CHEAH HOONG FEI (0311690) BUILDING SCIENCE 2
1.0 Lighting 1.1.1 Day Lighting (Informal Study Area) According to MS 1525, Daylight Factor distribution as below: Daylight Factor (%) >6 3-6 1-3 0-1
Distribution Very bright with thermal & glare problem Bright Average Dark
The selected area (Informal Study Area) located at first floor. This is an outdoor reading area, faรงades are openable to allow natural sunlight penetrate into this area. Hence, there are no artificial lighting will be using in this area.
Figure: First floor plan
Page | 1
CHEAH HOONG FEI (0311690) BUILDING SCIENCE 2
Figure: Section of informal study area
Daylight Factor Calculation Floor Area (m²) Area of façade that exposed to sunlight (m²) Exposed Façade to Floor Area Ratio/ Daylight Factor, DF
77 99 [(99) ÷ 77] = 1.286 = 128.6% x 0.1 = 12.86%
Natural Illumination Calculation Illuminance 120,000 lux 110,000 lux 20,000 lux 1,000 – 2,000 lux <200 lux 400 lux 40 lux <1 lux
Example Brightest sunlight Bright sunlight Shade illuminated by entire clear blue sky, midday Typical overcast day, midday Extreme of darkest storm clouds, midday Sunrise or sunset on a clear day (ambient illumination) Fully overcast, sunset/sunrise Extreme of darkest storm clouds, sunset/sunrise
E external = 20,000 lx DF = (Ei/Eo) x 100% DF
= 12.86 x 20 000 / 100 = 2572 lux
Page | 2
CHEAH HOONG FEI (0311690) BUILDING SCIENCE 2
Figure: Natural lighting contour diagram for informal study area
Conclusion The daylight contour diagrams is based on Dialux stimulation at 12pm, March. The Informal
Study Area has a daylight factor of 12.86 and natural illumination of 2572 lux. MS 1525 recommended illumination level for a study area is 400. This will cause thermal and glare problem. Hence, adjustable shading device is implemented to solve the glare problem and also to reduce the heat gain in this area.
Note Shadotimber is a fixed or controllable wooden louvre shading system that is proposed to install in front of the faรงade of the building. A shadotimber system can reduce solar heat gain, lower air conditioning running costs.
Page | 3
CHEAH HOONG FEI (0311690) BUILDING SCIENCE 2
1.1.2 Day Lighting (Play space) According to MS 1525, Daylight Factor distribution as below: Daylight Factor (%) >6 3-6 1-3 0-1
Distribution Very bright with thermal & glare problem Bright Average Dark
The selected area (Play space) is located at second floor. There is a skylight which bring the richness of natural sunlight into this area. Both facades for this area are openable and totally exposed to sunlight. Therefore, there are no need of artificial lighting in this area.
Figure: Second floor plan
Page | 4
CHEAH HOONG FEI (0311690) BUILDING SCIENCE 2
Figure: Section of play space
Daylight Factor Calculation Floor Area (m²) Area of façade that exposed to sunlight (m²) Area of skylight (m²) Exposed Façade & Skylight Area to Floor Area Ratio/ Daylight Factor, DF
42 46.35 18 [(46.35+18) ÷ 42] =1.532 = 153.2% x 0.1 = 15.32%
Natural Illumination Calculation Illuminance 120,000 lux 110,000 lux 20,000 lux 1,000 – 2,000 lux <200 lux 400 lux 40 lux <1 lux
Example Brightest sunlight Bright sunlight Shade illuminated by entire clear blue sky, midday Typical overcast day, midday Extreme of darkest storm clouds, midday Sunrise or sunset on a clear day (ambient illumination) Fully overcast, sunset/sunrise Extreme of darkest storm clouds, sunset/sunrise
E external = 20,000 lx DF = (Ei/Eo) x 100% DF
= 15.32 x 20 000 / 100 = 3064 lux
Page | 5
CHEAH HOONG FEI (0311690) BUILDING SCIENCE 2
Figure: Natural lighting contour diagram for play space
Conclusion The Play Space area has a daylight factor of 15.32 & natural illumination of 3064 lux. This will result in thermal and glare problem. Therefore, shading device and double glazed low e-value glass for skylight will be proposed to solve the glare problem and also to reduce the heat gain in this area.
