HIGH CAPACITY TURBINE PUMPS

HCP


HIGH CAPACITY TURBINE PUMPS A

vailable with either 3 or 5 horsepower, 50 or 60 hertz power, the FE Petro High Capacity Pump delivers efficient, reliable, and quiet performance when high volumes or high speed deliveries of gasoline or diesel fuel are required. Optional syphon assembly is available so more than one tank can be used for each grade of product.

of the unit without disturbing the discharge piping. The syphon (if connected) is not disturbed when removing the extractable assembly, and the pump motor

High Performance FE Petro’s two-stage centrifugal pump design is coupled with a dependable Franklin Electric motor to provide higher heads, faster fuel delivery and lower cost operation. Motors are all three phase for smooth trouble-free operation, and are available in various voltages. Units come standard with 6� diameter riser pipe to mount the pump to the tank.

Ease of Maintenance If service is required, all FE Petro products are designed to put the operator back in business fast. Maintenance on the pump motor assembly, can be performed without having an electrician on site, because no wires are broken. Large diameter pins and sockets provide automatic open circuiting and disconnecting of the wiring when the extractable portion of the pump is removed. There is no difficult cam lock which has to be turned. Easily removed bolts provide the means to extract the unit. Properly spaced lifting eyes facilitate the removal

assembly is easily removed from the discharge head by removing four bolts and using standard pusher bolts. Replacement pump motor assemblies are available for comparably sized existing Tokheim and Red Jacket pumps.

Reliability Quality engineering and simplicity of design work hand in hand to insure years of reliable performance from every High Capacity unit. The continuous duty, three-phase Franklin motor with carbon bearings and stainless steel journals is the industry standard. The impellers, made of molded Delrin, and diffusers of hard coated aluminum with a stainless

steel p u m p shaft assure trouble-free operation in motor fuels. Dual (180Ëš opposed) 3" horizontal discharge ports provide easy installation, and two built-in line check valves reduce installation costs. Two line pressure relief valves protect the dispenser, meters, and piping from abnormal pressures from thermal expansion. The mesh screen on the pump inlet prevents large particles from entering the unit, and the FE Petro High Capacity unit is compatible with existing high capacity leak detector technology. New units are easily connected to field wiring without disassembly of the unit.

Satisfaction Ever y FE Petro pump undergoes rigorous testing and inspection before leaving our factory. Each and every High Capacity pump is built to your tank and bury specifications and the complete assembly is performance tested to insure that your needs are met. All High Capacity pumps are UL listed and meet the requirements of UL 79.


HIGH CAPACITY TURBINE PUMPS

Liquid Compatibility: • Standard units compatible with fuel mixtures containing up to 15% ethanol or methanol with gasoline and 20% MTBE, 20% ETBE, or 17% TAME with gasoline, and diesel fuels. • Alcohol/Gasoline models (designated with AG in model number) are compatible in fuel mixtures containing any combination of ethanol or methanol and gasoline and 20% MTBE, 20% ETBE, or 17% TAME with gasoline, and diesel fuels.


HIGH CAPACITY CONTROLLER OPTIONS STP-CB 3/5 Magnetic Starter

STP-SCIII 3 Phase Smart Controller

The FE Petro magnetic starter incorporates ambient compensated relays with quick trip heaters and three leg protection. It assures proper pump motor protection.

Designed to replace 3-Phase Magnetic Starters. The STP-SCIII provides the following pump protection and performance features: • • • • • • • • •

Dry run protection Extended pump run detection Over/under voltage Voltage/load unbalance Phase loss Locked rotor Open circuit Alternating lead pump Auto start of secondary pumps on demand or in event of fault on lead pump

Available in: • 208/230V 3 Phase 60 HZ • 380-415V 3 Phase 50 HZ

HOW TO ORDER GRADE LEVEL

BURY DEPTH

CONTAINMENT SUMP (IF USED)

C

MANWAY (IF USED)

B EFFECTIVE TANK DIAMETER (ETD) A TANK INSIDE DIAMETER 5"

MODEL LENGTH=ETD + riser - bottom clearance DETERMINING MODEL LENGTH Effective Tank Diameter (ETD) is the combination of any or all of the following: Tank Diameter (to top of 6" bung) + Manway + Sump Adapter Riser to be determined by bury depth

HCPB001

To size your pump order correctly, the following information is needed: 1. Pump Model/Horsepower? 2. Effective tank (Inside) Diameter? 3. Steel or Fiberglass Tank? 4. If Fiberglass: • Manufacturer? • Single Wall or Double Wall? • Will pump mount on tank or on manway? 5. Bury Depth? 6. Containment Sump? The FE Petro Model Number is designated STP-A-B-C, using the critical dimensions shown above, where: A=Pump Horsepower B=Model Length C=Riser Length Minimum riser length=6" (3" increments)

3760 Marsh Road Madison, WI 53718, U.S.A. Tel: +1 608 838 8786 • Fax: +1 608 838 6433 Tel: USA & Canada: 1 800 225 9787 Tel: Mexico: 001 800 738 7610 Email: fepetro@franklinfueling.com Website: www.franklinfueling.com 4/04