Large Animal Surgery and Germ Free Facility

Page 1

DOCUMENT PACKAGE

LARGE ANIMAL SURGERY AND GERM FREE FACILITY MEDICAL SCIENCES BUILDING - FOURTH LEVEL ROCHESTER, MN

MAYO PROJECT: #7R120760 ISSUED:

07/03/13

PACKAGE:

CONSTRUCTION DOCUMENTS

RSP Architects 320 South Broadway Ste. B 507.285.6569 Rochester, Minnesota 55904 612.677.7499 fax www.rsparch.com

Consultants

Certification

DRAWING ABBREVIATIONS

ABV. A.F.F. ACC. ACC. PML. ACFLR. ACOUS. A.C.T. A.C.P. ADD. ADD'N(L) ADH. ADJ. A/C ALT. ALUM. A.D.A. ANCH. A.B. ANOD. & "L" ANTQ. APT. APPVD. ARCH.

ABOVE ABOVE FINISH FLOOR ACCESS or ACCESSARY (IES) ACCESS PANEL ACCESSIBLE FLOORING ACOUSTICAL ACOUSTICAL CEILING TILE ACOUSTICAL WALL PANEL ADDENDUM ADDITION(AL) ADHESIVE ADJACENT AIR CONDITIONING ALTERNATE ALUMINUM AMERICAN'S WITH DISABILITY ACT

ART. ATT. AUTO. AVG.

ANCHOR(AGE) ANCHOR BOLT ANODIZED AND ANGLE ANTIQUE APARTMENT APPROVED ARCHITECT OR ARCHITECTURAL ARCHITECTURAL WOODWORK ARTWORK ATTACH(ED) (MENT) AUTOMATIC AVERAGE

BQ. B. BSMT. BM. BRG. B.MK. BTWN. BEV. BLK. BLKG. BD. BT. B.S. BOT. BRKT. BRK. BRNZ. BLDG. B.U.R. B.S. B.BD.

BANQUETTE BASE MATERIAL BASEMENT BEAM BEARING BENCH MARK BETWEEN BEVELED BLOCK BLOCKING BOARD BOLT OR BOLTS BOTH SIDES BOTTOM BRACKET BRICK BRONZE BUILDING BUILT UP ROOFING BUILDING STANDARD BULLETIN BOARD

CAB. CPT. CSWRK. C.I. C.I.P. C.B. CALK. CLG. CEM. CTR. C.L. C.T. C.BD. CH. CR. CIRC.

CABINET CARPET CASEWORK CAST IRON CAST IN PLACE CATCH BASIN CAULKING CEILING CEMENT CENTER CENTER LINE CERAMIC TILE CHALK BOARD CHAIR CHROMIUM, CHROME CIRCLE, CIRCULAR CIRCUMFERENCE CLEANOUT CLEAR CLEAR OPENING CLOSET CLOSURE COLD WATER COLUMN COMPOSITE COMPRESSIBLE CONCRETE CONCRETE MASONRY UNIT CONFERENCE CONNECT OR CONNECTION CONSTRUCTION CONTINUED CONTINUOUS CONTRACTOR CONTRACT CONTROL JOINT JOINT CORNER CORNER GUARD CORRIDOR CORRUGATED COUNTER COUNTERSUNK CREDENZA

AWDWK.

C.O. CLR. CLR.OPG. CLO. CLS. C.W. COL. COMP. COMPR. CONC. CMU. CONF. CONNX. CONST. CONT'D. CONT. CONTR. C.J. COR. C.G. CORR. CORRUG. CTR. CSK. CRED.

SHEET INDEX DRAWINGS

DK. DEC. DEM. DMT. DEPT. DET. DIAG. DIA. DIM. DISP. DISPOS. DIST. DO. DIV. DR. D.O. DBL. D.A. DN. D.S. DRAP. DWR. DW. DWG. D.F. D.S.P. D.W. D.X.

EA. E.F. E.W. E. ELAST. ELEC. E.O. E.P. E.W.C. ELEV. ELEVR. EMER. ENCL. E. to E. ENGR. ENTR. ENVL. EQ. EQUIP. EQUIV. EXCAV. EXH. EXIST. EXPAN. EXP. BT. E.J. EXPOS. EXT. EX.

F. FABR. F.O.C. F.O.F. F.O.M. F.O.S. F.O.W. F-F F.M. FAS. FIN. F.F. F.A. F.E. F.E.C. F.H.C. F.H.R. F.P. FRT. FIX. FIXT. FLASH. F.H. F.H.S. FLEX. FLR. F.D. F. MTD. FLUOR. FL. FT. FTG. FDN. FRM. FRMG. F.S. FURN. F.B.O. FUR. FURR. FUT.

DARK DECORATIVE DEMOLITION DEMOUNTABLE DEPARTMENT DETAIL DIAGONAL DIAMETER DIMENSION DISPENSER DISPOSAL or DISPOSER DISTANCE DITTO DIVISION DOOR DOOR OPENING DOUBLE DOUBLE-ACTING DOWN DOWNSPOUT DRAPERY DRAWER DRYWALL DRAIN DRINKING FOUNTAIN DRY STANDPIPE DRYWALL DUPLEX

GA. GALV. G.I. GASK. GA. GEN. GL. G.B. GRD. GRN. GRT. GRV. GRND. GFCI. GT. GYP. GYP. BD.

HVY. HDF. HT. H.P. H.C. H. GRN. HORIZ. H.B. H.W. HR.

HANDRAIL HARDBOARD HARDWARE HARDWOOD HEAD HEATING HEATING, VENTILATING AND AIR CONDITIONING HEAVY HIGH DENSITY FIBERBOARD HEIGHT HIGH POINT HOLLOW CORE HONED GRANITE HORIZONTAL HOSE BIBB HOT WATER HOUR

I.C. INCAN. INCL. INFO. I.D. INSUL. INT. INTM. INV. I.O.C.

IN CONTRACT INCANDESCENT INCLUDE(D)(ING) INFORMATION INSIDE DIAMETER INSULATION INTERIOR INTERMEDIATE INVERT ITEM OF CHARGE

JAN. JAN. CLO. JNT. JTFILL JST. J.B.

JANITOR JANITOR CLOSET JOINT JOINT FILLER JOIST JUNCTION BOX BOX

K.P. KIT. K.O.

KICK PLATE KITCHEN KNOCKOUT

HNDRL. HDBD. HDWR. HDWD. HD. HTG. HVAC

EACH EACH FACE EACH WAY EAST ELASTIC ELECTRIC ELECTRIC OUTLET ELECTRIC PANEL ELECTRIC WATER COOLER ELEVATION ELEVATOR EMERGENCY ENCLOSURE END TO END ENGINEER ENTRANCE ENVELOPE EQUAL EQUIPMENT EQUIVALENT EXCAVATED or EXCAVATION EXHAUST EXISTING EXPANSION EXPANSION BOLT EXPANSION JOINT EXPOSED EXTERIOR EXISTING

FABRIC FABRICATE FACE OF CONCRETE FACE OF FINISH FACE OF MASONRY FACE OF STUD FACE OF WALL FACE TO FACE FACTORY MUTUAL FASTEN, FASTENER FINISH(ED) FINISH FLOOR FIRE ALARM FIRE EXTINGUISHER FIRE EXTINGUISHER CABINET FIRE HOSE CABINET FIRE HOSE RACK FIREPROOFING FORE FIRE RETARDANT FIXED FIXTURE FLASHING FLAT HEAD FLAT HEAD SCREW FLEXIBLE FLOOR FLOOR DRAIN FLOOR MOUNTED FLUORESCENT FLUSH FOOT OR FEET FOOTING FOUNDATION FRAME FRAMING FULL SIZE(SCALE) FURNITURE FURNISHED BY OTHERS FURRED FURRING FUTURE

GAGE, GAUGE GALVANIZED GALVANIZED IRON (STEEL) GASKET GAUGE GENERAL GLASS OR GLAZED GRAB BAR GRADE GRANITE GRATE, GRATING GRAVEL GROUND GROUND FAULT CIRCUIT INTERPRETER GROUT GYPSUM GYPSUM BOARD

LAB. LAM. LG. LAT. LAV. L.H. L.H.R. L. LT. LTWT. LIN. LTL. L.L. LKR. LONG'L. LOUV. L.P. LB. MACH. MAINT. MGR. MFGR. MRB. MAS. M.O. MATL. MAX. MECH. M.C. MED. MEMB. MET. M.L. MEZZ. MLWK. MIN. MIR. MISC. MTD. MUL.

LABORATORY LAMINATE LARGE LATERAL LAVATORY LEFT HAND LEFT HAND REVERS LENGTH LIGHT LIGHT WEIGHT LINEAR or LINOLEUM LINTEL LIVE LOAD LOCKER LONGITUDINAL LOUVER(S) LOW POINT POUND MACHINE MAINTENANCE MANAGER MANUFACTURE(ER) MARBLE MASONRY MASONRY OPENING MATERIAL MAXIMUM MECHANICAL MEDICINE CABINET MEDIUM MEMBRANE METAL METAL METAL LATH MEZZANINE MILLWORK MINIMUM MIRROR MISCELLANEOUS MOUNTED MULLION

NAT. NEG. NOM. N. N.I.C. N.T.S. NO.

NATURAL NEGATIVE NORMAL NORTH NOT IN CONTRACT NOT TO SCALE NUMBER

OBSC. OFF. OPNG. OPP. O.H. ORIG. ORN. OZ. O.D. OTOO OVHD. O.HD. O.C.

OBSCURE OFFICE OPENING OPPOSITE OPPOSITE HAND ORIGINAL ORNAMENTAL OUNCE OUTSIDE DIAMETER OUT TO OUT OVERHEAD OVERHEAD DOOR ON CENTER

P. PTD. PR. PNL. P.T.D. P.T.R. PART. BD. PTN. PATT. PAV. P.H. PERM. PC. PERP. PLAS. P.LAM. PL. PL.GL. PLBG.

PAINT PAINTED PAIR PANEL PAPER TOWEL DISPENSER PAPER TOWEL RECEPTACLE PARTICLE BOARD PARTITION PATTERN(ED) PAVING OR PAVEMENT PENTHOUSE PERMANENT PIECE PERPENDICULAR PLASTER PLASTIC LAMINATE PLATE PLATE GLASS PLUMBING

PLYWD. PT. POL. PVC. PORT. PSF. PREFAB. PROD. PROJ. PROP. P.L. PLAM

PLYWOOD POINT POLISH POLYVINYL CHLORIDE PORTABLE POUNDS PER SQUARE FOOT PREFABRICATED PRODUCTION, PRODUCT PROJECT PROPERTY PROPERTY LINE PLASTIC LAMINATE

QUAL. QUAN. Q.T.

QUALITY QUANTITY QUARRY TILE

RAD. RECEP. REF. RE: REFL. REFR. REINF. REBAR. REM. REMV. REQD. RESIL. R.B. R/A REV. R.H. R.H.R. R. R.D. RFG. RM. R.O. RND.

RADIUS RECEPTACLE REFERENCE REFER TO REFLECTED REFRIGERATOR REINFORCED REINFORCED BAR REMAINDER REMOVE REQUIRED RESILENT RESILENT BASE RETURN AIR REVISION RIGHT HAND RIGHT HAND REVERSE RISER ROOF DRAIN ROOFING ROOM ROUGH OPENING ROUND

SAN. S.N.D. SC. SCHED. SCHEM. SEAL. SECT. SEL. SEP. SERV. SVSNK SHT. SH. SHWR. SIM. SNK. SKYLT. SLDR. SM. S.D. S.C. S. SPKR. SPEC'L. SPECS. SPL. SQ. SF. SQ. IN. STAG. S.S. STD. STA. STL. ST. STOR. STFNT. STRUCT. SUP. SUSP. SYMM. SYST.

SANITARY SANITARY NAPKIN DISPENSER SCALE SCHEDULE SCHEMATIC SEALANT SECTION SELECT SEPARATE SERVICE SERVICE SINK SHEET SHELF or SHELVING SHOWER SIMILAR SINK SKYLIGHT SLIDING DOOR SMALL SOAP DISPENSER SOLID CORE or SEALED CONCRETE SOUTH SPEAKER SPECIAL SPECIFICATIONS SPLASH SQUARE SQUARE FEET SQUARE INCHES STAGGERED STAINLESS STEEL STANDARD STATION STEEL STONE STORAGE STOREFRONT STRUCTURAL SUPPLY SUPPORT SUSPEND(ED) SYMMETRICAL SYSTEM

T.BD. TAN. TECH. TEL. T.V. TEMPD. TEMP. TRZ. THK. THRESH. T.PAV. T.P.H. TOL. T&G T&B T.O.C. T.C. T.O.P. T.O.S. T.O.W. T.B. T.D. TR. T. TYP.

TACKBOARD TANGENT TECHNICAL TELEPHONE TELEVISION TEMPERED TEMPORARY TERRAZZO THICK(NESS) THRESHOLD TILEPAVERS TOILET PAPER HOLDER TOLERANCE TONGUE AND GROOVE TOP AND BOTTOM TOP OF CONCRETE TOP OF CURB TOP OF PAVEMENT TOP OF STEEL TOP OF WALL TOWEL BAR TOWEL DISPENSER TRANSFORM TREAD TYPICAL

WSCT. W.H. WC. W.H. W.R. W.P. W.S. WT. WLD. W.W.M. W. W.S.P. W.F. WDW. WDWALL W.GL. W/ W/IN W/O WD. W.B. W.PT. W.W.F.

WAINSCOT WALL HUNG WATER CLOSET WATER HEATER WATER RESISTANT WATERPROOF WEATHERSTRIPPING WEIGHT WELDED WELDED WIRE MESH WEST WET STANDPIPE WIDE FLANGE (STEEL) WINDOW WINDOW WALL WIRE GLASS WITH WITHIN WITHOUT WOOD WOOD BASE WORKING POINT WOVEN WIRE FABRIC

X

TIMES OR BY (AS IN 2X4)

YD.

YARD

& @ c L o

AND AT CENTERLINE DIAMETER FEET INCHES (OR DITTO) NUMBER ("NUMBER 5") PER ("POUNDS/FOOT") PERPENDICULAR POUNDS ("5 POUNDS")

' " #5 _ 5#

OWNER REPRESENTATIVE

MECH/ELEC ENGINEERS

MAYO FOUNDATION FACILITIES PROJECT SERVICES 200 FIRST STREET SW ROCHESTER, MN 55905

MEP ASSOCIATES, LLC 2900 43RD ST NW STE 100 ROCHESTER, MN 55901 PHONE: 507/281-1632 FAX: 507/281-6328

CONSTRUCTION MANAGER:

PROJECT MANAGER:

MIKE CRAVEN PHONE: 507/266-8548 EMAIL: CRAVEN.MICHAEL@MAYO.EDU

MECHANICAL CONTACT:

PHIL PLONKA PHONE: 507/284-8444 EMAIL: PLONKA.PHIL@MAYO.EDU

ELECTRICAL CONTACT:

ISSUE KEY: 1 ISSUED (WITH SIGNATURE) 2 REVISED AND RE-ISSUED (WITH SIGNATURE) 3 NOT FOR CONSTRUCTION - REFERENCE ONLY 4 RE-ISSUED FROM A PRIOR BID PACK - NO REVISIONS

LUKE JOHNSON PHONE: 507/281-1632 EMAIL: LUKEJ@MEPASSOCIATES.COM KERRY HAYDEN PHONE: 507/281-1632 EMAIL: KERRYH@MEPASSOCIATES.COM SHEET NO. NAME G000 COVER SHEET G104 FOURTH LEVEL FIRE AND LIFE SAFETY PLAN

ARCHITECT RSP ARCHITECTS, LTD. 320 SOUTH BROADWAY STE. B ROCHESTER, MN 55904 PHONE: 507/285-6569 FAX: 612/677-7499 PROJECT MANAGER:

TIM MILLER PHONE:507/292-8661 EMAIL: TIM.MILLER@RSPARCH.COM

VAR. VNR. V.I.F. VERT. VEST. VIN. V.B. V.C.T. V. VOL.

D104A D104B D204A D204B

PARTIAL FOURTH LEVEL DEMOLITION PLAN - AREA A PARTIAL FOURTH LEVEL DEMOLITION PLAN - AREA B PARTIAL FOURTH LEVEL DEMOLITION EQUIPMENT PLAN - AREA A PARTIAL FOURTH LEVEL DEMOLITION EQUIPMENT PLAN - AREA B

1 1 1 1

A104A A104B A204 A301

1 1 1 1

A801 A801A A801B A901 A902 A903 A920 A921

PARTIAL FOURTH LEVEL FLOOR PLAN - AREA A PARTIAL FOURTH LEVEL FLOOR PLAN - AREA B FOURTH LEVEL REFLECTED CEILING PLAN DOOR SCHEDULE, DETAILS, PARTITION TYPE INDICATOR, AND INTERIOR DETAILS EQUIPMENT SCHEDULE PARTIAL FOURTH LEVEL EQUIPMENT PLAN - AREA A PARTIAL FOURTH LEVEL EQUIPMENT PLAN - AREA B INTERIOR ELEVATIONS INTERIOR ELEVATIONS INTERIOR ELEVATIONS MILLWORK DETAILS CASEWORK DETAILS AND ACCESSORY MOUNTING DIAGRAM

I104 I304

FOURTH LEVEL FINISH PLAN AND SCHEDULE FOURTH LEVEL FURNITURE PLAN AND SCHEDULE

1 1

P001

PLUMBING SYMBOLS ABBREVIATIONS, GENERAL NOTES, DETAILS, AND SCHEDULES PARTIAL FOURTH LEVEL DEMOLITION PLUMBING PLAN AREA A PARTIAL FOURTH LEVEL DEMOLITION PLUMBING PLAN AREA B PARTIAL FOURTH LEVEL DEMOLITION PROCESS PIPING AND FIRE PROTECTION PLAN AREA A PARTIAL FOURTH LEVEL DEMOLITION PROCESS PIPING AND FIRE PROTECTION PLAN AREA B PARTIAL FOURTH LEVEL PLUMBING PLAN AREA A PARTIAL FOURTH LEVEL PLUMBING PLAN AREA B PARTIAL FOURTH LEVEL PROCESS PIPING AND FIRE PROTECTION PLAN AREA A PARTIAL FOURTH LEVEL PROCESS PIPING AND FIRE PROTECTION PLAN AREA B

1

PD104A PD104B PD204A PD204B

GENERAL NOTES 1. ALL CONTRACTORS ARE RESPONSIBLE TO REVIEW ALL CONSTRUCTION DOCUMENTS AND ARE RESPONSIBLE FOR INFORMATION ON ALL CONSTRUCTION DOCUMENTS.

P104A P104B P204A P204B

2. ALL CONTRACTORS AND SUBCONTRACTORS TO COMPLY WITH MAYO CAMPUS STANDARD SPECIFICATIONS AND STANDARD PROCEDURES. 3. THE AVAILABILITY OF ALL MATERIALS DESIGNATED ON PLANS TO MATCH EXISTING SHALL BE VERIFIED BY CONTRACTORS AND SUBCONTRACTORS PRIOR TO ESTIMATE SUBMITTALS. CONTRACTOR TO NOTIFY OWNER IF MATCHING MATERIALS ARE NOT AVAILABLE. ANY SUBSTITUTIONS TO BE REVIEWED AND APPROVED.

UNDERWRITERS LABORATORY UNDERCUT UNFINISHED UNLESS NOTED OTHERWISE URINAL UTILITY

5. CONTRACTORS TO PROVIDE TEMPORARY PARTITIONS AND DUST CONTROL AT ALL LOCATIONS WHERE WORK OCCURS IN CORRIDORS AND/OR CANNOT BE CONTAINED WITHIN ROOMS. 6. REMOVAL OF WALLS AND PARTITIONS TO INCLUDE ALL MECHANICAL AND ELECTRICAL ITEMS. DEMOLITION OF THESE ITEMS SHALL EXTEND BACK TO MAIN DISTRIBUTION POINTS UNLESS NOTED OTHERWISE. 7. THE GENERAL CONTRACTOR SHALL PROVIDE MAJOR DAILY CLEAN UP OF THE CONSTRUCTION SITE. ALL OTHER CONTRACTORS OR SUBCONTRACTORS SHALL CLEAN UP THEIR INDIVIDUAL TRASH AND DISPOSE OF IT. MAJOR SHIPPING CONTAINERS AND DEMOLITION ITEMS SHALL BE THE RESPONSIBILITY OF INDIVIDUAL CONTRACTORS OR SUBCONTRACTORS TO REMOVE DAILY.

VARIABLE VENEER VERIFY IN FIELD VERTICAL VESTIBULE VINYL SHEET GOODS VINYL BASE VINYL COMPOSITION TILE VINYL WALL COVERING VOLUME

1 1

Signature

DAVID NORBACK

Registration Number

11902

Date

07.03.13

I hereby certify that this plan, specification or report was prepared by me or under my direct supervision and that I am a duly licensed Architect under the laws of the State of Minnesota.

Signature

DAVID NORBCK

Registration Number

11902

Date

07.03.13

Project For

4. ALL CUTTING AND PATCHING SHALL BE PERFORMED BY THE GENERAL CONTRACTOR. GENERAL CONTRACTOR SHALL INCLUDE COST OF ALL REQUIRED CUTTING AND PATCHING FOR ALL TRADES IN THEIR ESTIMATE. U.L. U.C. UNFIN. U.N.O. UR. UTIL.

ISSUES 07/03/13 CONSTRUCTION DOCUMENTS

Note: Not all abbreviations listed below are necessarily used in the drawings; refer elsewhere for abbreviations related to product or material codes.

PROJECT TEAM

I hereby certify that I have reviewed the Mayo Clinic Standard General Specifications prepared by Ronald B. Carlson, License Number 10850, that they are appropriate for the work except as amended in this plan, specification or report, and that I am a duly licensed Architect under the laws of the State of Minnesota.

8. AT CONCLUSION OF PROJECT, ALL CONTRACTORS SHALL REDLINE THE CONSTRUCTION MANAGEMENT OFFICE SET FOR OWNER'S RECORDS SHOWING ALL DEVIATIONS FROM THE CONSTRUCTION DOCUMENTS. 9. FLAME SPREAD CLASSIFICATION OF INSTALLED FINISH MATERIALS SHALL CONFORM TO 2007 MINNESOTA BUILDING CODE (2006 INTERNATIONAL BUILDING CODE) CHAPTER 8. 10. ALL WORK SHALL CONFORM TO THE LATEST EDITION OF THE U.S. GYPSUM PRODUCTS AND SYSTEMS SPECIFICATION BULLETIN OR NATIONAL GYPSUM COMPANY'S LATEST SPECIFICATIONS EXCEPT AS NOTED. ALL GYPSUM BOARD TO BE FIRE RESISTIVE UNLESS NOTED OTHERWISE. 11. ALL WOOD BLOCKING AND CONCEALED LUMBER TO BE FIRE RETARDANT TREATED. 12. ALL HOLES IN FLOORS OR WALLS AS A RESULT OF DEMOLITION SHOULD BE FILLED AND SEALED TO MAINTAIN EXISTING FIRE AND SMOKE RATING OF FLOOR OR WALL SYSTEM ACCORDING TO MAYO STANDARD SPECIFICATION SECTION 07840. 13. IF ASBESTOS OR QUESTIONABLE MATERIAL IS ENCOUNTERED, CONTACT THE MAYO FOUNDATION CONSTRUCTION MANAGER. MAYO'S ASBESTOS EVALUATION AND ABATEMENT TEAM WILL ADDRESS ANY IDENTIFIED ASBESTOS EXPOSURE. 14. CONTRACTOR, CONSTRUCTION MANAGER AND RICK RAMAKER FROM FACILITIES WAREHOUSE TO VERIFY ALL ITEMS TO BE SALVAGED AND RETURNED TO OWNER'S STOCK BEFORE DEMOLITION OCCURS.

M001

1 1 1 1 1 1 1 1

Large Animal Surgery and Germ Free Facility

1 1 1

Medical Sciences Building Fourth Floor

1 1 1 1 1

Project #7R120760

MD104A MD104B M104A M104B M105A M106A M204A M204B M601

MECHANICAL SYMBOLS, ABBREVIATIONS, GENERAL NOTES AND SCHEDULES PARTIAL FOURTH LEVEL DEMOLITION HVAC PLAN AREA A PARTIAL FOURTH LEVEL DEMOLITION HVAC PLAN AREA B PARTIAL FOURTH LEVEL HVAC PLAN AREA A PARTIAL FOURTH LEVEL HVAC PLAN AREA B PARTIAL FIFTH LEVEL DEMOLITION AND HVAC PLANS AREA A PARTIAL SIXTH LEVEL DEMOLITION AND HVAC PLANS AREA A PARTIAL FOURTH LEVEL MECHANICAL PIPING PLAN AREA A PARTIAL FOURTH LEVEL MECHANICAL PIPING PLAN AREA B MECHANICAL DETAILS AND DIAGRAMS

1 1 1 1 1 1 1 1 1 1

E001 ED104A ED104B ED204A ED204B ED304A ED304B ED601 E104A E104B E204A E204B E206A E304A E304B E601 E602 E701

ELECTRICAL SYMBOLS ABBREVIATIONS AND GENERAL NOTES PARTIAL FOURTH LEVEL DEMOLITION LIGHTING PLAN AREA A PARTIAL FOURTH LEVEL DEMOLITION LIGHTING PLAN AREA B PARTIAL FOURTH LEVEL DEMOLITION POWER PLAN AREA A PARTIAL FOURTH LEVEL DEMOLITION POWER PLAN AREA B PARTIAL FOURTH LEVEL DEMOLITION SIGNAL PLAN AREA A PARTIAL FOURTH LEVEL DEMOLITION SIGNAL PLAN AREA B ELECTRICAL DEMOLITION ONE-LINE DIAGRAM PARTIAL FOURTH LEVEL LIGHTING PLAN AREA A PARTIAL FOURTH LEVEL LIGHTING PLAN AREA B PARTIAL FOURTH LEVEL POWER PLAN AREA A PARTIAL FOURTH LEVEL POWER PLAN AREA B PARTIAL SIXTH LEVEL DEMOLITION AND POWER PLANS AREA A PARTIAL FOURTH LEVEL SIGNAL PLAN AREA A PARTIAL FOURTH LEVEL SIGNAL PLAN AREA B ELECTRICAL ONE-LINE DIAGRAM ELECTRICAL PANEL SCHEDULES ELECTRICAL DETAILS

1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1

A

B

KEY PLAN

Project No. Drawn By

JAS

Checked By

JHA/MLK

Date

07/03/13

NOTICE: The designs shown and described herein including all technical drawings, graphics, and models thereof, are proprietary and cannot be copied, duplicated or commercially exploited, in whole or in part, without express written permission of RSP Architects. These are available for limited review and evaluation by clients, consultants, contractors, government agencies, vendors and office personnel only in accordance with this Notice. © Copyright RSP Architects 2007. All rights reserved.

Revisions No.

15. ALL FURNISHINGS SHALL CONFORM TO 2007 INTERNATIONAL FIRE CODE CHAPTER 8.

6287.040.04

Date

Description

16. NEW UPHOLSTERY MATERIALS MUST BE CALL TB117 COMPLIANT. 17. PREPARE PARTITION SURFACES (PATCH, SKIM COAT, ETC.) AS REQUIRED IN PREPARATION FOR SCHEDULED FINISHES - TYPICAL.

