Heat Pump Water Heater( (Northern Europe) ) Service Manual
GREE ELECTRIC APPLIANCES INC. OF ZHUHAI
CONTENTS RODUCT INTRODUCTION .....................................................................................2 1 MODELS LIST............................................................................................................................. 2 2 NOMENCLATURE ...................................................................................................................... 2 3 FUNCTION .................................................................................................................................. 3 4 PRODUCT DATA......................................................................................................................... 4 4.1 Product Data at Rated Condition........................................................................................ 4 4.2 Ambient Temp Range......................................................................................................... 4 4.3 Electrical Data.................................................................................................................... 5 5 PIPING DIAGRAM...................................................................................................................... 6
UNITS CONTROL ......................................................................................................8 1 OPERATION FLOWCHART....................................................................................................... 8 2 MAIN LOGIC............................................................................................................................. 10 2.1 Heating Mode................................................................................................................... 10 2.2 Defrosting Mode .............................................................................................................. 10 3 WIRED CONTROLLER ............................................................................................................ 11 3.1 Dimension ........................................................................................................................ 11 3.2 Function ........................................................................................................................... 11 3.3 Installation........................................................................................................................ 14 4 CONTROL WIRING DESIGN................................................................................................... 16
UNITS INSTALLATION ..........................................................................................18 1 UNITS INSTALL........................................................................................................................ 18 1.1 Installation Positions ........................................................................................................ 18 1.2 Matters need Attention ..................................................................................................... 18 1.3 Dimension Date................................................................................................................ 18 1.4 Installation Clearance Date .............................................................................................. 19 2 ELECTRIC WIRING WORK..................................................................................................... 21 2.1 Wiring Principle ............................................................................................................... 21 2.2 Electric Wiring Design..................................................................................................... 21 2.3 Specification of Power Supply Wire and Air Switch ....................................................... 22
UNITS MAINTENANCE..........................................................................................24 1 ERROR CODE LIST .................................................................................................................. 24 2 FLOW CHART OF TROUBLESHOOTING ............................................................................. 25 3 DISASSEMBLY AND ASSEMBLY PROCEDURE OF MAIN PARTS.................................... 31 4 EXPLODED VIEWS AND PART LIST..................................................................................... 37 4.1 Single Fan ........................................................................................................................ 37 4.2 Double Fan ....................................................................................................................... 38
