Evidence-Based Analysis_Daylighting & Energy

Page 6

ARCH 7530 - Building Performance Simulation Hardi Shah

CLIMATE INFORMATION

tmy3 file chosen

This project iteratively improves conditions within a unit on the 6th floor of a midrise apartment building in Augusta, Maine. The fabric of Augusta is largely low and mid rise buildings so the site was designed to reflect that. I placed an open garden on the south side of the building and oriented so the south has no solar obstruction.

introduced ‘capture internal heat’ as a passive strategy: brought 30% more hours into comfort

REVOLVING AROUND

REDUCING THE

HEATING LOAD

Assignment_FINAL PROJECT: Evidence-based Analysis
94% HOURS ARE BELOW 18C DEW POINT TEMP
SITE: AUGUSTA, MAINE; CLIMATE ZONE: 6A 64% HOURS ARE OUTSIDE COMFORTABLE RH 82% HOURS ARE BELOW 18C DRY BULB TEMP LARGE AMOUNT OF CLOUD COVER YEAR ROUND
only 454 (5.8%) hours out of the year are between 18c-25c and 40-70% relative humidity STRATEGIES
AND INCREASING THERMAL COMFORT INDOORS WHILE MAINTAINING ADEQUATE DAYLIGHTING IN THE SPACES.

Assignment_FINAL PROJECT: Evidence-based Analysis

BASELINE CONDITION

WALL: Wood Framed - R20

floor: Carpeted 8in Slab Floor-R5 [m2K/W]

WINDOW U-value: 0.30 [W/m2K] Window SHGC: 0.40 [dimensionless]

sensors in

window to wall ratios: wwr NORTH: 0 wwr EAST: 0.5 wwr south: 0.6 wwr west: 0.5

ARCH 7530 - Building Performance Simulation Hardi Shah

the thermal comfort in the office here needs to be addressed.

total energy use intensity: 224.87 kWh/m2 heating eui: 131.61 kWh/m2 cooling eui: 23.37 kWh/m2 lighting eui: 10.05 kWh/m2 elec equip eui: 33.67 kWh/m2

WE Want to bring this udi to above 50 as it is a workspace. as expected the heating eui is the highest and will be the main focus to reduce and create thermal comfort.

mean radiant temp: bedroom: 23.17c office: 21.58c

avg daylight autonomy is high overall. it is a more appropriate unit to measure daylight in the bedroom.

% of time comfortable: bedroom: 32.76% office: 22.93%

100% 50.23 90.12 bedroom bedroom bedroom office office office 48.7% 32.87 95.79 % of
pmv
% of time cold: bedroom: 54.92% office: 62.12% & 1 average useful daylight index percentages average daylight autonomy percentages
comfort between -1
Based on the solar site analysis that was done, I placed the office program on the east so that it would receive more daylight during occupied hours for that program.
Assignment_FINAL PROJECT: Evidence-based Analysis ARCH 7530 - Building Performance Simulation Hardi Shah march march june june december december 0.380.559am9am 0.38 1 0.45 0.43 0.40 0.37 0.39 0.19 0.31 0.400.53 0.21 0.390.42 0.43 1 9am9am 9am9am 12pm12pm 12pm12pm 12pm12pm 3pm3pm 3pm3pm 3pm3pm bedroom glare analysis sitting on the couch the glare values in color are over the acceptable threshold. office glare analysis sitting at the desk glare analysis

Point in time analysis shows percentage of useful illuminance at each sensor and shows the range of illuminances at its peaks and valleys but it does not reflect the overall annual conditions completely. It lets us see the general seasonal pattern shifts to make decisions.

THE WINDOW WALL RATIO COULD BE MANIPULATED TO GET MORE ROUNDED ILLUMINANCE VALUES THROUGH THE YEAR.

Assignment_FINAL PROJECT: Evidence-based Analysis ARCH
point in time illuminance march june december 9am 9am 9am 12pm 12pm 12pm 3pm 3pm 3pm 78% 87.75% 53.75%50.5%25% 69.75%62.25% 61.75%50.5% bedroom bedroom bedroombedroombedroom bedroombedroom bedroombedroom office office officeofficeoffice officeoffice officeoffice 85.5% 79.5% 60.75%77.75%79% 83%96% 80%91.5%
7530 - Building Performance Simulation Hardi Shah
THESE VALUES ARE LOWEST IN THE WINTER. THE LOW SUN ANGLE IN THE WINTER RESULTS IN A LOT OF DIRECT RADIATION OUTSIDE OF USEFUL ILLUMINANCE. THE BEDROOM SPECIFICALLY DOES NOT HAVE ENOUGH USEFUL DAYLIGHT IN THE WINTER.

