International Solar PV Power Presentation by JMV LPS LTD Place JMV Office in Noida Dt.25th July2017 Thanks note to the all International guest visted our office to attend Solar PV and other renewable Green method Presentaton for Generating Power Roof Top, Ground Mounted, Canal Top ,Water Floating along with Hybrid Combination like Wind Power Generator Machine and High Energy Storage Batteries. Your self introduction for related to present Power Generation ,Transmission and distribution along with presence of Solar PV Power Plant in your country ,this information is realy benefit to India and mile stone how to work in your country to support More & More Solar Pv Power for Larger Power Production Mega Watt up to your Home requirement in Watt/Kilo Watt Level. You can utilize Solar Power base Products in your cities and Urban Solar Power LED Street Light ,Trafiic Light ,out door CCTV Camera and many other Equipments. The Solar PV Plant can be Install near to your Facility connecting to distribution line from if your Power supply agencies or you can develop Stand along Off Grid with Battery Back for use when dark in Night. The power generation through Solar PV is Economical for installation waste land can be utilige and your are countributing carbon free environment to the world for that plz accept in advance big great Salute for supporting our earth towards Green and Carbon Free Environment. India belive Harmony with all Nabours and also support earth for peace and green life. India also very much fast growing country who can surve Latest better in Design which meets International all Electrical Standard with Economical in Cost as Compare to other Forward Countries. India have team of Young Talent who can decide Fast and take dynamic decision to support india and Their international Industries requirements. Power Generation ,Transmisson ,Distribution Facilties for Indian and International Requirements. Transportation for Passenger and Goods Bus,Train and Vechile which Complies International Requirements. Telecommunication Network Facilties for Indian and International Requirements. Building and other Infrastructure for Cities Facilties for Indian and International Requirements. JMV LPS LTD is Indian Company belive Make in India and Innovation of Products Fall under Earthing and Protection to best Practice of Electrical Equipment instalation and Safety of Products along with Human Being Products as below: Maintenance Free Earthing(Copper Bonded ROD, Earthing Enhance Compound , Earth Pits) Follow UL ,IEC,IEEE
Exothermic Joints ( Permanent Welding with 100% Surface Contact Suitable all Bi-Metals) UL ,IEC,IEEE Theft Free/Theft Protected Long Run in Drum Roll Copper Clad Steel/ Copper Clad Aluminum with or Without Insultation. Follow IEC,IEEE
Surge Protection for Power and Communication Ports Follow IEC,IEEE External Lightning Protection as per IEC 62305 and Early Stream Emision Type as per NFC17102/UNE21-186. Cable Jointing Kit for all LT Cable (Quick Lock and Quick Open Reusable) condition up IP68 and Flame Proof. We would like Further extend our support to develop our relation with your Govt Project Official and PVT Partners Handling above Segment along with our Special Support to Supply of Equipment Disaster Management Early Warning ,Earth Quake,Flood Warning,Sea High Tide, and Lighting to keep your people safe. Thanking you again for Visiting our Office in India With Regards Family JMV LPS LTD Team Mr.Neeraj Saini Protection.