Note Low-e coatings are proposed to minimize the amount of ultraviolet and infrared light that can pass through without compromising the amount of visible light that is transmitted.
Page | 6
CHEAH HOONG FEI (0311690) BUILDING SCIENCE 2
Task Lighting for infrequently used area
Lighting for working interiors
Localized lighting for exacting task
Illuminance (Lux) 20 100 100 100 100 150 100 100 100 100 200 200 300 – 400 300 – 400 150 200 150 – 300 150 150 100 100 300 – 500 200 – 750 300 500 1000 2000
Example of Applications Minimum service illuminance Interior walkway and car-park Hotel bedroom Lift interior Corridor, passageways, stairs Escalator, travellator Entrance and exit Staff changing room, locker and cleaner room, cloak room, lavatories, stores Entrance hall, lobbies, waiting room Inquiry desk Gate house Infrequent reading and writing General offices, shops and stores, reading and writing Drawing office Restroom Restaurant, canteen, cafeteria Kitchen Lounge Bathroom Toilet Bedroom Classroom, library Shop/ Supermarket/ Department store Museum and gallery Proof reading Exacting drawing Detailed and precise work
Table: Recommended average illuminance levels
Page | 7
CHEAH HOONG FEI (0311690) BUILDING SCIENCE 2
1.2.1 Artificial Lighting (Café) The café located on the ground floor that from day to night. Although natural light can be acquired but it is insufficient. Hence, artificial lighting is vital for the space.
Figure: Ground floor plan
According to MS1525, the minimum lighting level required for a café is 200 lux. Type of luminaire used as showed below: Type of fixture Type of light bulb
LED Downlight
Material of fixture Product Brand & Code Nominal Life (Hours) Wattage Range (W) CRI Colour Temperature (K) Colour Designation Lumens
Aluminium LEDXION K01116 50,000 44 85 3000 Warm white 3735 Page | 8
CHEAH HOONG FEI (0311690) BUILDING SCIENCE 2
Material
Function
Colour
Area (m²)
Surface Type Reflective
Reflectance Value 0.30
Concrete finish Glass Timber Timber flooring Timber
Ceiling
Grey
28.91
Wall Wall frame Floor
Transparent 60.15 Brown 9.51 Brown 28.91
Absorptive Absorptive Absorptive
0.10 0.14 0.14
Furniture (table)
Brown
Absorptive
0.14
3.63
Table: Sample LLMF graphic
Lumen method and calculation for Café (from 1.5m height) Location Dimension
Area (A) Luminaries height Mounting height (Hm) Recommended average illumination levels by MS 1525 (E) Reflectance value
Café Length (L) = 5.9m Width (W) = 4.9m Height of the ceiling = 4.3m L x W = 5.9 x 4.9 = 28.91m² 4.3m 4.3 – 0.8 = 3.5m 200 lux Ceiling: 0.3, Floor: 0.14, Wall: 0.24
Page | 9
CHEAH HOONG FEI (0311690) BUILDING SCIENCE 2