GREE COMMERCIAL AIR CONDITIONERS
HEAT PUMP WATER HEATER (NORTHERN EUROPE)
PRODUCT
1
HEAT PUMP WATER HEATER (NORTHERN EUROPE)
PRODUCT
RODUCT INTRODUCTION
1 MODELS LIST
Model Nominal Capacity (kW) Refrigerant
Power Supply (V,Ph,Hz)
Appearance
Model Name
KFRS-9/Na-M
9.0
380~415V
R410A
3Ph
GRS-S16/Na-M(O)
50Hz
16
Note:1Ton =12000Btu/h = 3.517kW
2 NOMENCLATURE K
F
RS
1
2
3
-
9 4
/
Na 5
-
M 6
2
HEAT PUMP WATER HEATER (NORTHERN EUROPE)
NO. 1 2 3 4 6
Description Air Source Split Type Heat Pump Water Heater Heating Capacity Refrigerant
7
Voltage
G
RS
1
2
PRODUCT
Options F= Split Type, Default= Integral Type 9KW Na=R410A, Default=R22 M=380~415V 3Ph 50Hz
-
S
16
3
4
NO. 1 2 3 4 5
Description GREE Heat Pump Water Heater Static Heating Capacity Refrigerant
6
Voltage
7
Outdoor Unit
/
Na 5
-
M
(0)
6
7 Options
S= Static ,C =Circulating 16KW Na=R410A, Default=R22 M=380~415V 3Ph 50Hz O= Outdoor Unit ,I=Indoor Unit
3 FUNCTION Function
Heating
Description Memory restart High efficiency and energy saving Environmentally friendly Healthy and comfortable Friendly man-machine interface Easy installation Low noise design Safety and reliability thanks to advance compressor balance control
3
HEAT PUMP WATER HEATER (NORTHERN EUROPE)
PRODUCT
4 PRODUCT DATA 4.1 Product Data at Rated Condition Technical parameters of host unit
Models
Nominal Capacity
Power
Heating
Consumption
Heating
KFRS-9/Na-M
GRS-S16/Na-M(O)
kW
9
16
Btu/h
30708
54592
RT
2.56
4.55
kW
3
5.5
Power Supply
380~415V,3Ph,50Hz
Safeties Refrigerant Compressor
Type Charge kg Type NO. Heat Exchanger
High/Low pressure switch, compressor thermal protection, over current protection, lose of phase/anti-phase protection, antifreeze protection, R410A 3.3 4.5 scroll 1 1 Aluminum fin-copper tube
Connection
Liquid
mm
1/2"
1/2"
Pipe
Gas
mm
3/4"
3/4"
Height Width Depth
mm mm mm
840/985 1018/1110 412/450
Net / Gross Weights
kg
90/100
Evaporator
Unit/ Packing Dimension
1250/1405 1032/1110 412/450 132/145
NOTE:Testing condition of heating :Setting temp of outlet water: 45℃, outdoor ambient temp : DB7℃/WB6 ℃.
4.2 Ambient Temp Range
Ambient temp range of unit during operation: -15~28℃.
4
HEAT PUMP WATER HEATER (NORTHERN EUROPE)
PRODUCT
4.3 Electrical Data
Compressor
Rated Model
Power Supply
KFRS-9/Na-M GRS-S16/Na-M(O)
380~415V 3Ph 50Hz
LRA
MRC
each
each
(A)
(A)
1
48
10.8
1
74
15.0
NO.
Fan Motor Outdoor
Total
MRC
MRC
NRC
(A)
(A)
(A)
1
1.5
12.3
8.2
2
2
19.5
12.0
NO.
Notes: LRA: Locked rotor amps (A) MRC: Maximum running current (A) NRC: Nominal running current (A)
5
HEAT PUMP WATER HEATER (NORTHERN EUROPE)
PRODUCT
5 PIPING DIAGRAM Water tank Hot water
High-pressure switch City water
Compressor
Low-pressure switch
Four-way valve High pressure tank Thermal expansion valve
Liquid-gas separator
Aluminum fin-copper tube coil
6
GREE COMMERCIAL AIR CONDITIONERS
HEAT PUMP WATER HEATER (NORTHERN EUROPE)
CONTROL
7
GREE COMMERCIAL AIR CONDITIONERS
HEAT PUMP WATER HEATER (NORTHERN EUROPE)
UNITS CONTROL
1 OPERATION FLOWCHART
8
HEAT PUMP WATER HEATER (NORTHERN EUROPE)
INSTALLATION
9
HEAT PUMP WATER HEATER (NORTHERN EUROPE)
INSTALLATION
2 MAIN LOGIC 2.1 Heating Mode When press ON button, if the temperature of water tank meets the heating running requirements, it starts the fans of outdoor unit. Then the compressor will run after 15s. If the temperature of water tank is over the set temperature , the unit will stop, and turn off all loads .The fans of outdoor unit will stop after 15s.
Turn off
Turn on
When it is turned off Fan 1
Fan 2
Compressor
When it is turned off 5S
15S
15S
30S
Four-way Valve
2.2 Defrosting Mode The condition of start defrosting mode: Under heating mode, if the accumulative running time of compressor is over the set interval time of defrosting ( default 45min ), and the defrosting temperature is lower than the set starting temperature(default -4℃) ,the unit will start running defrosting mode, and the 4-way valve will shut
10
HEAT PUMP WATER HEATER (NORTHERN EUROPE)
INSTALLATION
off and the outdoor fan will stop after 2s. The condition of quit defrosting mode: Under defrosting mode, if the continual defrosting time is over the set continual time of defrosting (default 8min),and the defrosting temperature is over the set stopping temperature(default 20℃) ,the unit will restart running heating mode, and the 4-way valve will turn on and the outdoor fan will run.
