Completed Review on Ventilation Services of Shop Drawing

Page 1


RMIT University Integrate Services Layout into Design Documentation AT5 Shop Drawing Review

Teacher name: David Anderson Student name: Deng Luolin Student number: s3749594 Due date: 29.05.2020

Contents 1: Process of the air flow .................................................................................................................... 1 2: Differentiation of Engineer’s Drawing and Shop Drawing .................................................................. 1 3: Duct Size compare ......................................................................................................................... 2 4: Air flow at each grille checked ........................................................................................................ 4 5: Total air flow calculated.................................................................................................................. 5


1: Process of the air flow The process of the air flow through as shown in Figure 1, 5 steps including 1. Outside air flow in through an exhaust damper 2. The air continuing flow into an air handler system (including the air-conditioning unit), and being heated up or cooled down. 3. Those air that being process in step 2 will continuing flow through a grille and then supply to working space 4. Recirculated air will flow back to the building and mix with the outside fresh air 5. Or being exhausted as exhaust air.

Air-conditioning units PAC1 TEMPERZONE OPA 201

https://www.temperzone.biz/AUHome/Products/624-OPA-201RKTYH/

Figure 1: Drawing of the air flow process This assessment requires us to review a single run of ductwork on a mechanical services shop drawing and compare that to run of duct on the consulting engineer’s drawing. Items required to be compare including the duct size, airflow at each grille and calculating the total airflow for duct run, making sure they are corresponding or the shop drawing should always up to standard requirement of engineer’s drawing. The project allocated to me is the Medical Care, Duct run 17. It is a set of duct work run for supplying air. Particular term further finding will be defined and explained in the report. 2: Differentiation of Engineer’s Drawing and Shop Drawing Mechanical Consulting Engineer’s Drawing provides only basic information about design of the system, equipment, airflows, duct sizing and duct insulation. Comparing to the Engineer’s Drawing, the shop drawing has more focus on how and where the system will fit, providing detailed information for the fabrication and installation of the system including equipment, ductwork, air diffusers, pipework, control systems.

Student name: Deng Luolin

Student number: s3749594

1|P a ge


3: Duct Size compare Duct run 17

Duct run 17

1

1

2 2

3

3

4

Duct run 17 SHOP DRAWING CONSULTANTS DRAWING DUCT 1 WITH 75MM INSULATION 675 X 375 (750 X 450)* 600 X 350 DUCT 2 450 X 300 600 X 300 DUCT 3 300 X 200 400 X 300 DUCT 4 250 X 250 * FLEXIBLE DUCTWORK - REFER TO FLEXIBLE DUCTWORK SCHEDULE (FIGURE 2) IN CONSULTANTS DRAWING –FLEXIBLE DUCT IS SELECTED BASE ON AIR FLOW RATE * DUCT 1 DETAIL WITH 75MM INSULATION REFER TO FIGURE 3 (next page)

Student name: Deng Luolin

Student number: s3749594

2|P a ge


All the selected flexible ductwork in Shop drawing has been checked to suit the air flow rate of grille.

Figure 2: Flexible ductwork schedule

(Size of airflow) (Size of sheet metal case) (750 – 75) x (450 – 75) 675 x 375 (Size of airflow)

Figure 3: Detail of Duct 1 with 75mm insulation

Student name: Deng Luolin

Student number: s3749594

3|P a ge


4: Air flow at each grille checked All the flexible ductwork have used to suit air flow rate of each grille.

AIR FLOW RATE AT EACH GRILLE L/s SHOP DRAWING CONSULTANTS DRAWING DUCT 1 WITH 260 DUCT 1 WITH 80 INSULATION 80 INSULATION (675 X 375) 150 (600 X 350) DUCT 2 140 DUCT 2 150 (450 X 300) 140 (600 X 300) 260 120 120 DUCT 3 150 DUCT 3 140 (300 X 200) 60 (400 X 300) 140 FLEXIBLE DUCTWORK – DUCT 4 60 REFER TO SCHEDULE TABLE (250 X 250) 150

Student name: Deng Luolin

Student number: s3749594

4|P a ge


5: Total air flow calculated Calculation of total air flow refer to red text.

TOTAL AIR FLOW L/s SHOP DRAWING DUCT 1 WITH INSULATION (750 X 450) 490 DUCT 2 (450 X 300) 400 DUCT 3 (300 X 200) 210 FLEXIBLE DUCTWORK - REFER TO SCHEDULE TOTAL 1100

Student name: Deng Luolin

CONSULTANTS DRAWING DUCT 1 WITH INSULATION (600 X 350) DUCT 2 (600 X 300) DUCT 3 (400 X 300) DUCT 4 (250 X 250) DUCT 3 (400 X 300)

Student number: s3749594

80 530 280 210 1100

5|P a ge