Config 1 – 4 cellular offices individually controlled with a presence detector and or manual switch in each.
Windows
Windows
Windows
CH6
CH6
CH7
CH1
CH2
CH2
CH3
Windows
CH5
SW1
CH4
SW2
L
SW3
SW4
N E PL
Detector/scene plate inputs
Switch inputs
Each switch operates luminaires within the same colour dashed line. Upon exiting the space any luminaires left on will switch off after an adjustable time out period.
Dimmable Luminaires – 20% Emergency Luminaires
Luminaires daylight link – window row only dimmable SW1
SW2
SW3
SW4 Emergency Lighting Test
Config 2 – 4 cellular offices individually controlled with a presence detector and or manual switch in each.
Windows
Windows
Windows
CH6
CH6
CH7
CH1
CH2
CH2
CH3
Windows
CH5
SW1
SW2
CH4
L
SW3
SW4
N E PL
Detector/scene plate inputs
Each switch operates luminaires within the same colour dashed line. Upon exiting the space any luminaires left on will switch off after an adjustable time out period.
Switch inputs
Daylight Switching Emergency Luminaires
Luminaires daylight link – window row only daylight switching. SW1
SW2
SW3
SW4 Emergency Lighting Test
Config 3 – Open plan office working in presence mode with channels 5, 6 and 7 daylight dimming for perimeter row(s).
Windows
CH6
CH5 Windows
CH1
CH2
CH3
CH4
CH7
Detector/scene plate inputs
Upon entering the space luminaires will automatically switch on.
Luminaires daylight link – window row only dimmable
Upon exiting the space any luminaires left on will switch off after an adjustable time out period.
Dimmable Luminaires – 20%
Emergency Luminaires
Config 4 – Open plan office working in presence mode with channels 5, 6 and 7 daylight switching for perimeter row(s).
Windows
CH6
CH5 Windows
CH1
CH2
CH3
CH4
Detector/scene plate inputs
Upon entering the space luminaires will automatically switch on.
Luminaires daylight link – window row only daylight switching.
Upon exiting the space any luminaires left on will switch off after an adjustable time out period.
Daylight Switching
Emergency Luminaires
CH7
Config 5 – Open plan office working in presence mode with channels 1–4 daylight dimming for perimeter row(s). Detector/scene plate inputs Windows
CH1
CH2
CH3
CH4
CH5
CH7
CH6
Upon entering the space luminaires will automatically switch on.
Luminaires daylight link – window row only dimmable
Upon exiting the space any luminaires left on will switch off after an adjustable time out period.
Dimmable Luminaires – 20%
Emergency Luminaires
Config 6 – Open plan office working in presence mode with channels 1–4 daylight switching for perimeter row(s). Detector/scene plate inputs Windows
CH1
CH2
CH3
CH4
CH5
CH7
CH6
Upon entering the space luminaires will automatically switch on.
Luminaires daylight link – window row only daylight switching.
Upon exiting the space any luminaires left on will switch off after an adjustable time out period.
Daylight Switching
Emergency Luminaires
Config 7 – Standard open plan office arrangement, operating in presence mode. Detector/scene plate inputs Windows
CH1
CH2
CH3
CH4
CH5
CH7
Upon entering the space luminaires will automatically switch on.
CH6
Upon exiting the space any luminaires left on will switch off after an adjustable time out period.
Emergency Luminaires
Config 34 – Two cellular offices with a detector and scene plate in each. Option for local switch in each office.
Windows
CH1
Windows
CH2
CH3
CH7
SC1 100% SC2 75% SC3 50% SC4 25%
SC1 100% SC2 75% SC3 50% SC4 25%
CH4
CH5
CH6
SW1
L
SW2
N E
Detector/scene plate inputs
PL
Switch inputs
Each switch operates luminaires within the same colour dashed line.
Luminaires daylight link – all luminaires in each office dim together
Upon exiting the space any luminaires left on will switch off after an adjustable time out period.