DRAWING SYMBOLS

18. ALL CONTRACTORS INCLUSIVE OF SUBCONTRACTORS ARE TO COMPLY WITH THE GUIDELINES OF THE INFECTION CONTROL UNIT IN RELATION TO ALL CONSTRUCTION IN HOSPITAL. CONTRACTORS TO REVIEW GUIDELINES PRIOR TO SUBMITTING ESTIMATES. 1

0

1

0

ROOM NAME REVISION REFERENCE

0

ELEVATION TAG SINGLE VIEW

101

1i COLUMN OR GRID LINE - EXISTING

A101

2

ELEVATION TAG MULTIPLE VIEW

PARTITION TAG

1

1 A101

DETAIL TAG

SIM MATCH LINE

MATCH LINE

12

SEE X/XXX

T.O. FOOTING Name Elevation EL. = 96'-0" EL. = 100'-0"

VIEW NAME 1/8" = 1'-0"

DRAWING TITLE

1 A101

1 A101

ELEVATION / LEVEL TAG NORTH ARROW

SPOT ELEVATION

NORTH NORTH

SIM

WALL SECTION TAG

SIM

ROOM TAG

KEY PLAN

(ROOM AREA)

XX

KEYNOTE

23 1t

WINDOW TAG

234

EQUIPMENT TAG

101

DOOR TAG

EXIST EXIST EXIST

(WALL FINISH) (BASE FINISH) (FLOOR FINISH)

PROJECT AREA

FINISH TAG ALL SURFACES

BUILDING SECTION TAG

EXIST EXIST

1 A101 SIM

(ROOM NUMBER)

150 SF

1

COLUMN OR GRID LINE - NEW

0

A101

(ROOM NAME)

ENLARGED PLAN OR DETAIL REFERENCE

CPT-01

CPT-02

FINISH TAG WITH EXTENT OF FINISH

COVER SHEET

FINISH TRANSITION

NORTH C:\Revit Projects\Med Sci 4 Central_jschmit.rvt 7/8/2013 11:23:11 AM

Please purchase PDF Split-Merge on www.verypdf.com to remove this watermark.

G000


UP

DN

SD

F

RSP Architects 320 South Broadway Ste. B 507.285.6569 Rochester, Minnesota 55904 612.677.7499 fax www.rsparch.com

FE SD

FE SD

SD

2F

Consultants

Certification

I hereby certify that I have reviewed the Mayo Clinic Standard General Specifications prepared by Ronald B. Carlson, License Number 10850, that they are appropriate for the work except as amended in this plan, specification or report, and that I am a duly licensed Architect under the laws of the State of Minnesota.

SD

SD

Signature

DAVID NORBACK

Registration Number

SD

11902

Date

I hereby certify that this plan, specification or report was prepared by me or under my direct supervision and that I am a duly licensed Architect under the laws of the State of Minnesota.

2F

FE

FE

07.03.13

SD

Signature

SD SD

DAVID NORBCK

Registration Number

11902

2F

Date

07.03.13

Project For SD FE

SD DN

UP

SD

FE SD

Large Animal Surgery and Germ Free Facility

F SD

SD

SD

SD

FE

Medical Sciences Building Fourth Floor

SD

Project #7R120760 PROJECT AREA

A

B

KEY PLAN

1

FOURTH LEVEL FIRE AND LIFE SAFETY PLAN

Project No.

1/8" = 1'-0"

Drawn By

NORTH

BUILDING CODE, OCCUPANCY AND EGRESS INFORMATION MEDICAL SCIENCES BUILDING - FOURTH LEVEL

ILSM FOR THE SCOPE OF WORK HAVE BEEN REVIEWED AND NO ACTION IS REQUIRED

1 HOUR RATED CORRIDOR: FULL HT PARTITION 1 HR RATED CONSTRUCTION, LIMIT PASSAGE OF SMOKE WITH 20 MINUTE DOORS.

CL

1 HOUR RATED CORRIDOR: FULL HT PARTITION 1 HR RATED CONSTRUCTION, LIMIT PASSAGE OF SMOKE.

CN

RATED CORRIDOR NOT REQUIRD: FULL HT PARTITION 1 HR RATED CONSTRUCTION.

CS

1 HOUR RATED CORRIDOR: FULL HT PARTITION 1 HR RATED CONSTRUCTION, MEMBRANE TO LIMIT PASSAGE OF SMOKE FROM RATED CORRIDOR BARRIER/CEILING UP TO DECK

PER 2007 MINNESOTA STATE BUILDING CODE (2006 IBC & GREB) IF A BOX IS CHECKED FOR THE FOLLOWING QUESTIONS BELOW, AN ACTION IS REQUIRED. ACTION REQUIRED

ITEM

ELEMENT OF PERFORMANCE

1

SIGNAGE SHALL BE POSTED IDENTIFYING ALTERNATE EXITS FOR EVERYONE AFFECTED.

2

CONTRACTOR SHALL FOLLOW HOT WORKS AND FIREWATCH POLICIES COORDINATED WITH MAYO CLINIC FACILITIES OPERATIONS, WHEN FIRE SYSTEMS ARE AFFECTED.

3

PROVIDE TEMPORARY BUT EQUIVALENT FIRE ALARM AND DETECTION SYSTEMS FOR USE WHEN THE FIRE SYSTEM IS NOT CONNECTED TO THE CENTRAL FIRE SYSTEM. INSPECT AND TEST TEMPORARY SYSTEMS MONTHLY.

LS.01.02.01 EP 5,12

4

TEMPORARY PARTITION SHALL BE CONSTRUCTED TO MAINTAIN THE INTEGRITY OF THE CONSTRUCTION SITE PERIMETER. TEMPORARY PARTITIONS MUST BE SMOKE TIGHT AND CONSTRUCTED OF LIMITED COMBUSTIBLE MATERIAL.

LS.01.02.01 EP 7

5

ADDITIONAL FIRE FIGHTING EQUIPMENT SHALL BE INSTALLED IN AND /OR AROUND CONSTRUCTION AREA.

LS.01.02.01 EP 6

LIFE SAFETY CODE DEFICIENCIES AFFECTING COMPARTMENTATION FEATURES OR EXITING PLANS OF ADJACENT OCCUPIED AREAS, MAY NEED ADDITIONAL FIRE SAFETY TRAINING OR DRILLS. THIS TRAINING SHALL BE DETERMINED AND PERFORMED BY MAYO SAFETY AND SECURITY. INTERIM LIFE SAFETY DAILY LOG SHALL DOCUMENT: STORAGE, DEBRIS REMOVAL AND HOUSEKEEPING ARE PRACTICED AND PERFORMED TO KEEP CONSTRUCTION AREA AT THE LOWEST FLAMMABLE AND COMBUSTIBLE LOAD. EGRESS ROUTES INA ND AROUND CONSTRUCTION AREA ARE CLEAR OF ALL OBSTRUCTIONS. SURVEILLANCE OF BUILDINGS, GROUNDS, AND EQUIPMENT, GIVING SPECIAL ATTENTION TO CONSTRUCTION AREAS AND STORAGE.

LS.01.02.01 EP 10,11,13,14

6 7

OCCUPANCY

HEIGHT INFORMATION ALLOWED ACTUAL

BUSINESS GROUP

STORIES SPRINKLER INCREASE TOTAL

LS.01.02.01 EP 2 LS.01.02.01 EP 1,5

LS.01.02.01 EP 9 LS.01.02.01 EP 4 LS.01.02.01 EP 8

TYPE OF CONSTRUCTION

III-A - FULLY SPRINKLERED

NOTE: ALL MEDICAL SCIENCE BUILDING FLOORS ARE 1 HR RATED. FLOORS 4-6 MUST BE 1 CONTROL AREA. COMPARTMENT ZONE MS-04-1

COMPARTMENT OCCUPANCY (TABLE 1004.1.1)

BUSINESS AREA

FOURTH LEVEL TOTALS

COMPARTMENT AREA (SQ.FT.) 12,946

12,946

SQ.FTG.PER OCCUPANT (TABLE 1004.1.1) 100

5

6

+1

6

6

AREA CALCULATIONS ALLOWED

BASIC AREA (4TH LEVEL) 28,500 21,375 INCREASE FOR FRONTAGE 57,000 INCREASE FOR SPRINKLERS 106,875 SUB-TOTAL INCREASE FOR MULTI-STORY x3 (MAX) 320,625 TOTAL

ACTUAL

12,946 SF 12,946 SF 148,509 SF

HAZARDOUS MATERIAL CONTROL AREA (IBC 2000 TABLE 414.2.2 AS AMENDED BY MN STATE BUILDING CODE) PERCENT OF THE NUMBER OF FIRE RESISTANCE FLOOR MAXIMUM ALLOWABLE CONTROL AREAS RATING FOR FIRE QUANTITY PER LEVEL PER FLOOR BARRIERS (IN HOURS) CONTROL AREA 2* 1* 10 4-6 1 2 50 3 1 3 75 2 1 4 100 1 1 3 75 SUBWAY 1 2 50 BASEMENT

OCCUPANT LOAD 130 130

EXIT INCHES REQUIRED VERTICAL

130 x 0.3 = 39.0 39.0

JAS

RATINGS C

INTERIM LIFE SAFETY MEASURES (ILSM) DESIGN REVIEW

6287.040.04

HORIZONTAL 0 x 0.2 = 0.0 0.0

INCHES PROVIDED VERTICAL 105 105

TOTAL EXIT INCHES PROVIDED

S

1 HOUR RATED SMOKE BARRIER WITH 20 MINUTE DOORS

1

1 HOUR RATED FIRE BARRIER WITH 45-60 MINUTE DOORS

1S

1 HOUR RATED FIRE/SMOKE BARRIER WITH 45-60 MINUTE DOORS

2F

2 HOUR RATED FIRE BARRIER

2S

2 HOUR RATED FIRE/SMOKE BARRIER

3

3 HOUR RATED FIRE BARRIER

4

4 HOUR RATED FIRE/SMOKE BARRIER

0 105

JHA/MLK

Date

07/03/13

NOTICE: The designs shown and described herein including all technical drawings, graphics, and models thereof, are proprietary and cannot be copied, duplicated or commercially exploited, in whole or in part, without express written permission of RSP Architects. These are available for limited review and evaluation by clients, consultants, contractors, government agencies, vendors and office personnel only in accordance with this Notice. © Copyright RSP Architects 2007. All rights reserved.

Revisions No.

Date

Description

1 HOUR RATED FIRE CEILING ASSEMBLY

HORIZONTAL 0

Checked By

BR

1 HOUR RATED BULKHEAD EXTENDING FROM CEILING UP TO DECK

BH

BULKHEAD MEMBRANE TO EXTEND FROM RATED CEILING ASSEMBLY UP TO DECK

FC

1 HOUR RATED FIRE BARRIER (CORRIDOR) EXTENDING FROM FLOOR UP TO RATED CEILING

SYMBOLS FE FEC

FIRE EXTINGUISHER

FHC

FIRE HOSE CONNECTION

F SD S

FIRE EXTINGUISHER CABINET

FIRE ALARM PULL SMOKE DETECTORS EMERGENCY SHOWER EXIT SIGN

35"

EXIT WIDTH IN INCHES

124'

TRAVEL DISTANCE TO NEAREST EXIT

NOTE: THESE PLANS ARE BEING PROVIDED FOR INFORMATION ONLY BY MAYO CLINIC FACILITIES PROJECT SERVICES.

C:\Revit Projects\Med Sci 4 Central_jschmit.rvt 7/8/2013 11:23:12 AM

Please purchase PDF Split-Merge on www.verypdf.com to remove this watermark.

FOURTH LEVEL FIRE AND LIFE SAFETY PLAN

G104


2

1

8

33

2

6

39

20

42

8

2

WORK RM 4-35B

3

9

39

2

"OUT"

1

39

13

45

8

1

"OUT"

2

"OUT"

27

7

7

CORRIDOR 4-004D

7

6

45

ELEC RM 4-004D-1

2

"OUT" 2

16

2

2

45

16

6

"OUT" "OUT"

46

"OUT"

45

8

12

CORRIDOR 4-004E 16

LAB 4-29

2

12

39

1

2

"OUT"

12

"OUT"

"OUT" "OUT" FELLOWS

EQUIPMENT RM 4-29-1

"OUT"

"OUT"

1

1

"OUT"

"OUT"

42

"OUT"

"OUT" "OUT"

"OUT"

"OUT"

"OUT"

"OUT"

1

1

1

16

33

7

Date

1

2

OFFICE 4-29B

"OUT"

7

45

1

46

2

7

30

1

7

LAB 4-55 39

Large Animal Surgery and Germ Free Facility

6

42

TISSUE CULTURE 4-55A

12

2

39

"OUT"

"OUT"

27 16 1

45

45 2

"OUT"

"OUT"

7 "OUT"

"OUT"

"OUT"

"OUT"

"OUT"

"OUT"

2

K2

"OUT"

"OUT"

BREAKROOM 4-30 16

2

1

8

32

"OUT"

CONFERENCE 4-60 "OUT"

"OUT"

45

"OUT"

16

"OUT"

"OUT"

45

2

42

Medical Sciences Building Fourth Floor

2

1

M

"OUT"

2

"OUT"

7

12 1

"OUT"

"OUT"

1

"OUT"

"OUT"

2

6

"OUT"

2

OFFICE 4-57 39

"OUT"

42

Project #7R120760 1 2

5

"OUT"

A

"OUT" "OUT"

B

4"

16

"OUT"

2

"OUT"

07.03.13

2

2

"OUT"

3' - 8"

"OUT"

"OUT"

1' - 7"

"OUT"

"OUT"

5' - 11"

"OUT"

OFFICE 4-29C

"OUT"

11902

Project For

3

12

8

CORRIDOR 4-004C

6

"OUT"

Registration Number

"OUT"

43

3

DAVID NORBCK

13

4 "OUT"

I hereby certify that this plan, specification or report was prepared by me or under my direct supervision and that I am a duly licensed Architect under the laws of the State of Minnesota.

7

LAB 4-56

2

"OUT"

12 "OUT"

12

"OUT"

07.03.13

2

3

3

11902

Date

1

LAB 4-53

12

3

"OUT"

45

7

"OUT"

"OUT"

"OUT" "OUT" 2

DAVID NORBACK

Registration Number

"OUT"

3

12

1

45

"OUT" "OUT"

13

"OUT"

1

"OUT"

2

1

2

8

"OUT"

"OUT"

"OUT"

1

I hereby certify that I have reviewed the Mayo Clinic Standard General Specifications prepared by Ronald B. Carlson, License Number 10850, that they are appropriate for the work except as amended in this plan, specification or report, and that I am a duly licensed Architect under the laws of the State of Minnesota.

2

13

"OUT"

2

"OUT"

FELLOWS "OUT" 2 4-31 16

2

12

4-32

"OUT"

"OUT"

"OUT" "OUT" "OUT"

6

42

Certification

Signature

"OUT"

45

"OUT"

"OUT"

42

Signature

39

"OUT"

"OUT"

16

"OUT"

2

8

"OUT"

3

"OUT"

"OUT" "OUT" "OUT"

45

"OUT"

2

1

"OUT"

"OUT" "OUT"

13

12

LAB 4-54

"OUT"

"OUT" 16

16

39

2

1

12

3

WORK RM 4-53A

1

"OUT"

ELEC RM 4-004D-2

7

45

2

"OUT"

2

"OUT"

33

12

OFFICE 4-34

12

12

2

"OUT"

27

"OUT"

"OUT"

1

3

6

7

"OUT"

WORK RM 4-29A

"OUT"

Consultants

409

"OUT"

12

1

46

29

PREP 4-35A

42

1

45

2

"OUT"

24

"OUT"

"OUT"

"OUT"

2

2

"OUT"

VESTIBULE 4-49

2

LAB 4-45

RSP Architects 320 South Broadway Ste. B 507.285.6569 Rochester, Minnesota 55904 612.677.7499 fax www.rsparch.com

STORAGE 4-49A

"OUT"

1

20

12

7

"OUT"

STAIR 4-49B

1

2 "OUT"

1

1

1

3

12

6

42

"OUT"

1

15

"OUT"

2

"OUT"

2

39

2

3

OPERATING RM 4-35C

"OUT"

2

7

2

VESTIBULE 4-78

1

CORRIDOR 4-004F 16

PARTIAL FOURTH LEVEL DEMOLITION PLAN - AREA A

46

2

KEY PLAN

"OUT" "OUT"

Project No.

STORAGE 4-28

6287.040.04

Drawn By

JAS

Checked By

1/4" = 1'-0"

JHA/MLK

Date

07/03/13

NORTH KEYNOTES - DEMOLITION PLAN

DEMOLITION PLAN GENERAL NOTES: 1. SEE MECHANICAL DRAWINGS FOR DUCTWORK, DIFFUSER, PLENUM BOX, LIGHTING, ELECTRICAL CONDUIT, ETC. DEMOLITION AND/OR PROTECTION. 2. DEMOLITION IS NOT NECESSARILY LIMITED TO WHAT IS SHOWN ON DRAWINGS. THE INTENT IS TO INDICATE THE GENERAL SCOPE OF DEMOLITION REQUIRED TO COMPLETE THE WORK IN ACCORDANCE WITH THE CONTRACT DRAWINGS. 3. FIRE SAFETY MUST BE MAINTAINED FOR ALL PERSONNEL WORKING ON THE FLOOR. ALL FIRE STAIRS, ALARMS,SPEAKERS, ETC. MUST REMAIN ACCESSIBLE AND OPERABLE AT ALL TIMES. IMMEDIATELY NOTIFY BUILDING SECURITY AND BUILDING MANAGER OF DAMAGED OR DISABLED SYSTEMS AND REPAIR OR REPLACE DAMAGED SYSTEMS IMMEDIATELY. 4. ALL FIRE SAFETY EQUIPMENT AND THE ASSOCIATED CONDUIT AND WIRING SYSTEM SHALL NOT BE HARMED DURING DEMOLITION AND/OR CONSTRUCTION AND SHALL BE PROTECTED FROM ANY PHYSICAL DAMAGE. NO EXISTING SMOKE DETECTOR, PUBLIC ADDRESS SPEAKER, FIRE ALARM BOX OR SIMILAR DEVICE, INCLUDING THE ASSOCIATED WIRING SHALL BE DAMAGED DURING DEMOLITION AND SUBSEQUENT CONSTRUCTION. RELOCATION OF SMOKE DETECTORS, PUBLIC ADDRESS SPEAKERS AND FIRE ALARM EQUIPMENT, NECESSITATED BY NEW CONSTRUCTION, SHALL BE ACCOMPLISHED AS A FIRST PRIORITY, AND PER THE PLANS. NOTIFY BUILDING SECURITY AND MAYO CONSTRUCTION MANAGER OF DAMAGED OR DISABLED SYSTEMS AND REPAIR OR REPLACE DAMAGED SYSTEMS IMMEDIATELY. 5. LOUD DEMOLITION WORK (i.e. CONCRETE REMOVAL) SHALL BE COORDINATED WITH THE BUILDING MANAGER TO MINIMIZE DISRUPTION TO BUILDING OCCUPANTS. 6. CONTRACTOR SHALL BE RESPONSIBLE FOR PATCHING AND/OR REPAIRING ANY DAMAGE CAUSED BY HIM OR HIS SUBCONTRACTORS TO EXISTING CONSTRUCTION IN ELEVATOR LOBBIES, PUBLIC CORRIDORS OR RESTROOMS. REFINISH TO MATCH EXISTING ADJACENT FINISH, OR AS NOTED HEREIN. 7. ALL DIMENSIONS TO EXISTING ELEMENTS ARE FOR REFERENCE ONLY AND SHOULD BE FIELD VERIFIED. 8. THE INTENT OF THIS DEMOLITION IS TO PROVIDE A CLEAN AND CLEAR AREA FOR NEW CONSTRUCTION AND FINISHES AS INDICATED ON THESE ARCHITECTURAL DRAWINGS. A. DEMOLISH DASHED WALLS, MILLWORK, OR MISCELLANEOUS ITEMS. RELATED FRAMING, BRACING, AND ANCHORS MUST BE REMOVED. PROVIDE RELATED MECHANICAL/ELECTRICAL FOR THIS WORK. B. DEMOLISH FINISHES ON EXISTING WALLS OR SURFACES TO REMAIN WHERE NEW FINISHES ARE SCHEDULED. C. DEMOLISH FLOOR FINISHES AND BASE AS NOTED OR WHERE NEW FLOOR FINISHES AND BASE ARE SCHEDULED, INCLUDING ADHESIVES. D. DEMOLISH CEILINGS AND SOFFITS AS REQUIRED TO PROVIDE THE NEW CEILING LAYOUT (SEE CEILING PLAN). COORDINATE WORK INCLUDING THAT REQUIRED FOR MECHANICAL/ELECTRICAL. E. EXISTING WALLS AND SURFACES NOTED TO REMAIN, BUT DAMAGED PRIOR TO OR DURING DEMOLITION, MUST BE REPAIRED TO ACCEPT NEW FINISHES.

DEMOLITION PLAN LEGEND: EXISTING PARTITION TO REMAIN

EXISTING DOOR AND FRAME TO REMAIN

EXISTING PARTITION, CASEWORK, SHELVING, EQUIPMENT TO BE REMOVED

EXISTING DOOR AND FRAME TO BE REMOVED

C:\Revit Projects\Med Sci 4 Central_jschmit.rvt 7/8/2013 11:23:06 AM

Please purchase PDF Split-Merge on www.verypdf.com to remove this watermark.

ROOM NAME

ROOM TAG

1i "OUT"

1

KEYNOTE

1i

EQUIPMENT TO BE RELOCATED, REFER TO EQUIPMENT SCHEDULE

A

SPECIALTY EQUIPMENT TO BE RELOCATED, REFER TO SPECIALTY EQUIPMENT SCHEDULE

EXISTING FURNITURE TO BE RELOCATED, REFER TO FURNITURE SCHEDULE EXISTING FURNITURE AND EQUIPMENT TO BE REMOVED AND RETURNED TO OWNER'S STOCK.

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 27 29 30 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46

REMOVE COUNTERTOP AND BASE CABINETS. REMOVE WALL CABINETS AND/OR ADJUSTABLE SHELVING, STANDARDS, AND BRACKETS. REMOVE REAGENT SHELF, COUNTERTOP, AND BASE CABINETS. COORDINATE WITH MECHANICAL AND ELECTRICAL CONTRACTOR. REMOVE PLASTIC LAMINATE PIPETTE RACK. REMOVE PORTION OF WALL AS REQUIRED FOR NEW DOOR OPENINGS - SEE FLOOR PLAN FOR LOCATION AND DOOR SCHEDULE FOR FRAME SIZE. REMOVE COAT HOOK STRIP. REMOVE CORKBOARD/ WHITEBOARD. REMOVE STAINLESS STEEL SINK AND TOP - SEE PLUMBING DRAWINGS. REMOVE SHELF AND COAT ROD. REMOVE SHOWER CONTROLS, CURTAIN, ROD, AND ALL ASSOCIATED HARDWARE. REMOVE METAL LOCKERS. REMOVE WIREMOLD - SEE ELECTRICAL DRAWINGS. REMOVE DRYING RACK - RETURN TO OWNER'S STOCK. REMOVE ALL TOILET ACCESSORIES AND GRAB BARS. REMOVE SINK - SEE PLUMBING DRAWINGS. REMOVE EXISTING SUSPENDED ACOUSTICAL CEILING TILE AND GRID SYSTEM REMOVE URINAL - COORDINATE W/ MECHANICAL REMOVE P-LAM STORAGE UNIT AND RETURN TO OWNER'S STOCK. REMOVE TOILET - SEE PLUMBING DRAWINGS REMOVE X-RAY VIEWBOX. RETURN TO OWNER'S STOCK. REMOVE OPEN BOOK SHELF, HOLDER AND ALL ASSOCIATED HARDWARE. REMOVE TOILET PARTITION AND ALL ASSOCIATED HARDWARE REMOVE METAL SHELF. REMOVE MIRROR. REMOVE FIRE EXTINGUISHER - RETURN TO OWNER'S STOCK. REMOVE SLIDING DOOR AND ALL ASSOCIATED HARDWARE. REMOVE PRIVACY CURTAIN AND ALL ASSOCIATED HARDWARE. REMOVE PROJECTOR SCREEN. REMOVE GAS CYLINDER AND SUPPORT BRAQCKETS. REMOVE ELECTRIC WATER COOLER - SEE PLUMBING AND ELECTRICAL DRAWINGS. REMOVE STERILIZER - CORDINATE W/ MECHANICAL & ELECTRICAL REMOVE MINI BLIND. REMOVE AND SALVAGE EXISTING SCRUB SINK FOR REUSE - SEE PLUMBING DRAWINGS. EXISTING SCRUB SINK TO REMAIN REMOVE EXISTING SUSPENDED GYPSUM BOARD CEILING SYSTEM. REMOVE EXISTING EXAM ROOM LIGHTING AND TRACK. PATCH EXISTING PLASTER CEILING AND PREPARE FOR NEW FINISHES. REMOVE EXISTING GYPSUM BOARD CEILING AND INSTALL NEW STRUCTURAL SUPPORT FOR EXAM LIGHT. FIELD VERIFY EXACT LOCATION. PATCH CEILING UPON COMPLETION OF STRUCTURAL SUPPORT WORK AND PREPARE FOR NEW FINISHES. REMOVE EXISTING SHEET VINYL FLOORING AND COVED BASE IN THIS ROOM - PREPARE FOR NEW FINISHES. REMOVE EXISTING SHEET VINYL FLOORING VINYL BASE IN THIS ROOM - PREPARE FOR NEW FINISHES. REMOVE EXISTING CERAMIC TILE AND BASE IN THIS ROOM - PREPARE FOR NEW FINISHES. REMOVE EXISTING VCT AND VINYL BASE IN THIS ROOM - PREPARE FOR NEW FINISHES. REMOVE EXISTING SUSPENDED GLUE ON ACT AND GYPSUM BACKER BOARD IN THIS ROOM/AREA.

NOTICE: The designs shown and described herein including all technical drawings, graphics, and models thereof, are proprietary and cannot be copied, duplicated or commercially exploited, in whole or in part, without express written permission of RSP Architects. These are available for limited review and evaluation by clients, consultants, contractors, government agencies, vendors and office personnel only in accordance with this Notice. © Copyright RSP Architects 2007. All rights reserved.

Revisions No.

Date

Description

PARTIAL FOURTH LEVEL DEMOLITION PLAN - AREA A

D104A


"OUT"

1

45

7

2

45

"OUT"

"OUT"

16

VESTIBULE 4-78

CORRIDOR 4-004F

5' - 0"

16

"OUT"

46

1

21

2

1

45

"OUT"

2

18

WORK RM 4-25 16

"OUT"

45

21

"OUT"

7

"OUT"

"OUT"

SOILED WORK 4-26 39

8

42

12

39 2

42

12

45

1

2

2

"OUT" "OUT"

"OUT"

"OUT"

6

"OUT"

1

39

16

45

3

5

"OUT"

6

6

5

5

7

MEN'S 4-01

9 39

44

39

46

2

22

14

LOCKER RM 4-01A 39

10

45 "OUT"

45

"OUT"

2

"OUT""OUT"

RECOVERY 4-74 39

45

22

18

1

29

PREP 4-72

23

39

38

42

21

"OUT"

1

2

14

"OUT"

EQUIPMENT 4-70 "OUT"

2

2

39

24

1

37

18

"OUT"

42

OPERATING 4-71

2

41

6

41

2

6

33

2

"OUT"

Signature

DAVID NORBCK 11902

2

K

40 41

"OUT"

K1

41

"OUT" 2

1

12 1

45

"OUT"

16

"OUT" "OUT"

"OUT"

2

LAB 4-65

45

"OUT"

"OUT"

8

"OUT"

1

2

2

Medical Sciences Building Fourth Floor

2

3

"OUT"

2

Large Animal Surgery and Germ Free Facility

"OUT"

7

"OUT"

"OUT"

Project For

"OUT"

7

"OUT"

7

OPERATING 4-67

OPERATING 4-69

2

6

6

6

07.03.13

27

12

1

07.03.13

I hereby certify that this plan, specification or report was prepared by me or under my direct supervision and that I am a duly licensed Architect under the laws of the State of Minnesota.

