Synopsis courtesy of:
Nantucket Building Science & Energy Consulting www.ackBS.com (508) 631-6633 Tom Barnes RESNET Certified HERS Rater BPI Certified Thermal Envelope Specialist LEED AP Licensed GC (MA)
Highlights: 2012 IECC - for Nantucket (Climate Zone 5A - Marine) - RESIDENTIAL CODE, Chapter 4 Note: There are two paths to meeting energy code requirements, either of which may be chosen: "Prescriptive" - simply follow what the code book "prescribes" - no "tradeoffs" are allowed this way. "Performance" - this allows for "tradeoffs" as long as overall energy performance is achieved. "Tradeoffs" means improving one or more elements that affect building performance allows one to select systems or assemblies that are less than the "prescriptive" requirements in the code book. For instance, choosing higher efficiency HVAC equipment, improving air sealing, and increasing ceiling insulation may allow one to use 2x4 walls with R-15 fiberglass in cavities.
Topic Area Building Label or Certificate
Building Thermal Envelope (R Values and U Factors)
Section Mandatory Requirement 401.3 Yes
Prescriptive
A permanent certificate supplied by the BUILDER or DESIGNER Applied to electric panel Showing "installed" R-values of building envelope components (roof, walls, floors, foundations, slabs, etc) Showing window U-factors and Solar Heat Gain Coefficients (NA in Zone 5) Showing results of BLOWER DOOR and DUCT TESTING Showing types and efficiencies of heating (AFUE) , cooling (SEER), and domestic hot water equipment (EF) This is the "prescriptive" approach to meeting code requirements. PRESCRIPTIVE means follow what Table 402.1.1 says to use for Zone 5A: Windows/Fenestration: U = 0.32 or less Skylights: U = 0.55 or less Solar Heat Gain Coefficient: NA - no requirement for Zone 5A Ceilings: R-49 (see exceptions allowed) Wood-Framed Walls: R-20 or R-13 in "cavity" PLUS R-5 "continuous" on exterior Framed Floors: R-30 OR sufficient to fill floor cavity (R-19 minimum) Basement Walls (if applicable): R-15/19 (Either R-15 "continuous" on interior or exterior OR R-19 in "cavity" on interior OR R-13 in cavity plus R-5 "continuous" on interior or exterior Slabs (if applicable): R-10 plus R-5 at edge of heated slabs (thermal break) Crawl Spaces: Same as for Basement Walls (if applicable)