Knauf Metal Furring (MF) Suspended Ceiling Membranes
Appendix
The 100% Knauf System Performance Warranty
Amendment table
For further information on these amendments, please contact our Technical Services via email; technical-uk@knauf.com or call 0800 521050 (option 2).
001 New publication launch: Knauf EN System Performance Tables (September 2023).
002 Document Title: Knauf EN System Performance Tables. 1. Removal of system: P-C-92-1x15-SSP-50. New system added as replacement: P-C-92-1x15-SSP-25 (page 8).
003 Document Title: Knauf EN System Performance Tables. 1. Change of sound insulation performance of P-CRB1-70-2x15-SSP-50. Acoustic change from 53 to 55dB Rw +Ctr (dB) and 59 to 60dB (Rw) (page 11).
004 Document Title: Knauf EN System Performance Tables. 1. Adjustment in height (mm) for systems
|
| P-C-146-1x15-SSP-25 | P-C-146-2x15-SSP-25. 5000mm to 4000mm (page 8). 13.11.23
005 Document Title: Knauf EN System Performance Tables. 1. Adjustment in height (mm)
006 1. Development of new layout of document - Knauf EN System Performance Tables September 2023 to Knauf EN Compliance Systems (April 2024).
008 1. Admendment table added (page 3). 2. Updated Table Header Definitions (page 6). 3. Additional Knauf Isolator System - Double 50 'C' (0.55) Stud (page 15) 4. New system category added: Framed Encasement System - Fire Panel (pages 22-25). 5. Additional MF Suspsended Ceiling Membranes - 12.5mm | 15mm Solutions using Wallboard, Moisture Panel, Soundshield Plus (page 26). New tone added throughtout document.
009 Added: 1. New System Category: Knauf Horizontal Shaftwall – Ceiling System (Page 19). 2. Performer System: 12.5mm Knauf Wallboard with Knauf Insulation 25mm Acoustic Roll solutions, 50 ‘C’, 70 ‘C’, 92 ‘C’, 146 ‘C’ fire performance change from 'NA' to '30' (page 8). 3. 2 x 15mm Knauf Performance Plus with Knauf Insulation 25mm Acoustic Roll solutions, 70 ‘C’, 92 ‘C’, 146 ‘C’ acoustic sound insulation change from '52' to '54'. 4. 1 x 15mm Knauf Soundshield Plus with Knauf Insulation 25mm Acoustic Roll solutions, 70 ‘C’, 92 ‘C’, 146 ‘C’ acoustic sound insulation change from '45' to '47' (page 11). 5. 2 x 15mm Knauf Soundshield Plus with Knauf Insulation 25mm Acoustic Roll solutions, 70 ‘C’, 92 ‘C’, 146 ‘C’ acoustic sound insulation change from '52' to '55' (page 11). 6. Knauf Isolator Systems – new format designated as unbraced and braced solutions with system code updates and braced acoustic note (Pages 15 | 16). 7. Added – New 100% Knauf System Performance Warranty Page (Page 30). 8. Note: Contents page reflected. Added - Month and revision to front cover (page 1).
01.10.24 MB
System Finder - Request For EN or BS compliance systems
Testing Methodology: BS EN 1363-1 AND BS 476-20
• Knauf interior drywall partition systems* that achieve a fire resistance performance are tested in accordance with BS EN 1363-1 and BS EN 1364-1. These are the up to date and most rigorous test methodology standards to follow.
• Determining the maximum height of a drywall partition as per the BS EN 1363-1 fire test methodology, is typically restricted by the 3 metre height of the test furnace.
• To understand the true maximum height of the system whilst under fire test conditions (‘Fire State Height’), there are three options. Increases can be determined by utilising greater test furnace heights, via Extended Field of Application (as outlined in BS EN 15254-3 - it is important to note this standard applies to single metal frame symmetrical systems only), or via BS EN 1364-1.
• The BS 476-20 standard is also restricted by the 3 metre height of the test furnace. However, under this BS standard, increasing the maximum heights of a system can be based on the ‘Cold State Height’. The cold state height is calculated using structural engineering methods to L/240 @ 200Pascals. (L = Height of wall).
Regulatory Requirements
• Specific to Approved Document B (England) there is a requirement to use European classifications and fire resistance test methodologies in accordance with BS EN 1363-1 and BS EN 1364-1, which means that the fire state height must be considered. However, Approved Document B (England) currently allows the usage of the BS 476 series, though it should be noted that, following consultation, the full BS 476 series will be removed in 2029. For other nationals, please consult relevant approved documents, technical guidance, and handbooks.
Knauf Approach & Recommendations
• Knauf advise and promote that EN compliance should be followed. That is to say Knauf advise utilising an EN 1364-1 fire resistance test and extend the maximum height of a drywall partition system via either BS EN 15254-3, BS EN 1364-1 or via a fire resistance test within a test rig greater than 3m in height.