Head of Company and Insparation for JMV Innovative Product for Earthing &
Mr.Mahesh Chandra Manav Head of Branding and belive Make In India Govt of India Programme. Mrs.Mousumi C
From Sales
Ms.Manisha Singh from Technical and Design Ms.Meenakshi from MD Desk and OPS Contact us Sales@jmv.co.in; neeraj@jmv.co.in Visit webpage www.jmv.co.in T-91-1204590000 We have some photograp while presentation is somebody require plz share their Gmail IT for Sahring drive related to photo. Special Thanks from India
Central Institute for Rural Electrification (Rural Electrification Corporation Ltd )
Solar Power Generation Grid Enabling 10th July, 2017-04 August, 2017 ITP Participants List Sl. No. 1
Name of the Executive Mr. G RAJESHWAR RAO
Country
Designation
ITEC / SCAAP
CIRE, HYD
Executive
ITEC ITEC ITEC
2
MR. MURIED SOFIZADA
AFGHANISTAN
Power Engineer, Substation Manager
3 4
Mr. BINOD SHARMA MS.TSHERING PELDEN
BHUTAN BHUTAN
TECHNICAL OFFICER Junior Engineer
5
DR. MUNA SABAH QASIM ALJAWABIR
IRAQ
6
MR. SANI LAWAN
NIGER
7 8
MR.ALI SEYNI ABDOULAHI MR. STEPHEN SIRI
NIGER SOUTH SUDAN
9
MR. THILANKA ALWIS
SRI LANKA
Consultant (Chemical and Process Engineering)
ITEC
10 11
MR. THOI NGUYEN MR.SALIFU GINDEH
VIETNAM GAMBIA
University Lecturer Mechanical Engineer
ITEC SCAAP
12
MR.STEPHEN WEKESA MANG'ENI
KENYA
INSTRUCTOR
SCAAP
13
MS.YUCABETH NYABOKE NYAMWAYA
KENYA
INSTRUCTOR
SCAAP
14 15
MR MANYORI JUMA KAPESSA MR.JUMBE OMARI JUMBE
TANZANIA TANZANIA
ELECTRICAL ENGINEER Mechanical Engineer
SCAAP SCAAP
Director of follow up division LABORATORY ASISTANT technical responsible ASSISTANT LECTURER
ITEC ITEC ITEC ITEC
A Warm Welcome To All At JMV LPS LIMITED
Global Threat and Impact Global Warming Reducing Water Sources for Drinking Ground Water Level Lowering Increasing Carbon on Environment Low Green Color on Earth(Tree)
Why This is happening We feel that Nature is Free and Gifted Thinking for ourself not for our future Generation Our Thinking is very Limited to ourself and Surrounding
What We all have do Use Nature Precisely and Think for Globe Sun Wind Water and Earth Maintain Harmony with all Four Balance between Need and Greed All Life are Equal Important and There is Limitation Lesson to Gain Use and Save
Welcome SUN to Ground Let Use for All
Method of Present Power Generation • • • • • • • • • • • • • • • • • •
Power Generation use of Coal , Gas, Liquid Fuel Power Generation use of Wind Power Generation use of Water(Hydro) Power Generation use of Waste/Baggass Power Generation through Fly Wheel Power Generation Through Use Chemical & Nuclear Power Generation Through other Kinetic Energy Require Huge Infrastructure and Raw Material (Storing and Handling). Disposal has to Handle Impact on Environment (Pollution) Vibration and Sound Pollution Reducing Natural Resources for Burning to Generate Power . High Cost of Generation and Further Loss due to Long Transmission , distribution and Theft. Huge to Pay Cost for SCRAP and Threat for Disposal. Dependency with Huge Staff and Their Union High Maintenance and Protection from Accidents Incidental Payments Cycle Increase and Power Generation Reduce over Period of Time. Resale value Difficult
Follow Sun Power /Follow Green Power /Follow Free Generation & Store of Power
Safe Practice in Earthing and Protection
• • • • • • • •
Solar Power Now Changing Many Phases Use with Genset Use with Wind Power Use with High Energy Storage(Battery) Installation on Ground/Cannel Mounted Installation on Roof (Building) Installation on Water (Floating) Installation on Building(BIPV Building Integrated Transparent Photovoltaic Solar Glass
External/Internal Surge Source
An Arcing Fault is the flow of current through the air between phase conductors or phase conductors and neutral or ground. Concentrated radiant energy is released at the point of arcing an a small amount of time resulting in Extremely High Temperature.