3 WIRED CONTROLLER 3.1 Dimension
3.2 Function 3.2.1 Operation View
11
HEAT PUMP WATER HEATER (NORTHERN EUROPE)
INSTALLATION
M O DE
CH ECK
QU IT
ON
O FF
NO.
Name
Function description
MODE button
This button is available only on heating unit.
2
CHECK button
Press it once under normal state to enter check mode, under check mode, press this button when “17” is displayed can change the value of “17”. Under parameter set mode, press this once can switch the adjusting objection between parameter and value, press this button for long (about 5s) to save and quit this parameter setting.
3
Increasing button
To increase present set value or change set/check object.
4
Decreasing button
To decrease present set value or change set/check object.
1
5
QUIT button
6
ON button
7
OFF button
8
LCD display
Under Set and Check mode, press it once to quit this mode. Under parameter set mode, this set value would not be saved. Press this button for long (about 5s) to set sound, and make sound switches between always on and always off. To turn on the unit; press it once to quit compel operation when the unit is under compel operation. To turn off the unit; press it once to quit compel operation when the unit is under compel operation. Display information of the unit. 12
HEAT PUMP WATER HEATER (NORTHERN EUROPE)
INSTALLATION
Note: (1) Turn On, Off Auxiliary Heater: It is only available for heat pump unit. Press CHECK once to enter Check mode. Press ▲ and ▼ to change check object, press CHECK again till the present check object becomes “17”, value “17” switches between 01/03 (auxiliary heater on) and 00/02 (auxiliary heater off). That is 00 Off —>01 On —>00 Off, or 02 Off —>03 On —>02 Off. (2) Check Parameter: After electrify for 20s, press QUIT then ▲ to enter parameter checking mode. Under this mode, Auxiliary display area shows the checking object, Main display area displays the value for the checking object. Press ▲ and ▼ to change the checking object. Press QUIT to quit from the check mode.
3.2.2 Display View
NO.
Name
1
Running mode display
Function description
: heating mode 2
Temp display
3
Auxiliary display area
4
Main display area
It shows temperature value displays at main display area. It contains 2 numbers and a comma, for showing temperature and number of parameter at main display area. It only displays when under Check mode and Parameter checking mode. It contains a minus, 2 numbers and 1 temperature unit, for displaying value of temperature and parameter (temperature or time value) and error code. When temperature value is displayed, it shows value in algorism and temperature unit; when time is displayed, it shows algorism value but no temperature unit (default unit is min); when it is code, it displays specific error (refer to Malfunction Error List) but no temperature unit. 13
HEAT PUMP WATER HEATER (NORTHERN EUROPE)
INSTALLATION
Individual temperature or parameter may exceed 99, then adopt AX for 100~109, bX for 110~119, CX for 120~129, dX for 130~139, EX for 140~149, FX for 150~159, and X stands for a number between 0~9. Under normal state, it shows temperature for back water. It means the value shown at present main display area is parameter. It shows only under Parameter Check mode.
5
Parameter display
6
Defrost display
It displays when defrosting, otherwise it doesn’t displays.
7
System ID
It displays when system or compressor orders, for showing which system is defrosting.
8
Testing display
For testing, it displays under compel operation.
9
Error code display
It shows the error code displayed on Main Display Area. It displays when there is error at system or communication.
Caution: When unit is off, it displays only temperature of water tank. When unit is on, under normal state, if there is no error, it displays temperature of water tank, if there is error, it displays error code; when there is no operation after 60s of pressing the button, it quit back to normal state display automatically. Auto antifreeze operation display (only for heat pump unit) When auto antifreeze function is started and relevant conditions are satisfied, unit begins auto antifreeze operation. At this time, LCD main display area displays code d2 (if there is error it displays error code).