• Projects that wish to use the BS 476 series must gain agreement between the Client, Accountable Persons, Duty Holders, and Local Building Control that the cold state height is an acceptable methodology.
For further information on Knauf system types that are applicable to support projects focusing on EN compliance, refer to Knauf EN Compliance Systems document, available at Compliance-documents or contact Knauf Technical Services – technical-uk@knauf.com or via telephone 0800 521050 (option 2).
*Performer (Partitions), Performer (Partitions with Resilient Bar), Isolator (Twin Frame), Shaftwall, Smokeshaft and Independent ‘I’ Stud Lining.
When choosing your Knauf systems please also refer to Knauf Fire Rated Deflection Heads document
An introduction to Knauf Drywall Systems
Knauf Performer Partition and Knauf Performer Hybrid Partition
The Knauf Performer system is our most versatile and commonly used partition system. It is constructed using a single row of Knauf metal studs with Knauf plasterboards to both sides in order to meet fire, acoustic, moisture and impact requirements. The Performer system is lightweight, simple to construct and should be used in conjunction with Knauf’s finishing solutions range.
Knauf Performer Partition with Knauf Resilient Bar
Knauf Resilient Bar can be added to both or one side of certain Knauf Performer systems. This additional component improves the acoustic sound reduction performance of the system in order to meet higher acoustic requirements.
The Knauf Isolator system is typically used to divide habitable dwellings. The twin stud build up, combined with Knauf’s high performance plasterboards, maximises acoustic performance in order to comply with building regulations, technical handbooks and guidances for sound insulation.
Knauf Shaftwall
Knauf Shaftwall is our innovative system to form enclosures around service and lift shafts while working from one side. The unique Knauf ‘CT’ Stud makes this possible with a minimum of components. The system can provide a high level of fire resistance performance to meet the requirements of your project.
Knauf Horizontal Shaftwall - Ceiling System
Knauf Horizontal Shaftwall - Ceiling System is our innovative, non-loadbearing independent ceiling system (membrane) providing fire resistance from below and or from above. The unique arrangement allows the system to be built from one side.
Knauf Smokeshaft
Knauf Smokeshaft is a system to be used when an A1 fire classification board (in accordance with BS EN 13501-1) is required to line a shaft.
Knauf ‘I’ Stud Linings
Knauf Independent ‘I’ Stud is a fully independent wall lining system that can be used in all building types to upgrade the acoustic, fire and thermal performance of an existing masonry wall and to deal with any irregularities. Due do the system using an Knauf ‘I’ Stud, there is no requirement for the lining system to be fixed back into the structure behind.
Knauf AQUAPANEL® Cement Board Indoor Board
/ Interior System
Knauf AQUAPANEL® Cement Board Indoor is exceptionally tough and durable, providing a solid tile backing substrate for wet indoor areas such as swimming pools, leisure centres, bathrooms and kitchens. The board is used in conjunction with specialist screws and finishing products to provide a full Knauf solution for humid and wet conditions.
Knauf Framed Encasement System – Fire Panel
Knauf Framed Encasement System is a specialist fire protection encasement system designed to protect loadbearing universal beams and or columns. The use of Knauf Fire Panel plasterboard and specialist encasement Knauf components provide a simple and easy to install system.
Knauf Metal Furring (MF) Suspended Ceiling System
The Knauf Metal Furring (MF) Suspended Ceiling system is versatile and easy to install. Deep voids are easily created to hide services and the ceiling can be used to provide fire protection to the soffit above. The Knauf MF Suspended Ceiling system is very familiar to contractors who will easily be able to form openings, bulkheads and coffers.
Table Header Definitions
The number of layers Knauf plasterboard fixed to either side of Knauf metal stud frame Knauf plasterboard/ board type
System width (in mm) which excludes finishes
The system code is a unique code that allows for easy reference if enquiring about a system.
EN-PC-50-055-6-1-12.5-WB-0
EN This is the standard in which this is accepted
PC System name (Performer) and stud type (C)
50 Stud Depth 50 (mm)
055 Stud Gauge 0.55 (mm)
6 Stud centres, 6= 600, 4= 400 and 3=300 (mm)
1 Layers of plasterboard on either side
15 Thickness of each individual board
WB Plasterboard type (Wallboard)
0 Thickness in mm of insulation in cavity
Acoustic Sound Insulation of system in measured in dB(Rw). Refer to appendix for test methodology.
Knauf metal component information providing size and gauge
Thickness of Knauf plasterboard/ board
Thickness of insulation used within Knauf metal stud frame. Refer to tables for information of Knauf Insulation type.
