HIMOINSA ATS

Page 1

AUTOMATIC TRANSFER SWITCH CC2 & AC5 CONTROL PANELS


AUTOMATIC TRANSFER SWITCH

HIMOINSA MANUFACTURES AUTOMATIC TRANSFER SWITCH PANELS (ATS) WHICH TRANSFER POWER BETWEEN THE MAINS AND THE GENERATOR SET. A PIECE DESIGNED WITH

DIAGRAMS

A COMPREHENSIVE ELECTRICAL MECHANISM THAT ALLOWS A RAPID RESPONSE TO THE DEMAND FOR POWER ON THE STAND-BY MARKET.

ELECTRICITY NETWORK

HIMOINSA automatic transfer switch panels have a manual emergency stop and have been manufactured in compliance with required quality standards. With an amperage range of 30 to 3150 A, the HIMOINSA ATS has an IP55 protection rating which guarantees sealing and insulation levels.

GENERIC GENERATOR SET

CC2 | CEC7 1 km (*1)

GENSET CONTROLLER

VOLTAGE FREE / DRY CONTACT.

CC2

+

GENERIC GENERATOR SET SELECTION OF POWER SOURCE

* CAN communication up to 1 km away. HIMOINSA shall not provide communication or power cables. ( 1)

FINAL SUPPLY

ELECTRICITY NETWORK

HIMOINSA GENERATOR SET

AC5 | CEA7

6 m (*2)

AC5

+

HIMOINSA GENERATOR SET SELECTION OF POWER SOURCE

* Standard extension 6 metres. Optionally available up to 100 metres. ( 2)

FINAL SUPPLY

2

3


CONTACTORS 30-250A

SWITCHES 400-3150A 1

1

2

5

4

3 2

4

3

MAIN COMPONENTS

MAIN COMPONENTS 1

IP55 cabinet

2

Controller

3

Emergency stop

Measurements module

4

Measurements module

Contactors

5

Key for manual transfer switch

6

Motorised switch

7

Grounding line connection

8

Plinth for cabinets >800A

1

IP55 cabinet

2

Controller

3

Emergency stop

4 5 6

Grounding line connection

5

6

6

7

8

M

AUTOMATIC TRANSFER SWITCH USING A PAIR OF MECHANICALLY INTERLOCKED CONTACTORS AND WITH STATUS CONTACTS. 4

AUTOMATIC TRANSFER SWITCH USING MOTORISED SWITCHES WITH MANUAL ACTIVATION OPTION. 5


CC2

1

PE | TIERRA

PE | TIERRA 19 | NO

19 | NO 18 | C

18 | C L | CAN L

L | CAN L H | CAN H

H | CAN H 20 | POSITIVO

PE | TIERRA

3150

Weight

kg

27

27

28

28

30

31

54

55

128

135

164

220

245

347

385

450

486

Height

cm

700

700

700

700

700

700

1000

1000

1200

1200

1750

1800

1800

1800

2000

2000

2000

Length

cm

500

500

500

500

500

500

600

600

800

800

800

1000

1000

1200

1200

1200

1200

Width

cm

250

250

250

250

250

250

300

300

400

400

400

600

600

600

800

800

800

PE NO

NO C

2

C

2 1 3 2 4 3 5 4 6 5 PE 6

PE | GROUNDING LINE CONNECTION

PE

PE

PE | GROUNDING LINE CONNECTION 19 | NO

STARTING CONTACT 19 | NO 18 | C

18 | C L | CAN L

L | CAN L H | CAN H

H | CAN H 20 | POSITIVE

20 | POSITIVE 1 | NEGATIVE

POWER CAN CAN STARTING SUPPLY CONNECTIONCONNECTION CONTACT

2 1

1

1

Connection to generic panel, start and stop via voltage-free contact.

LA TERRE

LA TERRE 19 | NO

19 | NO 18 | C

18 | C L | CAN L

L | CAN L H | CAN H

H | CAN H | POSITIF

| POSITIF | NÉGATIF

CONNEXION CONNEXION CONTACT CONTACT ALIMENTATION ALIMENTATION CAN CAN DÉMARRAGEDÉMARRAGE | NÉGATIF

LA TERRE

LA TERRE 19 | NO

19 | NO 18 | C

18 | C L | CAN L

CONNEXION CONNEXION CONTACT CONTACT ALIMENTATION ALIMENTATION CAN CAN DÉMARRAGEDÉMARRAGE

GENERIC GENSET

Connection to HIMOINSA AS5/M5 type panel with CEM7 control unit. Start and stop via CAN communication.