Assignment_FINAL PROJECT: Evidence-based Analysis

ITERATIONS - first round

BUILDING LENGTH: 15M, 20M, 25M 81 iterations

EAST WWR: 0.3, 0.4, 0.5

SOUTH WWR: 0.4, 0.6, 0.8

U-VALUE: 0.32, 0.64, 0.96

inputs

ARCH 7530 - Building Performance Simulation Hardi Shah

The iterations were set up in two steps: the first would address the balance between daylight and thermal comfort while the second step would focus on reducing overall EUI.

UNDERSTAND RELATIONSHIP

BETWEEN ADEQUATE DAYLIGHT (LENGTH & WWR) AND THERMAL COMFORT (U-VALUE)

PROJECT: Evidence-based Analysis

best iterations - by office avg udi

This is a filtering method to select an option while prioritizing Avg UDI.

ARCH 7530 - Building Performance Simulation

HIGH OFFICE AVG UDI --> HIGH OFFICE % COMFORT --> HIGH BEDROOM % COMFORT --> LOW HEATING EUI --> HIGH MEAN RADIANT TEMPERATURES

DECISION MAKING SEQUENCE

I prioritized choosing the highest Avg UDI of the office first because there was a wide range of AvgUDIs and the space should at least have 50% to make sure that it can function well as a workspace. Then I began to look into comfort and then the energy use intensity.

this option has the highest avg udi for the office: 53.74 and is relatively high in comfort and low in eui. the east and south wwr are smaller than i expected while the west wwr is very high at 0.9.

Assignment_FINAL
Hardi Shah

best iterations - by % comfort

This is a filtering method to select an option while prioritizing overall % comfort.

DECISION MAKING SEQUENCE

I prioritized choosing the highest comfort in this filtering process and then choosing the highest corresponding daylight values from there. This resulted in a different final iteration than in the previous method.

this option has the highest % comfort for the office while also having a high % comfort in the bedroom. the avg udi is also still the highest in the range.

Assignment_FINAL PROJECT: Evidence-based Analysis ARCH 7530 - Building Performance Simulation Hardi Shah
OFFICE % COMFORT --> HIGH
--> HIGH
-->
EUI
HIGH
BEDROOM % COMFORT
OFFICE AVG UDI
LOW HEATING

Assignment_FINAL PROJECT: Evidence-based Analysis

ITERATIONS - second round

BUILDING LENGTH: 15M, 20M 18 iterations

ARCH 7530 - Building Performance Simulation Hardi Shah

The iterations were set up in two steps: the first would address the balance between daylight and thermal comfort while the second step would focus on reducing overall EUI.

construction type: masonry, wood, steel-framed inputs

r-VALUE: r-13, r-17, r-21

by avg udiby % comfort i assumed the wwr that were the best performing per iteration 1. now testing the two building lengths that we concluded, with the other parameters for a focus on energy and comfort.

the best u-value and wwrs are the same in both iterations so that was established as the new baseline.

Wood-framed

Steel-framed

Wood-framed

Steel-framed

HIGH OFFICE % COMFORT --> HIGH BEDROOM % COMFORT --> HIGH OFFICE AVG UDI

DECISION MAKING SEQUENCE

I prioritized choosing the highest comfort in this filtering process and then choosing the highest corresponding daylight values from there. The resulting total and heating EUI were second lowest in the options while still providing higher thermal comfort. We have two resulting options.

+

ITERATIONS - best options

Wood-framed

We have two resulting options from these iterations that give us similar output metrics.

Steel-framed

Wood-framed

Steel-framed

masonry steel framed

in these two options, the metrics are quite similar. the avg udi’s are over 50% and the % overall comfort is also the same. The only input that varies is the construction. I chose the mass construction because the daylight metrics for the office were better than the steel framed.