Partition Height
Fire resistance period of system in minutes. Refer to appendix for test methodology
Knauf Perfomer Partitions – Isometrics
–
‘C’ Stud Partition – Soundshield Plus
Stud Partition –
Performer ‘C’ Stud Partition – Performance Plus
Stud Partition – Fire Panel
Click on typical system image to view performance details.
Refer to appendix for further information on performance of Performer partitions.
Knauf Performer ‘C’ Stud Partition
Wallboard
Knauf Performer ‘C’
Moisture Panel
Knauf Performer ‘C’
Knauf Performer
Knauf
Knauf Performer ‘C’ Stud Partitions – Wallboard
Performance tables
For further information on Knauf system performances, details and guidance on installation, please contact our Technical Services via email; technical-uk@knauf.com or call
521050 (option 2).
2
1
2
2
2
Insulation Acoustic Roll
For superscripts; 1,2 and 3, please refer to the appendix on page 29 for further information.
Note: Systems designed to accommodate up to -25mm or +/-12.5mm deflection allowance. Please refer to Knauf Fire Rated Deflection Head document for detailed information on design and specification.
For further information on Knauf system performances, details and guidance on installation, please contact our Technical Services via email; technical-uk@knauf.com or call 0800 521050 (option 2).
'C'
2
1 12.5 Moisture Panel 0 97
1
1 15 Moisture Panel 0 102
1 15 Moisture Panel 25 102
2 12.5 Moisture Panel 0 122
2 12.5 Moisture Panel 25 122
2 15 Moisture Panel 0 132
2 15 Moisture Panel
1
1
1
2
2
2
2
*Knauf Insulation Acoustic Roll
For superscripts; 1,2 and 3, please refer to the appendix on page 29 for further information. Note: Systems designed to accommodate up to -25mm or +/-12.5mm deflection allowance. Please refer to Knauf Fire Rated Deflection Head document for detailed information on design and specification.
Knauf Performer ‘C’ Stud Partitions – Fire Panel
Performance tables
For further information on Knauf system performances, details and guidance on installation, please contact our Technical Services via email; technical-uk@knauf.com or call 0800 521050 (option 2).
2
2 12.5 Fire
2
2
2
1
2
2
*Knauf Insulation Acoustic Roll
For superscripts; 1,2 and 3, please refer to the appendix on page 29 for further information.
Note: Systems designed to accommodate up to -25mm or +/-12.5mm deflection allowance. Please refer to Knauf Fire Rated Deflection Head document for detailed information on design and specification.
Knauf Performer ‘C’ Stud Partitions – Soundshield Plus
Performance tables
For further information on Knauf system performances, details and guidance on installation, please contact our Technical Services via email; technical-uk@knauf.com or call 0800 521050 (option 2).
2
2 12.5
2
2 15 Soundshield Plus 0 132
2
1
1
2
2
1
1 15
2
2
2
2
2
*Knauf Insulation Acoustic Roll
For superscripts; 1,2 and 3, please refer to the appendix on page 29 for further information. Note: Systems designed to accommodate up to -25mm or +/-12.5mm deflection allowance. Please refer to Knauf Fire Rated Deflection Head document for detailed information on design and specification.
Knauf Performer ‘C’ Stud Partitions – Performance Plus
Performance tables
For further information on Knauf system performances, details and guidance on installation, please contact our Technical Services via email; technical-uk@knauf.com or call 0800 521050 (option 2).
2
1
1
2
2
2
2
2
*Knauf Insulation Acoustic Roll
For superscripts; 1,2 and 3, please refer to the appendix on page 29 for further information.
Note: Systems designed to accommodate up to -25mm or +/-12.5mm deflection allowance. Please refer to Knauf Fire Rated Deflection Head document for detailed information on design and specification.
Knauf Performer ‘C’ Stud Partitions – Hybrid
Performance tables
For further information on Knauf system performances, details and guidance on installation, please contact our Technical Services via email; technical-uk@knauf.com or call 0800 521050 (option 2).
Insulation Acoustic Roll
For superscripts; 1,2 and 3, please refer to the appendix on page 29 for further information. Note: Systems designed to accommodate up to -25mm or +/-12.5mm deflection allowance. Please refer to Knauf Fire Rated Deflection Head document for detailed information on design and specification.
Knauf Performer Partition with Knauf Resilient Bar
Performance tables
For further information on Knauf system performances, details and guidance on installation, please contact our Technical Services via email; technical-uk@knauf.com or call 0800 521050 (option 2).
*Knauf Insulation Acoustic Roll
Superscripts:
1. The maximum height stated is the lower value between the cold state height, calculated structurally to limiting deflection of L/240 @ 200Pa and the fire state height, as outlined in accordance with BS EN 1364-1.
2. Fire resistance period
Tested in accordance with BS EN 1364-1.
Fire resistance period is inclusive of both fire integrity and fire insulation. Fire resistance performance must be reviewed against Knauf specifications, standard details, with inclusion of deflection head arrangement.
