SHC Adsorption Chiller
www.md-zenit.si +386 31 608 388
www.md-zenit.si +386 31 608 388
Adsorption Chiller Thermics SHC 18
Integrated hydraulic unit
Compact solution for efficient cooling at high outside temperatures
The adsorption chiller Thermics SHC 18 with an integrated hydraulic unit is especially easy to install. It can be used efficiently with dry recoolers at outside temperatures of up to 40°C. All SHC machines reach their optimal capacity at driving temperatures from 85°C. For operation at lower driving temperatures, the Thermics SHC 10 plus is available. 18 kW cooling capacity – compact design The nominal capacity of the SHC 18 is 18 kW. For an easy installation, all hydraulic connections are conveniently accessible on the top side of the machine. The unit is optimized for transport by pallet jack. The compact design allows for space saving set-up. Easy operation and setting – prepared for heat pump operation The setting of the target water temperatures in the cold water circuit, the driving circuit return flow and the recooling circuit is easily adjustable on the multi-color, multi-lingual touch display at the front of the machine. The heat pump mode is already installed and can be activated easily. SHC 18: Hydraulic unit integrated The SHC 18 is integrated with all basic components for thermal cooling. It includes a complete hydraulic unit with three electronically regulated high-efficiency pumps, so that all necessary water circuit tubes for heat supply, cold distribution and recooling can be connected directly to the SHC 18 plus.
Dimensions of the machine Length . . . . . . . . . . . . . . . . . . . . . . . . . . 1.100 mm Height . . . . . . . . . . . . . . . . . . . . . . . . . . 1.370 mm Width . . . . . . . . . . . . . . . . . . . . . . . . . . . . 750 mm Weight SHC 18 . . . . . . . . . . . . . . . . . . 420 kg Weight SHC 18-FC . . . . . . . . . . . . . . . 425 kg Position of the connectors from the ground . . . . . . . . . . . . . . . . 1.400 mm
SHC 18-FC: Hydraulic unit & free cooling function integrated The free cooling function allows for even more energy savings: If the outside air temperature is cold enough, it can be used directly for climatization and no driving heat is necessary to operate the chiller.
Nominal widths Drive (2x) . . . . . . . . . . . . . . . . . . . . . . . . . . . G 1 1⁄ 4 ” Cooling (2x) . . . . . . . . . . . . . . . . . . . . . . . . G 1 1⁄ 2” Recooling (2x) . . . . . . . . . . . . . . . . . . . . . . G 1 1⁄ 2”
General technical specifications Output range – cooling
kW
COP maximum
0,55
Max. overpressure
bar
4
Electrical connection
V~, Hz
230, 50/60
Approx. electrical power consumption
W
495
Specifications at nominal conditions
Cooling circuit
COP
0,52
Recooling circuit
Drive circuit
Performance values
kW
18
52,6
34,6
Temperatures – cooling system inlet (IN)
°C
18
27
85
Temperatures – cooling system outlet (OUT)
°C
14
34,5
76,5
Temperatures – possible application
°C
9–25
20–47
75–100
Volume flows
l/h
3.900
6.000
3.600
Available ext. pressure head
mbar
400
400
300
All specifications apply for operation with water in hydraulic circuits.
