fire ventilation systems
FIRE DAMPERS FANS CONTROL SYSTEMS OVERPRESSURE SYSTEMS
fire protection appliances examples of application
mcr WIP
mcr PL 1
mcr PL 1
mcr CJHCH
mcr FS
mcr DOR
mcr THT
mcr OMEGA
mcr FID S
mcr ZIPP
mcr FID PRO
Gelco Nordic ApS Hylkedamvej 70 : DK-5591 Gelsted Tel.: 45 63 46 54 08 : Fax: +45 6346 5404 w w w.gelco -nordic.dk Side 2 af 8
fire dampers and smoke control dampers
mcr FID PRO single-flap cut-off fire damper and fire ventilation damper
mcr FID S single-flap cut-off fire damper and fire ventilation damper
Fire resistance EIS 120, EIS 120 AA – depending on system of manufacturing and method and place of installation.
Fire resistance EIS 90, EIS 90 AA, EIS 120, EIS 120 AA – depending on system of manufacturing, method and place of installation.
Versions S – cut-off fire damper V – for fire ventilation systems (smoke exhaust) M – for double-function ducts (mixed systems)
Versions S – cut-off fire damper V – for fire ventilation systems (smoke exhaust) M – for double-function ducts (mixed systems)
Range of application The damper has been designed for separating fire-hazardous zones from safe parts of the building (S version) and assuring appropriate evacuation conditions through fire gas ventilation (V version) – inlet and outlet damper. Damper can be also used in so-called mixed systems (M version).
Range of application The damper has been designed for separating fire-hazardous zones from safe parts of the building (S version) and assuring appropriate evacuation conditions through fire gas ventilation (V version) – inlet and outlet damper. Damper can be also used in so-called mixed systems (M version).
Control – release RST mechanism – activated by a return spring with fusible link rated at 72°C, manual reset by means of a lever.
Control – release RST mechanism – activated by a return spring with fusible link rated at 72°C, manual reset by means of a lever.
Electric servo-motor – activated by a thermal link rated at 72°C or remotely by lack of supplying power (power break), remote reset by suppling power (pulse Uz= 24V AC/DC or 230V AC).
Electric servo-motor – activated by a thermal link rated at 72°C or remotely by lack of supplying power (power break), remote reset by suppling power (pulse Uz= 24V AC/DC or 230V AC).
Electric servo-motor – activated remotely by supplying power (pulse), remote reset by resupply of power (Uz= 24V AC/DC or 230V AC).
Electric servo-motor – activated remotely by supplying power (pulse), remote reset by resupply of power (Uz= 24V AC/DC or 230V AC)
KW1 mechanism – activated by a return spring with fusible link rated at 72°C or remotely by an electromagnet (pulse and power break), reset by means of a lever or additional servo-motor (Uz= 24V DC or 230V AC).
KW1 mechanism – activated by a return spring with fusible link rated at 72°C or remotely by an electromagnet (pulse and power break), reset by means of a lever or additional servo-motor (Uz= 24V DC or 230V AC).
Dimensions (to the exactness of 1 mm): – circular damper: diameter 100-315 mm, – male, female or type of execution with flange.
Dimensions (to the exactness of 1 mm): – rectangular damper without insulating separator: width 200 – 1200 mm; height 200 – 1200 mm; casing length 296 mm, – circular damper without insulating separator: diameter 200-1000 mm; casing length 296 mm, – rectangular damper with insulating separator: width 200 – 1500 mm; height 200 – 1500 mm; casing length 296 mm, – circular damper with insulating separator: diameter 125-1000 mm; casing length 296 mm.
Gelco Nordic ApS Hylkedamvej 70 : DK-5591 Gelsted Tel.: 45 63 46 54 08 : Fax: +45 6346 5404 w w w.gelco -nordic.dk Side 3 af 8
fire dampers and smoke control dampers
mcr WIP mcr DOR louver type cut-off, fire ventilation door-type smoke exhaust and and transfer fire damper
air-inlet damper
mcr FS curtain type transfer fire damper
Fire resistance EIS 60, EIS 60 AA, E 120, ES 120 – depending on system of manufacturing and method and place of installation.