"OUT"

12

16

12

2

36

41

11902

2

36

36

2

"OUT"

EQUIPMENT 4-65A

1

2

K3

12

2

23

40

"OUT"

1

37

23

"OUT"

OPERATING 4-73

Registration Number

DAVID NORBACK

Date

"OUT"

40

21

8

7

40

19

2

"OUT"

7

24

K1

40

45

Signature

Registration Number

6 1

16

5

PREP 4-68

15

9

LAB 4-64

4

"OUT"

Date

2

24

44 "OUT"

6

"OUT"

11

11

"OUT"

I hereby certify that I have reviewed the Mayo Clinic Standard General Specifications prepared by Ronald B. Carlson, License Number 10850, that they are appropriate for the work except as amended in this plan, specification or report, and that I am a duly licensed Architect under the laws of the State of Minnesota.

2

1

STORAGE 4-62C 39

7

5

46

2

"OUT"

44

ELECTRIC 4-00B-1

CORRIDOR 4-004B

45

Certification

20

OFFICE 4-75 WOMEN'S 4-04

Consultants

"OUT"

2

7

16

1

45

"OUT"

2

46

"OUT"

42

M

CUSTODIAL 4-03 10 2 39 44

45

12

45

2

VESTIBULE 4-76 21

LAB 4-63

10

WORK RM 4-62

2

RSP Architects 320 South Broadway Ste. B 507.285.6569 Rochester, Minnesota 55904 612.677.7499 fax www.rsparch.com

1

2

46

2

10

1

CORRIDOR 4-004

8

12

7

10

6

7 2

1

ANTE RM 4-24 21

15

"OUT"

"OUT"

7

OFFICE 4-62B 1 16 45

"OUT"

6

LAB 4-24A

16

"OUT" "OUT"

9

STAIR 4-08

24

5

42

2

"OUT"

7

"OUT"

21

12

45

"OUT"

6

7

1

11

OFFICE 4-62A

16

35

6

1

34

39

"OUT"

2

OFFICE 4-57

6

7

"OUT"

STERILIZER 4-27

2

2

2

2

"OUT"

9

37

22

"OUT"

"OUT"

"OUT" "OUT"

2

39

27

"OUT"

"OUT"

2 "OUT"

7' - 10 1/4"

12

"OUT"

19

32

STORAGE 4-28

"OUT"

21

17

16

"OUT"

STORAGE 4-07

39

45

2

MECH RM 4-05

22

8

2

6' - 0 1/4"

"OUT"

CLOSET 4-004-1

1

4"

"OUT"

"OUT"

"OUT"

2

BREAKROOM 4-30

1' - 7"

7 16

"OUT"

"OUT"

16

"OUT"

5' - 11"

OFFICE 4-29B

CONFERENCE 4-60 "OUT"

"OUT"

30

12

8

1

1 "OUT"

1

29

2 12

LAB 4-66 16

45

Project #7R120760

12 "OUT"

A

2 33 1

B

KEY PLAN

Project No.

PARTIAL FOURTH LEVEL DEMOLITION PLAN - AREA B

1

6287.040.04

Drawn By

1/4" = 1'-0"

NORTH

JAS

Checked By

JHA/MLK

KEYNOTES - DEMOLITION PLAN DEMOLITION PLAN GENERAL NOTES: 1. SEE MECHANICAL DRAWINGS FOR DUCTWORK, DIFFUSER, PLENUM BOX, LIGHTING, ELECTRICAL CONDUIT, ETC. DEMOLITION AND/OR PROTECTION. 2. DEMOLITION IS NOT NECESSARILY LIMITED TO WHAT IS SHOWN ON DRAWINGS. THE INTENT IS TO INDICATE THE GENERAL SCOPE OF DEMOLITION REQUIRED TO COMPLETE THE WORK IN ACCORDANCE WITH THE CONTRACT DRAWINGS. 3. FIRE SAFETY MUST BE MAINTAINED FOR ALL PERSONNEL WORKING ON THE FLOOR. ALL FIRE STAIRS, ALARMS,SPEAKERS, ETC. MUST REMAIN ACCESSIBLE AND OPERABLE AT ALL TIMES. IMMEDIATELY NOTIFY BUILDING SECURITY AND BUILDING MANAGER OF DAMAGED OR DISABLED SYSTEMS AND REPAIR OR REPLACE DAMAGED SYSTEMS IMMEDIATELY. 4. ALL FIRE SAFETY EQUIPMENT AND THE ASSOCIATED CONDUIT AND WIRING SYSTEM SHALL NOT BE HARMED DURING DEMOLITION AND/OR CONSTRUCTION AND SHALL BE PROTECTED FROM ANY PHYSICAL DAMAGE. NO EXISTING SMOKE DETECTOR, PUBLIC ADDRESS SPEAKER, FIRE ALARM BOX OR SIMILAR DEVICE, INCLUDING THE ASSOCIATED WIRING SHALL BE DAMAGED DURING DEMOLITION AND SUBSEQUENT CONSTRUCTION. RELOCATION OF SMOKE DETECTORS, PUBLIC ADDRESS SPEAKERS AND FIRE ALARM EQUIPMENT, NECESSITATED BY NEW CONSTRUCTION, SHALL BE ACCOMPLISHED AS A FIRST PRIORITY, AND PER THE PLANS. NOTIFY BUILDING SECURITY AND MAYO CONSTRUCTION MANAGER OF DAMAGED OR DISABLED SYSTEMS AND REPAIR OR REPLACE DAMAGED SYSTEMS IMMEDIATELY. 5. LOUD DEMOLITION WORK (i.e. CONCRETE REMOVAL) SHALL BE COORDINATED WITH THE BUILDING MANAGER TO MINIMIZE DISRUPTION TO BUILDING OCCUPANTS. 6. CONTRACTOR SHALL BE RESPONSIBLE FOR PATCHING AND/OR REPAIRING ANY DAMAGE CAUSED BY HIM OR HIS SUBCONTRACTORS TO EXISTING CONSTRUCTION IN ELEVATOR LOBBIES, PUBLIC CORRIDORS OR RESTROOMS. REFINISH TO MATCH EXISTING ADJACENT FINISH, OR AS NOTED HEREIN. 7. ALL DIMENSIONS TO EXISTING ELEMENTS ARE FOR REFERENCE ONLY AND SHOULD BE FIELD VERIFIED. 8. THE INTENT OF THIS DEMOLITION IS TO PROVIDE A CLEAN AND CLEAR AREA FOR NEW CONSTRUCTION AND FINISHES AS INDICATED ON THESE ARCHITECTURAL DRAWINGS. A. DEMOLISH DASHED WALLS, MILLWORK, OR MISCELLANEOUS ITEMS. RELATED FRAMING, BRACING, AND ANCHORS MUST BE REMOVED. PROVIDE RELATED MECHANICAL/ELECTRICAL FOR THIS WORK. B. DEMOLISH FINISHES ON EXISTING WALLS OR SURFACES TO REMAIN WHERE NEW FINISHES ARE SCHEDULED. C. DEMOLISH FLOOR FINISHES AND BASE AS NOTED OR WHERE NEW FLOOR FINISHES AND BASE ARE SCHEDULED, INCLUDING ADHESIVES. D. DEMOLISH CEILINGS AND SOFFITS AS REQUIRED TO PROVIDE THE NEW CEILING LAYOUT (SEE CEILING PLAN). COORDINATE WORK INCLUDING THAT REQUIRED FOR MECHANICAL/ELECTRICAL. E. EXISTING WALLS AND SURFACES NOTED TO REMAIN, BUT DAMAGED PRIOR TO OR DURING DEMOLITION, MUST BE REPAIRED TO ACCEPT NEW FINISHES.

DEMOLITION PLAN LEGEND: EXISTING PARTITION TO REMAIN

EXISTING DOOR AND FRAME TO REMAIN

ROOM NAME

ROOM TAG

"OUT"

1

KEYNOTE

EXISTING PARTITION, CASEWORK, SHELVING, EQUIPMENT TO BE REMOVED

1i

EQUIPMENT TO BE RELOCATED, REFER TO EQUIPMENT SCHEDULE

EXISTING DOOR AND FRAME TO BE REMOVED

A

SPECIALTY EQUIPMENT TO BE RELOCATED, REFER TO SPECIALTY EQUIPMENT SCHEDULE

C:\Revit Projects\Med Sci 4 Central_jschmit.rvt 7/8/2013 11:23:08 AM

Please purchase PDF Split-Merge on www.verypdf.com to remove this watermark.

1i

EXISTING FURNITURE TO BE RELOCATED, REFER TO FURNITURE SCHEDULE EXISTING FURNITURE AND EQUIPMENT TO BE REMOVED AND RETURNED TO OWNER'S STOCK.

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 27 29 30 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46

REMOVE COUNTERTOP AND BASE CABINETS. REMOVE WALL CABINETS AND/OR ADJUSTABLE SHELVING, STANDARDS, AND BRACKETS. REMOVE REAGENT SHELF, COUNTERTOP, AND BASE CABINETS. COORDINATE WITH MECHANICAL AND ELECTRICAL CONTRACTOR. REMOVE PLASTIC LAMINATE PIPETTE RACK. REMOVE PORTION OF WALL AS REQUIRED FOR NEW DOOR OPENINGS - SEE FLOOR PLAN FOR LOCATION AND DOOR SCHEDULE FOR FRAME SIZE. REMOVE COAT HOOK STRIP. REMOVE CORKBOARD/ WHITEBOARD. REMOVE STAINLESS STEEL SINK AND TOP - SEE PLUMBING DRAWINGS. REMOVE SHELF AND COAT ROD. REMOVE SHOWER CONTROLS, CURTAIN, ROD, AND ALL ASSOCIATED HARDWARE. REMOVE METAL LOCKERS. REMOVE WIREMOLD - SEE ELECTRICAL DRAWINGS. REMOVE DRYING RACK - RETURN TO OWNER'S STOCK. REMOVE ALL TOILET ACCESSORIES AND GRAB BARS. REMOVE SINK - SEE PLUMBING DRAWINGS. REMOVE EXISTING SUSPENDED ACOUSTICAL CEILING TILE AND GRID SYSTEM REMOVE URINAL - COORDINATE W/ MECHANICAL REMOVE P-LAM STORAGE UNIT AND RETURN TO OWNER'S STOCK. REMOVE TOILET - SEE PLUMBING DRAWINGS REMOVE X-RAY VIEWBOX. RETURN TO OWNER'S STOCK. REMOVE OPEN BOOK SHELF, HOLDER AND ALL ASSOCIATED HARDWARE. REMOVE TOILET PARTITION AND ALL ASSOCIATED HARDWARE REMOVE METAL SHELF. REMOVE MIRROR. REMOVE FIRE EXTINGUISHER - RETURN TO OWNER'S STOCK. REMOVE SLIDING DOOR AND ALL ASSOCIATED HARDWARE. REMOVE PRIVACY CURTAIN AND ALL ASSOCIATED HARDWARE. REMOVE PROJECTOR SCREEN. REMOVE GAS CYLINDER AND SUPPORT BRAQCKETS. REMOVE ELECTRIC WATER COOLER - SEE PLUMBING AND ELECTRICAL DRAWINGS. REMOVE STERILIZER - CORDINATE W/ MECHANICAL & ELECTRICAL REMOVE MINI BLIND. REMOVE AND SALVAGE EXISTING SCRUB SINK FOR REUSE - SEE PLUMBING DRAWINGS. EXISTING SCRUB SINK TO REMAIN REMOVE EXISTING SUSPENDED GYPSUM BOARD CEILING SYSTEM. REMOVE EXISTING EXAM ROOM LIGHTING AND TRACK. PATCH EXISTING PLASTER CEILING AND PREPARE FOR NEW FINISHES. REMOVE EXISTING GYPSUM BOARD CEILING AND INSTALL NEW STRUCTURAL SUPPORT FOR EXAM LIGHT. FIELD VERIFY EXACT LOCATION. PATCH CEILING UPON COMPLETION OF STRUCTURAL SUPPORT WORK AND PREPARE FOR NEW FINISHES. REMOVE EXISTING SHEET VINYL FLOORING AND COVED BASE IN THIS ROOM - PREPARE FOR NEW FINISHES. REMOVE EXISTING SHEET VINYL FLOORING VINYL BASE IN THIS ROOM - PREPARE FOR NEW FINISHES. REMOVE EXISTING CERAMIC TILE AND BASE IN THIS ROOM - PREPARE FOR NEW FINISHES. REMOVE EXISTING VCT AND VINYL BASE IN THIS ROOM - PREPARE FOR NEW FINISHES. REMOVE EXISTING SUSPENDED GLUE ON ACT AND GYPSUM BACKER BOARD IN THIS ROOM/AREA.

Date

07/03/13

NOTICE: The designs shown and described herein including all technical drawings, graphics, and models thereof, are proprietary and cannot be copied, duplicated or commercially exploited, in whole or in part, without express written permission of RSP Architects. These are available for limited review and evaluation by clients, consultants, contractors, government agencies, vendors and office personnel only in accordance with this Notice. © Copyright RSP Architects 2007. All rights reserved.

Revisions No.

Date

Description

PARTIAL FOURTH LEVEL DEMOLITION PLAN - AREA B

D104B


O107

O124

O108

M103

M101

M225

M100 O104 "OUT" O132

"OUT"

O105

M227

"OUT"

OPERATING RM 4-35C

"OUT" "OUT"

"OUT"

WORK RM 4-35B

M115

O113

"OUT"

M239

O101

OUT"

M242

M220

M114

M113

M112 M109

G108

CORRIDOR 4-004D

O133

ELEC RM 4-004D-1

ELEC RM 4-004D-2

G145

G146

WORK RM 4-29A

G144

"OUT"

"OUT"

G111

G112

N106

"OUT"

"OUT"

"OUT"

N108

N107

"OUT"

C112

C113

LAB 4-29

G120

C123 C121

"OUT"

C105

"OUT"

CORRIDOR 4-004C

"OUT"

"OUT"

C115

C122 C116

G118 G115

N101

C117

N100

C119

N102

"OUT"

G138 "OUT"

C101

G134

G135

G140

"OUT" "OUT"

Project #7R120760

OFFICE 4-57

"OUT"

CONFERENCE 4-60

"OUT"

"OUT"

Medical Sciences Building Fourth Floor

G141

G137

"OUT"

"OUT"

Large Animal Surgery and Germ Free Facility

G142

G139

BREAKROOM 4-30

M118

G117

TISSUE CULTURE 4-55A

N138

OFFICE 4-29C

G119

G143

LAB 4-55

N103

"OUT"

C102

C100

M119

07.03.13

G114

LAB 4-56

N105

N104

C118

EQUIPMENT RM 4-29-1

11902

C106

C120

"OUT"

DAVID NORBCK

Date

G116

C105

"OUT"

FELLOWS 4-31

1

I hereby certify that this plan, specification or report was prepared by me or under my direct supervision and that I am a duly licensed Architect under the laws of the State of Minnesota.

Project For

C105

"OUT"

M120

07.03.13

Registration Number

G113

C103

C111

CORRIDOR 4-004E

X111

G122

Date

Signature

"OUT"

X110

G123

11902

G121

FELLOWS 4-32

"OUT"

G124

LAB 4-53

"OUT"

N228

"OUT"

G125

G126 M104

DAVID NORBACK

Registration Number

G127

"OUT"

"OUT"

"OUT"

I hereby certify that I have reviewed the Mayo Clinic Standard General Specifications prepared by Ronald B. Carlson, License Number 10850, that they are appropriate for the work except as amended in this plan, specification or report, and that I am a duly licensed Architect under the laws of the State of Minnesota.

Signature

LAB M107 4-54

OFFICE 4-34

Certification

G130

"OUT"

"OUT"

"OUT"

G131

G128

"OUT"

"OUT"

G132

G129

O102

G147

WORK RM 4-53A G133

G109

M106 M105

G102

G104

G105

G107

Consultants

"OUT"

G101

M108

PREP 4-35A

"OUT"

STORAGE 4-49A

VESTIBULE 4-49

M243

M245

RSP Architects 320 South Broadway Ste. B 507.285.6569 Rochester, Minnesota 55904 612.677.7499 fax www.rsparch.com

M222

"OUT"

LAB 4-45

M244

M241

"OUT"

"OUT"

M226

"OUT"

M224

M116

M231

M110

"OUT"

O106

M102

O100

M230

STAIR 4-49B

A

"OUT" B

"OUT"

?

KEY PLAN

?

Project No.

6287.040.04

Drawn By

PARTIAL FOURTH LEVEL DEMOLITION EQUIPMENT PLAN - AREA A

JAS

Checked By

1/4" = 1'-0"

JHA/MLK

Date

NOTICE: The designs shown and described herein including all technical drawings, graphics, and models thereof, are proprietary and cannot be copied, duplicated or commercially exploited, in whole or in part, without express written permission of RSP Architects. These are available for limited review and evaluation by clients, consultants, contractors, government agencies, vendors and office personnel only in accordance with this Notice.

DEMOLITION PLAN LEGEND: EXISTING PARTITION TO REMAIN

EXISTING DOOR AND FRAME TO REMAIN

07/03/13

ROOM NAME

ROOM TAG

1i "OUT"

1

KEYNOTE

EXISTING PARTITION, CASEWORK, SHELVING, EQUIPMENT TO BE REMOVED

1i

EQUIPMENT TO BE RELOCATED, REFER TO EQUIPMENT SCHEDULE

EXISTING DOOR AND FRAME TO BE REMOVED

A

SPECIALTY EQUIPMENT TO BE RELOCATED, REFER TO SPECIALTY EQUIPMENT SCHEDULE

EXISTING FURNITURE TO BE RELOCATED, REFER TO FURNITURE SCHEDULE EXISTING FURNITURE AND EQUIPMENT TO BE REMOVED AND RETURNED TO OWNER'S STOCK.

© Copyright RSP Architects 2007. All rights reserved.

Revisions No.

Date

Description

PARTIAL FOURTH LEVEL DEMOLITION EQUIPMENT PLAN - AREA A

D204A C:\Revit Projects\Med Sci 4 Central_jschmit.rvt 7/8/2013 11:23:09 AM

Please purchase PDF Split-Merge on www.verypdf.com to remove this watermark.


"OUT"

"OUT"

M118

VESTIBULE 4-78

"OUT"

CORRIDOR 4-004F

"OUT"

"OUT"

MECH RM 4-05

?

"OUT"

WORK RM 4-25

"OUT"

Z208

"OUT"

SOILED WORK 4-26

"OUT"

"OUT"

Consultants

"OUT" "OUT"

WORK RM 4-62 OFFICE 4-62B

Certification

"OUT"

C109

"OUT"

Z206

"OUT"

LAB 4-63

C124

M123

"OUT"

"OUT"

Z212

Z210

Z209

STERILIZER 4-27

"OUT"

"OUT"

M122

OFFICE 4-62A

"OUT"

Z202

Z229

"OUT"

M117

"OUT"

Z225

RSP Architects 320 South Broadway Ste. B 507.285.6569 Rochester, Minnesota 55904 612.677.7499 fax www.rsparch.com

"OUT" "OUT"

Z224

"OUT"

?

?

STORAGE 4-28

"OUT"

STORAGE 4-07

"OUT"

I hereby certify that I have reviewed the Mayo Clinic Standard General Specifications prepared by Ronald B. Carlson, License Number 10850, that they are appropriate for the work except as amended in this plan, specification or report, and that I am a duly licensed Architect under the laws of the State of Minnesota.

"OUT"

Z215

C108

"OUT"

LAB Z207 4-24A

STAIR 4-08

Signature

STORAGE 4-62C

ANTE RM 4-24

Z205

Registration Number

"OUT"

"OUT"

"OUT" LAB

"OUT"

VESTIBULE 4-76

4-64

"OUT"

CUSTODIAL 4-03

OFFICE 4-75

"OUT" "OUT"

WOMEN'S 4-04

"OUT"

MEN'S 4-01

"OUT"

"OUT"

RECOVERY 4-74

"OUT"

"OUT"

"OUT"

"OUT"

"OUT"

"OUT" "OUT"

"OUT"

"OUT" "OUT"

Z131

"OUT"

"OUT"

"OUT"

Z174

PREP 4-68

N111

"OUT"

"OUT"

Z167

Z129

"OUT"

OPERATING 4-71

Z162

"OUT"

"OUT"

Z141 Z143 Z142

N109

"OUT"

OPERATING 4-69

N112

"OUT"

"OUT"

"OUT" "OUT"

"OUT"

"OUT"

"OUT" Z183

"OUT"

"OUT"

"OUT"

"OUT"

"OUT" "OUT"

N130

"OUT" "OUT"

N137

Project #7R120760

N119

N131

"OUT"

Medical Sciences Building Fourth Floor

N125

N123

N129 N110

Large Animal Surgery and Germ Free Facility

N124

N128

"OUT"

"OUT"

N126 N127

"OUT"

Project For

LAB 4-65

"OUT"

"OUT"

07.03.13

N117

N113

N118

Z181

"OUT"

"OUT" "OUT"

"OUT"

11902

N115

N136

OPERATING Z182 4-67

"OUT" "OUT" "OUT"

"OUT"

"OUT" "OUT"

Z128

"OUT"

"OUT"

"OUT"

"OUT"

Z163

"OUT"

"OUT"

"OUT"

Z161

"OUT"

Z130

Z165

OPERATING 4-73

"OUT"

"OUT"

EQUIPMENT 4-65A

"OUT"

"OUT"

"OUT"

4-70

"OUT"

Z160

"OUT"

N114

"OUT" EQUIPMENT

"OUT"

"OUT"

DAVID NORBCK

Date

"OUT"

LOCKER RM 4-01A

Signature Registration Number

PREP 4-72

"OUT"

07.03.13

I hereby certify that this plan, specification or report was prepared by me or under my direct supervision and that I am a duly licensed Architect under the laws of the State of Minnesota.

ELECTRIC 4-00B-1

CORRIDOR 4-004B

11902

Date

CLOSET 4-004-1 CORRIDOR 4-004

DAVID NORBACK

N121 A

N132

"OUT"

LAB 4-66 N120

N122

N133

B

KEY PLAN

N139

Project No.

6287.040.04

Drawn By

1

PARTIAL FOURTH LEVEL DEMOLITION EQUIPMENT PLAN - AREA B

Checked By

1/4" = 1'-0"

Date

JHA/MLK 07/03/13

NOTICE: The designs shown and described herein including all technical drawings, graphics, and models thereof, are proprietary and cannot be copied, duplicated or commercially exploited, in whole or in part, without express written permission of RSP Architects. These are available for limited review and evaluation by clients, consultants, contractors, government agencies, vendors and office personnel only in accordance with this Notice.

DEMOLITION PLAN LEGEND: EXISTING PARTITION TO REMAIN

JAS

ROOM NAME

ROOM TAG

1i

EXISTING FURNITURE TO BE RELOCATED, REFER TO FURNITURE SCHEDULE

© Copyright RSP Architects 2007. All rights reserved.

Revisions EXISTING DOOR AND FRAME TO REMAIN

"OUT"

1

KEYNOTE

EXISTING PARTITION, CASEWORK, SHELVING, EQUIPMENT TO BE REMOVED

1i

EQUIPMENT TO BE RELOCATED, REFER TO EQUIPMENT SCHEDULE

EXISTING DOOR AND FRAME TO BE REMOVED

A

SPECIALTY EQUIPMENT TO BE RELOCATED, REFER TO SPECIALTY EQUIPMENT SCHEDULE

EXISTING FURNITURE AND EQUIPMENT TO BE REMOVED AND RETURNED TO OWNER'S STOCK.

No.

Date

Description

PARTIAL FOURTH LEVEL DEMOLITION EQUIPMENT PLAN - AREA B

D204B C:\Revit Projects\Med Sci 4 Central_jschmit.rvt 7/8/2013 11:23:10 AM

Please purchase PDF Split-Merge on www.verypdf.com to remove this watermark.


5

2

35

A902

P

33

TOILET/ CHANGE 4-11A

O

4-11A

VESTIBULE/ LOCKER

2

G

2

M

3

10' - 0"

9' - 9 1/2"

5"

4-12D

E

6

D

J

A901

5"

B57-PL

9

13

B

2

O

5"

OFFICE

N

A

2

B

A902 8

3

A901

9

B57-PL 15

N

11' - 9"

N

4

21

8

E

1

4-12-2

N

B

B

2

A901 C37-PL

B

OFFICE

B57-PL

5"

29

5' - 0"

5"

10' - 0"

17

ENLARGED TOILET/CHANGE ROOM PLAN

A901 27

1/2" = 1'-0"

9

B57-PL

9

28

A901

4-26

Dr. McGregor

16' - 1"

24

4-12-3

31

D

33

10

1

A901

B

8' - 9 1/2"

3 9' - 7 1/4"

5' - 2"

B

J

A901

FLEX LAB (MICROBIOME)

9

B57-PL

16

26

9 1' - 0"

5' - 0" O

3

E

L 3

O

M

3

3

M

07.03.13

Project For

3

2

6' - 3"

CORRIDOR

B

4-04-5

1

2

N O

2

4-24

E TYP.

8 A301

1 U

2

B

11

26

TOILET/ CHANGE

4-24

2 B

2

B

14 4-16

Medical Sciences Building Fourth Floor

2

Project #7R120760

N O

2

E

2

1

2

M1

5

O N

19

4

A903

OFFICE

4-15

4-11A

M1

N

5" 4-04-4

4-11

4

Large Animal Surgery and Germ Free Facility

2

M

M1

O N

A

3

2 B

OFFICE

2

CORRIDOR 4-04-3

4-23

VESTIBULE/ LOCKER

A903

KEY PLAN

7

4-11

Project No. Drawn By

1/4" = 1'-0"

Checked By

NORTH FLOOR PLAN LEGEND:

KEYNOTES - FLOOR PLAN

1. LOCATION OF EQUIPMENT SUCH AS UMBILICAL, FUME HOODS, BRACES, OR ANY OTHER ITEMS THAT MAY INTERFERE WITH THE LIGHTING, STRUCTURAL, OR MECHANICAL SYSTEMS, SHALL BE CAREFULLY COORDINATED AND DISCREPANCIES BROUGHT TO THE ARCHITECTS ATTENTION IMMEDIATELY.

EXISTING PARTITION TO REMAIN

2. WALL SHELVING OR REAGENT SHELVING SUPPORTS SHALL BE SPACED AND POSITIONED TO CLEAR FITTINGS, ELECTRICAL PEDESTALS, SINKS AND CUP SINKS.

EXISTING DOOR AND FRAME TO REMAIN

3. OVERALL LENGTH OF TOPS SHALL BE DETERMINED BY CASEWORK AND DIMENSIONS AS INDICATED ON PLANS. TOPS SHALL OVERHANG ½” AT EACH END AND 1” FROM FRONT OF BASE CABINET. WHEN OVERALL DIMENSIONS ARE GIVEN, ½” OVERHANG IS NOT INCLUDED.

ROOM NAME

9. PLUMBING FITTINGS OTHER THAN THOSE IN THE FUME HOODS OR FUME HOOD BASE CABINETS SHALL BE SUPPLIED AND INSTALLED BY MECHANICAL CONTRACTOR. ALL PLUMBING FITTINGS SHALL HAVE FINAL CONNECTION BY MECHANICAL CONTRACTOR. 10. ALL PLUMBING SYSTEM HANGERS AND FASTENERS SHALL BE PROVIDED AND INSTALLED BY MECHANICAL CONTRACTOR. 11. ALL LABORATORY SINKS AND CUP SINKS SHALL BE FURNISHED BY LAB CASEWORK CONTRACTOR. FINAL CONNECTION BY MECHANICAL CONTRACTOR. 12. FUME HOODS WILL BE PRE-PLUMBED AND PRE-WIRED. 13. ALL EXPOSED PIPING AND CONDUIT SHALL BE PAINTED TO MATCH THE ADJACENT SURFACE. 14. ALL PENETRATIONS THROUGH COUNTERTOP SHALL BE SEALED BY LAB FURNISHINGS CONTRACTOR WITH ACID RESISTANT SEALANT. 15. ALL PLAN DIMENSIONS LOCATING INTERIOR WALLS ARE TO: a: FACE OF EXISTING WALL SYSTEM UNLESS NOTED OTHERWISE. b: FACE OF GYPSUM BOARD UNLESS NOTED OTHERWISE. c: CENTERLINE OF BUILDING GRID.