3. Acoustic sound insulation
Tested or assessed in accordance with BS EN ISO 10140-1 & BS EN ISO 10140-2.
Acoustic sound insulation performance based on studs at 600mm centres only and non-deflection head arrangement.
Note 1. System that require fire resistance and/or acoustic sound insulation performance must have all outer joints taped and filled in accordance with Knauf recommendations. Systems are tested as imperforate.
Note 2. Systems designed to accommodate up to -25mm or +/-12.5mm deflection allowance. Please refer to Knauf Fire Rated Deflection Head document for detailed information on design and specification.
Isometric of Knauf Performer with Knauf Resilient Bar
Knauf Isolator (Twin Frame) Partitions - Unbraced
Performance tables
For further information on Knauf system performances, details and guidance on installation, please contact our Technical Services via email; technical-uk@knauf.com or call 0800 521050 (option 2).
Plasterboard
Knauf
System Code & Maximum height1 (mm) @
EN-IC-70-055-6-2x15-SSP-2x25(229/60) 3000
System Code & Maximum height1 (mm) @ 400mm centres
EN-IC-70-055-4-2x15-SSP-2x25(229/60) 3000
System Code & Maximum height1 (mm) @ 300mm centres
EN-IC-70-055-3-2x15-SSP-2x25(229/60) 3000
Code & Maximum height1 (mm) @ 600mm centres
EN-IC-70-055-6-2x15-SSP-2x25(229/90) 3000
System Code & Maximum height1 (mm) @ 400mm centres
EN-IC-70-055-4-2x15-SSP-2x25(229/90) 3000
System Code & Maximum height1 (mm) @ 300mm centres
EN-IC-70-055-3-2x15-SSP-2x25(229/90) 3000
System Code & Maximum height1 (mm) @ 600mm centres
EN-IC-70-055-6-2x15-SSP-2x25(229/120) 3000
System Code & Maximum height1 (mm) @ 400mm centres
EN-IC-70-055-4-2x15-SSP-2x25(229/120) 3000
System Code & Maximum height1 (mm) @ 300mm centres
EN-IC-70-055-3-2x15-SSP-2x25(229/120) 3000
*Knauf Insulation Acoustic Roll
** Bracing using Knauf Flat Plate at 1500mm centres
† System fire resistance tested with the inclusion of baffle boxes
For superscripts; 1,2 and 3, please refer to the appendix on page 29 for further information. Note: Systems designed to accommodate up to -25mm or +/-12.5mm deflection allowance. Please refer to Knauf Fire Rated Deflection Head document for detailed information on design and specification.
Knauf Isolator (Twin Frame) Partitions - Braced
Performance tables
For further information on Knauf system performances, details and guidance on installation, please contact our Technical Services via email; technical-uk@knauf.com or call 0800 521050 (option 2).
System Code & Maximum height1 (mm) @ 600mm centres
EN-ICB-50-055-6-2x15-SSP-2x25(170/90) 4000
System Code & Maximum height1 (mm) @ 400mm centres
EN-ICB-50-055-4-2x15-SSP-2x25(170/90) 4000
System Code & Maximum height1 (mm) @ 300mm centres
EN-ICB-50-055-3-2x15-SSP-2x25(170/90) 4000
*Knauf Insulation Acoustic Roll
** Bracing using Knauf Flat Plate at 1500mm centres
For superscripts; 1,2 and 3, please refer to the appendix on page 29 for further information.
Note: Systems designed to accommodate up to -25mm or +/-12.5mm deflection allowance. Please refer to Knauf Fire Rated Deflection Head document for detailed information on design and specification.
For further information on Knauf system performances, details and guidance on installation, please contact our Technical Services via email; technical-uk@knauf.com or call 0800 521050 (option 2).
*Knauf Insulation Acoustic Roll
** Bracing using Knauf Flat Plate at 1500mm centres
EN-IC-70-055-6-2x15-SSP-2x15-PP-2x25(229/60) 3000
System Code & Maximum height1 (mm) @ 400mm centres
EN-IC-70-055-4-2x15-SSP-2x15-PP-2x25(229/60) 3000
System Code & Maximum height1 (mm) @ 300mm centres
EN-IC-70-055-3-2x15-SSP-2x15-PP-2x25(229/60) 3000
EN-IC-70-055-6-2x15-SSP-2x15-PP-2x25(229/90) 3000
System Code & Maximum height1 (mm) @ 400mm centres
EN-IC-70-055-4-2x15-SSP-2x15-PP-2x25(229/90) 3000
System Code & Maximum height1 (mm) @ 300mm centres
EN-IC-70-055-3-2x15-SSP-2x15-PP-2x25(229/90) 3000
For superscripts; 1,2 and 3, please refer to the appendix on page 29 for further information. Note: Systems designed to accommodate up to -25mm or +/-12.5mm deflection allowance. Please refer to Knauf Fire Rated Deflection Head document for detailed information on design and specification.
