DOCUMENT PACKAGE
LARGE ANIMAL SURGERY AND GERM FREE FACILITY MEDICAL SCIENCES BUILDING - FOURTH LEVEL ROCHESTER, MN
MAYO PROJECT: #7R120760 ISSUED:
07/03/13
PACKAGE:
CONSTRUCTION DOCUMENTS
RSP Architects 320 South Broadway Ste. B 507.285.6569 Rochester, Minnesota 55904 612.677.7499 fax www.rsparch.com
Consultants
Certification
DRAWING ABBREVIATIONS
ABV. A.F.F. ACC. ACC. PML. ACFLR. ACOUS. A.C.T. A.C.P. ADD. ADD'N(L) ADH. ADJ. A/C ALT. ALUM. A.D.A. ANCH. A.B. ANOD. & "L" ANTQ. APT. APPVD. ARCH.
ABOVE ABOVE FINISH FLOOR ACCESS or ACCESSARY (IES) ACCESS PANEL ACCESSIBLE FLOORING ACOUSTICAL ACOUSTICAL CEILING TILE ACOUSTICAL WALL PANEL ADDENDUM ADDITION(AL) ADHESIVE ADJACENT AIR CONDITIONING ALTERNATE ALUMINUM AMERICAN'S WITH DISABILITY ACT
ART. ATT. AUTO. AVG.
ANCHOR(AGE) ANCHOR BOLT ANODIZED AND ANGLE ANTIQUE APARTMENT APPROVED ARCHITECT OR ARCHITECTURAL ARCHITECTURAL WOODWORK ARTWORK ATTACH(ED) (MENT) AUTOMATIC AVERAGE
BQ. B. BSMT. BM. BRG. B.MK. BTWN. BEV. BLK. BLKG. BD. BT. B.S. BOT. BRKT. BRK. BRNZ. BLDG. B.U.R. B.S. B.BD.
BANQUETTE BASE MATERIAL BASEMENT BEAM BEARING BENCH MARK BETWEEN BEVELED BLOCK BLOCKING BOARD BOLT OR BOLTS BOTH SIDES BOTTOM BRACKET BRICK BRONZE BUILDING BUILT UP ROOFING BUILDING STANDARD BULLETIN BOARD
CAB. CPT. CSWRK. C.I. C.I.P. C.B. CALK. CLG. CEM. CTR. C.L. C.T. C.BD. CH. CR. CIRC.
CABINET CARPET CASEWORK CAST IRON CAST IN PLACE CATCH BASIN CAULKING CEILING CEMENT CENTER CENTER LINE CERAMIC TILE CHALK BOARD CHAIR CHROMIUM, CHROME CIRCLE, CIRCULAR CIRCUMFERENCE CLEANOUT CLEAR CLEAR OPENING CLOSET CLOSURE COLD WATER COLUMN COMPOSITE COMPRESSIBLE CONCRETE CONCRETE MASONRY UNIT CONFERENCE CONNECT OR CONNECTION CONSTRUCTION CONTINUED CONTINUOUS CONTRACTOR CONTRACT CONTROL JOINT JOINT CORNER CORNER GUARD CORRIDOR CORRUGATED COUNTER COUNTERSUNK CREDENZA
AWDWK.
C.O. CLR. CLR.OPG. CLO. CLS. C.W. COL. COMP. COMPR. CONC. CMU. CONF. CONNX. CONST. CONT'D. CONT. CONTR. C.J. COR. C.G. CORR. CORRUG. CTR. CSK. CRED.
SHEET INDEX DRAWINGS
DK. DEC. DEM. DMT. DEPT. DET. DIAG. DIA. DIM. DISP. DISPOS. DIST. DO. DIV. DR. D.O. DBL. D.A. DN. D.S. DRAP. DWR. DW. DWG. D.F. D.S.P. D.W. D.X.
EA. E.F. E.W. E. ELAST. ELEC. E.O. E.P. E.W.C. ELEV. ELEVR. EMER. ENCL. E. to E. ENGR. ENTR. ENVL. EQ. EQUIP. EQUIV. EXCAV. EXH. EXIST. EXPAN. EXP. BT. E.J. EXPOS. EXT. EX.
F. FABR. F.O.C. F.O.F. F.O.M. F.O.S. F.O.W. F-F F.M. FAS. FIN. F.F. F.A. F.E. F.E.C. F.H.C. F.H.R. F.P. FRT. FIX. FIXT. FLASH. F.H. F.H.S. FLEX. FLR. F.D. F. MTD. FLUOR. FL. FT. FTG. FDN. FRM. FRMG. F.S. FURN. F.B.O. FUR. FURR. FUT.
DARK DECORATIVE DEMOLITION DEMOUNTABLE DEPARTMENT DETAIL DIAGONAL DIAMETER DIMENSION DISPENSER DISPOSAL or DISPOSER DISTANCE DITTO DIVISION DOOR DOOR OPENING DOUBLE DOUBLE-ACTING DOWN DOWNSPOUT DRAPERY DRAWER DRYWALL DRAIN DRINKING FOUNTAIN DRY STANDPIPE DRYWALL DUPLEX
GA. GALV. G.I. GASK. GA. GEN. GL. G.B. GRD. GRN. GRT. GRV. GRND. GFCI. GT. GYP. GYP. BD.
HVY. HDF. HT. H.P. H.C. H. GRN. HORIZ. H.B. H.W. HR.
HANDRAIL HARDBOARD HARDWARE HARDWOOD HEAD HEATING HEATING, VENTILATING AND AIR CONDITIONING HEAVY HIGH DENSITY FIBERBOARD HEIGHT HIGH POINT HOLLOW CORE HONED GRANITE HORIZONTAL HOSE BIBB HOT WATER HOUR
I.C. INCAN. INCL. INFO. I.D. INSUL. INT. INTM. INV. I.O.C.
IN CONTRACT INCANDESCENT INCLUDE(D)(ING) INFORMATION INSIDE DIAMETER INSULATION INTERIOR INTERMEDIATE INVERT ITEM OF CHARGE
JAN. JAN. CLO. JNT. JTFILL JST. J.B.
JANITOR JANITOR CLOSET JOINT JOINT FILLER JOIST JUNCTION BOX BOX
K.P. KIT. K.O.
KICK PLATE KITCHEN KNOCKOUT
HNDRL. HDBD. HDWR. HDWD. HD. HTG. HVAC
EACH EACH FACE EACH WAY EAST ELASTIC ELECTRIC ELECTRIC OUTLET ELECTRIC PANEL ELECTRIC WATER COOLER ELEVATION ELEVATOR EMERGENCY ENCLOSURE END TO END ENGINEER ENTRANCE ENVELOPE EQUAL EQUIPMENT EQUIVALENT EXCAVATED or EXCAVATION EXHAUST EXISTING EXPANSION EXPANSION BOLT EXPANSION JOINT EXPOSED EXTERIOR EXISTING
FABRIC FABRICATE FACE OF CONCRETE FACE OF FINISH FACE OF MASONRY FACE OF STUD FACE OF WALL FACE TO FACE FACTORY MUTUAL FASTEN, FASTENER FINISH(ED) FINISH FLOOR FIRE ALARM FIRE EXTINGUISHER FIRE EXTINGUISHER CABINET FIRE HOSE CABINET FIRE HOSE RACK FIREPROOFING FORE FIRE RETARDANT FIXED FIXTURE FLASHING FLAT HEAD FLAT HEAD SCREW FLEXIBLE FLOOR FLOOR DRAIN FLOOR MOUNTED FLUORESCENT FLUSH FOOT OR FEET FOOTING FOUNDATION FRAME FRAMING FULL SIZE(SCALE) FURNITURE FURNISHED BY OTHERS FURRED FURRING FUTURE
GAGE, GAUGE GALVANIZED GALVANIZED IRON (STEEL) GASKET GAUGE GENERAL GLASS OR GLAZED GRAB BAR GRADE GRANITE GRATE, GRATING GRAVEL GROUND GROUND FAULT CIRCUIT INTERPRETER GROUT GYPSUM GYPSUM BOARD
LAB. LAM. LG. LAT. LAV. L.H. L.H.R. L. LT. LTWT. LIN. LTL. L.L. LKR. LONG'L. LOUV. L.P. LB. MACH. MAINT. MGR. MFGR. MRB. MAS. M.O. MATL. MAX. MECH. M.C. MED. MEMB. MET. M.L. MEZZ. MLWK. MIN. MIR. MISC. MTD. MUL.
LABORATORY LAMINATE LARGE LATERAL LAVATORY LEFT HAND LEFT HAND REVERS LENGTH LIGHT LIGHT WEIGHT LINEAR or LINOLEUM LINTEL LIVE LOAD LOCKER LONGITUDINAL LOUVER(S) LOW POINT POUND MACHINE MAINTENANCE MANAGER MANUFACTURE(ER) MARBLE MASONRY MASONRY OPENING MATERIAL MAXIMUM MECHANICAL MEDICINE CABINET MEDIUM MEMBRANE METAL METAL METAL LATH MEZZANINE MILLWORK MINIMUM MIRROR MISCELLANEOUS MOUNTED MULLION
NAT. NEG. NOM. N. N.I.C. N.T.S. NO.
NATURAL NEGATIVE NORMAL NORTH NOT IN CONTRACT NOT TO SCALE NUMBER
OBSC. OFF. OPNG. OPP. O.H. ORIG. ORN. OZ. O.D. OTOO OVHD. O.HD. O.C.
OBSCURE OFFICE OPENING OPPOSITE OPPOSITE HAND ORIGINAL ORNAMENTAL OUNCE OUTSIDE DIAMETER OUT TO OUT OVERHEAD OVERHEAD DOOR ON CENTER
P. PTD. PR. PNL. P.T.D. P.T.R. PART. BD. PTN. PATT. PAV. P.H. PERM. PC. PERP. PLAS. P.LAM. PL. PL.GL. PLBG.
PAINT PAINTED PAIR PANEL PAPER TOWEL DISPENSER PAPER TOWEL RECEPTACLE PARTICLE BOARD PARTITION PATTERN(ED) PAVING OR PAVEMENT PENTHOUSE PERMANENT PIECE PERPENDICULAR PLASTER PLASTIC LAMINATE PLATE PLATE GLASS PLUMBING
PLYWD. PT. POL. PVC. PORT. PSF. PREFAB. PROD. PROJ. PROP. P.L. PLAM
PLYWOOD POINT POLISH POLYVINYL CHLORIDE PORTABLE POUNDS PER SQUARE FOOT PREFABRICATED PRODUCTION, PRODUCT PROJECT PROPERTY PROPERTY LINE PLASTIC LAMINATE
QUAL. QUAN. Q.T.
QUALITY QUANTITY QUARRY TILE
RAD. RECEP. REF. RE: REFL. REFR. REINF. REBAR. REM. REMV. REQD. RESIL. R.B. R/A REV. R.H. R.H.R. R. R.D. RFG. RM. R.O. RND.
RADIUS RECEPTACLE REFERENCE REFER TO REFLECTED REFRIGERATOR REINFORCED REINFORCED BAR REMAINDER REMOVE REQUIRED RESILENT RESILENT BASE RETURN AIR REVISION RIGHT HAND RIGHT HAND REVERSE RISER ROOF DRAIN ROOFING ROOM ROUGH OPENING ROUND
SAN. S.N.D. SC. SCHED. SCHEM. SEAL. SECT. SEL. SEP. SERV. SVSNK SHT. SH. SHWR. SIM. SNK. SKYLT. SLDR. SM. S.D. S.C. S. SPKR. SPEC'L. SPECS. SPL. SQ. SF. SQ. IN. STAG. S.S. STD. STA. STL. ST. STOR. STFNT. STRUCT. SUP. SUSP. SYMM. SYST.
SANITARY SANITARY NAPKIN DISPENSER SCALE SCHEDULE SCHEMATIC SEALANT SECTION SELECT SEPARATE SERVICE SERVICE SINK SHEET SHELF or SHELVING SHOWER SIMILAR SINK SKYLIGHT SLIDING DOOR SMALL SOAP DISPENSER SOLID CORE or SEALED CONCRETE SOUTH SPEAKER SPECIAL SPECIFICATIONS SPLASH SQUARE SQUARE FEET SQUARE INCHES STAGGERED STAINLESS STEEL STANDARD STATION STEEL STONE STORAGE STOREFRONT STRUCTURAL SUPPLY SUPPORT SUSPEND(ED) SYMMETRICAL SYSTEM
T.BD. TAN. TECH. TEL. T.V. TEMPD. TEMP. TRZ. THK. THRESH. T.PAV. T.P.H. TOL. T&G T&B T.O.C. T.C. T.O.P. T.O.S. T.O.W. T.B. T.D. TR. T. TYP.
TACKBOARD TANGENT TECHNICAL TELEPHONE TELEVISION TEMPERED TEMPORARY TERRAZZO THICK(NESS) THRESHOLD TILEPAVERS TOILET PAPER HOLDER TOLERANCE TONGUE AND GROOVE TOP AND BOTTOM TOP OF CONCRETE TOP OF CURB TOP OF PAVEMENT TOP OF STEEL TOP OF WALL TOWEL BAR TOWEL DISPENSER TRANSFORM TREAD TYPICAL
WSCT. W.H. WC. W.H. W.R. W.P. W.S. WT. WLD. W.W.M. W. W.S.P. W.F. WDW. WDWALL W.GL. W/ W/IN W/O WD. W.B. W.PT. W.W.F.
WAINSCOT WALL HUNG WATER CLOSET WATER HEATER WATER RESISTANT WATERPROOF WEATHERSTRIPPING WEIGHT WELDED WELDED WIRE MESH WEST WET STANDPIPE WIDE FLANGE (STEEL) WINDOW WINDOW WALL WIRE GLASS WITH WITHIN WITHOUT WOOD WOOD BASE WORKING POINT WOVEN WIRE FABRIC
X
TIMES OR BY (AS IN 2X4)
YD.
YARD
& @ c L o
AND AT CENTERLINE DIAMETER FEET INCHES (OR DITTO) NUMBER ("NUMBER 5") PER ("POUNDS/FOOT") PERPENDICULAR POUNDS ("5 POUNDS")
' " #5 _ 5#
OWNER REPRESENTATIVE
MECH/ELEC ENGINEERS
MAYO FOUNDATION FACILITIES PROJECT SERVICES 200 FIRST STREET SW ROCHESTER, MN 55905
MEP ASSOCIATES, LLC 2900 43RD ST NW STE 100 ROCHESTER, MN 55901 PHONE: 507/281-1632 FAX: 507/281-6328
CONSTRUCTION MANAGER:
PROJECT MANAGER:
MIKE CRAVEN PHONE: 507/266-8548 EMAIL: CRAVEN.MICHAEL@MAYO.EDU
MECHANICAL CONTACT:
PHIL PLONKA PHONE: 507/284-8444 EMAIL: PLONKA.PHIL@MAYO.EDU
ELECTRICAL CONTACT:
ISSUE KEY: 1 ISSUED (WITH SIGNATURE) 2 REVISED AND RE-ISSUED (WITH SIGNATURE) 3 NOT FOR CONSTRUCTION - REFERENCE ONLY 4 RE-ISSUED FROM A PRIOR BID PACK - NO REVISIONS
LUKE JOHNSON PHONE: 507/281-1632 EMAIL: LUKEJ@MEPASSOCIATES.COM KERRY HAYDEN PHONE: 507/281-1632 EMAIL: KERRYH@MEPASSOCIATES.COM SHEET NO. NAME G000 COVER SHEET G104 FOURTH LEVEL FIRE AND LIFE SAFETY PLAN
ARCHITECT RSP ARCHITECTS, LTD. 320 SOUTH BROADWAY STE. B ROCHESTER, MN 55904 PHONE: 507/285-6569 FAX: 612/677-7499 PROJECT MANAGER:
TIM MILLER PHONE:507/292-8661 EMAIL: TIM.MILLER@RSPARCH.COM
VAR. VNR. V.I.F. VERT. VEST. VIN. V.B. V.C.T. V. VOL.
D104A D104B D204A D204B
PARTIAL FOURTH LEVEL DEMOLITION PLAN - AREA A PARTIAL FOURTH LEVEL DEMOLITION PLAN - AREA B PARTIAL FOURTH LEVEL DEMOLITION EQUIPMENT PLAN - AREA A PARTIAL FOURTH LEVEL DEMOLITION EQUIPMENT PLAN - AREA B
1 1 1 1
A104A A104B A204 A301
1 1 1 1
A801 A801A A801B A901 A902 A903 A920 A921
PARTIAL FOURTH LEVEL FLOOR PLAN - AREA A PARTIAL FOURTH LEVEL FLOOR PLAN - AREA B FOURTH LEVEL REFLECTED CEILING PLAN DOOR SCHEDULE, DETAILS, PARTITION TYPE INDICATOR, AND INTERIOR DETAILS EQUIPMENT SCHEDULE PARTIAL FOURTH LEVEL EQUIPMENT PLAN - AREA A PARTIAL FOURTH LEVEL EQUIPMENT PLAN - AREA B INTERIOR ELEVATIONS INTERIOR ELEVATIONS INTERIOR ELEVATIONS MILLWORK DETAILS CASEWORK DETAILS AND ACCESSORY MOUNTING DIAGRAM
I104 I304
FOURTH LEVEL FINISH PLAN AND SCHEDULE FOURTH LEVEL FURNITURE PLAN AND SCHEDULE
1 1
P001
PLUMBING SYMBOLS ABBREVIATIONS, GENERAL NOTES, DETAILS, AND SCHEDULES PARTIAL FOURTH LEVEL DEMOLITION PLUMBING PLAN AREA A PARTIAL FOURTH LEVEL DEMOLITION PLUMBING PLAN AREA B PARTIAL FOURTH LEVEL DEMOLITION PROCESS PIPING AND FIRE PROTECTION PLAN AREA A PARTIAL FOURTH LEVEL DEMOLITION PROCESS PIPING AND FIRE PROTECTION PLAN AREA B PARTIAL FOURTH LEVEL PLUMBING PLAN AREA A PARTIAL FOURTH LEVEL PLUMBING PLAN AREA B PARTIAL FOURTH LEVEL PROCESS PIPING AND FIRE PROTECTION PLAN AREA A PARTIAL FOURTH LEVEL PROCESS PIPING AND FIRE PROTECTION PLAN AREA B
1
PD104A PD104B PD204A PD204B
GENERAL NOTES 1. ALL CONTRACTORS ARE RESPONSIBLE TO REVIEW ALL CONSTRUCTION DOCUMENTS AND ARE RESPONSIBLE FOR INFORMATION ON ALL CONSTRUCTION DOCUMENTS.
P104A P104B P204A P204B
2. ALL CONTRACTORS AND SUBCONTRACTORS TO COMPLY WITH MAYO CAMPUS STANDARD SPECIFICATIONS AND STANDARD PROCEDURES. 3. THE AVAILABILITY OF ALL MATERIALS DESIGNATED ON PLANS TO MATCH EXISTING SHALL BE VERIFIED BY CONTRACTORS AND SUBCONTRACTORS PRIOR TO ESTIMATE SUBMITTALS. CONTRACTOR TO NOTIFY OWNER IF MATCHING MATERIALS ARE NOT AVAILABLE. ANY SUBSTITUTIONS TO BE REVIEWED AND APPROVED.
UNDERWRITERS LABORATORY UNDERCUT UNFINISHED UNLESS NOTED OTHERWISE URINAL UTILITY
5. CONTRACTORS TO PROVIDE TEMPORARY PARTITIONS AND DUST CONTROL AT ALL LOCATIONS WHERE WORK OCCURS IN CORRIDORS AND/OR CANNOT BE CONTAINED WITHIN ROOMS. 6. REMOVAL OF WALLS AND PARTITIONS TO INCLUDE ALL MECHANICAL AND ELECTRICAL ITEMS. DEMOLITION OF THESE ITEMS SHALL EXTEND BACK TO MAIN DISTRIBUTION POINTS UNLESS NOTED OTHERWISE. 7. THE GENERAL CONTRACTOR SHALL PROVIDE MAJOR DAILY CLEAN UP OF THE CONSTRUCTION SITE. ALL OTHER CONTRACTORS OR SUBCONTRACTORS SHALL CLEAN UP THEIR INDIVIDUAL TRASH AND DISPOSE OF IT. MAJOR SHIPPING CONTAINERS AND DEMOLITION ITEMS SHALL BE THE RESPONSIBILITY OF INDIVIDUAL CONTRACTORS OR SUBCONTRACTORS TO REMOVE DAILY.
VARIABLE VENEER VERIFY IN FIELD VERTICAL VESTIBULE VINYL SHEET GOODS VINYL BASE VINYL COMPOSITION TILE VINYL WALL COVERING VOLUME
1 1
Signature
DAVID NORBACK
Registration Number
11902
Date
07.03.13
I hereby certify that this plan, specification or report was prepared by me or under my direct supervision and that I am a duly licensed Architect under the laws of the State of Minnesota.
Signature
DAVID NORBCK
Registration Number
11902
Date
07.03.13
Project For
4. ALL CUTTING AND PATCHING SHALL BE PERFORMED BY THE GENERAL CONTRACTOR. GENERAL CONTRACTOR SHALL INCLUDE COST OF ALL REQUIRED CUTTING AND PATCHING FOR ALL TRADES IN THEIR ESTIMATE. U.L. U.C. UNFIN. U.N.O. UR. UTIL.
ISSUES 07/03/13 CONSTRUCTION DOCUMENTS
Note: Not all abbreviations listed below are necessarily used in the drawings; refer elsewhere for abbreviations related to product or material codes.
PROJECT TEAM
I hereby certify that I have reviewed the Mayo Clinic Standard General Specifications prepared by Ronald B. Carlson, License Number 10850, that they are appropriate for the work except as amended in this plan, specification or report, and that I am a duly licensed Architect under the laws of the State of Minnesota.
8. AT CONCLUSION OF PROJECT, ALL CONTRACTORS SHALL REDLINE THE CONSTRUCTION MANAGEMENT OFFICE SET FOR OWNER'S RECORDS SHOWING ALL DEVIATIONS FROM THE CONSTRUCTION DOCUMENTS. 9. FLAME SPREAD CLASSIFICATION OF INSTALLED FINISH MATERIALS SHALL CONFORM TO 2007 MINNESOTA BUILDING CODE (2006 INTERNATIONAL BUILDING CODE) CHAPTER 8. 10. ALL WORK SHALL CONFORM TO THE LATEST EDITION OF THE U.S. GYPSUM PRODUCTS AND SYSTEMS SPECIFICATION BULLETIN OR NATIONAL GYPSUM COMPANY'S LATEST SPECIFICATIONS EXCEPT AS NOTED. ALL GYPSUM BOARD TO BE FIRE RESISTIVE UNLESS NOTED OTHERWISE. 11. ALL WOOD BLOCKING AND CONCEALED LUMBER TO BE FIRE RETARDANT TREATED. 12. ALL HOLES IN FLOORS OR WALLS AS A RESULT OF DEMOLITION SHOULD BE FILLED AND SEALED TO MAINTAIN EXISTING FIRE AND SMOKE RATING OF FLOOR OR WALL SYSTEM ACCORDING TO MAYO STANDARD SPECIFICATION SECTION 07840. 13. IF ASBESTOS OR QUESTIONABLE MATERIAL IS ENCOUNTERED, CONTACT THE MAYO FOUNDATION CONSTRUCTION MANAGER. MAYO'S ASBESTOS EVALUATION AND ABATEMENT TEAM WILL ADDRESS ANY IDENTIFIED ASBESTOS EXPOSURE. 14. CONTRACTOR, CONSTRUCTION MANAGER AND RICK RAMAKER FROM FACILITIES WAREHOUSE TO VERIFY ALL ITEMS TO BE SALVAGED AND RETURNED TO OWNER'S STOCK BEFORE DEMOLITION OCCURS.
M001
1 1 1 1 1 1 1 1
Large Animal Surgery and Germ Free Facility
1 1 1
Medical Sciences Building Fourth Floor
1 1 1 1 1
Project #7R120760
MD104A MD104B M104A M104B M105A M106A M204A M204B M601
MECHANICAL SYMBOLS, ABBREVIATIONS, GENERAL NOTES AND SCHEDULES PARTIAL FOURTH LEVEL DEMOLITION HVAC PLAN AREA A PARTIAL FOURTH LEVEL DEMOLITION HVAC PLAN AREA B PARTIAL FOURTH LEVEL HVAC PLAN AREA A PARTIAL FOURTH LEVEL HVAC PLAN AREA B PARTIAL FIFTH LEVEL DEMOLITION AND HVAC PLANS AREA A PARTIAL SIXTH LEVEL DEMOLITION AND HVAC PLANS AREA A PARTIAL FOURTH LEVEL MECHANICAL PIPING PLAN AREA A PARTIAL FOURTH LEVEL MECHANICAL PIPING PLAN AREA B MECHANICAL DETAILS AND DIAGRAMS
1 1 1 1 1 1 1 1 1 1
E001 ED104A ED104B ED204A ED204B ED304A ED304B ED601 E104A E104B E204A E204B E206A E304A E304B E601 E602 E701
ELECTRICAL SYMBOLS ABBREVIATIONS AND GENERAL NOTES PARTIAL FOURTH LEVEL DEMOLITION LIGHTING PLAN AREA A PARTIAL FOURTH LEVEL DEMOLITION LIGHTING PLAN AREA B PARTIAL FOURTH LEVEL DEMOLITION POWER PLAN AREA A PARTIAL FOURTH LEVEL DEMOLITION POWER PLAN AREA B PARTIAL FOURTH LEVEL DEMOLITION SIGNAL PLAN AREA A PARTIAL FOURTH LEVEL DEMOLITION SIGNAL PLAN AREA B ELECTRICAL DEMOLITION ONE-LINE DIAGRAM PARTIAL FOURTH LEVEL LIGHTING PLAN AREA A PARTIAL FOURTH LEVEL LIGHTING PLAN AREA B PARTIAL FOURTH LEVEL POWER PLAN AREA A PARTIAL FOURTH LEVEL POWER PLAN AREA B PARTIAL SIXTH LEVEL DEMOLITION AND POWER PLANS AREA A PARTIAL FOURTH LEVEL SIGNAL PLAN AREA A PARTIAL FOURTH LEVEL SIGNAL PLAN AREA B ELECTRICAL ONE-LINE DIAGRAM ELECTRICAL PANEL SCHEDULES ELECTRICAL DETAILS
1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
A
B
KEY PLAN
Project No. Drawn By
JAS
Checked By
JHA/MLK
Date
07/03/13
NOTICE: The designs shown and described herein including all technical drawings, graphics, and models thereof, are proprietary and cannot be copied, duplicated or commercially exploited, in whole or in part, without express written permission of RSP Architects. These are available for limited review and evaluation by clients, consultants, contractors, government agencies, vendors and office personnel only in accordance with this Notice. © Copyright RSP Architects 2007. All rights reserved.
Revisions No.
15. ALL FURNISHINGS SHALL CONFORM TO 2007 INTERNATIONAL FIRE CODE CHAPTER 8.
6287.040.04
Date
Description
16. NEW UPHOLSTERY MATERIALS MUST BE CALL TB117 COMPLIANT. 17. PREPARE PARTITION SURFACES (PATCH, SKIM COAT, ETC.) AS REQUIRED IN PREPARATION FOR SCHEDULED FINISHES - TYPICAL.
