add the steel washer and the torque nut assembly and retorque to 30 ft-lbs. Make sure the washer and torque nut are securing the diagonal corner strut and not the end cap.

CABINET FRAME CORNER STRUT END CAP

ISO PAD INSERT

ANCHOR ASSEMBLY

CONCRETE FLOOR

Figure 11 - Securing the Anchor

Š Telect, Inc., All Rights Reserved, 142359 A0 1.509.926.6000 :: telect.com

25


Data Center Racks Racks :: tough. secure. cool.

2.2.2 Raised Computer Floor (DR-ANCRF Anchor Kit) Each Telect Anchoring Kit (sold separately) contains an isolation pad, concrete anchors, threaded rods, and fastening hardware to anchor and secure the base of one cabinet to a raised floor and the concrete below it. See “Isolation Pad for the Data Center Rack" on page 10 for a view of the isolation pad. 1. Locate the isolation pad over one raised floor panel. 2. Using the isolation pad as a template, mark the hole pattern, then move the pad aside. 3. Drill a 5/8" (18 mm) diameter hole at each of the four anchor locations. 4. Remove the floor panel, transfer the panel holes to the concrete, and drill a 5/8" (18 mm) diameter hole, 4" (100 mm) deep at each of the four marks. Use a HEPA filter shop vacuum while drilling to prevent concrete dust contamination of adjacent equipment.

!

ALERT

ALERT! If you drill past a reinforcing bar, you MUST use an isolation pad between the floor plate and 12 mm x 1.75 x 1 m All Thread Rod (4) cabinet to isolate the cabinet from the rebar ground. Telect recommends the use of isolation pads on all cabinet and rack installations to protect against inadvertent rebar grounds.

12 mm x 1.75 Nut (12)

5. Clean out the holes using a HEPA filter shop vacuum and carefully clean away ½ in. Spring Lockwasher (12) all debris.

½ in.onto Flatthe Washer (12) 6. Thread the torque nut and washer rod. (See “Securing the Anchor" on page 11.) The washer should touch the top of the metal sleeve. Delrin ® Shoulder Washer (4)

7. Insert the anchor into the hole. Tap the anchor rod down with a hammer until the washer touches the concrete. 8. Torque the anchor to approximately 30 ft-lbs. 9. Thread a nut, lock washer, flat washer, and square plate onto each rod so the square plate sits at the level required to fully support the floor panel at the proper height.

2 in. x 2 in. x ¼ in. Square Washer (4)

10. Cut any wire access holes required in the floor plate, then place it over the anchor rods. 11. Install the isolation pad. 12. Locate the cabinet over the anchor rods. 13. Install the insulating washers that accompany the isolation pad. 14. Add the Delrin® shoulder washer, flat washer, pressure washer, and nut and torque to 30 ft-lbs. Make sure the washer and torque nut are securing the diagonal corner strut and not the end cap.

M12/25, Heavy Duty Expansion Anchor (4)

© Telect, Inc., All Rights Reserved, 142359 A0 1.509.926.6000 :: telect.com

26


CABLE

Data Center Racks Racks :: tough. secure. cool.

2.2.3 Grounding

!

WARNING

!

WARNING

WARNING! To maintain proper grounding protocol, always ground this cabinet to the site master ground return that facilitates the earth ground for the site.

WARNING! Failure to properly ground this equipment can create hazardous conditions to installation personnel and to the equipment. 6

5

4

2

3

1. Route the 14 AWG (min.) ground wire in from the isolated chassis ground (use appropriate REV ECO DESCRIPTIONfittings) to the ground in the cabinet (ground lug locations vary).