Knauf Shaftwall
Performance tables
For further information on Knauf system performances, details and guidance on installation, please contact our Technical Services via email; technical-uk@knauf.com or call 0800 521050 (option 2).
*Knauf Insulation Acoustic Roll
Superscripts:
1. The maximum height for all Knauf Shaftwall systems follows the requirements as outlined within EN 1364-1 and DIAP (Direct Field of Application).
The stated maximum height figure is the lower value between the cold state height, calculated structurally to a limiting deflection of L/240 @ 200Pa and the fire state height, as outlined in accordance with EN 1364-1 and DIAP (Direct Field of Application).
2. Fire resistance period
Tested in accordance with BS EN 1364-1.
Fire resistance period is inclusive of both fire integrity and fire insulation.
Fire resistance performance must be reviewed against Knauf specifications, standard details, with inclusion of deflection head arrangement.
3. Acoustic sound insulation
Tested or assessed in accordance with BS EN ISO 10140-1 & BS EN ISO 10140-2.
Acoustic sound insulation performance based on studs at 600mm centres only and non-deflection head arrangement. Systems that denote N/A indicate that system has not been acoustically tested.
Note 1. System that require fire resistance and/or acoustic sound insulation performance must have all outer joints taped and filled in accordance with Knauf recommendations. Systems are tested as imperforate.
Note 2. Systems designed to accommodate up to -25mm or +/-12.5mm deflection allowance. Please refer to Knauf Fire Rated Deflection Head document for detailed information on design and specification.
Isometric of Knauf Shaftwall
Knauf Horizontal Shaftwall - Ceiling System
Performance tables
For further information on Knauf system performances, details and guidance on installation, please contact our Technical Services via email; technical-uk@knauf.com or call 0800 521050 (option 2).
*Knauf Insulation Rocksilk® RS60
† System performance stated is based on directions from below to above and above to below
Superscripts:
1. Fire resistance period
Tested in accordance with BS EN 1364-2.
Fire resistance period is inclusive of both fire integrity and fire insulation.
Fire resistance performance must be reviewed against Knauf specifications and standard details.
Note 1. System that require fire resistance and/or acoustic sound insulation performance must have all outer joints taped and filled in accordance with Knauf recommendations. Systems are tested as imperforate.
Note 2: For substrate fixings, approved fixings are required to meet performance constraint. Site design team to agree the suitability of design and method of installation suitability for the project.
Section view of Knauf Horizontal Shaftwall
Knauf Smokeshaft
Performance tables
For further information on Knauf system performances, details and guidance on installation, please contact our Technical Services via email; technical-uk@knauf.com or call 0800 521050 (option 2).
*Knauf Insulation Acoustic Roll
Superscripts:
1. The maximum height stated is the lower value between the cold state height, calculated structurally to a limiting deflection of L/240 @ 200Pa and the fire state height, as outlined in accordance within BS EN 1364-1 and DIAP (Direct Field of Application).
2. Fire resistance period
Tested in accordance with BS EN 1364-1.
Fire resistance period is inclusive of both fire integrity and fire insulation.
Fire resistance performance must be reviewed against Knauf specifications, standard details, with inclusion of deflection head arrangement.
3. Acoustic sound insulation
Tested or assessed in accordance with BS EN ISO 10140-1 & BS EN ISO 10140-2.
Acoustic sound insulation performance based on studs at 600mm centres only and non-deflection head arrangement.
Note 1. System that require fire resistance and/or acoustic sound insulation performance must have all outer joints taped and filled in accordance with Knauf recommendations. Systems are tested as imperforate.
Note 2. Systems designed to accommodate up to -25mm or +/-12.5mm deflection allowance. Please refer to Knauf Fire Rated Deflection Head document for detailed information on design and specification.
Note 3. System has not been tested in accordance with BS EN 1366-8:2004. If your project requires conformity to this standard, use an alternative approved construction type.
For further information on Knauf system performances, details and guidance on installation, please contact our Technical Services via email; technical-uk@knauf.com or call 0800 521050 (option 2).
*Knauf Insulation Rocksilk® RS60
Superscripts:
1. The maximum height stated is the lower value between the cold state height, calculated structurally to a limiting deflection of L/240 @ 200Pa and the fire state height, as outlined in accordance within BS EN 1364-1 and DIAP (Direct Field of Application).
2. Fire resistance period
Tested in accordance with BS EN 1364-1.
Fire resistance period is inclusive of both fire integrity and fire insulation. Fire resistance performance must be reviewed against Knauf specifications, standard details, with inclusion of deflection head arrangement.
3. Acoustic sound insulation
Tested or assessed in accordance with BS EN ISO 10140-1 & BS EN ISO 10140-2.