Assignment_FINAL
PROJECT: Evidence-based Analysis ARCH 7530 - Building Performance Simulation Hardi Shah
Assignment_FINAL PROJECT: Evidence-based Analysis ARCH 7530 - Building Performance Simulation
Hardi Shah
Wood-framed Steel-framed chosen ITERATION - masonry, 20m length, wall r-21
WALL: insulated exterior mass wall - R21 floor: Carpeted 8in Slab Floor-R4 [m2K/W] WINDOW U-value: 0.32 [W/m2K] Window SHGC: 0.40 [dimensionless] window to wall ratios: wwr NORTH: 0 wwr EAST: 0.3 wwr south: 0.4 wwr west: 0.9

bedroom pmv comfort is retained at 100% office pmv comfort is increased significantly from 48.7%

bedroom pmv comfort is increased by 4.56% from 50.23. office pmv comfort is increased by 21.19% significantly from 32.87%

daylight autonomy remained in the range of 90-98% throughout the project. so it was not considered too heavily.

total energy use intensity: 294.3 kWh/m2

heating eui: 185.17 kWh/m2 cooling eui: 39.24 kWh/m2 lighting eui: 10.05 kWh/m2

elec equip eui: 33.67 kWh/m2

the heating eui is still high. if i could adjust the infiltration rate, it would bring this eui down.

mean radiant temp: bedroom: 23.17c office: 21.58c

% of time comfortable: bedroom: 25.46% office: 20.33%

% of time cold: bedroom: 55.31% office: 61.12%

Assignment_FINAL PROJECT: Evidence-based Analysis ARCH 7530 - Building Performance Simulation Hardi Shah 100%88.46% % of sensors in pmv comfort between -1 & 1 bedroomoffice
54.79 92.54 bedroom bedroom office office 54.06 25.75% <2.00% 92.92 average useful daylight index percentages average daylight autonomy percentages 39.76%
chosen ITERATION - masonry, 20m length, wall r-21

chosen ITERATION - masonry, 20m length, wall r-21

the office loads are minimal compared to the bedroom. the solar gain in the winter is helping negate the need for excessive heating.

total energy use intensity: 294.3 kWh/m2

heating eui: 185.17 kWh/m2

cooling eui: 39.24 kWh/m2 lighting eui: 10.05 kWh/m2

elec equip eui: 33.67 kWh/m2

the solar gain during the summer is counter intuitive, natural ventilation during the summers might rid the need for cooling.

in the bedroom especially, the infiltration is high, resulting in higher heating loads. if i could change the infiltration rate, it would be beneficial for the space.

the heating eui is still high. if i could adjust the infiltration rate, it would bring this eui down.

mean radiant temp: bedroom: 23.17c office: 21.58c

% of time comfortable: bedroom: 25.46% office: 20.33%

% of time cold: bedroom: 55.31% office: 61.12%

Assignment_FINAL
PROJECT: Evidence-based Analysis ARCH 7530 - Building Performance Simulation Hardi Shah

PROJECT: Evidence-based Analysis

‘tight building’ + added occupancy schedules

overall the loads have decreased especially the heating loads. the solar loads here in the summer time might be mitigated if we incorporated natural ventilation.

total energy use intensity: 211.17 kWh/m2 (-83.13) heating eui: 101.33 kWh/m2 (-83.16) cooling eui: 39.94 kWh/m2 lighting eui: 10.05 kWh/m2 elec equip eui: 33.67 kWh/m2

this shows that the heating load is the most significant portion of the eui.

mean radiant temp: bedroom: 23.26c (+0.08) office: 22.41c (+0.83)

% of time comfortable: bedroom: 30.73% (+5.27) office: 24.05% (+3.62)

% of time cold: bedroom: 48.94% (-7.83%) office: 51.96% (-10%)

Assignment_FINAL
ARCH 7530 - Building Performance Simulation Hardi Shah
Assignment_FINAL PROJECT: Evidence-based Analysis ARCH 7530 - Building Performance Simulation
Shah march march june june december december 0.270.289am9am 0.21 0.35 0.25 0.23 0.29 0.23 0.22 0.09 0.25 0.340.320.19 0.30 0.38 0.30 0.50 9am9am 9am9am 12pm12pm 12pm12pm 12pm12pm 3pm3pm 3pm3pm 3pm3pm bedroom glare analysis sitting on the couch office glare analysis sitting at the desk glare analysis The glare values in color are over the acceptable threshold. Only two instances now have glare with adequate daylighting.
Hardi

Turn static files into dynamic content formats.

Create a flipbook
Issuu converts static files into: digital portfolios, online yearbooks, online catalogs, digital photo albums and more. Sign up and create your flipbook.