TID Solar Installation Checklist

Page 1

TID Solar Installation Checklist

1 Single Line Diagram INSTALLATION AS BUILT REFLECTS THE SLD AS APPROVED

2 Main Service Panel MSP LABELED PER NEC 690.14.C.2 & 690.52 SITE PLACARD (IF GENERATION METER NOT VISIBLE FROM MSP) NO SPLICES ON ENERGIZED CONDUCTORS MSP MEETS TID CONSTRUCTION STANDARDS (METER HEIGHT AND WORKING CLEARANCE) MSP IS UL RATED AND EUSERC APPROVED (NEWLY INSTALLED PANELS ONLY)

3 PV Breaker

5 Conduit LABELED PER NEC 690.14.C.2 & 690.52

7 Generation Meter Socket GENERATION METER SOCKET MEETS TID CONSTRUCTION STANDARDS (METER HEIGHT AND WORKING CLEARANCE) LOCATED NO MORE THAN 60 FEET FROM INVERTER (OR ARRAY IF USING MICRO INVERTERS) ONLY ONE GENERATION METER SOCKET IS INSTALLED PER NET METERED MSP GENERATION METER SOCKET WIRED WITH FEED FROM PV BREAKER ON BOTTOM (LOAD SIDE) NO SPLICES ON ENERGIZED CONDUCTORS ALL CONNECTORS USED ARE UL RATED

PV BREAKER IS LABELED PER NEC 690.14.C.2 & 690.52

SOCKET IS UL RATED AND EUSERC APPROVED

PV BREAKER POSITIONED OPPOSITE SIDE OF BUS RELATIVE TO MAIN

SOCKET HAS PROVISION FOR USE OF A METER LOCKRING

PV BREAKER SIZED CORRECTLY FOR MAIN BREAKER CONFIGURATION (MAIN IS DERATED IF NECESSARY) TAP CONNECTORS ARE UL RATED (LINE SIDE TAP ONLY) TOTAL GENERATION CAPACITY DOES NOT EXCEED SERVICE ENTRANCE RATING (LINE SIDE TAP ONLY) SUM OF ALL 6 BREAKERS DOES NOT EXCEED TID SERVICE ENTRANCE RATING (MSP WITHOUT MAIN BREAKER ONLY)

4 AC Disconnect

7 Battery Storage System OPERABLE AT TIME OF INSPECTION ABLE TO DEMONSTRATE NO BACKFEED WHEN UTILITY POWER IS INTERUPTED BATTERY SIZE AND MANUFACTURER MATCH APPROVED SLD

CUSTOMER INFORMATION

AC DISCONNECT LABELED PER NEC 690.14.C.2 & 690.52 LOCATED WITHIN 10 FEET AND LINE OF SIGHT FROM MSP LOCATED ON SAME SIDE OF OBSTRUCTIONS AS MSP WIRED WITH UTILITY FEED LANDED ON TOP OF SWITCH

Name Installation Address

FUSE RATING IS LESS THAN OR EQUAL TO SWITCH RATING (FUSED ONLY) NO SPLICES ON ENERGIZED CONDUCTORS ALL CONNECTORS USED ARE UL RATED SWITCH IS UL RATED ALL KNOCKOUTS OR HUBS ARE COVERED APPROPRIATELY

Phone Number Email Address

Turlock Irrigation District • 333 E. Canal Drive • P.O. Box 949 • Turlock, CA 95381 • (209) 883-8300 • www.tid.com