1 | NEGATIVE

PE | GROUNDING LINE CONNECTION

PE

PE

L

PE

2 1 3 2 4 3 5 4 6 5 PE 6

L H

POWER SUPPLY

STARTING CONTACT 19 | NO 18 | C PE | GROUNDING LINE CONNECTION 19 | NO

18 | C L | CAN L

L | CAN L H | CAN H

H | CAN H 20 | POSITIVE

POWER CAN CAN STARTING SUPPLY CONNECTIONCONNECTION CONTACT

H 2

TERMINAL CONNECTION DIAGRAMS

POWER SUPPLY

PE

2500

PE NO

2000

NO C

1600

C

1250

2

1000

2 1

800

1

630

PE

400

L | CAN L H | CAN H

Motorised 4-pole switch. CEC7 controller. Power failure detection. Emergency stop. Voltage measurement.

PE | TIERRA 19 | NO

250

PE

160

H | CAN H | POSITIF

6

2500-3150 A

19 | NO 18 | C

125

| NÉGATIF

Motorised 4-pole switch. CEC7 controller. Power failure detection. Emergency stop. Voltage measurement.

18 | C L | CAN L

100

L

63

L H

50

H 2

40

2 1

30

1

1600 A

PE

SWITCHES

A

20 | POSITIVE 1 | NEGATIVE

Motorised 4-pole switch. CEC7 controller. Power failure detection. Emergency stop. Voltage measurement.

2 1 3 2 4 3 5 4 6 5 PE 6

Amperage

1 HIMOINSA GENSET

Motorised 4-pole switch. CEC7 controller. Power failure detection. Emergency stop. Voltage measurement.

1000-1250 A

1

CONTACTORS

POWER PANEL X3 800 A

PE

CC2 CONTROL PANELS

2 1

Motorised switch. CEC7 controller. Power failure detection. Emergency stop. Voltage measurement.

supply is equipped with an auxiliary battery that maintains the power supply in both modules, from the time when a power failure occurs until the generator sets start.

1000 m

2 1 3 2 4 3 5 4 6 5 PE 6

| POSITIF | NÉGATIF

4-pole contactors. CEC7 controller. Power failure detection. Emergency stop. Voltage measurement.

400-630 A

1

4-pole contactors. CEC7 controller. Power failure detection. Emergency stop. Voltage measurement.

160-250 A

1 | NEGATIVE

30-125 A

of over 100 metres a supplemental power supply is necessary.

20 | POSITIVO 1 | NEGATIVO

1 | NEGATIVO

maximum distance:

L | CAN L H | CAN H

H | CAN H 20 | POSITIVO

CONEXIÓN CONEXIÓN CONTACTO CONTACTO POWER SUPPLYARRANQUE The power ALIMENTACIÓN ALIMENTACIÓN CAN CAN ARRANQUE

20 | POSITIVO 1 | NEGATIVO

CONEXIÓN CONEXIÓN CONTACTO CONTACTO For communications ALIMENTACIÓN ALIMENTACIÓN CAN CAN ARRANQUE ARRANQUE 1 | NEGATIVO

CONTROL PANELS

7


CEC7

CONTROLLER Genset Readings

ALLOWS THE DETECTION OF ANY MAINS FAILURE AND MANAGES THE TRANSFER OF THE LOAD TO THE GENERATOR SET.

DISPLAY MODULE

The display module is responsible for carrying out the information tasks regarding the status of the device and allows actions to be performed by the user; through the display module the user is able to control the control unit, as well as program and configure the functions. Through the display module, access is given to a record of the last errors registered by the control unit. MEASUREMENTS MODULE

The measurements module is responsible for performing the tasks of monitoring and control of the control unit. This module is located in the rear panel to reduce wiring and increase the control unit's immunity against electromagnetic noise. All the signal, sensor and actuators are connected to the measurements module.