Acoustic sound insulation performance based on studs at 600mm centres only and non-deflection head arrangement. Systems that denote N/A indicate that system has not been acoustically tested.
Note 1. System that require fire resistance and/or acoustic sound insulation performance must have all outer joints taped and filled in accordance with Knauf recommendations. Systems are tested as imperforate.
Note 2. Systems designed to accommodate up to -25mm or +/-12.5mm deflection allowance. Please refer to Knauf Fire Rated Deflection Head document for detailed information on design and specification.
For further information on Knauf system performances, details and guidance on installation, please contact our Technical Services via email; technical-uk@knauf.com or call 0800 521050 (option 2).
1
*Various Knauf plasterboards can be used for such system arrangement.
**The maximum height stated is the cold state height of the systems, calculated structurally to limiting deflection of L/240 @ 200Pa.
Knauf AQUAPANEL® Interior System
Performance tables
For further information on Knauf system performances, details and guidance on installation, please contact our Technical Services via email; technical-uk@knauf.com or call 0800 521050 (option 2).
System Code & Maximum height1 (mm) @ 400mm centres
EN-PAC-70-060-4-1-12.5-AQP-25 3300
System Code & Maximum height1 (mm) @ 300mm centres
EN-PAC-70-060-3-1-12.5-AQP-25 3600
*Knauf Insulation Acoustic Roll
Superscripts:
1. The maximum height stated is the lower value between the cold state height, calculated structurally to a limiting deflection of L/500 @ 200Pa and the fire state height, as outlined in accordance within BS EN 1364-1 and BS EN 15254-3.
2. Fire resistance period
Tested in accordance with EN 1364-1. Fire resistance period is inclusive of both fire integrity and fire insulation. Fire resistance performance must be reviewed against Knauf specifications, standard details, with inclusion of deflection head arrangement.
3. Acoustic sound insulation
Tested or assessed in accordance with BS EN ISO 10140-1 & BS EN ISO 10140-2.
Acoustic sound insulation performance based on studs at 600mm centres only and non-deflection head arrangement. Systems that denote N/A indicate that system has not been acoustically tested.
Note 1. System that require fire resistance and/or acoustic sound insulation performance must have all outer joints taped and filled in accordance with Knauf recommendations. Systems are tested as imperforate.
Note 2. Systems designed to accommodate up to -25mm or +/-12.5mm deflection allowance. Please refer to Knauf Fire Rated Deflection Head document for detailed information on design and specification. Isometric of
Knauf Framed Encasement System – Fire Panel
The Knauf Framed Encasement System – Fire Panel can be used to protect load-bearing universal steel beams and columns for up to 120 minutes load-bearing capacity which has been tested in accordance with EN 13881-4. The system comprises of specialist Knauf metal components which are attached to the steels creating a substructure for the Knauf Fire Panel plasterboards to be fixed to using Knauf drywall screws. All plasterboard joints must be taped and filled using Knauf jointing compounds. The plasterboards can be then be treated to the desired finish.
To help specify the required thickness and number of layers of Knauf Fire Panel for universal steel beams and columns with your required fire protection it is important to understand and obtain the following:
1. What type of steels require protecting? Is it...
• Hot finished / formed structural hollow sections
This is important as it will,
• Assist in understanding the number of how many sides of the universal beams or columns are required to be protected
• Help to understand the critical design temperatures and the variable load factors, the universal beams or columns will be subject to.
Note: In accordance with A.3.2, ASFP Yellow Book – Fire Protection for structural steel in buildings 5th edition (Volume 1 of 2), guidance is given to obtain the default critical temperature from Eurocodes if you know the building type, usage area and what steels are required protecting. See Table 16. If you do not know the building occupancy, a following table 17, provides the critical temperature from the Eurocodes.
2. What is the Hp/A factor? This is a critical parameter in structural fire engineering, when assessing the fire protection requirements for structural steel beams and columns. It is representing the section factor, which relates the heated perimeter (Hp) of the steel member to its cross-sectional area (A). This ratio influences how quickly the steel member will heat up in a fire and, consequently, how much fire protection it will need. The Hp/A factor for various universal beams and columns can be found within ASFP Yellow Book – Fire Protection for structural steel in buildings 5th edition (Volume 1 of 2). This should be referenced, whilst knowing the required size, mass, depth, width and thickness within Table A.2 for UK Beams (UKB) and Table A.3 Columns (UKC).
By understanding whether it is a universal beam or column, the size, mass and dimensions of the steel it is possible to obtain the Hp/A factor by cross-reference Table A.2 and A.3.
*Tables are extracted from section A.3.2 of ASFP Yellow Book – Fire Protection for structural steel in buildings. 5th edition (Volume 1 of 2) The system has been designed to meet project requirements of BS EN 1991-1 (Eurocode).