3.3 Installation
First select an installation position. According to the size of the communication line of the wire controller, leave a recess or a embedded wire hole to bury the communication line. If the communication line between the wire controller (85×85×20) and the indoor unit is surface-mounted, use 1# PVC pipe and make matching recess in the wall (refer to Figure 6); If concealed installation is adopted, 1# PVC pipe can be used (Refer to Figure 7). No matter if surface mounting or concealed mounting is selected, it is required to drill 2 holes (in the same level) which distance shall be the same as the distance (60mm) of installation holes in the bottom plate of the wire controller. Then insert a wood plug into each hole. Fix the bottom plate of the wire controller to the wall by using the two holes. Plug the communication line onto the control panel. Lastly install the panel of the wire controller.
14
HEAT PUMP WATER HEATER (NORTHERN EUROPE)
INSTALLATION
Caution: During the installation of the bottom plate of the wire controller, pay attention to the direction of the bottom plate. The plate’s side with two notches must be at the lower position, and otherwise the panel of the wire controller cannot be correctly installed.
PVC pi pe
Fig6:Surface Mounting of Cable
Fig7:Concealed mounting of Cable
1
2
3
4
Fig 8 Schematic Diagram of Installation No.
Name
1
Wall Surface
2
Bottom Plate of Wire Controller
3
Screw M4X10
4
Panel of Wire Controller
15
HEAT PUMP WATER HEATER (NORTHERN EUROPE)
INSTALLATION
Caution: The communication distance between the main board and the wire controller can be as far as 20m (The standard distance is 8m).The wire controller shall not be installed in a place where there is water drop or large amount of water vapor.
4 CONTROL WIRING DESIGN
WIRED CONTROLLER CN1
CN2 twisted-pair
twisted-pair J1
X17
Manual Unit Controller
Outdoor Unit Controller
The controllers of the unit include manual controller, wired controller and outdoor unit controller. The wired controller communications with manual controller and outdoor unit controller in RS485. The wired controller connects manual controller with 4-line twisted-pair. Similarly, wired controller connects outdoor unit controller with 4-line twisted-pair.
16
HEAT PUMP WATER HEATER (NORTHERN EUROPE)
INSTALLATION
INSTALLATION
17
HEAT PUMP WATER HEATER (NORTHERN EUROPE)
INSTALLATION
UNITS INSTALLATION
1 UNITS INSTALL 1.1 Installation Positions For outdoor unit: The installation is frost-free. The space around the unit is adequate for servicing. The space around the unit allows for sufficient air circulation. There is no danger of fire due to leakage of flammable gas. All piping lengths and distances have been taken into consideration. 1.2 Matters need Attention At delivery, the unit should be checked and any damage should be reported immediately to the carrier claims agent. 1.3 Dimension Date KFRS-9/Na-M
340
840
950
378 572
412
18
HEAT PUMP WATER HEATER (NORTHERN EUROPE)
INSTALLATION
GRS-S16/Na-M(O)
Unit: mm
air inlet
L1
1.4 Installation Clearance Date
L4 air outlet
L2
L3
19
HEAT PUMP WATER HEATER (NORTHERN EUROPE)
INSTALLATION
unit:mm demonstration
L1
L2
L3
L4
distance
>500
>1000
>500
>500
20
HEAT PUMP WATER HEATER (NORTHERN EUROPE)
MAINTENANCE
2 ELECTRIC WIRING WORK 2.1 Wiring Principle The power cord should firstly connect with dynamic power terminal in electric box and then connect with relevant power terminals of outdoor unit and electric heater. Never mistake the connection to avoid damage to electric elements. If the units is under protection condition. Check out leakage causes to clear the fault and then open the electric box without power supply to reset leakage protector. If leakage protector trips off again, stop the unit and ask professionals for help. Never check or repair it by yourself to avoid safety accident. With green mark is normal , while with red mark means conglutination between contactsďźŒ in which case, it should be replaced after cutting off its power supply.
