Feeney Lighting 24v 96w driver Specifications

Page 1

www.feeneyinc.com 800-888-2418

SPECIFICATION SHEET

24V 96W Driver

• • • • •

RoHS

Compliant

Specifications Input

Output

Environment

Additional Information

UL Class 2 power supply Constant voltage output Adjustable amperage / voltage output Universal AC input / full range (up to 295VAC) Protections: short circuit / overload / over voltage / over temperature • High efficiency up to 88.5% • IP 64 rating – suitable for dry / damp locations • Cooling by free air convection

Voltage ¹ Current Frequency Efficiency Wire or Terminal Connection Voltage Voltage Adjustment Range Current Adjustment Range Current Power (wattage) Wire or Terminal Connection # Output Connections ² Ripple & Noise (max) Operating Temp. ³ Operating Humidity IP Rating / Location Class 2 Compliant

100 - 240VAC; 277VAC (North America only) 1.1A/115VAC; 0.55A/230VAC; 0.45A/277VAC 47 ~ 63Hz 88.5% 18 AWG wire leads w/ framed ground connection 24VDC 20.4 ~ 24V 3 ~ 4A 0 ~ 4A 96W (refer to "Derating Curve") 18AWG wire leads 1 150mVp-p -22 ~ +122°F (-30 ~ +50°C) 20 ~ 95% RH non-condensing IP 64, suitable for dry and damp locations Yes

Safety Standards

UL879, UL1310, UL8750; UL # E334687, E320521, E307078; CE

Housing / Cooling

Plastic case / free air convection

Dimmability ⁴

May be paired with a compatible low voltage PWM dimmer/controller installed between the secondary output of driver and load (LED lighting)

Dimensions Weight Warranty

Feeney Lighting

7.87 x 2.78 x 1.38 in. (L x W x H) 1.15 lb. Two (2) Years

1 OF 2

www.feeneyinc.com


www.feeneyinc.com 800-888-2418

35

6.26

T case: Max. Case Temperature.

SPECIFICATION SHEET

24V 96W Driver Mechanical Specifications Output voltage and current adjustment : remove the upper case and adjust through SVR1 & SVR2 shown in the diagram.

100-240VAC~ 50/60 Hz

SVR1

2.78 in.

AC/L(Brown) AC/N(Blue) Ground (Green/Yellow)

V+ (Red) V- (Black)

SVR2 To Low Voltage LED Load

SVR1 Output voltage adjustment

7.80 in.

SVR2 Output current adjustment 1.30 in.

Fosc : 100KHz

Block Diagram Output voltage and current adjustment : EMI FILTER POWER PFC SVR2 shown in diagram. & Remove the upper case and adjust through SVR1 &SWITCHING CIRCUIT SVR1 RECTIFIERS

I/P

RECTIFIERS & FILTER

+V -V O.L.P.

SVR2

FG

O.L.P. PFC CONTROL

DETECTION CIRCUIT

PWM & PFC CONTROL

SVR1 Output voltage adjustment

O.V.P. SVR2 Output current adjustment

Derating Curve Derating Curve

Static Characteristics Static Characteristics Curve 100

100

90 80

230VAC Input only

80 70

LOAD (%)

LOAD (%)

60 40

20

-30

-25

-10

0

15

30

40

50 (HORIZONTAL)

60 50 40

90

AMBIENT TEMPERATURE ( )

100

125

135

145

155 165

175

180

200

230

295

INPUT VOLTAGE (V) 60Hz

Safety & Warnings • • • • •

Turn power OFF at main breaker before servicing or installing this product. File Name:PLN-100-SPEC 2012-12-2 This product is intended to be installed and serviced by a qualified, licensed electrician. Install in accordance with the National Electric Code, and local regulations. Proper heat dissipation will prolong the working lifespan of this product. Install in a well-ventilated area free from explosive gases and vapors. Drivers are rated for maximum power output at optimum thermal and voltage conditions. Please refer to the driver specifications for maximum load ratings. • Ensure a compatible LED fixture with the correct operating voltage is installed with this product. • Ensure proper gauge wire is installed. When choosing wire, factor in voltage drop and amperage rating. Improper wire gauge installation may overheat wires, leading to electric shock or fire. • Use only UL listed wire nuts and clamp accessories with this product.