Isometric of Knauf Framed Encasement System - Fire Panel
Table 16 - Default critical temperature from the Eurocodes (°C)*
Table 17 - Default critical temperature from the Eurocodes (°C) when the building is not known*
Knauf Framed Encasement System – Fire Panel
Table A.2
UK Beams (UKB)
Dimensions to BS4 Part 1:2005
Table A.2
UK Beams (UKB)
Dimensions to BS4 Part 1:2005 Section factor A/V(Hp/A)
Tables are extracted from Annex 4 of ASFP Yellow Book – Fire Protection for structural steel in buildings. 5th edition (Volume 1 of 2)
Knauf Framed Encasement System – Fire Panel
By knowing what steels (‘I’ and ‘H’) are required to be fire protected on your project, critical design temperatures and obtaining the Hp/A factor, dependent on size, mass and dimensions of your steels, you can specify the Knauf Framed Encasement System – Fire Panel system.
Tables A, B, and C, provide the Knauf plasterboard specification against the fire resistance period (minutes). The denoted Hp/A values stated are the maximum acceptance for the specification solutions. Therefore, any steels less than or equal to this value allows you to specify the number and layer of Knauf Fire Panel.
Let’s carry out some examples:
Example 1
You are required to provide fire protection (load-bearing capacity) of 60 minutes to a composite beam supporting a concrete slab, you know that the building occupancy is domestic, requiring critical design temperature 576°C as per Table 16 (page 22). The universal structural beam is 254 x 102 x 22 and requires 3-sided protection. By referring to Table A.2 (page 23) the Hp/A factor can be confirmed as 220.
By cross-referencing to Table A and B (critical design temperature solutions above 576 °C) it is acceptable to specify 2 x 12.5mm Knauf Fire Panel. The Hp/A value must be greater to the Hp/A value for the steel.
Example 2
You are required to be provide fire protection (load-bearing capacity) of 90 minutes to a composite beam supporting a concrete slab, you do not know the building occupancy and therefore, as per Table 17 (page 22), the critical design temperate to follow is 550 °C.
The universal structural beam is 254 x 146 x 31 and requires 3-sided protection. By referring to Table A.2 (page 23) the Hp/A factor can be confirmed as 165.
By cross-referencing to Table C (critical design temperature solutions 550 °C) it is acceptable to specify 2 x 12.5mm Knauf Fire Panel. The Hp/A value must be greater to the Hp/A value for the steel.
Important
The critical design temperatures of steel sections will vary on a project to project bases, dependent on location and intended use, and therefore you must consult with the structural engineer to gain confirmation the specific design temperatures that you need to use to help the determine your fire protection solution.
For further Knauf Framed Encasement System – Fire Panel solutions to support critical design temperature solutions less than 550 °C, please contact our Technical Services, email: technical-uk@ knauf.com or call 0800 521050.
Table A
Plasterboard
Table B
1
Table C
Knauf Metal Furring (MF) Suspended Ceiling Membranes
Performance tables
For further information on Knauf system performances, details and guidance on installation, please contact our Technical Services via email; technical-uk@knauf.com or call 0800 521050 (option 2).
1. The maximum height stated is for the fire resistance of the system to meet project requirements in accordance where EN compliance is required. The stated maximum height figure is the lower value between the cold state height, calculated via limiting deflection of L/240 @ 200Pa and the fire state height, as outlined in accordance with EN 1364:1 and EN 15254-3.
2. Fire resistance period
Tested in accordance with BS EN 1364-1
Fire resistance period is inclusive of both fire integrity and fire insulation. Fire resistance performance must be reviewed against Knauf specifications, standard details, with inclusion of deflection head arrangement.
3. Acoustic sound insulation
Tested or assessed in accordance with BS EN ISO 10140-1 & BS EN ISO 10140-2
Acoustic sound insulation performance based on studs at 600mm centres only
4. Fire resistance period
Tested in accordance with BS EN 1364-2
Fire resistance period is inclusive of both fire integrity and fire insulation. Fire resistance performance must be reviewed against Knauf specifications and standard details. Systems that denote N/A indicate that system has not been fire resistance tested.
Note 1. System that require fire resistance and/or acoustic sound insulation performance must have all outer joints taped and filled in accordance with Knauf recommendations. Systems are tested as imperforate.
Note 2: For substrate fixings, approved fixings are required to meet performance constraint. Site design team to agree the suitability of design and method of installation suitability for the project.
Isometrics of Knauf MF Suspended Ceiling Membranes
*Knauf Insulation Rocksilk ® RS45
Knauf Perfomer Partitions
1. The maximum height stated is for the fire resistance of the system to meet project requirements in accordance where EN compliance is required.
The stated maximum height figure is the lower value between the cold state height, calculated structurally to limiting deflection of L/240 @ 200Pa and the fire state height, as outlined in accordance with EN 1364:1 and EN 15254-3.
