Commercial Boiler Control Heatronic 4000 Don‘t let its small size fool you, the Heatronic 4000 is a powerful control packed with functionality. Designed for easy and intuitive set-up, the Heatronic 4000 is pre-loaded with the parameters for Bosch and Buderus commercial boilers.
A Flexible Control Solution for Light Commercial and Large Scale Residential Applications. The Heatronic 4000 is a cost effective control that works with up to four condensing and non-condensing boilers that are either modulating, single stage or two stage. Designed to accurately maintain target water temperature based on outdoor temperature reset or a fixed setpoint for space or process heating applications. Optional features to increase efficiency and boiler plant reliability include domestic hot water and setpoint heating, boiler run-time balancing,
Features
standby primary pump operation, and pump exercising.
▶ Control and monitor up to 4 boilers in any combination of condensing and conventional models
Remote monitoring and adjustments for the Heatronic 4000 are possible with Building Automation Systems - BACnet® or Modbus® Bosch and Buderus boiler parameters are pre-programmed in the Heatronic 4000 for ease of set up. Installing the Heatronic 4000 will save energy and further reduce the overall energy bill. BoschHeatingAndCooling.com
▶ BacNet® and Modbus® compatible ▶ Programmable scheduling DHW priority and Outdoor temperature reset ▶ Compatible with modulating, single stage, two stage and dual fuel burners, for NG, LP and oil fuel types ▶ Pre-configured with over 20 parameters for all Bosch / Buderus commercial boilers
3.5 3.5 Application Application 3 3
Features: Description: Features: Description: Single temperature system with two modulating condensing boilers Small size, big functionality 3.5 Application 3 Single temperature system with two modulating condensing boilers The The boiler boiler plant plant is is sequenced sequenced to to obtain obtain operated to to provide heat heat for for space space heating heating and and indirect indirect DHW DHW operated maximum efficiency efficiency based based on on the the boiler boiler Designed toprovide prolong the lifespan of the equipment the Heatronic 4000 Features: maximum loads. The The boiler boiler target target temperature temperature for for the the space space heating heating load load is is Description: loads. types & & target target temperatures. temperatures. For For detailed detailed types provides system reliability and for added comfortboilers and determined from reset. Schematic is Single temperature systemtemperature withredundancy two modulating condensing determined from outdoor outdoor temperature reset. Piping Piping Schematic is The boiler plant is sequencing, sequenced torotation obtain & information about sequencing, rotation & information about Primary /Secondary Piping. protection. Maximizing energy savings and system reliability is achieved operated to provide heat for space heating and indirect DHW Primary /Secondary Piping. maximum efficiency based on the boiler staging, refer to the Installation & Operation staging, refer to the Installation & Operation Applications Manual Bosch Heatronic 4000 Controls | loads. boiler target for the space heating load is using The sequencing basedtemperature on target temperatures - either outdoor reset or types & target temperatures. For detailed Manual. Manual. determined from outdoor temperature reset. Piping Schematic is information about sequencing, rotation & fixed set point, automatically maintaining the boiler differential, primary Temperature Reset energy Primary /Secondary Piping. Essential Source (#) Settings: Outdoor Outdoorrefer Temperature Reset saves saves energy Essential Source (#) Settings: staging, to the Installation & Operation pump sequencing, domestic hot water priority, set point operation and by operating the theFeatures: boiler plant plant using using the the by operating boiler 2 Controls Description & Manual. BOSC BOILER (2) = YES ENABLE (1) = AUTO BOILER for (2)optimal = YES energy ENABLE (1) =air AUTO combustion damper control allBOSC work together lowest possible temperatures. Lower water or Control and monitor up to 4 condensing, lowest possible temperatures. Lower water Speci cations BOSC BOSC BOILER (1) = YES non-condensing boilerscondensing BOSC MODL MODL (2) (2) = = “SB-Series” “SB-Series” BOSC BOILER (1)(#) = reliability. YES temperatures Outdoor Temperature Reset saves energy temperatures ensure modulating savings and system Essential Source Settings: ensure modulating condensing BOSC BacNet® and Modbus® compatible ENABLE (3) (3) = = OFF OFF BOSC MODL MODL (1) (1) = = “SB-Series” “SB-Series” ENABLE by operating the plant efficiency. using the boilers operate at maximum boilers operate atboiler maximum efficiency. 