DRAWING SYMBOLS
18. ALL CONTRACTORS INCLUSIVE OF SUBCONTRACTORS ARE TO COMPLY WITH THE GUIDELINES OF THE INFECTION CONTROL UNIT IN RELATION TO ALL CONSTRUCTION IN HOSPITAL. CONTRACTORS TO REVIEW GUIDELINES PRIOR TO SUBMITTING ESTIMATES. 1
0
1
0
ROOM NAME REVISION REFERENCE
0
ELEVATION TAG SINGLE VIEW
101
1i COLUMN OR GRID LINE - EXISTING
A101
2
ELEVATION TAG MULTIPLE VIEW
PARTITION TAG
1
1 A101
DETAIL TAG
SIM MATCH LINE
MATCH LINE
12
SEE X/XXX
T.O. FOOTING Name Elevation EL. = 96'-0" EL. = 100'-0"
VIEW NAME 1/8" = 1'-0"
DRAWING TITLE
1 A101
1 A101
ELEVATION / LEVEL TAG NORTH ARROW
SPOT ELEVATION
NORTH NORTH
SIM
WALL SECTION TAG
SIM
ROOM TAG
KEY PLAN
(ROOM AREA)
XX
KEYNOTE
23 1t
WINDOW TAG
234
EQUIPMENT TAG
101
DOOR TAG
EXIST EXIST EXIST
(WALL FINISH) (BASE FINISH) (FLOOR FINISH)
PROJECT AREA
FINISH TAG ALL SURFACES
BUILDING SECTION TAG
EXIST EXIST
1 A101 SIM
(ROOM NUMBER)
150 SF
1
COLUMN OR GRID LINE - NEW
0
A101
(ROOM NAME)
ENLARGED PLAN OR DETAIL REFERENCE
CPT-01
CPT-02
FINISH TAG WITH EXTENT OF FINISH
COVER SHEET
FINISH TRANSITION
NORTH C:\Revit Projects\Med Sci 4 Central_jschmit.rvt 7/8/2013 11:23:11 AM
Please purchase PDF Split-Merge on www.verypdf.com to remove this watermark.
G000
UP
DN
SD
F
RSP Architects 320 South Broadway Ste. B 507.285.6569 Rochester, Minnesota 55904 612.677.7499 fax www.rsparch.com
FE SD
FE SD
SD
2F
Consultants
Certification
I hereby certify that I have reviewed the Mayo Clinic Standard General Specifications prepared by Ronald B. Carlson, License Number 10850, that they are appropriate for the work except as amended in this plan, specification or report, and that I am a duly licensed Architect under the laws of the State of Minnesota.
SD
SD
Signature
DAVID NORBACK
Registration Number
SD
11902
Date
I hereby certify that this plan, specification or report was prepared by me or under my direct supervision and that I am a duly licensed Architect under the laws of the State of Minnesota.
2F
FE
FE
07.03.13
SD
Signature
SD SD
DAVID NORBCK
Registration Number
11902
2F
Date
07.03.13
Project For SD FE
SD DN
UP
SD
FE SD
Large Animal Surgery and Germ Free Facility
F SD
SD
SD
SD
FE
Medical Sciences Building Fourth Floor
SD
Project #7R120760 PROJECT AREA
A
B
KEY PLAN
1
FOURTH LEVEL FIRE AND LIFE SAFETY PLAN
Project No.
1/8" = 1'-0"
Drawn By
NORTH
BUILDING CODE, OCCUPANCY AND EGRESS INFORMATION MEDICAL SCIENCES BUILDING - FOURTH LEVEL
ILSM FOR THE SCOPE OF WORK HAVE BEEN REVIEWED AND NO ACTION IS REQUIRED
1 HOUR RATED CORRIDOR: FULL HT PARTITION 1 HR RATED CONSTRUCTION, LIMIT PASSAGE OF SMOKE WITH 20 MINUTE DOORS.
CL
1 HOUR RATED CORRIDOR: FULL HT PARTITION 1 HR RATED CONSTRUCTION, LIMIT PASSAGE OF SMOKE.
CN
RATED CORRIDOR NOT REQUIRD: FULL HT PARTITION 1 HR RATED CONSTRUCTION.
CS
1 HOUR RATED CORRIDOR: FULL HT PARTITION 1 HR RATED CONSTRUCTION, MEMBRANE TO LIMIT PASSAGE OF SMOKE FROM RATED CORRIDOR BARRIER/CEILING UP TO DECK
PER 2007 MINNESOTA STATE BUILDING CODE (2006 IBC & GREB) IF A BOX IS CHECKED FOR THE FOLLOWING QUESTIONS BELOW, AN ACTION IS REQUIRED. ACTION REQUIRED
ITEM
ELEMENT OF PERFORMANCE
1
SIGNAGE SHALL BE POSTED IDENTIFYING ALTERNATE EXITS FOR EVERYONE AFFECTED.
2
CONTRACTOR SHALL FOLLOW HOT WORKS AND FIREWATCH POLICIES COORDINATED WITH MAYO CLINIC FACILITIES OPERATIONS, WHEN FIRE SYSTEMS ARE AFFECTED.
3
PROVIDE TEMPORARY BUT EQUIVALENT FIRE ALARM AND DETECTION SYSTEMS FOR USE WHEN THE FIRE SYSTEM IS NOT CONNECTED TO THE CENTRAL FIRE SYSTEM. INSPECT AND TEST TEMPORARY SYSTEMS MONTHLY.
LS.01.02.01 EP 5,12
4
TEMPORARY PARTITION SHALL BE CONSTRUCTED TO MAINTAIN THE INTEGRITY OF THE CONSTRUCTION SITE PERIMETER. TEMPORARY PARTITIONS MUST BE SMOKE TIGHT AND CONSTRUCTED OF LIMITED COMBUSTIBLE MATERIAL.
LS.01.02.01 EP 7
5
ADDITIONAL FIRE FIGHTING EQUIPMENT SHALL BE INSTALLED IN AND /OR AROUND CONSTRUCTION AREA.
LS.01.02.01 EP 6
LIFE SAFETY CODE DEFICIENCIES AFFECTING COMPARTMENTATION FEATURES OR EXITING PLANS OF ADJACENT OCCUPIED AREAS, MAY NEED ADDITIONAL FIRE SAFETY TRAINING OR DRILLS. THIS TRAINING SHALL BE DETERMINED AND PERFORMED BY MAYO SAFETY AND SECURITY. INTERIM LIFE SAFETY DAILY LOG SHALL DOCUMENT: STORAGE, DEBRIS REMOVAL AND HOUSEKEEPING ARE PRACTICED AND PERFORMED TO KEEP CONSTRUCTION AREA AT THE LOWEST FLAMMABLE AND COMBUSTIBLE LOAD. EGRESS ROUTES INA ND AROUND CONSTRUCTION AREA ARE CLEAR OF ALL OBSTRUCTIONS. SURVEILLANCE OF BUILDINGS, GROUNDS, AND EQUIPMENT, GIVING SPECIAL ATTENTION TO CONSTRUCTION AREAS AND STORAGE.
LS.01.02.01 EP 10,11,13,14
6 7
OCCUPANCY
HEIGHT INFORMATION ALLOWED ACTUAL
BUSINESS GROUP
STORIES SPRINKLER INCREASE TOTAL
LS.01.02.01 EP 2 LS.01.02.01 EP 1,5
LS.01.02.01 EP 9 LS.01.02.01 EP 4 LS.01.02.01 EP 8
TYPE OF CONSTRUCTION
III-A - FULLY SPRINKLERED
NOTE: ALL MEDICAL SCIENCE BUILDING FLOORS ARE 1 HR RATED. FLOORS 4-6 MUST BE 1 CONTROL AREA. COMPARTMENT ZONE MS-04-1
COMPARTMENT OCCUPANCY (TABLE 1004.1.1)
BUSINESS AREA
FOURTH LEVEL TOTALS
COMPARTMENT AREA (SQ.FT.) 12,946
12,946
SQ.FTG.PER OCCUPANT (TABLE 1004.1.1) 100
5
6
+1
6
6
AREA CALCULATIONS ALLOWED
BASIC AREA (4TH LEVEL) 28,500 21,375 INCREASE FOR FRONTAGE 57,000 INCREASE FOR SPRINKLERS 106,875 SUB-TOTAL INCREASE FOR MULTI-STORY x3 (MAX) 320,625 TOTAL
ACTUAL
12,946 SF 12,946 SF 148,509 SF
HAZARDOUS MATERIAL CONTROL AREA (IBC 2000 TABLE 414.2.2 AS AMENDED BY MN STATE BUILDING CODE) PERCENT OF THE NUMBER OF FIRE RESISTANCE FLOOR MAXIMUM ALLOWABLE CONTROL AREAS RATING FOR FIRE QUANTITY PER LEVEL PER FLOOR BARRIERS (IN HOURS) CONTROL AREA 2* 1* 10 4-6 1 2 50 3 1 3 75 2 1 4 100 1 1 3 75 SUBWAY 1 2 50 BASEMENT
OCCUPANT LOAD 130 130
EXIT INCHES REQUIRED VERTICAL
130 x 0.3 = 39.0 39.0
JAS
RATINGS C
INTERIM LIFE SAFETY MEASURES (ILSM) DESIGN REVIEW
6287.040.04
HORIZONTAL 0 x 0.2 = 0.0 0.0
INCHES PROVIDED VERTICAL 105 105
TOTAL EXIT INCHES PROVIDED
S
1 HOUR RATED SMOKE BARRIER WITH 20 MINUTE DOORS
1
1 HOUR RATED FIRE BARRIER WITH 45-60 MINUTE DOORS
1S
1 HOUR RATED FIRE/SMOKE BARRIER WITH 45-60 MINUTE DOORS
2F
2 HOUR RATED FIRE BARRIER
2S
2 HOUR RATED FIRE/SMOKE BARRIER
3
3 HOUR RATED FIRE BARRIER
4
4 HOUR RATED FIRE/SMOKE BARRIER
0 105
JHA/MLK
Date
07/03/13
NOTICE: The designs shown and described herein including all technical drawings, graphics, and models thereof, are proprietary and cannot be copied, duplicated or commercially exploited, in whole or in part, without express written permission of RSP Architects. These are available for limited review and evaluation by clients, consultants, contractors, government agencies, vendors and office personnel only in accordance with this Notice. © Copyright RSP Architects 2007. All rights reserved.
Revisions No.
Date
Description
1 HOUR RATED FIRE CEILING ASSEMBLY
HORIZONTAL 0
Checked By
BR
1 HOUR RATED BULKHEAD EXTENDING FROM CEILING UP TO DECK
BH
BULKHEAD MEMBRANE TO EXTEND FROM RATED CEILING ASSEMBLY UP TO DECK
FC
1 HOUR RATED FIRE BARRIER (CORRIDOR) EXTENDING FROM FLOOR UP TO RATED CEILING
SYMBOLS FE FEC
FIRE EXTINGUISHER
FHC
FIRE HOSE CONNECTION
F SD S
FIRE EXTINGUISHER CABINET
FIRE ALARM PULL SMOKE DETECTORS EMERGENCY SHOWER EXIT SIGN
35"
EXIT WIDTH IN INCHES
124'
TRAVEL DISTANCE TO NEAREST EXIT
NOTE: THESE PLANS ARE BEING PROVIDED FOR INFORMATION ONLY BY MAYO CLINIC FACILITIES PROJECT SERVICES.
C:\Revit Projects\Med Sci 4 Central_jschmit.rvt 7/8/2013 11:23:12 AM
Please purchase PDF Split-Merge on www.verypdf.com to remove this watermark.
FOURTH LEVEL FIRE AND LIFE SAFETY PLAN
G104
2
1
8
33
2
6
39
20
42
8
2
WORK RM 4-35B
3
9
39
2
"OUT"
1
39
13
45
8
1
"OUT"
2
"OUT"
27
7
7
CORRIDOR 4-004D
7
6
45
ELEC RM 4-004D-1
2
"OUT" 2
16
2
2
45
16
6
"OUT" "OUT"
46
"OUT"
45
8
12
CORRIDOR 4-004E 16
LAB 4-29
2
12
39
1
2
"OUT"
12
"OUT"
"OUT" "OUT" FELLOWS
EQUIPMENT RM 4-29-1
"OUT"
"OUT"
1
1
"OUT"
"OUT"
42
"OUT"
"OUT" "OUT"
"OUT"
"OUT"
"OUT"
"OUT"
1
1
1
16
33
7
Date
1
2
OFFICE 4-29B
"OUT"
7
45
1
46
2
7
30
1
7
LAB 4-55 39
Large Animal Surgery and Germ Free Facility
6
42
TISSUE CULTURE 4-55A
12
2
39
"OUT"
"OUT"
27 16 1
45
45 2
"OUT"
"OUT"
7 "OUT"
"OUT"
"OUT"
"OUT"
"OUT"
"OUT"
2
K2
"OUT"
"OUT"
BREAKROOM 4-30 16
2
1
8
32
"OUT"
CONFERENCE 4-60 "OUT"
"OUT"
45
"OUT"
16
"OUT"
"OUT"
45
2
42
Medical Sciences Building Fourth Floor
2
1
M
"OUT"
2
"OUT"
7
12 1
"OUT"
"OUT"
1
"OUT"
"OUT"
2
6
"OUT"
2
OFFICE 4-57 39
"OUT"
42
Project #7R120760 1 2
5
"OUT"
A
"OUT" "OUT"
B
4"
16
"OUT"
2
"OUT"
07.03.13
2
2
"OUT"
3' - 8"
"OUT"
"OUT"
1' - 7"
"OUT"
"OUT"
5' - 11"
"OUT"
OFFICE 4-29C
"OUT"
11902
Project For
3
12
8
CORRIDOR 4-004C
6
"OUT"
Registration Number
"OUT"
43
3
DAVID NORBCK
13
4 "OUT"
I hereby certify that this plan, specification or report was prepared by me or under my direct supervision and that I am a duly licensed Architect under the laws of the State of Minnesota.
7
LAB 4-56
2
"OUT"
12 "OUT"
12
"OUT"
07.03.13
2
3
3
11902
Date
1
LAB 4-53
12
3
"OUT"
45
7
"OUT"
"OUT"
"OUT" "OUT" 2
DAVID NORBACK
Registration Number
"OUT"
3
12
1
45
"OUT" "OUT"
13
"OUT"
1
"OUT"
2
1
2
8
"OUT"
"OUT"
"OUT"
1
I hereby certify that I have reviewed the Mayo Clinic Standard General Specifications prepared by Ronald B. Carlson, License Number 10850, that they are appropriate for the work except as amended in this plan, specification or report, and that I am a duly licensed Architect under the laws of the State of Minnesota.
2
13
"OUT"
2
"OUT"
FELLOWS "OUT" 2 4-31 16
2
12
4-32
"OUT"
"OUT"
"OUT" "OUT" "OUT"
6
42
Certification
Signature
"OUT"
45
"OUT"
"OUT"
42
Signature
39
"OUT"
"OUT"
16
"OUT"
2
8
"OUT"
3
"OUT"
"OUT" "OUT" "OUT"
45
"OUT"
2
1
"OUT"
"OUT" "OUT"
13
12
LAB 4-54
"OUT"
"OUT" 16
16
39
2
1
12
3
WORK RM 4-53A
1
"OUT"
ELEC RM 4-004D-2
7
45
2
"OUT"
2
"OUT"
33
12
OFFICE 4-34
12
12
2
"OUT"
27
"OUT"
"OUT"
1
3
6
7
"OUT"
WORK RM 4-29A
"OUT"
Consultants
409
"OUT"
12
1
46
29
PREP 4-35A
42
1
45
2
"OUT"
24
"OUT"
"OUT"
"OUT"
2
2
"OUT"
VESTIBULE 4-49
2
LAB 4-45
RSP Architects 320 South Broadway Ste. B 507.285.6569 Rochester, Minnesota 55904 612.677.7499 fax www.rsparch.com
STORAGE 4-49A
"OUT"
1
20
12
7
"OUT"
STAIR 4-49B
1
2 "OUT"
1
1
1
3
12
6
42
"OUT"
1
15
"OUT"
2
"OUT"
2
39
2
3
OPERATING RM 4-35C
"OUT"
2
7
2
VESTIBULE 4-78
1
CORRIDOR 4-004F 16
PARTIAL FOURTH LEVEL DEMOLITION PLAN - AREA A
46
2
KEY PLAN
"OUT" "OUT"
Project No.
STORAGE 4-28
6287.040.04
Drawn By
JAS
Checked By
1/4" = 1'-0"
JHA/MLK
Date
07/03/13
NORTH KEYNOTES - DEMOLITION PLAN
DEMOLITION PLAN GENERAL NOTES: 1. SEE MECHANICAL DRAWINGS FOR DUCTWORK, DIFFUSER, PLENUM BOX, LIGHTING, ELECTRICAL CONDUIT, ETC. DEMOLITION AND/OR PROTECTION. 2. DEMOLITION IS NOT NECESSARILY LIMITED TO WHAT IS SHOWN ON DRAWINGS. THE INTENT IS TO INDICATE THE GENERAL SCOPE OF DEMOLITION REQUIRED TO COMPLETE THE WORK IN ACCORDANCE WITH THE CONTRACT DRAWINGS. 3. FIRE SAFETY MUST BE MAINTAINED FOR ALL PERSONNEL WORKING ON THE FLOOR. ALL FIRE STAIRS, ALARMS,SPEAKERS, ETC. MUST REMAIN ACCESSIBLE AND OPERABLE AT ALL TIMES. IMMEDIATELY NOTIFY BUILDING SECURITY AND BUILDING MANAGER OF DAMAGED OR DISABLED SYSTEMS AND REPAIR OR REPLACE DAMAGED SYSTEMS IMMEDIATELY. 4. ALL FIRE SAFETY EQUIPMENT AND THE ASSOCIATED CONDUIT AND WIRING SYSTEM SHALL NOT BE HARMED DURING DEMOLITION AND/OR CONSTRUCTION AND SHALL BE PROTECTED FROM ANY PHYSICAL DAMAGE. NO EXISTING SMOKE DETECTOR, PUBLIC ADDRESS SPEAKER, FIRE ALARM BOX OR SIMILAR DEVICE, INCLUDING THE ASSOCIATED WIRING SHALL BE DAMAGED DURING DEMOLITION AND SUBSEQUENT CONSTRUCTION. RELOCATION OF SMOKE DETECTORS, PUBLIC ADDRESS SPEAKERS AND FIRE ALARM EQUIPMENT, NECESSITATED BY NEW CONSTRUCTION, SHALL BE ACCOMPLISHED AS A FIRST PRIORITY, AND PER THE PLANS. NOTIFY BUILDING SECURITY AND MAYO CONSTRUCTION MANAGER OF DAMAGED OR DISABLED SYSTEMS AND REPAIR OR REPLACE DAMAGED SYSTEMS IMMEDIATELY. 5. LOUD DEMOLITION WORK (i.e. CONCRETE REMOVAL) SHALL BE COORDINATED WITH THE BUILDING MANAGER TO MINIMIZE DISRUPTION TO BUILDING OCCUPANTS. 6. CONTRACTOR SHALL BE RESPONSIBLE FOR PATCHING AND/OR REPAIRING ANY DAMAGE CAUSED BY HIM OR HIS SUBCONTRACTORS TO EXISTING CONSTRUCTION IN ELEVATOR LOBBIES, PUBLIC CORRIDORS OR RESTROOMS. REFINISH TO MATCH EXISTING ADJACENT FINISH, OR AS NOTED HEREIN. 7. ALL DIMENSIONS TO EXISTING ELEMENTS ARE FOR REFERENCE ONLY AND SHOULD BE FIELD VERIFIED. 8. THE INTENT OF THIS DEMOLITION IS TO PROVIDE A CLEAN AND CLEAR AREA FOR NEW CONSTRUCTION AND FINISHES AS INDICATED ON THESE ARCHITECTURAL DRAWINGS. A. DEMOLISH DASHED WALLS, MILLWORK, OR MISCELLANEOUS ITEMS. RELATED FRAMING, BRACING, AND ANCHORS MUST BE REMOVED. PROVIDE RELATED MECHANICAL/ELECTRICAL FOR THIS WORK. B. DEMOLISH FINISHES ON EXISTING WALLS OR SURFACES TO REMAIN WHERE NEW FINISHES ARE SCHEDULED. C. DEMOLISH FLOOR FINISHES AND BASE AS NOTED OR WHERE NEW FLOOR FINISHES AND BASE ARE SCHEDULED, INCLUDING ADHESIVES. D. DEMOLISH CEILINGS AND SOFFITS AS REQUIRED TO PROVIDE THE NEW CEILING LAYOUT (SEE CEILING PLAN). COORDINATE WORK INCLUDING THAT REQUIRED FOR MECHANICAL/ELECTRICAL. E. EXISTING WALLS AND SURFACES NOTED TO REMAIN, BUT DAMAGED PRIOR TO OR DURING DEMOLITION, MUST BE REPAIRED TO ACCEPT NEW FINISHES.
DEMOLITION PLAN LEGEND: EXISTING PARTITION TO REMAIN
EXISTING DOOR AND FRAME TO REMAIN
EXISTING PARTITION, CASEWORK, SHELVING, EQUIPMENT TO BE REMOVED
EXISTING DOOR AND FRAME TO BE REMOVED
C:\Revit Projects\Med Sci 4 Central_jschmit.rvt 7/8/2013 11:23:06 AM
Please purchase PDF Split-Merge on www.verypdf.com to remove this watermark.
ROOM NAME
ROOM TAG
1i "OUT"
1
KEYNOTE
1i
EQUIPMENT TO BE RELOCATED, REFER TO EQUIPMENT SCHEDULE
A
SPECIALTY EQUIPMENT TO BE RELOCATED, REFER TO SPECIALTY EQUIPMENT SCHEDULE
EXISTING FURNITURE TO BE RELOCATED, REFER TO FURNITURE SCHEDULE EXISTING FURNITURE AND EQUIPMENT TO BE REMOVED AND RETURNED TO OWNER'S STOCK.
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 27 29 30 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46
REMOVE COUNTERTOP AND BASE CABINETS. REMOVE WALL CABINETS AND/OR ADJUSTABLE SHELVING, STANDARDS, AND BRACKETS. REMOVE REAGENT SHELF, COUNTERTOP, AND BASE CABINETS. COORDINATE WITH MECHANICAL AND ELECTRICAL CONTRACTOR. REMOVE PLASTIC LAMINATE PIPETTE RACK. REMOVE PORTION OF WALL AS REQUIRED FOR NEW DOOR OPENINGS - SEE FLOOR PLAN FOR LOCATION AND DOOR SCHEDULE FOR FRAME SIZE. REMOVE COAT HOOK STRIP. REMOVE CORKBOARD/ WHITEBOARD. REMOVE STAINLESS STEEL SINK AND TOP - SEE PLUMBING DRAWINGS. REMOVE SHELF AND COAT ROD. REMOVE SHOWER CONTROLS, CURTAIN, ROD, AND ALL ASSOCIATED HARDWARE. REMOVE METAL LOCKERS. REMOVE WIREMOLD - SEE ELECTRICAL DRAWINGS. REMOVE DRYING RACK - RETURN TO OWNER'S STOCK. REMOVE ALL TOILET ACCESSORIES AND GRAB BARS. REMOVE SINK - SEE PLUMBING DRAWINGS. REMOVE EXISTING SUSPENDED ACOUSTICAL CEILING TILE AND GRID SYSTEM REMOVE URINAL - COORDINATE W/ MECHANICAL REMOVE P-LAM STORAGE UNIT AND RETURN TO OWNER'S STOCK. REMOVE TOILET - SEE PLUMBING DRAWINGS REMOVE X-RAY VIEWBOX. RETURN TO OWNER'S STOCK. REMOVE OPEN BOOK SHELF, HOLDER AND ALL ASSOCIATED HARDWARE. REMOVE TOILET PARTITION AND ALL ASSOCIATED HARDWARE REMOVE METAL SHELF. REMOVE MIRROR. REMOVE FIRE EXTINGUISHER - RETURN TO OWNER'S STOCK. REMOVE SLIDING DOOR AND ALL ASSOCIATED HARDWARE. REMOVE PRIVACY CURTAIN AND ALL ASSOCIATED HARDWARE. REMOVE PROJECTOR SCREEN. REMOVE GAS CYLINDER AND SUPPORT BRAQCKETS. REMOVE ELECTRIC WATER COOLER - SEE PLUMBING AND ELECTRICAL DRAWINGS. REMOVE STERILIZER - CORDINATE W/ MECHANICAL & ELECTRICAL REMOVE MINI BLIND. REMOVE AND SALVAGE EXISTING SCRUB SINK FOR REUSE - SEE PLUMBING DRAWINGS. EXISTING SCRUB SINK TO REMAIN REMOVE EXISTING SUSPENDED GYPSUM BOARD CEILING SYSTEM. REMOVE EXISTING EXAM ROOM LIGHTING AND TRACK. PATCH EXISTING PLASTER CEILING AND PREPARE FOR NEW FINISHES. REMOVE EXISTING GYPSUM BOARD CEILING AND INSTALL NEW STRUCTURAL SUPPORT FOR EXAM LIGHT. FIELD VERIFY EXACT LOCATION. PATCH CEILING UPON COMPLETION OF STRUCTURAL SUPPORT WORK AND PREPARE FOR NEW FINISHES. REMOVE EXISTING SHEET VINYL FLOORING AND COVED BASE IN THIS ROOM - PREPARE FOR NEW FINISHES. REMOVE EXISTING SHEET VINYL FLOORING VINYL BASE IN THIS ROOM - PREPARE FOR NEW FINISHES. REMOVE EXISTING CERAMIC TILE AND BASE IN THIS ROOM - PREPARE FOR NEW FINISHES. REMOVE EXISTING VCT AND VINYL BASE IN THIS ROOM - PREPARE FOR NEW FINISHES. REMOVE EXISTING SUSPENDED GLUE ON ACT AND GYPSUM BACKER BOARD IN THIS ROOM/AREA.
NOTICE: The designs shown and described herein including all technical drawings, graphics, and models thereof, are proprietary and cannot be copied, duplicated or commercially exploited, in whole or in part, without express written permission of RSP Architects. These are available for limited review and evaluation by clients, consultants, contractors, government agencies, vendors and office personnel only in accordance with this Notice. © Copyright RSP Architects 2007. All rights reserved.
Revisions No.
Date
Description
PARTIAL FOURTH LEVEL DEMOLITION PLAN - AREA A
D104A
"OUT"
1
45
7
2
45
"OUT"
"OUT"
16
VESTIBULE 4-78
CORRIDOR 4-004F
5' - 0"
16
"OUT"
46
1
21
2
1
45
"OUT"
2
18
WORK RM 4-25 16
"OUT"
45
21
"OUT"
7
"OUT"
"OUT"
SOILED WORK 4-26 39
8
42
12
39 2
42
12
45
1
2
2
"OUT" "OUT"
"OUT"
"OUT"
6
"OUT"
1
39
16
45
3
5
"OUT"
6
6
5
5
7
MEN'S 4-01
9 39
44
39
46
2
22
14
LOCKER RM 4-01A 39
10
45 "OUT"
45
"OUT"
2
"OUT""OUT"
RECOVERY 4-74 39
45
22
18
1
29
PREP 4-72
23
39
38
42
21
"OUT"
1
2
14
"OUT"
EQUIPMENT 4-70 "OUT"
2
2
39
24
1
37
18
"OUT"
42
OPERATING 4-71
2
41
6
41
2
6
33
2
"OUT"
Signature
DAVID NORBCK 11902
2
K
40 41
"OUT"
K1
41
"OUT" 2
1
12 1
45
"OUT"
16
"OUT" "OUT"
"OUT"
2
LAB 4-65
45
"OUT"
"OUT"
8
"OUT"
1
2
2
Medical Sciences Building Fourth Floor
2
3
"OUT"
2
Large Animal Surgery and Germ Free Facility
"OUT"
7
"OUT"
"OUT"
Project For
"OUT"
7
"OUT"
7
OPERATING 4-67
OPERATING 4-69
2
6
6
6
07.03.13
27
12
1
07.03.13
I hereby certify that this plan, specification or report was prepared by me or under my direct supervision and that I am a duly licensed Architect under the laws of the State of Minnesota.
