Heat Pump Water Heater( (Northern Europe) ) Service Manual

GREE ELECTRIC APPLIANCES INC. OF ZHUHAI


CONTENTS RODUCT INTRODUCTION .....................................................................................2 1 MODELS LIST............................................................................................................................. 2 2 NOMENCLATURE ...................................................................................................................... 2 3 FUNCTION .................................................................................................................................. 3 4 PRODUCT DATA......................................................................................................................... 4 4.1 Product Data at Rated Condition........................................................................................ 4 4.2 Ambient Temp Range......................................................................................................... 4 4.3 Electrical Data.................................................................................................................... 5 5 PIPING DIAGRAM...................................................................................................................... 6

UNITS CONTROL ......................................................................................................8 1 OPERATION FLOWCHART....................................................................................................... 8 2 MAIN LOGIC............................................................................................................................. 10 2.1 Heating Mode................................................................................................................... 10 2.2 Defrosting Mode .............................................................................................................. 10 3 WIRED CONTROLLER ............................................................................................................ 11 3.1 Dimension ........................................................................................................................ 11 3.2 Function ........................................................................................................................... 11 3.3 Installation........................................................................................................................ 14 4 CONTROL WIRING DESIGN................................................................................................... 16

UNITS INSTALLATION ..........................................................................................18 1 UNITS INSTALL........................................................................................................................ 18 1.1 Installation Positions ........................................................................................................ 18 1.2 Matters need Attention ..................................................................................................... 18 1.3 Dimension Date................................................................................................................ 18 1.4 Installation Clearance Date .............................................................................................. 19 2 ELECTRIC WIRING WORK..................................................................................................... 21 2.1 Wiring Principle ............................................................................................................... 21 2.2 Electric Wiring Design..................................................................................................... 21 2.3 Specification of Power Supply Wire and Air Switch ....................................................... 22

UNITS MAINTENANCE..........................................................................................24 1 ERROR CODE LIST .................................................................................................................. 24 2 FLOW CHART OF TROUBLESHOOTING ............................................................................. 25 3 DISASSEMBLY AND ASSEMBLY PROCEDURE OF MAIN PARTS.................................... 31 4 EXPLODED VIEWS AND PART LIST..................................................................................... 37 4.1 Single Fan ........................................................................................................................ 37 4.2 Double Fan ....................................................................................................................... 38


GREE COMMERCIAL AIR CONDITIONERS

HEAT PUMP WATER HEATER (NORTHERN EUROPE)

PRODUCT

1


HEAT PUMP WATER HEATER (NORTHERN EUROPE)

PRODUCT

RODUCT INTRODUCTION

1 MODELS LIST

Model Nominal Capacity (kW) Refrigerant

Power Supply (V,Ph,Hz)

Appearance

Model Name

KFRS-9/Na-M

9.0

380~415V

R410A

3Ph

GRS-S16/Na-M(O)

50Hz

16

Note:1Ton =12000Btu/h = 3.517kW

2 NOMENCLATURE K

F

RS

1

2

3

-

9 4

/

Na 5

-

M 6

2


HEAT PUMP WATER HEATER (NORTHERN EUROPE)

NO. 1 2 3 4 6

Description Air Source Split Type Heat Pump Water Heater Heating Capacity Refrigerant

7

Voltage

G

RS

1

2

PRODUCT

Options F= Split Type, Default= Integral Type 9KW Na=R410A, Default=R22 M=380~415V 3Ph 50Hz

-

S

16

3

4

NO. 1 2 3 4 5

Description GREE Heat Pump Water Heater Static Heating Capacity Refrigerant

6

Voltage

7

Outdoor Unit

/

Na 5

-

M

(0)

6

7 Options

S= Static ,C =Circulating 16KW Na=R410A, Default=R22 M=380~415V 3Ph 50Hz O= Outdoor Unit ,I=Indoor Unit

3 FUNCTION Function

Heating

Description Memory restart High efficiency and energy saving Environmentally friendly Healthy and comfortable Friendly man-machine interface Easy installation Low noise design Safety and reliability thanks to advance compressor balance control

