MMRCL Office Headquarters_Working Drawings_2021-22

Page 1

MMRC HEADQUARTERS AT SIDDHIVINAYAK METRO JUNCTION SEMESTER 6 WORKING DRAWING PORTFOLIO VRUSHALI KULKARNI ROLL NO-28 SEAT NO-3756


LAMP POST GENERAL NOTES 1) All dimensions are in 'millimeters' unless specified. 2) The drawing is not to be scaled. The dimensions are strictly are to be followed. 3) All levels are unfinished levels unless specified. 4) The contractor shall verify all on site dimensions including elevations prior to the commencement of work on site. 5) The contractor shall inform the architect and/or project engineer on site regarding any conditions/modifications. 6) The contractor shall coordinate and verify the work indicated on the drawings between the architectural and various trade drawings, including but not limited to structural, electrical, plumbing, fire protection and exterior enclosure systems. 7) All work shall conform to relevant BIS codes and shall be best practice of each trade. 8) Any discrepancy is to be brought to the notice of the architect/ consultant before commencement of the site. 9) All work is to be completed to the satisfaction of site engineer/ project manager and architects

27

05

0

16000

CENTER OF ROAD LEVEL LEVEL=0.0M

PLOT BOUNDARY

8800

38960 51° 17200

N

N=(-)3000 E=38840

N=(-)3000 E=17200

3210

ORIGIN N=0 E=0

21000

17500

P

Q

5600

LIFT PIT -1.5M

U

LIFT PIT -1.5M

0 2200

UGT -3.2M

N=(-)8600 E=14200 3000

0

9 271

0

00

0

67

19

24

0

UGT -3.2M

FORMATION LEVEL=0.15M

30 00 0

21400

90

0

29

19

67

6000

0

00 30

REVISION TABLE DATE

T

3000 N=(-)14600 E=14200

REVISION DESCRIPTION

PLINTH LEVEL=+0.6M

9800

21100

LIFT PIT -1.5M

R

S N=(-)24360 E=17200

N=(-)24360 E=38840

SHEET TITLE LINEOUT DRAWING SHEET NO.

001 VRUSHALI V KULKARNI T.Y B.ARCH

SEM-6

ACADEMY OF ARCHITECTURE 13/05/21

ROLL NO.

3756


11800

16600

17700

SW1

C6,C1,C15

SW2,SW3

SW4

C3,C7

C9,C11

SW5,SW7

C2,C4,C8,C10,C16,LW6 21400

C

D E

F

G H

J

K

300

27

05

0

14400

10760

CC1,C5,C12,C14

B

9300

00

A

GENERAL NOTES 1) All dimensions are in 'millimeters' unless specified. 2) The drawing is not to be scaled. The dimensions are strictly are to be followed. 3) All levels are unfinished levels unless specified. 4) The contractor shall verify all on site dimensions including elevations prior to the commencement of work on site. 5) The contractor shall inform the architect and/or project engineer on site regarding any conditions/modifications. 6) The contractor shall coordinate and verify the work indicated on the drawings between the architectural and various trade drawings, including but not limited to structural, electrical, plumbing, fire protection and exterior enclosure systems. 7) All work shall conform to relevant BIS codes and shall be best practice of each trade. 8) Any discrepancy is to be brought to the notice of the architect/ consultant before commencement of the site. 9) All work is to be completed to the satisfaction of site engineer/ project manager and architects

16000

CENTER OF ROAD LEVEL LEVEL=0.0M

20300

LAMP POST

PLOT BOUNDARY

21400

51° 300

17200

N=(-)3000 E=17200

3210

ORIGIN N=0 E=0

11

30900

SW3,SW4

10

30080

28220

9

SW1

N=(-)3300 E=17500

150 C1-600 x 600

N=(-)3150 E=29000

2680

2150

1115

N=(-)4210 E=31700 SW2 2600 x 300

N=(-)4210 E=29000

2590

Q C2-600 x 600 150

SW4 300 x 2500

11 10 9

N=(-)6950 E=38650

SW3 300 x 2500 N=(-)6950 E=33900

N=(-)8600 E=14200

N=(-)3000 E=38800

N=(-)3300 E=38500

2300MM x 1850MM

2200MM x 1850MM

N

1070

N=(-)4210 E=26500 SW1 300 x 3700

8

C3,C4

P

1450 1000

150

C1,SW2,C2

1860 790 1000

31870

9000

8

C3 -300 x 300

C4 -300 x 300

6790

U

ENTRY N=(-)13900 E=17500

7

C5,C6,C7,C8

3145

C5 -600 x 600

C6-600 x 600

DATE

N=(-)14600 E=14200

C9-300 x 300

C11,SW5

5

12200

SW6

4

11000

3

SW7,C12,C13

C10 -300 x 300

N=(-)24180 E=28000 C12 -600 x 600

5 SW6 300 x 2800

N=(-)24290 1850MM x 2200MM E=37600 150 C13-600 x 600

SW7 2500 x 300

S

6

SW5 2500 x 300

C11-300 x 300 N=(-)24180 E=17500

REVISION DESCRIPTION

N=(-)23100 E=38650

N=(-)21785 E=37600 N=(-)21785 E=35000

1050 1310

13530

REVISION TABLE

C8 -600 x 600

N=(-)17050 E=38650

N=(-)17050 E=35000

6

C9,C10

7

C7 -300 x 300

T

4725

18350

N=(-)13900 E=38500

N=(-)14050 E=33900 150

21300

N=(-)13900 E=28000

4 3

R N=(-)24400 E=38800

N=(-)24400 E=17200

SHEET TITLE

10500

21100

CENTERLINE DRAWING SHEET NO.

300

2

C14,C15,C16 00

1

N=(-)35200 E=17500

N=(-)35200 E=28000

300

C15 -600 x 600

C14 -600 x 600

002

2

N=(-)38500 E=28000 C16 -600 x 600

1

VRUSHALI V KULKARNI T.Y B.ARCH

SEM-6

ACADEMY OF ARCHITECTURE

A

B

C

D E

F

G H

J

K

13/05/21

ROLL NO.

SCALE-1:100

3756


LAMP POST

0

8800

05

16000

27

GENERAL NOTES 1) All dimensions are in 'millimeters' unless specified. 2) The drawing is not to be scaled. The dimensions are strictly are to be followed. 3) All levels are unfinished levels unless specified. 4) The contractor shall verify all on site dimensions including elevations prior to the commencement of work on site. 5) The contractor shall inform the architect and/or project engineer on site regarding any conditions/modifications. 6) The contractor shall coordinate and verify the work indicated on the drawings between the architectural and various trade drawings, including but not limited to structural, electrical, plumbing, fire protection and exterior enclosure systems. 7) All work shall conform to relevant BIS codes and shall be best practice of each trade. 8) Any discrepancy is to be brought to the notice of the architect/ consultant before commencement of the site. 9) All work is to be completed to the satisfaction of site engineer/ project manager and architects

51° 17200

N

38960

3210

ORIGIN N=0 E=0

17500

N=(-)3000 E=17200

N=(-)3000 E=38840

21000

P

Q LIFT PIT -1.5M

LIFT PIT -1.5M

15

31

5

11150

UGT -3.2M

15 73

24 31 0

5

BASEMENT LEVEL=-4.2M

N=(-)14150 E=38840

UGT -3.2M

V 0 31 30

U N=(-)14150 E=28340

REVISION TABLE

10500

DATE

REVISION DESCRIPTION

0 01 24

10150

0 90 29

21300

21100

11100

S

N=(-)24360 E=17200

T N=(-)24360 E=28300

SHEET TITLE BASEMENT LINEOUT DRAWING SHEET NO.

003 VRUSHALI V KULKARNI T.Y B.ARCH

SEM-6

ACADEMY OF ARCHITECTURE 13/05/21

ROLL NO.

SCALE-1:100

3756


300

2410

SW4

C3,C7

C9,C11

G

H J

K

L M

1920

455

1460

9300 2765

1460

1040

2680

2150

C2,C4,C8,C10,C16,SW6 21420

21420

SW2,SW3

20300

16340

C6,C13,C14

F

SW5,SW7

11800

SW1

E

14490

10770

TW4

D

6540

5080

C

TW3,TW10

B

TW2,TW5,TW6,TW9 3160

2700 TW11,TW12

C1,TW1,C5,TW7,TW8,C12,C14 300

00

A

N

1115

GENERAL NOTES 1) All dimensions are in 'millimeters' unless specified. 2) The drawing is not to be scaled. The dimensions are strictly are to be followed. 3) All levels are unfinished levels unless specified. 4) The contractor shall verify all on site dimensions including elevations prior to the commencement of work on site. 5) The contractor shall inform the architect and/or project engineer on site regarding any conditions/modifications. 6) The contractor shall coordinate and verify the work indicated on the drawings between the architectural and various trade drawings, including but not limited to structural, electrical, plumbing, fire protection and exterior enclosure systems. 7) All work shall conform to relevant BIS codes and shall be best practice of each trade. 8) Any discrepancy is to be brought to the notice of the architect/ consultant before commencement of the site. 9) All work is to be completed to the satisfaction of site engineer/ project manager and architects

P

3665

ORIGIN ORIGIN N=0 N=0 E=0 E=0 N=(-)3000 E=17200

12

30105 TW1,TW2,TW3,TW4,SW1

28240

C3,C4

27535

TW6

11 10 9

N=(-)3300 E=38500

SW2 (2600 x 300)

Q

N=(-)4210 E=29000

N=(-)4210 E=26500

N=(-)4210 E=31700

12

C2 (600 x 600)

SW3 SW1

N

13

SW4

(300 x 2500)

(300 x 3700)

(300 x 2500)

11

370

30895

SW3,SW4

P

N=(-)3210 E=20800

TW5

N=(-)3000 E=38840

(300 x 6000)

790 1075

13

1865

C1,C2

N=(-)3300 E=17500

TW1 (300 x 4000)

N=(-)4580 E=17350

TW2

TW3

TW4

(300 x 3700)

(300 x 3700)

(300 x 3700)

N=(-)4580 E=20350

N=(-)4580 E=22560

N=(-)6950 E=38650

N=(-)6950 E=33600

N=(-)4580 E=23720

10 9

C4 (300 x 300)

705

31970

N=(-)3150 E=29000

C3 (300 x 300) TW6

N=(-)7650 E=20800

4015

(300 x6000)

7

21265 20205 19330

C5,TW9,TW10,C6,C7,C8

6 5

TW8

4

TW12

8

N=(-)13920 E=22520

N=(-)13920 E=20550

TW7 (300 x 3900)

N=(-)13900 E=17500

TW9 (150 x 3700)

C5 (600 x 600)

N=(-)14050 E=33600

N=(-)13900 E=28000

TW10

C6 (600 x 600)

(300 x 3700)

21300

22485

TW7

TW11 (300 x 5400)

N=(-)12650 E=17350

N=(-)13900 E=38500

C7 (300 x 300)

C8 (600x600)

150

8

N=(-)11680 E=19900

875 1060 1220 1035

23520

TW11

N=(-)15050 E=17350

TW8

U N=(-)14150

N=(-)15850 E=19900

(300 x 3900)

E=28340

7 6 5

N=(-)17050 E=38650

N=(-)17050 E=35000

4 REVISION TABLE

C9 (300 x 300) C10 (300 x 300)

DATE

8215

N=(-)21785 E=37600 N=(-)21785 E=35000

REVISION DESCRIPTION

N=(-)23100 E=38650 SW5 (2500 x 300)

C11 (300 x 300)

SW6 (300 x 2800)

N=(-)24180 E=17500

11110

N=(-)24180 E=28000

C12 (600 x 600)

3

C12,C13

SW7

3

(2500 x 300)

T N=(-)24360 E=28300

N=(-)24360 E=17200

N=(-)24400 E=38800

10810

S

N=(-)24290 E=37600

C13 (600 x 600)

SHEET TITLE

300

2

C14,C15,C16 00

N=(-)35200 E=17500

N=(-)35200 E=28000

1

C14

C15

-600 x 600

2

N=(-)38500 E=28000 C16

-600 x 600

-600 x 600

1

BASEMENT CENTERLINE DRAWING SHEET NO.

004 VRUSHALI V KULKARNI

A

B

C

D

E

F

G

H J

K

L

M

N P

T.Y B.ARCH

SEM-6

ACADEMY OF ARCHITECTURE 13/05/21

ROLL NO.