"OUT"
12
16
12
2
36
41
11902
2
36
36
2
"OUT"
EQUIPMENT 4-65A
1
2
K3
12
2
23
40
"OUT"
1
37
23
"OUT"
OPERATING 4-73
Registration Number
DAVID NORBACK
Date
"OUT"
40
21
8
7
40
19
2
"OUT"
7
24
K1
40
45
Signature
Registration Number
6 1
16
5
PREP 4-68
15
9
LAB 4-64
4
"OUT"
Date
2
24
44 "OUT"
6
"OUT"
11
11
"OUT"
I hereby certify that I have reviewed the Mayo Clinic Standard General Specifications prepared by Ronald B. Carlson, License Number 10850, that they are appropriate for the work except as amended in this plan, specification or report, and that I am a duly licensed Architect under the laws of the State of Minnesota.
2
1
STORAGE 4-62C 39
7
5
46
2
"OUT"
44
ELECTRIC 4-00B-1
CORRIDOR 4-004B
45
Certification
20
OFFICE 4-75 WOMEN'S 4-04
Consultants
"OUT"
2
7
16
1
45
"OUT"
2
46
"OUT"
42
M
CUSTODIAL 4-03 10 2 39 44
45
12
45
2
VESTIBULE 4-76 21
LAB 4-63
10
WORK RM 4-62
2
RSP Architects 320 South Broadway Ste. B 507.285.6569 Rochester, Minnesota 55904 612.677.7499 fax www.rsparch.com
1
2
46
2
10
1
CORRIDOR 4-004
8
12
7
10
6
7 2
1
ANTE RM 4-24 21
15
"OUT"
"OUT"
7
OFFICE 4-62B 1 16 45
"OUT"
6
LAB 4-24A
16
"OUT" "OUT"
9
STAIR 4-08
24
5
42
2
"OUT"
7
"OUT"
21
12
45
"OUT"
6
7
1
11
OFFICE 4-62A
16
35
6
1
34
39
"OUT"
2
OFFICE 4-57
6
7
"OUT"
STERILIZER 4-27
2
2
2
2
"OUT"
9
37
22
"OUT"
"OUT"
"OUT" "OUT"
2
39
27
"OUT"
"OUT"
2 "OUT"
7' - 10 1/4"
12
"OUT"
19
32
STORAGE 4-28
"OUT"
21
17
16
"OUT"
STORAGE 4-07
39
45
2
MECH RM 4-05
22
8
2
6' - 0 1/4"
"OUT"
CLOSET 4-004-1
1
4"
"OUT"
"OUT"
"OUT"
2
BREAKROOM 4-30
1' - 7"
7 16
"OUT"
"OUT"
16
"OUT"
5' - 11"
OFFICE 4-29B
CONFERENCE 4-60 "OUT"
"OUT"
30
12
8
1
1 "OUT"
1
29
2 12
LAB 4-66 16
45
Project #7R120760
12 "OUT"
A
2 33 1
B
KEY PLAN
Project No.
PARTIAL FOURTH LEVEL DEMOLITION PLAN - AREA B
1
6287.040.04
Drawn By
1/4" = 1'-0"
NORTH
JAS
Checked By
JHA/MLK
KEYNOTES - DEMOLITION PLAN DEMOLITION PLAN GENERAL NOTES: 1. SEE MECHANICAL DRAWINGS FOR DUCTWORK, DIFFUSER, PLENUM BOX, LIGHTING, ELECTRICAL CONDUIT, ETC. DEMOLITION AND/OR PROTECTION. 2. DEMOLITION IS NOT NECESSARILY LIMITED TO WHAT IS SHOWN ON DRAWINGS. THE INTENT IS TO INDICATE THE GENERAL SCOPE OF DEMOLITION REQUIRED TO COMPLETE THE WORK IN ACCORDANCE WITH THE CONTRACT DRAWINGS. 3. FIRE SAFETY MUST BE MAINTAINED FOR ALL PERSONNEL WORKING ON THE FLOOR. ALL FIRE STAIRS, ALARMS,SPEAKERS, ETC. MUST REMAIN ACCESSIBLE AND OPERABLE AT ALL TIMES. IMMEDIATELY NOTIFY BUILDING SECURITY AND BUILDING MANAGER OF DAMAGED OR DISABLED SYSTEMS AND REPAIR OR REPLACE DAMAGED SYSTEMS IMMEDIATELY. 4. ALL FIRE SAFETY EQUIPMENT AND THE ASSOCIATED CONDUIT AND WIRING SYSTEM SHALL NOT BE HARMED DURING DEMOLITION AND/OR CONSTRUCTION AND SHALL BE PROTECTED FROM ANY PHYSICAL DAMAGE. NO EXISTING SMOKE DETECTOR, PUBLIC ADDRESS SPEAKER, FIRE ALARM BOX OR SIMILAR DEVICE, INCLUDING THE ASSOCIATED WIRING SHALL BE DAMAGED DURING DEMOLITION AND SUBSEQUENT CONSTRUCTION. RELOCATION OF SMOKE DETECTORS, PUBLIC ADDRESS SPEAKERS AND FIRE ALARM EQUIPMENT, NECESSITATED BY NEW CONSTRUCTION, SHALL BE ACCOMPLISHED AS A FIRST PRIORITY, AND PER THE PLANS. NOTIFY BUILDING SECURITY AND MAYO CONSTRUCTION MANAGER OF DAMAGED OR DISABLED SYSTEMS AND REPAIR OR REPLACE DAMAGED SYSTEMS IMMEDIATELY. 5. LOUD DEMOLITION WORK (i.e. CONCRETE REMOVAL) SHALL BE COORDINATED WITH THE BUILDING MANAGER TO MINIMIZE DISRUPTION TO BUILDING OCCUPANTS. 6. CONTRACTOR SHALL BE RESPONSIBLE FOR PATCHING AND/OR REPAIRING ANY DAMAGE CAUSED BY HIM OR HIS SUBCONTRACTORS TO EXISTING CONSTRUCTION IN ELEVATOR LOBBIES, PUBLIC CORRIDORS OR RESTROOMS. REFINISH TO MATCH EXISTING ADJACENT FINISH, OR AS NOTED HEREIN. 7. ALL DIMENSIONS TO EXISTING ELEMENTS ARE FOR REFERENCE ONLY AND SHOULD BE FIELD VERIFIED. 8. THE INTENT OF THIS DEMOLITION IS TO PROVIDE A CLEAN AND CLEAR AREA FOR NEW CONSTRUCTION AND FINISHES AS INDICATED ON THESE ARCHITECTURAL DRAWINGS. A. DEMOLISH DASHED WALLS, MILLWORK, OR MISCELLANEOUS ITEMS. RELATED FRAMING, BRACING, AND ANCHORS MUST BE REMOVED. PROVIDE RELATED MECHANICAL/ELECTRICAL FOR THIS WORK. B. DEMOLISH FINISHES ON EXISTING WALLS OR SURFACES TO REMAIN WHERE NEW FINISHES ARE SCHEDULED. C. DEMOLISH FLOOR FINISHES AND BASE AS NOTED OR WHERE NEW FLOOR FINISHES AND BASE ARE SCHEDULED, INCLUDING ADHESIVES. D. DEMOLISH CEILINGS AND SOFFITS AS REQUIRED TO PROVIDE THE NEW CEILING LAYOUT (SEE CEILING PLAN). COORDINATE WORK INCLUDING THAT REQUIRED FOR MECHANICAL/ELECTRICAL. E. EXISTING WALLS AND SURFACES NOTED TO REMAIN, BUT DAMAGED PRIOR TO OR DURING DEMOLITION, MUST BE REPAIRED TO ACCEPT NEW FINISHES.
DEMOLITION PLAN LEGEND: EXISTING PARTITION TO REMAIN
EXISTING DOOR AND FRAME TO REMAIN
ROOM NAME
ROOM TAG
"OUT"
1
KEYNOTE
EXISTING PARTITION, CASEWORK, SHELVING, EQUIPMENT TO BE REMOVED
1i
EQUIPMENT TO BE RELOCATED, REFER TO EQUIPMENT SCHEDULE
EXISTING DOOR AND FRAME TO BE REMOVED
A
SPECIALTY EQUIPMENT TO BE RELOCATED, REFER TO SPECIALTY EQUIPMENT SCHEDULE
C:\Revit Projects\Med Sci 4 Central_jschmit.rvt 7/8/2013 11:23:08 AM
Please purchase PDF Split-Merge on www.verypdf.com to remove this watermark.
1i
EXISTING FURNITURE TO BE RELOCATED, REFER TO FURNITURE SCHEDULE EXISTING FURNITURE AND EQUIPMENT TO BE REMOVED AND RETURNED TO OWNER'S STOCK.
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 27 29 30 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46
REMOVE COUNTERTOP AND BASE CABINETS. REMOVE WALL CABINETS AND/OR ADJUSTABLE SHELVING, STANDARDS, AND BRACKETS. REMOVE REAGENT SHELF, COUNTERTOP, AND BASE CABINETS. COORDINATE WITH MECHANICAL AND ELECTRICAL CONTRACTOR. REMOVE PLASTIC LAMINATE PIPETTE RACK. REMOVE PORTION OF WALL AS REQUIRED FOR NEW DOOR OPENINGS - SEE FLOOR PLAN FOR LOCATION AND DOOR SCHEDULE FOR FRAME SIZE. REMOVE COAT HOOK STRIP. REMOVE CORKBOARD/ WHITEBOARD. REMOVE STAINLESS STEEL SINK AND TOP - SEE PLUMBING DRAWINGS. REMOVE SHELF AND COAT ROD. REMOVE SHOWER CONTROLS, CURTAIN, ROD, AND ALL ASSOCIATED HARDWARE. REMOVE METAL LOCKERS. REMOVE WIREMOLD - SEE ELECTRICAL DRAWINGS. REMOVE DRYING RACK - RETURN TO OWNER'S STOCK. REMOVE ALL TOILET ACCESSORIES AND GRAB BARS. REMOVE SINK - SEE PLUMBING DRAWINGS. REMOVE EXISTING SUSPENDED ACOUSTICAL CEILING TILE AND GRID SYSTEM REMOVE URINAL - COORDINATE W/ MECHANICAL REMOVE P-LAM STORAGE UNIT AND RETURN TO OWNER'S STOCK. REMOVE TOILET - SEE PLUMBING DRAWINGS REMOVE X-RAY VIEWBOX. RETURN TO OWNER'S STOCK. REMOVE OPEN BOOK SHELF, HOLDER AND ALL ASSOCIATED HARDWARE. REMOVE TOILET PARTITION AND ALL ASSOCIATED HARDWARE REMOVE METAL SHELF. REMOVE MIRROR. REMOVE FIRE EXTINGUISHER - RETURN TO OWNER'S STOCK. REMOVE SLIDING DOOR AND ALL ASSOCIATED HARDWARE. REMOVE PRIVACY CURTAIN AND ALL ASSOCIATED HARDWARE. REMOVE PROJECTOR SCREEN. REMOVE GAS CYLINDER AND SUPPORT BRAQCKETS. REMOVE ELECTRIC WATER COOLER - SEE PLUMBING AND ELECTRICAL DRAWINGS. REMOVE STERILIZER - CORDINATE W/ MECHANICAL & ELECTRICAL REMOVE MINI BLIND. REMOVE AND SALVAGE EXISTING SCRUB SINK FOR REUSE - SEE PLUMBING DRAWINGS. EXISTING SCRUB SINK TO REMAIN REMOVE EXISTING SUSPENDED GYPSUM BOARD CEILING SYSTEM. REMOVE EXISTING EXAM ROOM LIGHTING AND TRACK. PATCH EXISTING PLASTER CEILING AND PREPARE FOR NEW FINISHES. REMOVE EXISTING GYPSUM BOARD CEILING AND INSTALL NEW STRUCTURAL SUPPORT FOR EXAM LIGHT. FIELD VERIFY EXACT LOCATION. PATCH CEILING UPON COMPLETION OF STRUCTURAL SUPPORT WORK AND PREPARE FOR NEW FINISHES. REMOVE EXISTING SHEET VINYL FLOORING AND COVED BASE IN THIS ROOM - PREPARE FOR NEW FINISHES. REMOVE EXISTING SHEET VINYL FLOORING VINYL BASE IN THIS ROOM - PREPARE FOR NEW FINISHES. REMOVE EXISTING CERAMIC TILE AND BASE IN THIS ROOM - PREPARE FOR NEW FINISHES. REMOVE EXISTING VCT AND VINYL BASE IN THIS ROOM - PREPARE FOR NEW FINISHES. REMOVE EXISTING SUSPENDED GLUE ON ACT AND GYPSUM BACKER BOARD IN THIS ROOM/AREA.
Date
07/03/13
NOTICE: The designs shown and described herein including all technical drawings, graphics, and models thereof, are proprietary and cannot be copied, duplicated or commercially exploited, in whole or in part, without express written permission of RSP Architects. These are available for limited review and evaluation by clients, consultants, contractors, government agencies, vendors and office personnel only in accordance with this Notice. © Copyright RSP Architects 2007. All rights reserved.
Revisions No.
Date
Description
PARTIAL FOURTH LEVEL DEMOLITION PLAN - AREA B
D104B
O107
O124
O108
M103
M101
M225
M100 O104 "OUT" O132
"OUT"
O105
M227
"OUT"
OPERATING RM 4-35C
"OUT" "OUT"
"OUT"
WORK RM 4-35B
M115
O113
"OUT"
M239
O101
OUT"
M242
M220
M114
M113
M112 M109
G108
CORRIDOR 4-004D
O133
ELEC RM 4-004D-1
ELEC RM 4-004D-2
G145
G146
WORK RM 4-29A
G144
"OUT"
"OUT"
G111
G112
N106
"OUT"
"OUT"
"OUT"
N108
N107
"OUT"
C112
C113
LAB 4-29
G120
C123 C121
"OUT"
C105
"OUT"
CORRIDOR 4-004C
"OUT"
"OUT"
C115
C122 C116
G118 G115
N101
C117
N100
C119
N102
"OUT"
G138 "OUT"
C101
G134
G135
G140
"OUT" "OUT"
Project #7R120760
OFFICE 4-57
"OUT"
CONFERENCE 4-60
"OUT"
"OUT"
Medical Sciences Building Fourth Floor
G141
G137
"OUT"
"OUT"
Large Animal Surgery and Germ Free Facility
G142
G139
BREAKROOM 4-30
M118
G117
TISSUE CULTURE 4-55A
N138
OFFICE 4-29C
G119
G143
LAB 4-55
N103
"OUT"
C102
C100
M119
07.03.13
G114
LAB 4-56
N105
N104
C118
EQUIPMENT RM 4-29-1
11902
C106
C120
"OUT"
DAVID NORBCK
Date
G116
C105
"OUT"
FELLOWS 4-31
1
I hereby certify that this plan, specification or report was prepared by me or under my direct supervision and that I am a duly licensed Architect under the laws of the State of Minnesota.
Project For
C105
"OUT"
M120
07.03.13
Registration Number
G113
C103
C111
CORRIDOR 4-004E
X111
G122
Date
Signature
"OUT"
X110
G123
11902
G121
FELLOWS 4-32
"OUT"
G124
LAB 4-53
"OUT"
N228
"OUT"
G125
G126 M104
DAVID NORBACK
Registration Number
G127
"OUT"
"OUT"
"OUT"
I hereby certify that I have reviewed the Mayo Clinic Standard General Specifications prepared by Ronald B. Carlson, License Number 10850, that they are appropriate for the work except as amended in this plan, specification or report, and that I am a duly licensed Architect under the laws of the State of Minnesota.
Signature
LAB M107 4-54
OFFICE 4-34
Certification
G130
"OUT"
"OUT"
"OUT"
G131
G128
"OUT"
"OUT"
G132
G129
O102
G147
WORK RM 4-53A G133
G109
M106 M105
G102
G104
G105
G107
Consultants
"OUT"
G101
M108
PREP 4-35A
"OUT"
STORAGE 4-49A
VESTIBULE 4-49
M243
M245
RSP Architects 320 South Broadway Ste. B 507.285.6569 Rochester, Minnesota 55904 612.677.7499 fax www.rsparch.com
M222
"OUT"
LAB 4-45
M244
M241
"OUT"
"OUT"
M226
"OUT"
M224
M116
M231
M110
"OUT"
O106
M102
O100
M230
STAIR 4-49B
A
"OUT" B
"OUT"
?
KEY PLAN
?
Project No.
6287.040.04
Drawn By
PARTIAL FOURTH LEVEL DEMOLITION EQUIPMENT PLAN - AREA A
JAS
Checked By
1/4" = 1'-0"
JHA/MLK
Date
NOTICE: The designs shown and described herein including all technical drawings, graphics, and models thereof, are proprietary and cannot be copied, duplicated or commercially exploited, in whole or in part, without express written permission of RSP Architects. These are available for limited review and evaluation by clients, consultants, contractors, government agencies, vendors and office personnel only in accordance with this Notice.
DEMOLITION PLAN LEGEND: EXISTING PARTITION TO REMAIN
EXISTING DOOR AND FRAME TO REMAIN
07/03/13
ROOM NAME
ROOM TAG
1i "OUT"
1
KEYNOTE
EXISTING PARTITION, CASEWORK, SHELVING, EQUIPMENT TO BE REMOVED
1i
EQUIPMENT TO BE RELOCATED, REFER TO EQUIPMENT SCHEDULE
EXISTING DOOR AND FRAME TO BE REMOVED
A
SPECIALTY EQUIPMENT TO BE RELOCATED, REFER TO SPECIALTY EQUIPMENT SCHEDULE
EXISTING FURNITURE TO BE RELOCATED, REFER TO FURNITURE SCHEDULE EXISTING FURNITURE AND EQUIPMENT TO BE REMOVED AND RETURNED TO OWNER'S STOCK.
© Copyright RSP Architects 2007. All rights reserved.
Revisions No.
Date
Description
PARTIAL FOURTH LEVEL DEMOLITION EQUIPMENT PLAN - AREA A
D204A C:\Revit Projects\Med Sci 4 Central_jschmit.rvt 7/8/2013 11:23:09 AM
Please purchase PDF Split-Merge on www.verypdf.com to remove this watermark.
"OUT"
"OUT"
M118
VESTIBULE 4-78
"OUT"
CORRIDOR 4-004F
"OUT"
"OUT"
MECH RM 4-05
?
"OUT"
WORK RM 4-25
"OUT"
Z208
"OUT"
SOILED WORK 4-26
"OUT"
"OUT"
Consultants
"OUT" "OUT"
WORK RM 4-62 OFFICE 4-62B
Certification
"OUT"
C109
"OUT"
Z206
"OUT"
LAB 4-63
C124
M123
"OUT"
"OUT"
Z212
Z210
Z209
STERILIZER 4-27
"OUT"
"OUT"
M122
OFFICE 4-62A
"OUT"
Z202
Z229
"OUT"
M117
"OUT"
Z225
RSP Architects 320 South Broadway Ste. B 507.285.6569 Rochester, Minnesota 55904 612.677.7499 fax www.rsparch.com
"OUT" "OUT"
Z224
"OUT"
?
?
STORAGE 4-28
"OUT"
STORAGE 4-07
"OUT"
I hereby certify that I have reviewed the Mayo Clinic Standard General Specifications prepared by Ronald B. Carlson, License Number 10850, that they are appropriate for the work except as amended in this plan, specification or report, and that I am a duly licensed Architect under the laws of the State of Minnesota.
"OUT"
Z215
C108
"OUT"
LAB Z207 4-24A
STAIR 4-08
Signature
STORAGE 4-62C
ANTE RM 4-24
Z205
Registration Number
"OUT"
"OUT"
"OUT" LAB
"OUT"
VESTIBULE 4-76
4-64
"OUT"
CUSTODIAL 4-03
OFFICE 4-75
"OUT" "OUT"
WOMEN'S 4-04
"OUT"
MEN'S 4-01
"OUT"
"OUT"
RECOVERY 4-74
"OUT"
"OUT"
"OUT"
"OUT"
"OUT"
"OUT" "OUT"
"OUT"
"OUT" "OUT"
Z131
"OUT"
"OUT"
"OUT"
Z174
PREP 4-68
N111
"OUT"
"OUT"
Z167
Z129
"OUT"
OPERATING 4-71
Z162
"OUT"
"OUT"
Z141 Z143 Z142
N109
"OUT"
OPERATING 4-69
N112
"OUT"
"OUT"
"OUT" "OUT"
"OUT"
"OUT"
"OUT" Z183
"OUT"
"OUT"
"OUT"
"OUT"
"OUT" "OUT"
N130
"OUT" "OUT"
N137
Project #7R120760
N119
N131
"OUT"
Medical Sciences Building Fourth Floor
N125
N123
N129 N110
Large Animal Surgery and Germ Free Facility
N124
N128
"OUT"
"OUT"
N126 N127
"OUT"
Project For
LAB 4-65
"OUT"
"OUT"
07.03.13
N117
N113
N118
Z181
"OUT"
"OUT" "OUT"
"OUT"
11902
N115
N136
OPERATING Z182 4-67
"OUT" "OUT" "OUT"
"OUT"
"OUT" "OUT"
Z128
"OUT"
"OUT"
"OUT"
"OUT"
Z163
"OUT"
"OUT"
"OUT"
Z161
"OUT"
Z130
Z165
OPERATING 4-73
"OUT"
"OUT"
EQUIPMENT 4-65A
"OUT"
"OUT"
"OUT"
4-70
"OUT"
Z160
"OUT"
N114
"OUT" EQUIPMENT
"OUT"
"OUT"
DAVID NORBCK
Date
"OUT"
LOCKER RM 4-01A
Signature Registration Number
PREP 4-72
"OUT"
07.03.13
I hereby certify that this plan, specification or report was prepared by me or under my direct supervision and that I am a duly licensed Architect under the laws of the State of Minnesota.
ELECTRIC 4-00B-1
CORRIDOR 4-004B
11902
Date
CLOSET 4-004-1 CORRIDOR 4-004
DAVID NORBACK
N121 A
N132
"OUT"
LAB 4-66 N120
N122
N133
B
KEY PLAN
N139
Project No.
6287.040.04
Drawn By
1
PARTIAL FOURTH LEVEL DEMOLITION EQUIPMENT PLAN - AREA B
Checked By
1/4" = 1'-0"
Date
JHA/MLK 07/03/13
NOTICE: The designs shown and described herein including all technical drawings, graphics, and models thereof, are proprietary and cannot be copied, duplicated or commercially exploited, in whole or in part, without express written permission of RSP Architects. These are available for limited review and evaluation by clients, consultants, contractors, government agencies, vendors and office personnel only in accordance with this Notice.
DEMOLITION PLAN LEGEND: EXISTING PARTITION TO REMAIN
JAS
ROOM NAME
ROOM TAG
1i
EXISTING FURNITURE TO BE RELOCATED, REFER TO FURNITURE SCHEDULE
© Copyright RSP Architects 2007. All rights reserved.
Revisions EXISTING DOOR AND FRAME TO REMAIN
"OUT"
1
KEYNOTE
EXISTING PARTITION, CASEWORK, SHELVING, EQUIPMENT TO BE REMOVED
1i
EQUIPMENT TO BE RELOCATED, REFER TO EQUIPMENT SCHEDULE
EXISTING DOOR AND FRAME TO BE REMOVED
A
SPECIALTY EQUIPMENT TO BE RELOCATED, REFER TO SPECIALTY EQUIPMENT SCHEDULE
EXISTING FURNITURE AND EQUIPMENT TO BE REMOVED AND RETURNED TO OWNER'S STOCK.
No.
Date
Description
PARTIAL FOURTH LEVEL DEMOLITION EQUIPMENT PLAN - AREA B
D204B C:\Revit Projects\Med Sci 4 Central_jschmit.rvt 7/8/2013 11:23:10 AM
Please purchase PDF Split-Merge on www.verypdf.com to remove this watermark.
5
2
35
A902
P
33
TOILET/ CHANGE 4-11A
O
4-11A
VESTIBULE/ LOCKER
2
G
2
M
3
10' - 0"
9' - 9 1/2"
5"
4-12D
E
6
D
J
A901
5"
B57-PL
9
13
B
2
O
5"
OFFICE
N
A
2
B
A902 8
3
A901
9
B57-PL 15
N
11' - 9"
N
4
21
8
E
1
4-12-2
N
B
B
2
A901 C37-PL
B
OFFICE
B57-PL
5"
29
5' - 0"
5"
10' - 0"
17
ENLARGED TOILET/CHANGE ROOM PLAN
A901 27
1/2" = 1'-0"
9
B57-PL
9
28
A901
4-26
Dr. McGregor
16' - 1"
24
4-12-3
31
D
33
10
1
A901
B
8' - 9 1/2"
3 9' - 7 1/4"
5' - 2"
B
J
A901
FLEX LAB (MICROBIOME)
9
B57-PL
16
26
9 1' - 0"
5' - 0" O
3
E
L 3
O
M
3
3
M
07.03.13
Project For
3
2
6' - 3"
CORRIDOR
B
4-04-5
1
2
N O
2
4-24
E TYP.
8 A301
1 U
2
B
11
26
TOILET/ CHANGE
4-24
2 B
2
B
14 4-16
Medical Sciences Building Fourth Floor
2
Project #7R120760
N O
2
E
2
1
2
M1
5
O N
19
4
A903
OFFICE
4-15
4-11A
M1
N
5" 4-04-4
4-11
4
Large Animal Surgery and Germ Free Facility
2
M
M1
O N
A
3
2 B
OFFICE
2
CORRIDOR 4-04-3
4-23
VESTIBULE/ LOCKER
A903
KEY PLAN
7
4-11
Project No. Drawn By
1/4" = 1'-0"
Checked By
NORTH FLOOR PLAN LEGEND:
KEYNOTES - FLOOR PLAN
1. LOCATION OF EQUIPMENT SUCH AS UMBILICAL, FUME HOODS, BRACES, OR ANY OTHER ITEMS THAT MAY INTERFERE WITH THE LIGHTING, STRUCTURAL, OR MECHANICAL SYSTEMS, SHALL BE CAREFULLY COORDINATED AND DISCREPANCIES BROUGHT TO THE ARCHITECTS ATTENTION IMMEDIATELY.
EXISTING PARTITION TO REMAIN
2. WALL SHELVING OR REAGENT SHELVING SUPPORTS SHALL BE SPACED AND POSITIONED TO CLEAR FITTINGS, ELECTRICAL PEDESTALS, SINKS AND CUP SINKS.
EXISTING DOOR AND FRAME TO REMAIN
3. OVERALL LENGTH OF TOPS SHALL BE DETERMINED BY CASEWORK AND DIMENSIONS AS INDICATED ON PLANS. TOPS SHALL OVERHANG ½” AT EACH END AND 1” FROM FRONT OF BASE CABINET. WHEN OVERALL DIMENSIONS ARE GIVEN, ½” OVERHANG IS NOT INCLUDED.
ROOM NAME
9. PLUMBING FITTINGS OTHER THAN THOSE IN THE FUME HOODS OR FUME HOOD BASE CABINETS SHALL BE SUPPLIED AND INSTALLED BY MECHANICAL CONTRACTOR. ALL PLUMBING FITTINGS SHALL HAVE FINAL CONNECTION BY MECHANICAL CONTRACTOR. 10. ALL PLUMBING SYSTEM HANGERS AND FASTENERS SHALL BE PROVIDED AND INSTALLED BY MECHANICAL CONTRACTOR. 11. ALL LABORATORY SINKS AND CUP SINKS SHALL BE FURNISHED BY LAB CASEWORK CONTRACTOR. FINAL CONNECTION BY MECHANICAL CONTRACTOR. 12. FUME HOODS WILL BE PRE-PLUMBED AND PRE-WIRED. 13. ALL EXPOSED PIPING AND CONDUIT SHALL BE PAINTED TO MATCH THE ADJACENT SURFACE. 14. ALL PENETRATIONS THROUGH COUNTERTOP SHALL BE SEALED BY LAB FURNISHINGS CONTRACTOR WITH ACID RESISTANT SEALANT. 15. ALL PLAN DIMENSIONS LOCATING INTERIOR WALLS ARE TO: a: FACE OF EXISTING WALL SYSTEM UNLESS NOTED OTHERWISE. b: FACE OF GYPSUM BOARD UNLESS NOTED OTHERWISE. c: CENTERLINE OF BUILDING GRID.