General principles: Wires, equipment and connectors supplied for use on the site must be in compliance with provisions of regulations and engineering requirements. Only electricians holding qualification are allowed to perform wire connection on the site. Before connection work is started, the power supply must be shut off. Installer shall be responsible for any damage due to incorrect connection of the external circuit of the unit. Caution --- MUST use copper wires. 2.2 Electric Wiring Design POWER 380-400V Hz 3N
Display Board
L1 L2 L3 N L1 L2 L3 XT2 XT1 Intdoor Unit Electric Box
CN2
AP2 CN1
CN5
L1 L2 L3 N XT3 4-core twsited pair wire
PE
4-core twsited pair wire
Electric heater PE PE
PE
L1 L2 L3 N XT1
Outdoor Unit Electric Box
Water Tank
X17
AP
Water-outlet Temp.Sensor
21
HEAT PUMP WATER HEATER (NORTHERN EUROPE)
MAINTENANCE
2.3 Specification of Power Supply Wire and Air Switch Power cable specifications and air switch types in the following list are recommended for selection. Min. sectional Min. sectional Air switch area of area of power capacity Unit Model Power supply grounding cable cable (A) (mm2) 2 (mm ) 380-415V KFRS-9/Na-M 13 1.5 4×1.5 3N~ 50Hz 380-415V GRS-S16/Na-M(O) 25 2.5 4×2.5 3N~ 50Hz Note:
The power supply wire must be copper core wire, and the working temperature can not be higher than limited value. If the length of power supply wire is longer than 15meters, do please increase the section area to avoid any accident due to over-load. If the supply cord is damaged, it must be replaced by the manufacturer or its service agent or a similar qualified person in order to avoid a hazard. The appliance shall be installed according to national regulations When installing the connection wiring for manual controller, the wire must be put inside a separate protective sheath to avoid direct sunshine.
Warning! An all-pole disconnection switch having a contact separation of at least 3mm in all poles should be connected in fixed wiring.
22
HEAT PUMP WATER HEATER (NORTHERN EUROPE)
MAINTENANCE
MAINTENANCE
23
HEAT PUMP WATER HEATER (NORTHERN EUROPE)
UNITS MAINTENANCE 1 Code Indication
E1
E3
E4
E5
E8
MAINTENANCE
ERROR CODE LIST
Error Name
Cause of Error Code
Control Description
Comp High-pressure switch is broken or the wiring is loose.
The water in the tank is not enough.
The installation of tank temp sensor is not correct.
The gas valve and liquid valve are not fully open.
The thermal expansion valve can not work normally.
Comp Low-pressure switch is broken or the wiring is loose.
The system has leaked.
The fans stop running or reverse.
The resistance of temperature sensor is not correct.
Comp Discharge temp
The thermal expansion valve is blocked.
protection
The system has leaked.
Mainboard of outdoor unit is damaged.
AC contactor is damaged.
The compressor wiring is not correct.
The voltage is not normal.
Overcurrent test board is damaged.
The refrigerant of the system is excessive.
Mainboard of outdoor unit is damaged.
The wire connecting the wiring terminals of the mainboard Press ON/OFF key to clear
Comp High-pressure protection
Comp Low- pressure protection
Comp overload protection
Fan 1 overload protection
Press ON/OFF key to clear
Press ON/OFF key to clear
Press ON/OFF key to clear
Press ON/OFF key to clear
breaks.
b8
Fan 2 overload protection
Mainboard of outdoor unit is damaged.
The wire connecting the wiring terminals of the mainboard Press ON/OFF key to clear breaks.
F3
F5
F7
EC
Defrost temp sensor failure
socket on mainboard.
The resistance of temperature sensor is not correct.
The plug on temperature sensor is not correctly connected to the
Discharge temp sensor error
socket on mainboard.
The resistance of temperature sensor is not correct.
The plug on temperature sensor is not correctly connected to the
Outdoor ambient temp sensor failure
Communication malfunction
The plug on temperature sensor is not correctly connected to the
socket on mainboard.
The resistance of temperature sensor is not correct.
The communication line of the unit is not connected.
The communication line is not through.
The communication line of the unit is not connected correctly.
The two ends of communication line are not mounted with
Auto resume
Auto resume
Auto resume
Auto resume
magnetic ring.
The outdoor unit is not electrically powered.
