TABLA SELECCION DE TUBERIA CONDUIT

Page 1

Lunes 13 de marzo del 2006 Norma oficial mexicana NOM- 001SEDE 2005 TABLA 10-5. DIMENSIONES DE LOS CONDUCTORES AISLADOS Y CABLES DE ARTEFACTOS TIPO TAMAÑO NOMINAL DIAMETRO AREAAPROX. 2 2 APROX. MM MM AWG MM2 TW 2.082 14 3.38 8.97 THHW, THHW-LS 3.307 12 3.86 11.7 THW, THW-LS 5.6 10 4.47 15.7 THW-2 8.367 8 5.99 28.2 13.3 6 7.72 46.8 TW 21.15 4 8.94 62.8 THW 26.67 3 9.65 73.2 THW-LS 33.62 2 10.5 86.0 THHW 42.41 1 12.5 123 THHW-LS 53.48 1/0 13.5 143 THW-2 67.43 2/0 14.7 169 RHH* 85.01 3/0 16.0 201 RHW* 107.2 4/0 17.5 240 RHW-2 126.67 250 19.4 297 152.01 300 20.8 341 177.34 350 22.1 384 202.68 400 23.3 427 253.35 500 25.5 510 304.02 600 28.3 628

DIMENSIONESDETUBO(CONDUIT) METALICOTIPOPESADO,SEMIPESADOY LIGEROY AREA DISPONIBLEPARALOSCONDUCTORES(BASADOEN LA TABLA 10-1. CAPITULO10). DESIGNACION DIAMETRO AREAINTERIOR AREADISPONIBLEPARACONDUCTORESMM2 TAMAÑO INTERIOR TOTALMM2 UN DOS MAS DE NOMINAL MM. DOS PULG (MM) CONDUCTORES CONDUCT CONDUCTOR ORES

Fr=31%

Fr=53% Fr=40% 1/2 (16) 15.8 196 103 60 78 3/4 (21) 20.9 344 181 106 137 1 (27) 26.6 557 294 162 222 1 1/4 (35) 35.1 955 513 299 387 1 1/2 (41) 40.9 1313 697 407 526 2 (53) 52.5 2165 1149 671 867 2 1/2 (63) 62.7 3089 1638 956 1236 3 (78) 77.9 4761 2523 1476 1904 3 1/2 (91) 90.1 6379 3385 1977 2555 4 (103) 102.3 8213 4349 2456 3282 5 (129) 128.2 12907 6440 4001 5163 6 (155) 154.1 18639 9879 5778 7456 Para tubo (conduit) flexible metálico o no metálico y para tubo (conduit) de PVCy de polietileno los cálculos deberán basarse en las dimensiones interiores reales proporcionadas por el fabricante o indicadasen la norma del producto.


Turn static files into dynamic content formats.

Create a flipbook
Issuu converts static files into: digital portfolios, online yearbooks, online catalogs, digital photo albums and more. Sign up and create your flipbook.