1

DATE

BY

2. In the cabinet, crimp a single-hole compression lug for a ¼-20 stud onto the ground wire. 3. Thread a ¼-20 KEPS nuts (not provided) on the stud and tighten to ~45 in.lb (~5 N•m). 4. Place the compression grounding lug over the stud. 5. If desired or required, place a washer on top of the lug. 6. Thread another KEPS nut onto the stud and also tighten to ~45 in.lb (~5 N•m). 2.2.4 Installing the Cable Managment Panel 1. Using two people, hold the cable management panel up against the side of the Data Center Rack 2. From the inside of the Data Center Rack, attach six 3/8" bolts, flatwashers, and lockwashers through the vertical support frame and into the panel at the mounting holes indicated in Figure 11. 3. To install a second Data Center Rack to the same cable manager, repeat steps 1 and 2 on the other side of the cable management panel. See figure 12. 3

2 ITEM NO.

PART NUMBER

1

141922

2

141921

3

116786

DESIGNED BY

1

DATE

B. Fuller

DESCRIPTION DUCT:CMS,HORIZ,4X4,ADJ,OUTER,19.75",10"-14" SPAN DUCT:CMS,HORIZ,4X4,ADJ,INNER,19.75",10"-14" SPAN SCREW:6-32x.250,FHPUC GROUNDING NIBS,STL,ZN,TFS,ROHS

6/2/2011

QTY. 2 2 16

23321 East Knox Avenue, PO Box 665 Liberty Lake, Washington 99019 (509) 926-6000

Figure 12 - Attaching2/8/2012 the Cable Management Panel G. Hilbert DRAWN BY

DATE

CONNECTING THE FUTURE

TITLE

24"-30"

6

REV

ECO

DESCRIPTION

DATE

drawing no

customer drawing

ACCE-DR6

CABLE MNGR USER MANUAL VIEWS

5

© Telect, Inc., All Rights Reserved, 142359 A0 1.509.926.6000 :: telect.com

NOT FOR REPRODUCTION

CUSTOMER DRAWING

COPYRIGHT: 2012

ADJUSTABLE CABLE MANAGER 6" TROUGH 24"-30" W/ HW This document contains proprietary information that is units designed by date sheet sheet size project projection QTY 2 scale property of TELECT, INC., Spokane, Washington.tolerances It is (unless otherwise specified) 6/2/2011 B. Fuller ±.060 hole size: ±.005 intended for the exclusive use of our customer for .X inch A0 R118 B NTS .XX ±.020 1 of 1 DRAWING NOangularity: ±1° UNITS SHEET SIZE date drawn by information, installation, and/or service. The recipient .XXX ±.010 G. HILBERT 2/8/2012 agrees not to reproduce or copy this document or its ACCE-DR6TS B INCH contents in whole or in part without prior written permission SHEET PROJECT SCALE REV from TELECT, INC. This document must be returned promptly if no longer needed or upon written request from 1 OF 1 A0 R118 NTS TELECT, INC. BY

rev

4

3

27

2

1


nel Assem

Racks :: tough. secure. cool.

2.2.5 Installing the End Panels You can install the end panel to the Data Center Rack with or without the cable management panel. The side panels are 79.7 inches high and 35.67 inches wide, with handles at the positions shown. 1. Hold the panel up against the side of the rack. 2. Using six 3/8" bolts, flatwashers, and lockwashers at the bolt holes indicated in figure 13, secure the panels to the side.

Figure 13 - Two Data Center Racks with Single Cable Management Panel

Locking Pull Latches

copyright 2012

telect.com :: 1.509.926.6000

Pull Latch Keeper

Panel Base Slot DESCRIPTION customer drawing

USER MANUAL VIEWS

DATE

BY rev

A0

units

inch

designed by

B. Fuller drawn by

Figure 14 - End PanelholeAssembly 6/2/2011 .X ±.060 size: ±.005

G. HILBERT

© Telect, Inc., All Rights Reserved, 142359 A0 1.509.926.6000 :: telect.com

date

date

3/20/2012

tolerances (unless otherwise specified)

.XX ±.020 .XXX ±.010

28

angularity: ±1°

sheet

1 of 1

sheet size

B

scale

NTS

project

R118

projection

CONFIDENTIAL NOT FOR REPRODUCTION

ECO

Data Center Racks


Data Center Racks Racks :: tough. secure. cool.