ROOM TAG
2
1i
KEYNOTE
1
18. EXISTING PENETRATIONS IN RATED PARTITIONS TO BE FIRESTOPPED & SEALED. NEW MECHANICAL / ELECTRICAL PENETRATIONS TO BE FIRESTOPPED & SEALED. ALL SUBCONTRACTORS TO USE THE SAME FIRESTOPPING SYSTEM.
Please purchase PDF Split-Merge on www.verypdf.com to remove this watermark.
NEW PARTITION AS SCHEDULED, SEE MAYO SPECIFICATIONS SECTION 09200 FOR PARTITION CONSTRUCTION
COUNTERTOP TAG
1i
EQUIPMENT TAG
A
SPECIALITY EQUIPMENT TAG
3 4 5 6
8
TAG B C.1 C.2 D E G
G1 GB-18 GB-36 GB-42 H J K K1 K2 K3 L
DESCRIPTION
SPECIALTY EQUIPMENT SCHEDULE ORDERED BY SUPPLIED BY INSTALLED BY
M M1 N O
9 10
QTY
TO ROOM
TOILET PAPER DISPENSER SANITARY PRODUCT DISPOSAL SANITARY PRODUCT DISPENSER SOAP DISPENSER PAPER TOWEL DISPENSER 24" X 60" MIRROR
4 2 1 8 8 3
CONTRACTOR CONTRACTOR CONTRACTOR CONTRACTOR CONTRACTOR CONTRACTOR
FACILITIES WAREHOUSE FACILITIES WAREHOUSE FACILITIES WAREHOUSE FACILITIES WAREHOUSE FACILITIES WAREHOUSE MANUFACTURER
CONTRACTOR CONTRACTOR CONTRACTOR CONTRACTOR CONTRACTOR CONTRACTOR
GEORGIA PACIFIC - MODEL #56784 ASI - MODEL #0852 ROCHESTER MIDLAND - MODEL #C2591100J655 DERMAPRO - MODEL #9021-ALMOND GEORGIA PACIFIC - MODEL #59462 TSM - MODEL #M-1
12" x 24" MIRROR GRAB BARS GRAB BARS GRAB BARS COAT HOOK 30" X 36" DRYING RACK 36" x 48" WHITEBOARD 48" x 36" WHITEBOARD 48" x 48" WHITEBOARD 72" x 48" WHITEBOARD METAL LOCKERS
1 3 3 3 3 4 1 2 1 1 16
SEE PLAN 4-03, 4-11A 4-03 4-02, 4-03, 4-11A 4-02, 4-03, 4-11A 236, 238, 274A (2), 274B (2) & 280F 4-10 SEE PLAN SEE PLAN SEE PLAN SEE PLAN SEE PLAN 4-10D SEE PLAN 4-15 4-10A 4-11
CONTRACTOR CONTRACTOR CONTRACTOR CONTRACTOR CONTRACTOR CONTRACTOR --------CONTRACTOR
MANUFACTURER FACILITIES WAREHOUSE FACILITIES WAREHOUSE FACILITIES WAREHOUSE MANUFACTURER MANUFACTURER --------MANUFACTURER
CONTRACTOR CONTRACTOR CONTRACTOR CONTRACTOR CONTRACTOR CONTRACTOR CONTRACTOR CONTRACTOR CONTRACTOR CONTRACTOR CONTRACTOR
48" x 36" CORKBOARD 60" x 16" CORKBOARD CABLE MANAGEMENT TRAY CPU CLIP AND BRACKET
2 10 31 31
SEE PLAN SEE PLAN SEE PLAN SEE PLAN
--CONTRACTOR CONTRACTOR CONTRACTOR
--MANUFACTURER MANUFACTURER MANUFACTURER
CONTRACTOR CONTRACTOR CONTRACTOR CONTRACTOR
MOUNT AT 3'-6" A.F.F. BOBRICK - SERIES B - 6806 BOBRICK - SERIES B - 6806 BOBRICK - SERIES B - 6806 SEE SHEET A921 FOR MOUNTNG DETAILS MOUNT AT 3'-6" A.F.F. SALVAGED, RE-MOUNT AT EXISTING LOCATION AND HEIGHT SALVAGED, RE-MOUNT AT EXISTING LOCATION AND HEIGHT SALVAGED, MOUNT AT 3'-0" A.F.F. SALVAGED, RE-MOUNT AT EXISTING LOCATION AND HEIGHT REPUBLIC DOUBLE TIER STANDARD LOCKER(12"X12"X36"), COLOR: #83 DECORATOR TAN, KT DIGILOCK SALVAGED, MOUNT AT 3'-0" A.F.F. MOUNT AT 2'-6" A.F.F. SEE REFERENCE STANDARD 5324-01 AND 5324-02 SEE REFERENCE STANDARD 5324-01 AND 5324-02
16. ALL ELEVATION MEASUREMENTS ARE IN REFERENCE TO THE FINISHED FLOOR. 17. SEE LIFE SAFETY PLANS, SHEETS "G103" FOR ALL RATED PARTITION LOCATIONS.
1 DOOR TAG
NEW DOOR, REFER TO DOOR SCHEDULE
6. ALL EXPOSED TO VIEW COUNTERTOP EDGES, BACK OF SPLASHES, ALL EDGES OF TABLES, BACKS OF COUNTERTOPS AND SPLASHES HELD AWAY FROM WALL SHALL BE FILLED, SEALED AND FINISHED.
8. ALL CASEWORK, FUME HOODS AND ANY OTHER FURNISHINGS WITH EXPOSED TO VIEW AND SIDES SHALL BE FINISHED.
101
7
5. COUNTERTOPS AND SPLASHES SHALL BE SEALED TO THE WALLS.
7. FILLER PANELS SHALL BE USED BETWEEN BACK OF CABINETS OR HOODS AND WALLS AT EXPOSED ENDS AND WHEN BASE CABINETS AND/OR HOODS ARE SET BACK TO BACK. FILLER SHALL OCCUR EVEN WHERE NO BASE CABINETS OCCURS BUT BENCH IS PRESENT.
1 C31-PL
NEW PARTITON
4. OVERALL HEIGHT OF BASE CABINETS MUST BE AS SHOWN ON DRAWINGS (NOMINAL HEIGHT).
C:\Revit Projects\Med Sci 4 Central_jschmit.rvt 7/8/2013 11:22:43 AM
Date
PARTIAL FOURTH LEVEL FLOOR PLAN AREA A
FLOOR PLAN GENERAL NOTES
11902
2
E
O N
3' - 8" MIN
5' - 0"
CORRIDOR
2
2
DAVID NORBCK
5
4-12-3
1
21
2
5"
2
14
2
4-25
B57-PL
5"
2' - 10" B
2
L
1
5"
4-12A
C31-PL
M
2' - 6"
L
11' - 2 1/2"
TISSUE CULTURE
16
07.03.13
Registration Number
M1
A903
OFFICE
A901
4-12
8"
1' - 0"
4' - 11 1/2" 1' - 0"
6' - 1"
8
B
20
A901
N O
2
4
TYP.
2' - 6"
4-12A
19
2
A903
Date
Signature
M
E
22
32
N
4
3
11902
I hereby certify that this plan, specification or report was prepared by me or under my direct supervision and that I am a duly licensed Architect under the laws of the State of Minnesota.
E
4-25
E 25
22
5"
2
Registration Number
N O
5
D
9' - 9 1/2"
M
A901
2
DAVID NORBACK
J
E
18
B
2
6 9
A903
B TYP.
LAB
M
2
N O
2
30
1
M1
M1
OFFICE
A901
3
3
4-26
5"
B57-PL
2
14' - 0"
23
2
2
4-27
B
A901
2
I hereby certify that I have reviewed the Mayo Clinic Standard General Specifications prepared by Ronald B. Carlson, License Number 10850, that they are appropriate for the work except as amended in this plan, specification or report, and that I am a duly licensed Architect under the laws of the State of Minnesota.
4-27
16' - 0"
Dr. Nyberg
Certification
Signature
2
C31-PL
9' - 9"
2
SIT-DOWN
O
A901
16
B
2
N
LAB 4-12
4-28
O
22
4-06C
B
E
O
C37-PL
4-11B
4-28
O
5" M
7
4
5"
2
EQUIPMENT
O
10' - 0"
B
2
14
2
ELEC RM 4-004D-2
14
4' - 11 1/2" +/-
B
6
5"
Consultants
2
N O
N
4-06C
L
5' - 0"
4-12-2
4' - 6 1/2"
5' - 8 1/2"
2' - 7"
2
5"
SIT-DOWN
5"
B
B
9' - 7"
4-12-1
L
2
11
4-12D
4' - 5"
ELEC RM 4-004D-1
14
A901
5"
4-12C
1' - 10"
A901
4
9' - 7"
4-12B
12
2
5"
B
9 10
7' - 8 1/2"
RSP Architects 320 South Broadway Ste. B 507.285.6569 Rochester, Minnesota 55904 612.677.7499 fax www.rsparch.com
DN
TISSUE CULTURE
4
15
4-11
C31-PL
A901
4-12B
8
B57-PL
22
M
1' - 3"
1' - 0"
Dr. V. Miller
D E
2
MICROSCOPY
4"
O
GB-36
4-12C
8
A901
6
A901
8
STORAGE 4-49A
5"
16' - 6"
4
8
TISSUE CULTURE
2' - 6"
5"
A901
2
8' - 4"
3
2
1
16
5"
A901
B
2
7
36
34
L
1
2
2
8' - 4"
2
2
2' - 8"
E
B
1
5"
P
L
B
E
8' - 4"
4-11
9
2 4' - 1"
4"
GB-18
B57-PL
14' - 9 1/2"
1' - 6"
9"
C31-PL GB-42
2
C31-PL
5"
C31-PL
8' - 4"
A28-PL
UP
STAIR 4-49B
5"
9
B
13' - 7"
2
2
C31-PL
2
5"
2
B
5' - 7"
E
U
8
9' - 3"
2
1' - 5"
5' - 4 1/2"
O
4"
1' - 0"
7' - 3"
12' - 1"
2
NOTE: SEE SHEET A921 FOR ACCESSORY MOUNTING DIAGRAM
9' - 7"
B
5"
5' - 0"
4' - 0"
4"
E
4"
6' - 1"
2' - 8 1/2" +/-
REMARKS 11 12 13 14 15 16 17 18 19 20 21 22 23 24
25 26 27
FACE OF NEW WALL TO BE ALIGNED WITH FACE OF EXISTING WALL. DASHED LINES INDICATE 12" DEEP ADJUSTABLE PLASTIC LAMINATE SHELVING ABOVE - SEE ELEVATIONS AND DETAILS. WALL HOOK FOR CLIPPERS - SEE DETAIL 15/A920. STAINLESS STEEL SINK - SEE MECHANICAL DRAWINGS EXISTING SCRUB SINK TO REMAIN. STAINLESS STEEL SINK AND TOP - SEE MECHANICAL DRAWINGS MOP SINK - SEE ELEVATIONS - SEE PLUMBING DRAWINGS. DASHED LINES INDICATE WALL CABINETS ABOVE SEE ELEVATIONS AND DETAILS REAGENT SHELVING - SEE ELEVATIONS STAINLESS STEEL SINK AND TOP W/ DRAINBOARDSEE MECHANICAL DRAWINGS STANDARD LAB COAT HOOK STRIP - SEE DETAIL 15/A920 ELECTRIC WATER COOLER - COORDINATE W/ MECHANICAL & ELECTRICAL RELOCATED SCRUB SINK - COORDINATE W/ MECHANICAL WALL MOUNTED FIRE EXTINGUISHER. NITROGEN TANK - BY OWNER. PLASTIC LAMINATE PIPETTE RACK - SEE ELEVATIONS SURFACE APPLY LAYER OF 5/8" GYPSUM BOARD TO EXISTING WALL CONSTRUCTION WALL MOUNTED SINK - SEE MECHANICAL WALL MOUNTED TOILET - SEE MECHANICAL WALL MOUNTED URINAL - SEE MECHANICAL GAS CYLINDER RACK AND HOOK - SEE DETAIL 13/A920 PLASTIC LAMINATE VENT CHASE - SEE DETAIL 9/A920 CEILING MOUNTED AIR HOSE AND REEL - CORDINATE W/MECHANICAL DASHED LINES INDICATE 18" DEEP ADJUSTABLE PLASTIC LAMINATE SHELVING ABOVE - SEE ELEVATIONS AND DETAILS. WALL MOUNTED TV MONITOR - BY A.V. A.V. CABINET - SEE DETAIL 5/A921. APPLY 3/4" FIRE RATED PLYWOOD TO BACK WALL OF CLOSET.
6287.040.04 JAS JHA/MLK
Date
07/03/13
NOTICE: The designs shown and described herein including all technical drawings, graphics, and models thereof, are proprietary and cannot be copied, duplicated or commercially exploited, in whole or in part, without express written permission of RSP Architects. These are available for limited review and evaluation by clients, consultants, contractors, government agencies, vendors and office personnel only in accordance with this Notice. © Copyright RSP Architects 2007. All rights reserved.
Revisions No.
Date
Description
PARTIAL FOURTH LEVEL FLOOR PLAN - AREA A
A104A
2
18
4-11A
4-11
3
L
2
2
4
1' - 6 1/2"
8
A902
2
B
5
B
UP
2
M
4-04A
B
3
M
1' - 1"
M
4-03
TOILET MEN
2' - 1"
TOILET WOMEN
4-02 O
4-03M
3
4
P
E
17
12
B
1' - 5"
1' - 5"
3
P
C31-PL
17
A902
2
4-10-1
19
3
11' - 1 1/2"
C31-PL
B
2
5"
5"
Consultants
Certification
N
4-21
18
5"
1
CLEAN STORAGE
B
2
I hereby certify that I have reviewed the Mayo Clinic Standard General Specifications prepared by Ronald B. Carlson, License Number 10850, that they are appropriate for the work except as amended in this plan, specification or report, and that I am a duly licensed Architect under the laws of the State of Minnesota.
M1
10' - 9" B
2
4-20
E
2
2 Signature
13
4-20
B
2
B
4-04-5
L
B
E
TYP.
B
1' - 6 1/2"
4-10C
3
19
2
A902
SCRUB 4-10-2
21
20
1
2
B
11
2
O
2
C31-PL
4-10F
1
6
J
B
ORTHO PREP 4-10F
2
C31-PL
2
4' - 1"
2
2
2
N
2
23
A902
PREP ROOM
4
3 4
22
8
E
4-10H
5 6
2
7 8
C31-PL
9 10
4-10HA
1
K1
B
2
11
B
2
12
2
13
14
14 15 16 17
K
OPERATING ROOM 4-10A
ORTHO OPERATING ROOM
OPERATING ROOM
OPERATING ROOM
4-10D
4-10B
GERM FREE FACILITY
K1
4-10E
4-10HA
E
18 19 20 21
2
22 23
23
K3
2
07.03.13
I hereby certify that this plan, specification or report was prepared by me or under my direct supervision and that I am a duly licensed Architect under the laws of the State of Minnesota.
M1
KEYNOTES - FLOOR PLAN 2
11902
Date
5
1
17
2 A104B
DAVID NORBACK
Registration Number
2
4
A903
4-10H
STORAGE
11 L
O
A902
16
5
SCRUB 4-10
3
2
2
O
SECRETARY
A902
5"
2' - 10 1/2"
G1
19
1
2
2
1
L
2
E 2
5
17
4-10C
4-06
2 2
4
A903
N
B
15
1 B
CORRIDOR
17 3
2
ELECTRIC 4-004B-1
2
PREP AREA
B
2
N
3
M1
4-22
24
19 P
24
2
3
20
10' - 9 3/4"
17
M
18
3
12
2
RSP Architects 320 South Broadway Ste. B 507.285.6569 Rochester, Minnesota 55904 612.677.7499 fax www.rsparch.com
OFFICE
4-06B
18
1
A902
5
M
A902
OFFICE
4-10G
2' - 10 1/2"
3
1
1' - 7"
O
11' - 7 1/2"
D
25
N
O
B
1
2
B
4-04-5
14
157°
4-04
4-01
C25-PL
N
2
CORRIDOR
4-02
2
10
1' - 2"
6' - 7 1/2"
BREAK ROOM
2
4-22
TYP.
4-10G
1' - 4"
B
O
2
M1
CORRIDOR
4-06A
14 6' - 7 1/2"
4-01
17
3
27 4-04A
4-06B
N
2
13
B
2
2
9
SURGICAL TECHS
1
B
CLOSET
O
B
A902
N
2
4-04
STAIR 4-08
CLOSET 4-04-1
2
C31-PL
8
3
14
2' - 8"
4
DN
4-11B
4-06A
4' - 6"
4-04-2
B
4-06C
B
O
B
E
4-23
2 O
5"
SOILED WORK
CORRIDOR
4-15
O
7' - 2"
D
7
A903
N
2
CONFERENCE
2
8
12
A902
N
K2
4-23
N
O 11
N
M
4-16
OFFICE 4-06C
6
OFFICE
FLEX OFFICE
O
E
B
O
1
5"
STORAGE 4-07
B
N
4-09
3
O N
A,G,V
CLEAN LINEN SUPPLY
L
VESTIBULE/ LOCKER
M1
8' - 4"
CORRIDOR 4-04-3
19
2
1
N
5"
4-05
2
O
8' - 4"
M
4-11
M
5"
MECHANICAL
26
TOILET/ CHANGE
2
4-16
8' - 5"
A902
2
B
14
5"
2
11
3' - 8"
2
B
2' - 0"
2' - 10" L
4-09
2
4-15
4-11A
7 32
1
21
10' - 1"
3
2
B
N O
5"
E
B
2
5"
L
4-04-4
2
13' - 2"
3
5"
4-12A
C31-PL
M
2' - 6"
U
9' - 0"
TISSUE CULTURE
8 A301
CORRIDOR
5"
2 A104A
1
24
21
2' - 4"
25 26 27
FACE OF NEW WALL TO BE ALIGNED WITH FACE OF EXISTING WALL. DASHED LINES INDICATE 12" DEEP ADJUSTABLE PLASTIC LAMINATE SHELVING ABOVE - SEE ELEVATIONS AND DETAILS. WALL HOOK FOR CLIPPERS - SEE DETAIL 15/A920. STAINLESS STEEL SINK - SEE MECHANICAL DRAWINGS EXISTING SCRUB SINK TO REMAIN. STAINLESS STEEL SINK AND TOP - SEE MECHANICAL DRAWINGS MOP SINK - SEE ELEVATIONS - SEE PLUMBING DRAWINGS. DASHED LINES INDICATE WALL CABINETS ABOVE SEE ELEVATIONS AND DETAILS REAGENT SHELVING - SEE ELEVATIONS STAINLESS STEEL SINK AND TOP W/ DRAINBOARDSEE MECHANICAL DRAWINGS STANDARD LAB COAT HOOK STRIP - SEE DETAIL 15/A920 ELECTRIC WATER COOLER - COORDINATE W/ MECHANICAL & ELECTRICAL RELOCATED SCRUB SINK - COORDINATE W/ MECHANICAL WALL MOUNTED FIRE EXTINGUISHER. NITROGEN TANK - BY OWNER. PLASTIC LAMINATE PIPETTE RACK - SEE ELEVATIONS SURFACE APPLY LAYER OF 5/8" GYPSUM BOARD TO EXISTING WALL CONSTRUCTION WALL MOUNTED SINK - SEE MECHANICAL WALL MOUNTED TOILET - SEE MECHANICAL WALL MOUNTED URINAL - SEE MECHANICAL GAS CYLINDER RACK AND HOOK - SEE DETAIL 13/A920 PLASTIC LAMINATE VENT CHASE - SEE DETAIL 9/A920 CEILING MOUNTED AIR HOSE AND REEL - CORDINATE W/MECHANICAL DASHED LINES INDICATE 18" DEEP ADJUSTABLE PLASTIC LAMINATE SHELVING ABOVE - SEE ELEVATIONS AND DETAILS. WALL MOUNTED TV MONITOR - BY A.V. A.V. CABINET - SEE DETAIL 5/A921. APPLY 3/4" FIRE RATED PLYWOOD TO BACK WALL OF CLOSET.
Signature
DAVID NORBCK
Registration Number
11902
Date
07.03.13
Project For
Large Animal Surgery and Germ Free Facility Medical Sciences Building Fourth Floor Project #7R120760 A
B
1 5"
PARTIAL FOURTH LEVEL FLOOR PLAN AREA B 1/4" = 1'-0"
Project No.
19' - 5 1/2" O
4-02
5"
KEY PLAN
NORTH M
3
O
1' - 1"
3
FLOOR PLAN LEGEND: ROOM NAME
EXISTING PARTITION TO REMAIN
4-03
101
1' - 8"
1' - 8" 4-02
EXISTING DOOR AND FRAME TO REMAIN
2' - 6"
D
TOILET WOMEN
6' - 10 1/2"
2' - 6"
D
1' - 6"
G
Checked By
24
A902
26
1' - 4"
4"
3 H
29
5' - 0" 28
2' - 11"
27
C.1
C.2
5' - 1"
GB-36
5' - 0"
P
8' - 3"
2
H
2
H
5' - 1"
GB-36
GB-42
P
2
B C.1
3
ENLARGED RESTROOM PLAN 1/2" = 1'-0"
C:\Revit Projects\Med Sci 4 Central_jschmit.rvt 7/8/2013 11:22:46 AM
Please purchase PDF Split-Merge on www.verypdf.com to remove this watermark.
1' - 6"
9 1/8" 4"
2
E
2
GB-18
1' - 6"
B
P
30
A902 31
B
P
1i
KEYNOTE
1
NEW PARTITION AS SCHEDULED, SEE MAYO SPECIFICATIONS SECTION 09200 FOR PARTITION CONSTRUCTION
1i
EQUIPMENT TAG
A
SPECIALITY EQUIPMENT TAG
FLOOR PLAN GENERAL NOTES 1. WALL SHELVING OR REAGENT SHELVING SUPPORTS SHALL BE SPACED AND POSITIONED TO CLEAR FITTINGS, ELECTRICAL PEDESTALS, AND SINKS.
3
TAG B C.1 C.2 D E G
G1 GB-18 GB-36 GB-42 H J K K1 K2 K3 L M M1 N O
GB-18 GB-42
DESCRIPTION
SPECIALTY EQUIPMENT SCHEDULE ORDERED BY SUPPLIED BY INSTALLED BY
07/03/13
NOTICE: The designs shown and described herein including all technical drawings, graphics, and models thereof, are proprietary and cannot be copied, duplicated or commercially exploited, in whole or in part, without express written permission of RSP Architects. These are available for limited review and evaluation by clients, consultants, contractors, government agencies, vendors and office personnel only in accordance with this Notice.
COUNTERTOP TAG
NEW DOOR, REFER TO DOOR SCHEDULE
M
8' - 11" +/-
E
2' - 9"
13' - 7 3/8" +/-
25
4"
3' - 0 7/8"
7' - 8"
JHA/MLK
ROOM TAG
G
P 3
1 C31-PL
NEW PARTITON
4-03
O
JAS
Date
TOILET MEN
5"
Drawn By
DOOR TAG
E
4-02
6287.040.04
© Copyright RSP Architects 2007. All rights reserved.
Revisions No.
Date
Description
2. OVERALL LENGTH OF TOPS SHALL BE DETERMINED BY CASEWORK AND DIMENSIONS AS INDICATED ON PLANS. TOPS SHALL OVERHANG ½” AT EACH END AND 1” FROM FRONT OF BASE CABINET. WHEN OVERALL DIMENSIONS ARE GIVEN, ½” OVERHANG IS NOT INCLUDED.
QTY
TO ROOM
REMARKS
TOILET PAPER DISPENSER SANITARY PRODUCT DISPOSAL SANITARY PRODUCT DISPENSER SOAP DISPENSER PAPER TOWEL DISPENSER 24" X 60" MIRROR
4 2 1 8 8 3
CONTRACTOR CONTRACTOR CONTRACTOR CONTRACTOR CONTRACTOR CONTRACTOR
FACILITIES WAREHOUSE FACILITIES WAREHOUSE FACILITIES WAREHOUSE FACILITIES WAREHOUSE FACILITIES WAREHOUSE MANUFACTURER
CONTRACTOR CONTRACTOR CONTRACTOR CONTRACTOR CONTRACTOR CONTRACTOR
GEORGIA PACIFIC - MODEL #56784 ASI - MODEL #0852 ROCHESTER MIDLAND - MODEL #C2591100J655 DERMAPRO - MODEL #9021-ALMOND GEORGIA PACIFIC - MODEL #59462 TSM - MODEL #M-1
12" x 24" MIRROR GRAB BARS GRAB BARS GRAB BARS COAT HOOK 30" X 36" DRYING RACK 36" x 48" WHITEBOARD 48" x 36" WHITEBOARD 48" x 48" WHITEBOARD 72" x 48" WHITEBOARD METAL LOCKERS
1 3 3 3 3 4 1 2 1 1 16
SEE PLAN 4-03, 4-11A 4-03 4-02, 4-03, 4-11A 4-02, 4-03, 4-11A 236, 238, 274A (2), 274B (2) & 280F 4-10 SEE PLAN SEE PLAN SEE PLAN SEE PLAN SEE PLAN 4-10D SEE PLAN 4-15 4-10A 4-11
CONTRACTOR CONTRACTOR CONTRACTOR CONTRACTOR CONTRACTOR CONTRACTOR --------CONTRACTOR
MANUFACTURER FACILITIES WAREHOUSE FACILITIES WAREHOUSE FACILITIES WAREHOUSE MANUFACTURER MANUFACTURER --------MANUFACTURER
CONTRACTOR CONTRACTOR CONTRACTOR CONTRACTOR CONTRACTOR CONTRACTOR CONTRACTOR CONTRACTOR CONTRACTOR CONTRACTOR CONTRACTOR
48" x 36" CORKBOARD 60" x 16" CORKBOARD CABLE MANAGEMENT TRAY CPU CLIP AND BRACKET
2 10 31 31
SEE PLAN SEE PLAN SEE PLAN SEE PLAN
--CONTRACTOR CONTRACTOR CONTRACTOR
--MANUFACTURER MANUFACTURER MANUFACTURER
CONTRACTOR CONTRACTOR CONTRACTOR CONTRACTOR
MOUNT AT 3'-6" A.F.F. BOBRICK - SERIES B - 6806 BOBRICK - SERIES B - 6806 BOBRICK - SERIES B - 6806 SEE SHEET A921 FOR MOUNTNG DETAILS MOUNT AT 3'-6" A.F.F. SALVAGED, RE-MOUNT AT EXISTING LOCATION AND HEIGHT SALVAGED, RE-MOUNT AT EXISTING LOCATION AND HEIGHT SALVAGED, MOUNT AT 3'-0" A.F.F. SALVAGED, RE-MOUNT AT EXISTING LOCATION AND HEIGHT REPUBLIC DOUBLE TIER STANDARD LOCKER(12"X12"X36"), COLOR: #83 DECORATOR TAN, KT DIGILOCK SALVAGED, MOUNT AT 3'-0" A.F.F. MOUNT AT 2'-6" A.F.F. SEE REFERENCE STANDARD 5324-01 AND 5324-02 SEE REFERENCE STANDARD 5324-01 AND 5324-02
3. OVERALL HEIGHT OF BASE CABINETS MUST BE AS SHOWN ON DRAWINGS (NOMINAL HEIGHT). 4. COUNTERTOPS AND SPLASHES SHALL BE SEALED TO THE WALLS. 5. ALL EXPOSED TO VIEW COUNTERTOP EDGES, BACK OF SPLASHES, ALL EDGES OF TABLES, BACKS OF COUNTERTOPS AND SPLASHES HELD AWAY FROM WALL SHALL BE FILLED, SEALED AND FINISHED. 6. FILLER PANELS SHALL BE USED BETWEEN BACK OF CABINETS AND WALLS AT EXPOSED ENDS AND WHEN BASE CABINETS ARE SET BACK TO BACK. FILLER SHALL OCCUR EVEN WHERE NO BASE CABINETS OCCURS BUT BENCH IS PRESENT. 7. ALL CASEWORK AND ANY OTHER FURNISHINGS WITH EXPOSED TO VIEW AND SIDES SHALL BE FINISHED. 8. ALL PLAN DIMENSIONS LOCATING INTERIOR WALLS ARE TO: a: FACE OF EXISTING WALL SYSTEM UNLESS NOTED OTHERWISE. b: FACE OF GYPSUM BOARD UNLESS NOTED OTHERWISE. c: CENTERLINE OF BUILDING GRID. 9. ALL ELEVATION MEASUREMENTS ARE IN REFERENCE TO THE FINISHED FLOOR. 10. SEE LIFE SAFETY PLANS, SHEETS FOR ALL RATED PARTITION LOCATIONS. 11. EXISTING PENETRATIONS IN RATED PARTITIONS TO BE FIRESTOPPED & SEALED. NEW MECHANICAL / ELECTRICAL PENETRATIONS TO BE FIRESTOPPED & SEALED. ALL SUBCONTRACTORS TO USE THE SAME FIRESTOPPING SYSTEM. 12. REFER TO SHEET A301 FOR DOOR SCHEDULE AND PARTITION TYPE KEY. 13. REFER TO SHEET A801 FOR EQUIPMENT SCHEDULES. 14. REFER TO SHEET A204 FOR RCP. NOTE: SEE SHEET A921 FOR ACCESSORY MOUNTING DIAGRAM
PARTIAL FOURTH LEVEL FLOOR PLAN - AREA B
A104B
TISSUE CULTURE
MICROSCOPY 4-12B
2
TISSUE CULTURE
4-12C
REFLECTED CEILING PLAN GENERAL NOTES:
4-12D
1. GENERAL CONTRACTOR TO COORDINATE ALL WORK OF ALL TRADES INVOLVED IN THE CEILING WORK TO INSURE CLEARANCES FOR FIXTURES, DUCTS, PIPING, CEILING SUSPENSION SYSTEMS, ETC. NECESSARY TO MAINTAIN THE FINISHED CEILING HEIGHTS INDICATED ON ARCHITECTS DRAWINGS.