2.1 description BOSC BOILER (2)Brief = YES ENABLE (1) = AUTO Programmable scheduling ENABLE (4) (4) = = OFF OFF ENABLE (2) (2) = = AUTO AUTO ENABLE ENABLE lowest possibletemperatures. Lower water DHW DHW priority The Heatronic 4000 communicates with aMODL Building BOSC (2) =Heatronic “SB-Series” BOSC BOILER (1) = YES Optional (IDHW) TheManagement 4000 is designed to up to four indirect operate Optional indirect DHW (IDHW) priority. priority. temperatures ensure modulating condensing boilers to produce and maintain a target temperature. Outdoor temperature reset ENABLE (3) = OFF BOSC MODL (1) = “SB-Series” System (BMS) using BACnet® or Modbus® for remote The Heatronic 4000 operates both condensing and nonboilers operate at maximum efficiency. Boiler ∆T monitoring is available when using Compatible with modulating, stage, two stag Boiler ∆T monitoring is available whensingle using condensing boilers that have modulating, single stage, two ENABLE (4) = OFF ENABLE (2) = adjustment AUTO Essential System Settings: monitoring & capability. and dual fuel burners Essential System Settings: optional boiler outlet sensors (S6 & S7) and stage, or dual fuel burners to provide a optional more exible,boiler cost outlet sensors (S6 & S7) and Optional indirect (IDHW) priority. DHW Compatible with NG, LPG & oil burners effective mixed plant solution with better system control,sensor IDHW = APP boiler (S5). IDHW LOCATION LOCATION = PRIM PRIM APP MODE MODE = = RSET RSET boiler inlet inlet sensor (S5). energy efciency and overall performance. Programmed Bosch / Buderus boiler list Boiler ∆T monitoring is available when using IDHW PUMP 1 AUTO IDHW SENSOR SENSOR = = ON ON PUMP 1= = System AUTO Settings: Pre-configured boiler default parameters Essential The The Common Common Flue Sensor (S8)(S6 is optional. optional. optional boilerFlue outlet sensors & S7) and Sensor (S8) is IDHW PRIM PRIM PUMP PUMP = = OFF OFF PUMP 2 2= = OFF OFF IDHW PUMP Front View inlet sensor (S5). IDHW LOCATION = PRIM APP MODE = RSET boiler Side View IDHW MODE Schematic IDHW MODE = = ON ONfor Single IDHW SENSOR = ON PUMP 1 = AUTO 1/2" Knock-out (x 16 back) (x 8 top) Temperature Boiler Control The Common Flue Sensor (x 8 bottom) (x 2 side)(S8) is optional. IDHW PRIM PUMP = OFF PUMP 2 = OFF TheMODE sample=schematic is for a space heating and IDHW ON PrimPump Comb Flow Proof AirProof 1
indirect DHW application using two Bosch Buderus SB
6
DHW Fuel 20V mA 5V Vdc Gnd EMS Out Prim Com Prim DHW Com Com Boil Com Boil1Boil2Com Boil3Boil4 Com Flue In Out Out Out Out Tank Call Switch dc (+) dc (+) (-) (+) door Sup (-) Ret Out In Out In In 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 Tem perature Sensors -D o N otApply Pow er Flow Pressure Sensor Sensor
1 2 3 4 5
47 48 49 50 Primary Primary Pump Pump P1 P2
H6106A
S8 S8 = = P1 S5 = P1 =
Vent Vent Sensor Sensor Primary Pump Boiler Inlet Sensor Primary Pump
S2 = Primary Supply Sensor
S6, S7 = Boiler Outlet Sensors
S3 = Primary Return Sensor
S8 =
Vent Sensor
S4 = DHW Sensor
P1 =
Primary Pump
S8 S7 S7
S6 S6
P2, P2, P3 P3 = = P4 = P4 =
S7
P2 P2
SB Series SB Series
Auxiliary
Alert Dry
43 44 45 46
59 60 61 62
63 64 65 66 67 68 69 70 71 72 73 74
158033 Type 1056-XX W ARNING!Before opening the coverdisconnectfrom powersupply
InputPower: 115 V (ac)±10% ,60 Hz,18 VA Primar y Pump Relays: 230V (ac),10 A,1/2 hp Boiler & DHW Pumps: 230V (ac),5 A,1/3 hp Boiler Stage,Auxiliary & Aler tRelays: 230V (ac),5 A,1/6 hp Calls :24 V (ac)orShort
Designed and assembled in Canada by tekmarControlSystems
75 76 77 78
79 80 81 82
83 84 85 86
Boiler1 Pump
Boiler3 Pump
PowerIn DHW Tank L N Pump
Boiler2 Pump
Boiler4 Pump
8-1/16" (204 mm)
Signal wiring mustbe rated atleast300 V.