24
HEAT PUMP WATER HEATER (NORTHERN EUROPE)
MAINTENANCE
2 FLOW CHART OF TROUBLESHOOTING (1)Comp High-pressure Protection E1 Comp High-pressure Protection E1
Check if the water in the tank is enough
NO Fill the tank with the water
YES
Check if the installation of tank temp sensor is correct
NO
Install rightly the tank temp sensor
YES
Check if the gas valve and liquid valve are fully open
NO Fully open the valve
YES NO Check if the thermal expansion valve can work normally
Replace the thermal expansion valve
(2)Comp Low- pressure Protection E3
25
HEAT PUMP WATER HEATER (NORTHERN EUROPE)
MAINTENANCE
(3)Comp Discharge Temp Protection E4
26
HEAT PUMP WATER HEATER (NORTHERN EUROPE)
MAINTENANCE
(4) Comp Overload Protection E5
27
HEAT PUMP WATER HEATER (NORTHERN EUROPE)
MAINTENANCE
(5)Fan 1 Overload Protection E8
(6)Fan 2 Overload Protection b8
28
HEAT PUMP WATER HEATER (NORTHERN EUROPE)
MAINTENANCE
(7) Temperature Sensor Error F3, F5, F7
(8) Communication Malfunction EC
29
HEAT PUMP WATER HEATER (NORTHERN EUROPE)
MAINTENANCE
Com m unication M alfunction EC
Check if the com m unication line of the unit is connected
NO
Check the orientation of plug and socket
YES
M easure if the Com munication line is through
NO Replace the com m unication line
YES
Check if the com m unication line of the unit is connected correctly
NO
Check the orientation of plug and socke t
YES NO Check if the outdoor unit is electrically powered
Please supply pow er to the outdoor unit
30
HEAT PUMP WATER HEATER (NORTHERN EUROPE)
MAINTENANCE
3 DISASSEMBLY AND ASSEMBLY PROCEDURE OF MAIN PARTS Disassembly and Assembly of external casing Remark:Please first cut off the power and drain let the Freon out of the unit
Operation Procedure
Illustration
(1) Remove the front case 1)
Remove the panel
·Loosen the two tapping screws fixing the front grill. ·Pull down and remove the front grill. (See Fig. 2)
Fig. 1
Fig. 2
2)
Remove the cover.
· Loosen the two tapping screws fixing the cover. Remove the cover(See Fig.
Fig. 3
31
HEAT PUMP WATER HEATER (NORTHERN EUROPE)
MAINTENANCE
3)Remove the front plate. · Loosen the two tapping screws fixing the front plate. Remove the front plate.(See Fig. 5)
grill Fig. 4
Fig. 5
4)Remove the grill · Loosen the two tapping screws fixing the grill. Remove the grill.
Fig. 6
(See Fig. 6)
32
HEAT PUMP WATER HEATER (NORTHERN EUROPE)
MAINTENANCE
(2) Remove the axial fan · Loosen the ball nuts fixing the axial fan and remove the washer.(See Fig. 7) ·Pull outward to remove the impeller. (See Fig. 7)
Ball Nut Fig. 7
Motor support Fig. 8
(3) Remove the motor · Loosen the screws fixing the motor support. Remove the motor support. (See Fig .8 & Fig.9)
Fig. 9
33
HEAT PUMP WATER HEATER (NORTHERN EUROPE)
MAINTENANCE
· Loosen the two screws fixing the motor. Pull backward and remove the motor.(See Fig .10) ·Loosen the wire of motor, and pull it through the hole.
Fig. 10
(4) Remove the 4-way valve Remove the 4-way valve ·Loosen the screws fixing the coil of 4-way valve。 ·Remove the coil of 4-way valve。 ·Welding out the tubes connected to the
Fig. 11
4-way valve. ·Remove the 4-way valve.(See Fig.11) Note:When welding, the valve should be covered by wet cloth in order to avoid the high temp. hurt。
(5) Remove electric box · Loosen the screws fixing the box 34
HEAT PUMP WATER HEATER (NORTHERN EUROPE)
cover.