SCALE-1:100

3756


300

2410

SW4

C3,C7

C9,C11

G

H J

K

L M

1920

455

9300

1460

2765

1460

1040

2680

2150

C2,C4,C8,C10,C16,SW6 21420

21420

SW2,SW3

20300

16340

C6,C13,C14

F

SW5,SW7

11800

SW1

E

14490

10770

TW4

D

6540

5080

C

TW3,TW10

B

TW2,TW5,TW6,TW9 3160

2700 TW11,TW12

C1,TW1,C5,TW7,TW8,C12,C14 300

00

A

N

1115

GENERAL NOTES 1) All dimensions are in 'millimeters' unless specified. 2) The drawing is not to be scaled. The dimensions are strictly are to be followed. 3) All levels are unfinished levels unless specified. 4) The contractor shall verify all on site dimensions including elevations prior to the commencement of work on site. 5) The contractor shall inform the architect and/or project engineer on site regarding any conditions/modifications. 6) The contractor shall coordinate and verify the work indicated on the drawings between the architectural and various trade drawings, including but not limited to structural, electrical, plumbing, fire protection and exterior enclosure systems. 7) All work shall conform to relevant BIS codes and shall be best practice of each trade. 8) Any discrepancy is to be brought to the notice of the architect/ consultant before commencement of the site. 9) All work is to be completed to the satisfaction of site engineer/ project manager and architects

P

3665

OVERALL FINISHED

B

21570

SSL=-3.6M

SSL=-3.6M

1800

KONE MRL LIFT 2200MM x1800MM

SUMP

20 21

22

1210

445

12

11

700

FIRE SHAFT 0.75M x 1.2M

D2 D2 31

30 29

28

02

03

04

05

06

07

08

09 10

11

950

C3 (300 x 300) 920

HIGH LOW VOLTAGE VOLTAGE SHAFT SHAFT

1590

8050

3960

D8

3685

4

TW12

21300

1840

975

3430

FLUSHING TANK 15 cu.m 3960

STP TANK 2.5M x 5M C5 (600 x 600)

ELECTRICAL ROOM 6.8M x 2.5M

SUMP

FFL=-4.235M SSL=-4.2M 4765

SSL=-3.6M

C6 (600 x 600)

5000

C8 (600x600)

5425

5

TW8

FFL=-4.165M SSL=-4.2M

SSL=-7.6M

C7 (300 x 300) 10500

1820 1420

3000

BOILER ROOM 5M x 3.3M

300MM THICK WALL

6

230MM THICK WALL

5

150MM THICK WALL

4 REVISION TABLE

C9 (300 x 300)

FFL=-4.235M SSL=-4.2M

2900

7

C10 (300 x 300) 9500

19330

6

A-301

8

1160

20205

C5,TW9,TW10,C6,C7,C8

BASEMENT

01

1520

21265

7

875 1060 1220 1035

22485

MONKEY LADDER (900MM WIDE)

21300

4015

3885 2145

10660

TW7

D4

2100

4280

D8

FFL=-4.235M SSL=-4.2M

8

SSL=-3.9M

D4

SSL=-4.2M 975

950

SSL=-3.9M

UP

5350

TW11

10 9

C4 (300 x 300)

27 26

4280

6210

23520

11

3070

4730

445 300

1475

PUMP ROOM 6.3M x 2.M

12

C2 (600 x 600)

STAIRCASE 13

1310

445

D3

SUMP

25

(300 x 2500)

01

MONKEY LADDER (900MM WIDE)

24

23

UP

2200MM x1800MM

SURVEILLANCE ROOM 4.5M x 3M FFL=-4.235M SSL=-4.2M

19

18

SW4

(300 x 3700)

RWH TANK 12 cu.m

17

1825

KONE MRL LIFT

SW1

15 16

13

11150

SSL=-3.6M

4200

4170

4170

4170

DOMESTIC TANK 18 cu.m

FIRE TANK 50 cu.m

14

2330

SW3 (300 x 2500)

1150

TW6

2450

2500

3780

27535

10 9

C3,C4

830

1230

2580

28240

11

1290

1690

1215

30105 TW1,TW2,TW3,TW4,SW1

2250 2450

950

12

C1 (600 x 600) 300

3070

30895

SW3,SW4

SW2 (2600 x 300)

790 1075

13

1865

C1,C2

705

31970

DATE

8215

5120

AC PLANT ROOM 5M x 5M

REVISION DESCRIPTION

10150

D8

D3

795

FFL=-4.235M SSL=-4.2M

2760

1565

4650

SW5 (2500 x 300)

D3

D3

C11

2615

(300 x 300)

FAN ROOM 2.5M x 2.5M FFL=-4.235M SSL=-4.2M

EXHAUST ROOM 2.5M x 2.5M

SW6 (300 x 2800)

FFL=-4.235M SSL=-4.2M

C12 (600 x 600)

11110

3

C12,C13

4620

2260

2540

SW7

C13 (600 x 600)

3

(2500 x 300)

10810

21570

SHEET TITLE BASEMENT PLAN 300

2

C14,C15,C16 00

2

1

C14

C15

C16

(600 x 600)

(600 x 600)

(600 x 600)

1

SHEET NO.

A-106 VRUSHALI V KULKARNI

A

B

C

D

E

F

G

H J

K

L

M

N P A-302 02

T.Y B.ARCH

SEM-6

ACADEMY OF ARCHITECTURE 13/05/21

ROLL NO.

SCALE-1:100

3756


A

B

D E

C

G H

F

GENERAL NOTES 1) All dimensions are in 'millimeters' unless specified. 2) The drawing is not to be scaled. The dimensions are strictly are to be followed. 3) All levels are unfinished levels unless specified. 4) The contractor shall verify all on site dimensions including elevations prior to the commencement of work on site. 5) The contractor shall inform the architect and/or project engineer on site regarding any conditions/modifications. 6) The contractor shall coordinate and verify the work indicated on the drawings between the architectural and various trade drawings, including but not limited to structural, electrical, plumbing, fire protection and exterior enclosure systems. 7) All work shall conform to relevant BIS codes and shall be best practice of each trade. 8) Any discrepancy is to be brought to the notice of the architect/ consultant before commencement of the site. 9) All work is to be completed to the satisfaction of site engineer/ project manager and architects

K

J

300 1000

2680

1115

2150

2590

1070

21645 21620

KONE MRL LIFT 2200MM x1800MM

14 15

16

17

10

370

6280

SW4 4730

SW1 445 300

LIFT LOBBY 1.5M x 1.5M

2580

D3

1210

445

2500

FIRE SHAFT 0.75M x 1.2M

700

UP D2 05 04

06

4280

850

2255

9

W1

D3

3230

03 02

950

950

H.V. SHAFT D4

L.V SHAFT D4

1025 1050

975

4500

8

C4 (300 x 300)

01

C3 (300 x 300)

1050

1310

2055

9160

STAIRCASE

(300 x 3700)

1330 600

4050 5840

AHU ROOM 3M x 3M

3900

1305

12 13

(300 x 2500)

SSF 003 SPIDER FITTING

1305

10 11

C2 (600 x 600)

2200MM x1800MM

445

8

09

300 300

1825

KONE MRL LIFT

3030

08

2330

3070

FROSTED GLASS PANEL (1400MM x 1200MM)

11

650

SW3 (300 x 2500)

5930

3070

700

5280

07

D4

900

650

C1 (600 x 600)

645

1305

950

1880

3520

1000

15690

1860

9

ACP PANEL (25 MM THICKNESS)

790

10

(2600 x 300)

1800

11

SW2

W7 5900

OVERALL FINISHED

1450

OVERALL UN-FINISHED

9000

6675

530 700 400

7520

700

D5

825

W3

21370

1620

4875

FFL=+0.635M SSL=+0.6M 5270

CERAMIC TILE (600 x 600)

20

02

19

03

18

04

C10 (300 x 300)

05

16

06

15

07

14

08

13

09

12

10

DATE

1440

3535

1200

16630

SW5

150

1000

W6

1440

1520 150

(2500 x 300)

5

150

1800

1190 2175

C12 (600 x 600)

1310

19120

KONE MRL LIFT

1470

1470

1470

1470

1470

1470

1470

1470

1470

3

(2500 x 300)

300

1470

1470

4

SW7

445

1200

1470

8000

SW6 (300 x 2800)

2200MM x1800MM

C13 (600 x 600) 9820

2150

445

LIFT LOBBY 1.5M x 1.5M

2850

(300 x 300) 1025 300 2515

1200

1310

C11

1050

REVISION DESCRIPTION

11

STAIRCASE 3385

3

REVISION TABLE

235

9545

1200

01

17

1200

4725

21

150MM THICK WALL

6

350

C9 (300 x 300)

1500

4

230MM THICK WALL

3560

1200

UP

2975

1200

GROUND 21M FLOOR PLAN x 21M

17605

5

300MM THICK WALL

1250

3585

1250

975

D3

1290

W5

UP

7

330

16490

6

21420

115 500 450

330

D3

W4

600

5395

10500

1600

795 950

C5 (600 x 600) RAMP

C8 (600x600)

1450 FFL=+0.615M 775

1500

795

500

MALE TOILET 4.6M x 1.9M

1125

500

C7 (300 x 300) FFL=+0.625M SSL=+0.4M

3145

500

W2

1625

4650

680

21420

21420

C6 (600 x 600)

700

FFL=+0.615M 145

D5

3050

25

STAINLESS STEEL RAILING

W2

FFL=+0.615M

01 D1

145

700

FFL=+0.625M SSL=+0.4M

705

500

795

D5

305

2170

5180

4000

1450

A-301

7

700

975

2320

FEMALE TOILET 4.6M x 1.9M

D3

UP

FFL=+0.625M SSL=+0.4M 2470

3675

1200

225

W2

D1

6000

ENTRY

TOILET 2.4M x 1.5M

775

FFL=+0.64M SSL=+0.6M

D3

975

5470

6790

8050

3700

D6

2650

675

1305

2000

1470

5530

750

2100 3000

1470

2500

21620 21645

10500

UP

UP

2200MM x1800MM

BUILDING LINE ABOVE

2

2

1

1

300

SHEET TITLE GROUND FLOOR PLAN SHEET NO.

A-101 VRUSHALI V KULKARNI T.Y B.ARCH

A

B

C

D E

F

G

H

K

J A-302 02

SEM-6

ACADEMY OF ARCHITECTURE 13/05/21

ROLL NO.

SCALE-1:100

3756


A

B

D E

C

G H

F

GENERAL NOTES 1) All dimensions are in 'millimeters' unless specified. 2) The drawing is not to be scaled. The dimensions are strictly are to be followed. 3) All levels are unfinished levels unless specified. 4) The contractor shall verify all on site dimensions including elevations prior to the commencement of work on site. 5) The contractor shall inform the architect and/or project engineer on site regarding any conditions/modifications. 6) The contractor shall coordinate and verify the work indicated on the drawings between the architectural and various trade drawings, including but not limited to structural, electrical, plumbing, fire protection and exterior enclosure systems. 7) All work shall conform to relevant BIS codes and shall be best practice of each trade. 8) Any discrepancy is to be brought to the notice of the architect/ consultant before commencement of the site. 9) All work is to be completed to the satisfaction of site engineer/ project manager and architects

K

J

300 1000

2680

2150

1115

1070

2590

21645 21620

5280

D4

SW3

17 18

19 20

21

22

KONE MRL LIFT 2200MM x1800MM

6280

SW4

700

UP D2 11

10 09

4280

850

2255

D3

3230

07

08

06

05 04

03 02

950

950

1460

975

H.V. SHAFT D4

L.V SHAFT D4

3375

750

6675

W3

D3

3560

01

20

02

19

03

18

04

5270

9545

06

15

07

14

08

13

09

12

10

705

REVISION TABLE

7520

32175

DATE

REVISION DESCRIPTION

235

1460

05

16

3560

17

17605

C10 (300 x 300)

2975

1460

21

150MM THICK WALL

6

300

C9 (300 x 300)

1460

150

3535 3385

1460

16605

SW5

150

1000

W6

1440

1520

11

STAIRCASE

1440

32175

32175 4725

W5 UP

FFL=+3.935M SSL=+3.9M

(2500 x 300)

5

C11 1310

(300 x 300) 1025 300 2515

150

1800

1190 2150

19120

C12 (600 x 600)

KONE MRL LIFT

SW6

4

(300 x 2800)

2200MM x1800MM

C13 (600 x 600)

SW7

445 9820

2150

LIFT LOBBY 1.5M x 1.5M

1310

1460

445

1050

230MM THICK WALL

1250

1315

975

FIRST FLOOR PLAN 21M x 32M

3

300MM THICK WALL

330

16490

CERAMIC TILE (600 x 600)

4

700

1620

4875

5

32125

450

330 795

D5

825

7

600

2200

C8 (600x600)

1450 FFL=+3.15M

1250

1460

D3

1125

5695

530 400 500

975

800

C5 (600 x 600)

W4

115

1460 1460

MALE TOILET 4.6M x 1.9M

FFL=+3.925M SSL=+3.7M 10500

W2

1625

4650

C7 (300 x 300)

700

700

795 305

795

D5

3025

C6 (600 x 600)

115

FFL=+3.915M 145

01 A-301

W2

D5

700

3730

2170

5180

FFL=+3.925M SSL=+3.7M

1450 145 FFL=+3.915M

775

5470 1460

2320

FEMALE TOILET 4.6M x 1.9M

700

FFL=+3.925M 3700SSL=+3.7M 2470

225

W2

275

D3 1200

1470

500

675 975

8050

1460

6790

TOILET 2.4M x 1.5M

975

D3

D6

2650

2000

3145

1330

2100

5530

6

8

C4 (300 x 300)

01

C3 (300 x 300)

1050

FIRE SHAFT 0.75M x 1.2M

600

LIFT LOBBY 1.5M x 1.5M

2580

1460

D3

1210

445

1600

3900

9875

445 300

2500

9

W1

775

1310

2055

9160

STAIRCASE

(300 x 3700)

3070

SW1

3070

4730

AHU ROOM 3M x 3M

SSF 003 SPIDER FITTING

7

10

370

(300 x 2500) 3520

4050

1460

15 16

C2 (600 x 600)

2200MM x1800MM

445

8

14

300 300

1825

KONE MRL LIFT

3030

13

2330

(300 x 2500)

5930

FROSTED GLASS PANEL (1400MM x 1200MM)

11

650

C1 (600 x 600)

650

12

1050

650

950

1880 900

1000

15690

1860

9

ACP PANEL (25 MM THICKNESS)

790

10

(2600 x 300)

1800

11

SW2

W7 5900

OVERALL FINISHED

1450

OVERALL UN-FINISHED

9000

3

(2500 x 300)

1460

8000

1460

1460

2220

10080

1460

1460

1460

13605

10500

1460

21315

2

1

650

1460

2 300

C14

1440

1440

1440

1440

1440

1440

(600 x 600)

1440

C15

1440

1440

1440

1440

1440

1440

(600 x 600)

1440

C16

1

SHEET TITLE FIRST FLOOR PLAN

(600 x 600)

SHEET NO.