Fire resistance EIS 120 AA
Fire resistance E 120
Versions S – cut-off fire damper, V – for fire ventilation systems (smoke exhaust), M – damper for mixed systems, T – transfer damper.
Versions V – for fire ventilation systems (smoke exhaust)
Versions 101 – curtain partially in air stream, 201 – curtain outside of air stream, 301 – curtain outside of air stream (round damper).
Range of application The flap has been designed for separating fire-hazardous zones from safe parts of the building (S version) and ensuring proper conditions of evacuation through fire ventilation system (V version)- inlet and outlet damper. It can be also used in so-called mixed systems (M version), as a transfer damper (T version) as well as at the end of ventilation ducts.
Range of application The flap has been designed for use in fire ventilation ducts and outlet damper (smoke removal) and as inlet damper for evacuation needs (intake of fresh air).
Range of application The damper has been designed for mounting in partitions as a transfer damper for transmission of air between rooms.
Control – release RST mechanism – activated by a return spring with fusible link rated at e.g. 72°C, manual reset by means of a lever.
Control – release EM 24 D mechanism – remotely activated by an electromagnet (pulse supply Uz= 24V AC/DC), manual reset. By implementing a intermediary module MP 230/24 damper can be released by 230 AC/DC voltage.
Control – release Spring mechanism – activated by a return spring with fusible link rated at e.g. 72°C, manual reset.
Electric servo-motor – activated by a thermal link rated at e.g. 72°C or remotely by lack of supplying power (power break), remote reset by resupply of power.
D1 – single-flap damper D2 – double-flap damper
Electromagnetic release – activated by a thermo element (e.g. 72°C) or remotely, by lack of supplying power (power break Uz= 24V AC/DC or 230V AC), manual reset.
KW1 mechanism – activated by a return spring with fusible link rated at e.g. 72°C or remotely by an electromagnet (pulse and power break), reset by means of a lever or additional servomotor.
Gelco Nordic ApS Hylkedamvej 70 : DK-5591 Gelsted Tel.: 45 63 46 54 08 : Fax: +45 6346 5404 w w w.gelco -nordic.dk Side 4 af 8
fire protection appliances
mcr THT duct mounted axial smoke
exhaust fan CE according to EN 12101-3
mcr CJTHT mcr ZIPP axial smoke exhaust fan with casing cut-off fire valve insulated acoustically CE according to EN 12101-3
Fire resistance F400 – 400°C during 120 min
Fire resistance F400 – 400°C during 120 min
Fire resistance EIS 120
Versions Long (LC) and short (CC) casing. Single or double speed motors.
Versions Long casing (LC). Single or double speed motors.
Versions – vertically mounted, – horizontally mounted.
Range of application The fan has been designed for removing smoke and heat from rooms during fire and for comfort ventilation. It facilitates evacuation of people and protects against fire spreading to adjacent fire zones.
Range of application The fan has been designed for removing smoke and heat from rooms during fire and for comfort ventilation. It facilitates evacuation of people and protects against fire spreading to adjacent fire zones.
Range of application The valve has been designed for assembly at the end of ventilation ducts and is used for separating fire-hazardous zones from safe parts of the building as well as for transferring air through building partitions.
Technical data Available in 10 sizes: from dia. 400 mm to dia. 1 250 mm. Standard capacity up to 120 000 m3/h. Compression up to 1 250 Pa.
Technical data Available in 10 sizes: from dia. 400 mm to dia. 1 250 mm. Standard capacity up to 120 000 m3/h. Compression up to 1 250 Pa.
Technical data Available in 4 sizes: dia 100 mm, 125 mm, 160 mm, 200 mm.