S
STAIR
3
2
SD
2. VERIFY FIELD CONDITIONS AND LOCATIONS OF ALL PLUMBING, MECHANICAL DUCTS, STRUCTURAL ELEMENTS AND ANY OTHER APPLICABLE ITEMS. INSTALL NEW PLUMBING, MECHANICAL FANS, DUCTS, CONDUITS, AND OTHER RELATED ITEMS SO AS NOT TO CONFLICT WITH LUMINARIES.
4-49B
3. VERIFY ALL RECESS DEPTHS OF FIXTURES AGAINST A.C. DUCTS, PIPES, BEAMS, ETC. BEFORE ORDERING FIXTURES. SUBMIT SHOP DRAWINGS OF ALL FIXTURES TO ARCHITECT AND ENGINEER FOR APPROVAL.
2
SD
S
S
4. REMOVE ALL OBSTRUCTIONS FROM CEILING, INCLUDING ABANDONED CONDUITS, WIRES, DUCK WORK, ETC. NOT SCHEDULED FOR REUSE.
SD
2 1
2
LAB S
SD
2
S
SD
EQUIPMENT 4-28
S
SD
4-12
9
OS
5. ALL SPECIFIC INFORMATION CONCERNING INSTALLATION OF VARIOUS ABOVE-CEILING ELEMENTS ARE TO BE FOUND IN HVAC, PLUMBING, FIRE PROTECTION, ELECTRICAL AND LIGHTING DRAWINGS. REFER TO ENGINEERING DRAWINGS FOR FULL WORK SCOPE ON DIFFUSERS, RETURNS, SPRINKLERS, LIGHT SWITCHES, THERMOSTATS, FIRE ALARMS, STROBES, ETC. 6. REFER TO ENGINEERING DRAWINGS FOR ALL LIFE SAFETY DEVICES REQUIRED BY CODE AND ALL EMERGENCY LIGHT FIXTURES. ARCHITECTURAL DRAWINGS SHALL GOVERN LOCATION OF THESE DEVICES.
SD
7. NOTIFY ARCHITECT OF ANY CONFLICTS OF LIGHT FIXTURE LOCATIONS WITH MAIN CEILING GRID RUNNERS, DUCTS, STRUCTURES, HVAC AND/OR ELECTRICAL CONDUIT, PRIOR TO FRAMING FOR LIGHTS. ANY DISCREPANCIES BETWEEN ARCHITECT'S CEILING GRID LOCATION AND ACTUAL FIELD CONDITIONS ARE TO BE CLARIFIED WITH THE ARCHITECT PRIOR TO FRAMING.
S
WAP
8
1
8. INSTALL LIGHT FIXTURES WITH PROTECTIVE FILM OR SIMILAR COVER OVER LOUVER, LENS, BAFFLE, AND THE LIKE, TO AVOID FIXTURE SOILING OR DAMAGE. FIXTURES SHALL BE KEPT CLEAN AND AS NEW. LAMPS SHALL BE NEW AT PROJECT COMPLETION.
OFFICE 4-27
2 OS
1
1
LAB
10. LIGHT FIXTURES, EXIT SIGNS, SPRINKLERS AND OTHER CEILING ELEMENTS SHALL BE LOCATED IN CENTER OF INDIVIDUAL CEILING TILE, U.N.O.
OFFICE
11. ALL SOFFITS AND CEILING HEIGHTS ARE DIMENSIONED FROM TOP OF FINISHED FLOOR TO BOTTOM OF GYB. BD. OR CEILING TILE AND SHALL ALLOW FOR THICKNESS OF ALL FLOOR FINISHES.
OS
2
SD
1
S
12. FIRE SAFETY MUST BE MAINTAIN FOR ALL PERSONNEL WORKING ON THE FLOOR. ALL FIRE STARS, ALARMS, SPEAKERS, ETC. MUST REMAIN ACCESSIBLE AND OPERABLE AT ALL TIMES. NOTIFY BUILDING FACILITIES MANAGER OF DAMAGED SYSTEMS AND REPAIR OR REPLACE DAMAGED SYSTEMS IMMEDIATELY.
OFFICE 4-25
CORRIDOR
4-09
MECHANICAL
2
VESTIBULE/ LOCKER
8
4
4-05A
4-05
1
4-11
3
2
OS
4-04-2
4-07
CONFERENCE
2
1
2
4-06B
4-08
4-04-1
S
4-04
1
OS
S
SD
4
S
4-01 1
TOILET WOMEN
OS TOILET MEN
4-03
4-10-1
4-10C
6' - 7"
6 5
7' - 4" 7
6
6' - 0"
7
OPERATING ROOM 4-10A
FOURTH LEVEL - REFLECTED CEILING PLAN
2
6' - 0"
5
2' - 11"
4-10B
12' - 3"
5
CENTER OF JOIST
CENTER OF JOIST
11902
Date
07.03.13
Project For
NEW SUSPENDED ACOUSTICAL CEILING SYSTEM (ACT-1) AT 8'-0" AFF. NEW SUSPENDED ACOUSTICAL CEILING SYSTEM (ACT-2) AT 8'-0" AFF. NO WORK IN THIS AREA. EXISTING GYPSUM CEILING TO REMAIN - PAINT PER ROOM FINISH SCHEDULE. EXISTING SUPPLY DIFFUSER TO REMAIN (PAINT) - SEE MECHANICAL DRAWINGS. REBURBISHED EXAM ROOM LIGHTS FROM WAREHOUSE - SEE DETAIL 3/A204 FOR STRUCTURAL SUPPORTS - SEE ELECTRICAL DRAWINGS FOR POWER REQUIREMENTS. DASHED LINE INDICATES LOCATION OF OPERATING TABLE BELOW. BULKHEAD AT 7'-11" A.F.F. - SEE DETAIL 2/A204 OVERHEAD SERVICES CARRIER - SEE DETAIL 5/A204.
4
GERM FREE FACILITY 4-10HA
4
LAY-IN ACOUSTICAL TILE CEILING SYSTEM - SEE REFLECTED CEILING PLANS
ORTHO OPERATING ROOM
OPERATING ROOM 4-10D
Large Animal Surgery and Germ Free Facility Medical Sciences Building Fourth Floor Project #7R120760
CEILING HEIGHT ELEV. 8'-0" A.F.F. BOTTOM OF BULKHEAD ELEV. 7'-11" A.F.F.
A
B
4-10E
1/8" = 1'-0" LESSER DIM TO
LINEAR DIFFUSER - SEE MECHANICAL
3 5/8" STEEL STUD FRAMING AT 16" OC
S
2 GREATER DIMENSION TO
OCCUPANCY SENSOR
Registration Number
5/8" GYP. BD.
6
OPERATING ROOM
RETURN AIR GRILLE - SEE MECHANICAL
2 SD
5' - 10"
4
FIRE ALARM
DAVID NORBCK
4-10H
S
7
5' - 10"
5' - 10"
5' - 10"
6
7 8 9
PREP ROOM
5
6
7
DIFFUSER - SEE MECHANICAL
2
4
5
1 2
4-10F
4-02 1
1
4-20
OS
4-10
OS
4-10-2
STORAGE
SCRUB
1 2 3 4 5 6
OFFICE
ORTHO PREP
SCRUB
Signature
EXIT SIGN
KEYNOTES - REFLECTED CEILING PLAN
S
SD
I hereby certify that this plan, specification or report was prepared by me or under my direct supervision and that I am a duly licensed Architect under the laws of the State of Minnesota.
EMERGENCY LIGHT FIXTURE - SEE ELECTRICAL SMOKE DETECTOR
1
OS
CORRIDOR
S
4-06
1
BREAK ROOM
SD
2
PREP AREA
SD
4-21
2
CORRIDOR
LIGHT FIXTURE - SEE ELECTRICAL
07.03.13
EXISTING SUSP. CEILING TILE AND GRID SYSTEM TO REMAIN
SECRETARY
4-10G
SD
11902
SPEAKER
NEW SUSP. CEILING TILE AND GRID SYSTEM
4-22
CLEAN STORAGE
CLOSET
OFFICE
S
SD
STAIR
WAP
OS
S
2
3
S
1
F
OS
1
SD
4-23
SD
4-06C
SURGICAL TECHS
S
OFFICE
OFFICE
2
SPRINKLER HEAD
1
4-16
4-15
S
S
SD
REFLECTED CEILING PLAN LEGEND
FLEX OFFICE
DAVID NORBACK
Date
SD S
Signature Registration Number
OS
OS
4-11A
4-06A
CORRIDOR
S
1
TOILET/ CHANGE
OS
SOILED WORK
STORAGE
SD
I hereby certify that I have reviewed the Mayo Clinic Standard General Specifications prepared by Ronald B. Carlson, License Number 10850, that they are appropriate for the work except as amended in this plan, specification or report, and that I am a duly licensed Architect under the laws of the State of Minnesota.
OFFICE 4-24
8
Certification
4"
2
1
4-04-4
WAP
S
SD
1
1"
4-12A CLEAN LINEN SUPPLY
S
SD
13. REMOVAL OF ANY EQUIPMENT, CABLING SWITCHES, AND CONDUIT PERTAINING TO DATA/COMMUNICATIONS AND TELEPHONE SHALL BE VERIFIED WITH TELEPHONE COMPANIES, SERVICE OWNER OR TENANT DATA/COMMUNICATIONS REPRESENTATIVE AS REQUIRED TO PREVENT NEW CONSTRUCTION DELAYS.
OS
4-04-5
TISSUE CULTURE
CUSTODIAL
S
CORRIDOR
2
Consultants
9. SWITCHES, THERMOSTATS, STROBES AND OTHER ELECTRICAL DEVICES ARE TO ALIGN ALONG THEIR CENTERLINE, WHEN DEVICES OCCUR IN THE PROXIMITY OF WALL OUTLETS. ALIGN OUTLETS WITH DEVICES ABOVE.
4-26
4-12-3
SD
RSP Architects 320 South Broadway Ste. B 507.285.6569 Rochester, Minnesota 55904 612.677.7499 fax www.rsparch.com
TYPICAL BULKHEAD DETAIL
NORTH
L3X3X1/4 WITH (2) 1/2" DIA HILTI KWIK BOLT 3 WITH 3 1/2" MIN EMBED
Project No.
5"
MIN.
KEY PLAN
1 1/2" = 1'-0"
6287.040.04
Drawn By L3X3X1/4 WITH (2) 3/8" DIA HILTI KWIK BOLT 3 WITH 1 5/8" MIN EMBED
Checked By
FIFITH FLOOR ELEV. 13'-9" A.F.F.
3 3/4"
FIFITH FLOOR ELEV. 13'-9" A.F.F.
1/4" THREADED ROD ANCHOR BOLT, TYP.
EXISTING CONCRETE FLOOR JOIST
CEILING BAFFLE, TYP
TS 4"X4"X1/4" STEEL TUBE WELDED TO BOTTOM OF EXISTING FLOOR JOIST AT EACH VERTICAL PLATE SUPPORT - CONNECT TO 3 JOISTS MINIMUM
3 3/4"
JAS
1/4" THREADED ROD, TYP.
EXISTING CEILING
JHA/MLK
Date
07/03/13
NOTICE: The designs shown and described herein including all technical drawings, graphics, and models thereof, are proprietary and cannot be copied, duplicated or commercially exploited, in whole or in part, without express written permission of RSP Architects. These are available for limited review and evaluation by clients, consultants, contractors, government agencies, vendors and office personnel only in accordance with this Notice. © Copyright RSP Architects 2007. All rights reserved.
0"
Revisions Date
Description
0"
No. QUICK CONNECT, TYP TS 4"X4"X1/4" STEEL TUBE WELDED TUBE TO CONNECT 3 JOIST MINIMUM
1/4"
4'-2 1/2" - FIELD VERIFY
NOTE: CONTRACTOR TO VERIFY WEIGHT OF EXAM LIGHT DOES NOT EXCEED 1800 LBS.
4"X3"X3/8" STEEL ANGLE VERTICAL PLATE SUPPORT - WELD TO HORIZONTAL TUBE STEEL AND PLATE ANGLES 4"X3"X3/8" STEEL PLATE ANGLE - WELD TO STEEL MOUNTING PLATE
3
3X3X1/4 STEEL ANGLE - SEE DETAIL 3/A204
1' - 11"
4"X3"X3/8" STEEL ANGLE VERTICAL PLATE SUPPORT - WELD TO HORIZONTAL TUBE STEEL AND PLATE ANGLES
4'-2 1/2" - FIELD VERIFY
3X3X1/4 STEEL ANGLE KICKER AT EACH VERTICAL PLATE SUPPORT (4 REQUIRED - 2 EACH DIRECTION). SEE DETAIL 4/A201 FOR ATTACHMENT TO DECK.
B22 UNI-STRUT
TYP UNO.
5
WIREMOLD 4000
DETAIL AT SERVICE CARRIER 1 1/2" = 1'-0"
4"X3"X3/8" STEEL PLATE ANGLE - WELD TO STEEL MOUNTING PLATE
3/4" THREADED BOLTS EXISTING GYPSUM BOARD SUPPORT SYSTEM
3/4" THREADED BOLTS 3/4" X16"X16" STEEL MOUNTING PLATE
3/4" X16"X16" STEEL MOUNTING PLATE
EXAM LIGHT MOUNTING BRACKET
EXAM LIGHT MOUNTING BRACKET
6"
6"
EXISTING 5/8" GYPSUM BOARD
EXISTING SUSPENDED GYPSUM CEILING ELEV. 8'-0" A.F.F.
EXISTING SUSPENDED GYPSUM CEILING' ELEV. 8'-0" A.F.F. SUSPENDED ACOUSTICAL CEILING SYSTEM
8"
8"
EXAM LIGHT CEILING HOOD
EXAM LIGHT CEILING HOOD EXAM LIGHT SUSPENSION TUBE
8"
1' - 4"
1' - 4"
4 A204
3
EXAM LIGHT SUPPORT DETAIL 1 1/2" = 1'-0"
C:\Revit Projects\Med Sci 4 Central_jschmit.rvt 7/8/2013 11:22:47 AM
Please purchase PDF Split-Merge on www.verypdf.com to remove this watermark.
8"
4
EXAM LIGHT SECTION 1 1/2" = 1'-0"
EXAM LIGHT SUSPENSION TUBE
FOURTH LEVEL REFLECTED CEILING PLAN
A204
SEE PARTITION TYPE
DOOR SCHEDULE
HEAD
JAMB
3' - 0" 3' - 0" 3' - 0" 3' - 0" 3' - 0" 3' - 6" 5' - 0" 3' - 6" 3' - 0" 3' - 8" 3' - 0" 3' - 0" 3' - 0" 3' - 6" 3' - 6" 3' - 0" 3' - 0" 3' - 0" 4' - 0" 3' - 0" 3' - 0" 3' - 0" 3' - 6" 3' - 6" 3' - 6" 3' - 0" 3' - 0" 3' - 0" 3' - 0" 3' - 0" 3' - 0" 3' - 0" 3' - 0" 3' - 0" 3' - 6"
7' - 0" 7' - 0" 7' - 0" 7' - 0" 7' - 0" 7' - 0" 7' - 0" 7' - 0" 7' - 0" 7' - 0" 7' - 0" 7' - 0" 7' - 0" 7' - 0" 7' - 0" 7' - 0" 7' - 0" 7' - 0" 7' - 0" 7' - 0" 7' - 0" 7' - 0" 7' - 0" 7' - 0" 7' - 0" 7' - 0" 7' - 0" 7' - 0" 7' - 0" 7' - 0" 7' - 0" 7' - 0" 7' - 0" 7' - 0" 7' - 0"
B A A B A A A,A C A A A A A A A A A A A,B C C C A C C A A A A A A A A A C
NO NO NO NO NO YES YES NO NO NO NO NO NO NO NO NO NO NO YES NO NO NO NO NO NO NO NO NO NO NO NO NO NO NO NO
F1 F1 F1 F1 F1 F1 F1 F1 F1 F1 F1 F1 F1 F1 F1 F1 F1 F1 F1 F1 F1 F1 F1 F1 F1 F1 F1 F1 F1 F1 F1
1/A301 1/A301 1/A301 1/A301 1/A301 1/A301 1/A301 1/A301 1/A301 1/A301 1/A301 1/A301 1/A301 1/A301 1/A301 1/A301 1/A301 1/A301 1/A301 1/A301 1/A301 3/A301 3/A301 3/A301 3/A301 1/A301 1/A301 1/A301 1/A301 1/A301 1/A301 1/A301 1/A301 1/A301 1/A301
2/A301 2/A301 2/A301 2/A301 2/A301 2/A301 2/A301 2/A301 2/A301 2/A301 2/A301 2/A301 2/A301 2/A301 2/A301 2/A301 2/A301 2/A301 2/A301 2/A301 2/A301 4,5/A301 4,5/A301 4,5/A301 4,5/A301 2/A301 2/A301 2/A301 2/A301 2/A301 2/A301 2/A301 2/A301 2/A301 2/A301
EL7 PP1 PP1 EL2 EL2 ST1 CL4 PA2 PA1 PA1 PA1 PA2 PA2 EL2 PA2 EL2 PR2 PA2 PA4 PA2 PA2 SL1 SL1 SL1 SL1 PA1 PA1 PA1 PA1 PA1 PA1 PA1 PA1 PA1 ST1
COMMENTS
KP KP KP, OS KP KP, CR KP, OS, DS, SG KP, CR KP KP KP, OS KP KP, OS NOTE 1 NOTE 1 NOTE 1 NOTE 1 KP KP
2.
DELETE LEVER FOR LOCKSET ON CORRIDOR SIDE OF DOOR
DOOR TYPES:
FRAME TYPE:
SEE DOOR SCHEDULE 3' - 0"
SEE DOOR SCHEDULE 3' - 0"
1/2"
1/2"
9"
1
9"
2"
SEE DOOR SCHED.
JAMB ANCHORS 3 PER JAMB
HOLLOW METAL FRAME
WOOD DR. - SEE DOOR SCHEDULE
DOUBLE STUDS AT JAMBS (TYPICAL)
TYPICAL DOOR HEAD DETAIL
TYPICAL DOOR JAMB DETAIL
HOLLOW METAL FRAME
2
3" = 1'-0"
3
TYPICAL SLIDING DOOR HEAD DETAIL 3" = 1'-0"
4' - 0"
8'-0"
2' - 0"
GL2
FLUSH PANEL SOLID CORE WOOD DOOR BIRCH, PLAIN SLICED BOOK MATCHED, SELECT WHITE
C
FLUSH PANEL HOLLOW CORE WOOD DOOR BIRCH, PLAIN SLICED BOOK MATCHED, SELECT WHITE
KP, OS
WALL
3 5/8" METAL STUDS - SEE PARTITION TYPES. DOUBLE STUDS AT JAMB (TYPICAL) FLOOR GUIDE
WOOD DOOR
SLIDING DOOR SEE SCHEDULE
GL1
1/4" CLEAR WIRE GLASS
FINISHED WOOD FRAME
GL2
1/4" CLEAR TEMPERED GLASS
DOUBLE STUDS AT JAMB TYPICAL
SLIDING DOOR SEE SCHEDULE
1/4"X3/4" GROOVE IN BOTTOM OF DOOR NYLON GUIDE
2.
PROVIDE CONTROL JOINTS AT JUNCTURE OF ALL FLOOR SUPPORTED WALLS WITH BULKHEAD & SOFFITS SUPPORTED FROM DECK ABOVE.
3.
PROVIDE U.L. APPROVED JOINT ASSEMBLY AT PERIMETER OF ALL FIRE RATED PARTITIONS.
Date
11902 07.03.13
Signature
DAVID NORBCK
Registration Number Date
TYPICAL SLIDING DOOR JAMB DETAIL FINISHED END
6
11902 07.03.13
3" = 1'-0"
DOOR GUIDE DETAIL 6" = 1'-0"
Large Animal Surgery and Germ Free Facility
3 A301 VARIES
Medical Sciences Building Fourth Floor
CASE DOOR OPENING WITH 3/4" X 5" +/WOOD TRIM
HOLLOW CORE WOOD DOOR, 6" WIDER THAN FINISHED OPENING
7' - 6"
PROVIDE DEFLECTION TRACK TO ALLOW FOR 1" DEFLECTION IN STRUCTURAL SYSTEM AT TOP OF ALL INTERIOR PARTITIONS EXTENDING FROM TOP OF SLAB TO UNDERSIDE OF STRUCTURE.
5
3" = 1'-0"
GENERAL NOTES 1.
Registration Number
Project For
TYPICAL SLIDING DOOR JAMB DETAIL DOOR END
HOLLOW METAL
DAVID NORBACK
I hereby certify that this plan, specification or report was prepared by me or under my direct supervision and that I am a duly licensed Architect under the laws of the State of Minnesota.
SHIM AS REQUIRED
FINISHED WOOD FRAME
4
F1
I hereby certify that I have reviewed the Mayo Clinic Standard General Specifications prepared by Ronald B. Carlson, License Number 10850, that they are appropriate for the work except as amended in this plan, specification or report, and that I am a duly licensed Architect under the laws of the State of Minnesota.
Signature
GLASS TYPES:
2"
HOLLOW CORE OAK DOOR - SEE DOOR SCHEDULE
Consultants
3" = 1'-0"
3 5/8" METAL STUDS - SEE PARTITION TYPES.
SEE DOOR SCHEDULE
SEE DOOR SCHEDULE
2' - 0" B
1/2"
HEADER BY STEEL STUD SUPPLIER
RSP Architects 320 South Broadway Ste. B 507.285.6569 Rochester, Minnesota 55904 612.677.7499 fax www.rsparch.com
CASE DOOR OPENING WITH 3/4" X 5" +/- OAK
5/8" GYPSUM BOARD
1' - 4"
GL1
8'-0"
8'-0"
FLUSH PANEL SOLID CORE WOOD DOOR BIRCH, PLAIN SLICED BOOK MATCHED, SELECT WHITE
1/2"
5/8" GYPSUM BOARD
SEE DOOR SCHEDULE
SEE DOOR SCHEDULE A
SLIDING DOOR HARDWARE SEE DOOR SCHEDULE
3/8" DIA. LAG BOLTS AT MAX. 2'-0" O.C.
SHIM AS REQUIRED
3' - 0"
4"
REMOVABLE WOOD VALANCE 3 5/8" METAL STUDS - SEE PARTITION TYPES.
Certification
2"
6"
SEE DOOR SCHED.
3 5/8" METAL STUDS -SEE PARTITION TYPES.
SEE PLANS FOR PARTITION TYPE
SEE DOOR SCHEDULE
FINISHED DOOR OPENING IS INDICATED IN DOOR SCHEDULE. DOORS SHALL BE 6" WIDER THAN OPENING
5/8" GYPSUM BOARD FIRE TREATED SOLID WOOD BLOCK
3 5/8" STEEL STUD FRAMING
DOOR SCHEDULE NOTES 1.
5/8" GYP. BD.
5/8" TYPE 'X' GYP. BD.
KP KP KP KP, CR KP, CR KP KP, OS, NOTE 2 KP, OS
SEE DOOR SCHEDULE
BREAK ROOM TOILET MEN TOILET WOMEN CORRIDOR CORRIDOR CORRIDOR PREP AREA PREP AREA OFFICE CLEAN LINEN SUPPLY STORAGE ORTHO PREP CLEAN STORAGE PREP ROOM GERM FREE FACILITY VESTIBULE/ LOCKER TOILET/ CHANGE VESTIBULE/ LOCKER LAB SIT-DOWN LAB TISSUE CULTURE MICROSCOPY TISSUE CULTURE TISSUE CULTURE CONFERENCE FLEX OFFICE OFFICE OFFICE OFFICE OFFICE OFFICE OFFICE OFFICE EQUIPMENT
FIRE LABEL HDWR.
5"
FRAME TYPE
6'-11" A.F.F.
PAIR
6'-11 1/4" A.F.F.
DOOR TYPE
2"
H
TYPE
5/8"
4-01 4-02 4-03 4-04-2 4-04-5 4-04 4-06 4-06 4-06C 4-09 4-10C 4-10F 4-10G 4-10H 4-10HA 4-11 4-11A 4-11 4-12 4-12-2 4-12-3 4-12A 4-12B 4-12C 4-12D 4-15 4-16 4-20 4-22 4-23 4-24 4-25 4-26 4-27 4-28
W
ROOM NAME
SEE PARTITION
SPECS.
2"
SIZE
DOOR ROOM NO. NO. 4-01 4-02 4-03 4-04 4-04-5 4-04A 4-06A 4-06B 4-06C 4-09 4-10C 4-10F 4-10G 4-10H 4-10HA 4-11 4-11A 4-11B 4-12 4-12-2 4-12-3 4-12A 4-12B 4-12C 4-12D 4-15 4-16 4-20 4-22 4-23 4-24 4-25 4-26 4-27 4-28
FRAME
5/8"
DOOR
3 3/4"
2' - 0"
Project #7R120760
3 3/4"
5/8" GYPSUM BOARD
FINISHED OPENING SEE FLOOR PLAN FOR PARTITION TYPES AND REQUIRED RATINGS
DEFINES TOP OF LOW PARTITION: REFER TO NOTES THIS SHEET, OR SEE CONSTRUCTION DOCUMENTS FOR SPECIAL CONDITIONS
INDICATES NEW PATITION CONSTRUCTION (REFER TO PARTITION TYPE INDICATOR)
1i
1 1i
1
6 A301
PARTITION TYPE INDICATOR: REFER TO REFERENCE STANDARDS #3520.01-.04 OR SEE CONSTRUCTION DOCUMENTS FOR SPECIAL PARTITION TYPES DEFINES HEIGHT TO TERMINATE PARTITION; REFER TO NOTES, THIS SHEET, OR SEE CONSTRUCTION DOCUMENTS FOR SPECIAL HEIGHTS
PARTITION SUBSCRIBT NOTES 1
CONSTRUCT PARTITION FROM FLOOR TO UNDERSIDE OF CEILING
2
CONSTRUCT PARTITION FROM FLOOR TO 6" ABOVE CEILING
3
CONSTRUCT FIRE RATED PARTITION FROM FLOOR DECK/STRUCTURE ABOVE. SEE LIFE SAFETY PLANS FOR EXTENT
48
CONSTRUCT PARTITION FROM FLOOR UP TO 48" A.F.F.