Room index
đ??żđ?&#x2018;Ľđ?&#x2018;&#x160; 5.9 đ?&#x2018;Ľ 4.9 = (đ??ż + đ?&#x2018;&#x160;)đ??ťđ?&#x2018;&#x161; (5.9 + 4.9)3.5 = 0.8
Utilisation factor Maintenance factor
Type of light Number of light required
From table, UF = 0.26 Luminaire category = C (closed top reflector) Time between cleaning (years) = 1 đ?&#x2018;&#x20AC;đ??š = đ??żđ??żđ?&#x2018;&#x20AC;đ??š đ?&#x2018;Ľ đ??żđ?&#x2018;&#x2020;đ??š đ?&#x2018;Ľ đ??żđ?&#x2018;&#x20AC;đ??š đ?&#x2018;Ľ đ?&#x2018;&#x2026;đ?&#x2018;&#x2020;đ?&#x2018;&#x20AC;đ??š đ?&#x2018;&#x20AC;đ??š = 0.7 đ?&#x2018;Ľ 1.0 đ?&#x2018;Ľ 0.89 đ?&#x2018;Ľ 0.9 đ?&#x2018;&#x20AC;đ??š = 0.56 LED light with 1 bulb, 3735 x 1 = 3735 lumen (F) đ??¸đ?&#x2018;Ľđ??´ đ?&#x2018; = đ??š đ?&#x2018;Ľ đ?&#x2018;&#x2C6;đ??š đ?&#x2018;Ľ đ?&#x2018;&#x20AC;đ??š đ?&#x2018; =
200 đ?&#x2018;Ľ 28.91 3735 đ?&#x2018;Ľ 0.26 đ?&#x2018;Ľ 0.56
đ?&#x2018; = 11 11 luminaries are needed to reach the minimum requirement for MS1525 = 200 lux Spacing to height ratio (SHR) đ?&#x2018;&#x2020;đ??ťđ?&#x2018;&#x2026; =
đ?&#x2018;&#x2020;đ??ťđ?&#x2018;&#x2026; =
1 đ??´ đ?&#x2018;Ľâ&#x2C6;&#x161; đ??ťđ?&#x2018;&#x161; đ?&#x2018;
1 28.91 đ?&#x2018;Ľâ&#x2C6;&#x161; 3.5 11 = 0.46
đ?&#x2018;&#x2020;đ??ťđ?&#x2018;&#x2026; =
Approximate fittings layout/m
đ?&#x2018;&#x2020; = 0.46 3.5
đ?&#x2018;&#x2020; = 3.5 đ?&#x2018;Ľ 0.46 = 1.61 Fittings required along 5.9 m wall; 5.9 á 1.61 = 3.66 = 4 rows Therefore, approximately 4 x 3 = 12 luminaries required; Spacing along 4.9 m wall; 4.9 / 3 = 1.63 m Page | 10
CHEAH HOONG FEI (0311690) BUILDING SCIENCE 2
Final layout
Figure: Fittings layout of café
Figure: Artificial lighting contour diagram for cafe
Conclusion 12 LED lights are used to illuminate the café to achieve the minimum of 200 lux stated by MS1525. With sufficient level of illumination, the users can enjoy food and good times in a well illuminated atmosphere.
Page | 11
CHEAH HOONG FEI (0311690) BUILDING SCIENCE 2
1.2.2 Multipurpose room The multipurpose located on the third floor that. Although natural light can be acquired but it is insufficient. Hence, artificial lighting is vital for the space.
Figure: Third floor plan
According to MS1525, the minimum lighting level required for a multipurpose room is 300 lux. Type of luminaire used as showed below: Type of fixture Type of light bulb
Fluorescent tube with reflector
Material of fixture Product Brand & Code Nominal Life (Hours) Wattage Range (W) CRI Colour Temperature (K)
Aluminium F39W/TS/830/ECO 36,000 39 85 3000 Page | 12
CHEAH HOONG FEI (0311690) BUILDING SCIENCE 2
Colour Designation Lumens
Warm white 3500
Material
Function
Colour
Area (m²) 132.28