ROOM TAG

2

1i

KEYNOTE

1

18. EXISTING PENETRATIONS IN RATED PARTITIONS TO BE FIRESTOPPED & SEALED. NEW MECHANICAL / ELECTRICAL PENETRATIONS TO BE FIRESTOPPED & SEALED. ALL SUBCONTRACTORS TO USE THE SAME FIRESTOPPING SYSTEM.

Please purchase PDF Split-Merge on www.verypdf.com to remove this watermark.

NEW PARTITION AS SCHEDULED, SEE MAYO SPECIFICATIONS SECTION 09200 FOR PARTITION CONSTRUCTION

COUNTERTOP TAG

1i

EQUIPMENT TAG

A

SPECIALITY EQUIPMENT TAG

3 4 5 6

8

TAG B C.1 C.2 D E G

G1 GB-18 GB-36 GB-42 H J K K1 K2 K3 L

DESCRIPTION

SPECIALTY EQUIPMENT SCHEDULE ORDERED BY SUPPLIED BY INSTALLED BY

M M1 N O

9 10

QTY

TO ROOM

TOILET PAPER DISPENSER SANITARY PRODUCT DISPOSAL SANITARY PRODUCT DISPENSER SOAP DISPENSER PAPER TOWEL DISPENSER 24" X 60" MIRROR

4 2 1 8 8 3

CONTRACTOR CONTRACTOR CONTRACTOR CONTRACTOR CONTRACTOR CONTRACTOR

FACILITIES WAREHOUSE FACILITIES WAREHOUSE FACILITIES WAREHOUSE FACILITIES WAREHOUSE FACILITIES WAREHOUSE MANUFACTURER

CONTRACTOR CONTRACTOR CONTRACTOR CONTRACTOR CONTRACTOR CONTRACTOR

GEORGIA PACIFIC - MODEL #56784 ASI - MODEL #0852 ROCHESTER MIDLAND - MODEL #C2591100J655 DERMAPRO - MODEL #9021-ALMOND GEORGIA PACIFIC - MODEL #59462 TSM - MODEL #M-1

12" x 24" MIRROR GRAB BARS GRAB BARS GRAB BARS COAT HOOK 30" X 36" DRYING RACK 36" x 48" WHITEBOARD 48" x 36" WHITEBOARD 48" x 48" WHITEBOARD 72" x 48" WHITEBOARD METAL LOCKERS

1 3 3 3 3 4 1 2 1 1 16

SEE PLAN 4-03, 4-11A 4-03 4-02, 4-03, 4-11A 4-02, 4-03, 4-11A 236, 238, 274A (2), 274B (2) & 280F 4-10 SEE PLAN SEE PLAN SEE PLAN SEE PLAN SEE PLAN 4-10D SEE PLAN 4-15 4-10A 4-11

CONTRACTOR CONTRACTOR CONTRACTOR CONTRACTOR CONTRACTOR CONTRACTOR --------CONTRACTOR

MANUFACTURER FACILITIES WAREHOUSE FACILITIES WAREHOUSE FACILITIES WAREHOUSE MANUFACTURER MANUFACTURER --------MANUFACTURER

CONTRACTOR CONTRACTOR CONTRACTOR CONTRACTOR CONTRACTOR CONTRACTOR CONTRACTOR CONTRACTOR CONTRACTOR CONTRACTOR CONTRACTOR

48" x 36" CORKBOARD 60" x 16" CORKBOARD CABLE MANAGEMENT TRAY CPU CLIP AND BRACKET

2 10 31 31

SEE PLAN SEE PLAN SEE PLAN SEE PLAN

--CONTRACTOR CONTRACTOR CONTRACTOR

--MANUFACTURER MANUFACTURER MANUFACTURER

CONTRACTOR CONTRACTOR CONTRACTOR CONTRACTOR

MOUNT AT 3'-6" A.F.F. BOBRICK - SERIES B - 6806 BOBRICK - SERIES B - 6806 BOBRICK - SERIES B - 6806 SEE SHEET A921 FOR MOUNTNG DETAILS MOUNT AT 3'-6" A.F.F. SALVAGED, RE-MOUNT AT EXISTING LOCATION AND HEIGHT SALVAGED, RE-MOUNT AT EXISTING LOCATION AND HEIGHT SALVAGED, MOUNT AT 3'-0" A.F.F. SALVAGED, RE-MOUNT AT EXISTING LOCATION AND HEIGHT REPUBLIC DOUBLE TIER STANDARD LOCKER(12"X12"X36"), COLOR: #83 DECORATOR TAN, KT DIGILOCK SALVAGED, MOUNT AT 3'-0" A.F.F. MOUNT AT 2'-6" A.F.F. SEE REFERENCE STANDARD 5324-01 AND 5324-02 SEE REFERENCE STANDARD 5324-01 AND 5324-02

16. ALL ELEVATION MEASUREMENTS ARE IN REFERENCE TO THE FINISHED FLOOR. 17. SEE LIFE SAFETY PLANS, SHEETS "G103" FOR ALL RATED PARTITION LOCATIONS.

1 DOOR TAG

NEW DOOR, REFER TO DOOR SCHEDULE

6. ALL EXPOSED TO VIEW COUNTERTOP EDGES, BACK OF SPLASHES, ALL EDGES OF TABLES, BACKS OF COUNTERTOPS AND SPLASHES HELD AWAY FROM WALL SHALL BE FILLED, SEALED AND FINISHED.

8. ALL CASEWORK, FUME HOODS AND ANY OTHER FURNISHINGS WITH EXPOSED TO VIEW AND SIDES SHALL BE FINISHED.

101

7

5. COUNTERTOPS AND SPLASHES SHALL BE SEALED TO THE WALLS.

7. FILLER PANELS SHALL BE USED BETWEEN BACK OF CABINETS OR HOODS AND WALLS AT EXPOSED ENDS AND WHEN BASE CABINETS AND/OR HOODS ARE SET BACK TO BACK. FILLER SHALL OCCUR EVEN WHERE NO BASE CABINETS OCCURS BUT BENCH IS PRESENT.

1 C31-PL

NEW PARTITON

4. OVERALL HEIGHT OF BASE CABINETS MUST BE AS SHOWN ON DRAWINGS (NOMINAL HEIGHT).

C:\Revit Projects\Med Sci 4 Central_jschmit.rvt 7/8/2013 11:22:43 AM

Date

PARTIAL FOURTH LEVEL FLOOR PLAN AREA A

FLOOR PLAN GENERAL NOTES

11902

2

E

O N

3' - 8" MIN

5' - 0"

CORRIDOR

2

2

DAVID NORBCK

5

4-12-3

1

21

2

5"

2

14

2

4-25

B57-PL

5"

2' - 10" B

2

L

1

5"

4-12A

C31-PL

M

2' - 6"

L

11' - 2 1/2"

TISSUE CULTURE

16

07.03.13

Registration Number

M1

A903

OFFICE

A901

4-12

8"

1' - 0"

4' - 11 1/2" 1' - 0"

6' - 1"

8

B

20

A901

N O

2

4

TYP.

2' - 6"

4-12A

19

2

A903

Date

Signature

M

E

22

32

N

4

3

11902

I hereby certify that this plan, specification or report was prepared by me or under my direct supervision and that I am a duly licensed Architect under the laws of the State of Minnesota.

E

4-25

E 25

22

5"

2

Registration Number

N O

5

D

9' - 9 1/2"

M

A901

2

DAVID NORBACK

J

E

18

B

2

6 9

A903

B TYP.

LAB

M

2

N O

2

30

1

M1

M1

OFFICE

A901

3

3

4-26

5"

B57-PL

2

14' - 0"

23

2

2

4-27

B

A901

2

I hereby certify that I have reviewed the Mayo Clinic Standard General Specifications prepared by Ronald B. Carlson, License Number 10850, that they are appropriate for the work except as amended in this plan, specification or report, and that I am a duly licensed Architect under the laws of the State of Minnesota.

4-27

16' - 0"

Dr. Nyberg

Certification

Signature

2

C31-PL

9' - 9"

2

SIT-DOWN

O

A901

16

B

2

N

LAB 4-12

4-28

O

22

4-06C

B

E

O

C37-PL

4-11B

4-28

O

5" M

7

4

5"

2

EQUIPMENT

O

10' - 0"

B

2

14

2

ELEC RM 4-004D-2

14

4' - 11 1/2" +/-

B

6

5"

Consultants

2

N O

N

4-06C

L

5' - 0"

4-12-2

4' - 6 1/2"

5' - 8 1/2"

2' - 7"

2

5"

SIT-DOWN

5"

B

B

9' - 7"

4-12-1

L

2

11

4-12D

4' - 5"

ELEC RM 4-004D-1

14

A901

5"

4-12C

1' - 10"

A901

4

9' - 7"

4-12B

12

2

5"

B

9 10

7' - 8 1/2"

RSP Architects 320 South Broadway Ste. B 507.285.6569 Rochester, Minnesota 55904 612.677.7499 fax www.rsparch.com

DN

TISSUE CULTURE

4

15

4-11

C31-PL

A901

4-12B

8

B57-PL

22

M

1' - 3"

1' - 0"

Dr. V. Miller

D E

2

MICROSCOPY

4"

O

GB-36

4-12C

8

A901

6

A901

8

STORAGE 4-49A

5"

16' - 6"

4

8

TISSUE CULTURE

2' - 6"

5"

A901

2

8' - 4"

3

2

1

16

5"

A901

B

2

7

36

34

L

1

2

2

8' - 4"

2

2

2' - 8"

E

B

1

5"

P

L

B

E

8' - 4"

4-11

9

2 4' - 1"

4"

GB-18

B57-PL

14' - 9 1/2"

1' - 6"

9"

C31-PL GB-42

2

C31-PL

5"

C31-PL

8' - 4"

A28-PL

UP

STAIR 4-49B

5"

9

B

13' - 7"

2

2

C31-PL

2

5"

2

B

5' - 7"

E

U

8

9' - 3"

2

1' - 5"

5' - 4 1/2"

O

4"

1' - 0"

7' - 3"

12' - 1"

2

NOTE: SEE SHEET A921 FOR ACCESSORY MOUNTING DIAGRAM

9' - 7"

B

5"

5' - 0"

4' - 0"

4"

E

4"

6' - 1"

2' - 8 1/2" +/-

REMARKS 11 12 13 14 15 16 17 18 19 20 21 22 23 24

25 26 27

FACE OF NEW WALL TO BE ALIGNED WITH FACE OF EXISTING WALL. DASHED LINES INDICATE 12" DEEP ADJUSTABLE PLASTIC LAMINATE SHELVING ABOVE - SEE ELEVATIONS AND DETAILS. WALL HOOK FOR CLIPPERS - SEE DETAIL 15/A920. STAINLESS STEEL SINK - SEE MECHANICAL DRAWINGS EXISTING SCRUB SINK TO REMAIN. STAINLESS STEEL SINK AND TOP - SEE MECHANICAL DRAWINGS MOP SINK - SEE ELEVATIONS - SEE PLUMBING DRAWINGS. DASHED LINES INDICATE WALL CABINETS ABOVE SEE ELEVATIONS AND DETAILS REAGENT SHELVING - SEE ELEVATIONS STAINLESS STEEL SINK AND TOP W/ DRAINBOARDSEE MECHANICAL DRAWINGS STANDARD LAB COAT HOOK STRIP - SEE DETAIL 15/A920 ELECTRIC WATER COOLER - COORDINATE W/ MECHANICAL & ELECTRICAL RELOCATED SCRUB SINK - COORDINATE W/ MECHANICAL WALL MOUNTED FIRE EXTINGUISHER. NITROGEN TANK - BY OWNER. PLASTIC LAMINATE PIPETTE RACK - SEE ELEVATIONS SURFACE APPLY LAYER OF 5/8" GYPSUM BOARD TO EXISTING WALL CONSTRUCTION WALL MOUNTED SINK - SEE MECHANICAL WALL MOUNTED TOILET - SEE MECHANICAL WALL MOUNTED URINAL - SEE MECHANICAL GAS CYLINDER RACK AND HOOK - SEE DETAIL 13/A920 PLASTIC LAMINATE VENT CHASE - SEE DETAIL 9/A920 CEILING MOUNTED AIR HOSE AND REEL - CORDINATE W/MECHANICAL DASHED LINES INDICATE 18" DEEP ADJUSTABLE PLASTIC LAMINATE SHELVING ABOVE - SEE ELEVATIONS AND DETAILS. WALL MOUNTED TV MONITOR - BY A.V. A.V. CABINET - SEE DETAIL 5/A921. APPLY 3/4" FIRE RATED PLYWOOD TO BACK WALL OF CLOSET.

6287.040.04 JAS JHA/MLK

Date

07/03/13

NOTICE: The designs shown and described herein including all technical drawings, graphics, and models thereof, are proprietary and cannot be copied, duplicated or commercially exploited, in whole or in part, without express written permission of RSP Architects. These are available for limited review and evaluation by clients, consultants, contractors, government agencies, vendors and office personnel only in accordance with this Notice. © Copyright RSP Architects 2007. All rights reserved.

Revisions No.

Date

Description

PARTIAL FOURTH LEVEL FLOOR PLAN - AREA A

A104A


2

18

4-11A

4-11

3

L

2

2

4

1' - 6 1/2"

8

A902

2

B

5

B

UP

2

M

4-04A

B

3

M

1' - 1"

M

4-03

TOILET MEN

2' - 1"

TOILET WOMEN

4-02 O

4-03M

3

4

P

E

17

12

B

1' - 5"

1' - 5"

3

P

C31-PL

17

A902

2

4-10-1

19

3

11' - 1 1/2"

C31-PL

B

2

5"

5"

Consultants

Certification

N

4-21

18

5"

1

CLEAN STORAGE

B

2

I hereby certify that I have reviewed the Mayo Clinic Standard General Specifications prepared by Ronald B. Carlson, License Number 10850, that they are appropriate for the work except as amended in this plan, specification or report, and that I am a duly licensed Architect under the laws of the State of Minnesota.

M1

10' - 9" B

2

4-20

E

2

2 Signature

13

4-20

B

2

B

4-04-5

L

B

E

TYP.

B

1' - 6 1/2"

4-10C

3

19

2

A902

SCRUB 4-10-2

21

20

1

2

B

11

2

O

2

C31-PL

4-10F

1

6

J

B

ORTHO PREP 4-10F

2

C31-PL

2

4' - 1"

2

2

2

N

2

23

A902

PREP ROOM

4

3 4

22

8

E

4-10H

5 6

2

7 8

C31-PL

9 10

4-10HA

1

K1

B

2

11

B

2

12

2

13

14

14 15 16 17

K

OPERATING ROOM 4-10A

ORTHO OPERATING ROOM

OPERATING ROOM

OPERATING ROOM

4-10D

4-10B

GERM FREE FACILITY

K1

4-10E

4-10HA

E

18 19 20 21

2

22 23

23

K3

2

07.03.13

I hereby certify that this plan, specification or report was prepared by me or under my direct supervision and that I am a duly licensed Architect under the laws of the State of Minnesota.

M1

KEYNOTES - FLOOR PLAN 2

11902

Date

5

1

17

2 A104B

DAVID NORBACK

Registration Number

2

4

A903

4-10H

STORAGE

11 L

O

A902

16

5

SCRUB 4-10

3

2

2

O

SECRETARY

A902

5"

2' - 10 1/2"

G1

19

1

2

2

1

L

2

E 2

5

17

4-10C

4-06

2 2

4

A903

N

B

15

1 B

CORRIDOR

17 3

2

ELECTRIC 4-004B-1

2

PREP AREA

B

2

N

3

M1

4-22

24

19 P

24

2

3

20

10' - 9 3/4"

17

M

18

3

12

2

RSP Architects 320 South Broadway Ste. B 507.285.6569 Rochester, Minnesota 55904 612.677.7499 fax www.rsparch.com

OFFICE

4-06B

18

1

A902

5

M

A902

OFFICE

4-10G

2' - 10 1/2"

3

1

1' - 7"

O

11' - 7 1/2"

D

25

N

O

B

1

2

B

4-04-5

14

157°

4-04

4-01

C25-PL

N

2

CORRIDOR

4-02

2

10

1' - 2"

6' - 7 1/2"

BREAK ROOM

2

4-22

TYP.

4-10G

1' - 4"

B

O

2

M1

CORRIDOR

4-06A

14 6' - 7 1/2"

4-01

17

3

27 4-04A

4-06B

N

2

13

B

2

2

9

SURGICAL TECHS

1

B

CLOSET

O

B

A902

N

2

4-04

STAIR 4-08

CLOSET 4-04-1

2

C31-PL

8

3

14

2' - 8"

4

DN

4-11B

4-06A

4' - 6"

4-04-2

B

4-06C

B

O

B

E

4-23

2 O

5"

SOILED WORK

CORRIDOR

4-15

O

7' - 2"

D

7

A903

N

2

CONFERENCE

2

8

12

A902

N

K2

4-23

N

O 11

N

M

4-16

OFFICE 4-06C

6

OFFICE

FLEX OFFICE

O

E

B

O

1

5"

STORAGE 4-07

B

N

4-09

3

O N

A,G,V

CLEAN LINEN SUPPLY

L

VESTIBULE/ LOCKER

M1

8' - 4"

CORRIDOR 4-04-3

19

2

1

N

5"

4-05

2

O

8' - 4"

M

4-11

M

5"

MECHANICAL

26

TOILET/ CHANGE

2

4-16

8' - 5"

A902

2

B

14

5"

2

11

3' - 8"

2

B

2' - 0"

2' - 10" L

4-09

2

4-15

4-11A

7 32

1

21

10' - 1"

3

2

B

N O

5"

E

B

2

5"

L

4-04-4

2

13' - 2"

3

5"

4-12A

C31-PL

M

2' - 6"

U

9' - 0"

TISSUE CULTURE

8 A301

CORRIDOR

5"

2 A104A

1

24

21

2' - 4"

25 26 27

FACE OF NEW WALL TO BE ALIGNED WITH FACE OF EXISTING WALL. DASHED LINES INDICATE 12" DEEP ADJUSTABLE PLASTIC LAMINATE SHELVING ABOVE - SEE ELEVATIONS AND DETAILS. WALL HOOK FOR CLIPPERS - SEE DETAIL 15/A920. STAINLESS STEEL SINK - SEE MECHANICAL DRAWINGS EXISTING SCRUB SINK TO REMAIN. STAINLESS STEEL SINK AND TOP - SEE MECHANICAL DRAWINGS MOP SINK - SEE ELEVATIONS - SEE PLUMBING DRAWINGS. DASHED LINES INDICATE WALL CABINETS ABOVE SEE ELEVATIONS AND DETAILS REAGENT SHELVING - SEE ELEVATIONS STAINLESS STEEL SINK AND TOP W/ DRAINBOARDSEE MECHANICAL DRAWINGS STANDARD LAB COAT HOOK STRIP - SEE DETAIL 15/A920 ELECTRIC WATER COOLER - COORDINATE W/ MECHANICAL & ELECTRICAL RELOCATED SCRUB SINK - COORDINATE W/ MECHANICAL WALL MOUNTED FIRE EXTINGUISHER. NITROGEN TANK - BY OWNER. PLASTIC LAMINATE PIPETTE RACK - SEE ELEVATIONS SURFACE APPLY LAYER OF 5/8" GYPSUM BOARD TO EXISTING WALL CONSTRUCTION WALL MOUNTED SINK - SEE MECHANICAL WALL MOUNTED TOILET - SEE MECHANICAL WALL MOUNTED URINAL - SEE MECHANICAL GAS CYLINDER RACK AND HOOK - SEE DETAIL 13/A920 PLASTIC LAMINATE VENT CHASE - SEE DETAIL 9/A920 CEILING MOUNTED AIR HOSE AND REEL - CORDINATE W/MECHANICAL DASHED LINES INDICATE 18" DEEP ADJUSTABLE PLASTIC LAMINATE SHELVING ABOVE - SEE ELEVATIONS AND DETAILS. WALL MOUNTED TV MONITOR - BY A.V. A.V. CABINET - SEE DETAIL 5/A921. APPLY 3/4" FIRE RATED PLYWOOD TO BACK WALL OF CLOSET.

Signature

DAVID NORBCK

Registration Number

11902

Date

07.03.13

Project For

Large Animal Surgery and Germ Free Facility Medical Sciences Building Fourth Floor Project #7R120760 A

B

1 5"

PARTIAL FOURTH LEVEL FLOOR PLAN AREA B 1/4" = 1'-0"

Project No.

19' - 5 1/2" O

4-02

5"

KEY PLAN

NORTH M

3

O

1' - 1"

3

FLOOR PLAN LEGEND: ROOM NAME

EXISTING PARTITION TO REMAIN

4-03

101

1' - 8"

1' - 8" 4-02

EXISTING DOOR AND FRAME TO REMAIN

2' - 6"

D

TOILET WOMEN

6' - 10 1/2"

2' - 6"

D

1' - 6"

G

Checked By

24

A902

26

1' - 4"

4"

3 H

29

5' - 0" 28

2' - 11"

27

C.1

C.2

5' - 1"

GB-36

5' - 0"

P

8' - 3"

2

H

2

H

5' - 1"

GB-36

GB-42

P

2

B C.1

3

ENLARGED RESTROOM PLAN 1/2" = 1'-0"

C:\Revit Projects\Med Sci 4 Central_jschmit.rvt 7/8/2013 11:22:46 AM

Please purchase PDF Split-Merge on www.verypdf.com to remove this watermark.

1' - 6"

9 1/8" 4"

2

E

2

GB-18

1' - 6"

B

P

30

A902 31

B

P

1i

KEYNOTE

1

NEW PARTITION AS SCHEDULED, SEE MAYO SPECIFICATIONS SECTION 09200 FOR PARTITION CONSTRUCTION

1i

EQUIPMENT TAG

A

SPECIALITY EQUIPMENT TAG

FLOOR PLAN GENERAL NOTES 1. WALL SHELVING OR REAGENT SHELVING SUPPORTS SHALL BE SPACED AND POSITIONED TO CLEAR FITTINGS, ELECTRICAL PEDESTALS, AND SINKS.

3

TAG B C.1 C.2 D E G

G1 GB-18 GB-36 GB-42 H J K K1 K2 K3 L M M1 N O

GB-18 GB-42

DESCRIPTION

SPECIALTY EQUIPMENT SCHEDULE ORDERED BY SUPPLIED BY INSTALLED BY

07/03/13

NOTICE: The designs shown and described herein including all technical drawings, graphics, and models thereof, are proprietary and cannot be copied, duplicated or commercially exploited, in whole or in part, without express written permission of RSP Architects. These are available for limited review and evaluation by clients, consultants, contractors, government agencies, vendors and office personnel only in accordance with this Notice.

COUNTERTOP TAG

NEW DOOR, REFER TO DOOR SCHEDULE

M

8' - 11" +/-

E

2' - 9"

13' - 7 3/8" +/-

25

4"

3' - 0 7/8"

7' - 8"

JHA/MLK

ROOM TAG

G

P 3

1 C31-PL

NEW PARTITON

4-03

O

JAS

Date

TOILET MEN

5"

Drawn By

DOOR TAG

E

4-02

6287.040.04

© Copyright RSP Architects 2007. All rights reserved.

Revisions No.

Date

Description

2. OVERALL LENGTH OF TOPS SHALL BE DETERMINED BY CASEWORK AND DIMENSIONS AS INDICATED ON PLANS. TOPS SHALL OVERHANG ½” AT EACH END AND 1” FROM FRONT OF BASE CABINET. WHEN OVERALL DIMENSIONS ARE GIVEN, ½” OVERHANG IS NOT INCLUDED.

QTY

TO ROOM

REMARKS

TOILET PAPER DISPENSER SANITARY PRODUCT DISPOSAL SANITARY PRODUCT DISPENSER SOAP DISPENSER PAPER TOWEL DISPENSER 24" X 60" MIRROR

4 2 1 8 8 3

CONTRACTOR CONTRACTOR CONTRACTOR CONTRACTOR CONTRACTOR CONTRACTOR

FACILITIES WAREHOUSE FACILITIES WAREHOUSE FACILITIES WAREHOUSE FACILITIES WAREHOUSE FACILITIES WAREHOUSE MANUFACTURER

CONTRACTOR CONTRACTOR CONTRACTOR CONTRACTOR CONTRACTOR CONTRACTOR

GEORGIA PACIFIC - MODEL #56784 ASI - MODEL #0852 ROCHESTER MIDLAND - MODEL #C2591100J655 DERMAPRO - MODEL #9021-ALMOND GEORGIA PACIFIC - MODEL #59462 TSM - MODEL #M-1

12" x 24" MIRROR GRAB BARS GRAB BARS GRAB BARS COAT HOOK 30" X 36" DRYING RACK 36" x 48" WHITEBOARD 48" x 36" WHITEBOARD 48" x 48" WHITEBOARD 72" x 48" WHITEBOARD METAL LOCKERS

1 3 3 3 3 4 1 2 1 1 16

SEE PLAN 4-03, 4-11A 4-03 4-02, 4-03, 4-11A 4-02, 4-03, 4-11A 236, 238, 274A (2), 274B (2) & 280F 4-10 SEE PLAN SEE PLAN SEE PLAN SEE PLAN SEE PLAN 4-10D SEE PLAN 4-15 4-10A 4-11

CONTRACTOR CONTRACTOR CONTRACTOR CONTRACTOR CONTRACTOR CONTRACTOR --------CONTRACTOR

MANUFACTURER FACILITIES WAREHOUSE FACILITIES WAREHOUSE FACILITIES WAREHOUSE MANUFACTURER MANUFACTURER --------MANUFACTURER

CONTRACTOR CONTRACTOR CONTRACTOR CONTRACTOR CONTRACTOR CONTRACTOR CONTRACTOR CONTRACTOR CONTRACTOR CONTRACTOR CONTRACTOR

48" x 36" CORKBOARD 60" x 16" CORKBOARD CABLE MANAGEMENT TRAY CPU CLIP AND BRACKET

2 10 31 31

SEE PLAN SEE PLAN SEE PLAN SEE PLAN

--CONTRACTOR CONTRACTOR CONTRACTOR

--MANUFACTURER MANUFACTURER MANUFACTURER

CONTRACTOR CONTRACTOR CONTRACTOR CONTRACTOR

MOUNT AT 3'-6" A.F.F. BOBRICK - SERIES B - 6806 BOBRICK - SERIES B - 6806 BOBRICK - SERIES B - 6806 SEE SHEET A921 FOR MOUNTNG DETAILS MOUNT AT 3'-6" A.F.F. SALVAGED, RE-MOUNT AT EXISTING LOCATION AND HEIGHT SALVAGED, RE-MOUNT AT EXISTING LOCATION AND HEIGHT SALVAGED, MOUNT AT 3'-0" A.F.F. SALVAGED, RE-MOUNT AT EXISTING LOCATION AND HEIGHT REPUBLIC DOUBLE TIER STANDARD LOCKER(12"X12"X36"), COLOR: #83 DECORATOR TAN, KT DIGILOCK SALVAGED, MOUNT AT 3'-0" A.F.F. MOUNT AT 2'-6" A.F.F. SEE REFERENCE STANDARD 5324-01 AND 5324-02 SEE REFERENCE STANDARD 5324-01 AND 5324-02

3. OVERALL HEIGHT OF BASE CABINETS MUST BE AS SHOWN ON DRAWINGS (NOMINAL HEIGHT). 4. COUNTERTOPS AND SPLASHES SHALL BE SEALED TO THE WALLS. 5. ALL EXPOSED TO VIEW COUNTERTOP EDGES, BACK OF SPLASHES, ALL EDGES OF TABLES, BACKS OF COUNTERTOPS AND SPLASHES HELD AWAY FROM WALL SHALL BE FILLED, SEALED AND FINISHED. 6. FILLER PANELS SHALL BE USED BETWEEN BACK OF CABINETS AND WALLS AT EXPOSED ENDS AND WHEN BASE CABINETS ARE SET BACK TO BACK. FILLER SHALL OCCUR EVEN WHERE NO BASE CABINETS OCCURS BUT BENCH IS PRESENT. 7. ALL CASEWORK AND ANY OTHER FURNISHINGS WITH EXPOSED TO VIEW AND SIDES SHALL BE FINISHED. 8. ALL PLAN DIMENSIONS LOCATING INTERIOR WALLS ARE TO: a: FACE OF EXISTING WALL SYSTEM UNLESS NOTED OTHERWISE. b: FACE OF GYPSUM BOARD UNLESS NOTED OTHERWISE. c: CENTERLINE OF BUILDING GRID. 9. ALL ELEVATION MEASUREMENTS ARE IN REFERENCE TO THE FINISHED FLOOR. 10. SEE LIFE SAFETY PLANS, SHEETS FOR ALL RATED PARTITION LOCATIONS. 11. EXISTING PENETRATIONS IN RATED PARTITIONS TO BE FIRESTOPPED & SEALED. NEW MECHANICAL / ELECTRICAL PENETRATIONS TO BE FIRESTOPPED & SEALED. ALL SUBCONTRACTORS TO USE THE SAME FIRESTOPPING SYSTEM. 12. REFER TO SHEET A301 FOR DOOR SCHEDULE AND PARTITION TYPE KEY. 13. REFER TO SHEET A801 FOR EQUIPMENT SCHEDULES. 14. REFER TO SHEET A204 FOR RCP. NOTE: SEE SHEET A921 FOR ACCESSORY MOUNTING DIAGRAM

PARTIAL FOURTH LEVEL FLOOR PLAN - AREA B

A104B


TISSUE CULTURE

MICROSCOPY 4-12B

2

TISSUE CULTURE

4-12C

REFLECTED CEILING PLAN GENERAL NOTES:

4-12D

1. GENERAL CONTRACTOR TO COORDINATE ALL WORK OF ALL TRADES INVOLVED IN THE CEILING WORK TO INSURE CLEARANCES FOR FIXTURES, DUCTS, PIPING, CEILING SUSPENSION SYSTEMS, ETC. NECESSARY TO MAINTAIN THE FINISHED CEILING HEIGHTS INDICATED ON ARCHITECTS DRAWINGS.

