Appendix c

Page 1

APPENDIX C – EFFECTIVE ASSEMBLY R-VALUES


C1.

Clear Field Thermal Performance Table C.1: Clear Field Effective Assembly R-Values with Uninsulated Steel Stud Wall Assembly Effective R-Value Clip System

hr·ft2·oF/BTU (m2K/W)

Nominal Insulation hr·ft2·oF/BTU (m2K/W) 24” Vertical Clip Spacing

36” Vertical Clip Spacing

48” Vertical Clip Spacing

T100

R-16.8 (3.0)

R-16.4 (2.88)

R-17.4 (3.06)

R-17.9 (3.16)

T125

R-21.0 (3.7)

R-19.2 (3.38)

R-20.6 (3.63)

R-21.4 (3.77)

T150

R-25.2 (4.4)

R-21.7 (3.82)

R-23.5 (4.15)

R-24.6 (4.33)

Table C.2: Clear Field Effective Assembly R-Values with Steel Stud Wall with R-12 Batt Assembly Effective R-Value Clip System

hr·ft2·oF/BTU (m2K/W)

Nominal Insulation hr·ft2·oF/BTU (m2K/W) 24” Vertical Clip Spacing

36” Vertical Clip Spacing

48” Vertical Clip Spacing

T100

R-12 batt + R-16.8 (2.11 batt + 3.0)

R-22.2 (3.92)

R-23.2 (4.09)

R-24.1 (4.24)

T125

R-12 batt + R-21.0 (2.11 batt + 3.7)

R-25.0 (4.40)

R-26.6 (4.68)

R-27.5 (4.84)

T150

R-12 batt + R-25.2 (2.11 batt + 4.4)

R-27.2 (4.80)

R-29.4 (5.19)

R-30.6 (5.39)


Table C.3: Clear Field Effective Assembly R-Values with Concrete Wall Assembly Effective R-Value Clip System

hr·ft2·oF/BTU (m2K/W)

Nominal Insulation hr·ft2·oF/BTU (m2K/W)

24” Vertical Clip Spacing

36” Vertical Clip Spacing

48” Vertical Clip Spacing

T100

R-16.8 (3.0)

R-16.2 (2.85)

R-17.0 (2.99)

R-17.4 (3.07)

T125

R-21.0 (3.7)

R-19.2 (3.38)

R-20.3 (3.58)

R-21.0 (3.70)

T150

R-25.2 (4.4)

R-21.2 (3.82)

R-22.9 (4.02)

R-23.7 (4.17)

Table C.4: Clear Field Effective Assembly R-Values with Concrete Block Wall Assembly Effective R-Value Clip System

Nominal Insulation

hr·ft2·oF/BTU (m2K/W)

hr·ft2·oF/BTU (m2K/W) 24” Vertical Clip Spacing

36” Vertical Clip Spacing

48” Vertical Clip Spacing

T100

R-16.8 (3.0)

R-16.4 (2.89)

R-17.3 (3.05)

R-17.8 (3.13)

T125

R-21.0 (3.7)

R-19.5 (3.44)

R-21.4 (3.77)

R-21.4 (3.77)

T150

R-25.2 (4.4)

R-21.6 (3.80)

R-23.3 (4.10)

R-24.0 (4.23)


C2.

Slab Edge Thermal Performance

Table C.5: Effective Assembly R-Values including the effects of an insulated slab edge for 9 foot floor to ceiling height with uninsulated Steel Stud wall

Clip System

Nominal Insulation

Assembly Effective R-Value with Slab Edge hr·ft2·oF/BTU (m2K/W)

hr·ft2·oF/BTU (m2K/W)

24” Vertical Spacing

36” Vertical Spacing

48” Vertical Spacing

T100

16.8 (2.96)

15.3 (2.69)

16.5 (2.91)

17.2 (3.03)

T125

21.0 (3.70)

17.7 (3.12)

19.4(3.42)

20.4 (3.59)

T150

25.2 (4.44)

19.8 (3.49)

22.0 (3.87)

23.3 (4.10)

Ψ Slab Edge Linear Transmittance BTU/hr·ft·oF (W/mK)

0.029 (0.050)