EXISTING 2 1/2" SHAFT WALL STUDS AT 16" OC
EXISTING 1" GYPSUM LINER PANEL EXISTING 5/8" GYPSUM BOARD EXISTING SHAFT
7
SLIDE-BY DOOR 1/2" = 1'-0"
8
SHAFT INFILL DETAIL 1 1/2" = 1'-0"
Project No.
6287.040.04
Drawn By
JAS
Checked By
JHA/MLK
Date
07/03/13
NOTICE: The designs shown and described herein including all technical drawings, graphics, and models thereof, are proprietary and cannot be copied, duplicated or commercially exploited, in whole or in part, without express written permission of RSP Architects. These are available for limited review and evaluation by clients, consultants, contractors, government agencies, vendors and office personnel only in accordance with this Notice. © Copyright RSP Architects 2007. All rights reserved.
Revisions No.
Date
Description
PARTITION TYPE INDICATOR LEGEND
DOOR SCHEDULE, DETAILS, PARTITION TYPE INDICATOR, AND INTERIOR DETAILS
A301 C:\Revit Projects\Med Sci 4 Central_jschmit.rvt 7/8/2013 11:22:49 AM
Please purchase PDF Split-Merge on www.verypdf.com to remove this watermark.
EXIST TAG ROOM C100 C101 C102 C103 C104 C105 C106 C108 C109 C111 C112 C113 C115 C116 C117 C118 C119 C120 C121 C122 C123 C124 C300 C301 F400 F401 F402 F406 F407 F408 F409 F410 F412 F413 G101 G102 G104 G105 G107 G108 G109 G111 G112 G113 G114 G115 G116 G117 G118 G119 G120 G121 G122 G123 G124 G125 G126 G127 G128 G129 G130 G131 G132 G133 G134 G135 G137 G138 G139 G140 G141 G142 G143 G144 G145 G146 G147 G300 G303 G304 G305 G309 G310 G311 M100 M101 M102 M103 M104 M105 M106 M107 M108 M109 M110 M112 M113 M114 M115 M116 M117 M118 M119 M120 M122 M123 M220 M222 M224 M225 M226 M227 M230 M231 M239 M241 M242 M243 M244 M245 N100 N101 N102 N103 N104 N105 N106 N107 N108 N109 N110 N111 N112 N113 N114 N115 N117 N118 N119 N120 N121 N122 N123 N124 N125 N126 N127 N128 N129 N130 N131 N132
4-56 4-56 4-56 4-56 4-63 4-56 4-56 4-63 4-63 4-56 4-56 4-56 4-56 4-56 4-56 4-56 4-56 4-56 4-56 4-56 4-56 4-63 NEW NEW 5-80B 5-80B 5-80B NEW NEW 5-80B 5-80B 5-80B 5-80B NEW 4-53 4-53 4-53 4-53 4-53 4-53 4-53 4-53 4-53 4-53 4-53 4-53 4-53 4-53 4-53 4-53 4-53 4-53 4-53 4-53 4-53 4-53 4-53 4-53 4-53 4-53 4-53 4-53 4-53 4-53 4-55 4-53 4-55A 4-55A 4-55A 4-55A 4-55A 4-55A 4-55A 4-29A 4-29A 4-29A 4-29A NEW NEW NEW NEW NEW NEW NEW 4-45 4-45 4-45 4-45 4-54 4-54 4-54 4-54 4-45 4-45 4-45 4-45 4-45 4-45 4-45 4-45 4-28 4-28 4-29-1 4-29-1 4-62 4-62 4-45 4-45 4-45 4-45 4-45 4-45 4-45 4-45 4-45 4-45 4-45 4-45 4-45 4-45 4-56 4-56 4-56 4-56 4-56 4-56 4-56 4-56 4-56 4-65 4-65 4-65A 4-65A 4-56A 4-56A 4-56A 4-56A 4-65 4-66 4-66 4-66 4-66 4-66 4-66 4-66 4-65 4-65 4-65 4-65 4-65 4-65 4-65
DESCRIPTION FASTPREP-24 SCALE MINI CENTRIFUGE CENTRIFUGE FREEZER THERMAL CYCLER THERMAL CYCLER TAPE STATION QUBIT 2.0 FLAM CAB STOMACHER 400 CIRCULATOR BIO STORAGE BOX ISOTEMP PIPETTE HEATER UC REF INSTRUMENT CHARGER MINISPIN VORTEX MIXER SHAK-R-BATH THERMAL CYCLER GALAXY MINI SHAKER PLATFORM SHAKER 4' BIO HOOD REFRIGERATOR BREEDER ISOLATOR CART EXPERIMENTAL ISOLATOR CART TRANSFER CART 4' - FUME HOOD ACID STORAGE CABINET ANAEROBIC CHAMBER 4' BIO HOOD WORK CART BLUE STORAGE BIN FLAM CAB -70 -70 POLOROID GEL CAM CRYOCAN FREEZER CPU UV TRANSILLUMINATOR ENCLOSED SCALE SCALE FREEZER DELI CENTRIFUGE CENTRIFUGE 5' - FUME HOOD FLAM CABINET ACID STORAGE CABINET BELLY DANCER WATERBATH MICRO TWIN HEAT BLOCK HEAT BLOCK DRY BATH THERMAL CYCLER HOTPLATE MICROWAVE ELECTROPHORESIS SYSTEM SCAN WASHER NANO-DROP SPECTAMAX CRYOCAN FACSCALIBUR SHAKER CENTRIFUGE POWER PAC CYTOSPIN COULTER-Z1 5'-0" BIO HOOD STACKED INCUBATOR REFRIGERATOR ANIMAL CART X-CITE TEMPERATURE CONTROL PRINTER 5'-0" BIO HOOD ACID STORAGE CABINET FLAM CABINET ACID STORAGE CABINET REFRIGERATOR MICROWAVE COFFEE POT 5' - FUME HOOD FLAM CABINET ACID STORAGE CABINET FLAM CAB 4' BIO HOOD UC REF INCUB INCUB REFRIGERATOR REFRIGERATOR SPEED VAC SCOPE STATION SCOPE STATION TURBIDIMETER DRY BATH INCUBATOR PROTEAN IEF CELL REFRIGERATOR -80 FREEZER -80 FREEZER -80 FREEZER PRINTER FAX/SCANNER BIO-PHOTOMETER MINI INCUBATOR EPPENDORF BATH UC FREEZER OSOMETER SHAKING BATH SOUND BOX SONICATOR GS-6KR CENTRIFUGE ULTRA ROCKER SHAKER GRANITE BLOCK DIGI SCALE UC FREEZER CENTRIFUGE ROCKING SHAKER EMERSON 1056 RAND-SRL I.V. CART 4' BIO HOOD FREEZER DELI STACKED INCUBATOR FREEZER REFRIGERATOR -80 FREEZER -80 FREEZER REFRIGERATOR CENTRIFUGE CENTRIFUGE CAPTURE HOOD 4' BIO HOOD STACKED INCUBATOR 4' BIO HOOD WATERBATH MICROSCOPE BIOTEK ELx50 MINI CENTRIFUGE VORTEX GENIE MICROSCOPE SCALE PH METER STIR PLATE SCALE COULTER COUNTER ENCLOSED SCALE
C:\Revit Projects\Med Sci 4 Central_jschmit.rvt 7/8/2013 11:22:49 AM
EQUIPMENT SCHEDULE ROOM NUMBER ORDERED BY
QTY
NEW ROOM
1 1 1 1 1 3 1 1 1 1 1 1 3 1 1 1 1 1 1 1 1 1 1 1 2 4 3 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
LAB LAB LAB LAB LAB LAB LAB LAB LAB LAB LAB LAB LAB LAB LAB LAB LAB LAB LAB LAB LAB LAB LAB LAB GERM FREE FACILITY GERM FREE FACILITY
4-12 4-12 4-12 4-12 4-12 4-12 4-12 4-12 4-12 4-12 4-12 4-12 4-12 4-12 4-12 4-12 4-12 4-12 4-12 4-12 4-12 4-12 4-12 4-12 4-10HA 4-10HA
PREP ROOM PREP ROOM PREP ROOM GERM FREE FACILITY GERM FREE FACILITY GERM FREE FACILITY PREP ROOM EQUIPMENT EQUIPMENT LAB LAB LAB LAB LAB LAB LAB LAB LAB LAB LAB LAB LAB LAB LAB LAB LAB LAB LAB LAB LAB LAB LAB LAB LAB LAB LAB LAB LAB SIT-DOWN LAB LAB LAB TISSUE CULTURE TISSUE CULTURE TISSUE CULTURE TISSUE CULTURE LAB LAB LAB LAB TISSUE CULTURE LAB LAB LAB BREAK ROOM BREAK ROOM BREAK ROOM LAB LAB LAB LAB TISSUE CULTURE TISSUE CULTURE TISSUE CULTURE TISSUE CULTURE LAB LAB LAB LAB LAB LAB LAB LAB EQUIPMENT EQUIPMENT EQUIPMENT EQUIPMENT SECRETARY SECRETARY LAB LAB LAB LAB LAB LAB LAB LAB LAB LAB LAB LAB LAB LAB LAB LAB LAB LAB LAB TISSUE CULTURE LAB LAB TISSUE CULTURE LAB LAB EQUIPMENT EQUIPMENT LAB LAB LAB LAB TISSUE CULTURE TISSUE CULTURE TISSUE CULTURE TISSUE CULTURE TISSUE CULTURE LAB LAB LAB TISSUE CULTURE LAB LAB LAB LAB LAB TISSUE CULTURE
4-10H 4-10H 4-10H 4-10HA 4-10HA 4-10HA 4-10H 4-28 4-28 4-12-3 4-12-3 4-12-3 4-12-3 4-12-3 4-12 4-12 4-12-3 4-12-3 4-12-3 4-12-3 4-12-3 4-12-3 4-12-3 4-12-3 4-12-3 4-12-3 4-12-3 4-12-3 4-12-3 4-12-3 4-12-3 4-12-3 4-12-3 4-12-3 4-12-3 4-12-3 4-12-3 4-12-3 4-12-2 4-12-3 4-12-3 4-12-3 4-12D 4-12D 4-12D 4-12D 4-12-3 4-12-3 4-12-3 4-12-3 4-12D 4-12-3 4-12-3 4-12-3 4-01 4-01 4-01 4-12 4-12 4-12 4-12 4-12C 4-12C 4-12C 4-12C 4-12 4-12 4-12 4-12 4-12 4-12 4-12 4-12 4-28 4-28 4-28 4-28 4-21 4-21 4-12 4-12 4-12 4-12 4-12 4-12 4-12 4-12 4-12 4-12 4-12 4-12 4-12 4-12 4-12 4-12 4-12 4-12 4-12 4-12A 4-12-3 4-12 4-12A 4-12 4-12 4-28 4-28 4-12 4-12 4-12 4-12 4-12A 4-12A 4-12C 4-12C 4-12D 4-12 4-12 4-12 4-12C 4-12 4-12 4-12 4-12 4-12 4-12A
Please purchase PDF Split-Merge on www.verypdf.com to remove this watermark.
PROPONENT PROPONENT CONSTRUCTION MANAGER CONSTRUCTION MANAGER CONSTRUCTION MANAGER PROPONENT PROPONENT PROPONENT PROPONENT PROPONENT PROPONENT PROPONENT -
SUPPLIED BY
INSTALLED BY
MANUFACTURER MANUFACTURER MANUFACTURER MANUFACTURER MANUFACTURER MANUFACTURER MANUFACTURER MANUFACTURER MANUFACTURER MANUFACTURER MANUFACTURER MANUFACTURER -
EQUIPMENT SERVICES EQUIPMENT SERVICES EQUIPMENT SERVICES EQUIPMENT SERVICES OPERATIONS EQUIPMENT SERVICES EQUIPMENT SERVICES EQUIPMENT SERVICES EQUIPMENT SERVICES CONTRACTOR EQUIPMENT SERVICES CONTRACTOR EQUIPMENT SERVICES OPERATIONS EQUIPMENT SERVICES EQUIPMENT SERVICES EQUIPMENT SERVICES EQUIPMENT SERVICES EQUIPMENT SERVICES EQUIPMENT SERVICES EQUIPMENT SERVICES EQUIPMENT SERVICES CONTRACTOR CONTRACTOR EQUIPMENT SERVICES EQUIPMENT SERVICES CONTRACTOR CONTRACTOR CONTRACTOR EQUIPMENT SERVICES OPERATIONS CONTRACTOR CONTRACTOR CONTRACTOR OPERATIONS OPERATIONS EQUIPMENT SERVICES EQUIPMENT SERVICES OPERATIONS EQUIPMENT SERVICES EQUIPMENT SERVICES EQUIPMENT SERVICES EQUIPMENT SERVICES OPERATIONS OPERATIONS EQUIPMENT SERVICES EQUIPMENT SERVICES CONTRACTOR CONTRACTOR CONTRACTOR EQUIPMENT SERVICES EQUIPMENT SERVICES EQUIPMENT SERVICES EQUIPMENT SERVICES EQUIPMENT SERVICES EQUIPMENT SERVICES EQUIPMENT SERVICES EQUIPMENT SERVICES CONTRACTOR EQUIPMENT SERVICES EQUIPMENT SERVICES EQUIPMENT SERVICES EQUIPMENT SERVICES EQUIPMENT SERVICES EQUIPMENT SERVICES EQUIPMENT SERVICES EQUIPMENT SERVICES EQUIPMENT SERVICES EQUIPMENT SERVICES EQUIPMENT SERVICES CONTRACTOR EQUIPMENT SERVICES OPERATIONS CONTRACTOR EQUIPMENT SERVICES EQUIPMENT SERVICES EQUIPMENT SERVICES CONTRACTOR CONTRACTOR CONTRACTOR CONTRACTOR OPERATIONS CONTRACTOR CONTRACTOR CONTRACTOR CONTRACTOR CONTRACTOR CONTRACTOR CONTRACTOR OPERATIONS EQUIPMENT SERVICES EQUIPMENT SERVICES OPERATIONS OPERATIONS EQUIPMENT SERVICES EQUIPMENT SERVICES EQUIPMENT SERVICES EQUIPMENT SERVICES EQUIPMENT SERVICES EQUIPMENT SERVICES OPERATIONS OPERATIONS OPERATIONS OPERATIONS EQUIPMENT SERVICES EQUIPMENT SERVICES EQUIPMENT SERVICES EQUIPMENT SERVICES EQUIPMENT SERVICES CONTRACTOR EQUIPMENT SERVICES EQUIPMENT SERVICES EQUIPMENT SERVICES EQUIPMENT SERVICES EQUIPMENT SERVICES EQUIPMENT SERVICES EQUIPMENT SERVICES EQUIPMENT SERVICES EQUIPMENT SERVICES CONTRACTOR EQUIPMENT SERVICES EQUIPMENT SERVICES EQUIPMENT SERVICES EQUIPMENT SERVICES EQUIPMENT SERVICES CONTRACTOR OPERATIONS OPERATIONS EQUIPMENT SERVICES OPERATIONS OPERATIONS OPERATIONS OPERATIONS OPERATIONS EQUIPMENT SERVICES EQUIPMENT SERVICES CONTRACTOR CONTRACTOR EQUIPMENT SERVICES CONTRACTOR EQUIPMENT SERVICES EQUIPMENT SERVICES EQUIPMENT SERVICES EQUIPMENT SERVICES EQUIPMENT SERVICES EQUIPMENT SERVICES EQUIPMENT SERVICES EQUIPMENT SERVICES EQUIPMENT SERVICES EQUIPMENT SERVICES EQUIPMENT SERVICES EQUIPMENT SERVICES
REMARKS
EXIST TAG ROOM N133 N136 N137 N138 N139 N228 N300 O100 O101 O102 O104 O105 O106 O107 O108 O113 O124 O132 O133 X110 X111 X300 Z128 Z129 Z130 Z131 Z141 Z142 Z143 Z160 Z161 Z162 Z163 Z164 Z165 Z166 Z167 Z181 Z182 Z183 Z202 Z205 Z206 Z207 Z208 Z209 Z210 Z212 Z215 Z224 Z225 Z229 Z300 Z301 Z302 Z303 Z304 Z305
4-65 4-65 4-65 4-56 4-65 4-56 NEW 4-35C 4-35A 4-35A 4-35C 4-35C 4-35C 4-35C 4-35C 4-35A 4-35C 4-35C 4-35A 4-29-1 4-29-1 NEW 4-71 4-71 4-71 4-73 4-73 4-73 4-73 4-73 4-73 4-73 4-73 4-73 4-73 4-73 4-73 4-67 4-67 4-67 4-25 4-24 4-24 4-24 4-24 4-24 4-24 4-24 4-24 4-25 4-25 4-25 NEW NEW NEW NEW NEW NEW
DESCRIPTION MICROSCOPE PLASTIC CART PROFUSION CART FREEZING BATH MICROPLATE READER NANOPURE INCUB ANESTHESIA MACHINE UC REF S.S. CART CAUTERY ROBOTIC SCOPE S.S. CART S.S. CART HYDROGEN GENERATOR BATTERY PACK OPERATING TABLE THERMAL PAD VACUUM -80 FREEZER -80 FREEZER -70 OPERATING TABLE I.V. CART MODULUS-SE DEFIBRILLATOR CART S.S. CART DEFIBRILLATOR SSE2L MODULUS-SE I.V. CART OPERATING TABLE OPERATING TABLE MASTERFLEX L/S CART MODULUS-SE I.V. CART I.V. CART MODULUS-SE I.V. CART OPERATING TABLE UC REFRIGERATOR UC REFRIGERATOR ICE MACHINE TABLE SCALE SHOP VAC I.V. CART ANESTHESIA MACHINE MEDTRONIC AUTOLOG SOILED LINEN PRINTER PRINTER/COPIER PRINTER SUPPLY CART DEFIBRILLATOR CART SCRUBBER UTILITY CART GONDOLA GETINGE 533LS STERILIZER
EQUIPMENT SCHEDULE ROOM NUMBER ORDERED BY
QTY
NEW ROOM
1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 11 2 1 1 1 1
TISSUE CULTURE LAB LAB LAB LAB LAB TISSUE CULTURE ORTHO OPERATING ROOM ORTHO PREP ORTHO PREP ORTHO OPERATING ROOM ORTHO OPERATING ROOM ORTHO OPERATING ROOM ORTHO OPERATING ROOM ORTHO OPERATING ROOM ORTHO PREP ORTHO OPERATING ROOM ORTHO OPERATING ROOM ORTHO PREP EQUIPMENT EQUIPMENT EQUIPMENT OPERATING ROOM OPERATING ROOM OPERATING ROOM OPERATING ROOM OPERATING ROOM OPERATING ROOM OPERATING ROOM OPERATING ROOM OPERATING ROOM OPERATING ROOM OPERATING ROOM
4-12A 4-12 4-12 4-12 4-12 4-12 4-12C 4-10E 4-10F 4-10F 4-10E 4-10E 4-10E 4-10E 4-10E 4-10F 4-10E 4-10E 4-10F 4-28 4-28 4-28 4-10B 4-10B 4-10B 4-10A 4-10A 4-10A 4-10A 4-10A 4-10A 4-10A 4-10A
OPERATING ROOM
4-10A
OPERATING ROOM OPERATING ROOM OPERATING ROOM OPERATING ROOM SURGICAL TECHS PREP AREA SOILED WORK PREP AREA PREP AREA PREP AREA PREP AREA PREP AREA PREP AREA SURGICAL TECHS SURGICAL TECHS SURGICAL TECHS
4-10A 4-10D 4-10D 4-10D 4-06B 4-06 4-06A 4-06 4-06 4-06 4-06 4-06 4-06 4-06B 4-06B 4-06B
OPERATING ROOM CUSTODIAL CUSTODIAL CUSTODIAL SOILED WORK
4-05A 4-05A 4-05A 4-06A
PROPONENT PROPONENT PROPONENT PROPONENT PROPONENT PROPONENT PROPONENT FACILITIES
SUPPLIED BY
INSTALLED BY
-
EQUIPMENT SERVICES CONTRACTOR CONTRACTOR EQUIPMENT SERVICES EQUIPMENT SERVICES EQUIPMENT SERVICES EQUIPMENT SERVICES EQUIPMENT SERVICES OPERATIONS CONTRACTOR EQUIPMENT SERVICES EQUIPMENT SERVICES CONTRACTOR CONTRACTOR EQUIPMENT SERVICES EQUIPMENT SERVICES EQUIPMENT SERVICES EQUIPMENT SERVICES EQUIPMENT SERVICES OPERATIONS OPERATIONS OPERATIONS EQUIPMENT SERVICES EQUIPMENT SERVICES EQUIPMENT SERVICES EQUIPMENT SERVICES CONTRACTOR EQUIPMENT SERVICES EQUIPMENT SERVICES EQUIPMENT SERVICES CONTRACTOR EQUIPMENT SERVICES EQUIPMENT SERVICES EQUIPMENT SERVICES EQUIPMENT SERVICES CONTRACTOR CONTRACTOR EQUIPMENT SERVICES EQUIPMENT SERVICES EQUIPMENT SERVICES OPERATIONS OPERATIONS OPERATIONS EQUIPMENT SERVICES EQUIPMENT SERVICES EQUIPMENT SERVICES EQUIPMENT SERVICES EQUIPMENT SERVICES CONTRACTOR EQUIPMENT SERVICES EQUIPMENT SERVICES EQUIPMENT SERVICES EQUIPMENT SERVICES EQUIPMENT SERVICES EQUIPMENT SERVICES EQUIPMENT SERVICES EQUIPMENT SERVICES EQUIPMENT SERVICES
MANUFACTURER MANUFACTURE MANUFACTURE MANUFACTURE MANUFACTURE MANUFACTURE MANUFACTURE MANUFACTURE
REMARKS
RSP Architects 320 South Broadway Ste. B 507.285.6569 Rochester, Minnesota 55904 612.677.7499 fax www.rsparch.com
Consultants
Certification
I hereby certify that I have reviewed the Mayo Clinic Standard General Specifications prepared by Ronald B. Carlson, License Number 10850, that they are appropriate for the work except as amended in this plan, specification or report, and that I am a duly licensed Architect under the laws of the State of Minnesota.
Signature
DAVID NORBACK
Registration Number Date
11902 07.03.13
I hereby certify that this plan, specification or report was prepared by me or under my direct supervision and that I am a duly licensed Architect under the laws of the State of Minnesota.
Signature
DAVID NORBCK
Registration Number Date
11902 07.03.13
Project For
Large Animal Surgery and Germ Free Facility Medical Sciences Building Fourth Floor Project #7R120760
Project No.
6287.040.04
Drawn By
JAS
Checked By
JHA/MLK
Date
07/03/13
NOTICE: The designs shown and described herein including all technical drawings, graphics, and models thereof, are proprietary and cannot be copied, duplicated or commercially exploited, in whole or in part, without express written permission of RSP Architects. These are available for limited review and evaluation by clients, consultants, contractors, government agencies, vendors and office personnel only in accordance with this Notice. © Copyright RSP Architects 2007. All rights reserved.
Revisions No.
Date
Description
EQUIPMENT SCHEDULE
A801
M105 M112
G142
M107 M114
M106
M115
M113
N120
M116
M108
4-12B
M104
STAIR 4-49B
N122
STORAGE 4-49A
TISSUE CULTURE
4-12C
MICROSCOPY
M220 M110
N300
TISSUE CULTURE
M222
M109
G300
4-12D
N121
DN
G140
M119
G143
M100
Consultants
EQUIPMENT
M102
4-28
M103
ELEC RM 4-004D-1 M224 M230
ELEC RM 4-004D-2
M117
M239
M226
G101
Certification
G102
I hereby certify that I have reviewed the Mayo Clinic Standard General Specifications prepared by Ronald B. Carlson, License Number 10850, that they are appropriate for the work except as amended in this plan, specification or report, and that I am a duly licensed Architect under the laws of the State of Minnesota.
X111
SIT-DOWN 4-12-1
M227
M241 M242
M120
M118
X300
M101
M245
RSP Architects 320 South Broadway Ste. B 507.285.6569 Rochester, Minnesota 55904 612.677.7499 fax www.rsparch.com
G141
N126
M225
UP
SIT-DOWN
M231
4-12-2
X110
Signature
N111
DAVID NORBACK
N112 Registration Number
M244
M243
G111
N228
G112
Date
N127
N123
G134
C105 N101 N128
N124
N129
N130
N138
N125
N115
N100
C105
G104
C105
C108
C116
C115
N139 C112
N137
C111
C113
C124
C100
C103
C122
C102 C123
C101
N103
N110
G127
G128
C129
C104
C301
Signature
G118
G305
Registration Number
G120
Project For
4-26
N106
4-12-3
G138 G137
G116
G113
G114 G145
G146
G109
Large Animal Surgery and Germ Free Facility
OFFICE 4-25
G108 G115
C300
CORRIDOR
Medical Sciences Building Fourth Floor
4-04-5
G107
N105 N132 N133
N108
N119
OFFICE
N113
4-24
TISSUE CULTURE
Project #7R120760
CORRIDOR
4-12A
4-04-4
N109 N104
N118
A
N102
Z303
TOILET/ CHANGE
B
4-11A
CUSTODIAL 4-05A
OFFICE
KEY PLAN
4-23
MECHANICAL 4-05
1
PARTIAL FOURTH LEVEL EQUIPMENT PLAN - AREA A
07.03.13
OFFICE LAB
G139
11902
Date
G129
G133
DAVID NORBCK
G304
G147
N136
4-27
C120
C121 N107
G125
G126
G105 C118 C119
C117
G124
G130
G131
C109
G123
G122 G132
C106 N131
N114
G121
OFFICE G117
4-12
G119
S108
G144
LAB
07.03.13
I hereby certify that this plan, specification or report was prepared by me or under my direct supervision and that I am a duly licensed Architect under the laws of the State of Minnesota.
G135
N117
11902
VESTIBULE/ LOCKER 4-11
Project No.
FLEX OFFICE
6287.040.04
Drawn By
4-16
JAS
Checked By
1/4" = 1'-0"
JHA/MLK
Date
07/03/13
NORTH
NOTICE: The designs shown and described herein including all technical drawings, graphics, and models thereof, are proprietary and cannot be copied, duplicated or commercially exploited, in whole or in part, without express written permission of RSP Architects. These are available for limited review and evaluation by clients, consultants, contractors, government agencies, vendors and office personnel only in accordance with this Notice. Š Copyright RSP Architects 2007. All rights reserved.
Revisions No.
Date
Description
PARTIAL FOURTH LEVEL EQUIPMENT PLAN - AREA A
A801A C:\Revit Projects\Med Sci 4 Central_jschmit.rvt 7/8/2013 11:22:50 AM
Please purchase PDF Split-Merge on www.verypdf.com to remove this watermark.