2
6–22
www.md-zenit.si +386 31 608 388
Adsorption Chiller Technical specification at different conditions Capacity and COP at different temperatures of recooling and driving energy Thermics Chiller SHC 18 – COP
Thermics Chiller SHC 18 – Cooling Capacity Recooling Temperatures[°C] (inlet temperature into the chiller(IN)) 42°C
37°C
32°C
27 °C
Cold Water Inlet (IN) Outlet at nom. point (OUT)
18°C 14 °C
Cold Water Inlet (IN) Outlet at nom. point (OUT)
Recooling Temperatures[°C] (inlet temp. into the chiller(IN))
47 °C
32 °C
27 °C
37 °C
42 °C
18°C 14 °C
47 °C
0,6
25
Nominal point Nominal point
20 0,5
15
0,3
5
COP
Cooling capacity [kW]
0,4
10
0 65
70
75
80
85
90
0,2 65
95
Driving temperatures [°C] (inlet temperature into the chiller (IN))
70
75
80
85
90
95
Driving temperatures [°C] (inlet temp. into the chiller (IN))
Capacity and COP at different temperatures of driving energy and recooling Thermics Chiller SHC 18 – Cooling Capacity
70 °C
75 °C
80 °C
85 °C
Thermics Chiller SHC 18 – COP Cold Water Inlet (IN) Outlet at nom. point (OUT)
DrivingTemperatures[°C] (inlet temp. into the chiller(IN)) 90 °C
18°C 14 °C
Cold Water Inlet (IN) Outlet at nom. point (OUT)
DrivingTemperatures[°C] (inlet temp. into the chiller(IN))
95 °C
70 °C
25
75 °C
80 °C
85 °C
90 °C
18°C 14 °C
95 °C
0,6 Nominal point
20 0,5
Nominal point
15
0,3
0 27
32
37
0,2
42
27
Recooling temperatures [°C] (inlet temp. into the chiller (IN))
32
37
42
Recooling temperatures [°C] (inlet temp. into the chiller (IN))
Capacity and COP at different temperatures of driving energy and chilled water Thermics Chiller SHC 18 – COP
Thermics Chiller SHC 18 – Cooling Capacity Cold Water Inlet (IN) 27°C Outlet at nom. point (OUT) 34,5 °C
DrivingTemperatures[°C] (inlet temp. into the chiller(IN)) 70 °C
65 °C
75 °C
80 °C
85 °C
90 °C
Cold Water Inlet (IN) 27°C Outlet at nom. point (OUT) 34,5 °C
DrivingTemperatures[°C] (inlet temp. into the chiller(IN))
95 °C
70 °C
65 °C
75 °C
80 °C
85 °C
90 °C
95 °C
0,6
25
20
Nominal point 0,5 Nominal point
15
0,3
5
COP
Cooling Capacity [kW]
0,4
10
0
0,2 18–14 °C
15–10 °C
Chilled Water Temperatures [°C] (inlet temp. – outlet temp.)
12–9 °C
18–14 °C
15–10 °C
Chilled Water Temperatures [°C] (inlet temp. – outlet temp.)
12–9 °C
SHC18.01.en Technical modifications and errors reserved (Status: 02/2012)
5
COP
Cooling Capacity [kW]
0,4
10
3
www.md-zenit.si +386 31 608 388
Adsorption Chiller Thermics SHC 10
Integrated hydraulic unit
with integrated hydraulic unit The Thermics SHC 10 is an adsorption chiller with especially low driving temperatures and few requirements for installation and service. All LTC machines reach almost 100% of their nominal capacity at driving temperatures as low as 65°C. They are suitable for outside temperatures of up to approx. 35°C. For operation at higher temperatures, Thermics offers the Thermics SHC series. 10 kW cooling capacity – compact design The nominal capacity of the SHC 10 is 10 kW. The compact design allows for space saving set-up. For an easy installation, all hydraulic connections are conveniently accessible on the top side of the machine. The unit is optimized for transport by pallet jack. Easy operation and setting – prepared for heat pump operation The setting of the target water temperatures in the cold water circuit, the driving circuit return flow and the recooling circuit is easily adjustable on the multi-color, multi-lingual touch display at the front of the machine. The heat pump mode is already installed and can be activated easily. SHC 10: Thermics chilling station integrated The SHC 10 is integrated with all basic components for thermal cooling. pumps, so that all necessary water circuit tubes for heat supply, cold distribution and recooling can be connected directly to the SHC 10. SHC 10-FC: Thermics chilling station & free cooling function integrated The free cooling function allows for even more energy savings: If the outside air temperature is cold enough, it can be used directly for climatization and no driving heat is necessary to operate the chiller.