Accessories PS mounting feet, ACE flexible connections, BTUB counter-flanges, RI or RT protecting nets, spring shock absorbers.
Accessories PS mounting feet, ACE flexible connections, BTUB counter-flanges, RI or RT protecting nets, spring shock absorbers.
Control – release RST mechanism – activated by a return spring with fusible link rated at e.g. 72°C, manual reset. EMz mechanism – activated by a return spring with fusible link rated at e.g. 72°C or remotely by an electromagnet (pulse and power break Uz= 24V DC or 230V AC), manual reset.
Gelco Nordic ApS Hylkedamvej 70 : DK-5591 Gelsted Tel.: 45 63 46 54 08 : Fax: +45 6346 5404 w w w.gelco -nordic.dk Side 5 af 8
overpressure systems systems for vertical evacuation overpressure evacuation paths paths
mcr PL1 PL1 mcr overpressure-bleed damper overpressure-bleed damper
mcr CJHCH mcr CJHCH axial air-inlet and air-extract fan axial air-inlet and air-extract fan
with casing insulated acoustically with casing insulated acoustically
mcr OMEGA mcr OMEGA central supply-control unit for
central supply-control unit for fire ventilation and overpressure fire ventilation and overpressure systems systems
Fire resistance Conforms with EN-12101-6 standard. Fire resistance Conforms with EN-12101-6 standard.
Fire resistance Not required. Fire resistance Not required.
Cooperates with other control units and alarm systems. Specialised, modular design Cooperates with other control units enables and alarm itsystems. to perform unlimitedmodular fire scenarios within Specialised, design enables the controlled supplied it to perform and unlimited firesystem. scenarios within the controlled and supplied system.
Versions S – wall-mounted, Versions duct-mounted, S K– – wall-mounted, roof-mounted. KD– – duct-mounted, D – roof-mounted.
Versions Long casing (LC). Versions Singlecasing or double Long (LC).speed motors. Single or double speed motors.
Versions mcr Omega 2300 – fire ventilation systems. Versions mcr evacuation paths mcrOmega Omega2100 2300– –vertical fire ventilation systems. mcr Omega 2100 –systems. vertical evacuation paths
Range of application The overpressure bleed damper has been Range of application designed for maintaining pressure differences The overpressure bleed damper has been before and behind its partition and is designed for maintaining pressure differences implemented as a pressure relieve damper in before and behind its partition and is overpressure systems of stairways. implemented as a pressure relieve damper in It can also be used in any room protected overpressure systems of stairways. against smoke by establishing overpressure. It can also be used in any room protected against smoke by establishing overpressure.
Range of application The fan has been designed for air intake in Range of application overpressure systems of vertical evacuation The fan has been designed for air intake in paths (stairways), it can be implemented in overpressure systems of vertical evacuation systems designed for comfort ventilation as paths (stairways), it can be implemented in well. systems designed for comfort ventilation as well.
Range of application mcr Omega 2300 – controls and supplies Range of application appliances operating in such fire ventilation mcr Omega 2300 – controls and supplies systems as: cut-off fire dampers, fire appliances operating in such fire ventilation ventilation dampers or transfer dampers. systems as: cut-off fire dampers, fire Central control unit also controls operation ventilation dampers or transfer dampers. of smoke exhaust fans and other system Central control unit also controls operation appliances. of smoke exhaust fans and other system mcr Omega 2100 – controls and supplies appliances. overpressure systems for vertical evacuation mcr Omega 2100 – controls supplies paths including air intake fans,and airflow overpressure systems for vertical regulating dampers, actuators andevacuation paths including air intake overpressure damper sets. fans, airflow regulating dampers, actuators and overpressure damper sets.