3


HEAT PUMP WATER HEATER (NORTHERN EUROPE)

PRODUCT

4 PRODUCT DATA 4.1 Product Data at Rated Condition Technical parameters of host unit

Models

Nominal Capacity

Power

Heating

Consumption

Heating

KFRS-9/Na-M

GRS-S16/Na-M(O)

kW

9

16

Btu/h

30708

54592

RT

2.56

4.55

kW

3

5.5

Power Supply

380~415V,3Ph,50Hz

Safeties Refrigerant Compressor

Type Charge kg Type NO. Heat Exchanger

High/Low pressure switch, compressor thermal protection, over current protection, lose of phase/anti-phase protection, antifreeze protection, R410A 3.3 4.5 scroll 1 1 Aluminum fin-copper tube

Connection

Liquid

mm

1/2"

1/2"

Pipe

Gas

mm

3/4"

3/4"

Height Width Depth

mm mm mm

840/985 1018/1110 412/450

Net / Gross Weights

kg

90/100

Evaporator

Unit/ Packing Dimension

1250/1405 1032/1110 412/450 132/145

NOTE:Testing condition of heating :Setting temp of outlet water: 45℃, outdoor ambient temp : DB7℃/WB6 ℃.

4.2 Ambient Temp Range

Ambient temp range of unit during operation: -15~28℃.

4


HEAT PUMP WATER HEATER (NORTHERN EUROPE)

PRODUCT

4.3 Electrical Data

Compressor

Rated Model

Power Supply

KFRS-9/Na-M GRS-S16/Na-M(O)

380~415V 3Ph 50Hz

LRA

MRC

each

each

(A)

(A)

1

48

10.8

1

74

15.0

NO.

Fan Motor Outdoor

Total

MRC

MRC

NRC

(A)

(A)

(A)

1

1.5

12.3

8.2

2

2

19.5

12.0

NO.

Notes: LRA: Locked rotor amps (A) MRC: Maximum running current (A) NRC: Nominal running current (A)

5


HEAT PUMP WATER HEATER (NORTHERN EUROPE)

PRODUCT

5 PIPING DIAGRAM Water tank Hot water

High-pressure switch City water

Compressor

Low-pressure switch

Four-way valve High pressure tank Thermal expansion valve

Liquid-gas separator

Aluminum fin-copper tube coil

6


GREE COMMERCIAL AIR CONDITIONERS

HEAT PUMP WATER HEATER (NORTHERN EUROPE)

CONTROL

7


GREE COMMERCIAL AIR CONDITIONERS

HEAT PUMP WATER HEATER (NORTHERN EUROPE)

UNITS CONTROL

1 OPERATION FLOWCHART

8


HEAT PUMP WATER HEATER (NORTHERN EUROPE)

INSTALLATION

9


HEAT PUMP WATER HEATER (NORTHERN EUROPE)

INSTALLATION

2 MAIN LOGIC 2.1 Heating Mode When press ON button, if the temperature of water tank meets the heating running requirements, it starts the fans of outdoor unit. Then the compressor will run after 15s. If the temperature of water tank is over the set temperature , the unit will stop, and turn off all loads .The fans of outdoor unit will stop after 15s.

Turn off

Turn on

When it is turned off Fan 1

Fan 2

Compressor

When it is turned off 5S

15S

15S

30S

Four-way Valve

2.2 Defrosting Mode The condition of start defrosting mode: Under heating mode, if the accumulative running time of compressor is over the set interval time of defrosting ( default 45min ), and the defrosting temperature is lower than the set starting temperature(default -4℃) ,the unit will start running defrosting mode, and the 4-way valve will shut

10


HEAT PUMP WATER HEATER (NORTHERN EUROPE)

INSTALLATION

off and the outdoor fan will stop after 2s. The condition of quit defrosting mode: Under defrosting mode, if the continual defrosting time is over the set continual time of defrosting (default 8min),and the defrosting temperature is over the set stopping temperature(default 20℃) ,the unit will restart running heating mode, and the 4-way valve will turn on and the outdoor fan will run.