21645 21645

A-102 VRUSHALI V KULKARNI T.Y B.ARCH

A

B

C

D E

F

G

H

K

J A-302 02

SEM-6

ACADEMY OF ARCHITECTURE 13/05/21

ROLL NO.

SCALE-1:100

3756


D E

C

300

9000

G H

F

1450 1000

2150

2680

K

J

1115

2590

1075

21645 21620

C1 (600 x 600) 5280

12

D4

SW3

19 20

21

22

6280

10

370

SW4

SW1

STAIRCASE

(300 x 3700) 445

LIFT LOBBY 1.5M x 1.5M

2580

2055

D3

1210

FIRE SHAFT 0.75M x 1.2M

700

UP D2 11

10 09

4280

850

2255

D3

3230

07

08

06

05 04

03 02

950

950

975

H.V. SHAFT D4

L.V SHAFT D4

3375

8

C4 (300 x 300)

01

C3 (300 x 300)

1050

445 300

2500

9

W1

1330 600

3900

1310

3070

4730

AHU ROOM 3M x 3M

SSF 003 SPIDER FITTING

9160

17 18

(300 x 2500) 3520

4050

2200MM x1800MM

2200MM x1800MM

445

8

15 16

C2 (600 x 600)

KONE MRL LIFT

KONE MRL LIFT

3030

14

300 300

1825

3070

FROSTED GLASS PANEL (1400MM x 1200MM)

13

2330

(300 x 2500)

5930

1050

650

11

650

950

1880 900

650

15690

9875

9

ACP PANEL (25 MM THICKNESS)

1860 790 1000

10

(2600 x 300)

1800

11

SW2

W7 5900

OVERALL FINISHED

B

OVERALL UN-FINISHED

A

GENERAL NOTES 1) All dimensions are in 'millimeters' unless specified. 2) The drawing is not to be scaled. The dimensions are strictly are to be followed. 3) All levels are unfinished levels unless specified. 4) The contractor shall verify all on site dimensions including elevations prior to the commencement of work on site. 5) The contractor shall inform the architect and/or project engineer on site regarding any conditions/modifications. 6) The contractor shall coordinate and verify the work indicated on the drawings between the architectural and various trade drawings, including but not limited to structural, electrical, plumbing, fire protection and exterior enclosure systems. 7) All work shall conform to relevant BIS codes and shall be best practice of each trade. 8) Any discrepancy is to be brought to the notice of the architect/ consultant before commencement of the site. 9) All work is to be completed to the satisfaction of site engineer/ project manager and architects

750

2100

6675

500

675 1555

275

305

115

1450 FFL=+7.215M 145

795

D5

W2

500

975

330

MALE TOILET 4.6M x 1.9M

1620

D3

3585

4875

150MM THICK WALL

DOWN C9 (300 x 300) 01

20

02

19

03

18

04

17 5270

17605 CERAMIC TILE (600 x 600)

05

16

06

15

07

14

08

13

09

12

10

REVISION TABLE DATE

REVISION DESCRIPTION

235

9545

6

C10 (300 x 300)

3560

FFL=+7.235M SSL=+7.2M

21

2975

24420

24420

1250

975

1290

W5

4725

230MM THICK WALL

330

16490

SECOND 21M FLOOR PLAN x 26M

6

300MM THICK WALL

W3 D5

825

7

C8 (600x600)

1450 FFL=+7.215M

1250

3145

FFL=+7.225M SSL=+7.2M 2500

D3

1125

5365

10500

795

C5 (600 x 600)

450

C7 (300 x 300)

C6 (600 x 600)

W4

540

4650

680

7

115

1625

24370

01 A-301

145

W2

D5

7520

2170

FFL=+7.225M SSL=+7.0M

1450 FFL=+7.215M

795

FEMALE TOILET 4.6M x 1.9M

24420

2320

5180

W2

FFL=+7.225M SSL=+7.0M 2470

3675

1200

600

975

8050 5470

6790

TOILET 2.4M x 1.5M

D3

975

D3

D6

2650

2000

1470

5530

1440

150

3535 3385

16630

150

5

1800

1190 2150

19125

C12 (600 x 600)

KONE MRL LIFT

1310

LIFT LOBBY 1.5M x 1.5M

SW6

4

(300 x 2800)

2200MM x1800MM

C13 (600 x 600)

SW7

445 9820

2150

445

(2500 x 300)

3

8000

3000

5850

2220

3000

5450

D7 19135

1365

FFL=+7.225M SSL=+6.9M 7405 7405

3

(300 x 300) 1025 300 2515

7705

4

(2500 x 300)

C11

1185 1310

5

SW5

150

1000

W6

1440

1520

11

STAIRCASE

SHEET TITLE 21045

SECOND FLOOR PLAN SHEET NO.

21650 21650

A-103 VRUSHALI V KULKARNI T.Y B.ARCH

A

B

C

D E

F

G H

K

J A-302 02

SEM-6

ACADEMY OF ARCHITECTURE 13/05/21

ROLL NO.

SCALE-1:100

3756


D E

C

300

9000

G H

F

1450 1000

2150

2680

K

J

1115

2590

1075

21645 21620

950

1880

C1 (600 x 600) 5280

12

D4

SW3

1420

17 18

19 20

21

22

6280

10

370

SW4

3900

9875

445 300

LIFT LOBBY 1.5M x 1.5M

2580

2055

D3

1420

445

2500

1210

700

FIRE SHAFT 0.75M x 1.2M

4280

UP D2 11

10 09

850

2255

9

W1

D3

3230

07

08

05 04

06

03 02

950

950

975

H.V. SHAFT D4 720

L.V SHAFT D4

3375

8

C4 (300 x 300)

01

C3 (300 x 300)

600

1310

445

9160

STAIRCASE

3070

SW1 (300 x 3700)

2240

AHU ROOM 3M x 3M

4730

(300 x 2500) 3520

4050

2200MM x1800MM

2200MM x1800MM

SSF 003 SPIDER FITTING

8

15 16

C2 (600 x 600)

KONE MRL LIFT

KONE MRL LIFT

3030

14

300 300

1825

3070

FROSTED GLASS PANEL (1400MM x 1200MM)

13

2330

(300 x 2500)

5930

1050

650

11

650

15690

900

650

620

ACP PANEL (25 MM THICKNESS)

1420

9

1860 790 1000

10

(2600 x 300)

1800

11

SW2

W7 5900

OVERALL FINISHED

B

OVERALL UN-FINISHED

A

GENERAL NOTES 1) All dimensions are in 'millimeters' unless specified. 2) The drawing is not to be scaled. The dimensions are strictly are to be followed. 3) All levels are unfinished levels unless specified. 4) The contractor shall verify all on site dimensions including elevations prior to the commencement of work on site. 5) The contractor shall inform the architect and/or project engineer on site regarding any conditions/modifications. 6) The contractor shall coordinate and verify the work indicated on the drawings between the architectural and various trade drawings, including but not limited to structural, electrical, plumbing, fire protection and exterior enclosure systems. 7) All work shall conform to relevant BIS codes and shall be best practice of each trade. 8) Any discrepancy is to be brought to the notice of the architect/ consultant before commencement of the site. 9) All work is to be completed to the satisfaction of site engineer/ project manager and architects

750 500

D3

530

3585

20

02

19

03

18

04

07

14

08 09

12

10

1520

235

13

3535 3385

7520

W6

150

5

1800

1190 2175

C13 (600 x 600) D7 9820

1470

1470

1500

1500

1470

1470

2150

1310

SW6 (300 x 2800)

2200MM x1800MM

1470

4

SW7 (2500 x 300)

3

300

8000

1470

KONE MRL LIFT

445

C12 (600 x 600)

2475

1090

445

LIFT LOBBY 1.5M x 1.5M

2850

1185 1310

1420

(2500 x 300)

(300 x 300) 1025 300 2515

REVISION DESCRIPTION

SW5

150

C11

1470

21420

21370 600

DATE

11

1440

STAIRCASE

REVISION TABLE

3560

06

15

1440

5270

1420

C10 (300 x 300)

05

16

150

6

01

17

CERAMIC TILE (600 x 600)

1420

150MM THICK WALL

350

1420

C9 (300 x 300)

21

3050

1420

W5

1000

3

230MM THICK WALL

DOWN

16630

4

300MM THICK WALL

775

W3 1620

4875

FFL=+10.535M SSL=+10.5M

5

700

115

D5

FFL=+10.515M

7

1250

975

1290

THIRD FLOOR PLAN 21M x 21M

6

W4

330

16490

4725

500

825

1250

3145

D3

775

1125

1420

10500

C8 (600x600)

1450

795

FFL=+10.525M SSL=+10.3M

C5 (600 x 600)

450

MALE TOILET 4.6M x 1.9M 330

975

680

4650

C7 (300 x 300)

400

115

W2

1625

1600

795

D5

1420 540

21420

C6 (600 x 600)

700

W2

FFL=+10.515M 145

3025

7

705

1470

D5

01 A-301

SPOT LEVEL=0.0M

145

FFL=+10.515M

305

FFL=+10.525M SSL=+10.3M

795

1450

FEMALE TOILET 4.6M x 1.9M

5180

700

275

2320

1420

W2

FFL=+10.525M SSL=+10.3M 2470

3675

1200

225

700

975

5470

6790

1420

8050

675

1330

TOILET 2.4M x 1.5M

D3

975

D3

D6

2650

2000

700

1420

2100

6650

5530

1470

FFL=+10.525M SSL=+10.2M

SHEET TITLE THIRD FLOOR PLAN SHEET NO.

A-104 VRUSHALI V KULKARNI T.Y B.ARCH

A

B

C

D E

F

G H

K

J A-302 02

SEM-6

ACADEMY OF ARCHITECTURE 13/05/21

ROLL NO.

SCALE-1:100

3756


A

B

D E

C

300

9000

1450 1000

K

J

1115

1075

2590

SW2

11 650

(2600 x 300)

1860 790 1000

22 8835

21

20

19 18

17 16

15 14

13

12

10

C2 (600 x 600)

2330

SLOPE 0.5%

1800

300 300

KONE MRL LIFT

KONE MRL LIFT

2200MM x1800MM

370

6280

SW4

2200MM x1800MM

1310

445

445 300

LIFT LOBBY 1.5M x 1.5M

1000

2580

8

1210

445

2920

FIRE D2 SHAFT 0.75M x 1.2M

4280

FFL=+13.835M SSL=+13.8M

D9

700

3070

STAIRCASE

3070

4730

(300 x 2500)

4700

9

2150

2680

11 10

G H

F

GENERAL NOTES 1) All dimensions are in 'millimeters' unless specified. 2) The drawing is not to be scaled. The dimensions are strictly are to be followed. 3) All levels are unfinished levels unless specified. 4) The contractor shall verify all on site dimensions including elevations prior to the commencement of work on site. 5) The contractor shall inform the architect and/or project engineer on site regarding any conditions/modifications. 6) The contractor shall coordinate and verify the work indicated on the drawings between the architectural and various trade drawings, including but not limited to structural, electrical, plumbing, fire protection and exterior enclosure systems. 7) All work shall conform to relevant BIS codes and shall be best practice of each trade. 8) Any discrepancy is to be brought to the notice of the architect/ consultant before commencement of the site. 9) All work is to be completed to the satisfaction of site engineer/ project manager and architects

FFL=+13.835M SSL=+13.8M

9

W1

DOWN 01

02 03

850

04

05

07 08

06

09 10

8

C4 (300 x 300)

11

C3 (300 x 300)

D9

FFL=+11.335M

1330

975 5530 4015

6790

MONKEY LADDER (900MM WIDE)

FIREFIGHTING TANK 25 cu.m

SLOPE 0.5% FFL=+14.1M SSL=+13.5M

01

5170

DOMESTIC TANK 10 cu.m

A-301

17305

7

7

FLUSHING TANK 7 cu.m

1660

230MM THICK WALL

D9

3490

FFL=+13.835M SSL=+13.8M

350

21

02

20

03

19

04

18

15

08

14

09

13

10

12

1520

STAIRCASE

150

3535 3385

LIFT LOBBY 1.5M x 1.5M

SW6 (300 x 2800)

445

2200MM x1800MM

4

SW7 (2500 x 300)

3

300

2300

2175

KONE MRL LIFT

2150

D9

5

1800

1310

(300 x 300) 1190 2515

445

1185 1310

3

W6

(2500 x 300)

C11

SLOPE 0.5%

REVISION DESCRIPTION

SW5

1000

4

DATE

11

1440

SLOPE 0.5%

REVISION TABLE

3560

16

07

235

4725

17

06

6

C10 (300 x 300)

2975

01

1440

C9 (300 x 300)

05

5

150MM THICK WALL

DOWN

FFL=+13.825M SSL=+13.5M

6

W5

1250

5080 1250

975

3145

TERRACE PLAN 21M x 21M

300MM THICK WALL

SHEET TITLE TERRACE LEVEL PLAN SHEET NO.