Remove
all
MAINTENANCE
pressure
switches and temp. sensor.(See Fig.12)
Fig.12
(6)Remove compressor and gas-liquid separator · Remove the connection wire of compressor。(See Fig.13)
Compressor
· welding out the suction pipe and
Gas-liquid separator Fig.13
discharge pipe.(See Fig.13) ·Loosen the bolts fixing the compressor and Remove the gas-liquid separator.
(7)Remove
compressor
gas
and
and
liquid
valve 35
HEAT PUMP WATER HEATER (NORTHERN EUROPE)
MAINTENANCE
1. Remove gas valve ·Loosen the bolts fixing the gas valve. ·welding out the pipe connected to the gas valve (See Fig.14).
Note:When welding, the valve should be
Bolts
covered by wet cloth in order to avoid the high temp hurt.
Gas valve Fig.14
2. Remove liquid valve · Loosen the bolts fixing the liquid
Bolts
Liquid valve Fig.15
valve. ·welding out the pipe connected to the liquid valve (See Fig.15).
Note:When welding, the valve should be covered by wet cloth in order to avoid the high temp hurt.
36
HEAT PUMP WATER HEATER (NORTHERN EUROPE)
MAINTENANCE
4 EXPLODED VIEWS AND PART LIST 4.1 Single Fan Exploded Views:
No.
Name of part
Part code
Quantity
1
Valve Support Sub-Assy
01715001
1
2
Compressor Support Sub-Assy
01802222
1
3
Chassis Sub-Assy
01282235
1
4
Wooden Package Base
501154042
1
5
Compressor and Fittings
00205208
1
6
Cabinet
01435103
1
7
Front Grill
22265401
1
8
Condenser Inlet Pipe
04655706
1
9
Fan Motor
150154011
1
10
Axial Flow Fan
10335401
1
11
Motor Support Sub-Assy
01705402
1
12
Top Cover
01255402
1
13
Electric Box Sub-Assy
01392129
1
14
Clapboard Assy
01242214
1
15
Condenser Assy
01122216
1
16
4-way Valve Sub-Assy
04142216
1
17
Inhalation Tube Sub-Assy
04672240
1 37
HEAT PUMP WATER HEATER (NORTHERN EUROPE)
MAINTENANCE
18
Cut-off Valve Sub-Assy
07332217
1
19
Gas-liquid Separator Assy
07255403
1
20
Bidirection Accumulator
07228741
1
21
Inflate Valve Sub-Assy
07332218
1
22
Rear Grill
01475401
1
23
Front Side Plate Sub-Assy
01312232
1
24
Rear Side Plate Sub-Assy
01305402
1
25
Capacitor CBB61
33010013
1
26
Main Board
30221602
1
27
Terminal Board
42011043
1
28
Terminal Board
42011103
2
29
Capacitor CBB65
3300002232
1
30
Transformer
43110240
1
31
AC Contactor
44010226
1
Part code
Quantity
4.2 Double Fan Exploded views:
No.
Name of part
1
Rear Side Plate Sub-Assy
01312815P
1
2
Valve Support Sub-Assy
01715001
1
3
4-way Valve Sub-Assy
04142815
1
4
Inflate Valve Sub-Assy
07332818
1 38
HEAT PUMP WATER HEATER (NORTHERN EUROPE)
MAINTENANCE
5
Accumulator
07422204
1
6
Chassis Sub-Assy
01192813P
1
7
Liquid Valve Sub-Assy
07302803
1
8
Compressor and Fittings
00205205
1
9
Front Side Plate Sub-Assy
01305430
1
10
Handle
26235253
3
11
Axial Flow Fan
10338731
1
12
Fan Motor
150154513
1
13
Motor Support Sub-Assy
01705471
1
14
Front Grill
22414102
1
15
Cabinet
01435436
1
16
Top Cover
01255262
1
17
Condenser Assy
01122808
1
18
Inhalation Tube Sub-Assy
04672820
1
19
Electric Box Assy
01393734
1
20
Upper Insulation Plate Sub-Assy
01242802
1
21
Gas-liquid Separator Sub-Assy
07225018
1
22
Lower Insulation Plate
01242804
1
39