3 WIRED CONTROLLER 3.1 Dimension

3.2 Function 3.2.1 Operation View

11


HEAT PUMP WATER HEATER (NORTHERN EUROPE)

INSTALLATION

M O DE

CH ECK

QU IT

ON

O FF

NO.

Name

Function description

MODE button

This button is available only on heating unit.

2

CHECK button

Press it once under normal state to enter check mode, under check mode, press this button when “17” is displayed can change the value of “17”. Under parameter set mode, press this once can switch the adjusting objection between parameter and value, press this button for long (about 5s) to save and quit this parameter setting.

3

Increasing button

To increase present set value or change set/check object.

4

Decreasing button

To decrease present set value or change set/check object.

1

5

QUIT button

6

ON button

7

OFF button

8

LCD display

Under Set and Check mode, press it once to quit this mode. Under parameter set mode, this set value would not be saved. Press this button for long (about 5s) to set sound, and make sound switches between always on and always off. To turn on the unit; press it once to quit compel operation when the unit is under compel operation. To turn off the unit; press it once to quit compel operation when the unit is under compel operation. Display information of the unit. 12


HEAT PUMP WATER HEATER (NORTHERN EUROPE)

INSTALLATION

Note: (1) Turn On, Off Auxiliary Heater: It is only available for heat pump unit. Press CHECK once to enter Check mode. Press ▲ and ▼ to change check object, press CHECK again till the present check object becomes “17”, value “17” switches between 01/03 (auxiliary heater on) and 00/02 (auxiliary heater off). That is 00 Off —>01 On —>00 Off, or 02 Off —>03 On —>02 Off. (2) Check Parameter: After electrify for 20s, press QUIT then ▲ to enter parameter checking mode. Under this mode, Auxiliary display area shows the checking object, Main display area displays the value for the checking object. Press ▲ and ▼ to change the checking object. Press QUIT to quit from the check mode.

3.2.2 Display View

NO.

Name

1

Running mode display

Function description

: heating mode 2

Temp display

3

Auxiliary display area

4

Main display area

It shows temperature value displays at main display area. It contains 2 numbers and a comma, for showing temperature and number of parameter at main display area. It only displays when under Check mode and Parameter checking mode. It contains a minus, 2 numbers and 1 temperature unit, for displaying value of temperature and parameter (temperature or time value) and error code. When temperature value is displayed, it shows value in algorism and temperature unit; when time is displayed, it shows algorism value but no temperature unit (default unit is min); when it is code, it displays specific error (refer to Malfunction Error List) but no temperature unit. 13


HEAT PUMP WATER HEATER (NORTHERN EUROPE)

INSTALLATION

Individual temperature or parameter may exceed 99, then adopt AX for 100~109, bX for 110~119, CX for 120~129, dX for 130~139, EX for 140~149, FX for 150~159, and X stands for a number between 0~9. Under normal state, it shows temperature for back water. It means the value shown at present main display area is parameter. It shows only under Parameter Check mode.

5

Parameter display

6

Defrost display

It displays when defrosting, otherwise it doesn’t displays.

7

System ID

It displays when system or compressor orders, for showing which system is defrosting.

8

Testing display

For testing, it displays under compel operation.

9

Error code display

It shows the error code displayed on Main Display Area. It displays when there is error at system or communication.

Caution: When unit is off, it displays only temperature of water tank. When unit is on, under normal state, if there is no error, it displays temperature of water tank, if there is error, it displays error code; when there is no operation after 60s of pressing the button, it quit back to normal state display automatically. Auto antifreeze operation display (only for heat pump unit) When auto antifreeze function is started and relevant conditions are satisfied, unit begins auto antifreeze operation. At this time, LCD main display area displays code d2 (if there is error it displays error code).