Technical data Dampers mcr PL1.../S and mcr PL1.../K – Technical standard data dimensions: 450x450 mm, Dampers andmm, mcr800x800 PL1.../K –mm. 550x550mcr mm,PL1.../S 650x650 standard dimensions: 450x450 mm, There is a possibility to combine dampers in 550x550 650x650 mm, 800x800 mm. multiplemm, assemblies. There is a possibility to –combine dampers in Dampers mcr PL1.../D dimensions: multiple 600x600assemblies. mm, 800x800 mm, 1000x1000 mm, Dampers mcrmm. PL1.../D – dimensions: 1300x1300 600x600 800x800 mm, 1000x1000 mm, Standardmm, pressure threshold for activation: 1300x1300 mm. 50 Pa. Standard pressure threshold for activation: 50 Pa.
Technical data Available in 10 sizes: from dia. 400 mm to dia. Technical 1 250 mm.data Available 10 sizes: dia. 400 Standard in capacity up from to 120 000 m3mm /h. to dia. 1Compression 250 mm. up to 1 250 Pa. Standard capacity up to 120 000 m3/h. Compression up to 1 250 Pa.
Benefits arising from implementing central control units mcr OMEGA: –Benefits safety arising from implementing central units mcr OMEGA: –control reliability safety –– simplicity reliability –– flexibility simplicity –– comprehensiveness flexibility –– cost optimization – comprehensiveness – cost optimization
Accessories Wall mounted air intakes, protective grilles, cut-off air dampers, assembly elements. Accessories Wall mounted air intakes, protective grilles, cut-off air dampers, assembly elements.
Accessories PS mounting feet, ACE flexible connections, BTUB counter-flanges, RI or RT protecting Accessories nets, absorbers. PS mounting feet, ACE flexible connections, BTUB counter-flanges, RI or RT protecting nets, absorbers.
Accessories Smoke detection modules, smoke evacuation buttons, optical smoke sensors. Accessories Smoke detection modules, smoke evacuation buttons, optical smoke sensors.
systems.
Gelco Nordic ApS Hylkedamvej 70 : DK-5591 Gelsted Tel.: 45 63 46 54 08 : Fax: +45 6346 5404 w w w.gelco -nordic.dk Side 6 af 8
Went folder ENG 2009.indd 6
2009-06-04 14:59:38
table of initial choice of appliances table of initial choice of appliances
type of appliance mcr FID PRO
application application
cut-off fire dampers for ventilation and air mcr FIDXPRO conditioning ducts
fire resistance fire resistance
mcr WIP mcr DOR type of appliance
mcr FS
mcr ZIPP
X S mcr FID
mcr X WIP
mcr –DOR
mcr– FS
mcrXZIPP
cut-off firecontrol dampers for ventilation and air smoke dampers for fire ventilation conditioning ducts
XX
XX
XX
––
––
–X
transfer dampers smoke control dampers for fire ventilation
X–
X–
XX
–X
X –
X–
EIS 60dampers / EIS 60 AA transfer
–X/X
X/X –
X/X X
–/X X
– X
X/– X
EIS 90 EIS 60 / EIS 60 AA
minimal wall thickness with dimensions place of installation built-in damper minimal wall thickness with dimensions place of installation built-in damper
mcr FID S
X X/X
X X/X
– X/X
– –/X
– –
X X/–
X
X X
X –
X –
X –
X X
X
X X
X X
– X
– X
X X
X
X X
– X
– –
– –
X X
X
X X
– –
X –
– –
– X
X
X X
X –
– X
– –
X –
X
X X
X X
X –
X –
X X
X
X X
X X
X X
X X
X X
X
X X
X X
X X
X X
X X
–
– X
X X
X X
X X
X X
110 mm –
110 mm –
110 mm X
110 mm X