Chilling capacity
kW
COP maximum
Position of the connectors from the ground . . . . . . . . . . . . . . . .
1,400 mm
Nominal widths Drive (2x) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . G 1” Cooling (2x) . . . . . . . . . . . . . . . . . . . . . . . G 1 1⁄4” Re-cooling (2x) . . . . . . . . . . . . . . . . . . . . . G 1 1⁄2”
4–12 0.65
Max. overpressure
bar
4
Electrical connection
V~, Hz
230, 50 / 60
Electrical power consumption (incl. pumps)
W
395 Cooling circuit
COP
4
Dimensions of the machine Length . . . . . . . . . . . . . . . . . . . . . . . . . . 1,100 mm Height . . . . . . . . . . . . . . . . . . . . . . . . . . 1,370 mm Width . . . . . . . . . . . . . . . . . . . . . . . . . . . . 750 mm Weight SHC 10 . . . . . . . . . . . . . . . . . . 390 kg Weight SHC 10-FC . . . . . . . . . . . . . . . 395 kg
Recooling circuit
Drive circuit
0.6
Capacity
kW
10
26.7
16.7
Temperature – chiller inlet (IN)
°C
18
27
72
Temperature – chiller outlet (OUT)
°C
15
31.5
66
Temperatures – range
°C
10–25
20–37
45–100
Volume flows
l/h
2,900
5,100
2,500
Available ext. pressure head
mbar
400
400
300
www.md-zenit.si +386 31 608 388
Adsorption Chiller Technical specification at different conditions Capacity and COP at different temperatures of recooling and driving energy
InvenSor Chiller HTC 10
– Cooling Capacity
InvenSor Chiller HTC 10
Cold Water Inlet: 18°C Outlet at nom. point: 15°C
Recooling Temperatures [°C] (inlet temp. into the chiller)
Cold Water Inlet: 18°C Outlet at nom. point: 15°C
Recooling Temperatures [°C] (inlet temp. into the chiller)
37 °C
32 °C
27 °C
22 °C
– COP
37 °C
32 °C
27 °C
22 °C
12
0.7
Nominal point
10 Nominal point
0.6
8
0.5
4 0.4 2
COP
Cooling Capacity [kW]
6
0
45
50
55
Driving Temperatures [°C]
60
65
70
75
0.3
45
50
55
Driving Temperatures [°C]
(inlet temp. into the chiller)
60
65
70
75
(inlet temp. into the chiller)
Capacity and COP at different temperatures of driving energy and recooling InvenSor Chiller HTC 10
– Cooling Capacity
InvenSor Chiller HTC 10
Cold Water Inlet: 18°C Outlet at nom. point: 15°C
Driving Temperatures [°C] (inlet temp. into the chiller) 60 °C
55 °C
65 °C
70 °C
– COP
Cold Water Inlet: 18°C Outlet at nom. point: 15°C
Driving Temperatures [°C] (inlet temp. into the chiller) 75 °C
60 °C
55 °C
65 °C
70 °C
75 °C
0.7
12 Nominal point 10
Nominal point 0.6
8
0.5
4 0.4 2
COP
Cooling Capacity [kW]
6
0
22
27
Recooling Temperatures [°C]
32
37
0.3
22
27
Recooling Temperatures [°C]
(inlet temp. into the chiller)
32
37
(inlet temp. into the chiller)
Capacity and COP at different temperatures of driving energy and chilled water InvenSor Chiller HTC 10
– Cooling Capacity
InvenSor Chiller HTC 10
Recool Water Inlet: 27 °C Outlet at nom. point: 32 °C
Driving Temperatures [°C] (inlet temp. into the chiller) 60 °C
55 °C
65 °C
70 °C
– COP
Recool Water Inlet: 27 °C Outlet at nom. point: 32 °C
Driving Temperatures [°C] (inlet temp. into the chiller) 75 °C
60 °C
55 °C
12
65 °C
70 °C
75 °C
0.7 Nominal point
10 0.6 Nominal point
8
0.5
4 0.4
0
18–15 °C
Chilled Water Temperatures [°C]
18–13 °C (inlet temp. – outlet temp.)