Counters

Voltage between phases

*

Total hour counter

Voltage between phase and neutral

*

Partial hour counter

Currents

*

Kilowatt meter

Frequency

*

Valid start counter

Apparent power (kVA)

*

Unsuccessful start counter

Active power (kW)

*

Maintenance

Reactive power (kVAr)

*

Power Factor

*

Communications RS232

Mains Readings

RS485

Voltage between phases

Modbus

Voltage between phase and neutral

Modbus IP Software for PC

Currents Engine Protection Devices Emergency stop

Analogue modem

GSM/GPRS modem

Performance

Alternator Protection Devices

Alarm history

High frequency

*

External start

Low frequency

*

Start inhibited

High voltage

*

Starting due to mains failure

Low voltage

*

Asymmetry between phases

*

Incorrect phases sequence

*

Unit signal failure

**

(*) Available only with connection to CEM7 control unit |

High protection Protection from overvoltage, undervoltage asymmetry, overcurrent, overfrequency, underfrequency, overload, incorrect network phase sequence, incorrect genset phase sequence.

8

Multiple starting methods Starting in manual, automatic, due to mains failure, via voltage-free contact. Reading and control of parameters The communication of the CEC7 control unit with HIMOINSA generator sets with CEM7 control unit, allows multiple electrical signal parameters

to be read, both those generated as well as the mains without adding instruments or external gauges. Reading of parameters such as voltage, current, frequency, active, apparent and reactive mains power (current transformer option); also the mains power factor and cosine phi (current transformer option) and

(**) Alarm with engine stop. |

10 (100 optional)

Mains and Genset breaker activation Multilingual Special Applications Short term paralelling on utility return Repetitive panel

CEC7 CONTROLLER

• • (***)

•* •

• Optional | • (***) Supplied to include optional communication.

instantaneous power (KwH) and accumulated power (day, month and year) of the generator set. Easy programming and management Possibility of customising the operation of the control unit to a specific application and programming the measurement parameters, thresholds,

times, alarms, adjustments. Allows the adjustment of measurements and levels such as the automatic filling of the fuel tank. The power outputs are protected. Addressable and expandable modules. More than 64 nodes and up to 1,000 metres without the need for a repeater using the appropriate cable.

9


AC5

CONTROL PANELS

AC5

AC5 control panels are only compatible with HIMOINSA gensets.

30-125 A

4-pole contactors. CEA7 controller. Detection of mains failure and genset control. Emergency stop. Current and voltage measurement.

160-250 A

4-pole contactors. CEA7 controller. Detection of mains failure and genset control. Emergency stop. Current and voltage measurement.

maximum distance:

400-630 A

100 m

Motorised switch. CEA7 controller. Detection of mains failure and genset control. Emergency stop. Current and voltage measurement.

AC5 CONTROL PANELS CONTACTORS

800 A

Motorised 4-pole switch. CEA7 controller. Detection of mains failure and genset control. Emergency stop. Current and voltage measurement.

SWITCHES

Amperage

A

30

40

50

63

100

125

160

250

400

630

800

1000

1250

1600

2000

2500

3150

Weight

kg

49

49

49

49

49

49

56

57

130

137

166

222

247

349

387

452

488

Height

cm

1000

1000

1000

1000

1000

1000

1000

1000

1200

1200

1750

1800

1800

1800

2000

2000

2000

Length

cm

600

600

600

600

600

600

600

600

800

800

600

1000

1000

1200

1200

1200

1200

Width

cm

300

300

300

300

300

300

300

300

400

400

400

600

600

600

800

800

800

1000-1250 A

Motorised 4-pole switch. CEA7 controller. Detection of mains failure and genset control. Emergency stop. Current and voltage measurement.

MULTI-PIN QUICK CONNECTOR

flexible connection, compact hose, resistant

1600 A

Motorised 4-pole switch. CEA7 controller. Detection of mains failure and genset control. Emergency stop. Current and voltage measurement.

10

2500-3150 A

Motorised 4-pole switch. CEA7 controller. Detection of mains failure and genset control. Emergency stop. Current and voltage measurement.

to impacts and hydrocarbons. Transmits information from the engine and the alternator to the control unit. The length of the standard hose supplied by HIMOINSA is 6 metres and is optionally available up to 100 metres.

16/24 pins. Robust and secure device used in our ATS with AC5 configuration. connector

11


CEA7

CONTROLLER ALLOWS TOTAL CONTROL OF THE GENERATOR SET AND THE TRANSFER SWITCH WITH THE MAINS. DISPLAY MODULE

Reports on the status of the device and allows interaction with the user, who can manage the control unit as well as program and configure its operation. It consists of a backlit display and various LEDs and pushbuttons used to monitor the control device. MEASUREMENTS MODULE

Performs tasks of supervision and control of the generator set. It is located inside the panel to reduce the wiring and increase immunity of the control unit to electromagnetic noise. All the signals, sensors and actuators are connected to the measurements module. The connection between the measurements module and display module is performed via a CAN communications bus, enabling the interconnection of additional modules which ensures the versatility of the control unit.