2.2.6 Installing the Ground Bar To install the ground bar, mount it to the top of the vertical frame rail at hole 1 down from the top, using 12-24 mounting hardware, as shown. 2.2.7 Installing Doors Two door options are available: single doors with the latch on the side, or double doors with the latch in the center. The double doors allow you to open one side of the door in a narrow corridor. See “1.6 Accessories" on page 18 for details.

Figure 15 - Mounting the Ground Bar

Door hinges are partially installed at the factory. To install a door, first locate the M6x10m Phillips panhead hinge mount screws, the bracket mount screws, the hinge, and the bracket.

Figure 16 - Installing the Door Hinges

Š Telect, Inc., All Rights Reserved, 142359 A0 1.509.926.6000 :: telect.com

29


Data Center Racks Racks :: tough. secure. cool.

Procedure steps: 1. Install the hinge to the rack, using the screws provided. 2. Install the other side of the hinge to the bracket, using the other two screws. 3. Repeat steps 1 & 2 to install the bottom hinge. 4. With an assistant holding the door up against the frame, align the door hinge components and lower the door onto the hinge. This procedure is complete. 2.2.8 Replacing DoorsFigure If it is necessary to replace the cabinet doors, follow these steps: 1. Lift the door straight up and out to remove it from the hinge pin. 2. To replace the door, have an assistant help align the door hinge components with those on the cabinet and lower the door onto the hinge.

Figure 17 - Door Hinge

Factory-installed hinge section

Hinge

Frame bracket mounting hardware

Figure 18 - Back Door Hinge tcejorp

811R

elacs

STN

ezis teehs

teehs

)defiiceps esiwrehto sselnu( secnarelot

etad

1102/9/8 0.± Rights :ezis eloh Reserved, 060.± X. © Telect, Inc., 50All 142359 A0 B °1± :ytiralugna 020.± XX. 1 fo 1 etad 1.509.926.6000 :: telect.com010.± XXX. 2102/62/3

yb dengised

TREBLIH .G yb nward

TREBLIH .G

stinu

hcni

ver

300A

gniward remotsuc

on gniward

WEIV EGNIH ROOD LAUD LAUNAM RESU

weiv egnih rooD raeR


Data Center Racks Racks :: tough. secure. cool.

2.3 Maintenance Telect’s indoor cabinets require no preventive maintenance

2.4 Service Technical support Email: support@telect.com Phone: 1-509-926-6000 2.4.1 In-warranty service Contact your Telect equipment distributor, or call a Telect Customer Service Representative: 1-509-926-6000 Telect will repair or replace defective products within the limits of the warranty. NOTE: Call a Customer Service Representative for a Return Material Authorization (RMA) before returning any equipment. 2.4.2 Out-of-warranty service Contact a Telect Customer Service Representative as detailed above. Telect will provide a Purchase Order form along with a Return Material Authorization (RMA) to be included with the enclosure when it is shipped for repair. A processing fee will be charged to guarantee a repair estimate. The charge is credited against actual material and labor costs. 2.4.3 Repacking for shipment 1. Tag the equipment showing owner’s name, address, and telephone number, together with a detailed description of the problem. 2. Use the original shipping container if possible. If you do not have it, package the equipment in a way to prevent shipping damage. Include the RMA inside the container and legibly print the RMA number on the outside of the package, near the shipping address. 3. Insure the package.

© Telect, Inc., All Rights Reserved, 142359 A0 1.509.926.6000 :: telect.com

31


Data Center Racks Racks :: tough. secure. cool.