Surface Type Reflective
Reflectance Value 0.30
Concrete finish Glass Timber Concrete Timber flooring
Ceiling
Grey
Wall Wall Wall Floor
Transparent Brown Grey Brown
29.24 79.55 79.55 132.28
Absorptive Absorptive Reflective Absorptive
0.10 0.14 0.30 0.14
Table: Sample LLMF graphic
Lumen method and calculation for Multipurpose room (from 1.5m height) Location Dimension
Area (A) Luminaries height Mounting height (Hm)
Multipurpose room Length (L) = 18.5m Width (W) = 7.15m Height of the ceiling = 4.3m L x W = 18.5 x 7.15 = 132.28m² 4.3m 4.3 – 0.8 = 3.5m Page | 13
CHEAH HOONG FEI (0311690) BUILDING SCIENCE 2
Recommended average illumination levels by MS 1525 (E) Reflectance value Room index
Utilisation factor Maintenance factor
300 lux Ceiling: 0.3, Floor: 0.14, Wall: 0.54 đ??żđ?&#x2018;Ľđ?&#x2018;&#x160; 18.5 đ?&#x2018;Ľ 7.15 = (đ??ż + đ?&#x2018;&#x160;)đ??ťđ?&#x2018;&#x161; (18.5 + 7.15)3.5 = 1.47 From table, UF = 0.4 Luminaire category = C (closed top reflector)
Time between cleaning (years) = 1
Type of light Number of light required
đ?&#x2018;&#x20AC;đ??š = đ??żđ??żđ?&#x2018;&#x20AC;đ??š đ?&#x2018;Ľ đ??żđ?&#x2018;&#x2020;đ??š đ?&#x2018;Ľ đ??żđ?&#x2018;&#x20AC;đ??š đ?&#x2018;Ľ đ?&#x2018;&#x2026;đ?&#x2018;&#x2020;đ?&#x2018;&#x20AC;đ??š đ?&#x2018;&#x20AC;đ??š = 0.92 đ?&#x2018;Ľ 1.0 đ?&#x2018;Ľ 0.81 đ?&#x2018;Ľ 0.82 đ?&#x2018;&#x20AC;đ??š = 0.61 Fluorescent lamps with 2 bulbs, 3500 x 2 = 7000 lumen (F) đ??¸đ?&#x2018;Ľđ??´ đ?&#x2018; = đ??š đ?&#x2018;Ľ đ?&#x2018;&#x2C6;đ??š đ?&#x2018;Ľ đ?&#x2018;&#x20AC;đ??š đ?&#x2018; =
300 đ?&#x2018;Ľ 132.28 7000 đ?&#x2018;Ľ 0.4 đ?&#x2018;Ľ 0.61
đ?&#x2018; = 23 23 luminaries are needed to reach the minimum requirement for MS1525 = 300 lux Spacing to height ratio (SHR) đ?&#x2018;&#x2020;đ??ťđ?&#x2018;&#x2026; =
đ?&#x2018;&#x2020;đ??ťđ?&#x2018;&#x2026; =
1 đ??´ đ?&#x2018;Ľâ&#x2C6;&#x161; đ??ťđ?&#x2018;&#x161; đ?&#x2018;
1 132.28 đ?&#x2018;Ľâ&#x2C6;&#x161; 3.5 23 = 0.69
đ?&#x2018;&#x2020;đ??ťđ?&#x2018;&#x2026; =
đ?&#x2018;&#x2020; = 0.69 3.5
đ?&#x2018;&#x2020; = 3.5 đ?&#x2018;Ľ 0.69 = 2.42 Approximate fittings layout/m
Fittings required along 18.5 m wall; 18.5 á 2.42 = 7.64 = 8 rows
Page | 14
CHEAH HOONG FEI (0311690) BUILDING SCIENCE 2
Therefore, approximately 8 x 3 = 24 luminaries required; Spacing along 7.15 m wall; 7.15 / 3 = 2.38 m Final layout
Figure: Fittings layout for multipurpose room
Figure: Artificial lighting contour diagram for multipurpose room
Conclusion 24 fluorescent lamps are used to achieve minimum of 300 lux for this area according to MS1525. The whole floor area is well illuminated so that performance is not weakened due to poor lighting and comfort.