Fire Accident in Solar PV Power Plant Reason Lose Contact Earthing Disorder and Lightning
Solar Panel Fire Accident
More Picture Fire in Solar PV Power Plant
Damages Due To Lightning
Fire Component Level
Solar PV Power Plant
Surge in Systems and Result
Surge in DC Application
Sikhana to Padega Hi Follow Electrical Safety
Follow Safety in Electrical Installation Shocks
Earthing Design and Require Result
• For substation Large Power below 1.00Ohm • For substation Small Power below 2.00Ohm • SCADA/TELECOM and Automation For substation Large Power below 0.50Ohm • Tower and Other Structure between 8-15Ohm • Lightning Surge Protection 50KA below 5Ohm or 100KA between 8-15Ohm • Follow Standard IEC /IEEE • Recommended use of Hybrid Metal to Protect from Theft Copper Clad Steel/Alumineum Clad Copper • Exothermic weld IEEE 837
Products
Copper Clad Steel/ Aluminium Conductor For Electrical Installation
The Copper Clad Steel Grounding Conductor is made up of steel with the coating of 99.99% pure copper. These conductors/ wires or strands are equipped with the strength of steel with the conductivity and copper with the better corrosion resistance property. The concentric copper cladding is metallurgic ally bonded to a steel core through a continuous, solid cladding process using pressure rolling for primary bonding. The copper cladding thickness remains constant surrounding steel. We use different steel grades for the steel core result in Dead Soft Annealed, High strength and Extra High Strength Characteristics. The Copper Clad Steel Wire yields a composite conductivity of 21%, 30% and 40% IACS, and available in Annealed and Hard drawn. We are delivering products with varied conductivity and tensile strength as per the customer need. Further, the wire can be processed to be silver plated or tinned copper clad steel wire.
Most Efficient Joint Process
It is efficient and superior to all existing surface –to-surface mechanical retention connectors. https://www.youtube.com/watch?v=ijdF5hK-MAk
What is Exothermic Welding System? Copper to Bi-Metal and Aluminium Types of Exothermic Joints:
Possible to join any bi metal except aluminum Exothermic welding is a process of making maintain free highly molecular bonding process is superior in
performance connection to any known mechanical or compression-type surface-to-surface contact connector. Exothermic weld connections provide current carrying (fusing) capacity equal to that of the conductor and will not deteriorate with age. It offers Electrical connections between two or more copper to copper and copper to steel conductors. Highly portable method as it does not require any external power source or heat source, so it can be done almost anywhere. It provides strong permanent molecular bond among metallic conductors that cannot loosen and further will not deteriorate with age. Connection does not corrode with time and it offers permanent conductivity.
Copper Clad Steel Solid ROD and Conductor
LIGHTNING FORMATION
Facts About Lightning • • • •
A strike can average 100 million volts of electricity Current of up to 200,000 amperes Can generate 54,000 oF 10/350MicroSec/50KA Fault Current/Discharge in Nano Sec
Protection Earthing Design100KA Fault Current/Joints Exothermic /Flexible Down Conductor with Shortest Route & Less Corner
• Lightning Protection Standard use in India ( IEC 62305-3 and 4) Working Principle Angular No Compromise with Design Max Protection 30Mtrs from One No Product warranty from Manufacturer High Maintenance Require NFC17-102(2011) Now European Standard(ESE LA) Working Principle Radius Compromise with Design Possible with Increasing Qty of ESE Max Protection 109 Mtr. Radius from One Manufacturing Warranty and Test Certificate for Products Available Maintenance on Call Basis
Lightning Risk assessment Study is actually the measure of risk of a lightning strike and probability of damages. As Per IEC62305-2.
All these calculations are based on: lightning strike density in that particular area (provided by OMV i.e. Ng = 8), Danger for people, Occupation coefficient of structure, Relative location of site, Fire Risk, Associated services, Electrical Lines, Lightning Protection Level, Surge Arrestor and Dimensions of installation.
Lighting Strike Density (Ng)
It is the measure of lightning strikes per kilometre square per year in the particular area. Higher the lighting strike density, higher the probability of lightning strike which needs higher level of lightning protection level. Danger for People (h) It is the factor of presence of people and panic in the building in case of a lightning strike
No particular danger
1
Low panic level(<=2 floors, < 100 persons
2
Medium risk of panic (< 1000 persons)
5
Difficult to evacuate (disabled people, hospitals)
5
High risk of panic (> 1000 persons)
10
Hazard for surroundings or environment 20 Contamination of surroundings or environment
50
Occupancy Coefficient (Lf1) It is the risk reduction factor with respect to theoccupancy of the building / installation. For example, loss due to lighting strike is higher in hospital as compared to a store / warehouse. Structure unoccupied
0.1
Structure normally occupied
0.01
Relative Location of Site (Cd) It is the risk reduction factor with respect to the location and surrounding of the building / installation. For example, chance of lighting strike is minimized if the building is near to a high tower. Structure surrounded by higher objects 0.25 or trees Structure surrounded by similar or 0.5 lower objects Isolated structure-No other objects 1 nearby Isolated structure on top of a hill or a 2 hillock Fire Risk (rf) It is the risk reduction factor with respect to the flammability of the material present in the building / installation. For example, in case of lighting strike, loss will be very high at a gas station as compare to the cement store.