Table of Contents Chapter 1 ������������������������������������������������������������������������������������������������������������������������������1 1.1 Introduction ���������������������������������������������������������������������������������������������������������������������1 1.3 750 Data Center Rack ��������������������������������������������������������������������������������������������������2 1.4 Specifications ������������������������������������������������������������������������������������������������������������������2 1.5 1250 Data Center Rack ������������������������������������������������������������������������������������������������6 1.6 Specifications �����������������������������������������������������������������������������������������������������������������6 1.7 2000 Data Center Rack ����������������������������������������������������������������������������������������������10 1.8 Specifications ���������������������������������������������������������������������������������������������������������������10 1.9 Non-Seismic Data Rack ����������������������������������������������������������������������������������������������14 1.10 Specifications ��������������������������������������������������������������������������������������������������������������14 Chapter 2 ����������������������������������������������������������������������������������������������������������������������������21 2.1 Installation ���������������������������������������������������������������������������������������������������������������������21 2.1 Inspecting the shipment ������������������������������������������������������������������������������������������������21 2.1.1 Important Installation Guidelines ��������������������������������������������������������������������������� 22 2.1.2 Installation Considerations ������������������������������������������������������������������������������������22 2.1.3 Location & Space ��������������������������������������������������������������������������������������������������22 2.1.4 Tools & Equipment ������������������������������������������������������������������������������������������������22 2.2 Mounting �����������������������������������������������������������������������������������������������������������������������23 2.2.1 Concrete Floor (51005-ANCS Anchor Kit) ������������������������������������������������������������ 23 2.2.2 Raised Computer Floor (DR-ANCRF Anchor Kit) ������������������������������������������������� 26 2.2.3 Grounding �������������������������������������������������������������������������������������������������������������27 2.2.4 Installing the Cable Managment Panel ����������������������������������������������������������������� 27 2.2.5 Installing the End Panels ��������������������������������������������������������������������������������������28 2.2.6 Installing the Ground Bar ��������������������������������������������������������������������������������������29 2.2.7 Installing Doors �����������������������������������������������������������������������������������������������������29 2.2.8 Replacing DoorsFigure �����������������������������������������������������������������������������������������30 2.3 Maintenance �����������������������������������������������������������������������������������������������������������������31 2.4 Service ��������������������������������������������������������������������������������������������������������������������������31 2.4.1 In-warranty service ������������������������������������������������������������������������������������������������31 2.4.2 Out-of-warranty service �����������������������������������������������������������������������������������������31 2.4.3 Repacking for shipment ����������������������������������������������������������������������������������������31

© Telect, Inc., All Rights Reserved, 142359 A0 1.509.926.6000 :: telect.com

32


Data Center Racks Racks :: tough. secure. cool.

List of Figures Figure 1 - 19" Dimensions for 1250 lb and part number DR1250-84442 ����������������������������� 7 Figure 2 - 2,000 lb Rack with cable management �������������������������������������������������������������� 10 Figure 3 - 19" Dimensions for 2000 lb and part number DR2000-84442 ��������������������������� 11 Figure 4 - Non-Seismic Data Rack with no cable management ����������������������������������������� 14 Figure 5 - 19" Non-Seismic Dimensions for DR-84442, Front and Side Views ���������������� 15 Figure 6 - 23" Data Center Dimensions for DR-ISO2847, Top and Bottom Views ������������� 18 Figure 7 - 19" Data Center Dimensions for DR-ISO2442, Top and Bottom Views ������������� 19 Figure 8 - Data Center Isolation Pad 28"W 36"D, part number DRISO-2824 �������������������� 20 Figure 9 - Mounting Hardware ��������������������������������������������������������������������������������������������23 Figure 10 - Isolation Pad for the Data Center Rack ������������������������������������������������������������ 24 Figure 11 - 51005-ANCS Anchor Kit �����������������������������������������������������������������������������������24 Figure 12 - Securing the Anchor �����������������������������������������������������������������������������������������25 Figure 13 - Attaching the Cable Management Panel ���������������������������������������������������������� 27 Figure 14 - Two Data Center Racks with Single Cable Management Panel ���������������������� 28 Figure 15 - End Panel Assembly ���������������������������������������������������������������������������������������28 Figure 16 - Mounting the Ground Bar ��������������������������������������������������������������������������������29 Figure 17 - Installing the Door Hinges �������������������������������������������������������������������������������29 Figure 18 - Door Hinge �������������������������������������������������������������������������������������������������������30 Figure 19 - Back Door Hinge ����������������������������������������������������������������������������������������������30