S

STAIR

3

2

SD

2. VERIFY FIELD CONDITIONS AND LOCATIONS OF ALL PLUMBING, MECHANICAL DUCTS, STRUCTURAL ELEMENTS AND ANY OTHER APPLICABLE ITEMS. INSTALL NEW PLUMBING, MECHANICAL FANS, DUCTS, CONDUITS, AND OTHER RELATED ITEMS SO AS NOT TO CONFLICT WITH LUMINARIES.

4-49B

3. VERIFY ALL RECESS DEPTHS OF FIXTURES AGAINST A.C. DUCTS, PIPES, BEAMS, ETC. BEFORE ORDERING FIXTURES. SUBMIT SHOP DRAWINGS OF ALL FIXTURES TO ARCHITECT AND ENGINEER FOR APPROVAL.

2

SD

S

S

4. REMOVE ALL OBSTRUCTIONS FROM CEILING, INCLUDING ABANDONED CONDUITS, WIRES, DUCK WORK, ETC. NOT SCHEDULED FOR REUSE.

SD

2 1

2

LAB S

SD

2

S

SD

EQUIPMENT 4-28

S

SD

4-12

9

OS

5. ALL SPECIFIC INFORMATION CONCERNING INSTALLATION OF VARIOUS ABOVE-CEILING ELEMENTS ARE TO BE FOUND IN HVAC, PLUMBING, FIRE PROTECTION, ELECTRICAL AND LIGHTING DRAWINGS. REFER TO ENGINEERING DRAWINGS FOR FULL WORK SCOPE ON DIFFUSERS, RETURNS, SPRINKLERS, LIGHT SWITCHES, THERMOSTATS, FIRE ALARMS, STROBES, ETC. 6. REFER TO ENGINEERING DRAWINGS FOR ALL LIFE SAFETY DEVICES REQUIRED BY CODE AND ALL EMERGENCY LIGHT FIXTURES. ARCHITECTURAL DRAWINGS SHALL GOVERN LOCATION OF THESE DEVICES.

SD

7. NOTIFY ARCHITECT OF ANY CONFLICTS OF LIGHT FIXTURE LOCATIONS WITH MAIN CEILING GRID RUNNERS, DUCTS, STRUCTURES, HVAC AND/OR ELECTRICAL CONDUIT, PRIOR TO FRAMING FOR LIGHTS. ANY DISCREPANCIES BETWEEN ARCHITECT'S CEILING GRID LOCATION AND ACTUAL FIELD CONDITIONS ARE TO BE CLARIFIED WITH THE ARCHITECT PRIOR TO FRAMING.

S

WAP

8

1

8. INSTALL LIGHT FIXTURES WITH PROTECTIVE FILM OR SIMILAR COVER OVER LOUVER, LENS, BAFFLE, AND THE LIKE, TO AVOID FIXTURE SOILING OR DAMAGE. FIXTURES SHALL BE KEPT CLEAN AND AS NEW. LAMPS SHALL BE NEW AT PROJECT COMPLETION.

OFFICE 4-27

2 OS

1

1

LAB

10. LIGHT FIXTURES, EXIT SIGNS, SPRINKLERS AND OTHER CEILING ELEMENTS SHALL BE LOCATED IN CENTER OF INDIVIDUAL CEILING TILE, U.N.O.

OFFICE

11. ALL SOFFITS AND CEILING HEIGHTS ARE DIMENSIONED FROM TOP OF FINISHED FLOOR TO BOTTOM OF GYB. BD. OR CEILING TILE AND SHALL ALLOW FOR THICKNESS OF ALL FLOOR FINISHES.

OS

2

SD

1

S

12. FIRE SAFETY MUST BE MAINTAIN FOR ALL PERSONNEL WORKING ON THE FLOOR. ALL FIRE STARS, ALARMS, SPEAKERS, ETC. MUST REMAIN ACCESSIBLE AND OPERABLE AT ALL TIMES. NOTIFY BUILDING FACILITIES MANAGER OF DAMAGED SYSTEMS AND REPAIR OR REPLACE DAMAGED SYSTEMS IMMEDIATELY.

OFFICE 4-25

CORRIDOR

4-09

MECHANICAL

2

VESTIBULE/ LOCKER

8

4

4-05A

4-05

1

4-11

3

2

OS

4-04-2

4-07

CONFERENCE

2

1

2

4-06B

4-08

4-04-1

S

4-04

1

OS

S

SD

4

S

4-01 1

TOILET WOMEN

OS TOILET MEN

4-03

4-10-1

4-10C

6' - 7"

6 5

7' - 4" 7

6

6' - 0"

7

OPERATING ROOM 4-10A

FOURTH LEVEL - REFLECTED CEILING PLAN

2

6' - 0"

5

2' - 11"

4-10B

12' - 3"

5

CENTER OF JOIST

CENTER OF JOIST

11902

Date

07.03.13

Project For

NEW SUSPENDED ACOUSTICAL CEILING SYSTEM (ACT-1) AT 8'-0" AFF. NEW SUSPENDED ACOUSTICAL CEILING SYSTEM (ACT-2) AT 8'-0" AFF. NO WORK IN THIS AREA. EXISTING GYPSUM CEILING TO REMAIN - PAINT PER ROOM FINISH SCHEDULE. EXISTING SUPPLY DIFFUSER TO REMAIN (PAINT) - SEE MECHANICAL DRAWINGS. REBURBISHED EXAM ROOM LIGHTS FROM WAREHOUSE - SEE DETAIL 3/A204 FOR STRUCTURAL SUPPORTS - SEE ELECTRICAL DRAWINGS FOR POWER REQUIREMENTS. DASHED LINE INDICATES LOCATION OF OPERATING TABLE BELOW. BULKHEAD AT 7'-11" A.F.F. - SEE DETAIL 2/A204 OVERHEAD SERVICES CARRIER - SEE DETAIL 5/A204.

4

GERM FREE FACILITY 4-10HA

4

LAY-IN ACOUSTICAL TILE CEILING SYSTEM - SEE REFLECTED CEILING PLANS

ORTHO OPERATING ROOM

OPERATING ROOM 4-10D

Large Animal Surgery and Germ Free Facility Medical Sciences Building Fourth Floor Project #7R120760

CEILING HEIGHT ELEV. 8'-0" A.F.F. BOTTOM OF BULKHEAD ELEV. 7'-11" A.F.F.

A

B

4-10E

1/8" = 1'-0" LESSER DIM TO

LINEAR DIFFUSER - SEE MECHANICAL

3 5/8" STEEL STUD FRAMING AT 16" OC

S

2 GREATER DIMENSION TO

OCCUPANCY SENSOR

Registration Number

5/8" GYP. BD.

6

OPERATING ROOM

RETURN AIR GRILLE - SEE MECHANICAL

2 SD

5' - 10"

4

FIRE ALARM

DAVID NORBCK

4-10H

S

7

5' - 10"

5' - 10"

5' - 10"

6

7 8 9

PREP ROOM

5

6

7

DIFFUSER - SEE MECHANICAL

2

4

5

1 2

4-10F

4-02 1

1

4-20

OS

4-10

OS

4-10-2

STORAGE

SCRUB

1 2 3 4 5 6

OFFICE

ORTHO PREP

SCRUB

Signature

EXIT SIGN

KEYNOTES - REFLECTED CEILING PLAN

S

SD

I hereby certify that this plan, specification or report was prepared by me or under my direct supervision and that I am a duly licensed Architect under the laws of the State of Minnesota.

EMERGENCY LIGHT FIXTURE - SEE ELECTRICAL SMOKE DETECTOR

1

OS

CORRIDOR

S

4-06

1

BREAK ROOM

SD

2

PREP AREA

SD

4-21

2

CORRIDOR

LIGHT FIXTURE - SEE ELECTRICAL

07.03.13

EXISTING SUSP. CEILING TILE AND GRID SYSTEM TO REMAIN

SECRETARY

4-10G

SD

11902

SPEAKER

NEW SUSP. CEILING TILE AND GRID SYSTEM

4-22

CLEAN STORAGE

CLOSET

OFFICE

S

SD

STAIR

WAP

OS

S

2

3

S

1

F

OS

1

SD

4-23

SD

4-06C

SURGICAL TECHS

S

OFFICE

OFFICE

2

SPRINKLER HEAD

1

4-16

4-15

S

S

SD

REFLECTED CEILING PLAN LEGEND

FLEX OFFICE

DAVID NORBACK

Date

SD S

Signature Registration Number

OS

OS

4-11A

4-06A

CORRIDOR

S

1

TOILET/ CHANGE

OS

SOILED WORK

STORAGE

SD

I hereby certify that I have reviewed the Mayo Clinic Standard General Specifications prepared by Ronald B. Carlson, License Number 10850, that they are appropriate for the work except as amended in this plan, specification or report, and that I am a duly licensed Architect under the laws of the State of Minnesota.

OFFICE 4-24

8

Certification

4"

2

1

4-04-4

WAP

S

SD

1

1"

4-12A CLEAN LINEN SUPPLY

S

SD

13. REMOVAL OF ANY EQUIPMENT, CABLING SWITCHES, AND CONDUIT PERTAINING TO DATA/COMMUNICATIONS AND TELEPHONE SHALL BE VERIFIED WITH TELEPHONE COMPANIES, SERVICE OWNER OR TENANT DATA/COMMUNICATIONS REPRESENTATIVE AS REQUIRED TO PREVENT NEW CONSTRUCTION DELAYS.

OS

4-04-5

TISSUE CULTURE

CUSTODIAL

S

CORRIDOR

2

Consultants

9. SWITCHES, THERMOSTATS, STROBES AND OTHER ELECTRICAL DEVICES ARE TO ALIGN ALONG THEIR CENTERLINE, WHEN DEVICES OCCUR IN THE PROXIMITY OF WALL OUTLETS. ALIGN OUTLETS WITH DEVICES ABOVE.

4-26

4-12-3

SD

RSP Architects 320 South Broadway Ste. B 507.285.6569 Rochester, Minnesota 55904 612.677.7499 fax www.rsparch.com

TYPICAL BULKHEAD DETAIL

NORTH

L3X3X1/4 WITH (2) 1/2" DIA HILTI KWIK BOLT 3 WITH 3 1/2" MIN EMBED

Project No.

5"

MIN.

KEY PLAN

1 1/2" = 1'-0"

6287.040.04

Drawn By L3X3X1/4 WITH (2) 3/8" DIA HILTI KWIK BOLT 3 WITH 1 5/8" MIN EMBED

Checked By

FIFITH FLOOR ELEV. 13'-9" A.F.F.

3 3/4"

FIFITH FLOOR ELEV. 13'-9" A.F.F.

1/4" THREADED ROD ANCHOR BOLT, TYP.

EXISTING CONCRETE FLOOR JOIST

CEILING BAFFLE, TYP

TS 4"X4"X1/4" STEEL TUBE WELDED TO BOTTOM OF EXISTING FLOOR JOIST AT EACH VERTICAL PLATE SUPPORT - CONNECT TO 3 JOISTS MINIMUM

3 3/4"

JAS

1/4" THREADED ROD, TYP.

EXISTING CEILING

JHA/MLK

Date

07/03/13

NOTICE: The designs shown and described herein including all technical drawings, graphics, and models thereof, are proprietary and cannot be copied, duplicated or commercially exploited, in whole or in part, without express written permission of RSP Architects. These are available for limited review and evaluation by clients, consultants, contractors, government agencies, vendors and office personnel only in accordance with this Notice. © Copyright RSP Architects 2007. All rights reserved.

0"

Revisions Date

Description

0"

No. QUICK CONNECT, TYP TS 4"X4"X1/4" STEEL TUBE WELDED TUBE TO CONNECT 3 JOIST MINIMUM

1/4"

4'-2 1/2" - FIELD VERIFY

NOTE: CONTRACTOR TO VERIFY WEIGHT OF EXAM LIGHT DOES NOT EXCEED 1800 LBS.

4"X3"X3/8" STEEL ANGLE VERTICAL PLATE SUPPORT - WELD TO HORIZONTAL TUBE STEEL AND PLATE ANGLES 4"X3"X3/8" STEEL PLATE ANGLE - WELD TO STEEL MOUNTING PLATE

3

3X3X1/4 STEEL ANGLE - SEE DETAIL 3/A204

1' - 11"

4"X3"X3/8" STEEL ANGLE VERTICAL PLATE SUPPORT - WELD TO HORIZONTAL TUBE STEEL AND PLATE ANGLES

4'-2 1/2" - FIELD VERIFY

3X3X1/4 STEEL ANGLE KICKER AT EACH VERTICAL PLATE SUPPORT (4 REQUIRED - 2 EACH DIRECTION). SEE DETAIL 4/A201 FOR ATTACHMENT TO DECK.

B22 UNI-STRUT

TYP UNO.

5

WIREMOLD 4000

DETAIL AT SERVICE CARRIER 1 1/2" = 1'-0"

4"X3"X3/8" STEEL PLATE ANGLE - WELD TO STEEL MOUNTING PLATE

3/4" THREADED BOLTS EXISTING GYPSUM BOARD SUPPORT SYSTEM

3/4" THREADED BOLTS 3/4" X16"X16" STEEL MOUNTING PLATE

3/4" X16"X16" STEEL MOUNTING PLATE

EXAM LIGHT MOUNTING BRACKET

EXAM LIGHT MOUNTING BRACKET

6"

6"

EXISTING 5/8" GYPSUM BOARD

EXISTING SUSPENDED GYPSUM CEILING ELEV. 8'-0" A.F.F.

EXISTING SUSPENDED GYPSUM CEILING' ELEV. 8'-0" A.F.F. SUSPENDED ACOUSTICAL CEILING SYSTEM

8"

8"

EXAM LIGHT CEILING HOOD

EXAM LIGHT CEILING HOOD EXAM LIGHT SUSPENSION TUBE

8"

1' - 4"

1' - 4"

4 A204

3

EXAM LIGHT SUPPORT DETAIL 1 1/2" = 1'-0"

C:\Revit Projects\Med Sci 4 Central_jschmit.rvt 7/8/2013 11:22:47 AM

Please purchase PDF Split-Merge on www.verypdf.com to remove this watermark.

8"

4

EXAM LIGHT SECTION 1 1/2" = 1'-0"

EXAM LIGHT SUSPENSION TUBE

FOURTH LEVEL REFLECTED CEILING PLAN

A204


SEE PARTITION TYPE

DOOR SCHEDULE

HEAD

JAMB

3' - 0" 3' - 0" 3' - 0" 3' - 0" 3' - 0" 3' - 6" 5' - 0" 3' - 6" 3' - 0" 3' - 8" 3' - 0" 3' - 0" 3' - 0" 3' - 6" 3' - 6" 3' - 0" 3' - 0" 3' - 0" 4' - 0" 3' - 0" 3' - 0" 3' - 0" 3' - 6" 3' - 6" 3' - 6" 3' - 0" 3' - 0" 3' - 0" 3' - 0" 3' - 0" 3' - 0" 3' - 0" 3' - 0" 3' - 0" 3' - 6"

7' - 0" 7' - 0" 7' - 0" 7' - 0" 7' - 0" 7' - 0" 7' - 0" 7' - 0" 7' - 0" 7' - 0" 7' - 0" 7' - 0" 7' - 0" 7' - 0" 7' - 0" 7' - 0" 7' - 0" 7' - 0" 7' - 0" 7' - 0" 7' - 0" 7' - 0" 7' - 0" 7' - 0" 7' - 0" 7' - 0" 7' - 0" 7' - 0" 7' - 0" 7' - 0" 7' - 0" 7' - 0" 7' - 0" 7' - 0" 7' - 0"

B A A B A A A,A C A A A A A A A A A A A,B C C C A C C A A A A A A A A A C

NO NO NO NO NO YES YES NO NO NO NO NO NO NO NO NO NO NO YES NO NO NO NO NO NO NO NO NO NO NO NO NO NO NO NO

F1 F1 F1 F1 F1 F1 F1 F1 F1 F1 F1 F1 F1 F1 F1 F1 F1 F1 F1 F1 F1 F1 F1 F1 F1 F1 F1 F1 F1 F1 F1

1/A301 1/A301 1/A301 1/A301 1/A301 1/A301 1/A301 1/A301 1/A301 1/A301 1/A301 1/A301 1/A301 1/A301 1/A301 1/A301 1/A301 1/A301 1/A301 1/A301 1/A301 3/A301 3/A301 3/A301 3/A301 1/A301 1/A301 1/A301 1/A301 1/A301 1/A301 1/A301 1/A301 1/A301 1/A301

2/A301 2/A301 2/A301 2/A301 2/A301 2/A301 2/A301 2/A301 2/A301 2/A301 2/A301 2/A301 2/A301 2/A301 2/A301 2/A301 2/A301 2/A301 2/A301 2/A301 2/A301 4,5/A301 4,5/A301 4,5/A301 4,5/A301 2/A301 2/A301 2/A301 2/A301 2/A301 2/A301 2/A301 2/A301 2/A301 2/A301

EL7 PP1 PP1 EL2 EL2 ST1 CL4 PA2 PA1 PA1 PA1 PA2 PA2 EL2 PA2 EL2 PR2 PA2 PA4 PA2 PA2 SL1 SL1 SL1 SL1 PA1 PA1 PA1 PA1 PA1 PA1 PA1 PA1 PA1 ST1

COMMENTS

KP KP KP, OS KP KP, CR KP, OS, DS, SG KP, CR KP KP KP, OS KP KP, OS NOTE 1 NOTE 1 NOTE 1 NOTE 1 KP KP

2.

DELETE LEVER FOR LOCKSET ON CORRIDOR SIDE OF DOOR

DOOR TYPES:

FRAME TYPE:

SEE DOOR SCHEDULE 3' - 0"

SEE DOOR SCHEDULE 3' - 0"

1/2"

1/2"

9"

1

9"

2"

SEE DOOR SCHED.

JAMB ANCHORS 3 PER JAMB

HOLLOW METAL FRAME

WOOD DR. - SEE DOOR SCHEDULE

DOUBLE STUDS AT JAMBS (TYPICAL)

TYPICAL DOOR HEAD DETAIL

TYPICAL DOOR JAMB DETAIL

HOLLOW METAL FRAME

2

3" = 1'-0"

3

TYPICAL SLIDING DOOR HEAD DETAIL 3" = 1'-0"

4' - 0"

8'-0"

2' - 0"

GL2

FLUSH PANEL SOLID CORE WOOD DOOR BIRCH, PLAIN SLICED BOOK MATCHED, SELECT WHITE

C

FLUSH PANEL HOLLOW CORE WOOD DOOR BIRCH, PLAIN SLICED BOOK MATCHED, SELECT WHITE

KP, OS

WALL

3 5/8" METAL STUDS - SEE PARTITION TYPES. DOUBLE STUDS AT JAMB (TYPICAL) FLOOR GUIDE

WOOD DOOR

SLIDING DOOR SEE SCHEDULE

GL1

1/4" CLEAR WIRE GLASS

FINISHED WOOD FRAME

GL2

1/4" CLEAR TEMPERED GLASS

DOUBLE STUDS AT JAMB TYPICAL

SLIDING DOOR SEE SCHEDULE

1/4"X3/4" GROOVE IN BOTTOM OF DOOR NYLON GUIDE

2.

PROVIDE CONTROL JOINTS AT JUNCTURE OF ALL FLOOR SUPPORTED WALLS WITH BULKHEAD & SOFFITS SUPPORTED FROM DECK ABOVE.

3.

PROVIDE U.L. APPROVED JOINT ASSEMBLY AT PERIMETER OF ALL FIRE RATED PARTITIONS.

Date

11902 07.03.13

Signature

DAVID NORBCK

Registration Number Date

TYPICAL SLIDING DOOR JAMB DETAIL FINISHED END

6

11902 07.03.13

3" = 1'-0"

DOOR GUIDE DETAIL 6" = 1'-0"

Large Animal Surgery and Germ Free Facility

3 A301 VARIES

Medical Sciences Building Fourth Floor

CASE DOOR OPENING WITH 3/4" X 5" +/WOOD TRIM

HOLLOW CORE WOOD DOOR, 6" WIDER THAN FINISHED OPENING

7' - 6"

PROVIDE DEFLECTION TRACK TO ALLOW FOR 1" DEFLECTION IN STRUCTURAL SYSTEM AT TOP OF ALL INTERIOR PARTITIONS EXTENDING FROM TOP OF SLAB TO UNDERSIDE OF STRUCTURE.

5

3" = 1'-0"

GENERAL NOTES 1.

Registration Number

Project For

TYPICAL SLIDING DOOR JAMB DETAIL DOOR END

HOLLOW METAL

DAVID NORBACK

I hereby certify that this plan, specification or report was prepared by me or under my direct supervision and that I am a duly licensed Architect under the laws of the State of Minnesota.

SHIM AS REQUIRED

FINISHED WOOD FRAME

4

F1

I hereby certify that I have reviewed the Mayo Clinic Standard General Specifications prepared by Ronald B. Carlson, License Number 10850, that they are appropriate for the work except as amended in this plan, specification or report, and that I am a duly licensed Architect under the laws of the State of Minnesota.

Signature

GLASS TYPES:

2"

HOLLOW CORE OAK DOOR - SEE DOOR SCHEDULE

Consultants

3" = 1'-0"

3 5/8" METAL STUDS - SEE PARTITION TYPES.

SEE DOOR SCHEDULE

SEE DOOR SCHEDULE

2' - 0" B

1/2"

HEADER BY STEEL STUD SUPPLIER

RSP Architects 320 South Broadway Ste. B 507.285.6569 Rochester, Minnesota 55904 612.677.7499 fax www.rsparch.com

CASE DOOR OPENING WITH 3/4" X 5" +/- OAK

5/8" GYPSUM BOARD

1' - 4"

GL1

8'-0"

8'-0"

FLUSH PANEL SOLID CORE WOOD DOOR BIRCH, PLAIN SLICED BOOK MATCHED, SELECT WHITE

1/2"

5/8" GYPSUM BOARD

SEE DOOR SCHEDULE

SEE DOOR SCHEDULE A

SLIDING DOOR HARDWARE SEE DOOR SCHEDULE

3/8" DIA. LAG BOLTS AT MAX. 2'-0" O.C.

SHIM AS REQUIRED

3' - 0"

4"

REMOVABLE WOOD VALANCE 3 5/8" METAL STUDS - SEE PARTITION TYPES.

Certification

2"

6"

SEE DOOR SCHED.

3 5/8" METAL STUDS -SEE PARTITION TYPES.

SEE PLANS FOR PARTITION TYPE

SEE DOOR SCHEDULE

FINISHED DOOR OPENING IS INDICATED IN DOOR SCHEDULE. DOORS SHALL BE 6" WIDER THAN OPENING

5/8" GYPSUM BOARD FIRE TREATED SOLID WOOD BLOCK

3 5/8" STEEL STUD FRAMING

DOOR SCHEDULE NOTES 1.

5/8" GYP. BD.

5/8" TYPE 'X' GYP. BD.

KP KP KP KP, CR KP, CR KP KP, OS, NOTE 2 KP, OS

SEE DOOR SCHEDULE

BREAK ROOM TOILET MEN TOILET WOMEN CORRIDOR CORRIDOR CORRIDOR PREP AREA PREP AREA OFFICE CLEAN LINEN SUPPLY STORAGE ORTHO PREP CLEAN STORAGE PREP ROOM GERM FREE FACILITY VESTIBULE/ LOCKER TOILET/ CHANGE VESTIBULE/ LOCKER LAB SIT-DOWN LAB TISSUE CULTURE MICROSCOPY TISSUE CULTURE TISSUE CULTURE CONFERENCE FLEX OFFICE OFFICE OFFICE OFFICE OFFICE OFFICE OFFICE OFFICE EQUIPMENT

FIRE LABEL HDWR.

5"

FRAME TYPE

6'-11" A.F.F.

PAIR

6'-11 1/4" A.F.F.

DOOR TYPE

2"

H

TYPE

5/8"

4-01 4-02 4-03 4-04-2 4-04-5 4-04 4-06 4-06 4-06C 4-09 4-10C 4-10F 4-10G 4-10H 4-10HA 4-11 4-11A 4-11 4-12 4-12-2 4-12-3 4-12A 4-12B 4-12C 4-12D 4-15 4-16 4-20 4-22 4-23 4-24 4-25 4-26 4-27 4-28

W

ROOM NAME

SEE PARTITION

SPECS.

2"

SIZE

DOOR ROOM NO. NO. 4-01 4-02 4-03 4-04 4-04-5 4-04A 4-06A 4-06B 4-06C 4-09 4-10C 4-10F 4-10G 4-10H 4-10HA 4-11 4-11A 4-11B 4-12 4-12-2 4-12-3 4-12A 4-12B 4-12C 4-12D 4-15 4-16 4-20 4-22 4-23 4-24 4-25 4-26 4-27 4-28

FRAME

5/8"

DOOR

3 3/4"

2' - 0"

Project #7R120760

3 3/4"

5/8" GYPSUM BOARD

FINISHED OPENING SEE FLOOR PLAN FOR PARTITION TYPES AND REQUIRED RATINGS

DEFINES TOP OF LOW PARTITION: REFER TO NOTES THIS SHEET, OR SEE CONSTRUCTION DOCUMENTS FOR SPECIAL CONDITIONS

INDICATES NEW PATITION CONSTRUCTION (REFER TO PARTITION TYPE INDICATOR)

1i

1 1i

1

6 A301

PARTITION TYPE INDICATOR: REFER TO REFERENCE STANDARDS #3520.01-.04 OR SEE CONSTRUCTION DOCUMENTS FOR SPECIAL PARTITION TYPES DEFINES HEIGHT TO TERMINATE PARTITION; REFER TO NOTES, THIS SHEET, OR SEE CONSTRUCTION DOCUMENTS FOR SPECIAL HEIGHTS

PARTITION SUBSCRIBT NOTES 1

CONSTRUCT PARTITION FROM FLOOR TO UNDERSIDE OF CEILING

2

CONSTRUCT PARTITION FROM FLOOR TO 6" ABOVE CEILING

3

CONSTRUCT FIRE RATED PARTITION FROM FLOOR DECK/STRUCTURE ABOVE. SEE LIFE SAFETY PLANS FOR EXTENT

48

CONSTRUCT PARTITION FROM FLOOR UP TO 48" A.F.F.

