Salamander Pumps
Positive head system (Gravity-fed) Usable capacity minimum 50 gallons per bathroom and 30 gallons per en suite
Air vents, both hot and cold
Positive head
Vent and other services The hot connection must be via an approved side or top entry flange
MAX 65°C
Non return valve Hot outlet ONLY
Outlets
C
H
Inlet
Negative head When the distance between the cold water storage cistern and the shower head is 600 mm or less, or when the natural flow is poor or less than 2 litres per minute of combined hot and cold it is possible a negative head pump may be required.
Salamander Pumps
Salamander Pumps
RHP 50,75,100_NEW
2.80 2.10 1.30
2.55 1.95 1.10
2.35 1.75 1.00
2.05 1.55 0.75
1.45
1.10
1.05 0.55 60
70
12 13 14 15
Salamander Pumps
RHP 45,75&100
2.80 2.55 2.10
1.30
25
1.95
1.10
2.35 2.05 1.75
1.00
1.55
0.75
1.45 1.10
1.05 0.55
60
70
12 13 14 15
3.18 2.81 2.15
RGP 50
1.09
1.81
2.21 1.39
1.00
0.72
Salamander Pumps
2.10
1.30
1.95
1.10
1.75
1.00
1.55 1.05 0.75
0.55 60 12 13
2.80
2.55
2.05 1.45
60
1.10
70
12 13 14 15 16
Salamander Pumps
ESP 120 ESP 80 ESP 55
3.18 2.81 2.15
1.09
3.18 2.15
1.81
2.21 1.39
1.00
0.72
2.81 1.61
2.21 1.39
Salamander Pumps
Salamander Pumps
Bar Rating Closed Head
Bar Rating @ 9 ltr/min
Performance
RGP 50
1.5
1.4
RGP 80
2.4
2.2
RGP 120
3.6
3.3
RSP 50
1.5
1.4
RSP 75
2.2
2.0
RSP 100
3.0
2.8
RHP 50
1.5
1.4
RHP 75
2.2
2.0
RHP 100
3.0
2.8
ESP 55 CPV
1.5
1.4
ESP 80 CPV
2.4
2.2
ESP 120 CPV
3.6
3.3
ESP 50 CPV
1.5
1.4
ESP 75 CPV
2.2
2.0
ESP 100 CPV
3.0
2.8
ESP 80 CPV SB
2.4
2.2
ESP 120 CPV SB
3.6
3.2
•
•
• • • • •
• • • • •
• • • • •
• • • • •
• • • • •
• • • • • • • • •
• • • • • • • • •
• • • • • • •
• • • • • •
• • •
• • • • •
• • • • •
• • • • • • • • •
• • • • • • • • •
•
• • • • •
• • • • •
• • • • • • • • 0.5
• • • • • 1.0
• • • • • 1.0
• • • 0.5
•
• • • • •
• • • • • •
•
•
• • • • • • • • 15mm 10mm • •
• • • • • • • • • • 22mm 15mm • •
• • • • • • • • • • 22mm 15mm • •
• • • • • • • 15mm 10mm • •
• • • • • • • • •
• • • • • • • • •
• • • • • • •
• • • • • • •
• • • • • • •
• • • • • • •
• • • • • • •
• • • • • • •
• • • • • • •
• • • • • • •
• • • • • • •
• • • • • • •
• • • • • • •
• • • • •
• • • • • 1.0 Bar
Specification Impellor Seal Pump
15mm
Motor
22mm
Type
Input Parameters
G3/4 (M)
220-240v 50Hz Single Phase. Induction Motor. (complies with BS5000 part 11)
Max Input Temperature (°C)
Max Input Pressure (Bar)
Universal
Positive Head
Pump Type
65°C
•
1.0 Bar
•
Twin Impellor
Outlet
•
Inlet
•
Diameter
•
Pushfit
•
Ceramic
•
PTFE Carbon
•
Centrifugal
•
Composite
•
Continuously Rated
•
Single Impellor
•
Individual Hot/Cold Taps or Both
•
Washbasins
• Toilets
•
Whole House
Body Jets (4 max)
Chanpagne Spray
Massage Function
Multi Function Shower
Victorian Can Shower Head
Conventional Shower
Washing Machine / Dishwasher
Instant Electric Water Heater
Instant Electric Shower
Combi Boiler
Application Connection Size / Type Hose Isolators
Salamander Pumps
Positive head system
Pump fitted above cylinder
Usable capacity minimum 50 gallons per bathroom
Usable capacity minimum 50 gallons per bathroom
Air vents, both hot and cold Min 600mm Positive head
Cold water cistern
Air vents, both hot and cold
Outlets
Cold water cistern
Inlet
Negative head system
C
H
Shower head
Shower head Vent and other services Hot water cylinder
Shower valve
The hot connection must be via an approved side or top entry flange
MAX 65°C
H
Shower head
Pump
Cold water cistern
No Stop Essex Flange MUST be used with an anti-gravity loop at least 200mm in depth
RSP Twin Pump with up and over pipework and natural flow of 1Litre/min per side.