15–10 °C
0.3
18–15 °C
Chilled Water Temperatures [°C]
18–13 °C (inlet temp. – outlet temp.)
15–10 °C
HTC 10
2
COP
Cooling Capacity [kW]
6
5
www.md-zenit.si +386 31 608 388
Recooling unit Thermics C5) 32 Recooling unit type Thermics CTH32, optimized for use with Thermics chillers. Ready for connection, silent and energy efficient EC-fans (31 dB(A) in 10 m). Fanspeed and optional peak load spray unit (Art. 30 60 30) are directly controlled by Thermics chiller, reduce electric power consumption of the fans as well as the water consumption for peak load spraying to its minimum.
picture similar
Recooling unit Thermics CTH 32 technical data for use with
Thermics CTH 10
recooling power
27,0 kW water (R718)2
medium flow rate
5,1 m³/h
pressure loss
180 mbar
Fans
2 pieces× 1~230 V; 50 H
nominal data per fan 715 min -1
max. speed speed control voltage max. electric power consumption per fan (full speed) -1
noise level in 10 m distance
0 – 10V
max. current
0,27 kW
total electric power consumption (full speed)
31 dB(A)3 1,17 A 0,54 kW
power consumption per fan at 572 min (80%)
0,13 kW total electric power consumption (80% speed)
0,27 kW
power consumption per fan362 min-1 (50%)
0,03 kW
0,07 kW
total electric power consumption (50% speed)
Case zinc plated steel , RAL 7035 heat exchanger pipes pipe volume
copper heat exchanger fins empty weight
209 kg
hydraulic connections inlet/outlet
Cu 35×1,5 mm max. pressure
16,0 bar
hydraulic connections peak load spray unit
Cu 22×1,0 mm max pressure peak load spray unit
approximate water consumption
36 l
epoxy coated aluminum
3 bar
< 4 m³/ year
Dimensions L
2250 mm H
950 mm
L1
2175 mm H1
400 mm
B
1145 mm H2
295 mm
R
110 mm S
50 mm
2
Fluidgroup 2 in regard to pressure equipment directive 97/23/EG and directive 67/548/EWG Fluidgroup 2 in regard to pressure equipment directive 97/23/EG and directive 67/548/EWG in regard to employing and enveloping measurement surface method EN 13487
6
Solar thermal field 2 x 8 Thermics 10 RTH-CPC collectors Aperture area 31,36 sqm Campo solare termico 2 x 8 collettori Thermics 10 RTH-CPC Area di apertura totale 31,36 mq
Drinkable hot water producer Stazione produzione acqua sanitaria
pre-heated water acqua sanitaria preriscaldata
Pre-heating DHW tank Preriscaldo acqua sanitaria
Solar station with layered temperature charging sistem Stazione solare con funzione di stratificazione termica
grid water acqua di rete
Hot water puffer tank - 1000 l Accumulo acqua calda - 1000 l
Adsorption heat-pump 10 kW Pompa di calore ad adsorbimento 10 kW 8TAC00010 Swimming pool Piscina
Auxiliary boiler Caldaia di riserva
Heat recovery pre-heating Yearly hot water Acqua calda tutto l'anno Recupero calore su preriscaldo
www.md-zenit.si +386 31 608 388
Bore-hole dissipation / heat storage Dissipazione estiva su sonde geotermiche
Summer cooling up to COP 15 Raffrescamento estivo con COP 15
Air Dry-cooler Dissipatore ad aria
Winter gas-heating up to 150% efficiency Riscaldamento invernale con efficienza del 150%
7