A-105 VRUSHALI V KULKARNI T.Y B.ARCH

A

B

C

D E

F

G H

K

J A-302 02

SEM-6

ACADEMY OF ARCHITECTURE 13/05/21

ROLL NO.

SCALE-1:100

3756


9300

10760

11800

14400

16600

17700

20300

CC1,C5,C12,C14

SW1

C6,C1,C15

SW2,SW3

SW4

C3,C7

C9,C11

SW5,SW7

C2,C4,C8,C10,C16,SW6 21400

B

C

D E

F

G H

J

K

300 00

A

GENERAL NOTES 1) All dimensions are in 'millimeters' unless specified. 2) The drawing is not to be scaled. The dimensions are strictly are to be followed. 3) All levels are unfinished levels unless specified. 4) The contractor shall verify all on site dimensions including elevations prior to the commencement of work on site. 5) The contractor shall inform the architect and/or project engineer on site regarding any conditions/modifications. 6) The contractor shall coordinate and verify the work indicated on the drawings between the architectural and various trade drawings, including but not limited to structural, electrical, plumbing, fire protection and exterior enclosure systems. 7) All work shall conform to relevant BIS codes and shall be best practice of each trade. 8) Any discrepancy is to be brought to the notice of the architect/ consultant before commencement of the site. 9) All work is to be completed to the satisfaction of site engineer/ project manager and architects

300 1450

1000

2680

2150

1115

1070

2590

OVERALL FINISHED

9000

21570

11 1000

10

(300 x 600)

6330

(300 x 2500)

150

SW4

PB4

PB23

PB22

6130

(300 x 330)

PB25

3130

8

C4 (300 x 300) C3 (300 x 300) PB6

(300 x 600)

3960

9

4480

PB5

(300 x 700)

(300 x 330)

PB3 (300 x 600)

(300 x 300)

4005

PB24

3430

(300 x 3700) 1280

PB21

1860

SW1

(300 x 330)

3430

(300 x 2500)

8

C3,C4

28220

SW3

(300 x 700)

11

C2 (600 x 600)

PB2

PB1

8560

3130

9

SW1

30080

C1 (600 x 600)

790

10

SW3,SW4

30900

SW2 (2600 x 300)

(300 x 300)

C1,SW2,C2

31870

2150

(300 x 450)

2150

2065

1770

21380

PB9 (300 x 600)

(300 x 650)

4480

3055

01 A-301

PB30

1715

(300 x 700)

PB28

PB8 (300 x 600)

6060

21300

PB7 (300 x 600)

6795

PB27

6520

(300 x 700)

(300 x 700)

6790

PB26

4455

PB29

3165(300 x 310)

(300 x 700)

PB20

2330 3790

21300

7

C5,C6,C7,C8

C5 (600 x 600)

PB10 4520

5420

C6 (600 x 600)

3810

5745

C7 (300 x 300)

C8 (600x600)

PB11

5050

(300 x 700)

7

PB12

4180

(300 x 700)

(300 x 700)

(300 x 300)

1570

6

(300 x 700)

PB34

PB14

3365

(300 x 330)

PB38

DATE

REVISION DESCRIPTION

4425

(300 x 450)

(300 x 450)

PB37

9930

REVISION TABLE (300 x 450)

PB33

4725

PB15

(300 x 700)

7035

PB32

4820

(300 x 700)

PB31

4550

6

C9,C10

(300 x 450)

(300 x 300)

4550

PB35

PB13

(300 x 700)

18350

PB36

3145

5420

5350

PB16 PB17

(300 x 450)

11000

5

PB40

(300 x 300)

PB39

1310

SW6 (300 x 2800)

C12 (600 x 600)

4

SW7

C13 (600 x 600)

4525

3

SW7,C12,C13

(300 x 300)

4

SW6

(2500 x 300)

1215

2595

12200

5

C11,SW5

1050

13530

SW5

(300 x 300)

4780

815

2160

PB18

3

(2500 x 300)

150

PB19

(300 x 700)

(300 x 700)

10500

21570

300

C14,C15,C16 00

2

2

1

1

300

C14

C15

C16

(600 x 600)

(600 x 600)

(600 x 600)

SHEET TITLE PLINTH BEAM PLAN SHEET NO.

A-106S VRUSHALI V KULKARNI T.Y B.ARCH

A

B

C

D E

F

G H

K

J A-302 02

SEM-6

ACADEMY OF ARCHITECTURE 13/05/21

ROLL NO.

SCALE-1:100

3756


9300

10760

11800

14400

16600

17700

20300

CC1,C5,C12,C14

SW1

C6,C1,C15

SW2,SW3

SW4

C3,C7

C9,C11

SW5,SW7

C2,C4,C8,C10,C16,SW6 21400

B

C

D E

F

G H

J

K

300 00

A

GENERAL NOTES 1) All dimensions are in 'millimeters' unless specified. 2) The drawing is not to be scaled. The dimensions are strictly are to be followed. 3) All levels are unfinished levels unless specified. 4) The contractor shall verify all on site dimensions including elevations prior to the commencement of work on site. 5) The contractor shall inform the architect and/or project engineer on site regarding any conditions/modifications. 6) The contractor shall coordinate and verify the work indicated on the drawings between the architectural and various trade drawings, including but not limited to structural, electrical, plumbing, fire protection and exterior enclosure systems. 7) All work shall conform to relevant BIS codes and shall be best practice of each trade. 8) Any discrepancy is to be brought to the notice of the architect/ consultant before commencement of the site. 9) All work is to be completed to the satisfaction of site engineer/ project manager and architects

300 1450

1000

2680

2150

1115

2590

1070

OVERALL UN-FINISHED

9000

21620

(300 x 2500)

705

B3

B10 (300 x 450)

13

6790

0

50

0

80

0

2400

10 80

4170

16

10

B37

2010

16

950

950

75

19

60

10

50 750 0

13 70

80

13

1950

72

0

FFL=+3.925M SSL=+3.7M 4480

1430

1430

13 1330

85

1100

4180

C8 (600x600)

(300 x 450)

(300 x 300)

FFL=+3.925M SSL=+3.7M

3145

5570

B15 (300 x 470)

815

3365

B40

(300 x 300)

1300

B41

(600 x 600) 9870

C7

300

4480

B16

1355

18

04

17

05

16

06

15

07

14

08

10

6 REVISION TABLE DATE

REVISION DESCRIPTION

3365

B20

C11

SW5

(300 x 300)

(2500 x 300)

815

1310

B21

5

1215

2800

2200

B44

(300 x 300)

2200

(300 x 300)

SW6 SW7

3

(2500 x 300)

C13

C12

(600 x 600)

(600 x 600)

B22

B23

9870

8050

(300 x 700)

10130

B46

(300 x 700)

B45

(300 x 700) 10155

B44

(300 x 700)

10500

10130

(300 x 700)

4

(300 x 2800)

2330

3

SW7,C12,C13

09

12

4700

10045 9620

11000

4

SW6

13

11

1050

12200

1270

03

B43

19

C10 (300 x 300)

4700

02

(300 x 300) 815

B42

20

(300 x 500)

01

B18

(300 x 300)

5

(300 x 330) 21

4700

B39

(300 x 700)

B39

(300 x 700)

B38

(300 x 700)

4725

FFL=+3.935M SSL=+3.9M

B17

(300 x 470)

B19

6

7

VOID

(300 x 470)

C9 (300 x 300)

(300 x 600)

(300 x 450)

(600 x 600)

B14

(300 x 500)

C6

1125

B13

C5

C11,SW5

32070

72

15

630

0

63 5

32070

1070

18

5870

10

4350

16

10

845

1570

1570

1350

10

950

16

850

4170

2430

2430

13530

(300 x 310)

B12 (300 x 300)

1070 14

15

C9,C10

1920

B36

B11 (300 x 470)

2430

01

18350

(300 x 600)

925

B35

(300 x 300)

B8 (300 x 300)

2550

73

VOID

(300 x 600)

73

0 63

13

70

700

830

1100

1330

8

1800

2050

B9

2125

(300 x 600)

B33

2050

5570

B34

B7 (300 x 300)

(300 x 700)

B6

(300 x 450)

B32

3130

B31

(300 x 310)

3430

4780

1850

(300 x 300)

0

9

DOWN

B5

A-301

7

(300 x 300)

B30

1280

B29

VOID

(300 x 700)

50

21300

(300 x 300)

2270

1860

B4 (300 x 300) 4005 3855

750

C5,C6,C7,C8

SW4

SW1

10320

11 10

(600 x 600)

(300 x 2500)

(300 x 300)

(300 x 2500)

8

C3,C4

28220

C2

(300 x 500)

VOID SW3

B28

9

SW1

30080

B2 1655

(300 x 340)

10

B27

SW3,SW4

(300 x 340)

30900

3100

11 1000

C1,SW2,C2

790

31870

300

2

2

C14,C15,C16

9870 9900

00

1

C14 -600 x 600

300

B25

C15 -600 x 600

B24 (300 x 700)

C16 -600 x 600

(300 x 700)

1

SHEET TITLE GROUND FLOOR BEAM LAYOUT SHEET NO.

21620

A-101S VRUSHALI V KULKARNI T.Y B.ARCH

A

B

C

D E

F

G H

K

J A-302 02

SEM-6

ACADEMY OF ARCHITECTURE 13/05/21

ROLL NO.

SCALE-1:100

3756


9300

10760

11800

14400

16600

17700

20300

CC1,C5,C12,C14

SW1

C6,C1,C15

SW2,SW3

SW4

C3,C7

C9,C11

SW5,SW7

C2,C4,C8,C10,C16,SW6 21400

B

C

D E

F

G H

J

K

300 00

A

GENERAL NOTES 1) All dimensions are in 'millimeters' unless specified. 2) The drawing is not to be scaled. The dimensions are strictly are to be followed. 3) All levels are unfinished levels unless specified. 4) The contractor shall verify all on site dimensions including elevations prior to the commencement of work on site. 5) The contractor shall inform the architect and/or project engineer on site regarding any conditions/modifications. 6) The contractor shall coordinate and verify the work indicated on the drawings between the architectural and various trade drawings, including but not limited to structural, electrical, plumbing, fire protection and exterior enclosure systems. 7) All work shall conform to relevant BIS codes and shall be best practice of each trade. 8) Any discrepancy is to be brought to the notice of the architect/ consultant before commencement of the site. 9) All work is to be completed to the satisfaction of site engineer/ project manager and architects

300 1450

1000

2680

2150

1115

2590

1070

OVERALL UN-FINISHED

9000

21620

B2 6280

SW4 (300 x 310)

3130

B29

4480

1850

8

C4 (300 x 300)

1920

B32

200

925

VOID

1800

5570

B33

(300 x 300)

(300 x 300)

B7

C3 (300 x 300)

1540

B31

(300 x 310)

3430

B6 (300 x 600) (300 x 700)

B5 (300 x 700)

1540

DOWN

VOID

3855

10320

(300 x 300)

B28

B27

1280

B4 (300 x 300) 4005

(300 x 300)

2270

SW1 (300 x 2500)

1860

9

(300 x 2500)

(300 x 300)

(300 x 600)

B26

(300 x 340)

(300 x 2500)

B3

11 10

(600 x 600)

SW3

8

C3,C4

28220

C2

(300 x 500)

VOID

B30

1655

B34

5330

(300 x 600)

705

B1 (300 x 600)

B25

9

SW1

30080

C1 (600 x 600)

(300 x 340)

10

3100

SW3,SW4

B24

30900

SW2 (2600 x 300)

(300 x 700)

11 1000

C1,SW2,C2

790

31870

B8

B10 (300 x 300)

1520

6640

B35

B9 (300 x 470)

(300 x 600)

1450 6520

1520 6520

300

6790

1450

(300 x 300)

5870

FFL=+3.925M SSL=+3.7M

01 A-301

1420

1500

1450

200

1450

300

1500

200

1450

1600

1660

1600

4180

(300 x 470)

815

3365

1600

02

C10 (300 x 300)

6

03

4700

B41

(300 x 700)

B38

04

17

05

16

06

15

07

14

08

13

09

12

10 11

4700

2420

18

B42

815

3

(300 x 500)

2450

01

19

9920

2430

B17

3365

B15

(300 x 470)

(300 x 330)

20

(300 x 300)

240

B37

(300 x 700)

9600

2430

B36

(300 x 700)

4725

50 34

1355

21

B16

FFL=+7.235M SSL=+7.2M

B14

7

VOID

(300 x 470)

DOWN C9 (300 x 300)

5 64

B40

FFL=+7.225M SSL=+6.9M

(300 x 600)

(300 x 300)

2100

2110

3145

(300 x 450) 5270

1270

(600 x 600)

B13

4480

REVISION TABLE

(300 x 500)

(300 x 450)

B12

DATE

REVISION DESCRIPTION

4700

(600 x 600)

C6

B39

B11

300

(300 x 300)

C5

C7

6

C9,C10

C8 (600x600)

9870

18350

32070

7

C5,C6,C7,C8

950

21300

32070

1400

1400

4480

3365

B18 140

5

B19

1930 1920

(300 x 300)

2200

B43

C12

2800

1215

(300 x 300)

1310

815

SW6

2120

200

2450

300

200

2610

2450

SW7

2330

2610

3

(2500 x 300)

C13 (600 x 600)

B20

B21

9870

10130

2430

B46

300

B45

10155

(300 x 700)

10130

2430

200

2430 200 2430 300

B44

(300 x 700)

8050

(300 x 700)

(300 x 700)

10500

4

(300 x 2800) 2210

(600 x 600)

3

SW7,C12,C13

(2500 x 300)

(300 x 700)

11000

4

SW6

SW5

(300 x 300)

2200

12200

5

C11,SW5

1050

13530

C11

140

(300 x 300)

2

C14,C15,C16

2120

00

1

200

C14 -600 x 600

300

2430

34

50

2160

300

2160

2430

50 34

2450

9870 300

2450

2210

2 2120

2450

200

(300 x 700)

2450

2030

B23

C15 -600 x 600

B22

9900 300

C16 -600 x 600

(300 x 700)

1

SHEET TITLE FIRST FLOOR BEAM LAYOUT SHEET NO.