3.3 Installation

First select an installation position. According to the size of the communication line of the wire controller, leave a recess or a embedded wire hole to bury the communication line. If the communication line between the wire controller (85×85×20) and the indoor unit is surface-mounted, use 1# PVC pipe and make matching recess in the wall (refer to Figure 6); If concealed installation is adopted, 1# PVC pipe can be used (Refer to Figure 7). No matter if surface mounting or concealed mounting is selected, it is required to drill 2 holes (in the same level) which distance shall be the same as the distance (60mm) of installation holes in the bottom plate of the wire controller. Then insert a wood plug into each hole. Fix the bottom plate of the wire controller to the wall by using the two holes. Plug the communication line onto the control panel. Lastly install the panel of the wire controller.

14


HEAT PUMP WATER HEATER (NORTHERN EUROPE)

INSTALLATION

Caution: During the installation of the bottom plate of the wire controller, pay attention to the direction of the bottom plate. The plate’s side with two notches must be at the lower position, and otherwise the panel of the wire controller cannot be correctly installed.

PVC pi pe

Fig6:Surface Mounting of Cable

Fig7:Concealed mounting of Cable

1

2

3

4

Fig 8 Schematic Diagram of Installation No.

Name

1

Wall Surface

2

Bottom Plate of Wire Controller

3

Screw M4X10

4

Panel of Wire Controller

15


HEAT PUMP WATER HEATER (NORTHERN EUROPE)

INSTALLATION

Caution: The communication distance between the main board and the wire controller can be as far as 20m (The standard distance is 8m).The wire controller shall not be installed in a place where there is water drop or large amount of water vapor.

4 CONTROL WIRING DESIGN

WIRED CONTROLLER CN1

CN2 twisted-pair

twisted-pair J1

X17

Manual Unit Controller

Outdoor Unit Controller

The controllers of the unit include manual controller, wired controller and outdoor unit controller. The wired controller communications with manual controller and outdoor unit controller in RS485. The wired controller connects manual controller with 4-line twisted-pair. Similarly, wired controller connects outdoor unit controller with 4-line twisted-pair.

16


HEAT PUMP WATER HEATER (NORTHERN EUROPE)

INSTALLATION

INSTALLATION

17


HEAT PUMP WATER HEATER (NORTHERN EUROPE)

INSTALLATION

UNITS INSTALLATION

1 UNITS INSTALL 1.1 Installation Positions For outdoor unit: The installation is frost-free. The space around the unit is adequate for servicing. The space around the unit allows for sufficient air circulation. There is no danger of fire due to leakage of flammable gas. All piping lengths and distances have been taken into consideration. 1.2 Matters need Attention At delivery, the unit should be checked and any damage should be reported immediately to the carrier claims agent. 1.3 Dimension Date KFRS-9/Na-M

340

840

950

378 572

412

18


HEAT PUMP WATER HEATER (NORTHERN EUROPE)

INSTALLATION

GRS-S16/Na-M(O)

Unit: mm

air inlet

L1

1.4 Installation Clearance Date

L4 air outlet

L2

L3

19


HEAT PUMP WATER HEATER (NORTHERN EUROPE)

INSTALLATION

unit:mm demonstration

L1

L2

L3

L4

distance

>500

>1000

>500

>500

20


HEAT PUMP WATER HEATER (NORTHERN EUROPE)

MAINTENANCE

2 ELECTRIC WIRING WORK 2.1 Wiring Principle The power cord should firstly connect with dynamic power terminal in electric box and then connect with relevant power terminals of outdoor unit and electric heater. Never mistake the connection to avoid damage to electric elements. If the units is under protection condition. Check out leakage causes to clear the fault and then open the electric box without power supply to reset leakage protector. If leakage protector trips off again, stop the unit and ask professionals for help. Never check or repair it by yourself to avoid safety accident. With green mark is normal , while with red mark means conglutination between contactsďźŒ in which case, it should be replaced after cutting off its power supply.