EXISTING 2 1/2" SHAFT WALL STUDS AT 16" OC

EXISTING 1" GYPSUM LINER PANEL EXISTING 5/8" GYPSUM BOARD EXISTING SHAFT

7

SLIDE-BY DOOR 1/2" = 1'-0"

8

SHAFT INFILL DETAIL 1 1/2" = 1'-0"

Project No.

6287.040.04

Drawn By

JAS

Checked By

JHA/MLK

Date

07/03/13

NOTICE: The designs shown and described herein including all technical drawings, graphics, and models thereof, are proprietary and cannot be copied, duplicated or commercially exploited, in whole or in part, without express written permission of RSP Architects. These are available for limited review and evaluation by clients, consultants, contractors, government agencies, vendors and office personnel only in accordance with this Notice. © Copyright RSP Architects 2007. All rights reserved.

Revisions No.

Date

Description

PARTITION TYPE INDICATOR LEGEND

DOOR SCHEDULE, DETAILS, PARTITION TYPE INDICATOR, AND INTERIOR DETAILS

A301 C:\Revit Projects\Med Sci 4 Central_jschmit.rvt 7/8/2013 11:22:49 AM

Please purchase PDF Split-Merge on www.verypdf.com to remove this watermark.


EXIST TAG ROOM C100 C101 C102 C103 C104 C105 C106 C108 C109 C111 C112 C113 C115 C116 C117 C118 C119 C120 C121 C122 C123 C124 C300 C301 F400 F401 F402 F406 F407 F408 F409 F410 F412 F413 G101 G102 G104 G105 G107 G108 G109 G111 G112 G113 G114 G115 G116 G117 G118 G119 G120 G121 G122 G123 G124 G125 G126 G127 G128 G129 G130 G131 G132 G133 G134 G135 G137 G138 G139 G140 G141 G142 G143 G144 G145 G146 G147 G300 G303 G304 G305 G309 G310 G311 M100 M101 M102 M103 M104 M105 M106 M107 M108 M109 M110 M112 M113 M114 M115 M116 M117 M118 M119 M120 M122 M123 M220 M222 M224 M225 M226 M227 M230 M231 M239 M241 M242 M243 M244 M245 N100 N101 N102 N103 N104 N105 N106 N107 N108 N109 N110 N111 N112 N113 N114 N115 N117 N118 N119 N120 N121 N122 N123 N124 N125 N126 N127 N128 N129 N130 N131 N132

4-56 4-56 4-56 4-56 4-63 4-56 4-56 4-63 4-63 4-56 4-56 4-56 4-56 4-56 4-56 4-56 4-56 4-56 4-56 4-56 4-56 4-63 NEW NEW 5-80B 5-80B 5-80B NEW NEW 5-80B 5-80B 5-80B 5-80B NEW 4-53 4-53 4-53 4-53 4-53 4-53 4-53 4-53 4-53 4-53 4-53 4-53 4-53 4-53 4-53 4-53 4-53 4-53 4-53 4-53 4-53 4-53 4-53 4-53 4-53 4-53 4-53 4-53 4-53 4-53 4-55 4-53 4-55A 4-55A 4-55A 4-55A 4-55A 4-55A 4-55A 4-29A 4-29A 4-29A 4-29A NEW NEW NEW NEW NEW NEW NEW 4-45 4-45 4-45 4-45 4-54 4-54 4-54 4-54 4-45 4-45 4-45 4-45 4-45 4-45 4-45 4-45 4-28 4-28 4-29-1 4-29-1 4-62 4-62 4-45 4-45 4-45 4-45 4-45 4-45 4-45 4-45 4-45 4-45 4-45 4-45 4-45 4-45 4-56 4-56 4-56 4-56 4-56 4-56 4-56 4-56 4-56 4-65 4-65 4-65A 4-65A 4-56A 4-56A 4-56A 4-56A 4-65 4-66 4-66 4-66 4-66 4-66 4-66 4-66 4-65 4-65 4-65 4-65 4-65 4-65 4-65

DESCRIPTION FASTPREP-24 SCALE MINI CENTRIFUGE CENTRIFUGE FREEZER THERMAL CYCLER THERMAL CYCLER TAPE STATION QUBIT 2.0 FLAM CAB STOMACHER 400 CIRCULATOR BIO STORAGE BOX ISOTEMP PIPETTE HEATER UC REF INSTRUMENT CHARGER MINISPIN VORTEX MIXER SHAK-R-BATH THERMAL CYCLER GALAXY MINI SHAKER PLATFORM SHAKER 4' BIO HOOD REFRIGERATOR BREEDER ISOLATOR CART EXPERIMENTAL ISOLATOR CART TRANSFER CART 4' - FUME HOOD ACID STORAGE CABINET ANAEROBIC CHAMBER 4' BIO HOOD WORK CART BLUE STORAGE BIN FLAM CAB -70 -70 POLOROID GEL CAM CRYOCAN FREEZER CPU UV TRANSILLUMINATOR ENCLOSED SCALE SCALE FREEZER DELI CENTRIFUGE CENTRIFUGE 5' - FUME HOOD FLAM CABINET ACID STORAGE CABINET BELLY DANCER WATERBATH MICRO TWIN HEAT BLOCK HEAT BLOCK DRY BATH THERMAL CYCLER HOTPLATE MICROWAVE ELECTROPHORESIS SYSTEM SCAN WASHER NANO-DROP SPECTAMAX CRYOCAN FACSCALIBUR SHAKER CENTRIFUGE POWER PAC CYTOSPIN COULTER-Z1 5'-0" BIO HOOD STACKED INCUBATOR REFRIGERATOR ANIMAL CART X-CITE TEMPERATURE CONTROL PRINTER 5'-0" BIO HOOD ACID STORAGE CABINET FLAM CABINET ACID STORAGE CABINET REFRIGERATOR MICROWAVE COFFEE POT 5' - FUME HOOD FLAM CABINET ACID STORAGE CABINET FLAM CAB 4' BIO HOOD UC REF INCUB INCUB REFRIGERATOR REFRIGERATOR SPEED VAC SCOPE STATION SCOPE STATION TURBIDIMETER DRY BATH INCUBATOR PROTEAN IEF CELL REFRIGERATOR -80 FREEZER -80 FREEZER -80 FREEZER PRINTER FAX/SCANNER BIO-PHOTOMETER MINI INCUBATOR EPPENDORF BATH UC FREEZER OSOMETER SHAKING BATH SOUND BOX SONICATOR GS-6KR CENTRIFUGE ULTRA ROCKER SHAKER GRANITE BLOCK DIGI SCALE UC FREEZER CENTRIFUGE ROCKING SHAKER EMERSON 1056 RAND-SRL I.V. CART 4' BIO HOOD FREEZER DELI STACKED INCUBATOR FREEZER REFRIGERATOR -80 FREEZER -80 FREEZER REFRIGERATOR CENTRIFUGE CENTRIFUGE CAPTURE HOOD 4' BIO HOOD STACKED INCUBATOR 4' BIO HOOD WATERBATH MICROSCOPE BIOTEK ELx50 MINI CENTRIFUGE VORTEX GENIE MICROSCOPE SCALE PH METER STIR PLATE SCALE COULTER COUNTER ENCLOSED SCALE

C:\Revit Projects\Med Sci 4 Central_jschmit.rvt 7/8/2013 11:22:49 AM

EQUIPMENT SCHEDULE ROOM NUMBER ORDERED BY

QTY

NEW ROOM

1 1 1 1 1 3 1 1 1 1 1 1 3 1 1 1 1 1 1 1 1 1 1 1 2 4 3 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1

LAB LAB LAB LAB LAB LAB LAB LAB LAB LAB LAB LAB LAB LAB LAB LAB LAB LAB LAB LAB LAB LAB LAB LAB GERM FREE FACILITY GERM FREE FACILITY

4-12 4-12 4-12 4-12 4-12 4-12 4-12 4-12 4-12 4-12 4-12 4-12 4-12 4-12 4-12 4-12 4-12 4-12 4-12 4-12 4-12 4-12 4-12 4-12 4-10HA 4-10HA

PREP ROOM PREP ROOM PREP ROOM GERM FREE FACILITY GERM FREE FACILITY GERM FREE FACILITY PREP ROOM EQUIPMENT EQUIPMENT LAB LAB LAB LAB LAB LAB LAB LAB LAB LAB LAB LAB LAB LAB LAB LAB LAB LAB LAB LAB LAB LAB LAB LAB LAB LAB LAB LAB LAB SIT-DOWN LAB LAB LAB TISSUE CULTURE TISSUE CULTURE TISSUE CULTURE TISSUE CULTURE LAB LAB LAB LAB TISSUE CULTURE LAB LAB LAB BREAK ROOM BREAK ROOM BREAK ROOM LAB LAB LAB LAB TISSUE CULTURE TISSUE CULTURE TISSUE CULTURE TISSUE CULTURE LAB LAB LAB LAB LAB LAB LAB LAB EQUIPMENT EQUIPMENT EQUIPMENT EQUIPMENT SECRETARY SECRETARY LAB LAB LAB LAB LAB LAB LAB LAB LAB LAB LAB LAB LAB LAB LAB LAB LAB LAB LAB TISSUE CULTURE LAB LAB TISSUE CULTURE LAB LAB EQUIPMENT EQUIPMENT LAB LAB LAB LAB TISSUE CULTURE TISSUE CULTURE TISSUE CULTURE TISSUE CULTURE TISSUE CULTURE LAB LAB LAB TISSUE CULTURE LAB LAB LAB LAB LAB TISSUE CULTURE

4-10H 4-10H 4-10H 4-10HA 4-10HA 4-10HA 4-10H 4-28 4-28 4-12-3 4-12-3 4-12-3 4-12-3 4-12-3 4-12 4-12 4-12-3 4-12-3 4-12-3 4-12-3 4-12-3 4-12-3 4-12-3 4-12-3 4-12-3 4-12-3 4-12-3 4-12-3 4-12-3 4-12-3 4-12-3 4-12-3 4-12-3 4-12-3 4-12-3 4-12-3 4-12-3 4-12-3 4-12-2 4-12-3 4-12-3 4-12-3 4-12D 4-12D 4-12D 4-12D 4-12-3 4-12-3 4-12-3 4-12-3 4-12D 4-12-3 4-12-3 4-12-3 4-01 4-01 4-01 4-12 4-12 4-12 4-12 4-12C 4-12C 4-12C 4-12C 4-12 4-12 4-12 4-12 4-12 4-12 4-12 4-12 4-28 4-28 4-28 4-28 4-21 4-21 4-12 4-12 4-12 4-12 4-12 4-12 4-12 4-12 4-12 4-12 4-12 4-12 4-12 4-12 4-12 4-12 4-12 4-12 4-12 4-12A 4-12-3 4-12 4-12A 4-12 4-12 4-28 4-28 4-12 4-12 4-12 4-12 4-12A 4-12A 4-12C 4-12C 4-12D 4-12 4-12 4-12 4-12C 4-12 4-12 4-12 4-12 4-12 4-12A

Please purchase PDF Split-Merge on www.verypdf.com to remove this watermark.

PROPONENT PROPONENT CONSTRUCTION MANAGER CONSTRUCTION MANAGER CONSTRUCTION MANAGER PROPONENT PROPONENT PROPONENT PROPONENT PROPONENT PROPONENT PROPONENT -

SUPPLIED BY

INSTALLED BY

MANUFACTURER MANUFACTURER MANUFACTURER MANUFACTURER MANUFACTURER MANUFACTURER MANUFACTURER MANUFACTURER MANUFACTURER MANUFACTURER MANUFACTURER MANUFACTURER -

EQUIPMENT SERVICES EQUIPMENT SERVICES EQUIPMENT SERVICES EQUIPMENT SERVICES OPERATIONS EQUIPMENT SERVICES EQUIPMENT SERVICES EQUIPMENT SERVICES EQUIPMENT SERVICES CONTRACTOR EQUIPMENT SERVICES CONTRACTOR EQUIPMENT SERVICES OPERATIONS EQUIPMENT SERVICES EQUIPMENT SERVICES EQUIPMENT SERVICES EQUIPMENT SERVICES EQUIPMENT SERVICES EQUIPMENT SERVICES EQUIPMENT SERVICES EQUIPMENT SERVICES CONTRACTOR CONTRACTOR EQUIPMENT SERVICES EQUIPMENT SERVICES CONTRACTOR CONTRACTOR CONTRACTOR EQUIPMENT SERVICES OPERATIONS CONTRACTOR CONTRACTOR CONTRACTOR OPERATIONS OPERATIONS EQUIPMENT SERVICES EQUIPMENT SERVICES OPERATIONS EQUIPMENT SERVICES EQUIPMENT SERVICES EQUIPMENT SERVICES EQUIPMENT SERVICES OPERATIONS OPERATIONS EQUIPMENT SERVICES EQUIPMENT SERVICES CONTRACTOR CONTRACTOR CONTRACTOR EQUIPMENT SERVICES EQUIPMENT SERVICES EQUIPMENT SERVICES EQUIPMENT SERVICES EQUIPMENT SERVICES EQUIPMENT SERVICES EQUIPMENT SERVICES EQUIPMENT SERVICES CONTRACTOR EQUIPMENT SERVICES EQUIPMENT SERVICES EQUIPMENT SERVICES EQUIPMENT SERVICES EQUIPMENT SERVICES EQUIPMENT SERVICES EQUIPMENT SERVICES EQUIPMENT SERVICES EQUIPMENT SERVICES EQUIPMENT SERVICES EQUIPMENT SERVICES CONTRACTOR EQUIPMENT SERVICES OPERATIONS CONTRACTOR EQUIPMENT SERVICES EQUIPMENT SERVICES EQUIPMENT SERVICES CONTRACTOR CONTRACTOR CONTRACTOR CONTRACTOR OPERATIONS CONTRACTOR CONTRACTOR CONTRACTOR CONTRACTOR CONTRACTOR CONTRACTOR CONTRACTOR OPERATIONS EQUIPMENT SERVICES EQUIPMENT SERVICES OPERATIONS OPERATIONS EQUIPMENT SERVICES EQUIPMENT SERVICES EQUIPMENT SERVICES EQUIPMENT SERVICES EQUIPMENT SERVICES EQUIPMENT SERVICES OPERATIONS OPERATIONS OPERATIONS OPERATIONS EQUIPMENT SERVICES EQUIPMENT SERVICES EQUIPMENT SERVICES EQUIPMENT SERVICES EQUIPMENT SERVICES CONTRACTOR EQUIPMENT SERVICES EQUIPMENT SERVICES EQUIPMENT SERVICES EQUIPMENT SERVICES EQUIPMENT SERVICES EQUIPMENT SERVICES EQUIPMENT SERVICES EQUIPMENT SERVICES EQUIPMENT SERVICES CONTRACTOR EQUIPMENT SERVICES EQUIPMENT SERVICES EQUIPMENT SERVICES EQUIPMENT SERVICES EQUIPMENT SERVICES CONTRACTOR OPERATIONS OPERATIONS EQUIPMENT SERVICES OPERATIONS OPERATIONS OPERATIONS OPERATIONS OPERATIONS EQUIPMENT SERVICES EQUIPMENT SERVICES CONTRACTOR CONTRACTOR EQUIPMENT SERVICES CONTRACTOR EQUIPMENT SERVICES EQUIPMENT SERVICES EQUIPMENT SERVICES EQUIPMENT SERVICES EQUIPMENT SERVICES EQUIPMENT SERVICES EQUIPMENT SERVICES EQUIPMENT SERVICES EQUIPMENT SERVICES EQUIPMENT SERVICES EQUIPMENT SERVICES EQUIPMENT SERVICES

REMARKS

EXIST TAG ROOM N133 N136 N137 N138 N139 N228 N300 O100 O101 O102 O104 O105 O106 O107 O108 O113 O124 O132 O133 X110 X111 X300 Z128 Z129 Z130 Z131 Z141 Z142 Z143 Z160 Z161 Z162 Z163 Z164 Z165 Z166 Z167 Z181 Z182 Z183 Z202 Z205 Z206 Z207 Z208 Z209 Z210 Z212 Z215 Z224 Z225 Z229 Z300 Z301 Z302 Z303 Z304 Z305

4-65 4-65 4-65 4-56 4-65 4-56 NEW 4-35C 4-35A 4-35A 4-35C 4-35C 4-35C 4-35C 4-35C 4-35A 4-35C 4-35C 4-35A 4-29-1 4-29-1 NEW 4-71 4-71 4-71 4-73 4-73 4-73 4-73 4-73 4-73 4-73 4-73 4-73 4-73 4-73 4-73 4-67 4-67 4-67 4-25 4-24 4-24 4-24 4-24 4-24 4-24 4-24 4-24 4-25 4-25 4-25 NEW NEW NEW NEW NEW NEW

DESCRIPTION MICROSCOPE PLASTIC CART PROFUSION CART FREEZING BATH MICROPLATE READER NANOPURE INCUB ANESTHESIA MACHINE UC REF S.S. CART CAUTERY ROBOTIC SCOPE S.S. CART S.S. CART HYDROGEN GENERATOR BATTERY PACK OPERATING TABLE THERMAL PAD VACUUM -80 FREEZER -80 FREEZER -70 OPERATING TABLE I.V. CART MODULUS-SE DEFIBRILLATOR CART S.S. CART DEFIBRILLATOR SSE2L MODULUS-SE I.V. CART OPERATING TABLE OPERATING TABLE MASTERFLEX L/S CART MODULUS-SE I.V. CART I.V. CART MODULUS-SE I.V. CART OPERATING TABLE UC REFRIGERATOR UC REFRIGERATOR ICE MACHINE TABLE SCALE SHOP VAC I.V. CART ANESTHESIA MACHINE MEDTRONIC AUTOLOG SOILED LINEN PRINTER PRINTER/COPIER PRINTER SUPPLY CART DEFIBRILLATOR CART SCRUBBER UTILITY CART GONDOLA GETINGE 533LS STERILIZER

EQUIPMENT SCHEDULE ROOM NUMBER ORDERED BY

QTY

NEW ROOM

1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 11 2 1 1 1 1

TISSUE CULTURE LAB LAB LAB LAB LAB TISSUE CULTURE ORTHO OPERATING ROOM ORTHO PREP ORTHO PREP ORTHO OPERATING ROOM ORTHO OPERATING ROOM ORTHO OPERATING ROOM ORTHO OPERATING ROOM ORTHO OPERATING ROOM ORTHO PREP ORTHO OPERATING ROOM ORTHO OPERATING ROOM ORTHO PREP EQUIPMENT EQUIPMENT EQUIPMENT OPERATING ROOM OPERATING ROOM OPERATING ROOM OPERATING ROOM OPERATING ROOM OPERATING ROOM OPERATING ROOM OPERATING ROOM OPERATING ROOM OPERATING ROOM OPERATING ROOM

4-12A 4-12 4-12 4-12 4-12 4-12 4-12C 4-10E 4-10F 4-10F 4-10E 4-10E 4-10E 4-10E 4-10E 4-10F 4-10E 4-10E 4-10F 4-28 4-28 4-28 4-10B 4-10B 4-10B 4-10A 4-10A 4-10A 4-10A 4-10A 4-10A 4-10A 4-10A

OPERATING ROOM

4-10A

OPERATING ROOM OPERATING ROOM OPERATING ROOM OPERATING ROOM SURGICAL TECHS PREP AREA SOILED WORK PREP AREA PREP AREA PREP AREA PREP AREA PREP AREA PREP AREA SURGICAL TECHS SURGICAL TECHS SURGICAL TECHS

4-10A 4-10D 4-10D 4-10D 4-06B 4-06 4-06A 4-06 4-06 4-06 4-06 4-06 4-06 4-06B 4-06B 4-06B

OPERATING ROOM CUSTODIAL CUSTODIAL CUSTODIAL SOILED WORK

4-05A 4-05A 4-05A 4-06A

PROPONENT PROPONENT PROPONENT PROPONENT PROPONENT PROPONENT PROPONENT FACILITIES

SUPPLIED BY

INSTALLED BY

-

EQUIPMENT SERVICES CONTRACTOR CONTRACTOR EQUIPMENT SERVICES EQUIPMENT SERVICES EQUIPMENT SERVICES EQUIPMENT SERVICES EQUIPMENT SERVICES OPERATIONS CONTRACTOR EQUIPMENT SERVICES EQUIPMENT SERVICES CONTRACTOR CONTRACTOR EQUIPMENT SERVICES EQUIPMENT SERVICES EQUIPMENT SERVICES EQUIPMENT SERVICES EQUIPMENT SERVICES OPERATIONS OPERATIONS OPERATIONS EQUIPMENT SERVICES EQUIPMENT SERVICES EQUIPMENT SERVICES EQUIPMENT SERVICES CONTRACTOR EQUIPMENT SERVICES EQUIPMENT SERVICES EQUIPMENT SERVICES CONTRACTOR EQUIPMENT SERVICES EQUIPMENT SERVICES EQUIPMENT SERVICES EQUIPMENT SERVICES CONTRACTOR CONTRACTOR EQUIPMENT SERVICES EQUIPMENT SERVICES EQUIPMENT SERVICES OPERATIONS OPERATIONS OPERATIONS EQUIPMENT SERVICES EQUIPMENT SERVICES EQUIPMENT SERVICES EQUIPMENT SERVICES EQUIPMENT SERVICES CONTRACTOR EQUIPMENT SERVICES EQUIPMENT SERVICES EQUIPMENT SERVICES EQUIPMENT SERVICES EQUIPMENT SERVICES EQUIPMENT SERVICES EQUIPMENT SERVICES EQUIPMENT SERVICES EQUIPMENT SERVICES

MANUFACTURER MANUFACTURE MANUFACTURE MANUFACTURE MANUFACTURE MANUFACTURE MANUFACTURE MANUFACTURE

REMARKS

RSP Architects 320 South Broadway Ste. B 507.285.6569 Rochester, Minnesota 55904 612.677.7499 fax www.rsparch.com

Consultants

Certification

I hereby certify that I have reviewed the Mayo Clinic Standard General Specifications prepared by Ronald B. Carlson, License Number 10850, that they are appropriate for the work except as amended in this plan, specification or report, and that I am a duly licensed Architect under the laws of the State of Minnesota.

Signature

DAVID NORBACK

Registration Number Date

11902 07.03.13

I hereby certify that this plan, specification or report was prepared by me or under my direct supervision and that I am a duly licensed Architect under the laws of the State of Minnesota.

Signature

DAVID NORBCK

Registration Number Date

11902 07.03.13

Project For

Large Animal Surgery and Germ Free Facility Medical Sciences Building Fourth Floor Project #7R120760

Project No.

6287.040.04

Drawn By

JAS

Checked By

JHA/MLK

Date

07/03/13

NOTICE: The designs shown and described herein including all technical drawings, graphics, and models thereof, are proprietary and cannot be copied, duplicated or commercially exploited, in whole or in part, without express written permission of RSP Architects. These are available for limited review and evaluation by clients, consultants, contractors, government agencies, vendors and office personnel only in accordance with this Notice. © Copyright RSP Architects 2007. All rights reserved.

Revisions No.

Date

Description

EQUIPMENT SCHEDULE

A801


M105 M112

G142

M107 M114

M106

M115

M113

N120

M116

M108

4-12B

M104

STAIR 4-49B

N122

STORAGE 4-49A

TISSUE CULTURE

4-12C

MICROSCOPY

M220 M110

N300

TISSUE CULTURE

M222

M109

G300

4-12D

N121

DN

G140

M119

G143

M100

Consultants

EQUIPMENT

M102

4-28

M103

ELEC RM 4-004D-1 M224 M230

ELEC RM 4-004D-2

M117

M239

M226

G101

Certification

G102

I hereby certify that I have reviewed the Mayo Clinic Standard General Specifications prepared by Ronald B. Carlson, License Number 10850, that they are appropriate for the work except as amended in this plan, specification or report, and that I am a duly licensed Architect under the laws of the State of Minnesota.

X111

SIT-DOWN 4-12-1

M227

M241 M242

M120

M118

X300

M101

M245

RSP Architects 320 South Broadway Ste. B 507.285.6569 Rochester, Minnesota 55904 612.677.7499 fax www.rsparch.com

G141

N126

M225

UP

SIT-DOWN

M231

4-12-2

X110

Signature

N111

DAVID NORBACK

N112 Registration Number

M244

M243

G111

N228

G112

Date

N127

N123

G134

C105 N101 N128

N124

N129

N130

N138

N125

N115

N100

C105

G104

C105

C108

C116

C115

N139 C112

N137

C111

C113

C124

C100

C103

C122

C102 C123

C101

N103

N110

G127

G128

C129

C104

C301

Signature

G118

G305

Registration Number

G120

Project For

4-26

N106

4-12-3

G138 G137

G116

G113

G114 G145

G146

G109

Large Animal Surgery and Germ Free Facility

OFFICE 4-25

G108 G115

C300

CORRIDOR

Medical Sciences Building Fourth Floor

4-04-5

G107

N105 N132 N133

N108

N119

OFFICE

N113

4-24

TISSUE CULTURE

Project #7R120760

CORRIDOR

4-12A

4-04-4

N109 N104

N118

A

N102

Z303

TOILET/ CHANGE

B

4-11A

CUSTODIAL 4-05A

OFFICE

KEY PLAN

4-23

MECHANICAL 4-05

1

PARTIAL FOURTH LEVEL EQUIPMENT PLAN - AREA A

07.03.13

OFFICE LAB

G139

11902

Date

G129

G133

DAVID NORBCK

G304

G147

N136

4-27

C120

C121 N107

G125

G126

G105 C118 C119

C117

G124

G130

G131

C109

G123

G122 G132

C106 N131

N114

G121

OFFICE G117

4-12

G119

S108

G144

LAB

07.03.13

I hereby certify that this plan, specification or report was prepared by me or under my direct supervision and that I am a duly licensed Architect under the laws of the State of Minnesota.

G135

N117

11902

VESTIBULE/ LOCKER 4-11

Project No.

FLEX OFFICE

6287.040.04

Drawn By

4-16

JAS

Checked By

1/4" = 1'-0"

JHA/MLK

Date

07/03/13

NORTH

NOTICE: The designs shown and described herein including all technical drawings, graphics, and models thereof, are proprietary and cannot be copied, duplicated or commercially exploited, in whole or in part, without express written permission of RSP Architects. These are available for limited review and evaluation by clients, consultants, contractors, government agencies, vendors and office personnel only in accordance with this Notice. Š Copyright RSP Architects 2007. All rights reserved.

Revisions No.

Date

Description

PARTIAL FOURTH LEVEL EQUIPMENT PLAN - AREA A

A801A C:\Revit Projects\Med Sci 4 Central_jschmit.rvt 7/8/2013 11:22:50 AM

Please purchase PDF Split-Merge on www.verypdf.com to remove this watermark.