Page | 15
CHEAH HOONG FEI (0311690) BUILDING SCIENCE 2
Table: Typical lumen maintenance and lamp survival data. (Source: SSL code for lighting, 2013)
Table: Luminaire categories and a list of typical locations where the various environmental conditions may be found (Source: SSL code for lighting, 2013)
Page | 16
CHEAH HOONG FEI (0311690) BUILDING SCIENCE 2
Table: Typical changes in light output from a luminaire caused by dirt deposition, for a number of luminaire and environment categories. (Source: SSL code for lighting, 2013)
Table: Typical changes in the illuminance from an installation that occur with time due to dirt deposition on the room surfaces. (Source: SSL code for lighting, 2013)
Page | 17
CHEAH HOONG FEI (0311690) BUILDING SCIENCE 2
Table: Utilization factor (UF) value. (source: Phillips, 2015)
Page | 18
CHEAH HOONG FEI (0311690) BUILDING SCIENCE 2
1.3.1 Permanent Supplementary Artificial Lighting of Interiors (PSALI) 1.3.1 Formal study area
Figure: Formal study area- second floor plan
Page | 19
CHEAH HOONG FEI (0311690) BUILDING SCIENCE 2
Daylight Factor Calculation Floor Area (m²) Area of façade that exposed to sunlight (m²) Exposed Façade & Skylight Area to Floor Area Ratio/ Daylight Factor, DF
52.8 67.08 [(67.08) ÷ 52.8] = 1.27 = 127% x 0.1 = 12.7%
Natural Illumination Calculation
E external = 20,000 lx DF = (Ei/Eo) x 100% DF
= 12.7 x 20 000 / 100 = 2540 lux
Conclusion The formal study area has a daylight factor of 12.7% and natural illumination of 2540 lux. According to MS 1525, illumination level for a study area is 400. This will cause thermal and glare problem. Hence, adjustable shading device is implemented to solve the glare problem and also to reduce the heat gain in this area.
Artificial lighting According to MS 1525, the minimum lighting level required for a formal study area is 400. Type of luminaire used as showed below: Type of fixture Type of light bulb
Fluorescent tube with reflector
Page | 20
CHEAH HOONG FEI (0311690) BUILDING SCIENCE 2
Material of fixture Product Brand & Code Nominal Life (Hours) Wattage Range (W) CRI Colour Temperature (K) Colour Designation Lumens
Aluminium F39W/TS/830/ECO 36,000 39 85 3000 Warm white 3500
Material
Function
Colour
Area (m²) 52.5
Surface Type Reflective
Reflectance Value 0.30
Concrete finish Glass Timber Concrete Timber flooring
Ceiling
Grey
Wall Wall frame Wall Floor
Transparent Brown Grey Brown
58.56 8.52 79.36 52.8
Absorptive Absorptive Reflective Absorptive
0.10 0.14 0.30 0.14
Lumen method and calculation for Formal study area room (from 1.5m height) Location Dimension
Area (A) Luminaries height Mounting height (Hm) Recommended average illumination levels by MS 1525 (E) Reflectance value Room index
Formal study room Length (L) = 16m Width (W) = 3.3m Height of the ceiling = 4.3m L x W = 16 x 3.3 = 52.5m² 4.3m 4.3 â&#x20AC;&#x201C; 0.8 = 3.5m 400 lux Ceiling: 0.3, Floor: 0.14, Wall: 0.54 đ??żđ?&#x2018;Ľđ?&#x2018;&#x160; 16 đ?&#x2018;Ľ 3.3 = (đ??ż + đ?&#x2018;&#x160;)đ??ťđ?&#x2018;&#x161; (16 + 3.3)3.5 = 0.78
Utilisation factor Maintenance factor
From table, UF = 0.3 Luminaire category = C (closed top reflector)
Time between cleaning (years) = 1
Type of light
đ?&#x2018;&#x20AC;đ??š = đ??żđ??żđ?&#x2018;&#x20AC;đ??š đ?&#x2018;Ľ đ??żđ?&#x2018;&#x2020;đ??š đ?&#x2018;Ľ đ??żđ?&#x2018;&#x20AC;đ??š đ?&#x2018;Ľ đ?&#x2018;&#x2026;đ?&#x2018;&#x2020;đ?&#x2018;&#x20AC;đ??š đ?&#x2018;&#x20AC;đ??š = 0.92 đ?&#x2018;Ľ 1.0 đ?&#x2018;Ľ 0.81 đ?&#x2018;Ľ 0.82 đ?&#x2018;&#x20AC;đ??š = 0.61 Fluorescent lamps with 2 bulbs, 3500 x 2 = 7000 lumen (F) Page | 21
CHEAH HOONG FEI (0311690) BUILDING SCIENCE 2