21620

A-102S VRUSHALI V KULKARNI T.Y B.ARCH

A

B

C

D E

F

G H

K

J A-302 02

SEM-6

ACADEMY OF ARCHITECTURE 13/05/21

ROLL NO.

SCALE-1:100

3756


10760

11800

14400

16600

17700

SW1

C6,C1,C15

SW2,SW3

SW4

C3,C7

C9,C11

SW5,SW7

C2,C4,C8,C10,C16,LW6 21400

20300

9300

CC1,C5,C12,C14

B

C

D E

F

G H

J

K

300

9000

1450 1000

2680

2150

1115

2590

1075 OVERALL UN-FINISHED

300 00

A

GENERAL NOTES 1) All dimensions are in 'millimeters' unless specified. 2) The drawing is not to be scaled. The dimensions are strictly are to be followed. 3) All levels are unfinished levels unless specified. 4) The contractor shall verify all on site dimensions including elevations prior to the commencement of work on site. 5) The contractor shall inform the architect and/or project engineer on site regarding any conditions/modifications. 6) The contractor shall coordinate and verify the work indicated on the drawings between the architectural and various trade drawings, including but not limited to structural, electrical, plumbing, fire protection and exterior enclosure systems. 7) All work shall conform to relevant BIS codes and shall be best practice of each trade. 8) Any discrepancy is to be brought to the notice of the architect/ consultant before commencement of the site. 9) All work is to be completed to the satisfaction of site engineer/ project manager and architects

21570

1850

(300 x 2500)

SW4

4005

1920

B34

(300 x 600)

VOID

1800

B32

2125

(300 x 600)

5270

925

B7 (300 x 300)

B33

B6 (300 x 600)

(300 x 300)

8

B5 (300 x 700)

B31

B30

3130

B29

DOWN

VOID

3855

10320

(300 x 310)

(300 x 300)

B27

1280

B4 (300 x 300)

B28

(300 x 2500)

(300 x 300)

SW1 2270

9

(300 x 2500)

(300 x 300)

3430

B26

(300 x 340)

SW3

8

10

(600 x 600)

4180

B3

11

C2

(300 x 500)

VOID

(300 x 310)

705 1655

(300 x 700)

C3,C4

28220

B2

5330

B25

9

B1 (300 x 600)

(300 x 340)

SW1

C1 (600 x 600)

3100

SW3,SW4

10

SW2 (2600 x 300)

B24

30080

11 (300 x 700)

30900

C1,SW2,C2

1860 790 1000

31870

B8

B10 (300 x 300)

FFL=+10.525M SSL=+10.3M

5870

01 A-301

C6

C7

(600 x 600)

(300 x 300)

B39

2150

02

(300 x 300) 815

19

03

18

04

17

05

16

06

15

07

14

08

B41

20

(300 x 500)

01

B16

4700

(300 x 600)

B40

B17 (300 x 330)

13

09

12

10 11

9600

B15

(300 x 470)

4700

9920

B38

B37

(300 x 700)

1355

21

C10

6

(300 x 300)

REVISION TABLE DATE

REVISION DESCRIPTION

3365

B18 640

2735

(300 x 300)

C11

SW5

(300 x 300)

(2500 x 300)

B19

5

1215

C12 (600 x 600) 850

2800

2200

B43

(300 x 300)

2200

1940

840

(300 x 300)

SW6 SW7

2330 2340

2340

C13

2395

2240

655

185

1905

(2500 x 300)

3

(600 x 600)

B21

9870

8050

(300 x 700)

3175

B46 3175

B45

2150

10320

(300 x 300)

B20 (300 x 700)

4

(300 x 2800)

3200 (300 x 300)

3

B14

VOID

(300 x 470)

DOWN C9 (300 x 300)

815

B44

SW7,C12,C13

4

(300 x 300)

1300

16 65 2720

B36

(300 x 700)

FFL=+10.535M SSL=+10.5M

(300 x 300)

11000

SW6

5

3365

2675

4725 12200

C11,SW5

(300 x 470)

815

6

1185 1310

13530

FFL=+10.525M SSL=+10.3M

1270

(300 x 450) 5270

B42

(300 x 450)

B13

(300 x 500)

(600 x 600)

B12

4700

B11

950

C5

300

4480

2450

3145 C9,C10

7

C8 (600x600)

9870

18350

4180

2150

C5,C6,C7,C8

7

(300 x 700) 640

21300

24420

4480

24545

6640

6520

6520

B35

6790

B9 (300 x 470)

(300 x 600)

(300 x 300)

10350

B22

B23

(300 x 700)

(300 x 700)

21570

SHEET TITLE SECOND FLOOR BEAM LAYOUT SHEET NO.

A-103S VRUSHALI V KULKARNI T.Y B.ARCH

A

B

C

D E

F

G H

K

J A-302 02

SEM-6

ACADEMY OF ARCHITECTURE 13/05/21

ROLL NO.

SCALE-1:100

3756


10760

11800

14400

16600

17700

SW1

C6,C1,C15

SW2,SW3

SW4

C3,C7

C9,C11

SW5,SW7

C2,C4,C8,C10,C16,LW6 21400

20300

9300

CC1,C5,C12,C14

B

C

D E

F

G H

J

K

300 00

A

9000

1450 1000

2680

2150

1115

2590

1075 OVERALL UN-FINISHED

300

GENERAL NOTES 1) All dimensions are in 'millimeters' unless specified. 2) The drawing is not to be scaled. The dimensions are strictly are to be followed. 3) All levels are unfinished levels unless specified. 4) The contractor shall verify all on site dimensions including elevations prior to the commencement of work on site. 5) The contractor shall inform the architect and/or project engineer on site regarding any conditions/modifications. 6) The contractor shall coordinate and verify the work indicated on the drawings between the architectural and various trade drawings, including but not limited to structural, electrical, plumbing, fire protection and exterior enclosure systems. 7) All work shall conform to relevant BIS codes and shall be best practice of each trade. 8) Any discrepancy is to be brought to the notice of the architect/ consultant before commencement of the site. 9) All work is to be completed to the satisfaction of site engineer/ project manager and architects

21570

855

SW4

4780

1920

B32

VOID

(300 x 600)

925

B31

8

1800

2425

B8

200

B30

5570

(300 x 600)

B9

B10

(300 x 470)

(300 x 300)

6640

1475

FFL=+13.825M SSL=+13.6M

5870

200

200

6520

1475

300

B33

1450

(300 x 300)

(300 x 600)

B29

200

1605

B7 (300 x 300)

1450

B6

(300 x 300)

1850

(300 x 600)

1450

(300 x 310)

DOWN

B5 10320

B28

3130

B27

(300 x 310)

(300 x 300)

VOID

(300 x 700)

300 6520

6790 01

B26

B25

1280

2270

B4 (300 x 300) 4005

(300 x 300)

SW1

3855

A-301

9

(300 x 2500)

(300 x 300)

3430

B24

(300 x 340)

(300 x 2500)

B3

11 10

(600 x 600)

SW3

(300 x 2500)

8

C2

(300 x 500)

VOID

1655

(300 x 700)

C3,C4

28220

B2

5330

B23

9

B1 (300 x 600)

(300 x 340)

SW1

C1 (600 x 600)

3100

SW3,SW4

10

SW2 (2600 x 300)

B22

30080

11 (300 x 700)

30900

C1,SW2,C2

1860 790 1000

31870

1450

1450

300

200

1500

1510

1680

4180

(300 x 450)

(600 x 600)

(300 x 450)

(300 x 300)

FFL=+13.825M SSL=+13.6M

3365

B37

(300 x 300)

200

200

1300

815

6

1270

(300 x 300) 815

19

03

18

04

17

05

16

06

15

07

14

08

13

09

12

10

B39

11 4700

C10

6

(300 x 300)

B40

02

REVISION TABLE DATE

REVISION DESCRIPTION

4700

01

20

(300 x 500)

B36

50 34 9620

3

(300 x 330)

B16

9920

2430

300

B35

(300 x 700)

80

B15

(300 x 470)

21

2430

2430 300

FFL=+13.835M SSL=+13.8M

2430

(300 x 700)

B34

SW7,C12,C13

3365

B18 200

200

C11

SW5

(300 x 300)

(2500 x 300)

815

B19

5

1215

C12

2150 2120

200

2450

300

2610

2450

200

8050 2610

SW6 SW7

2630

(2500 x 300)

3

(600 x 600)

B21

B20

4

(300 x 2800)

C13

(600 x 600)

2775

2200

B41

2200 9870

(300 x 300)

2005

(300 x 300) 2005

4

1355

B17

4725 11000

SW6

B14

7

VOID

(300 x 470)

C9 (300 x 300)

1185 1310

12200

5

(300 x 470)

2030

2030

5570

(300 x 300)

C11,SW5

B13

B38

(600 x 600)

B12

(300 x 600)

B11

(300 x 500)

C5

300

4480

C7 950

C6

36

13530

C8 (600x600)

3145 C9,C10

1680

1655

10020

18350

21370

1285 1500

4700

C5,C6,C7,C8

7

1360

(300 x 700)

21300

21370

1435

4480

(300 x 700)

(300 x 700)

21570

SHEET TITLE

SHEET NO.

A-104S VRUSHALI V KULKARNI T.Y B.ARCH

A

B

C

D E

F

G H

K

J A-302 02

SEM-6

ACADEMY OF ARCHITECTURE 13/05/21

ROLL NO.

SCALE-1:100

3756


10760

11800

14400

16600

17700

SW1

C6,C1,C15

SW2,SW3

SW4

C3,C7

C9,C11

SW5,SW7

C2,C4,C8,C10,C16,LW6 21400

C

D E

F

G H

J

K

300

8

(300 x 310)

B17

B16

B2 (300 x 500)

B13

C3,C4

28220

10 (300 x 310)

9

B1

(300 x 300)

SW1

1075

2590

(300 x 500)

B15

30080

1115

11

B14

SW3,SW4

2150

2680

(300 x 300)

30900

10

1450 1000

(300 x 310)

11

9000

1860 790 1000

C1,SW2,C2

31870

20300

9300

CC1,C5,C12,C14

B

300 00

A

GENERAL NOTES 1) All dimensions are in 'millimeters' unless specified. 2) The drawing is not to be scaled. The dimensions are strictly are to be followed. 3) All levels are unfinished levels unless specified. 4) The contractor shall verify all on site dimensions including elevations prior to the commencement of work on site. 5) The contractor shall inform the architect and/or project engineer on site regarding any conditions/modifications. 6) The contractor shall coordinate and verify the work indicated on the drawings between the architectural and various trade drawings, including but not limited to structural, electrical, plumbing, fire protection and exterior enclosure systems. 7) All work shall conform to relevant BIS codes and shall be best practice of each trade. 8) Any discrepancy is to be brought to the notice of the architect/ consultant before commencement of the site. 9) All work is to be completed to the satisfaction of site engineer/ project manager and architects

9 8

B3

B4

(300 x 500)

(300 x 500)

B5

6790

(300 x 500)

01 A-301

21300

C5,C6,C7,C8

7

7 B6

3145

(300 x 500)

18350

C9,C10

B7 (300 x 500)

6

6 B8

B9

(300 x 300)

(300 x 330)

4725

REVISION TABLE

12200 11000

C11,SW5 SW6 SW7,C12,C13

5 4 3

1185 1310

13530

DATE

B10

B11

(300 x 300)

(300 x 300)

REVISION DESCRIPTION

5 4 3

B12 (300 x 300)

SHEET TITLE TERRACE LEVEL PLAN SHEET NO.

A-105 VRUSHALI V KULKARNI T.Y B.ARCH

A

B

C

D E

F

G H

K

J A-302 02

SEM-6

ACADEMY OF ARCHITECTURE 13/05/21

ROLL NO.