General principles: Wires, equipment and connectors supplied for use on the site must be in compliance with provisions of regulations and engineering requirements. Only electricians holding qualification are allowed to perform wire connection on the site. Before connection work is started, the power supply must be shut off. Installer shall be responsible for any damage due to incorrect connection of the external circuit of the unit. Caution --- MUST use copper wires. 2.2 Electric Wiring Design POWER 380-400V Hz 3N

Display Board

L1 L2 L3 N L1 L2 L3 XT2 XT1 Intdoor Unit Electric Box

CN2

AP2 CN1

CN5

L1 L2 L3 N XT3 4-core twsited pair wire

PE

4-core twsited pair wire

Electric heater PE PE

PE

L1 L2 L3 N XT1

Outdoor Unit Electric Box

Water Tank

X17

AP

Water-outlet Temp.Sensor

21


HEAT PUMP WATER HEATER (NORTHERN EUROPE)

MAINTENANCE

2.3 Specification of Power Supply Wire and Air Switch Power cable specifications and air switch types in the following list are recommended for selection. Min. sectional Min. sectional Air switch area of area of power capacity Unit Model Power supply grounding cable cable (A) (mm2) 2 (mm ) 380-415V KFRS-9/Na-M 13 1.5 4×1.5 3N~ 50Hz 380-415V GRS-S16/Na-M(O) 25 2.5 4×2.5 3N~ 50Hz Note:

The power supply wire must be copper core wire, and the working temperature can not be higher than limited value. If the length of power supply wire is longer than 15meters, do please increase the section area to avoid any accident due to over-load. If the supply cord is damaged, it must be replaced by the manufacturer or its service agent or a similar qualified person in order to avoid a hazard. The appliance shall be installed according to national regulations When installing the connection wiring for manual controller, the wire must be put inside a separate protective sheath to avoid direct sunshine.

Warning! An all-pole disconnection switch having a contact separation of at least 3mm in all poles should be connected in fixed wiring.

22


HEAT PUMP WATER HEATER (NORTHERN EUROPE)

MAINTENANCE

MAINTENANCE

23


HEAT PUMP WATER HEATER (NORTHERN EUROPE)

UNITS MAINTENANCE 1 Code Indication

E1

E3

E4

E5

E8

MAINTENANCE

ERROR CODE LIST

Error Name

Cause of Error Code

Control Description

Comp High-pressure switch is broken or the wiring is loose.

The water in the tank is not enough.

The installation of tank temp sensor is not correct.

The gas valve and liquid valve are not fully open.

The thermal expansion valve can not work normally.

Comp Low-pressure switch is broken or the wiring is loose.

The system has leaked.

The fans stop running or reverse.

The resistance of temperature sensor is not correct.

Comp Discharge temp

The thermal expansion valve is blocked.

protection

The system has leaked.

Mainboard of outdoor unit is damaged.

AC contactor is damaged.

The compressor wiring is not correct.

The voltage is not normal.

Overcurrent test board is damaged.

The refrigerant of the system is excessive.

Mainboard of outdoor unit is damaged.

The wire connecting the wiring terminals of the mainboard Press ON/OFF key to clear

Comp High-pressure protection

Comp Low- pressure protection

Comp overload protection

Fan 1 overload protection

Press ON/OFF key to clear

Press ON/OFF key to clear

Press ON/OFF key to clear

Press ON/OFF key to clear

breaks.

b8

Fan 2 overload protection

Mainboard of outdoor unit is damaged.

The wire connecting the wiring terminals of the mainboard Press ON/OFF key to clear breaks.

F3

F5

F7

EC

Defrost temp sensor failure

socket on mainboard.

The resistance of temperature sensor is not correct.

The plug on temperature sensor is not correctly connected to the

Discharge temp sensor error

socket on mainboard.

The resistance of temperature sensor is not correct.

The plug on temperature sensor is not correctly connected to the

Outdoor ambient temp sensor failure

Communication malfunction

The plug on temperature sensor is not correctly connected to the

socket on mainboard.

The resistance of temperature sensor is not correct.

The communication line of the unit is not connected.

The communication line is not through.

The communication line of the unit is not connected correctly.

The two ends of communication line are not mounted with

Auto resume

Auto resume

Auto resume

Auto resume

magnetic ring.

The outdoor unit is not electrically powered.