Number of light required
đ?&#x2018; = đ?&#x2018; =
đ??¸đ?&#x2018;Ľđ??´ đ??š đ?&#x2018;Ľ đ?&#x2018;&#x2C6;đ??š đ?&#x2018;Ľ đ?&#x2018;&#x20AC;đ??š
400 đ?&#x2018;Ľ 52.5 7000 đ?&#x2018;Ľ 0.3 đ?&#x2018;Ľ 0.61
đ?&#x2018; = 16 16 luminaries are needed to reach the minimum requirement for MS1525 = 400 lux Spacing to height ratio (SHR) đ?&#x2018;&#x2020;đ??ťđ?&#x2018;&#x2026; =
đ?&#x2018;&#x2020;đ??ťđ?&#x2018;&#x2026; =
1 đ??´ đ?&#x2018;Ľâ&#x2C6;&#x161; đ??ťđ?&#x2018;&#x161; đ?&#x2018; 1 52.5 đ?&#x2018;Ľâ&#x2C6;&#x161; 3.5 16
= 0.52 đ?&#x2018;&#x2020;đ??ťđ?&#x2018;&#x2026; =
đ?&#x2018;&#x2020; = 0.52 3.5
đ?&#x2018;&#x2020; = 3.5 đ?&#x2018;Ľ 0.52 = 1.82 Approximate fittings layout/m
Fittings required along 16 m wall; 16 á 1.82 = 8.79 = 9 rows Therefore, approximately 9 x 2 = 18 luminaries required; Spacing along 3.3 m wall; 3.3 / 2 = 1.65 m
Page | 22
CHEAH HOONG FEI (0311690) BUILDING SCIENCE 2
Final layout
Figure: Fittings layout for formal study area
Figure: PSALI contour diagram for formal study area
Conclusion 18 fluorescent lamps are used to illuminate the formal study area to achieve the minimum of 400 lux stated by MS 1525. With sufficient level of illumination, the users can enjoy reading in a comfortable environment. This area is supplemented by the natural lighting which hence will switch from artificial lighting use to the natural one.
Page | 23
CHEAH HOONG FEI (0311690) BUILDING SCIENCE 2
2.0 Acoustics 2.1 External Noise (Sound Pressure Level) 2.1.1 Cafe Noise source:
Figure: CafĂŠ- ground floor plan
a) Back alley (wet market)
= 60 dB 60
= 10log (l1 / l0)
Antilog 6
= [l1 / (1.0 x 10-12)]
1 x 106
= [l1 / (1.0 x 10-12)]
l1
b) Public space
= 1.0 x 10-6
= 65 dB 65
= 10log (l1 / l0)
Antilog 6.5
= [l1 / (1.0 x 10-12)]
3.16 x 106
= [l1 / (1.0 x 10-12)]
l1
= 3.16 x 10-6 Page | 24
CHEAH HOONG FEI (0311690) BUILDING SCIENCE 2
Total intensities, I
= (1.0 x 10-6) + (3.16 x 10-6) = 4.16 x 10-6
Combined SPL
= 10log (l1 / l0) = 10log [(4.16 x 10-6) / (1.0 x 10-12)] = 66 dB
Conclusion The noise criteria for café is within the range of NC-45-NC-50 (medium loud). The combined SPL of the wet market and public space surrounding the café = 66dB, exceeds the noise criteria for the café, making discussions communications not possible. To reduce the noise produced by the street and market, green wall and the sound transmitting properties of the facades of the café need to be considered so as to mask the exterior noise.
Note Vegetated facades reduce noise from all sourced situated outside the café, act as sound barrier walls reflect and deflect noise.
Page | 25
CHEAH HOONG FEI (0311690) BUILDING SCIENCE 2
2.1.2 Informal study area
Figure: Informal study area- first floor plan
Noise source: a) Busy traffic noise
= 70 dB 70
= 10log (l1 / l0)
Antilog 7
= [l1 / (1.0 x 10-12)]
1 x 107
= [l1 / (1.0 x 10-12)]
l1
b) Corridors
= 1.0 x 10-5
= 65 dB 65
= 10log (l1 / l0)
Antilog 6.5
= [l1 / (1.0 x 10-12)]
3.16 x 106
= [l1 / (1.0 x 10-12)]
l1
= 3.16 x 10-6
Page | 26
CHEAH HOONG FEI (0311690) BUILDING SCIENCE 2
Total intensities, l
= (1.0 x 10-5) + (3.16 x 10-6) = 1.32 x 10-5
Combined SPL
= 10log (l1 / l0) = 10log [(1.32 x 10-5) / (1.0 x 10-12)] = 71 dB
Conclusion The noise criteria for a study area is within the range of NC-35 – NC- 40. The combined SPL of the traffic noise and the corridors surrounding the study area = 71dB, exceeds the noise criteria for the children’s area, making discussion and learning hardly possible. Design strategies such as design a courtyard which acts as buffer zone and double façade to filter and deflect noise.