SCALE-1:100

3756


11 10

9

8

7

6

4 3

5

2

GENERAL NOTES 1) All dimensions are in 'millimeters' unless specified. 2) The drawing is not to be scaled. The dimensions are strictly are to be followed. 3) All levels are unfinished levels unless specified. 4) The contractor shall verify all on site dimensions including elevations prior to the commencement of work on site. 5) The contractor shall inform the architect and/or project engineer on site regarding any conditions/modifications. 6) The contractor shall coordinate and verify the work indicated on the drawings between the architectural and various trade drawings, including but not limited to structural, electrical, plumbing, fire protection and exterior enclosure systems. 7) All work shall conform to relevant BIS codes and shall be best practice of each trade. 8) Any discrepancy is to be brought to the notice of the architect/ consultant before commencement of the site. 9) All work is to be completed to the satisfaction of site engineer/ project manager and architects

1 STAIRCASE MUMTY

OHT 6000MM x3000MM x2000MM

STAIRCASE MUMTY +18.335M

LIFT KONE MRL OF SIZE 2200MM x1800MM -17.5M

OHT +16.675M

BRICK WALL OF THICKNESS 150MM

-8.8M

STAIRCASE MUMTY

-17.5M

D9

PARAPET WALL +15.175M

D9

MONKEY LADDER

0.00M

TERRACE FLOOR +13.8M

0.00M

THIRD FLOOR +10.5M

0.00M

TERRACE

COPING

SECOND FLOOR +7.2M

N

0.00M

FIRST FLOOR +3.9M GLASS PANEL (1200MM x 1650MM x25MM FROSTED GLASS CANOPY (6000MM x 3000MM)

D1 -0.15M

RCC COLUMN (600MM x 600MM) AT SPAN OF 10500MM

D1 -0.15M

GLASS DOUBLE DOOR

PLINTH LEVEL +0.635M GROUND LEVEL +0.0M

STAIRCASE

+3.0M +3.3M +3.6M +3.9M

RAMP

01 A-201

A

B

D E

C

G H

F

K

J

ARCHITECTURAL ELEVATION WEST FACING ELEVATION

STAIRCASE MUMTY +18.335M

REVISION TABLE

STAIRCASE MUMTY

REVISION DESCRIPTION

DATE LIFT KONE MRL OF SIZE 2200MM x1800MM

-13.1M

-26.5M

-10.5M STAIRCASE MUMTY

D9

PARAPET WALL +15.175M

D9

TERRACE FLOOR +13.835M

-10.5M ACP PANEL (25MM THICKNESS)

D7

TERRACE

THIRD FLOOR +10.535M PLUMBING SHAFT

-7.7M

D7 UP

01 COPING UP

SECOND FLOOR +7.235M

2200MM x1800MM

02

GLASS PANEL (1200MM x 1650MM x25MM

0.0M

GLASS CANOPY(5000MMx 6000MM)

FIRST FLOOR +3.935M

TENSION ROD

SHEET TITLE

-10.5M SPIDER FITTING

2390

0.0M

FROSTED GLASS CANOPY (6000MM x 5000MM)

0.0M 0.0M

ELEVATION

RCC COLUMN (600MM x 600MM) AT SPAN OF 10500MM

SHEET NO.

PLINTH LEVEL +0.635M GROUND LEVEL +0.0M

A-201 VRUSHALI V KULKARNI T.Y B.ARCH

SEM-6

ACADEMY OF ARCHITECTURE 02 A-201

ARCHITECTURAL ELEVATION NORTH FACING ELEVATION

13/05/21

ROLL NO.

SCALE-1:100

3756


1

2

3

4

8

7

6

5

GENERAL NOTES 1) All dimensions are in 'millimeters' unless specified. 2) The drawing is not to be scaled. The dimensions are strictly are to be followed. 3) All levels are unfinished levels unless specified. 4) The contractor shall verify all on site dimensions including elevations prior to the commencement of work on site. 5) The contractor shall inform the architect and/or project engineer on site regarding any conditions/modifications. 6) The contractor shall coordinate and verify the work indicated on the drawings between the architectural and various trade drawings, including but not limited to structural, electrical, plumbing, fire protection and exterior enclosure systems. 7) All work shall conform to relevant BIS codes and shall be best practice of each trade. 8) Any discrepancy is to be brought to the notice of the architect/ consultant before commencement of the site. 9) All work is to be completed to the satisfaction of site engineer/ project manager and architects

10 11

9

BUND WALL

STAIRCASE MUMTY +18.335M

STAIRCASE MUMTY

PARAPET WALL +15.175M

W4

W4

DOWNTAKE PIPE

W1

W6

TERRACE FLOOR +13.835M

W5 PLUMBING SHAFT

W4

W4

THIRD FLOOR +10.535M

W1

W6

LOUVERED AWNING WINDOW

W5

W4

W4 SECOND FLOOR +7.235M

N

W1

W6

GLASS PANEL (1200MM x 1650MM x25MM

W5 1.30M

0.00M

0.00M

W4

FIRST FLOOR +3.935M

0.00M

W4 W1

W6

SLIDING WINDOW

RCC COLUMN (600MM x 600MM) AT SPAN OF 10500MM

W5

STORM WATER DRAIN

PLINTH LEVEL +0.635M

TRIMIX FLOORING

GROUND LEVEL +0.0M

PCC (150MM THICK)

01 A-202

K

J

H G

F

E D

B

C

ARCHITECTURAL ELEVATION EAST FACING ELEVATION

A REVISION TABLE DATE

STAIRCASE MUMTY +18.335M

REVISION DESCRIPTION

BUND WALL

STAIRCASE MUMTY

PARAPET WALL +15.175M

PARAPET WALL

TERRACE FLOOR +13.835M

W7 02 SLIDING WINDOW UP

01

THIRD FLOOR +10.535M

UP

2200MM x1800MM

PLUMBING SHAFT

W7

DOWNTAKE PIPE (25MM THICK ACP CLADDED)

SECOND FLOOR +7.235M -4.70M

SHEET TITLE

0.00M

0.00M

+0.15M

W7 GLASS PANEL (1200MM x 1650MM x25MM

FIRST FLOOR +3.935M

ELEVATION SHEET NO.

A-202

W7

STORM WATER DRAIN

VRUSHALI V KULKARNI

PLINTH LEVEL +0.635M GROUND LEVEL +0.0M

T.Y B.ARCH TRIMIX FLOORING PCC (150MM THICK)

02 A-202

ARCHITECTURAL ELEVATION SOUTH FACING ELEVATION

SEM-6

ACADEMY OF ARCHITECTURE 13/05/21

ROLL NO.

SCALE-1:100

3756


11

8

7

6

5

4

3

GENERAL NOTES 1) All dimensions are in 'millimeters' unless specified. 2) The drawing is not to be scaled. The dimensions are strictly are to be followed. 3) All levels are unfinished levels unless specified. 4) The contractor shall verify all on site dimensions including elevations prior to the commencement of work on site. 5) The contractor shall inform the architect and/or project engineer on site regarding any conditions/modifications. 6) The contractor shall coordinate and verify the work indicated on the drawings between the architectural and various trade drawings, including but not limited to structural, electrical, plumbing, fire protection and exterior enclosure systems. 7) All work shall conform to relevant BIS codes and shall be best practice of each trade. 8) Any discrepancy is to be brought to the notice of the architect/ consultant before commencement of the site. 9) All work is to be completed to the satisfaction of site engineer/ project manager and architects

2

N

STAIRCASE MUMTY +18.335M B2 (300 x 500)

B7 (300 x 300)

HOISTING

4450

C2 (600 x 600)

C4 (300 x 300)

C10 (300 x 300)

BRICK WALL OF THICKNESS 230MM

6090

3990

6090

OHT +16.675M

TERRACE

BRICK BAT COBA (300MM)

SW5 (2500 x 300)

SW7 (2500 x 300)

FFL=+13.835M SSL=+13.6M

FLUSHING TANK

300

W1 B8 (300 x 300) B9 (300 x 470)

TOILET FFL=+10.515M SSL=+10.3M

STAIRCASE MID LANDING

W2

W2

B13 (300 x 470)

TOILET

COPING

STAIRCASE 11

LIFT

09

W2

W5

08

LIFT KONE MRL OF SIZE 2200MM x1800MM SLIDING WINDOW

07

LOUVRE WINDOW(700MMx1000MM)

06

W3

3090

W2

05 04

FFL=+7.235M SSL=+7.2M

03 02 01

SUNK SLAB (300MM)

B13 (300 x 470)

TOILET

B17 (300 x 330)

B14 (300 x 470)

W6

RCC BEAM (300MM x 600MM)

B23 (300 x 330)

FEMALE TOILET 09

W2

08 07 06

W3

W2

BRICK WALL OF THICKNESS 150MM 2340

2080

W2

W5

2815

11

10

MALE TOILET

LINTEL (150MM x 300MM) WAFFLE SLAB (200MM x 300MM)

STAIRCASE

D4 LOW VOLTAGE SHAFT

GLASS FACADE 25MM THICK

685

D4

FFL=+3.925M SSL=+3.7M

B7 (300 x 300)

B23 (300 x 450)

PLYWOOD PARTITION WALL (25MMTHICK)

MALE TOILET

B9 (300 x 470)

B2 (300 x 500)

W6

FEMALE TOILET

B8 (300 x 300)

STAIRCASE MID LANDING

B17 (300 x 330)

B14 (300 x 470)

D6 W1

PLASTERING(25MM)

10

W2 SECOND FLOOR +7.235M

BRICK BAT COBA

W3

W2

PARAPET WALL (300MM x 900MM)

STAIRCASE MID LANDING B7 (300 x 300)

POLYURETHANE

FFL=+10.535M SSL=+10.5M

FFL=+7.225M SSL=+7.0M

B2 (300 x 500)

IPS FLOORING SCREEDING

W5

B8 (300 x 300) B9 (300 x 470)

HOISTING ROPE

SW6 (300 x 2800)

2780

W1

W6

C4 (300 x 300)

STAIRCASE

D6

THIRD FLOOR +10.535M

B17 (300 x 330)

C8 (600x600)

MALE TOILET

D4

3090

B7 (300 x 300)

FEMALE TOILET

B14 (300 x 470)

3090

B2 (300 x 500)

B13 (300 x 470)

2490

TERRACE FLOOR +13.835M

OHT 6000MM x3000MM x2000MM

DOMESTIC TANK

FIRE FIGHTING TANK

8275

PARAPET WALL +15.175M

SPIDER FITTING

05 04

965

03 02

B8 (300 x 300) B15 (300 x 470)

TOILET FFL=+0.625M SSL=+0.4M

FEMALE TOILET

STAIRCASE MID LANDING B2 (300 x 500)

B16 (300 x 470)

CERAMIC TILE(600MMx600MMx10MM)

B19 (300 x 330)

B25 (300 x 700)

W6

2910

B11 (300 x 470)

01

11

MALE TOILET W2

W2

2460

D4

W5

NOSING

08

RCC COLUMN (600MM x 600MM) AT SPAN OF 10500MM

07 06

W3

W2

05 04 03

C16 (600 x 600)

02

200

B2 (300 x 500)

01

LIFT PIT

+0.0M

1625

4390

STAIRCASE MID LANDING

ELECTRICAL ROOM

4090

GROUND LEVEL +0.0M

FFL=+0.635M SSL=+0.6M

D6 3840

PLINTH LEVEL +0.635M

REVISION DESCRIPTION

DATE

STAIRCASE

10

B7 (300 x 300)

REVISION TABLE

RCC BEAM (300MM x600MM)

09

1465

W1

COUNTERWEIGHT

3115

FFL=+3.935M SSL=+3.9M

D6

FIRST FLOOR +3.935M

BASEMENT FFL=-4.235M SSL=-4.2M

BASEMENT -4.165M

D4

UP

01

UP

2200MM x1800MM

02

02

A-302

ARCHITECTURAL SECTION

SHEET TITLE

SECTION THROUGH BASEMENT ,TOILET AND STAIRCASE SECTION SHEET NO.

A-302 VRUSHALI V KULKARNI T.Y B.ARCH

SEM-6

ACADEMY OF ARCHITECTURE 13/05/21

ROLL NO.