OFFICE
N113 N133
4-24
TISSUE CULTURE
CORRIDOR
4-12A
4-04-4
N109
N108
N104
N118
N119
N102
Z303
TOILET/ CHANGE 4-11A
CUSTODIAL 4-05A
RSP Architects 320 South Broadway Ste. B 507.285.6569 Rochester, Minnesota 55904 612.677.7499 fax www.rsparch.com
OFFICE 4-23
MECHANICAL
Z304
4-05
VESTIBULE/ LOCKER
Z302
FLEX OFFICE
4-11
4-16
Z206
STORAGE 4-07
Z305
Consultants
OFFICE 4-06C
OFFICE 4-22
CONFERENCE 4-15
SOILED WORK 4-06A
Certification
Z202
CORRIDOR 4-04-2
M122
Z225
4-06B
Z224
I hereby certify that I have reviewed the Mayo Clinic Standard General Specifications prepared by Ronald B. Carlson, License Number 10850, that they are appropriate for the work except as amended in this plan, specification or report, and that I am a duly licensed Architect under the laws of the State of Minnesota.
Z229
SURGICAL TECHS
M123
SECRETARY
DN
Signature
4-21
UP STAIR 4-08
CLEAN STORAGE
DAVID NORBACK
Registration Number
4-10G
11902
Date
07.03.13
I hereby certify that this plan, specification or report was prepared by me or under my direct supervision and that I am a duly licensed Architect under the laws of the State of Minnesota.
CLOSET 4-04-1
OFFICE 4-20
Signature
ELECTRIC 4-004B-1
CORRIDOR 4-04
DAVID NORBCK
Registration Number
CORRIDOR 4-10-1
11902
Date
Z208
G309
Z207
TOILET MEN 4-02
Z215
TOILET WOMEN 4-03
BREAK ROOM 4-01
O102
Z210
4-06
O133
SCRUB 4-10
SCRUB
STORAGE
ORTHO PREP
4-10-2
4-10C
Z212
4-10F
PREP ROOM
O113
O101
4-10H
F407
F408
F402
OPERATING ROOM 4-10D
Z160
Z165
Z130
Z131
Z301
Z167
Z161
OPERATING ROOM
F401
O132
F402
GERM FREE FACILITY
Medical Sciences Building Fourth Floor
4-10HA O124
F400
4-10E F401
4-10B
Z163
Z162
Z182
OPERATING ROOM
4-10A
Z141
Z129
O104
ORTHO OPERATING ROOM
Large Animal Surgery and Germ Free Facility F400
O100
Z181
Z301
Z143
F413
F402
Z205
G311
Project For
F406
Z209
PREP AREA
07.03.13
F401
O105 Z183
Z128
O106
Z142
Project #7R120760
F409
O107
A
O108 Z300
Z300
Z300
Z300
Z300
Z300
Z300
Z300
Z300
Z300
Z300
F401 F410 B
F412 KEY PLAN
Project No.
6287.040.04
Drawn By
1
PARTIAL FOURTH LEVEL EQUIPMENT PLAN - AREA B
JAS
Checked By
1/4" = 1'-0"
NORTH
JHA/MLK
Date
07/03/13
NOTICE: The designs shown and described herein including all technical drawings, graphics, and models thereof, are proprietary and cannot be copied, duplicated or commercially exploited, in whole or in part, without express written permission of RSP Architects. These are available for limited review and evaluation by clients, consultants, contractors, government agencies, vendors and office personnel only in accordance with this Notice. Š Copyright RSP Architects 2007. All rights reserved.
Revisions No.
Date
Description
PARTIAL FOURTH LEVEL EQUIPMENT PLAN - AREA B
A801B C:\Revit Projects\Med Sci 4 Central_jschmit.rvt 7/8/2013 11:22:52 AM
Please purchase PDF Split-Merge on www.verypdf.com to remove this watermark.
M103
M102
2' - 0"
M101
5' - 0"
6' - 1"
2' - 7 3/4" 24BC1WB
18BD4WB
4' - 5 3/4"
1"
18BD4WB 14' - 9 1/2"
2' - 7 3/4" 24BC1WB
18BD4WB 14' - 9 1/2"
18BD4WB
1"
6
1
2' - 10 3/4"
2' - 10 3/4"
3' - 5"
18BD4WB
1/4" = 1'-0"
14' - 9 1/2"
14' - 6" 3036W
3036W
1 3/4"
3036W
3036W
2436W
3' - 0" 8' - 0"
4' - 1"
2' - 9 3/4"
30BC1WB
18BD4WB
3' - 0 3/4"
18BD4WB
11
1
1
3' - 4"
3' - 4"
2' - 6" 1' - 0"
4
1"
18BD4WB 14' - 9 1/2"
11
4
6 1 3' - 4"
3' - 4"
6"
RSP Architects 320 South Broadway Ste. B 507.285.6569 Rochester, Minnesota 55904 612.677.7499 fax www.rsparch.com
14' - 9 1/2"
LAB BENCH 2 - DR. V. MILLER - SOUTH
5
1/4" = 1'-0"
36BC1WB
4
2' - 6"
8' - 0"
30BC1WB
LAB BENCH 2 - DR. V. MILLER - NORTH
4
7 A920
11"
11" 4
LAB BENCH 1 - DR. V. MILLER - SOUTH
3
1/4" = 1'-0"
M115
3
3
3' - 0"
M225
3
4' - 0"
7
LAB BENCH 1 - DR. V. MILLER - NORTH
2
1/4" = 1'-0"
1"
1 3/4"
12' - 3 1/2"
8' - 0"
M114
4' - 0"
4' - 0"
7
24BC1WB 2' - 7 3/4"
12' - 3 1/2"
4' - 1"
M116
3' - 0"
M222
M220
E
8' - 0"
4' - 1" 4
DR. V. MILLER LAB - SOUTH WALL
1
9
8' - 0"
8' - 0"
6
M110
3' - 0"
1
2' - 6"
6' - 0"
M112
M108
M109
2' - 6"
M113
M100
3
1 A921
3036W
9
3' - 0"
2' - 0"
10
11' - 10 1/2"
5
5
11"
3636W
11' - 10 1/2"
11"
3636W
4
1 A921
3' - 0"
1"
1 A921
4' - 0"
5' - 6"
1 A921
4' - 1"
7 A920
1 A920
DR. V. MILLER LAB - NORTH WALL
6
1/4" = 1'-0"
1/4" = 1'-0"
Consultants
2' - 4 3/4"
1
2' - 4 3/4"
1
2' - 4 3/4" 6"
3' - 0 3/4"
MICROSCOPY - WEST WALL
7
1
6
3' - 0 3/4"
6"
3' - 3"
5
3' - 0"
3636W
30SC
2' - 11 3/4"
N121
2' - 0"
4
4
1"
9' - 7"
J
4' - 6"
4' - 2"
Certification
8' - 0"
8' - 0"
1
3' - 3"
3636W
N122
G142
1
1"
G141
3' - 0"
3' - 0"
5' - 4 1/2"
6"
D E
I hereby certify that I have reviewed the Mayo Clinic Standard General Specifications prepared by Ronald B. Carlson, License Number 10850, that they are appropriate for the work except as amended in this plan, specification or report, and that I am a duly licensed Architect under the laws of the State of Minnesota.
G143
1
3' - 0"
30SC
G300
3' - 0"
1
3636W
8
M100
N121
N126
M107
7 11 1/2"
1' - 0"
6
7 11 1/2"
30SC
4' - 9"
12' - 1"
Signature
7" 8 3/4"
4' - 9"
1/4" = 1'-0"
Date
TISSUE CULTURE 1 - DR. NYBERG & C.G.A. McGREGOR - NORTH WALL
9
DAVID NORBACK
Registration Number
3 A920
MICROSCOPY - NORTH WALL
8
1/4" = 1'-0"
3' - 0 3/4"
3636W
3' - 0"
8' - 0"
2' - 0" 1
3636W
M106
M105
3' - 0"
3' - 0"
6
3636W
3' - 0"
4236W
7 A920
1"
4
4
2' - 0"
4' - 9 1/2"
1"
3' - 0"
4' - 9 1/2"
1 A920
2' - 0"
4' - 9 1/2"
7 A920
N300
10
1/4" = 1'-0"
TISSUE CULTURE 2 - DR. NYBERG & C.G.A. McGREGOR - SOUTH WALL
11
1/4" = 1'-0"
TISSUE CULTURE 2 - DR. NYBERG & C.G.A. McGREGOR - NORTH WALL 1/4" = 1'-0"
07.03.13
I hereby certify that this plan, specification or report was prepared by me or under my direct supervision and that I am a duly licensed Architect under the laws of the State of Minnesota.
DR. V. MILLER LAB - WEST WALL
12
1/4" = 1'-0" Signature
5"
18BD418BD4
2' - 8"
1"
36BC1
16' - 0"
LAB BENCH 3 - DR. V. MILLER - WEST
7 A920
8
2436W 2436W 2436W
5' - 0"
2' - 8"
36BC1
18BD418BD4
2' - 8"
24BC1
2' - 6"
30BC1
30BC1
1/2"
16' - 0"
17
18BD418BD4 2' - 6 1/2"
1' - 0"
36BC1
20
1/4" = 1'-0"
FLEX LAB - MICROBIOME - WEST WALL
21
1/4" = 1'-0"
22
1/4" = 1'-0"
4' - 1"
8' - 0"
30BC1 18BD4
18BD4 18BD4
3' - 3 1/2"
16' - 0"
3' - 0 1/2"
LAB BENCH 1 - FLEX LAB - MICROBIOME EAST
23
1/4" = 1'-0"
1"
26
4
FLEX LAB - MICROBIOME - EAST WALL
30BC1
1/4" = 1'-0"
Please purchase PDF Split-Merge on www.verypdf.com to remove this watermark.
24BC1
2' - 8 1/2"
18BD4
2' - 8 1/2"
11" 4' - 0"
3' - 0"
18BD4
4' - 6"
18BD4
3' - 0"
5"
16' - 1"
LAB BENCH 2 - FLEX LAB - MICROBIOME EAST
24
Project No.
1/4" = 1'-0"
6287.040.04
Drawn By
BCS
31
30BC1
LAB BENCH 2 - DR. C.G.A. McGREGOR EAST 1/4" = 1'-0"
1 A921 11' - 6"
4' - 6"
1"
G124
G126 C301
1' - 8"
3"
7"
4
4' - 9"
1"
30SC
4' - 9"
1"
G121 G122
G127
G134
G123
3' - 0"
3' - 0" 4
48BC1
G125
30BC1
7
24BC1
2' - 6"
18BD4
5' - 5"
14' - 0"
FLEX LAB - MICROBIOME - NORTH WALL
29
1/4" = 1'-0"
© Copyright RSP Architects 2007. All rights reserved.
Revisions No.
Date
Description
3' - 0"
D
4' - 0"
J
07/03/13
NOTICE: The designs shown and described herein including all technical drawings, graphics, and models thereof, are proprietary and cannot be copied, duplicated or commercially exploited, in whole or in part, without express written permission of RSP Architects. These are available for limited review and evaluation by clients, consultants, contractors, government agencies, vendors and office personnel only in accordance with this Notice.
11"
9 C106
JHA/MLK
Date
6
LAB BENCH 1 - DR. C.G.A. McGREGOR EAST 1/4" = 1'-0"
1"
KEYNOTES - ELEVATIONS
G146
G108
9 G147
E
4' - 0"
3' - 0"
3' - 0"
G120
14' - 0"
14' - 0"
LAB BENCH 1 - DR. C.G.A. McGREGOR WEST
C:\Revit Projects\Med Sci 4 Central_jschmit.rvt 7/8/2013 11:22:56 AM
1"
4' - 0"
4' - 0"
3' - 0"
1"
4
5
5
G109
9
4' - 1"
8' - 0"
8' - 0"
G139
24BC1
7"
28
8' - 0"
G138
4' - 1"
4' - 1"
G128
G116
2' - 8"
4
1/4" = 1'-0"
3
G145 11"
11"
3
G137
J
18BD4
7"
4
DR. NYBERG & V. MILLER LAB - SOUTH WALL
11"
5
G129
Project #7R120760
1 A921
9
2' - 8"
27
1/4" = 1'-0" 1 A921
G104
30BC1
36BC1
E
1' - 0"
1 A921
G130
C301
4' - 9"
1/4" = 1'-0"
G132
N101 3' - 0"
5' - 0"
4
LAB BENCH 2 - FLEX LAB - MICROBIOME WEST
G131
J
C112
C116
1"
1/4" = 1'-0"
6
3' - 0"
C104
N137
3' - 0"
36BC1
16' - 1"
11' - 6"
N107
C129
4' - 2"
2' - 8 1/2"
C300
4' - 6"
18BD418BD4
4' - 9 1/2"
4
LAB BENCH 1 - FLEX LAB - MICROBIOME WEST
1
4' - 0"
C101
C111 2' - 5"
C115
9
5
4
4
32
11 30BC1
1"
2' - 8 1/2"
18BD4
2' - 8 1/2"
14' - 0"
LAB BENCH 2 - DR. C.G.A. McGREGOR WEST 1/4" = 1'-0"
4
24BC1
D
J
E
G133
55SC1
4' - 9"
33
DR. C.G.A. McGREGOR LAB - SOUTH WALL 1/4" = 1'-0"
G105
G134 6 G127
1"
1"
G128
3' - 0"
C102
8' - 0"
C122
C103
7
C118
C113
E
1"
16' - 0"
C117
D
4
C100
4' - 1"
C121
8' - 0"
3' - 0"
30BC1
11"
C123
TISSUE CULTURE - DR. NYBERG & V. MILLER - NORTH WALL
4' - 0"
4' - 0"
3' - 0"
18BD4 30BC1
8
C120
30
2' - 8"
C105
J
4
18BD4 24BC1
5
Checked By
9
25
5' - 9"
6
13' - 2"
1 A921
13' - 2" 3
1"
4
4 A920
TISSUE CULTURE - DR. NYBERG & V. MILLER - SOUTH WALL
5
36BC1
11' - 8"
4' - 10"
6 A920
19
18BD4
C108
Medical Sciences Building Fourth Floor
8' - 0"
1"
18BD4
1/4" = 1'-0"
C119 C124
Large Animal Surgery and Germ Free Facility
LAB BENCH 2 - DR. NYBERG - WEST
3
C109
30BC1 18BD418BD4 30BC1
16' - 0"
1 A921
1 A921
3
C106
C105
8' - 0"
8' - 0"
30SC
4
3
2' - 8 1/4"
4' - 1"
30SC
18
1/4" = 1'-0"
13' - 6"
2' - 7 3/4"
6
LAB BENCH 2 - DR. NYBERG - EAST
07.03.13
1 2' - 7 1/4"
6
11902
3
4' - 2"
18BD4 6' - 1"
1
2' - 6 1/2"
16' - 0"
13' - 6"
4' - 1"
2' - 0"
3' - 0"
N108
N118
3' - 0"
8' - 0"
N105
2' - 0"
3' - 0" N119
N133
24BC1
3636W
N228
2' - 0"
N132
8' - 0"
4
1/4" = 1'-0"
1 A921
4' - 1"
N123
Registration Number
Project For
4' - 1"
11"
4' - 0"
3' - 0"
N138
4' - 0"
4' - 1"
N128
LAB BENCH 1 - DR. NYBERG - WEST
16
N124
N115
4
1 A920
N125
11"
1836W
4
1/4" = 1'-0"
N101
N139
N117
1"
LAB BENCH 1 - DR. NYBERG - EAST
15
1/4" = 1'-0"
4
2' - 8"
24BC1
N131
4' - 0"
18BD4WB 16' - 0"
30BC1
4
N100
11"
18BD4WB
30BC1
N130
4' - 1"
1/4" = 1'-0"
1"
2' - 8 1/2"
N129
3' - 0"
14
2' - 8 1/2"
30BC1
N127
8' - 0"
8' - 0"
4' - 0"
4' - 0"
18BD4WB
1"
M244
4
LAB BENCH 3 - DR. V. MILLER - EAST
13
11"
11"
4' - 8"
18BD4WB 16' - 0"
3
G112
DAVID NORBCK
Date
8' - 0"
2' - 9"
G111
1 A921
13' - 6"
3
11"
1' - 0 1/2" 42BC1
6
M243
13' - 6"
3
3' - 0"
7
13' - 6"
3' - 0"
M239
M245
4' - 0" 3' - 0"
M231
3
4' - 1"
M241
8' - 0"
M224
8' - 0"
M230
M226
4' - 1"
M227
11"
M242
13' - 6"
1 A921
3' - 0"
13' - 6"
3
1 A921
11"
13' - 6"
1 A921
1 A921
4' - 1"
1 A921
11902
1"
4
7" 4' - 9"
3"
1 3 4 5 6 7 8 9 10 11 12
STANDARD STEEL COUNTERTOP SUPPORT WALL BRACKET (27x19) - SEE DETAIL 19/A920 ELECTRIC/ VOICE/ DATA RACEWAY - COORDINATE WITH ELECTRICAL PLASTIC LAMINATE FILLER. PLASTIC LAMINATE VENT CHASE - SEE DETAIL 9/A920 PLASTIC LAMINATE WALL CLEAT 1" PLASTIC LAMINATE END PANEL. PLASTIC LAMINATE PIPETE RACK - SEE DETAIL 16/A920 1" PLASTIC LAMINATE BACKER BOARD. GAS CYLINDER FURNITURE - SEE FURNITURE PLAN (I304) STANDARD LAB COAT HOOK STRIP MOUNTED AT 5'-0" A.F.F. UNLESS NOTED OTHERWISE SEE DETAIL 15/A920
INTERIOR ELEVATIONS
1' - 8"
A901
2' - 6"
4
18BC1
30BC1
4
+/-
2 A920
5' - 0"
EQ
EQ
11
11
Z229
Z224
5' - 0"
5' - 0"
Z225
EQ
EQ
11
11
8' - 0" 5' - 0"
8' - 0"
RSP Architects 320 South Broadway Ste. B 507.285.6569 Rochester, Minnesota 55904 612.677.7499 fax www.rsparch.com
OFFICE - SURGICAL TECH - WEST WALL
6
OFFICE - SURGICAL TECH - NORTH WALL
7
1/4" = 1'-0"
1/4" = 1'-0"
2 A920
12' - 0"
EQ
11
4
2"
1/4" = 1'-0"
2 A920 EQ
2' - 0"
3' - 0" 2' - 0"
8' - 0"
+/-
11
11
SOILDED WORK - EAST WALL
5
15' - 11"
2' - 0" Z202
3 A920
18BC1
2' - 9"
1"
1/4" = 1'-0"
EQ
8' - 0"
8' - 0"
5' - 0"
8' - 0"
2' - 0"
2' - 0"
EQ
24BC1
4
2' - 5"
SOILDED WORK - SOUTH WALL
2 A920
16' - 1"
Z206
EQ
Consultants
EQ
2' - 0"
2 A920
1/4" = 1'-0"
30SC
6
11
8' - 0"
1/4" = 1'-0"
4
18BD4
3' - 5 3/4"
4' - 9 1/2"
4
3636W
5' - 0"
1/4" = 1'-0"
PREP AREA - EAST WALL
3
3636W
2' - 0"
PREP AREA - SOUTH WALL
1836W
8' - 0"
18BD4
4
3' - 0" D
6 A920
2
3036W
E
8' - 0"
2' - 6"
12 A920
11 A920
3636W
2' - 0"
8' - 0"
4' - 0"
18BC1
BREAK ROOM - NORTH WALL
4' - 11"
Z205
3 3/4"
10 A920
1
6
24BD4 24BD4
10' - 9 3/4"
3636W
4
3"
2 A920
11
11
11
11
11
11
11
11
11
Certification
11
I hereby certify that I have reviewed the Mayo Clinic Standard General Specifications prepared by Ronald B. Carlson, License Number 10850, that they are appropriate for the work except as amended in this plan, specification or report, and that I am a duly licensed Architect under the laws of the State of Minnesota.
11
5' - 0"
30BC1
4
3636W
3"
8' - 0"
30BC1
Z215
2436W
3 1/4"
7 A920
3' - 0"
2' - 10"
G309
E
3' - 0"
G311
6
2' - 2"
D
4
Z212
4
9' - 0"
G310
3 1/4"
3' - 7 1/2"
2' - 0"
3636W
5' - 0"
7 A920
2' - 0"
1' - 0"
3636W
3' - 6"
5' - 0"
3' - 0"
MCB3018 2436W
3' - 6"
1 A920
3' - 0"
3 3/4"
1 A920
3' - 0"
20 A920
17 A920
11
11
11
11
11
11
11
11
Signature
DAVID NORBACK
Registration Number
6' - 1 1/2"
14
CLEAN STORAGE - SOUTH WALL
15
1/4" = 1'-0"
CLEAN STORAGE - WEST WALL
16
1/4" = 1'-0"
1/4" = 1'-0"
SECRETARY - WEST WALL
17
EQ
5' - 6"
I hereby certify that this plan, specification or report was prepared by me or under my direct supervision and that I am a duly licensed Architect under the laws of the State of Minnesota.
1 A920
Signature
18
1/4" = 1'-0"
4' - 0"
224 42 SF 52127 SF SF SF
SECRETARY - NORTH WALL
19
1/4" = 1'-0"
1' - 0" 8' - 0"
2' - 0"
434 30BC1 SF 143 SF
ORTHO PREP - WEST WALL
20
1/4" = 1'-0"
Project For
30SC
1"
ORTHO PREP - NORTH WALL
ORTHO PREP - EAST WALL
21
1/4" = 1'-0"
1/4" = 1'-0"
Large Animal Surgery and Germ Free Facility
4' - 0"
2' - 0"
22
30SC
18BD4
2' - 0"
F407
PREP ROOM - WEST WALL
23
1/4" = 1'-0"
2' - 6 1/4"
2' - 6 1/4"
E
GB-42
GB-36
D
GB-42
CWT-1
B
B
2' - 10"
52 248 235SF SF SF 140 51 SF 62 SF156 65 116 109 107 SF 129 SF SF SF SF SF 2' - 6 1/4"
GB-36
GB-42
TYP
D
2' - 10"
6
D
3' - 0"
3' - 0"
1
E
GB-18
8' - 0"
8' - 0"
8' - 0"
2' - 0"
2' - 0" 2' - 0"
1"
17-4
F413
4
1
E G
Medical Sciences Building Fourth Floor
GB-18
GB-36
G
6
07.03.13
4 30BC1 18BD4 1' - 8"
4
11902
6' - 0"
2' - 0"
8' - 0"
O101
3' - 0"
16-7
O102
O113
1836W
F406
DAVID NORBCK
Date
1 A920
10' - 1"
J
CLEAN STORAGE - NORTH WALL
O133
11
11
4"
4"
4"
11
12
4' - 1 1/4"
8' - 0"
4' - 6"
M123
EQ
07.03.13
Registration Number
4' - 6"
8' - 0"
3' - 0" 8' - 0"
7' - 0"
7' - 0"
8' - 0"
8' - 0"
7' - 0"
M122
5' - 6"
1' - 0"
5' - 7"
8' - 0"
5' - 7"
1 A920
8' - 4"
1' - 0"
5' - 9 3/4"
Date
1/4" = 1'-0"
1 A920
2 A920
6' - 0"
5' - 9 3/4"
1/4" = 1'-0"
1' - 0"
2 A920
8"
5' - 0 3/4"
1/4" = 1'-0"
CORRIDOR - SOUTH WALL
13
3' - 0"
1 A920
LARGE OFFICE 1 - NORTH WALL
12
3' - 6"
1/4" = 1'-0"
8"
1 A920
LARGE OFFICE 1 - SOUTH WALL
11
6"
1/4" = 1'-0"
3' - 6 1/4" 8"
4' - 10 1/2"
1 A920
SURGICAL TECHS - EAST WALL
10
3' - 0"
1/4" = 1'-0"
SURGICAL TECHS - NORTH WALL
6"
9
9
OFFICE - SURGICAL TECH - EAST WALL
8
11902
B C.1
Project #7R120760
2' - 6 1/4"
10' - 1"
PREP ROOM - NORTH WALL
TOILET MEN - WEST ELEVATION
24
1/4" = 1'-0"
1/4" = 1'-0"
25
TOILET MEN - NORTH ELEVATION
26
1/4" = 1'-0"
TOILET MEN - EAST ELEVATION
27
1/4" = 1'-0"
TOILET MEN - SOUTH ELEVATION 1/4" = 1'-0"
28
TOILET WOMEN - WEST ELEVATION 1/4" = 1'-0"
12"D. PLAM SHELF 3' - 0"
48" H. FRP PANELS ON BOTH WALLS ABOVE MOP BASIN
2' - 6"
Project No.
6287.040.04
Drawn By
BCS
D
BASE
C.1
G
12
E
GB-42
D
4' - 6"
E
8' - 0"
GB-36
B
8"
G
GB-18
2' - 10"
B
SERVICE FAUCET, RE: PLUMBING SILICONE SEALANT @ TOP EDGES OF BASIN AND ABUTTING F.R.P.
3' - 0"
G
HOSE BRACKET
9"
G
GB-36
1' - 6"
E
4' - 0"
GB-42
6' - 0"
GB-18
Checked By
G
MOP RACK
10"
C.2
SILICONE SEALANT @ ALL EDGES OF FRP BOARD
24" X 30" MOP SERVICE BASIN
TOILET WOMEN - NORTH ELEVATION 1/4" = 1'-0"
30
TOILET WOMEN - EAST ELEVATION 1/4" = 1'-0"
31
TOILET WOMEN - SOUTH ELEVATION 1/4" = 1'-0"
07/03/13
NOTICE: The designs shown and described herein including all technical drawings, graphics, and models thereof, are proprietary and cannot be copied, duplicated or commercially exploited, in whole or in part, without express written permission of RSP Architects. These are available for limited review and evaluation by clients, consultants, contractors, government agencies, vendors and office personnel only in accordance with this Notice. © Copyright RSP Architects 2007. All rights reserved.
Revisions No.
29
JHA/MLK
Date
32
MOP BASIN ELEVATION 1/2" = 1'-0"
33
TOILET/CHANGE - NORTH ELEVATION 1/4" = 1'-0"
34
TOILET/CHANGE - EAST ELEVATION 1/4" = 1'-0"
35
Date
Description
TOILET/CHANGE - SOUTH ELEVATION 1/4" = 1'-0"
KEYNOTES - ELEVATIONS
GB-18
12
GB-42 GB-36
B
36
1 3 4 5 6 7 8 9 10 11 12
STANDARD STEEL COUNTERTOP SUPPORT WALL BRACKET (27x19) - SEE DETAIL 19/A920 ELECTRIC/ VOICE/ DATA RACEWAY - COORDINATE WITH ELECTRICAL PLASTIC LAMINATE FILLER. PLASTIC LAMINATE VENT CHASE - SEE DETAIL 9/A920 PLASTIC LAMINATE WALL CLEAT 1" PLASTIC LAMINATE END PANEL. PLASTIC LAMINATE PIPETE RACK - SEE DETAIL 16/A920 1" PLASTIC LAMINATE BACKER BOARD. GAS CYLINDER FURNITURE - SEE FURNITURE PLAN (I304) STANDARD LAB COAT HOOK STRIP MOUNTED AT 5'-0" A.F.F. UNLESS NOTED OTHERWISE SEE DETAIL 15/A920
TOILET/CHANGE - WEST ELEVATION 1/4" = 1'-0"
INTERIOR ELEVATIONS
A902 C:\Revit Projects\Med Sci 4 Central_jschmit.rvt 7/8/2013 11:23:01 AM
Please purchase PDF Split-Merge on www.verypdf.com to remove this watermark.