Note 1. Shrubs- Have thick, waxy leaves, dense evergreen foliage and branches to filter the noise when it is transmitted into the buildings 2. Trees- Plantings of two staggered rows where space allowed to provide visual screening, it is more efficient to reduce noise. 3. Double skin- The cavity of the double skin façade is only ventilated to the outside and is built to reduce noise.
Page | 27
CHEAH HOONG FEI (0311690) BUILDING SCIENCE 2
2.2 Reverberation time, RT
Page | 28
CHEAH HOONG FEI (0311690) BUILDING SCIENCE 2
Table: Sound absorption coefficient
Page | 29
CHEAH HOONG FEI (0311690) BUILDING SCIENCE 2
2.2.1 Multipurpose room
Figure: Multipurpose room- third floor plan
Component
Material
Wall Floor Ceiling People peak
Surface area/m² [A] or quantity Plaster wall (7.1+14.3+7.1) x 4.5= 128.25 Carpet 7.1 x 14.3= 101.53 Concrete 101.53 35 Total absorption [A]
Absorption coefficient [S] (500 Hz) 0.06
Sound absorption [SA]
0.14
14.20
0.30 0.5
30.42 17.50 69.82
7.70
Volume = area of the room x height = 101.53 x 4.5 = 456.89 máľ&#x152;
RT
đ?&#x2018;&#x2030;
= 0.16 đ??´ = 0.16 x
456.89 69.82
Page | 30
CHEAH HOONG FEI (0311690) BUILDING SCIENCE 2
= 1.05 s
Conclusion The reverberation time for the multipurpose room in 500 Hz of absorption coefficient is 1.05s. According to the standards of reverberation time, the standard comfort reverberation for multipurpose room is between 1.6-1.8s. So the reverberation time of the multipurpose room on 500 Hz is within the standard comfort reverberation time.
2.2.2 Electronic laboratory
Figure: Electronic laboratory- first floor plan
Component
Material
Wall
Plaster wall
Surface area/m² [A] or quantity (3.22 + 2.6 + 2) x 4.3= 33.63
Absorption coefficient [S] (500 Hz) 0.06
Sound absorption [SA] 2.02
Page | 31
CHEAH HOONG FEI (0311690) BUILDING SCIENCE 2
Glass Floor Ceiling People peak
(10.2 + 12.2) x 4.3 = 96.32 Carpet 12 x 5.2 = 62.4 Concrete 62.4 20 Total absorption [A]
0.04
3.85
0.14 0.30 0.5
8.74 18.72 10 43.33
Volume = area of the room x height = 62.4 x 4.3 = 268.32 máľ&#x152;
RT
đ?&#x2018;&#x2030;
= 0.16 đ??´ = 0.16 x
268.32 43.33
= 0.99 s
Conclusion The reverberation time for the electronic laboratory in 500 Hz of absorption coefficient is 0.99s. According to the standards of reverberation time, the standard comfort reverberation for electronic laboratory is between 1.0 â&#x20AC;&#x201C; 1.2s. So the reverberation time of electronic laboratory on 500 Hz is within the standard comfort reverberation time.