24


HEAT PUMP WATER HEATER (NORTHERN EUROPE)

MAINTENANCE

2 FLOW CHART OF TROUBLESHOOTING (1)Comp High-pressure Protection E1 Comp High-pressure Protection E1

Check if the water in the tank is enough

NO Fill the tank with the water

YES

Check if the installation of tank temp sensor is correct

NO

Install rightly the tank temp sensor

YES

Check if the gas valve and liquid valve are fully open

NO Fully open the valve

YES NO Check if the thermal expansion valve can work normally

Replace the thermal expansion valve

(2)Comp Low- pressure Protection E3

25


HEAT PUMP WATER HEATER (NORTHERN EUROPE)

MAINTENANCE

(3)Comp Discharge Temp Protection E4

26


HEAT PUMP WATER HEATER (NORTHERN EUROPE)

MAINTENANCE

(4) Comp Overload Protection E5

27


HEAT PUMP WATER HEATER (NORTHERN EUROPE)

MAINTENANCE

(5)Fan 1 Overload Protection E8

(6)Fan 2 Overload Protection b8

28


HEAT PUMP WATER HEATER (NORTHERN EUROPE)

MAINTENANCE

(7) Temperature Sensor Error F3, F5, F7

(8) Communication Malfunction EC

29


HEAT PUMP WATER HEATER (NORTHERN EUROPE)

MAINTENANCE

Com m unication M alfunction EC

Check if the com m unication line of the unit is connected

NO

Check the orientation of plug and socket

YES

M easure if the Com munication line is through

NO Replace the com m unication line

YES

Check if the com m unication line of the unit is connected correctly

NO

Check the orientation of plug and socke t

YES NO Check if the outdoor unit is electrically powered

Please supply pow er to the outdoor unit

30


HEAT PUMP WATER HEATER (NORTHERN EUROPE)

MAINTENANCE

3 DISASSEMBLY AND ASSEMBLY PROCEDURE OF MAIN PARTS Disassembly and Assembly of external casing Remark:Please first cut off the power and drain let the Freon out of the unit

Operation Procedure

Illustration

(1) Remove the front case 1)

Remove the panel

·Loosen the two tapping screws fixing the front grill. ·Pull down and remove the front grill. (See Fig. 2)

Fig. 1

Fig. 2

2)

Remove the cover.

· Loosen the two tapping screws fixing the cover. Remove the cover(See Fig.

Fig. 3

31


HEAT PUMP WATER HEATER (NORTHERN EUROPE)

MAINTENANCE

3)Remove the front plate. · Loosen the two tapping screws fixing the front plate. Remove the front plate.(See Fig. 5)

grill Fig. 4

Fig. 5

4)Remove the grill · Loosen the two tapping screws fixing the grill. Remove the grill.

Fig. 6

(See Fig. 6)

32


HEAT PUMP WATER HEATER (NORTHERN EUROPE)

MAINTENANCE

(2) Remove the axial fan · Loosen the ball nuts fixing the axial fan and remove the washer.(See Fig. 7) ·Pull outward to remove the impeller. (See Fig. 7)

Ball Nut Fig. 7

Motor support Fig. 8

(3) Remove the motor · Loosen the screws fixing the motor support. Remove the motor support. (See Fig .8 & Fig.9)

Fig. 9

33


HEAT PUMP WATER HEATER (NORTHERN EUROPE)

MAINTENANCE

· Loosen the two screws fixing the motor. Pull backward and remove the motor.(See Fig .10) ·Loosen the wire of motor, and pull it through the hole.

Fig. 10

(4) Remove the 4-way valve Remove the 4-way valve ·Loosen the screws fixing the coil of 4-way valve。 ·Remove the coil of 4-way valve。 ·Welding out the tubes connected to the

Fig. 11

4-way valve. ·Remove the 4-way valve.(See Fig.11) Note:When welding, the valve should be covered by wet cloth in order to avoid the high temp. hurt。

(5) Remove electric box · Loosen the screws fixing the box 34


HEAT PUMP WATER HEATER (NORTHERN EUROPE)

cover.