OFFICE

N113 N133

4-24

TISSUE CULTURE

CORRIDOR

4-12A

4-04-4

N109

N108

N104

N118

N119

N102

Z303

TOILET/ CHANGE 4-11A

CUSTODIAL 4-05A

RSP Architects 320 South Broadway Ste. B 507.285.6569 Rochester, Minnesota 55904 612.677.7499 fax www.rsparch.com

OFFICE 4-23

MECHANICAL

Z304

4-05

VESTIBULE/ LOCKER

Z302

FLEX OFFICE

4-11

4-16

Z206

STORAGE 4-07

Z305

Consultants

OFFICE 4-06C

OFFICE 4-22

CONFERENCE 4-15

SOILED WORK 4-06A

Certification

Z202

CORRIDOR 4-04-2

M122

Z225

4-06B

Z224

I hereby certify that I have reviewed the Mayo Clinic Standard General Specifications prepared by Ronald B. Carlson, License Number 10850, that they are appropriate for the work except as amended in this plan, specification or report, and that I am a duly licensed Architect under the laws of the State of Minnesota.

Z229

SURGICAL TECHS

M123

SECRETARY

DN

Signature

4-21

UP STAIR 4-08

CLEAN STORAGE

DAVID NORBACK

Registration Number

4-10G

11902

Date

07.03.13

I hereby certify that this plan, specification or report was prepared by me or under my direct supervision and that I am a duly licensed Architect under the laws of the State of Minnesota.

CLOSET 4-04-1

OFFICE 4-20

Signature

ELECTRIC 4-004B-1

CORRIDOR 4-04

DAVID NORBCK

Registration Number

CORRIDOR 4-10-1

11902

Date

Z208

G309

Z207

TOILET MEN 4-02

Z215

TOILET WOMEN 4-03

BREAK ROOM 4-01

O102

Z210

4-06

O133

SCRUB 4-10

SCRUB

STORAGE

ORTHO PREP

4-10-2

4-10C

Z212

4-10F

PREP ROOM

O113

O101

4-10H

F407

F408

F402

OPERATING ROOM 4-10D

Z160

Z165

Z130

Z131

Z301

Z167

Z161

OPERATING ROOM

F401

O132

F402

GERM FREE FACILITY

Medical Sciences Building Fourth Floor

4-10HA O124

F400

4-10E F401

4-10B

Z163

Z162

Z182

OPERATING ROOM

4-10A

Z141

Z129

O104

ORTHO OPERATING ROOM

Large Animal Surgery and Germ Free Facility F400

O100

Z181

Z301

Z143

F413

F402

Z205

G311

Project For

F406

Z209

PREP AREA

07.03.13

F401

O105 Z183

Z128

O106

Z142

Project #7R120760

F409

O107

A

O108 Z300

Z300

Z300

Z300

Z300

Z300

Z300

Z300

Z300

Z300

Z300

F401 F410 B

F412 KEY PLAN

Project No.

6287.040.04

Drawn By

1

PARTIAL FOURTH LEVEL EQUIPMENT PLAN - AREA B

JAS

Checked By

1/4" = 1'-0"

NORTH

JHA/MLK

Date

07/03/13

NOTICE: The designs shown and described herein including all technical drawings, graphics, and models thereof, are proprietary and cannot be copied, duplicated or commercially exploited, in whole or in part, without express written permission of RSP Architects. These are available for limited review and evaluation by clients, consultants, contractors, government agencies, vendors and office personnel only in accordance with this Notice. Š Copyright RSP Architects 2007. All rights reserved.

Revisions No.

Date

Description

PARTIAL FOURTH LEVEL EQUIPMENT PLAN - AREA B

A801B C:\Revit Projects\Med Sci 4 Central_jschmit.rvt 7/8/2013 11:22:52 AM

Please purchase PDF Split-Merge on www.verypdf.com to remove this watermark.


M103

M102

2' - 0"

M101

5' - 0"

6' - 1"

2' - 7 3/4" 24BC1WB

18BD4WB

4' - 5 3/4"

1"

18BD4WB 14' - 9 1/2"

2' - 7 3/4" 24BC1WB

18BD4WB 14' - 9 1/2"

18BD4WB

1"

6

1

2' - 10 3/4"

2' - 10 3/4"

3' - 5"

18BD4WB

1/4" = 1'-0"

14' - 9 1/2"

14' - 6" 3036W

3036W

1 3/4"

3036W

3036W

2436W

3' - 0" 8' - 0"

4' - 1"

2' - 9 3/4"

30BC1WB

18BD4WB

3' - 0 3/4"

18BD4WB

11

1

1

3' - 4"

3' - 4"

2' - 6" 1' - 0"

4

1"

18BD4WB 14' - 9 1/2"

11

4

6 1 3' - 4"

3' - 4"

6"

RSP Architects 320 South Broadway Ste. B 507.285.6569 Rochester, Minnesota 55904 612.677.7499 fax www.rsparch.com

14' - 9 1/2"

LAB BENCH 2 - DR. V. MILLER - SOUTH

5

1/4" = 1'-0"

36BC1WB

4

2' - 6"

8' - 0"

30BC1WB

LAB BENCH 2 - DR. V. MILLER - NORTH

4

7 A920

11"

11" 4

LAB BENCH 1 - DR. V. MILLER - SOUTH

3

1/4" = 1'-0"

M115

3

3

3' - 0"

M225

3

4' - 0"

7

LAB BENCH 1 - DR. V. MILLER - NORTH

2

1/4" = 1'-0"

1"

1 3/4"

12' - 3 1/2"

8' - 0"

M114

4' - 0"

4' - 0"

7

24BC1WB 2' - 7 3/4"

12' - 3 1/2"

4' - 1"

M116

3' - 0"

M222

M220

E

8' - 0"

4' - 1" 4

DR. V. MILLER LAB - SOUTH WALL

1

9

8' - 0"

8' - 0"

6

M110

3' - 0"

1

2' - 6"

6' - 0"

M112

M108

M109

2' - 6"

M113

M100

3

1 A921

3036W

9

3' - 0"

2' - 0"

10

11' - 10 1/2"

5

5

11"

3636W

11' - 10 1/2"

11"

3636W

4

1 A921

3' - 0"

1"

1 A921

4' - 0"

5' - 6"

1 A921

4' - 1"

7 A920

1 A920

DR. V. MILLER LAB - NORTH WALL

6

1/4" = 1'-0"

1/4" = 1'-0"

Consultants

2' - 4 3/4"

1

2' - 4 3/4"

1

2' - 4 3/4" 6"

3' - 0 3/4"

MICROSCOPY - WEST WALL

7

1

6

3' - 0 3/4"

6"

3' - 3"

5

3' - 0"

3636W

30SC

2' - 11 3/4"

N121

2' - 0"

4

4

1"

9' - 7"

J

4' - 6"

4' - 2"

Certification

8' - 0"

8' - 0"

1

3' - 3"

3636W

N122

G142

1

1"

G141

3' - 0"

3' - 0"

5' - 4 1/2"

6"

D E

I hereby certify that I have reviewed the Mayo Clinic Standard General Specifications prepared by Ronald B. Carlson, License Number 10850, that they are appropriate for the work except as amended in this plan, specification or report, and that I am a duly licensed Architect under the laws of the State of Minnesota.

G143

1

3' - 0"

30SC

G300

3' - 0"

1

3636W

8

M100

N121

N126

M107

7 11 1/2"

1' - 0"

6

7 11 1/2"

30SC

4' - 9"

12' - 1"

Signature

7" 8 3/4"

4' - 9"

1/4" = 1'-0"

Date

TISSUE CULTURE 1 - DR. NYBERG & C.G.A. McGREGOR - NORTH WALL

9

DAVID NORBACK

Registration Number

3 A920

MICROSCOPY - NORTH WALL

8

1/4" = 1'-0"

3' - 0 3/4"

3636W

3' - 0"

8' - 0"

2' - 0" 1

3636W

M106

M105

3' - 0"

3' - 0"

6

3636W

3' - 0"

4236W

7 A920

1"

4

4

2' - 0"

4' - 9 1/2"

1"

3' - 0"

4' - 9 1/2"

1 A920

2' - 0"

4' - 9 1/2"

7 A920

N300

10

1/4" = 1'-0"

TISSUE CULTURE 2 - DR. NYBERG & C.G.A. McGREGOR - SOUTH WALL

11

1/4" = 1'-0"

TISSUE CULTURE 2 - DR. NYBERG & C.G.A. McGREGOR - NORTH WALL 1/4" = 1'-0"

07.03.13

I hereby certify that this plan, specification or report was prepared by me or under my direct supervision and that I am a duly licensed Architect under the laws of the State of Minnesota.

DR. V. MILLER LAB - WEST WALL

12

1/4" = 1'-0" Signature

5"

18BD418BD4

2' - 8"

1"

36BC1

16' - 0"

LAB BENCH 3 - DR. V. MILLER - WEST

7 A920

8

2436W 2436W 2436W

5' - 0"

2' - 8"

36BC1

18BD418BD4

2' - 8"

24BC1

2' - 6"

30BC1

30BC1

1/2"

16' - 0"

17

18BD418BD4 2' - 6 1/2"

1' - 0"

36BC1

20

1/4" = 1'-0"

FLEX LAB - MICROBIOME - WEST WALL

21

1/4" = 1'-0"

22

1/4" = 1'-0"

4' - 1"

8' - 0"

30BC1 18BD4

18BD4 18BD4

3' - 3 1/2"

16' - 0"

3' - 0 1/2"

LAB BENCH 1 - FLEX LAB - MICROBIOME EAST

23

1/4" = 1'-0"

1"

26

4

FLEX LAB - MICROBIOME - EAST WALL

30BC1

1/4" = 1'-0"

Please purchase PDF Split-Merge on www.verypdf.com to remove this watermark.

24BC1

2' - 8 1/2"

18BD4

2' - 8 1/2"

11" 4' - 0"

3' - 0"

18BD4

4' - 6"

18BD4

3' - 0"

5"

16' - 1"

LAB BENCH 2 - FLEX LAB - MICROBIOME EAST

24

Project No.

1/4" = 1'-0"

6287.040.04

Drawn By

BCS

31

30BC1

LAB BENCH 2 - DR. C.G.A. McGREGOR EAST 1/4" = 1'-0"

1 A921 11' - 6"

4' - 6"

1"

G124

G126 C301

1' - 8"

3"

7"

4

4' - 9"

1"

30SC

4' - 9"

1"

G121 G122

G127

G134

G123

3' - 0"

3' - 0" 4

48BC1

G125

30BC1

7

24BC1

2' - 6"

18BD4

5' - 5"

14' - 0"

FLEX LAB - MICROBIOME - NORTH WALL

29

1/4" = 1'-0"

© Copyright RSP Architects 2007. All rights reserved.

Revisions No.

Date

Description

3' - 0"

D

4' - 0"

J

07/03/13

NOTICE: The designs shown and described herein including all technical drawings, graphics, and models thereof, are proprietary and cannot be copied, duplicated or commercially exploited, in whole or in part, without express written permission of RSP Architects. These are available for limited review and evaluation by clients, consultants, contractors, government agencies, vendors and office personnel only in accordance with this Notice.

11"

9 C106

JHA/MLK

Date

6

LAB BENCH 1 - DR. C.G.A. McGREGOR EAST 1/4" = 1'-0"

1"

KEYNOTES - ELEVATIONS

G146

G108

9 G147

E

4' - 0"

3' - 0"

3' - 0"

G120

14' - 0"

14' - 0"

LAB BENCH 1 - DR. C.G.A. McGREGOR WEST

C:\Revit Projects\Med Sci 4 Central_jschmit.rvt 7/8/2013 11:22:56 AM

1"

4' - 0"

4' - 0"

3' - 0"

1"

4

5

5

G109

9

4' - 1"

8' - 0"

8' - 0"

G139

24BC1

7"

28

8' - 0"

G138

4' - 1"

4' - 1"

G128

G116

2' - 8"

4

1/4" = 1'-0"

3

G145 11"

11"

3

G137

J

18BD4

7"

4

DR. NYBERG & V. MILLER LAB - SOUTH WALL

11"

5

G129

Project #7R120760

1 A921

9

2' - 8"

27

1/4" = 1'-0" 1 A921

G104

30BC1

36BC1

E

1' - 0"

1 A921

G130

C301

4' - 9"

1/4" = 1'-0"

G132

N101 3' - 0"

5' - 0"

4

LAB BENCH 2 - FLEX LAB - MICROBIOME WEST

G131

J

C112

C116

1"

1/4" = 1'-0"

6

3' - 0"

C104

N137

3' - 0"

36BC1

16' - 1"

11' - 6"

N107

C129

4' - 2"

2' - 8 1/2"

C300

4' - 6"

18BD418BD4

4' - 9 1/2"

4

LAB BENCH 1 - FLEX LAB - MICROBIOME WEST

1

4' - 0"

C101

C111 2' - 5"

C115

9

5

4

4

32

11 30BC1

1"

2' - 8 1/2"

18BD4

2' - 8 1/2"

14' - 0"

LAB BENCH 2 - DR. C.G.A. McGREGOR WEST 1/4" = 1'-0"

4

24BC1

D

J

E

G133

55SC1

4' - 9"

33

DR. C.G.A. McGREGOR LAB - SOUTH WALL 1/4" = 1'-0"

G105

G134 6 G127

1"

1"

G128

3' - 0"

C102

8' - 0"

C122

C103

7

C118

C113

E

1"

16' - 0"

C117

D

4

C100

4' - 1"

C121

8' - 0"

3' - 0"

30BC1

11"

C123

TISSUE CULTURE - DR. NYBERG & V. MILLER - NORTH WALL

4' - 0"

4' - 0"

3' - 0"

18BD4 30BC1

8

C120

30

2' - 8"

C105

J

4

18BD4 24BC1

5

Checked By

9

25

5' - 9"

6

13' - 2"

1 A921

13' - 2" 3

1"

4

4 A920

TISSUE CULTURE - DR. NYBERG & V. MILLER - SOUTH WALL

5

36BC1

11' - 8"

4' - 10"

6 A920

19

18BD4

C108

Medical Sciences Building Fourth Floor

8' - 0"

1"

18BD4

1/4" = 1'-0"

C119 C124

Large Animal Surgery and Germ Free Facility

LAB BENCH 2 - DR. NYBERG - WEST

3

C109

30BC1 18BD418BD4 30BC1

16' - 0"

1 A921

1 A921

3

C106

C105

8' - 0"

8' - 0"

30SC

4

3

2' - 8 1/4"

4' - 1"

30SC

18

1/4" = 1'-0"

13' - 6"

2' - 7 3/4"

6

LAB BENCH 2 - DR. NYBERG - EAST

07.03.13

1 2' - 7 1/4"

6

11902

3

4' - 2"

18BD4 6' - 1"

1

2' - 6 1/2"

16' - 0"

13' - 6"

4' - 1"

2' - 0"

3' - 0"

N108

N118

3' - 0"

8' - 0"

N105

2' - 0"

3' - 0" N119

N133

24BC1

3636W

N228

2' - 0"

N132

8' - 0"

4

1/4" = 1'-0"

1 A921

4' - 1"

N123

Registration Number

Project For

4' - 1"

11"

4' - 0"

3' - 0"

N138

4' - 0"

4' - 1"

N128

LAB BENCH 1 - DR. NYBERG - WEST

16

N124

N115

4

1 A920

N125

11"

1836W

4

1/4" = 1'-0"

N101

N139

N117

1"

LAB BENCH 1 - DR. NYBERG - EAST

15

1/4" = 1'-0"

4

2' - 8"

24BC1

N131

4' - 0"

18BD4WB 16' - 0"

30BC1

4

N100

11"

18BD4WB

30BC1

N130

4' - 1"

1/4" = 1'-0"

1"

2' - 8 1/2"

N129

3' - 0"

14

2' - 8 1/2"

30BC1

N127

8' - 0"

8' - 0"

4' - 0"

4' - 0"

18BD4WB

1"

M244

4

LAB BENCH 3 - DR. V. MILLER - EAST

13

11"

11"

4' - 8"

18BD4WB 16' - 0"

3

G112

DAVID NORBCK

Date

8' - 0"

2' - 9"

G111

1 A921

13' - 6"

3

11"

1' - 0 1/2" 42BC1

6

M243

13' - 6"

3

3' - 0"

7

13' - 6"

3' - 0"

M239

M245

4' - 0" 3' - 0"

M231

3

4' - 1"

M241

8' - 0"

M224

8' - 0"

M230

M226

4' - 1"

M227

11"

M242

13' - 6"

1 A921

3' - 0"

13' - 6"

3

1 A921

11"

13' - 6"

1 A921

1 A921

4' - 1"

1 A921

11902

1"

4

7" 4' - 9"

3"

1 3 4 5 6 7 8 9 10 11 12

STANDARD STEEL COUNTERTOP SUPPORT WALL BRACKET (27x19) - SEE DETAIL 19/A920 ELECTRIC/ VOICE/ DATA RACEWAY - COORDINATE WITH ELECTRICAL PLASTIC LAMINATE FILLER. PLASTIC LAMINATE VENT CHASE - SEE DETAIL 9/A920 PLASTIC LAMINATE WALL CLEAT 1" PLASTIC LAMINATE END PANEL. PLASTIC LAMINATE PIPETE RACK - SEE DETAIL 16/A920 1" PLASTIC LAMINATE BACKER BOARD. GAS CYLINDER FURNITURE - SEE FURNITURE PLAN (I304) STANDARD LAB COAT HOOK STRIP MOUNTED AT 5'-0" A.F.F. UNLESS NOTED OTHERWISE SEE DETAIL 15/A920

INTERIOR ELEVATIONS

1' - 8"

A901


2' - 6"

4

18BC1

30BC1

4

+/-

2 A920

5' - 0"

EQ

EQ

11

11

Z229

Z224

5' - 0"

5' - 0"

Z225

EQ

EQ

11

11

8' - 0" 5' - 0"

8' - 0"

RSP Architects 320 South Broadway Ste. B 507.285.6569 Rochester, Minnesota 55904 612.677.7499 fax www.rsparch.com

OFFICE - SURGICAL TECH - WEST WALL

6

OFFICE - SURGICAL TECH - NORTH WALL

7

1/4" = 1'-0"

1/4" = 1'-0"

2 A920

12' - 0"

EQ

11

4

2"

1/4" = 1'-0"

2 A920 EQ

2' - 0"

3' - 0" 2' - 0"

8' - 0"

+/-

11

11

SOILDED WORK - EAST WALL

5

15' - 11"

2' - 0" Z202

3 A920

18BC1

2' - 9"

1"

1/4" = 1'-0"

EQ

8' - 0"

8' - 0"

5' - 0"

8' - 0"

2' - 0"

2' - 0"

EQ

24BC1

4

2' - 5"

SOILDED WORK - SOUTH WALL

2 A920

16' - 1"

Z206

EQ

Consultants

EQ

2' - 0"

2 A920

1/4" = 1'-0"

30SC

6

11

8' - 0"

1/4" = 1'-0"

4

18BD4

3' - 5 3/4"

4' - 9 1/2"

4

3636W

5' - 0"

1/4" = 1'-0"

PREP AREA - EAST WALL

3

3636W

2' - 0"

PREP AREA - SOUTH WALL

1836W

8' - 0"

18BD4

4

3' - 0" D

6 A920

2

3036W

E

8' - 0"

2' - 6"

12 A920

11 A920

3636W

2' - 0"

8' - 0"

4' - 0"

18BC1

BREAK ROOM - NORTH WALL

4' - 11"

Z205

3 3/4"

10 A920

1

6

24BD4 24BD4

10' - 9 3/4"

3636W

4

3"

2 A920

11

11

11

11

11

11

11

11

11

Certification

11

I hereby certify that I have reviewed the Mayo Clinic Standard General Specifications prepared by Ronald B. Carlson, License Number 10850, that they are appropriate for the work except as amended in this plan, specification or report, and that I am a duly licensed Architect under the laws of the State of Minnesota.

11

5' - 0"

30BC1

4

3636W

3"

8' - 0"

30BC1

Z215

2436W

3 1/4"

7 A920

3' - 0"

2' - 10"

G309

E

3' - 0"

G311

6

2' - 2"

D

4

Z212

4

9' - 0"

G310

3 1/4"

3' - 7 1/2"

2' - 0"

3636W

5' - 0"

7 A920

2' - 0"

1' - 0"

3636W

3' - 6"

5' - 0"

3' - 0"

MCB3018 2436W

3' - 6"

1 A920

3' - 0"

3 3/4"

1 A920

3' - 0"

20 A920

17 A920

11

11

11

11

11

11

11

11

Signature

DAVID NORBACK

Registration Number

6' - 1 1/2"

14

CLEAN STORAGE - SOUTH WALL

15

1/4" = 1'-0"

CLEAN STORAGE - WEST WALL

16

1/4" = 1'-0"

1/4" = 1'-0"

SECRETARY - WEST WALL

17

EQ

5' - 6"

I hereby certify that this plan, specification or report was prepared by me or under my direct supervision and that I am a duly licensed Architect under the laws of the State of Minnesota.

1 A920

Signature

18

1/4" = 1'-0"

4' - 0"

224 42 SF 52127 SF SF SF

SECRETARY - NORTH WALL

19

1/4" = 1'-0"

1' - 0" 8' - 0"

2' - 0"

434 30BC1 SF 143 SF

ORTHO PREP - WEST WALL

20

1/4" = 1'-0"

Project For

30SC

1"

ORTHO PREP - NORTH WALL

ORTHO PREP - EAST WALL

21

1/4" = 1'-0"

1/4" = 1'-0"

Large Animal Surgery and Germ Free Facility

4' - 0"

2' - 0"

22

30SC

18BD4

2' - 0"

F407

PREP ROOM - WEST WALL

23

1/4" = 1'-0"

2' - 6 1/4"

2' - 6 1/4"

E

GB-42

GB-36

D

GB-42

CWT-1

B

B

2' - 10"

52 248 235SF SF SF 140 51 SF 62 SF156 65 116 109 107 SF 129 SF SF SF SF SF 2' - 6 1/4"

GB-36

GB-42

TYP

D

2' - 10"

6

D

3' - 0"

3' - 0"

1

E

GB-18

8' - 0"

8' - 0"

8' - 0"

2' - 0"

2' - 0" 2' - 0"

1"

17-4

F413

4

1

E G

Medical Sciences Building Fourth Floor

GB-18

GB-36

G

6

07.03.13

4 30BC1 18BD4 1' - 8"

4

11902

6' - 0"

2' - 0"

8' - 0"

O101

3' - 0"

16-7

O102

O113

1836W

F406

DAVID NORBCK

Date

1 A920

10' - 1"

J

CLEAN STORAGE - NORTH WALL

O133

11

11

4"

4"

4"

11

12

4' - 1 1/4"

8' - 0"

4' - 6"

M123

EQ

07.03.13

Registration Number

4' - 6"

8' - 0"

3' - 0" 8' - 0"

7' - 0"

7' - 0"

8' - 0"

8' - 0"

7' - 0"

M122

5' - 6"

1' - 0"

5' - 7"

8' - 0"

5' - 7"

1 A920

8' - 4"

1' - 0"

5' - 9 3/4"

Date

1/4" = 1'-0"

1 A920

2 A920

6' - 0"

5' - 9 3/4"

1/4" = 1'-0"

1' - 0"

2 A920

8"

5' - 0 3/4"

1/4" = 1'-0"

CORRIDOR - SOUTH WALL

13

3' - 0"

1 A920

LARGE OFFICE 1 - NORTH WALL

12

3' - 6"

1/4" = 1'-0"

8"

1 A920

LARGE OFFICE 1 - SOUTH WALL

11

6"

1/4" = 1'-0"

3' - 6 1/4" 8"

4' - 10 1/2"

1 A920

SURGICAL TECHS - EAST WALL

10

3' - 0"

1/4" = 1'-0"

SURGICAL TECHS - NORTH WALL

6"

9

9

OFFICE - SURGICAL TECH - EAST WALL

8

11902

B C.1

Project #7R120760

2' - 6 1/4"

10' - 1"

PREP ROOM - NORTH WALL

TOILET MEN - WEST ELEVATION

24

1/4" = 1'-0"

1/4" = 1'-0"

25

TOILET MEN - NORTH ELEVATION

26

1/4" = 1'-0"

TOILET MEN - EAST ELEVATION

27

1/4" = 1'-0"

TOILET MEN - SOUTH ELEVATION 1/4" = 1'-0"

28

TOILET WOMEN - WEST ELEVATION 1/4" = 1'-0"

12"D. PLAM SHELF 3' - 0"

48" H. FRP PANELS ON BOTH WALLS ABOVE MOP BASIN

2' - 6"

Project No.

6287.040.04

Drawn By

BCS

D

BASE

C.1

G

12

E

GB-42

D

4' - 6"

E

8' - 0"

GB-36

B

8"

G

GB-18

2' - 10"

B

SERVICE FAUCET, RE: PLUMBING SILICONE SEALANT @ TOP EDGES OF BASIN AND ABUTTING F.R.P.

3' - 0"

G

HOSE BRACKET

9"

G

GB-36

1' - 6"

E

4' - 0"

GB-42

6' - 0"

GB-18

Checked By

G

MOP RACK

10"

C.2

SILICONE SEALANT @ ALL EDGES OF FRP BOARD

24" X 30" MOP SERVICE BASIN

TOILET WOMEN - NORTH ELEVATION 1/4" = 1'-0"

30

TOILET WOMEN - EAST ELEVATION 1/4" = 1'-0"

31

TOILET WOMEN - SOUTH ELEVATION 1/4" = 1'-0"

07/03/13

NOTICE: The designs shown and described herein including all technical drawings, graphics, and models thereof, are proprietary and cannot be copied, duplicated or commercially exploited, in whole or in part, without express written permission of RSP Architects. These are available for limited review and evaluation by clients, consultants, contractors, government agencies, vendors and office personnel only in accordance with this Notice. © Copyright RSP Architects 2007. All rights reserved.

Revisions No.

29

JHA/MLK

Date

32

MOP BASIN ELEVATION 1/2" = 1'-0"

33

TOILET/CHANGE - NORTH ELEVATION 1/4" = 1'-0"

34

TOILET/CHANGE - EAST ELEVATION 1/4" = 1'-0"

35

Date

Description

TOILET/CHANGE - SOUTH ELEVATION 1/4" = 1'-0"

KEYNOTES - ELEVATIONS

GB-18

12

GB-42 GB-36

B

36

1 3 4 5 6 7 8 9 10 11 12

STANDARD STEEL COUNTERTOP SUPPORT WALL BRACKET (27x19) - SEE DETAIL 19/A920 ELECTRIC/ VOICE/ DATA RACEWAY - COORDINATE WITH ELECTRICAL PLASTIC LAMINATE FILLER. PLASTIC LAMINATE VENT CHASE - SEE DETAIL 9/A920 PLASTIC LAMINATE WALL CLEAT 1" PLASTIC LAMINATE END PANEL. PLASTIC LAMINATE PIPETE RACK - SEE DETAIL 16/A920 1" PLASTIC LAMINATE BACKER BOARD. GAS CYLINDER FURNITURE - SEE FURNITURE PLAN (I304) STANDARD LAB COAT HOOK STRIP MOUNTED AT 5'-0" A.F.F. UNLESS NOTED OTHERWISE SEE DETAIL 15/A920

TOILET/CHANGE - WEST ELEVATION 1/4" = 1'-0"

INTERIOR ELEVATIONS

A902 C:\Revit Projects\Med Sci 4 Central_jschmit.rvt 7/8/2013 11:23:01 AM

Please purchase PDF Split-Merge on www.verypdf.com to remove this watermark.