Explosion
High
1
0.1
Ordinary
0.01
Low
0.001
Risk Assessment Calculator as per IS/IEC 62305
PASSIVE PROTECTION SYSTEM
The Simple Rod air terminal is composed from a metallic rod with 2 to 8 m height dominating the structure to protect, and linked to 2 down conductors minimum, and 2 earthing systems. The protection radius ensured by this air terminal which is limited to 30 m more or less (Protection level IV, height = 60 m), especially dedicated to the protection of small structures or areas like towers, chimneys, tanks, water tower, antenna mastsâ&#x20AC;Ś The EN 62305-3 standard describes the installation procedure for these air terminals. 13 Simple Rods, 13 down conductors, and 13 earthing systems are necessary to ensure the protection below :
The meshed cage protection is composed from a meshing in roof surface and in the front face around the building. Surrounding the roof surface, and on high points, capture points are positioned. A conductorsâ&#x20AC;&#x2122; network is placed at the outer perimeter of the roof. This network is completed by transverse conductors. The size of the meshing is 5 to meters, and depends on the efficiency needed for the protection. On the front face of the building, the down conductors are linked at the top to the meshing of the roof. And, down, to specific earthing systems. The distance between two conductors is 10 to 25 meters, and depend on the efficiency needed for the protection. The EN 62305-3 describes the installation procedure for this method. Generally, this method is heavy and expensive, due to the complexity of the structures to protect. 26 capture points, 26 down conductors and a grounded loop earthing system are necessaries to ensure the protection of the structure here below :
The catenary wires protection is a method closed to the meshed cage principle, because it is constituted with meshing of the conductors far from the structure to protect, to avoid any contact with lightning current. Catenary wires are located over the structure to protect, connected to down conductors and specific earthing systems. The width of the meshing and distance between the down conductors must respect the same rules as for the meshed cage. The EN 62305-3 describes the installation procedure for this method. Generally, this method is heavy and expensive, due to the complexity of the structures to protect.
The ESE air terminal is a terminal which enables to generate artificially an upward leader earlier than a simple rod, with an ionization system, in order to establish a special impact on its point. The capture of the lightning strike being faster than a simple rod, this technology enables to benefit from larger protection areas, ensuring protection for large dimensions structures. The generated protection radius depends on the early streamer emission value of the air terminal (Î&#x201D;t in Âľs), its height, and the efficiency of the protection. The protection radius ensured by this type of air terminal is 120 m (Protection level IV, height = 60 m , early streamer emission time 60Âľs) The NFC 17-102 standard describes the installation procedure for this type of air terminal. The installation of this type of air terminal is easy and cheaper than other technologies. It can protect whole buildings with one E.S.E. air terminal. It enables the protection of a structure and its environment, the protection of opened areas and well integrate in the architecture of a structure without aesthetic alteration. 1 ESE, 2 down conductors and 2 earthing systems are necessary to ensure the protection below :
Installation
ESE AT with radius protection form 32 mtr to 107 mtr. DMC Insulator .
GI/FRP Mast .
Down Conductor Copper / Copper Cadmium Cable 70 sq. mm Copper Bonded Ground Earthing
Thimble
Joint all phase wire/ cable with the help of crimping tools and lugs Step – 1
Separation Sheet Fixed the separation sheet between all wires/ cables
Step – 2
Gel / Silicon Close the filled Silicon enclosure from top and bottom , complete installation is done.
Step – 3
Features : Provides cable with cable connections and jointing wires in switchboard / electric boxes Being a jelly it can be easily fit into molds of any shape and size. Helps in safeguarding electrical connections and also protects electrical connection joints from catching fire, sparking and leakage current. Eradicates all the possibilities of fire, electric shocks and sparks, etc. causes due to improper electrical connection joints and safeguards structure, equipment and person. Offers safety to your electrical joints from ageing, corrosion, moisture and also observes leakage current. Advantages : Nontoxic Insulating Highly reliable operation Maintenance Free Repairable Cost Effective High repeat value Elasticity Shape retention