Genset Readings

Engine Protection Devices

Counters

Voltage between phases.

High water temperature

Total hour counter

Voltage between phase and neutral

High water temperature by sensor

Partial hour counter

Currents

Low engine temperature by sensor

Kilowatt meter

Frequency

Low oil pressure

Valid start counter

Apparent power (kVA)

Low oil pressure by sensor

Unsuccessful start counter

Active power (kW)

Low water level

Maintenance

Reactive power (kVAr)

Unexpected stop

Communications

Power Factor

Fuel reserve

Calculation of harmonics up to order 20

Fuel reserve by sensor

Mains Readings

Stop failure

Voltage between phases. Voltage between phase and neutral Currents Frequency Apparent power Active power

Battery voltage failure Battery charging alternator failure Overspeeding Underfrequency Starting failure Emergency stop

RS232

RS485

Modbus IP

Modbus

Software for PC

Analogue modem

GSM/GPRS modem

J1939 bus communication Performance

Reactive power

Alternator Protection Devices

Power Factor

High frequency

Calculation of harmonics up to order 20

External start

Low frequency

Start inhibited

Engine Readings

High voltage

Starting due to mains failure

Coolant temperature

Low voltage

Mains and Genset breaker activation

Oil pressure

Short Circuit

Multilingual

Fuel level

Asymmetry between phases

Battery voltage

Incorrect phases sequence

RPM

Reverse Power

Battery charging alternator voltage

Overload

Alarm history

10 (100 optional)

Unit signal failure • Optional

CEA7 CONTROLLER

High protection Protection from overvoltage, undervoltage asymmetry, overcurrent, overfrequency, underfrequency, overload, incorrect network phase sequence, incorrect genset phase sequence. Reading and control of parameters Reading parameters such as voltage, current, frequency, fuel level, tachometer (revolution counter), current power consumption, battery voltage, engine temperature, oil pressure, cos phi per phase, measurements of total energy consumed (per day, month and year), alarm control.

12

Easy programming and management Possibility of customising the operation of the control unit to a specific application and programming the measurement parameters, thresholds, times, alarms, adjustments... Allows the adjustment of measurements and levels such as the automatic filling of the fuel tank. The power outputs are protected. Addressable and expandable modules. More than 64 nodes and up to 1,000 metres without the need for a repeater using the appropriate cable.

13


TECHNICAL SERVICE AND SPARES PARTS

TECHNICAL SERVICE Comprehensive technical support through qualified professionals and authorised technical centres.

INTELLIGENT CONTROL Intelligent storage centres allowing automatic searches and selection of spare parts.

FLEET MANAGER Provides information on the location and status of the rented product.

24/7 ONLINE SPARE PARTS 24-hour service for online purchasing of replacement parts.

HIMOINSA provides its customers with a fast and efficient technical service through a technical assistance network, distributed worldwide. The spare parts department supplies original replacement parts for every component of the genset through a centralised system.

Personalised Assistance. Technical experts provide the customer with a wide range of solutions throughout the lifetime of the product.

Quality Assurance. After-sales service guarantees the investment made in purchasing the product through the extensive network of authorised support centres, distributors and the technical service.


© HIMOINSA - May 2016

www.himoinsa.com

FACTORIES: SPAIN • FRANCE • INDIA • CHINA • USA • BRAZIL • ARGENTINA

SUBSIDIARIES: PORTUGAL | POLAND | GERMANY | UK | SINGAPORE UAE | PANAMA | DOMINICAN REPUBLIC | ARGENTINA | ANGOLA HEADQUARTERS: Ctra. Murcia - San Javier, km 23.6 30730 SAN JAVIER (Murcia) SPAIN TLF. +34 968 19 11 28 | +34 902 19 11 28 Fax +34 968 19 12 17 | Export Fax +34 968 33 43 03 HIMOINSA reserves the right to change any feature without prior notice. The illustrations may include optional equipment and/or accessories. Not contractual images. The technical indications described in this brochure correspond to the information available at the moment of printing. HIMOINSA ® - 2016 © All rights reserved.


Turn static files into dynamic content formats.

Create a flipbook
Issuu converts static files into: digital portfolios, online yearbooks, online catalogs, digital photo albums and more. Sign up and create your flipbook.