OFFICE 4-27 - WEST WALL 1/4" = 1'-0"

2

1/4" = 1'-0"

1/4" = 1'-0"

4

11

5

5' - 10"

OFFICE - TYPICAL - EAST WALL 1/4" = 1'-0"

11

6

OFFICE 4-23 - WEST WALL 1/4" = 1'-0"

11

7

11

OFFICE 4-23 - NORTH WALL 1/4" = 1'-0"

M1

5' - 0"

M1

2 A920

2' - 0"

2' - 0"

5' - 1 1/2"

2' - 0"

2' - 0" M1

OFFICE - TYPICAL - NORTH WALL 1/4" = 1'-0"

5' - 0"

4' - 8"

2 A920

5' - 0"

5' - 0"

2' - 0"

3

OFFICE 4-27 - EAST WALL

4' - 2"

11

11

11

OFFICE 4-27 - NORTH WALL

4' - 2"

5' - 0"

5' - 0"

11

11

M1

2 A920

2 A920

5' - 0"

5' - 0"

2' - 0"

2' - 0" 5' - 0"

M1

2 A920

5' - 0"

5' - 1 1/2"

5' - 10"

1

2 A920

2' - 0"

2 A920

2 A920

11

8

OFFICE 4-23 - EAST WALL

RSP Architects 320 South Broadway Ste. B 507.285.6569 Rochester, Minnesota 55904 612.677.7499 fax www.rsparch.com

Consultants

1/4" = 1'-0"

Certification

I hereby certify that I have reviewed the Mayo Clinic Standard General Specifications prepared by Ronald B. Carlson, License Number 10850, that they are appropriate for the work except as amended in this plan, specification or report, and that I am a duly licensed Architect under the laws of the State of Minnesota.

Signature

DAVID NORBACK

Registration Number Date

11902 07.03.13

I hereby certify that this plan, specification or report was prepared by me or under my direct supervision and that I am a duly licensed Architect under the laws of the State of Minnesota.

Signature

DAVID NORBCK

Registration Number Date

11902 07.03.13

Project For

Large Animal Surgery and Germ Free Facility Medical Sciences Building Fourth Floor Project #7R120760

Project No.

6287.040.04

Drawn By

BCS

Checked By

JHA/MLK

Date

07/03/13

NOTICE: The designs shown and described herein including all technical drawings, graphics, and models thereof, are proprietary and cannot be copied, duplicated or commercially exploited, in whole or in part, without express written permission of RSP Architects. These are available for limited review and evaluation by clients, consultants, contractors, government agencies, vendors and office personnel only in accordance with this Notice. Š Copyright RSP Architects 2007. All rights reserved.

Revisions No.

Date

Description

INTERIOR ELEVATIONS

A903 C:\Revit Projects\Med Sci 4 Central_jschmit.rvt 7/8/2013 11:23:02 AM

Please purchase PDF Split-Merge on www.verypdf.com to remove this watermark.


VARIES

VARIES

SEE ELEVATIONS 5' - 1 1/4"

SEE PLANS FOR COUNTERTOP SIZE AND TYPE

PLASTIC LAMINATE SINK CABINET

PLASTIC LAMINATE BASE CABINET

3'-0"

4 3/8"

NOTE: SEE ELEVATIONS FOR THE QUANTITY OF SHELVES, USE HEAVY DUTY UNISTRUT STANDARDS AND BRACKETS. SPACED AT 2'-6" OC MAX

NOTE: SEE ELEVATIONS FOR THE QUANTITY OF SHELVES, USE STANDARD KV STANDARDS AND BRACKETS. SPACED AT 2'-6" OC MAX

3"

1' - 7"

7"

3"

1' - 7"

1 5/8" X 1 5/8" UNISTRUT

RSP Architects 320 South Broadway Ste. B 507.285.6569 Rochester, Minnesota 55904 612.677.7499 fax www.rsparch.com

WIREMOLD G4000

VARIES

Consultants

TYPICAL STANDARD KV ADJUSTABLE SHELVING

2

3/4" = 1'-0"

5 1/8"

WIREMOLD G4000

TYPICAL HEAVY DUTY UNISTRUT ADJUSTABLE SHELVING

1

6"

VARIES

6"

3/4" PLASTIC LAMINATE BOOKEND - AS INDICATED IN ELEVATIONS (PLAM-1) SEE ELEVATION

SEE ELEVATION

1" PLASTIC LAMINATE BOOKEND (PLAM-1) AS INDICATED IN ELEVATIONS P4100 UNISTRUT CHANNEL HORIZONTAL

EQ

SEE PLANS FOR COUNTERTOP SIZE AND TYPE

STANDARD KV VERTICAL CHANNELS

3'-0"

11" TYP.

P4100 UNISTRUT CHANNELS VERTICAL

EQ

3/4" PLASTIC LAMINATE SHELVING ON STANDARD KV ADJUSTABLE BRACKETS - SEE ELVATION FOR QUANTITY

SEE ELEVATION

3'-0"

SEE ELEVATION

6"

1" PLASTIC LAMINATE SHELVING (PLAM-1) 1" PLASTIC LAMINATE SHELVING ON UNISTRUT ADJUSTABLE BRACKETS - SEE ELEVATIONS FOR QUANTITY

6"

3/4" PLASTIC LAMINATE SHELVING (PLAM-1)

SEE ELEVATIONS

6"

2' - 7"

VARIES

EQ

3'-0"

EQ

1' - 0" U.N.O.

2' - 7"

SEE ELEVATIONS

6"

P4100 UNISTRUT CHANNEL HORIZONTAL

5' - 1 1/4"

11" TYP.

1' - 0" U.N.O.

SEE ELEVATIONS

TYPICAL SINK CABINET SECTION

3

3/4" = 1'-0"

4

3/4" = 1'-0"

TYPICAL BASE CABINET SECTION

5

3/4" = 1'-0"

WIREMOLD POWER POLE DETAIL 3" = 1'-0"

Certification

I hereby certify that I have reviewed the Mayo Clinic Standard General Specifications prepared by Ronald B. Carlson, License Number 10850, that they are appropriate for the work except as amended in this plan, specification or report, and that I am a duly licensed Architect under the laws of the State of Minnesota.

1' - 0 5/8" P4100 UNISTRUT CHANNEL

6

1' - 7"

TYPICAL BASE CABINET SECTION W/ DRAWERS

7

3/4" = 1'-0"

UPPER CABINET - TWO ADJ. SHELVES W/UNISTRUT

2 1/2"

4"

7 1/8"

BACK PANEL WITH PLASTIC LAMINATE FACE

3/4"

2' - 10 1/2"

3/4"

2' - 4 1/2"

3"

BASE CABINET SECTION - BREAKROOM

10

1/2"

4 3/4"

3" X 3" LEG

HOOKS (TYP.)

SEE ELEVATIONS

SHELF BRACKET HOLES @ 32 MM O.C. (TYP.)

3"

2' - 6"

FRONT VIEW

6" TYP. PLAM MOUNTING BOARD (PLAM-1)

SIDE VIEW

3/4" = 1'-0"

CYLINDER SUPPORT DETAIL

14

3/4" = 1'-0"

SECTION AT SAND TABLE

15

3/4" = 1'-0"

TYPICAL LAB COAT HOOK

1" P-LAM (TYP.)

1" = 1'-0"

4"

13

1' - 0 1/2"

2' - 2 3/4"

BASE CABINET SECTION W/ DRAWERS BREAKROOM

CEILING LINE

Project #7R120760

3/4" PLASTIC LAMINATE SHELVING

2' - 6"

2' - 0"

2' - 2 5/8"

3"

SLIDE OUT PLASTIC LAMINATE SHELVES WITH HEAVY DUTY SHELF GUIDES

8 5/8"

3"

3' - 0"

1"

1" P-LAM PULL OUT WRITING BOARD

6" 2' - 6"

5'-0" A.F.F.

3"

2' - 6"

1' - 1"

1' - 0"

SECTION VIEW

WALL LINE

ALL EXTERIOR EXPOSED SURFACES AND EDGES ARE PLASTIC LAMINATE OVER 3/4" MDF INCLUDING FLUSH OVERLAY DOOR(S) ON CONCEALED HINGES TYPICAL

2' - 0"

FRONT VIEW

Project No.

3/4" = 1'-0"

Checked By

1' - 9"

1'-6"

17

C:\Revit Projects\Med Sci 4 Central_jschmit.rvt 7/8/2013 11:23:03 AM

Please purchase PDF Split-Merge on www.verypdf.com to remove this watermark.

18

P-LAM STORAGE CABINET SECTION (18" DEEP) 1" = 1'-0"

1" = 1'-0"

1"

11" 1/8" DRIP GROOVE

COUNTERTOP TYPE: E

COUNTERTOP TYPE: F

DIM. 2' - 4 1/2"

4" WIRE PULL

1' - 5" NOTE: G.C. TO PROVIDE BLOCKING IN STUD WALL AS REQUIRED

4 1/2" 1"

WHITE THERMOFUSED MELAMINE OVER 3/4" MDF INTERIORS W/ ADJUSTABLE SHELVES AND 1/4" THERMOFUSED MELAMINE BACK TYPICAL

1/8" DRIP GROOVE COUNTERTOP DESIGNATION COUNTERTOP TYPE - SEE ABOVE

1/8" DRIP GROOVE

C31-PL

INDICATES: FINISH ( SEE BELOW )

DIM TYPICAL FINISHES PL = PLASTIC LAMINATE SS = STAINLESS STEEL AR = ACID RESISTANT

TYPICAL LABORATORY COUNTERTOPS

20

UPPER CABINET - TWO ADJ. SHELVES 1" = 1'-0"

DIM. 2' - 4 1/2"

4 1/2"

11"

SEE ELEVATIONS

1/8" DRIP GROOVE

COUNTERTOP INSTALLATION CLEARANCES

19

1" 1"

ALL EXTERIOR EXPOSED SURFACES AND EDGES ARE PLASTIC LAMINATE OVER 3/4" MDF INCLUDING FLUSH OVERLAY DOOR(S) ON CONCEALED HINGES TYPICAL

6"

DETAIL OF COUNTER SUPPORT BRACKET

1"

2' - 1"

DIM.

1"

2' - 3"

EQ

1" = 1'-0"

1' - 6"

Description

COUNTERTOP TYPE: D

1"

7' - 4 1/2"

4" 1' - 11 1/2"

Date

2' - 1"

HATCHED AREA INDICATES MIN. A.D.A. TOE SPACE CLEARANCE

3"

PLAM BASE

No.

DIM.

1' - 0"

DEEP TOP DEEP TOP DEEP TOP DEEP TOP

8"

B

4"

NOTE: SUPPORTS TO BE SHOP PRIMED: PAINT TO MATCH WALLS AT TIME OF INSTALLATION

1/8" DRIP GROOVE

2"

5"

VARIES SEE ELEVATIONS

2' - 4 1/2"

PROVIDE FIRE TREATED 2" x 8" WOOD BLOCKING AS REQ'D. TO SUPPORT BRACKET

WHITE THERMOFUSED MELAMINE OVER 3/4" MDF INTERIORS W/ ADJUSTABLE SHELF AND 1/4" THERMOFUSED MELAMINE BACK TYPICAL

SECTION AT MICROWAVE CABINET WITH BASE CABINET DRAWER AND DOOR

1/8" DRIP GROOVE COUNTERTOP TYPE: C

"A" "B" 16" 12" FOR 18" - 21" 21" 15" FOR 22" - 26" 27" 19" FOR 29" - 32" 32" 22" FOR 33" - 36"

ADJUSTABLE PLASTIC LAMINATE SHELVING SEE ELEVATIONS FOR QUANTITY

2' - 0 1/2"

1"

1/4" DIA. MOUNTING HOLES FOR WALL FASTENER (TYPICAL)

STEEL SUPPORT BRACKET - PROVIDE BRACKETS AS SHOWN ON DRAWINGS AT 3'-0" O.C. MAX.

SHELF BRACKET HOLES @ 32 MM O.C.

Revisions

DIM.

2' - 0"

A

4" WIRE PULL

2 1/4"

DIM.

TYPICAL SUPPORT BRACKET

FIXED PLASTIC LAMINATE SHELF

COUNTERTOP TYPE: B

1/8" STEEL

9"

1 1/2"

ALL EXTERIOR EXPOSED VERTICAL SURFACES AND EDGES ARE PLASTIC LAMINATE OVER 3/4" MDF INCLUDING FLUSH OVERLAY DOOR(S) ON CONCEALED HINGES TYPICAL

COUNTERTOP TYPE: A

5"

1"

PLASTIC LAMINATE COUNTER TOP AND BACK SPLASH

4"

1' - 8"

© Copyright RSP Architects 2007. All rights reserved.

1/4" DIA. MOUNTING HOLES FOR CSK. FHWS. (TYPICAL)

PLASTIC LAMINATE CABINET DOOR PLASTIC LAMINATE OVER 1" MDF SHELF

2' - 10"

SEE SCHED. BELOW

EQ

1' - 6"

ELECTRICAL OUTLET, SEE ELECTRICAL

ADJUSTABLE PLASTIC LAMINATE SHELVING SEE ELEVATIONS FOR QUANTITY

3"

2 43/64"

FIRE TREATED WOOD BLOCKING ANCHORED BETWEEN STEEL STUD

07/03/13

NOTICE: The designs shown and described herein including all technical drawings, graphics, and models thereof, are proprietary and cannot be copied, duplicated or commercially exploited, in whole or in part, without express written permission of RSP Architects. These are available for limited review and evaluation by clients, consultants, contractors, government agencies, vendors and office personnel only in accordance with this Notice.

3"

4" WIRE PULL

3/4"

JHA/MLK

Date

WHITE THERMOFUSED MELAMINE OVER 3/4" MDF INTERIORS W/ ADJUSTABLE SHELVES AND 1/4" THERMOFUSED MELAMINE BACK TYPICAL

1"

JAS

PLASTIC LAMINATE PIPETTE RACK

SEE SCHED. BELOW

2' - 1"

6287.040.04

Drawn By

16

1' - 6"

Medical Sciences Building Fourth Floor

4' - 6"

SAND FILL

3" 3"

2' - 10"

12

1' - 7"

EQ

3/4" ADJUSTABLE PLASTIC LAMINATE SHELVING - SEE ELEVATIONS FOR QUANTITY (TYP.)

3" X 3" SIDE RAIL

3"

9"

Large Animal Surgery and Germ Free Facility

5' - 0 "

LIGHT WEIGHT CHAIN ATTACHED TO UNISTRUT WITH ATTACHMENT BOLTS. CHAIN SHALL BE CUT AT MID POINT AND CONNECTED TO EACH OTHER WITH SPRING CLIP.

07.03.13

3/4" = 1'-0"

3/4"

1"

PLASTIC LAMINATE BASE CABINET W/ DRAWERS

11902

ADA COMPLIANT SINK SECTION BREAKROOM

11

3/4" = 1'-0"

1" RIGID INSULATION

1' - 10 1/4"

1 1/4" UNISTRUT ATTACHED TO 2"X8" FIRE TREATED WOOD BLOCKING IN WALL WITH 3/8" X 3 1/2" THRU BOLTS AT 10" OC MAX

2' - 10 1/2"

SEE ELEVATIONS

CYLINDERS - BY OWNER

Registration Number

1' - 8"

1" MARBLE TOP SEE PLANS FOR COUNTERTOP SIZE AND TYPE

DAVID NORBCK

Project For

3" = 1'-0"

3/4"

I hereby certify that this plan, specification or report was prepared by me or under my direct supervision and that I am a duly licensed Architect under the laws of the State of Minnesota.

7' - 0"

VARIES - SEE FLOOR PLAN

07.03.13

Date

EQ

2' - 1"

11902

SCHEDULED BASE

2 1/2"

P-LAM VENT CHASE

9

1" = 1'-0"

Date

Signature

5"

UPPER CABINET - ONE ADJ. SHELF

8

1" = 1'-0"

WALL BLOCKING AS REQUIRED

REMOVABLE PLASTIC LAMINATE (PLAM-1) PANEL W/ EXPOSED SCREWS & GROMMETS

NOTE: G.C. TO PROVIDE BLOCKING IN STUD WALL AS REQUIRED

3/4"

SOAP DISPENSER PLASTIC LAMINATE BASE CABINET

DAVID NORBACK

Registration Number

2' - 10"

4" WIRE PULL

2' - 1"

PLASTIC LAMINATE COUNTER TOP ON 3/4" MDF WITH BACK SPLASH

CENTERLINE OF BENCH SEE MECH & ELEC FOR PIPING AND CONDUITS

Signature

1 1/2"

6"

ALL EXTERIOR EXPOSED SURFACES AND EDGES ARE PLASTIC LAMINATE OVER 3/4" MDF INCLUDING FLUSH OVERLAY DOOR(S) ON CONCEALED HINGES TYPICAL

NOTE: G.C. TO PROVIDE BLOCKING IN STUD WALL AS REQUIRED

VARIES

FIXED PLASTIC LAMINATE END PANELS (PLAM-1)

SEE ELEVATIONS

WHITE PLASTIC LAMINATE OVER 3/4" MDF INTERIORS W/ ADJUSTABLE SHELVES AND 1/4" BACK TYPICAL

SEE PLANS FOR COUNTERTOP SIZE AND TYPE

6"

SEE ELEVATIONS

1' - 0"

4" WIRE PULL

3"

BLACK THERMOFUSED MELAMINE OVER 3/4" MDF INTERIORS W/ ADJUSTABLE SHELF AND 1/4" THERMOFUSED MELAMINE BACK TYPICAL

SEE ELEVATIONS

3'-0"

PLASTIC LAMINATE BASE CABINET W/ DRAWERS

VARIES

SEE ELEVATIONS

SEE PLANS FOR COUNTERTOP SIZE AND TYPE

ADA COMPLIANT SINK AND FAUCET, REFER TO PLUMBING DRAWINGS

2' - 1"

ALL EXTERIOR EXPOSED SURFACES AND EDGES ARE PLASTIC LAMINATE OVER 3/4" MDF INCLUDING FLUSH OVERLAY DOOR(S) ON CONCEALED HINGES TYPICAL

1' - 0"

2' - 7"

LINE OF BACKSPLASH

NOT TO SCALE

MILLWORK DETAILS

A920


2' - 2"

2' - 2" 1 1/4" x 2" REEVE #80 TUBE WITH OUT SLOTS. FILLER @ EXPOSED END

VARIES - SEE ELEVATIONS

3"

8 3/4"

1/8" 1"

SECTION AT KNEE SPACE

1' - 7"

2" 2"

1 5/8"

3"

11"

6 1/2"

9"

1' - 10" 1 7/8" 1 5/8"

Consultants SEE ELEVATIONS FOR SPACING OF TUBES

9"

2"

5/8"

1 1/4" VERTICAL TUBE SUPPORTS

Certification

2"

1' - 10"

1' - 0" 2"

1 7/8" 1 5/8"

1' - 0"

1' - 8 1/2" 3/4"

2" FACE OF COUNTERTOP ABOVE

PLAN DETAIL AT ISLAND ABOVE COUNTERTOP

I hereby certify that I have reviewed the Mayo Clinic Standard General Specifications prepared by Ronald B. Carlson, License Number 10850, that they are appropriate for the work except as amended in this plan, specification or report, and that I am a duly licensed Architect under the laws of the State of Minnesota.

Signature

PLASTIC LAMINATE END PANELS

PLASTIC LAMINATE BASE CABINET

4

3/4" = 1'-0"

Date

VERTICAL TUBE DETAIL AT ISLAND

07.03.13

Signature

PLASTIC LAMINATE (PLAM-5) COUNTERTOP

DAVID NORBCK

Registration Number Date

9 A921

11902 07.03.13

Project For

WOOD EDGE (WD-1) ALL EXPOSED SIDES MDF VENEER (PLAM-5) SHELF

MDF VENEER (PLAM-5) PANEL BEYOND

MDF VENEER (PLAM-5) PANEL BEYOND

MDF VENEERED BACK PANEL COORDINATE OPENINGS WITH A.V.

MDF VENEERED BACK PANEL COORDINATE OPENINGS WITH A.V.

MDF VENEER (PLAM-5) BASE

MDF VENEER (PLAM-5) BASE

WOOD EDGE (WD-1) ALL EXPOSED SIDES

1"

1" PLASTIC LAMINATE COUNTERTOP (PLAM-5)

Large Animal Surgery and Germ Free Facility

3/4" PLASTIC LAMINATE INSIDE CABINET FACING

4"

MDF VENEER BASE (PLAM-5)

11902

I hereby certify that this plan, specification or report was prepared by me or under my direct supervision and that I am a duly licensed Architect under the laws of the State of Minnesota.

6" = 1'-0"

2' - 0"

5

DAVID NORBACK

Registration Number

PLAN DETAIL AT ISLAND BELOW COUNTERTOP

3

3/4" = 1'-0"

MDF VENEER (PLAM-5) SHELF

3' - 5"

5"

3/4"

2' - 0 1/2"

FACE OF COUNTERTOP

WOOD EDGE (WD-1) ALL EXPOSED SIDES

MDF VENEER (PLAM-1) BASE

4"

3/4"

1 1/4"

9 A921

MDF VENEER (PLAM-5) PHONE POCKET HOLDER - ATTACH TO CABINET WITH (4) MOD-EEZ CLIPS

6"

1' - 2"

5/8"

3/4" PLYWOOD

6"

6"

1" 3/4" 3/4"

3' - 5"

2' - 3"

5"

MDF VENEER PHONE POCKET HOLDER (PLAM-1)

3/4"

3/4" PLYWOOD

PLAM COUNTERTOP (PLAM-5)

2' - 1"

WIRELESS KEYBOARD & MOUSE SHELF

3/4"

DVD/VCR

DASHED LINES INDICATE FACE OF CABINET BELOW

PLASTIC LAMINATE (PLAM-5) COUNTERTOP

4' - 3 1/2"

4 A921

DASHED LINES INDICATE REAGENT SHELVING ABOVE

2 3/4"

CABLE NOOK

"LIFT-OFF" LOCKABLE RACK MDF VENEER (PLAM-1) DOOR

4' - 9"

2' - 3 1/2" 2"

4' - 9"

1 5/8"

2

PLAM COUNTERTOP (PLAM-1)

VARIES SEE ELEVATIONS 1 5/8"

PLASTIC LAMINATE END PANEL

3/4" = 1'-0"

8 A921

RSP Architects 320 South Broadway Ste. B 507.285.6569 Rochester, Minnesota 55904 612.677.7499 fax www.rsparch.com

1 1/4" x 2" VERTICAL TUBE SUPPORTS SEE ELEVATIONS FOR SPACING

1 1/2" 1/8" 1"

TYPICAL PENINSULA/ ISLAND SECTION DETAILS

7 A921

1 5/8" UNISTRUT FRAMING

2"

VARIES

3'-0"

BOLT TO CONC. W/ EXPAN. BOLTS AND UNISTRUT ANGLES

9"

1

1' - 7"

2" 2"

BOLT REEVE #80 TUBE TO UNISTRUT

1 5/8" FRAMING

4" 1 5/8"

5/8"

1 1/4" x 2" VERTICAL TUBE SUPPORTS

PLAM CHASE AS NOTED ON PLAN

4' - 9"

PLASTIC LAMINATE PANELS

1 1/2" 1 5/8"

5/8" 1 5/8"

FACE OF PLASTIC LAMINATE PANEL

CENTERLINE OF VERTICAL TUBE SUPPORT

2' - 3 1/2"

BOLT UNISTRUT CONNECTIONS SPRING LOADED NUTS, TYP.

SEE ELEVATIONS

3' - 0"

VARIES

SCALE: 3" = 1'-0"

2"

WIREMOLD

1 5/8" UNISTRUT FRAMING CHANNEL

4' - 9"

SECTION AT CABINETS

4'-1"

SEAL COUNTERTOP AROUND TUBE SUPPORTS

WIREMOLD

3/4"

CENTERLINE OF VERTICAL TUBE SUPPORT

SPACING OF VERTICAL TUBE SUPPORTS

5/8" 5/8"

SEE ELEVATIONS

BACK PLATE: 1/8" x 2" CLEAR PLEXIGLAS, MECHANICALLY FASTEN TO BACK OF SHELF ( TYP. )

VARIES

BACK PLATE: 1/8" x 2" CLEAR PLEXIGLAS, MECHANICALLY FASTEN TO BACK OF SHELF ( TYP. )

1" P. LAM. SHELF ON REEVE #81-12 SHELF BRACKET AT EACH SHELF

SEE ELEVATIONS FOR

4"

FACE OF PLAM PANEL BELOW

SEE ELEVATIONS

SCALE: 3" = 1'-0"

1 1/4" x 2" REEVE #80 TUBE W/ SLOTS STARTING 38" A.F.F. SEE ELEVATIONS FOR SPACING

SEE ELEVATIONS

4' - 1"

VARIES

VARIES - SEE ELEVATIONS

2 1/2"

4' - 5"

ALL OTHER NOTES SIMILAR

AV CABINET FRONT ELEVATION

6

1" = 1'-0"

ACCESSORY MOUNTING DIAGRAM FOR MINIMUM ADA GUIDELINES

AV CABINET SIDE ELEVATION

AV CABINET SECTION A

7

1" = 1'-0"

8

1" = 1'-0"

AV CABINET SECTION B

9

1" = 1'-0"

Medical Sciences Building Fourth Floor

AV CABINET COUNTER DETAIL 3" = 1'-0"

INFORMATION HERE IS FOR REFERENCE ONLY. ANY DIMENSIONS, NOTES, TEXT OR FINISHES ON ARCHITECTURAL PLANS OVERRIDES THE INFORMATION FOUND ON THIS SHEET.

SCALE: 1/2" = 1'-0"

Project #7R120760

NOTE: REFER TO TOILET PLAN LAYOUT FOR GRAB BAR DIMENSIONS AND LAYOUT

42" 3' -MIN. 6"

TO START BUTTON

(3'-6" AT COUNTER)

JHA/MLK

Date

3' - 4"

36" - 48"

1' - 6 1/8"

JAS

Checked By

4'-0" MAX. TO DISP. SLOT

TO SPOUT

TO SHELF

30" - 33"

33" - 36"

6287.040.04

Drawn By

7" - 9"

1'-5"

17" - 19"

1' - 0"

40" - 44"

7" - 9"

Project No.

30" - 33"

MIN.

1' - 6"

39" - 41"

39" - 41"

MAX.

KEEP WASTE RECEPTACLE IN LINE WITH TOILET TISSUE DISPENSER

15" MIN.

1' - 0"

07/03/13

NOTICE: The designs shown and described herein including all technical drawings, graphics, and models thereof, are proprietary and cannot be copied, duplicated or commercially exploited, in whole or in part, without express written permission of RSP Architects. These are available for limited review and evaluation by clients, consultants, contractors, government agencies, vendors and office personnel only in accordance with this Notice. © Copyright RSP Architects 2007. All rights reserved.

Revisions

TOILET TISSUE DISPENSER

D

SANITARY PRODUCT DISPOSAL

E

F

UTILITY SHELF

G1

SOAP DISPENSER

PAPER TOWEL DISPENSER

H

No.

HAND DRYER

SANITARY PRODUCT DISPENSER

C:\Revit Projects\Med Sci 4 Central_jschmit.rvt 7/8/2013 11:23:05 AM

K

FRAMED MIRROR

Please purchase PDF Split-Merge on www.verypdf.com to remove this watermark.

K1

FRAMED MIRROR

L

UNFRAMED MIRROR

M

COAT HOOK

N

SHOWER SEAT

O

BABY CHANGING STATION

48" MAX.

54" MAX.

LATC H M EC H AN I SM

18" MAX.

2' - 10"

TO TRAY

60" TYP.

ACCESSIBLE

48" MAX.

35" MAX AT FLOOR

MEASURED TO BOTTOM OF VIEWING SURFACE

40" MAX AT LAVATORY

1' - 6"

MEASURED TO BOTTOM OF VIEWING SURFACE

Description

CL

3'-4"

3'-4" MAX AT LAVATORY 2'-11" MAX AT FLOOR

TO HIGHEST OPERATING MECHANISM

4' - 0" MAX.

J

MEASURED TO BOTTOM OF VIEWING SURFACE

Date

4' - 0"

C

GRAB BAR HEIGHT

48" MAX.

B

TOILET SEAT HEIGHT

5' - 0"

A

CASEWORK DETAILS AND ACCESSORY MOUNTING DIAGRAM P

EMERGENCY NURSE CALL

Q

SHARPS CONTAINER

R

GLOVE DISPENSER

A921


Turn static files into dynamic content formats.

Create a flipbook
Issuu converts static files into: digital portfolios, online yearbooks, online catalogs, digital photo albums and more. Sign up and create your flipbook.