Vent and other services
Hot water cylinder
The hot connection must be via an approved side or top entry flange
Pump
Inlet
Shower valve
Usable capacity minimum 50 gallons per bathroom
Shower valve
MAX 60°C
Non-return valve hot outlet only
Outlets
C
Hot water cylinder
Vent and other services
NEGATIVE HEAD
Non-return valve hot outlet only
Pump fitted in loft above cylinder. Must use no stop Essex flange and anti-gravity loop.
MAX 65°C
Pump
Outlets Inlet C
H
Inlet
ESP CPV Twin Pump to a bathroom in a loft conversion.
Pump feeding two showers
Whole house system Usable capacity minimum 50 gallons per bathroom
Vent and other services
Positive head
Hot water cylinder
MAX 65°C
Outlets
C
H Pump Inlet
Usable capacity minimum 50 gallons per bathroom
Cold water cistern
Cold water cistern
Shower head
Shower valve
The hot connection must be via an approved side or top entry flange
Usable capacity minimum 50 gallons per bathroom
Cold water cistern Positive head
Pump on steam cabinet
Fit an equilibrium ball valve
Vent and other services The hot connection must be via an approved side or top entry flange
Min 600mm Inlet
Hot water cylinder
Shower head
Air vents, both hot and cold
Outlets
C
H Pump Shower head
Shower valve
MAX 65°C
Pump
Outlets
C
H
Inlet
Vent and other services
RSP Twin Pump feeding two showers. MAX 60°C
Shower valve No Stop Essex Flange MUST be used with an anti-gravity loop at least 250mm in depth Hot water cylinder
RHP Twirl Pump on a whole house system. ESP CPV Pump fitted above cylinder on a steam shower cabinet.
Fit an equilibrium ball valve
Large whole house system
Large whole house system
Combi with CWS tanks and cylinder
Cold water cistern Usable capacity minimum 50 gallons per bathroom
Whole House
•
Shower head Shower valve 8ft Second
Fit an equilibrium ball valve
Usable capacity minimum 50 gallons per bathroom
Cold water cistern
MAXIMUM 10 METRES
Shower valve
Pump
7ft Basement
MUST USE No Stop Essex Flange with 3 inch insert into cylinder
Shower head
•
Vent and other services Fit an equilibrium ball valve
MAX 60°C
Hot water cylinder
Hot water cylinder MAX 65°C
Positive head
Outlets C
Cylinder heated by Economy Seven or indirectly from the combination boiler
H Shower head
Pump
Shower valve
MAX 65°C H
•
Shower valve
Whole house antigravity loop
Vent and other services
Cold water cistern The hot connection must be via an approved side or top entry flange
8ft Ground Hot water cylinder
Usable capacity minimum 50 gallons per bathroom
Shower head
Pump Min 600mm
Pump
Pump Combi boiler
Washing machine
Large whole house system with the ESP CPV SB hot and cold pumps independently mounted with hot pump above cylinder.
Incoming water mains
Large whole house system with the ESP CPV SB hot and cold pumps mounted in the airing cupboard. Combi boiler system with RSP twin pump to boost the shower from a CWS tank and a direct cylinder.
Pumped tank supplies to combi or pressurised cylinder
Multiple showers
Pumping hot water only
Usable capacity minimum 50 gallons per bathroom Min 600mm
Cold water cistern
Positive head
Cold water cistern Usable capacity minimum 50 gallon per bathroom
Pump
Hot water cylinder
MAX 65°C
MAX 65°C
• Incoming cold water mains
Hot water cylinder
MAX 65°C
Shower valve
Combi boiler
Shower head
Mixer valve
Vent and other services
Shower head
Sports complex with multiple showers.
Pump
Shower valve Double action non-return valves Incoming cold water mains
Tank-fed (hot) with cw mains cold systems MUST USE Right ESP CPV.
H
Pump
Tank-fed, pressurised cylinder or combi boiler system with ESP CPV single to boost the hot supply water pressure and cold water mains supplies “cold” to shower, bath, basin and toilet.
Salamander Pumps
Typical pipework arrangement Systems without a flange will risk aeration of the supply water to the pump.
MAX 65°C
Cold feed to cylinder
Pump
S flange The S flange will encourage aeration to follow a natural path to vent and prevents aerated supply water being drawn into the pump.
To vent
S flange
HOT WATER CYLINDER
To pump
Usable capacity minimum 50 gallons per bathroom and 30 gallons per en suite Vent and other services
Can be off the vent if the distance is at least 1 metre
Surrey or No Stop Essex ange Outlets Inlet C
H
Inlet
Hot water supply blending valve controller is factory set at 55-60°C
Salamander Pumps