2. Fire resistance period
Tested in accordance with BS EN 1364-1
Fire resistance period is inclusive of both fire integrity and fire insulation.
Fire resistance performance must be reviewed against Knauf specifications, standard details, with inclusion of deflection head arrangement.
Systems that denote N/A indicate that system has not been fire resistance tested.
3. Acoustic sound insulation
Tested or assessed in accordance with BS EN ISO 10140-1 & BS EN ISO 10140-2
Acoustic sound insulation performance based on studs at 600mm centres only and non-deflection head arrangement.
Note 1. System that require fire resistance and/or acoustic sound insulation performance must have all outer joints taped and filled in accordance with Knauf recommendations. Systems are tested as imperforate.
Note 2. Systems designed to accommodate up to -25mm or +/-12.5mm deflection allowance. Please refer to Knauf Fire Rated Deflection Head document for detailed information on design and specification.
1. The maximum height stated is the lower value between the cold state height, calculated structurally to limiting deflection of L/240 @ 200Pa and the fire state height, as outlined in accordance with BS EN 1364-1.
2. Fire resistance period
Tested in accordance with BS EN 1364-1.
Fire resistance period is inclusive of both fire integrity and fire insulation.
Fire resistance performance must be reviewed against Knauf specifications, standard details, with inclusion of deflection head arrangement.
3. Acoustic sound insulation
Tested or assessed in accordance with BS EN ISO 10140-1 & BS EN ISO 10140-2.
Acoustic sound insulation performance based on studs at 600mm centres only and non-deflection head arrangement.
Note 1. System that require fire resistance and/or acoustic sound insulation performance must have all outer joints taped and filled in accordance with Knauf recommendations. Systems are tested as imperforate.
Note 2. Systems designed to accommodate up to -25mm or +/-12.5mm deflection allowance. Please refer to Knauf Fire Rated Deflection Head document for detailed information on design and specification.
The 100% Knauf System Performance Warranty
All of our systems are covered by our comprehesive 100% Knauf System Performance Warranty, giving you the insurance that the system you specify and install will perform to specification. Our 100% Knauf System Performance Warranty is available at system performance warranty or contact Knauf technical services - technical-uk@knauf.com or via telephone: 0800521050 (option 2).
The 100% Knauf System Performance Warranty
Knauf
Substantiated System Solutions
Knauf provides a comprehensive range of interior and exterior solutions, systems, and products, robustly tested to provide complete peace of mind for its customers. Systems have been developed and designed as complete building solutions to meet required specified performances. The systems and components are tested by accredited testing facilities in accordance with recognised industry s tandards and regulations.
The 100% Knauf System Performance Warranty guarantees that your Knauf systems are:
o Manufactured from the highest quality raw materials in state -of-the-art factories. Products comply with UK and/or EU standards and are subject to rigorous quality assurance procedures.
o System testing conducted at UKAS accredited laboratories or equivalent recognised (under ILAC MRA) European testing facilities for fire resistance and acoustic sound insulation testing with continuous factory production control testing to review and maintain published performances.
o Fully supported at every stage of the project by Knauf’s market -leading technical and sales support personnel, both pre -site and during construction.
Knauf Technical Services
Help is available via our team of ‘Technical Support Officers’ who are ready to take your technical enquiries providing you w ith expert technical advice on interior and exterior solutions to meet your project needs.
Knauf Specification Service
Tailored project specifications can be delivered with the support of highly skilled and trained Project Specification Manager s and via Knauf Planner Suite https://discover.knauf.com/en-gb/planner-suite) Knauf Planner Suite – System Finder is a three-in-one solution for simple product and system searches, immediate supporting data, and Drywall Specification Documents. Load your free planning assistan t directly in your Revit or ArchiCAD, or simply use the Knauf Planner Suite – System Finder web app.
Knauf On-Site Service
Knauf Project Technical Managers provide on -site project support to assist with the installation of Knauf systems. If Knauf product and system training is required, this can be delivered by the Knauf Technical Services Team
Customer Service
UK: 0800 521 050
Eire: 01 4620739 cservice@knauf.com
Technical Service
0800 521050 (option 2) technical-uk@knauf.com
Addresses
Knauf
Kemsley Fields Business Park Sittingbourne Kent ME9 8SR Knauf 87 Broomhill Road Tallaght Dublin 24 D24 WR85
Website knauf.com knauf.ie
Email technical-uk@knauf.com
SOCIAL MEDIA
KnaufUK
@Knauf_UK
Knauf UK & Ireland @Knauf_UK
Creation Date: 25/09/2023
Revision Reference: 009
Revision Date: 01/10/2024
The information given in this publication is believed to be current and accurate as at the date of publication, but no warranty, express or implied is given. Updates will not be automatically issued.