110 mm X
110 mm X
E 120 EIS 90
X
ES 120 E 120
X
EIS 120 ES 120
X
EIS 120 AA EIS 120
X
ventilation and air conditioning ducts in transitions through fire protection EIS 120 AA partitions
X
ventilation andpath air conditioning ducts evacuation in transitions through fire protection partitions vestibule evacuation path
X
garage vestibule
X
as a duct end garage
X
concrete as a duct end brickwork
concrete made of cellular concrete blocks
brickwork made of gypsum-cardboard panels on a steel grid made of cellular concrete blocks made of fireproof boards made of gypsum-cardboard panels on a steel grid width from – to [mm]
X
120 mm
110 mm 115 mm
120 mm 125 mm
115 mm –
125 mm
120 mm
110 mm 115 mm
120 mm 125 mm
115 mm –
125 mm
120 mm
120 mm
120 mm
120 mm
110 mm
110 mm
110 mm
110 mm
115 mm
115 mm
115 mm
115 mm
120 mm
120 mm
120 mm
120 mm
110 mm
125 mm
125 mm
115 mm
115 mm
115 mm
–
115 mm –
–
–
–
125 mm
125 mm
200–1150
100–1250
–
–
200–1500
50 mm
–
–
–
200–1500
120–1020
300–1250
100–1016
–
width from – to [mm] diameter from – to [mm]
– 100–315
200–1500 125–1000
160–1000 100–1000
200–1150 –
100–1250 100–1016
– 100–200
height from – to [mm] length from – to [mm]
– 140–310
200–1500 296–390
120–1020 135
300–1250 125
100–1016 154–202
– 130
125–1000
100–1000
–
100–1016
100–200
made of fireproof boards height from – to [mm]
diameter from – to [mm]
–
–
100–315
160–1000
50 mm
110 mm
–
length from – toApS [mm] Hylkedamvej 70 : DK-5591 140–310 Gelsted 296–390 Gelco Nordic Tel.: 45 63135 46 54 08 : 125 Fax: +45 154–202 6346 5404 130 w w w.gelco -nordic.dk Side 7 af 8
Went folder ENG 2009.indd 7
2009-06-04 14:59:38
F I R E P ROTEC TION SYSTE M S F I R E P ROTEC TION SYSTE M S
fireproof partitions fireproof partitions smoke and heat exhaust systems smoke and heat exhaust systems fire ventilation systems fire ventilation systems fire protection of building structures fire protection of building structures
Arkońska Arkońska Business Business Park Park ul.ul. Arkońska Arkońska 6 bud. 6 bud. A2A2 80-387 80-387 Gdańsk, Gdańsk, Poland Poland tel.: tel.: +48 +48 5858 732 732 6363 0000 fax: fax: +48 +48 5858 732 732 6363 0202 mercor@mercor.com.pl mercor@mercor.com.pl
www.mercor.com.pl www.mercor.com.pl Arkońska Business Park ul. Arkońska 6 bud. A2 80-387 Gdańsk, Poland tel.: +48 58 732 63 00 Hylkedamvej : DK-5591 Gelsted fax: +48 58 732 70 63 02 mercor@mercor.com.pl
Gelco Nordic ApS
Tel.: 45 63 46 54 08 : Fax: +45 6346 5404 Mercor SA
w wwww.mercor.com.pl w . g e l c o - nMercor o r dSAi zcSanoka . d k2 Grzegorza Grzegorza z Sanoka 2 Arkońska Business Park
80-408 Gdaƒsk, Poland 80-408 tel. +48 Gdaƒsk, 58 341 42Poland 45 tel. +48 58 341 341 39 42 85 45 fax +48 58 fax +48 58 341 39 85 mercor@mercor.com.pl mercor@mercor.com.pl
www.mercor.com.pl Photos: Mateusz Grzanka and company archives Photos: Mateusz Grzanka and company archives ul. Arkońska bud. A2 Gelsted Gelco Nordic ApS Hylkedamvej 70 : 6DK-5591 Tel.: 45 63 46 54 08 : Fax: +45 6346 5404 www.mercor.com.pl 80-387 Gdańsk, Poland w tel.: w +48 w .58g732 e l63c00o - n o r d i c . d k Side 8 af 8 fax: +48 58 732 63 02