ENVIROLEX® CABLES For a healthier Aotearoa New Zealand
Reduced acid, gas and smoke generation
Flexible Copper Conductor for ease of handling and installation
Halogen free (i.e. no chlorine, bromine etc)
Envirolex® is an extensive range of environmentally friendly cables with a Red List Free Declare status, developed for both domes�c and commercial applica�ons. Made with low smoke zero halogen (LSZH) materials, making them PVC free and engineered to reduce environmental impact under fire condi�ons. By reducing emissions of harmful gases that may hinder an evacua�on process during fire, these cables have been designed with safety in mind whilst retaining excellent mechanical and electrical proper�es.
Conductor range up to 630mm for Single Core cables
Manufactured in accordance with AS/NZS 5000.1
Nexans New Zealand par�cipate in and support Declare, a cri�cal product ingredients transparency pla�orm interna�onally transforming the materials marketplace. WHAT IS DECLARE? A Declare Label provides nutri�on informa�on for building products. Designers and developers who value transparency and long term health, use the system to check which materials are free of red List chemicals. Declare was developed by the Interna�onal Living Future Ins�tute (ILFI). The global Red List is a database of the worst in class toxic chemicals known to be a hazard to health by pollu�ng the environment, bio-accumula�ng up the food chain to reach toxic concentra�ons which harm building occupants, construc�on and factory workers.
ENVIROLEX® FLAT TPS ALSO AVAILABLE!
Nexans received Red List Free Declare status in 2019 for all Envirolex® and Alsecure® product ranges. These products meet the prerequisite to support green projects a�emp�ng ra�ngs such as NZGBC Home Star, ILFI's transforma�onal CORE and Living Building Challenge standards.
Single Core - Black Nominal conductor Maximum area diameter of wires
Min.bending Nominal overall radius during diameter installation
Approx.mass
kg/100m
mm2
mm
mm
10 16 25 35 50 70 95 120 150 185 240 300 400 500 630
0.21 0.21 0.21 0.21 0.31 0.31 0.31 0.51 0.51 0.51 0.51 0.51 0.51 0.51 0.51
34 40 46 51 57 65 74 83 90 100 111 124 141 160 176
mm 8.5 9.8 11.3 12.6 14.2 16.2 18.3 20.7 22.5 24.8 27.7 31 35.4 40.0 44
Nominal Insulation Thickness
Min.bending radius during installation
Nominal Sheath Thickness
Nominal Overall Diameter
Approx.mass
mm
mm
mm
mm
kg/100m
14 23 31 40 56 75 98 113 151 179 240 290 389 498 629
Code
Product code
7742 1711 3032 9388 2647 5466 7420 7240 1805 5364 7721 4412 5674 3794 2095
BZHX01AA001CXNA BZHX02AA001CXNA BZHX03AA001CXNA BZHX04AA001CXNA BZHX05AA001CXNA BZHX06AA001CXNA BZHX07AA001CXNA BZHE87AA001CXNA BZHE88AA001CXNA BZHE89AA001CXNA BZHE90AA001CXNA BZHE91AA001CXNA BZHE92AA001CXNA BZHE93AA001CXNA BZHE94AA001CXNA
Mul�core - Orange Nominal conductor area mm
2
1.5 2.5 4.0 6.0
0.7 0.7 0.7 0.7
43 47 51.7 55
1.8 1.8 1.8 1.8
1.5 2.5 4.0 6.0 10.0
0.7 0.7 0.7 0.7 0.7
46 49 52 60 71
1.8 1.8 1.8 1.8 1.8
1.5 2.5 4.0 6.0 10.0 16.0 25.0 35.0
0.7 0.7 0.7 0.7 0.7 0.8 0.9 0.9
50 55 60 65 78 92 106 120
1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8
0508 NEXANS | www.nexans.co.nz
2C+E 10.7 11.6 12.9 13.6 3C+E 11.5 12.2 13.0 14.9 17.7 4C+E 12.5 13.6 15.0 16.2 19.5 22.8 26.5 29.8
Code
Product code
15 19.2 24.1 30.4
9613 8293 8340 9893
DTHR04HF002OMHF DTHR05HF002OMHF DTHR06HF002OMHF DTHR07HF002OMHF
17.8 23.8 29.0 35.3 51.9
1017 6257 1202 2611 4662
FTHR04HF003OMRJ FTHR05HF003OMRJ FTHR06HF003OMRJ FTHR07HF003OMRJ FTHX01HF003OMRJ
21.0 27.5 33.5 42.3 64.4 89.4 130.3 176.6
9501 7956 7524 4320 5670 8926 3338 7099
HTHR04HF004OMEM HTHR05HF004OMEM HTHR06HF004OMEM HTHR07HF004OMEM HTHX01HF004OMEM HTHX02HF004OMEM HTHX03HF004OMEM HTHX04HF004OMEM
Maximum Opera�ng Temperature Single Core: 110˚ C
Voltage Ra�ng
Mul� Core: 90˚ C
0.6/1 kv
Construc�on Single and Mul�core flexible copper conductor (Class 5) Single core:
X-110 (XLPE) insulated
Mul� Core:
X-90 insulated
Single Core: HFS-110-TP sheathed Mul� Core: HFS-90-TP sheathed (Low Smoke Zero Halogen)
Standards
Current Ra�ngs
AS/NZS 5000.1
Refer to AS/NZS 3008
AS/NZS 4507 RHE-1
Single core table 6, 9, & 15 Mul� Core table 5, 8, 11 & 14
Applica�ons A comprehensive range of cables that are typically used for mains/sub-mains, final circuits connecting to electrical devices, lights, li�s etc for hospitals, office buildings, tunnels, public high traffic areas and emergency exits. Being PVC free, Envirolex® cables are also suitable for lower temperatures (-25�) and non-migratory applica�ons. }Ž | ý ÅŽ Halogen free
Low smoke
Operating temp 110°C
High flexibility
Flame retardant