SCALE-1:100

3756


B

E

C

F

K

G

COPING FOR PARAPET WALL

DRIP MOULD

GENERAL NOTES 1) All dimensions are in 'millimeters' unless specified. 2) The drawing is not to be scaled. The dimensions are strictly are to be followed. 3) All levels are unfinished levels unless specified. 4) The contractor shall verify all on site dimensions including elevations prior to the commencement of work on site. 5) The contractor shall inform the architect and/or project engineer on site regarding any conditions/modifications. 6) The contractor shall coordinate and verify the work indicated on the drawings between the architectural and various trade drawings, including but not limited to structural, electrical, plumbing, fire protection and exterior enclosure systems. 7) All work shall conform to relevant BIS codes and shall be best practice of each trade. 8) Any discrepancy is to be brought to the notice of the architect/ consultant before commencement of the site. 9) All work is to be completed to the satisfaction of site engineer/ project manager and architects

STAIRCASE MUMTY +18.335M STAIRCASE MUMTY IPS FLOORING SCREEDING 25MM THICK BUND

OHT +16.675M

POLYURETHANE

PARAPET WALL +15.175M

2000

4165

FIREFIGHTING TANK D9

D9

OHT 6000MM x3000MM x2000MM

SSL=13.6M

N

FFL=+13.835M SSL=+13.6M

TERRACE FLOOR +13.835M

B36 B34

B31

B32

(300 x 700)

(300 x 600)

(300 x 600)

(300 x 600)

PLASTERING(25MM)

WAFFLE SLAB (200MM x 300MM)

PLUMBING SHAFT

FEMALE TOILET

D3 LIFT LOBBY

D3

FFL=+10.535M SSL=+10.5M

FFL=+10.515M SSL=+10.3M

PATLI (RCC TRANSOM)

1015

AHU ROOM

2655

2200

2940

B24 (300 x 700)

THIRD FLOOR +10.535M

SCURTING

B26 (300 x 700)

B38

B33

B34

(300 x 700)

B36

(300 x 600)

(300 x 600)

(300 x 600)

FEMALE TOILET

LINTEL (150MM x 150MM)

AHU ROOM

SPIDER FITTING

LIFT LOBBY

D3

GLASS FACADE 25MM THICK

FFL=+7.235M SSL=+7.2M

SECOND FLOOR +7.235M

SILL (150MM x 150MM)

D3 FFL=+7.225M SSL=+7.0M

SEVICE SLAB B26 (300 x 700)

B38

B33

B34

(300 x 700)

B36

(300 x 600)

(300 x 600)

(300 x 600)

C2 (600 x 600)

BRICK WALL OF THICKNESS 150MM

FEMALE TOILET

AHU ROOM LIFT LOBBY

D3

LIFT KONE MRL OF SIZE 2200MM x1800MM

D3

BRICK WALL OF THICKNESS 230MM

FFL=+3.935M SSL=+3.9M

FIRST FLOOR +3.935M

DIAGRID (200MM x 300MM)

FFL=+3.925M SSL=+3.7M

B28 (300 x 700)

B40

B35

B36

(300 x 700)

(300 x 600)

B38

(300 x 600)

(300 x 600)

LIFT LOBBY

WAFFLE SLAB (200MM x 300MM)

D3

2900

2200

2390

2490

AHU ROOM

LOUVRE WINDOW(700MMx1000MM)

FEMALE TOILET D3

NOSING

CERAMIC TILE(600MMx600MMx10MM)

FFL=+0.635M SSL=+0.6M

PLINTH LEVEL +0.635M GROUND LEVEL +0.0M

3090

2790

TENSION ROD GLASS CANOPY(5000MMx 6000MM)

FFL=+0.625M SSL=+0.4M

SCREEDING 25MM THICK BRICK BAT COBA(200MMTHICK)

BB15

BB21 (300 x 700)

(300 x 700)

BB22

BB23

(300 x 600)

(300 x 600)

LIFT LOBBY SURVEILLANCE ROOM

BB26

BB25

(300 x 330)

(300 x 600)

REVISION TABLE

ELECTRICAL ROOM

REVISION DESCRIPTION

DATE

FLUSHING TANK SSL=-3.6M

BASEMENT FFL=-4.235M SSL=-4.2M

BASEMENT -4.165M STP SSL=-4.2M

RUBBLE SOLING BACK FILLING

UP

01

UP

2200MM x1800MM

02

SHEET TITLE SECTION 01

A-301

ARCHITECTURAL SECTION SECTION THROUGH BASEMENT ,TOILET AND ADVANCED SLAB

SHEET NO.

A-301 VRUSHALI V KULKARNI T.Y B.ARCH

SEM-6

ACADEMY OF ARCHITECTURE 13/05/21

ROLL NO.

SCALE-1:100

3756


K

F

G

E C3 (300 x 300)

NEWEL POST OF DIAMETER 50MM

NEWEL POST OF DIAMETER 50MM HOLLOW CIRCULAR SECTION WELDED TO BASEPLATE OF1 0MM THICKNESS

BUND WALL

C4 (300 x 300) WATERPROOFING

10MM THICK M S PLATE (100MM x10MM) TO CONNECT NEWEL POST TO FLOOR

C3 (300 x 300) SW4 (300 x 2500)

STAIRCASE MUMTY

POST OF DIAMETER 50MM HOLLOW CIRCULAR SECTION WELDED TO BASEPLATE OF10MM THICKNESS

20MMØ BALUSTERS - STAINLESS STEEL HOLLOW CIRCULAR SECTIONS WHICH IS WELDED TO BASEPLATE

1735

TERRACE FLOOR +13.835M

FLOOR LANDING

120

116

HANDRAIL OF 50MM HOLLOW BOX SECTION WELDED TO BALUSTER

FFL=-2.515M 18 17

10MM THICK M S PLATE (100MM x10MM) TO CONNECT NEWEL POST TO FLOOR

FFL=+13.825M

16

B29 (300 x 330)

117

14

115

114

13

113 111

FFL=11.585M

110 109 108

B30 (300 x 330)

11

300

10 MM THICK RISER TILE- CERAMIC TILE WITH MATTE FINISH,ANTI-SKID , BULL NOSE FINISH(1500MMx300)

2095

10

107

10 MM THICK FLOOR TILING- CERAMIC TILE WITH MATTE FINISH,ANTI-SKID , BULL NOSE FINISH(1500MMx300)

09 106

ANCHOR FASTENER

12

112

1475

MIDDLE LANDING

MS BASEPLATE OF 12MM THICKNESS

10MM TREAD TILE- CERAMIC TILE WITH MATTE FINISH,ANTI-SKID , BULL NOSE FINISH(1500MMx300)

15

118

W1

MIDDLE LANDING

NEWEL POST OF DIAMETER 50MM HOLLOW CIRCULAR SECTION WELDED TO BASEPLATE OF1 0MM THICKNESS

3150

D3

905

C4 (300 x 300)

105 104

20MMØ BALUSTERS - STAINLESS STEEL HOLLOW CIRCULAR SECTIONS WHICH IS WELDED TO BASEPLATE

D3 103 102 101

BASEMENT

08

10 MM THICK FLOOR TILINGCERAMIC TILE WITH MATTE FINISH,ANTI-SKID ,BULL NOSE FINISH(1500MMx300)

FFL=-4.165M 25MM THICK PLASTERING

FLOOR LANDING

100

FFL=+10.535M

99 98

12

W1 96 94

B31 (300 x 330)

95

25MMM THICK SCREEDING

93

92 91 MIDDLE LANDING FFL=8.285M

87

LIFT WELL

90

89

SW3

1500

THIRD FLOOR +10.535M

(300 x 2500)

88 86

85

B32 (300 x 330)

84

83

HANDRAIL OF 50MM HOLLOW BOX SECTION WELDED TO BALUSTER

D3

82

A-401e

79

150MM THICKNESS SLAB

SCALE1:20

230MM RUBBLE SOLING

FLOOR LANDING

78

N

150MM THICKNESS SLAB

DETAILED SECTION

81 80 FFL=+7.235M

77

SECOND FLOOR +7.235M

GENERAL NOTES 1) All dimensions are in 'millimeters' unless specified. 2) The drawing is not to be scaled. The dimensions are strictly are to be followed. 3) All levels are unfinished levels unless specified. 4) The contractor shall verify all on site dimensions including elevations prior to the commencement of work on site. 5) The contractor shall inform the architect and/or project engineer on site regarding any conditions/modifications. 6) The contractor shall coordinate and verify the work indicated on the drawings between the architectural and various trade drawings, including but not limited to structural, electrical, plumbing, fire protection and exterior enclosure systems. 7) All work shall conform to relevant BIS codes and shall be best practice of each trade. 8) Any discrepancy is to be brought to the notice of the architect/ consultant before commencement of the site. 9) All work is to be completed to the satisfaction of site engineer/ project manager and architects

BACKFILLING(150MM THICKNESS) 76

W1

74 72

B31 (300 x 330)

73

PLINTH BEAM (300MM x300MM) TO SUPPORT STAIRCASE

71

70 69 68

67

MIDDLE LANDING FFL=4.985M 65

66 64

62

61

SCALE1:10

D3

60

10MM TREAD TILE- CERAMIC TILE WITH MATTE FINISH,ANTI-SKID , BULL NOSE FINISH(1500MMx300)

59 58 57

56

FLOOR LANDING FFL=+3.935M

55

FIRST FLOOR +3.935M

POST TO FLOORING DETAIL

A-401f

63

B32 (300 x 330)

54

W1 1295

52 50

B33 (300 x 330)

51

20MMØ BALUSTERS - STAINLESS STEEL HOLLOW CIRCULAR SECTIONS WHICH IS WELDED TO BASEPLATE

49

48 47

MIDDLE LANDING

45

FFL=1.685M

46

44

43

42

20MMØ BALUSTERS - STAINLESS STEEL HOLLOW CIRCULAR SECTIONS WHICH IS WELDED TO BASEPLATE

41

B34 (300 x 330)

40 39

37

36 35

10MM TREAD TILE- CERAMIC TILE WITH MATTE FINISH,ANTI-SKID , BULL NOSE FINISH(1500MMx300)

10 MM THICK FLOOR TILING- CERAMIC TILE WITH MATTE FINISH,ANTI-SKID , BULL NOSE FINISH(1500MMx300)

D3

38

34 FLOOR LANDING

33

PLINTH LEVEL +0.635M

10MM TREAD TILE- CERAMIC TILE WITH MATTE FINISH,ANTI-SKID , BULL NOSE FINISH(1500MMx300)

10

FFL=+0.635M

10 MM THICK RISER TILE- CERAMIC TILE WITH MATTE FINISH,ANTI-SKID , BULL NOSE FINISH(1500MMx300)

BB20 (300 x 330)

MIDDLE LANDING

ANTI SKID GRIP SELF EMBOSSED PROJECTIONS ON TREAD

300

FFL=-1.25M

ANTI SKID GRIP SELF EMBOSSED PROJECTIONS ON TREAD

25

10

24

20 19

17

635

510

BB21 (300 x 330)

18 16

MS BASEPLATE OF 10MM THICKNESS

140

21

1090

22

NOSING

10 10 MM THICK RISER TILE- CERAMIC TILE WITH MATTE FINISH,ANTI-SKID , BULL NOSE FINISH(1500MMx300)

15 14

REVISION TABLE

10 MM THICK RISER TILE- CERAMIC TILE WITH MATTE FINISH,ANTI-SKID , BULL NOSE FINISH(1500MMx300)

140

23

DATE

REVISION DESCRIPTION

25MMM THICK SCREEDING ANCHOR FASTENER

25MM THICK PLASTERING

150MM THICKNESS SLAB ALTERNATE BENTUP BAR TOR 10MM 150MM c/c

950

25MMM THICK SCREEDING

150MM THICKNESS SLAB

150MM THICKNESS SLAB 230MM RUBBLE SOLING

ANCHOR FASTENERS ALTERNATE BENTUP BAR TOR 10MM 150MM c/c

PLINTH BEAM (300MM x300MM) TO SUPPORT STAIRCASE

A-401g

TREAD TO RISER DETAIL SCALE1:5

01 A-401d

BALUSTER TO TREAD DETAIL

DETAILED SECTION

4730

A-401g

SCALE1:5

UP

SCALE1:25 UP

14

15 16

17

18

19

20 21

22

23

24

25

33

C2 (600 x 600)

34

35

36 37

38 39

40 41

42

F

11 55

43

C2 (600 x 600)

2330

SW4

01

(300 x 2500)

SW4

445

300

445

700

D2

D2 31

02

03

04

05

06

07

08

09 10

11

STAIRCASE

01

1800

LIFT

2200MM x1800MM

(300 x 2500)

30 29

28

8

27 26

C3 (300 x 300) SSL=-3.9M 1150

2025

UP

D4

D3

1210

700

D2 01

62 63

64

445

DOWN

D3 975

28

C3 (300 x 300) 1375

D4

300

445

UP

32 31 30 29

SSL=-3.9M

SHEET TITLE

65

300

300

300

300

300

300

300

300

150

300 370

UP

STAIRCASE DETAIL

SW4 STAIRCASE

11

1210

8

60 61

44

950

2050

L.V SHAFT D4

950

H.V. SHAFT D4

LIFT LOBBY 1.5M x 1.5M

8

FIRE SHAFT 0.75M x 1.2M

FFL=+2.285M

FFL=+0.635M

700

D2 53 52

D3 975

51

50

49 48

47

46 45

C3 (300 x 300)

950

3375

A-401

C4 (300 x 300)

67

L.V SHAFT D4

950

H.V. SHAFT D4

2100

2100

SHEET NO.

UP 54

850

W1

MIDDLE LANDING

FLOOR LANDING

1210

1050

12

2200MM x1800MM

(300 x 2500)

1050

445

4730

STAIRCASE 13

300

A-401

(300 x 2500) 3070

4730

(300 x 2500)

445

10

150

LIFT

2200MM x1800MM

1800

A-401

58 59

3000

4730

(300 x 2500)

10

UP

150

LIFT

2200MM x1800MM

SW3

3070

01

1800

A-401

150

10

57

C2 (600 x 600) 1825

SW3

56

2330

1825

SW3

K

G

650

11 2330

E

K

G

650

11

F

3070

E

K

G

2240

F

3070

E

VRUSHALI V KULKARNI T.Y B.ARCH

SEM-6

5350

ACADEMY OF ARCHITECTURE

A-401a

DETAILED BASEMENT PLAN SCALE1:25

A-401b

DETAILED GROUND FLOOR PLAN SCALE1:25

A-401c

DETAILED TYPICAL FLOOR PLAN SCALE1:25

13/05/21 SCALE-1:25

ROLL NO.