Ø 3/16" (5 mm)
External Flow Flow Proof Proof External // Off Off DIP Settings: External C.A. C.A. Proof Proof External Off // Off
P2, P3 = Boiler Pump
Description
P4 =
Literature Control
Packaged weight
DIP DIP Settings: Settings: 2-15/16" (74 mm)
11-1/8" (282 mm)
Specications
8-1/16” H x 11-1/8” W x 2-15/16” D (204 x 282 x 74 mm) Grey PC+ABS plastic with metal top and bottom conduit connection walls, NEMA type 1
Approvals
CSA C US, meets class B: ICES & FCC Part 15, BTL Listed
Ambient conditions
Indoor use only, 32 to 122°F (0 to 50°C), < 90% RH non-condensing
Power supply
115 V (ac) ±10%, 60 Hz, 18 VA
Primary pump relays
230 V (ac) 10 A, 1/2 hp
Boiler & IDHW pump relays
230 V (ac) 5 A, 1/3 hp
S1
Auxiliary & Alert Relays
230 V (ac) 5 A, 1/6 hp
Boiler Stage Relays
230 V (ac) 5 A
Modulating outputs
4 x 0-10 V (dc) 500 Ω minimum load impedance / 4-20 mA 1 kΩ max load impedance
Calls
S4 24 V (ac) or Short
Sensors
NTC thermistor, 10 kΩ @ 77°F (25°C ±0.2°C) ß=3892
–Included –Optional
Table
External Flow Proof IDHW Pump / Off 7738003457, ESS 7738003458 I/O Manual 7738003455, App Manual 7738003456, Building Integration External C.A. Proof Microprocessor control. This is not a safety (limit) control (part# 7738003450) / Off S1 5.5 lb. (2490 g) S1 Value
Enclosure
P4 P4
S4
Outdoor Sensor (part #7738003452) and 5 Universal Sensors (part #7738003451) Universal Sensor S4 (part# 7738003451) Limited 3 Year
S2 S2 P4 Bosch Thermotechnology Corp.
S5 S5 SB Series SB Series
M AN UAL O VER R ID E
4 boilercontrol,D H W ,BAC netand M odbus
51 52 53 54 55 56 57 58
Boiler2 Boiler3 Boiler4 Boiler1 + Mod- Stage 1 Stage 2 + Mod- Stage 1 Stage 2 + Mod- Stage 1 Stage 2 + Mod- Stage 1 Stage 2
Boiler Boiler Pump Pump IDHW IDHW Pump Pump
Warranty
S6
B A Gnd (+) (–) RS485 40 41 42
tekm arN etC om m unication
CL
Dimensions
S8 S8
tN4 C0 tN4 C1 tN4 C2 tN4 C3 Bus b Bus 1 Bus 2 Bus 3 Boiler Boiler Boiler Boiler 32 33 34 35 36 37 38 39
H eatronic 4000
7/16" (11 mm)
S5 Boiler S5 = = Boiler Inlet Inlet Sensor Sensor S6, S7 = Boiler Outlet S6, S7 = Boiler Outlet Sensors Sensors Fig. 1
BACnetIP
H om e
7/16" (11 mm)
LEGEND: LEGEND:
LEGEND:
CH Call
5
Prim Pump Flow Proof/O Comb AirProof/O O /xer Ecise Setback /O
our website at www.BoschHeatingAndCooling.com.
S3 S3 = = Primary Primary Return Return Sensor Sensor S4 DHW Sensor S1 = Outdoor Sensor S4 = DHW Sensor
4
8-1/16" (204 mm)
modulating condensing boilers with primary/secondary
S1 S1 = = Outdoor Outdoor Sensor Sensor S2 = S2 = Primary Primary Supply Supply Sensor Sensor
3
tektra 1056-02
Application 3 Piping: Application Piping: application schematic please visit piping For3additional Application 3 Piping:
2
Meets Class B:Canadian ICES & FCC Part15
S2 S3 S3
P1 P1
Data subject to chan
P1
P3 P3
S5all design, installation, code, or safety considerations. The diagrams in this manual are for reference use by code officials, designers and DISCLAIMER: Application drawings in this manual are conceptual only and do not purport to address DISCLAIMER: Application drawings in this manual are conceptual only and do not purport to address all design, installation, code, or safety considerations. The diagrams in this manual are for reference use by code officials, designers and S3accepted licensed installers. It is expected that installers have adequate knowledge of national and local codes, as well as industry practices, and are trained on equipment, procedures, and applications involved. Drawings are not to scale. licensed installers. It is expected that installers have adequate knowledge of national and local codes, as well as accepted industry practices, and are trained on equipment, procedures, and applications involved. Drawings are not to scale. Refer to the boiler, control and module installer manuals for additional detailed information! Refer to the boiler, control and module installer manuals for additional detailed information! SB Series
P2
SB Series
P3
DISCLAIMER: Application drawings in this manual are conceptual only and do not purport to address all design, installation, code, or safety considerations. The diagrams in this manual are for reference use by code officials, designers and licensed installers. It is expected that installers have adequate knowledge of national and local codes, as well as accepted industry practices, and are trained on equipment, procedures, and applications involved. Drawings are not to scale. Refer to the boiler, control and module installer manuals for additional detailed information!
Bosch Thermotechnology Corp.
Data subject to Watertown, MA | Londonderry, Data subject to change change NH | Ft. Lauderdale, FL