Remove

all

MAINTENANCE

pressure

switches and temp. sensor.(See Fig.12)

Fig.12

(6)Remove compressor and gas-liquid separator · Remove the connection wire of compressor。(See Fig.13)

Compressor

· welding out the suction pipe and

Gas-liquid separator Fig.13

discharge pipe.(See Fig.13) ·Loosen the bolts fixing the compressor and Remove the gas-liquid separator.

(7)Remove

compressor

gas

and

and

liquid

valve 35


HEAT PUMP WATER HEATER (NORTHERN EUROPE)

MAINTENANCE

1. Remove gas valve ·Loosen the bolts fixing the gas valve. ·welding out the pipe connected to the gas valve (See Fig.14).

Note:When welding, the valve should be

Bolts

covered by wet cloth in order to avoid the high temp hurt.

Gas valve Fig.14

2. Remove liquid valve · Loosen the bolts fixing the liquid

Bolts

Liquid valve Fig.15

valve. ·welding out the pipe connected to the liquid valve (See Fig.15).

Note:When welding, the valve should be covered by wet cloth in order to avoid the high temp hurt.

36


HEAT PUMP WATER HEATER (NORTHERN EUROPE)

MAINTENANCE

4 EXPLODED VIEWS AND PART LIST 4.1 Single Fan Exploded Views:

No.

Name of part

Part code

Quantity

1

Valve Support Sub-Assy

01715001

1

2

Compressor Support Sub-Assy

01802222

1

3

Chassis Sub-Assy

01282235

1

4

Wooden Package Base

501154042

1

5

Compressor and Fittings

00205208

1

6

Cabinet

01435103

1

7

Front Grill

22265401

1

8

Condenser Inlet Pipe

04655706

1

9

Fan Motor

150154011

1

10

Axial Flow Fan

10335401

1

11

Motor Support Sub-Assy

01705402

1

12

Top Cover

01255402

1

13

Electric Box Sub-Assy

01392129

1

14

Clapboard Assy

01242214

1

15

Condenser Assy

01122216

1

16

4-way Valve Sub-Assy

04142216

1

17

Inhalation Tube Sub-Assy

04672240

1 37


HEAT PUMP WATER HEATER (NORTHERN EUROPE)

MAINTENANCE

18

Cut-off Valve Sub-Assy

07332217

1

19

Gas-liquid Separator Assy

07255403

1

20

Bidirection Accumulator

07228741

1

21

Inflate Valve Sub-Assy

07332218

1

22

Rear Grill

01475401

1

23

Front Side Plate Sub-Assy

01312232

1

24

Rear Side Plate Sub-Assy

01305402

1

25

Capacitor CBB61

33010013

1

26

Main Board

30221602

1

27

Terminal Board

42011043

1

28

Terminal Board

42011103

2

29

Capacitor CBB65

3300002232

1

30

Transformer

43110240

1

31

AC Contactor

44010226

1

Part code

Quantity

4.2 Double Fan Exploded views:

No.

Name of part

1

Rear Side Plate Sub-Assy

01312815P

1

2

Valve Support Sub-Assy

01715001

1

3

4-way Valve Sub-Assy

04142815

1

4

Inflate Valve Sub-Assy

07332818

1 38


HEAT PUMP WATER HEATER (NORTHERN EUROPE)

MAINTENANCE

5

Accumulator

07422204

1

6

Chassis Sub-Assy

01192813P

1

7

Liquid Valve Sub-Assy

07302803

1

8

Compressor and Fittings

00205205

1

9

Front Side Plate Sub-Assy

01305430

1

10

Handle

26235253

3

11

Axial Flow Fan

10338731

1

12

Fan Motor

150154513

1

13

Motor Support Sub-Assy

01705471

1

14

Front Grill

22414102

1

15

Cabinet

01435436

1

16

Top Cover

01255262

1

17

Condenser Assy

01122808

1

18

Inhalation Tube Sub-Assy

04672820

1

19

Electric Box Assy

01393734

1

20

Upper Insulation Plate Sub-Assy

01242802

1

21

Gas-liquid Separator Sub-Assy

07225018

1

22

Lower Insulation Plate

01242804