OFFICE 4-27 - WEST WALL 1/4" = 1'-0"
2
1/4" = 1'-0"
1/4" = 1'-0"
4
11
5
5' - 10"
OFFICE - TYPICAL - EAST WALL 1/4" = 1'-0"
11
6
OFFICE 4-23 - WEST WALL 1/4" = 1'-0"
11
7
11
OFFICE 4-23 - NORTH WALL 1/4" = 1'-0"
M1
5' - 0"
M1
2 A920
2' - 0"
2' - 0"
5' - 1 1/2"
2' - 0"
2' - 0" M1
OFFICE - TYPICAL - NORTH WALL 1/4" = 1'-0"
5' - 0"
4' - 8"
2 A920
5' - 0"
5' - 0"
2' - 0"
3
OFFICE 4-27 - EAST WALL
4' - 2"
11
11
11
OFFICE 4-27 - NORTH WALL
4' - 2"
5' - 0"
5' - 0"
11
11
M1
2 A920
2 A920
5' - 0"
5' - 0"
2' - 0"
2' - 0" 5' - 0"
M1
2 A920
5' - 0"
5' - 1 1/2"
5' - 10"
1
2 A920
2' - 0"
2 A920
2 A920
11
8
OFFICE 4-23 - EAST WALL
RSP Architects 320 South Broadway Ste. B 507.285.6569 Rochester, Minnesota 55904 612.677.7499 fax www.rsparch.com
Consultants
1/4" = 1'-0"
Certification
I hereby certify that I have reviewed the Mayo Clinic Standard General Specifications prepared by Ronald B. Carlson, License Number 10850, that they are appropriate for the work except as amended in this plan, specification or report, and that I am a duly licensed Architect under the laws of the State of Minnesota.
Signature
DAVID NORBACK
Registration Number Date
11902 07.03.13
I hereby certify that this plan, specification or report was prepared by me or under my direct supervision and that I am a duly licensed Architect under the laws of the State of Minnesota.
Signature
DAVID NORBCK
Registration Number Date
11902 07.03.13
Project For
Large Animal Surgery and Germ Free Facility Medical Sciences Building Fourth Floor Project #7R120760
Project No.
6287.040.04
Drawn By
BCS
Checked By
JHA/MLK
Date
07/03/13
NOTICE: The designs shown and described herein including all technical drawings, graphics, and models thereof, are proprietary and cannot be copied, duplicated or commercially exploited, in whole or in part, without express written permission of RSP Architects. These are available for limited review and evaluation by clients, consultants, contractors, government agencies, vendors and office personnel only in accordance with this Notice. Š Copyright RSP Architects 2007. All rights reserved.
Revisions No.
Date
Description
INTERIOR ELEVATIONS
A903 C:\Revit Projects\Med Sci 4 Central_jschmit.rvt 7/8/2013 11:23:02 AM
Please purchase PDF Split-Merge on www.verypdf.com to remove this watermark.
VARIES
VARIES
SEE ELEVATIONS 5' - 1 1/4"
SEE PLANS FOR COUNTERTOP SIZE AND TYPE
PLASTIC LAMINATE SINK CABINET
PLASTIC LAMINATE BASE CABINET
3'-0"
4 3/8"
NOTE: SEE ELEVATIONS FOR THE QUANTITY OF SHELVES, USE HEAVY DUTY UNISTRUT STANDARDS AND BRACKETS. SPACED AT 2'-6" OC MAX
NOTE: SEE ELEVATIONS FOR THE QUANTITY OF SHELVES, USE STANDARD KV STANDARDS AND BRACKETS. SPACED AT 2'-6" OC MAX
3"
1' - 7"
7"
3"
1' - 7"
1 5/8" X 1 5/8" UNISTRUT
RSP Architects 320 South Broadway Ste. B 507.285.6569 Rochester, Minnesota 55904 612.677.7499 fax www.rsparch.com
WIREMOLD G4000
VARIES
Consultants
TYPICAL STANDARD KV ADJUSTABLE SHELVING
2
3/4" = 1'-0"
5 1/8"
WIREMOLD G4000
TYPICAL HEAVY DUTY UNISTRUT ADJUSTABLE SHELVING
1
6"
VARIES
6"
3/4" PLASTIC LAMINATE BOOKEND - AS INDICATED IN ELEVATIONS (PLAM-1) SEE ELEVATION
SEE ELEVATION
1" PLASTIC LAMINATE BOOKEND (PLAM-1) AS INDICATED IN ELEVATIONS P4100 UNISTRUT CHANNEL HORIZONTAL
EQ
SEE PLANS FOR COUNTERTOP SIZE AND TYPE
STANDARD KV VERTICAL CHANNELS
3'-0"
11" TYP.
P4100 UNISTRUT CHANNELS VERTICAL
EQ
3/4" PLASTIC LAMINATE SHELVING ON STANDARD KV ADJUSTABLE BRACKETS - SEE ELVATION FOR QUANTITY
SEE ELEVATION
3'-0"
SEE ELEVATION
6"
1" PLASTIC LAMINATE SHELVING (PLAM-1) 1" PLASTIC LAMINATE SHELVING ON UNISTRUT ADJUSTABLE BRACKETS - SEE ELEVATIONS FOR QUANTITY
6"
3/4" PLASTIC LAMINATE SHELVING (PLAM-1)
SEE ELEVATIONS
6"
2' - 7"
VARIES
EQ
3'-0"
EQ
1' - 0" U.N.O.
2' - 7"
SEE ELEVATIONS
6"
P4100 UNISTRUT CHANNEL HORIZONTAL
5' - 1 1/4"
11" TYP.
1' - 0" U.N.O.
SEE ELEVATIONS
TYPICAL SINK CABINET SECTION
3
3/4" = 1'-0"
4
3/4" = 1'-0"
TYPICAL BASE CABINET SECTION
5
3/4" = 1'-0"
WIREMOLD POWER POLE DETAIL 3" = 1'-0"
Certification
I hereby certify that I have reviewed the Mayo Clinic Standard General Specifications prepared by Ronald B. Carlson, License Number 10850, that they are appropriate for the work except as amended in this plan, specification or report, and that I am a duly licensed Architect under the laws of the State of Minnesota.
1' - 0 5/8" P4100 UNISTRUT CHANNEL
6
1' - 7"
TYPICAL BASE CABINET SECTION W/ DRAWERS
7
3/4" = 1'-0"
UPPER CABINET - TWO ADJ. SHELVES W/UNISTRUT
2 1/2"
4"
7 1/8"
BACK PANEL WITH PLASTIC LAMINATE FACE
3/4"
2' - 10 1/2"
3/4"
2' - 4 1/2"
3"
BASE CABINET SECTION - BREAKROOM
10
1/2"
4 3/4"
3" X 3" LEG
HOOKS (TYP.)
SEE ELEVATIONS
SHELF BRACKET HOLES @ 32 MM O.C. (TYP.)
3"
2' - 6"
FRONT VIEW
6" TYP. PLAM MOUNTING BOARD (PLAM-1)
SIDE VIEW
3/4" = 1'-0"
CYLINDER SUPPORT DETAIL
14
3/4" = 1'-0"
SECTION AT SAND TABLE
15
3/4" = 1'-0"
TYPICAL LAB COAT HOOK
1" P-LAM (TYP.)
1" = 1'-0"
4"
13
1' - 0 1/2"
2' - 2 3/4"
BASE CABINET SECTION W/ DRAWERS BREAKROOM
CEILING LINE
Project #7R120760
3/4" PLASTIC LAMINATE SHELVING
2' - 6"
2' - 0"
2' - 2 5/8"
3"
SLIDE OUT PLASTIC LAMINATE SHELVES WITH HEAVY DUTY SHELF GUIDES
8 5/8"
3"
3' - 0"
1"
1" P-LAM PULL OUT WRITING BOARD
6" 2' - 6"
5'-0" A.F.F.
3"
2' - 6"
1' - 1"
1' - 0"
SECTION VIEW
WALL LINE
ALL EXTERIOR EXPOSED SURFACES AND EDGES ARE PLASTIC LAMINATE OVER 3/4" MDF INCLUDING FLUSH OVERLAY DOOR(S) ON CONCEALED HINGES TYPICAL
2' - 0"
FRONT VIEW
Project No.
3/4" = 1'-0"
Checked By
1' - 9"
1'-6"
17
C:\Revit Projects\Med Sci 4 Central_jschmit.rvt 7/8/2013 11:23:03 AM
Please purchase PDF Split-Merge on www.verypdf.com to remove this watermark.
18
P-LAM STORAGE CABINET SECTION (18" DEEP) 1" = 1'-0"
1" = 1'-0"
1"
11" 1/8" DRIP GROOVE
COUNTERTOP TYPE: E
COUNTERTOP TYPE: F
DIM. 2' - 4 1/2"
4" WIRE PULL
1' - 5" NOTE: G.C. TO PROVIDE BLOCKING IN STUD WALL AS REQUIRED
4 1/2" 1"
WHITE THERMOFUSED MELAMINE OVER 3/4" MDF INTERIORS W/ ADJUSTABLE SHELVES AND 1/4" THERMOFUSED MELAMINE BACK TYPICAL
1/8" DRIP GROOVE COUNTERTOP DESIGNATION COUNTERTOP TYPE - SEE ABOVE
1/8" DRIP GROOVE
C31-PL
INDICATES: FINISH ( SEE BELOW )
DIM TYPICAL FINISHES PL = PLASTIC LAMINATE SS = STAINLESS STEEL AR = ACID RESISTANT
TYPICAL LABORATORY COUNTERTOPS
20
UPPER CABINET - TWO ADJ. SHELVES 1" = 1'-0"
DIM. 2' - 4 1/2"
4 1/2"
11"
SEE ELEVATIONS
1/8" DRIP GROOVE
COUNTERTOP INSTALLATION CLEARANCES
19
1" 1"
ALL EXTERIOR EXPOSED SURFACES AND EDGES ARE PLASTIC LAMINATE OVER 3/4" MDF INCLUDING FLUSH OVERLAY DOOR(S) ON CONCEALED HINGES TYPICAL
6"
DETAIL OF COUNTER SUPPORT BRACKET
1"
2' - 1"
DIM.
1"
2' - 3"
EQ
1" = 1'-0"
1' - 6"
Description
COUNTERTOP TYPE: D
1"
7' - 4 1/2"
4" 1' - 11 1/2"
Date
2' - 1"
HATCHED AREA INDICATES MIN. A.D.A. TOE SPACE CLEARANCE
3"
PLAM BASE
No.
DIM.
1' - 0"
DEEP TOP DEEP TOP DEEP TOP DEEP TOP
8"
B
4"
NOTE: SUPPORTS TO BE SHOP PRIMED: PAINT TO MATCH WALLS AT TIME OF INSTALLATION
1/8" DRIP GROOVE
2"
5"
VARIES SEE ELEVATIONS
2' - 4 1/2"
PROVIDE FIRE TREATED 2" x 8" WOOD BLOCKING AS REQ'D. TO SUPPORT BRACKET
WHITE THERMOFUSED MELAMINE OVER 3/4" MDF INTERIORS W/ ADJUSTABLE SHELF AND 1/4" THERMOFUSED MELAMINE BACK TYPICAL
SECTION AT MICROWAVE CABINET WITH BASE CABINET DRAWER AND DOOR
1/8" DRIP GROOVE COUNTERTOP TYPE: C
"A" "B" 16" 12" FOR 18" - 21" 21" 15" FOR 22" - 26" 27" 19" FOR 29" - 32" 32" 22" FOR 33" - 36"
ADJUSTABLE PLASTIC LAMINATE SHELVING SEE ELEVATIONS FOR QUANTITY
2' - 0 1/2"
1"
1/4" DIA. MOUNTING HOLES FOR WALL FASTENER (TYPICAL)
STEEL SUPPORT BRACKET - PROVIDE BRACKETS AS SHOWN ON DRAWINGS AT 3'-0" O.C. MAX.
SHELF BRACKET HOLES @ 32 MM O.C.
Revisions
DIM.
2' - 0"
A
4" WIRE PULL
2 1/4"
DIM.
TYPICAL SUPPORT BRACKET
FIXED PLASTIC LAMINATE SHELF
COUNTERTOP TYPE: B
1/8" STEEL
9"
1 1/2"
ALL EXTERIOR EXPOSED VERTICAL SURFACES AND EDGES ARE PLASTIC LAMINATE OVER 3/4" MDF INCLUDING FLUSH OVERLAY DOOR(S) ON CONCEALED HINGES TYPICAL
COUNTERTOP TYPE: A
5"
1"
PLASTIC LAMINATE COUNTER TOP AND BACK SPLASH
4"
1' - 8"
© Copyright RSP Architects 2007. All rights reserved.
1/4" DIA. MOUNTING HOLES FOR CSK. FHWS. (TYPICAL)
PLASTIC LAMINATE CABINET DOOR PLASTIC LAMINATE OVER 1" MDF SHELF
2' - 10"
SEE SCHED. BELOW
EQ
1' - 6"
ELECTRICAL OUTLET, SEE ELECTRICAL
ADJUSTABLE PLASTIC LAMINATE SHELVING SEE ELEVATIONS FOR QUANTITY
3"
2 43/64"
FIRE TREATED WOOD BLOCKING ANCHORED BETWEEN STEEL STUD
07/03/13
NOTICE: The designs shown and described herein including all technical drawings, graphics, and models thereof, are proprietary and cannot be copied, duplicated or commercially exploited, in whole or in part, without express written permission of RSP Architects. These are available for limited review and evaluation by clients, consultants, contractors, government agencies, vendors and office personnel only in accordance with this Notice.
3"
4" WIRE PULL
3/4"
JHA/MLK
Date
WHITE THERMOFUSED MELAMINE OVER 3/4" MDF INTERIORS W/ ADJUSTABLE SHELVES AND 1/4" THERMOFUSED MELAMINE BACK TYPICAL
1"
JAS
PLASTIC LAMINATE PIPETTE RACK
SEE SCHED. BELOW
2' - 1"
6287.040.04
Drawn By
16
1' - 6"
Medical Sciences Building Fourth Floor
4' - 6"
SAND FILL
3" 3"
2' - 10"
12
1' - 7"
EQ
3/4" ADJUSTABLE PLASTIC LAMINATE SHELVING - SEE ELEVATIONS FOR QUANTITY (TYP.)
3" X 3" SIDE RAIL
3"
9"
Large Animal Surgery and Germ Free Facility
5' - 0 "
LIGHT WEIGHT CHAIN ATTACHED TO UNISTRUT WITH ATTACHMENT BOLTS. CHAIN SHALL BE CUT AT MID POINT AND CONNECTED TO EACH OTHER WITH SPRING CLIP.
07.03.13
3/4" = 1'-0"
3/4"
1"
PLASTIC LAMINATE BASE CABINET W/ DRAWERS
11902
ADA COMPLIANT SINK SECTION BREAKROOM
11
3/4" = 1'-0"
1" RIGID INSULATION
1' - 10 1/4"
1 1/4" UNISTRUT ATTACHED TO 2"X8" FIRE TREATED WOOD BLOCKING IN WALL WITH 3/8" X 3 1/2" THRU BOLTS AT 10" OC MAX
2' - 10 1/2"
SEE ELEVATIONS
CYLINDERS - BY OWNER
Registration Number
1' - 8"
1" MARBLE TOP SEE PLANS FOR COUNTERTOP SIZE AND TYPE
DAVID NORBCK
Project For
3" = 1'-0"
3/4"
I hereby certify that this plan, specification or report was prepared by me or under my direct supervision and that I am a duly licensed Architect under the laws of the State of Minnesota.
7' - 0"
VARIES - SEE FLOOR PLAN
07.03.13
Date
EQ
2' - 1"
11902
SCHEDULED BASE
2 1/2"
P-LAM VENT CHASE
9
1" = 1'-0"
Date
Signature
5"
UPPER CABINET - ONE ADJ. SHELF
8
1" = 1'-0"
WALL BLOCKING AS REQUIRED
REMOVABLE PLASTIC LAMINATE (PLAM-1) PANEL W/ EXPOSED SCREWS & GROMMETS
NOTE: G.C. TO PROVIDE BLOCKING IN STUD WALL AS REQUIRED
3/4"
SOAP DISPENSER PLASTIC LAMINATE BASE CABINET
DAVID NORBACK
Registration Number
2' - 10"
4" WIRE PULL
2' - 1"
PLASTIC LAMINATE COUNTER TOP ON 3/4" MDF WITH BACK SPLASH
CENTERLINE OF BENCH SEE MECH & ELEC FOR PIPING AND CONDUITS
Signature
1 1/2"
6"
ALL EXTERIOR EXPOSED SURFACES AND EDGES ARE PLASTIC LAMINATE OVER 3/4" MDF INCLUDING FLUSH OVERLAY DOOR(S) ON CONCEALED HINGES TYPICAL
NOTE: G.C. TO PROVIDE BLOCKING IN STUD WALL AS REQUIRED
VARIES
FIXED PLASTIC LAMINATE END PANELS (PLAM-1)
SEE ELEVATIONS
WHITE PLASTIC LAMINATE OVER 3/4" MDF INTERIORS W/ ADJUSTABLE SHELVES AND 1/4" BACK TYPICAL
SEE PLANS FOR COUNTERTOP SIZE AND TYPE
6"
SEE ELEVATIONS
1' - 0"
4" WIRE PULL
3"
BLACK THERMOFUSED MELAMINE OVER 3/4" MDF INTERIORS W/ ADJUSTABLE SHELF AND 1/4" THERMOFUSED MELAMINE BACK TYPICAL
SEE ELEVATIONS
3'-0"
PLASTIC LAMINATE BASE CABINET W/ DRAWERS
VARIES
SEE ELEVATIONS
SEE PLANS FOR COUNTERTOP SIZE AND TYPE
ADA COMPLIANT SINK AND FAUCET, REFER TO PLUMBING DRAWINGS
2' - 1"
ALL EXTERIOR EXPOSED SURFACES AND EDGES ARE PLASTIC LAMINATE OVER 3/4" MDF INCLUDING FLUSH OVERLAY DOOR(S) ON CONCEALED HINGES TYPICAL
1' - 0"
2' - 7"
LINE OF BACKSPLASH
NOT TO SCALE
MILLWORK DETAILS
A920
2' - 2"
2' - 2" 1 1/4" x 2" REEVE #80 TUBE WITH OUT SLOTS. FILLER @ EXPOSED END
VARIES - SEE ELEVATIONS
3"
8 3/4"
1/8" 1"
SECTION AT KNEE SPACE
1' - 7"
2" 2"
1 5/8"
3"
11"
6 1/2"
9"
1' - 10" 1 7/8" 1 5/8"
Consultants SEE ELEVATIONS FOR SPACING OF TUBES
9"
2"
5/8"
1 1/4" VERTICAL TUBE SUPPORTS
Certification
2"
1' - 10"
1' - 0" 2"
1 7/8" 1 5/8"
1' - 0"
1' - 8 1/2" 3/4"
2" FACE OF COUNTERTOP ABOVE
PLAN DETAIL AT ISLAND ABOVE COUNTERTOP
I hereby certify that I have reviewed the Mayo Clinic Standard General Specifications prepared by Ronald B. Carlson, License Number 10850, that they are appropriate for the work except as amended in this plan, specification or report, and that I am a duly licensed Architect under the laws of the State of Minnesota.
Signature
PLASTIC LAMINATE END PANELS
PLASTIC LAMINATE BASE CABINET
4
3/4" = 1'-0"
Date
VERTICAL TUBE DETAIL AT ISLAND
07.03.13
Signature
PLASTIC LAMINATE (PLAM-5) COUNTERTOP
DAVID NORBCK
Registration Number Date
9 A921
11902 07.03.13
Project For
WOOD EDGE (WD-1) ALL EXPOSED SIDES MDF VENEER (PLAM-5) SHELF
MDF VENEER (PLAM-5) PANEL BEYOND
MDF VENEER (PLAM-5) PANEL BEYOND
MDF VENEERED BACK PANEL COORDINATE OPENINGS WITH A.V.
MDF VENEERED BACK PANEL COORDINATE OPENINGS WITH A.V.
MDF VENEER (PLAM-5) BASE
MDF VENEER (PLAM-5) BASE
WOOD EDGE (WD-1) ALL EXPOSED SIDES
1"
1" PLASTIC LAMINATE COUNTERTOP (PLAM-5)
Large Animal Surgery and Germ Free Facility
3/4" PLASTIC LAMINATE INSIDE CABINET FACING
4"
MDF VENEER BASE (PLAM-5)
11902
I hereby certify that this plan, specification or report was prepared by me or under my direct supervision and that I am a duly licensed Architect under the laws of the State of Minnesota.
6" = 1'-0"
2' - 0"
5
DAVID NORBACK
Registration Number
PLAN DETAIL AT ISLAND BELOW COUNTERTOP
3
3/4" = 1'-0"
MDF VENEER (PLAM-5) SHELF
3' - 5"
5"
3/4"
2' - 0 1/2"
FACE OF COUNTERTOP
WOOD EDGE (WD-1) ALL EXPOSED SIDES
MDF VENEER (PLAM-1) BASE
4"
3/4"
1 1/4"
9 A921
MDF VENEER (PLAM-5) PHONE POCKET HOLDER - ATTACH TO CABINET WITH (4) MOD-EEZ CLIPS
6"
1' - 2"
5/8"
3/4" PLYWOOD
6"
6"
1" 3/4" 3/4"
3' - 5"
2' - 3"
5"
MDF VENEER PHONE POCKET HOLDER (PLAM-1)
3/4"
3/4" PLYWOOD
PLAM COUNTERTOP (PLAM-5)
2' - 1"
WIRELESS KEYBOARD & MOUSE SHELF
3/4"
DVD/VCR
DASHED LINES INDICATE FACE OF CABINET BELOW
PLASTIC LAMINATE (PLAM-5) COUNTERTOP
4' - 3 1/2"
4 A921
DASHED LINES INDICATE REAGENT SHELVING ABOVE
2 3/4"
CABLE NOOK
"LIFT-OFF" LOCKABLE RACK MDF VENEER (PLAM-1) DOOR
4' - 9"
2' - 3 1/2" 2"
4' - 9"
1 5/8"
2
PLAM COUNTERTOP (PLAM-1)
VARIES SEE ELEVATIONS 1 5/8"
PLASTIC LAMINATE END PANEL
3/4" = 1'-0"
8 A921
RSP Architects 320 South Broadway Ste. B 507.285.6569 Rochester, Minnesota 55904 612.677.7499 fax www.rsparch.com
1 1/4" x 2" VERTICAL TUBE SUPPORTS SEE ELEVATIONS FOR SPACING
1 1/2" 1/8" 1"
TYPICAL PENINSULA/ ISLAND SECTION DETAILS
7 A921
1 5/8" UNISTRUT FRAMING
2"
VARIES
3'-0"
BOLT TO CONC. W/ EXPAN. BOLTS AND UNISTRUT ANGLES
9"
1
1' - 7"
2" 2"
BOLT REEVE #80 TUBE TO UNISTRUT
1 5/8" FRAMING
4" 1 5/8"
5/8"
1 1/4" x 2" VERTICAL TUBE SUPPORTS
PLAM CHASE AS NOTED ON PLAN
4' - 9"
PLASTIC LAMINATE PANELS
1 1/2" 1 5/8"
5/8" 1 5/8"
FACE OF PLASTIC LAMINATE PANEL
CENTERLINE OF VERTICAL TUBE SUPPORT
2' - 3 1/2"
BOLT UNISTRUT CONNECTIONS SPRING LOADED NUTS, TYP.
SEE ELEVATIONS
3' - 0"
VARIES
SCALE: 3" = 1'-0"
2"
WIREMOLD
1 5/8" UNISTRUT FRAMING CHANNEL
4' - 9"
SECTION AT CABINETS
4'-1"
SEAL COUNTERTOP AROUND TUBE SUPPORTS
WIREMOLD
3/4"
CENTERLINE OF VERTICAL TUBE SUPPORT
SPACING OF VERTICAL TUBE SUPPORTS
5/8" 5/8"
SEE ELEVATIONS
BACK PLATE: 1/8" x 2" CLEAR PLEXIGLAS, MECHANICALLY FASTEN TO BACK OF SHELF ( TYP. )
VARIES
BACK PLATE: 1/8" x 2" CLEAR PLEXIGLAS, MECHANICALLY FASTEN TO BACK OF SHELF ( TYP. )
1" P. LAM. SHELF ON REEVE #81-12 SHELF BRACKET AT EACH SHELF
SEE ELEVATIONS FOR
4"
FACE OF PLAM PANEL BELOW
SEE ELEVATIONS
SCALE: 3" = 1'-0"
1 1/4" x 2" REEVE #80 TUBE W/ SLOTS STARTING 38" A.F.F. SEE ELEVATIONS FOR SPACING
SEE ELEVATIONS
4' - 1"
VARIES
VARIES - SEE ELEVATIONS
2 1/2"
4' - 5"
ALL OTHER NOTES SIMILAR
AV CABINET FRONT ELEVATION
6
1" = 1'-0"
ACCESSORY MOUNTING DIAGRAM FOR MINIMUM ADA GUIDELINES
AV CABINET SIDE ELEVATION
AV CABINET SECTION A
7
1" = 1'-0"
8
1" = 1'-0"
AV CABINET SECTION B
9
1" = 1'-0"
Medical Sciences Building Fourth Floor
AV CABINET COUNTER DETAIL 3" = 1'-0"
INFORMATION HERE IS FOR REFERENCE ONLY. ANY DIMENSIONS, NOTES, TEXT OR FINISHES ON ARCHITECTURAL PLANS OVERRIDES THE INFORMATION FOUND ON THIS SHEET.
SCALE: 1/2" = 1'-0"
Project #7R120760
NOTE: REFER TO TOILET PLAN LAYOUT FOR GRAB BAR DIMENSIONS AND LAYOUT
42" 3' -MIN. 6"
TO START BUTTON
(3'-6" AT COUNTER)
JHA/MLK
Date
3' - 4"
36" - 48"
1' - 6 1/8"
JAS
Checked By
4'-0" MAX. TO DISP. SLOT
TO SPOUT
TO SHELF
30" - 33"
33" - 36"
6287.040.04
Drawn By
7" - 9"
1'-5"
17" - 19"
1' - 0"
40" - 44"
7" - 9"
Project No.
30" - 33"
MIN.
1' - 6"
39" - 41"
39" - 41"
MAX.
KEEP WASTE RECEPTACLE IN LINE WITH TOILET TISSUE DISPENSER
15" MIN.
1' - 0"
07/03/13
NOTICE: The designs shown and described herein including all technical drawings, graphics, and models thereof, are proprietary and cannot be copied, duplicated or commercially exploited, in whole or in part, without express written permission of RSP Architects. These are available for limited review and evaluation by clients, consultants, contractors, government agencies, vendors and office personnel only in accordance with this Notice. © Copyright RSP Architects 2007. All rights reserved.
Revisions
TOILET TISSUE DISPENSER
D
SANITARY PRODUCT DISPOSAL
E
F
UTILITY SHELF
G1
SOAP DISPENSER
PAPER TOWEL DISPENSER
H
No.
HAND DRYER
SANITARY PRODUCT DISPENSER
C:\Revit Projects\Med Sci 4 Central_jschmit.rvt 7/8/2013 11:23:05 AM
K
FRAMED MIRROR
Please purchase PDF Split-Merge on www.verypdf.com to remove this watermark.
K1
FRAMED MIRROR
L
UNFRAMED MIRROR
M
COAT HOOK
N
SHOWER SEAT
O
BABY CHANGING STATION
48" MAX.
54" MAX.
LATC H M EC H AN I SM
18" MAX.
2' - 10"
TO TRAY
60" TYP.
ACCESSIBLE
48" MAX.
35" MAX AT FLOOR
MEASURED TO BOTTOM OF VIEWING SURFACE
40" MAX AT LAVATORY
1' - 6"
MEASURED TO BOTTOM OF VIEWING SURFACE
Description
CL
3'-4"
3'-4" MAX AT LAVATORY 2'-11" MAX AT FLOOR
TO HIGHEST OPERATING MECHANISM
4' - 0" MAX.
J
MEASURED TO BOTTOM OF VIEWING SURFACE
Date
4' - 0"
C
GRAB BAR HEIGHT
48" MAX.
B
TOILET SEAT HEIGHT
5' - 0"
A
CASEWORK DETAILS AND ACCESSORY MOUNTING DIAGRAM P
EMERGENCY NURSE CALL
Q
SHARPS CONTAINER
R
GLOVE DISPENSER
A921