Page | 32
CHEAH HOONG FEI (0311690) BUILDING SCIENCE 2
2.3 Sound Reduction Index (SRI)
Figure: Recommended NC level for space
Page | 33
CHEAH HOONG FEI (0311690) BUILDING SCIENCE 2
2.3.1 Café
Figure: Café- ground floor plan
The sound pressure level of café is 40 – 45dB according to MS1525 standards. Components Material
Area (m²)
Wall
Brick
Wall
Glass
Door
Glass
2.9 x 4.5= 13.05 4.3 x 4.5= 19.35 (5.8 + 5.9) x 4.5= 52.65
Sound Reduction Index (SRI) 42dB
Transmission Coefficient, T
26dB
2.51 x 10-3
26dB
2.51 x 10-3
6.31 x 10-5
Transmission coefficient of materials a) Brick (wall) SRI
= 10 log (1/T)
42
= 10 log (1/T)
Antilog 4.2
= 1/T
T
= 6.31 x 10-5 Page | 34
CHEAH HOONG FEI (0311690) BUILDING SCIENCE 2
b) Glass (wall) SRI
= 10 log (1/T)
26
= 10 log (1/T)
Antilog 2.6
= 1/T
T
= 2.51 x 10-3
c) Glass (door) SRI
= 10 log (1/T)
26
= 10 log (1/T)
Antilog 2.6
= 1/T
T
= 2.51 x 10-3
Average transmission coefficient of materials Tav
= (13.05 x 6.31 x 10-5) + (19.35 x 2.51 x 10-3) + (52.65 x 2.51 x 10-3) 13.05 + 19.35 + 52.65 = 2.26 x 10-3
Total surface reflection index, SRI SRI (overall) = 10 log (1/Tav) = 10 log (1/ 2.26 x 10-3) = 26.5dB Noise level in Café = 66dB – 26.5dB = 39.5dB
After transmission loss, the sound pressure level of the café is 39.5dB. According to MS1525, the standard SPL for café is 40 – 45 dB, thus the space meets the requirements.
Page | 35
CHEAH HOONG FEI (0311690) BUILDING SCIENCE 2
2.3.2 Informal study area
Figure: Informal study area- first floor plan
The sound pressure level of open plan study room is 35 – 40dB according to MS1525 standards. Components Material
Area (m²)
Wall
Brick
Window
Single laminated glass
(4.5 + 3.3 + 3.5 + 3.5) x 4.5= 66.6 12.5 x 4.5= 56.25
Sound Transmission Reduction Index Coefficient, T (SRI) 42dB 6.31 x 10-5
35dB
3.61 x 10-4
Page | 36
CHEAH HOONG FEI (0311690) BUILDING SCIENCE 2
Transmission coefficient of materials a) Brick (wall) SRI
= 10 log (1/T)
42
= 10 log (1/T)
Antilog 4.2
= 1/T
T
= 6.31 x 10-5
b) Single laminated glass (window) SRI
= 10 log (1/T)
35
= 10 log (1/T)
Antilog 3.5
= 1/T
T
= 3.16 x 10-4
Average transmission coefficient of materials Tav
= (66.6 x 6.31 x 10-5) + (56.25 x 3.16 x 10-4) 66.6 + 56.25 = 1.79 x 10-4
Total surface reflection index, SRI SRI (overall) = 10 log (1/Tav) = 10 log (1/ 1.79 x 10-4) = 37.5dB Noise level in Informal study area = 71dB â&#x20AC;&#x201C; 37.5dB = 33.5dB The transmission loss from the front and back street is 37.5dB. After transmission loss, the sound pressure level of the informal study area is 33.5dB. According to MS1525, the standard SPL for open study area is 35 â&#x20AC;&#x201C; 40 dB, thus it meets the requirements.
Page | 37
CHEAH HOONG FEI (0311690) BUILDING SCIENCE 2
4.0 References 1. Architectsâ&#x20AC;&#x2122; Data. (2012). Chicester: John Wiley and Sons. 2. ASHRAE. (1995). ASHRAE handbook 1984 systems. Atlanta, GA: American Society Heating, Refrigerating &. 3. In Gibbs, B., In Goodchild, J., In Hopkins, C., & In Oldham, D. (2010). Collected Papers in Building Acoustics: Room Acoustics and Environmental Noise. Brentwood, Essex: Multi-Science Publishing Co. Ltd. 4. Malaysia. (2007). Code of practice on energy efficiency and use of renewable energy for non-residential buildings (first revision). Putrajaya: Department of Standard Malaysia. 5. Sound Absorption Coefficients of architectural acoustical materials. (1957). New York.
Page | 38