3756


A

B 1330

720

600

BRICK WALL OF THICKNESS 230MM

4850

445

115

115

N

900

705 530

A-402d

1450

TILE DROP DETAIL SCALE1:10

330

WC 775

D5

825

W3

F

1620

JAQUAR ALD-573 ALD - 573 JET SPRAY

N

3535

W

WASH BASIN

GALASSIA,CERAMIC WASHBASIN

WB

WASH BASIN

JAQUAR - SLS-WHT-6601,600X400X185MM COUNTER RECESSED WASH BASIN

1250

1250

975

A-402d

1

C8 (600x600)

FFL=+3.15M

2200

D3

200

WASH BASIN DETAIL SCALE1:10

330

1315

25

200

75MMØ FLUSHING PIPE

BRICK WALL OF THICKNESS 150MM J

795

1125

D3

N

BRICK BAT COBA 200MM THICK

W4

U

SLAB 150MM THICK

CERAMIC TILE(600MMx600MMx10MM)

JAQUAR -600X400X185MM COUNTER RECESSED WASH BASIN

N

450

800

FFL=+3.925M SSL=+3.7M

W2

F

500

575

WC

MALE TOILET 4.6M x 1.9M

C7 (300 x 300)

SLAB 150MM THICK

1625

U

4650

1275

400

145

975

WB

SCREEDING 25MM THICK

BRICK BAT COBA 200MM THICK 7520

700

D5

WB

FA

WB

1

FA

10

PLASTERING(25MM)

N

600

M

FA

WB

SCREEDING 25MM THICK

700

700

795 795

M

FA

W2

F

FFL=+3.915M 1095

CERAMIC TILE (600MMx600MMx10MM)

PLASTERING(25MM)

145

WC

305

3730

2170

5180

FA

BOTTLE TRAP (CERA AUXILLARIES BOTTLE TRAP)

J

1930

WB

N

FFL=+3.915M D5

FFL=+3.925M SSL=+3.7M

PATLI (RCC TRANSOM)

J

1450

FEMALE TOILET 4.6M x 1.9M

100MMØ WASTE WATER PIPE

JAQUAR,CLOSED COUPLED WATER CLOSET

F

J

2320

GRANITE COUNTER TOP (20 MM THICK)

390

1470

2470

25Ø MM WATER SUPPLY PIPE

150MMØ SOIL PIPE

700

3675

D3

700

FFL=+3.925M SSL=+3.7M

1200

01

W2

1600

975

WC

775

D3

225

275

975

TOILET 2.4M x 1.5M

CERAMIC TILE(300MMx300MMx10MM)

T

H

W

A-402

GALASSIA,CERAMIC WASHBASIN WB

500

675

375

M

FA

PLASTERING(25MM)

M

D6

2650

2000

PLYWOOD PARTITION WALL (25MMTHICK)

GENERAL NOTES 1) All dimensions are in 'millimeters' unless specified. 2) The drawing is not to be scaled. The dimensions are strictly are to be followed. 3) All levels are unfinished levels unless specified. 4) The contractor shall verify all on site dimensions including elevations prior to the commencement of work on site. 5) The contractor shall inform the architect and/or project engineer on site regarding any conditions/modifications. 6) The contractor shall coordinate and verify the work indicated on the drawings between the architectural and various trade drawings, including but not limited to structural, electrical, plumbing, fire protection and exterior enclosure systems. 7) All work shall conform to relevant BIS codes and shall be best practice of each trade. 8) Any discrepancy is to be brought to the notice of the architect/ consultant before commencement of the site. 9) All work is to be completed to the satisfaction of site engineer/ project manager and architects

4850

A

B

JAQUAR ,CNS-WHT-751P180SPPZ,CLOSED COUPLED WATER CLOSET

WATER CLOSET

WC M

MIRROR

DEKNUDT BATHROOM MIRROR,25MM THICK GLASS,WOODEN FRAME(1900MM x 1000MM)

FA

FAUCET

JAQUAR , BALL FAUCET,OPP-CHR-15041PM

F

FLUSH TANK

JAQUAR JCS-WHT-2400S DUAL FLUSH TANK

J

JET SPRAY

JAQUAR ALD-573 ALD - 573 HEALTH FAUCET

REVISION TABLE DATE

A-402 02

REVISION DESCRIPTION

WALL MOUNT

DETAILED PLAN OF TOILET SCALE1:25

1

FEMALE TOILET

3060

J

WC

RCC BEAM (300MM x600MM)

F

B40

B36

B38

(300 x 600)

WC

LOUVRE WINDOW(700MMx1000MM)

LINTEL (150MM x 150MM)

BRICK WALL OF THICKNESS 150MM

CERAMIC TILE(300MMx300MMx10MM) W2

M

RCC COLUMN (600MM x600MM)

D3 FA

FA

FEMALE TOILET

SCURTING WB

WB

SCALE1:25

WC

WB

600

DETAILED SECTION OF TOILET

F

FA

FFL=+0.625M SSL=+0.4M 200

CERAMIC TILE (600MMx600MMx10MM)

02 A-402b

SCREEDING 25MM THICK BRICK BAT COBA 200MM THICK SLAB 150MM THICK

UP

SEVICE SLAB

2200MM x1800MM

BRICK WALL OF THICKNESS 150MM

WINDOW SILL

W3

(300 x 600)

UP

(300 x 600)

200

535

440

500

1145

U

950

WC

PLASTERING(25MM)

CERAMIC TILE (300MMx300MMx10MM)

W2

F 3650

J

WC

W2

F

STAINLESS STEEL WALL MOUNTED ROD

PLASTERING(25MM)

1210

W2

F

HANDLE

RCC BEAM (300MM x600MM)

PATLI (RCC TRANSOM)

MALE TOILET

H

CAST IRON FLOOR TRAP WITH STEEL GRATING

1010

B19 (300 x 470)

3640

FFL=+0.625M SSL=+0.4M

B18 (300 x 470)

NAHNI TRAP

HEALTH FAUCET,CERA FAUCETS (POM FAUCET)

2900

TOILET

B15 (300 x 470)

N

2200

B14 (300 x 470)

URINAL

LOUVRE WINDOW(700MMx1000MM) CERAMIC TILE(600MMx600MMx10MM) SCREEDING 25MM THICK SILL (150MM x 150MM) STANDARD PIPE CLAMPS PATLI (RCC TRANSOM)

435

A-402a

U

BRICK BAT COBA 200MM THICK SLAB 150MM THICK

DETAILED SECTION OF TOILET SCALE1:25

TOILET DETAIL SHEET NO.

A-402

BRICK WALL OF THICKNESS 230MM

RCC BEAM (300MM x600MM) 01 A-402c

SHEET TITLE

VRUSHALI V KULKARNI T.Y B.ARCH

ACADEMY OF ARCHITECTURE 13/05/21

RUBBLE SOLING BACK FILLING

SEM-6

SCALE-1:25

ROLL NO.

3756


RCC BEAM (300MMx 700MM) 02 A-403 4000

1300

PREFABRICATED CHANNEL SECTION (200MM x 50MM x 5MM)

FROSTED GLASS (1300MMx1000MM x 10MM) GLASS PANEL 25MM THICK

1000

CAP SCREW PREFABRICATED I SECTION (200MM x 25MM x 5MM)

6MM THICK ACP CLADDED TO THE MS PLATE OF 20MM THICK SPIDER FITTING FROSTED GLASS

GUTTER ( 100MM x100MM)

01

PREFABRICATED CHANNEL SECTION (200MM x 50MM x 5MM)

6000

A-403

PREFABRICATED I SECTION (200MM x 25MM x 5MM)

6MM THICK ACP CLADDED TO THE MS PLATE OF 20MM THICK 2500

D1 M.S.PLATE OF 20MM THICKNESS IS USED TO CONNECT CANOPY TO THE WALL

-0.15M

D1

ANGLE CLEAT ( 25MM x 50MMx5MM)

-0.15M ACP CLADDED TO DOWNTAKE PIPE

GLASS PANEL 25MM THICK

SINGLE GLAZED DOOR DOWNTAKE PIPE(100MM DIAMETER)

CAP SCREW

RCC COLUMN (600MM x 600MM)

BOX SECTION USED AS BRACING(50MM x50MM)

GENERAL NOTES 1) All dimensions are in 'millimeters' unless specified. 2) The drawing is not to be scaled. The dimensions are strictly are to be followed. 3) All levels are unfinished levels unless specified. 4) The contractor shall verify all on site dimensions including elevations prior to the commencement of work on site. 5) The contractor shall inform the architect and/or project engineer on site regarding any conditions/modifications. 6) The contractor shall coordinate and verify the work indicated on the drawings between the architectural and various trade drawings, including but not limited to structural, electrical, plumbing, fire protection and exterior enclosure systems. 7) All work shall conform to relevant BIS codes and shall be best practice of each trade. 8) Any discrepancy is to be brought to the notice of the architect/ consultant before commencement of the site. 9) All work is to be completed to the satisfaction of site engineer/ project manager and architects

ANGLE CLEAT (50MM x 50MMx5MM)

200

RCC BEAM (300MM x 700MM)

02 A-403c

PREFABRICATED I SECTION (200MM x 25MM x 5MM)

DETAILED SECTION OF CANOPY SCALE1:50 A-403g

CANOPY TO BEAM DETAIL

N

SCALE1:5

A-403a

DETAILED PLAN OF CANOPY SCALE1:50 SILICON 25 MM THICK ACP PANEL SSF 003 SPIDER FITTING

SPIDER FITTING SILICON SEALANT

DOWNTAKE PIPE(150MM DIAMETER)

50MM DIA. FLAT HEAD FIXED BOLT

ANGLE CLEAT ( 25MM x 50MMx5MM)

CAP SCREW GLASS PANEL 25MM THICK LOW MODULOUS SILICON CHAULKING

GUTTER ( 100MM x100MM)

ANGLE CLEAT ( 25MM x 50MMx5MM) FORM BACKING ROD 10MM DIAMETER

ANGLE CLEAT (50MM x 50MMx5MM)

CAP SCREW PREFABRICATED I SECTION (200MM x 25MM x 5MM) BOX SECTION USED AS BRACING(50MM x50MM) 2500

Z ANGLE M. S .PLATE 5MM THICK TO ATTACH A.C.P PANEL

PREFABRICATED I SECTION (200MM x 25MM x 5MM)

D1 SINGLE GLAZED DOOR

A-403e

I SECTION TO GLASS PANEL(CANOPY) CONNECTION DETAIL SCALE1:5 DATE

DETAILED SECTION OF CANOPY

REVISION DESCRIPTION

SCALE1:50

GLASS PANEL 25MM THICK

A-403h

25 MM THICK ACP PANEL

DOWNTAKE PIPE DETAIL SCALE1:5

50MM DIA. FIXED BOLT UP

GLASS PANEL 25MM THICK

UP

CAP SCREW 2200MM x1800MM

10MM THICK ACP CLADDED TO THE MS PLATE OF 20MM THICK SPIDER FITTING

Z ANGLE M. S .PLATE 5MM THICK TO ATTACH A.C.P PANEL

FROSTED GLASS CANOPY (6000MM x 3000MM)

ANCHOR FASTENER

GLASS PANEL 25MM THICK

PREFABRICATED CHANNEL SECTION (200MM x 50MM x 5MM)

LOW MODULOUS SILICON CHAULKING D1 2500

01 A-403b

REVISION TABLE

-0.15M

D1

SHEET TITLE

FORM BACKING ROD 10MM DIAMETER

-0.15M ACP CLADDED TO DOWNTAKE PIPE

GLASS PANEL 25MM THICK

50MM DIA. FLAT HEAD FIXED BOLT

SINGLE GLAZED DOOR

SSF 003 SPIDER FITTING

ARCHITECTURAL DETAIL SHEET NO.

A-403 GLASS PANEL 25MM THICK

A-403d

VRUSHALI V KULKARNI T.Y B.ARCH

DETAILED ELEVATION OF CANOPY

SEM-6

ACADEMY OF ARCHITECTURE

SCALE1:50 A-403f

GLASS PANEL TO COLUMN DETAIL SCALE1:5

A-403i

GLASS TO SPIDER FITTING DETAIL SCALE1:5

13/05/21 SCALE-1:25

ROLL NO.

3756


GENERAL NOTES 1) All dimensions are in 'millimeters' unless specified. 2) The drawing is not to be scaled. The dimensions are strictly are to be followed. 3) All levels are unfinished levels unless specified. 4) The contractor shall verify all on site dimensions including elevations prior to the commencement of work on site. 5) The contractor shall inform the architect and/or project engineer on site regarding any conditions/modifications. 6) The contractor shall coordinate and verify the work indicated on the drawings between the architectural and various trade drawings, including but not limited to structural, electrical, plumbing, fire protection and exterior enclosure systems. 7) All work shall conform to relevant BIS codes and shall be best practice of each trade. 8) Any discrepancy is to be brought to the notice of the architect/ consultant before commencement of the site. 9) All work is to be completed to the satisfaction of site engineer/ project manager and architects

REVISION TABLE DATE

REVISION DESCRIPTION

SHEET TITLE DOOR SCHEDULE SHEET NO.

A-501 VRUSHALI V KULKARNI T.Y B.ARCH

SEM-6

ACADEMY OF ARCHITECTURE 13/05/21

ROLL NO.

3756