Dimmable Luminaires – daylight linking, Scene 1 only Emergency Luminaires
SW1
SW2
Emergency Lighting Test
Config 35 – 4 cellular offices with a scene plate in each. Option for local switch in each office. Detector in each.
Windows
CH5
Windows
CH6
CH6
SC1 100% SC2 75% SC3 50% SC4 25%
CH1
CH2
SW1
CH2
SW2
CH7 SC1 100% SC2 75% SC3 50% SC4 25%
SC1 100% SC2 75% SC3 50% SC4 25%
CH3
CH4
L
SW3
Windows
SC1 100% SC2 75% SC3 50% SC4 25%
Windows
SW4
N E
Detector/scene plate inputs
PL
Switch inputs
Each switch operates luminaires within the same colour dashed line.
Luminaires daylight link – all luminaires in each office dim together
Upon exiting the space any luminaires left on will switch off after an adjustable time out period.
Dimmable Luminaires – daylight linking, Scene 1 only Emergency Luminaires
SW1
SW2
SW3
SW4 Emergency Lighting Test
Config 36 – Large office/meeting room with detector used for lux and occupancy and scene plate and opiton for master all on switch 1 scene plate. Detector/scene plate inputs
GROUP 1
CH1
CH2
SC1 100% SC2 OFF SC3 50% SC4 25%
CH3
CH4 L
GROUP 2
GROUP 3
CH6 SC1 100% SC2 75% SC3 50% SC4 25%
Switch inputs
SC1 100% SC2 75% SC3 50% SC4 25%
N E PL
GROUP 4
CH5
CH7
SC1 100% SC2 75% SC3 50% SC4 25%
MASTER SWITCH
Master Switch
Upon exiting the space any luminaires left on will switch off after an adjustable time out period.
Luminaires daylight link – window row only
Emergency Luminaires
Master Switch
Emergency Lighting Test
Dimmable Luminaires
Config 37 – Large office or meeting room with LUX refereenced on channels 1-3 only. Detector used for LUX and occupancy, 1 scene plate. Detector/scene plate inputs
CH1
GROUP 1
GROUP 2
SC1 100% SC2 75% SC3 50% SC4 25%
SC1 100% SC2 OFF SC3 50% SC4 25%
CH2
CH3
CH4 L
GROUP 3
Switch inputs
SC1 100% SC2 75% SC3 50% SC4 25%
CH6
N E PL
GROUP 4 SC1 100% SC2 75% SC3 50% SC4 25%
CH7
CH5
MASTER SWITCH
Master Switch Luminaires daylight link – window row only
Upon exiting the space any luminaires left on will switch off after an adjustable time out period. Dimmable Luminaires
Emergency Luminaires
Master Switch
Emergency Lighting Test
Config 38 – Large office or meeting room with detector for occupancy and no LUX on any channels. 1 scene plate. Detector/scene plate inputs
CH1
GROUP 1
GROUP 2
SC1 100% SC2 75% SC3 50% SC4 25%
SC1 100% SC2 OFF SC3 50% SC4 25%
CH2
CH3
CH4 L
GROUP 3
Switch inputs
SC1 100% SC2 75% SC3 50% SC4 25%
CH6
N E PL
GROUP 4 SC1 100% SC2 75% SC3 50% SC4 25%
CH7
CH5
MASTER SWITCH
Master Switch
Dimmable Luminaires
Upon exiting the space any luminaires left on will switch off after an adjustable time out period.
Emergency Luminaires
Master Switch
Emergency Lighting Test
Config 61 – 3 cellular offices working in presence mode with a detector and manual switch in each. Window row dimming.
Windows
Windows
Windows
CH7
Windows
CH6
CH5
CH1
SW1
CH2
CH3
SW2
CH4
L
SW3
N E
Detector/scene plate inputs
PL
Switch inputs
Each switch operates luminaires within the same colour dashed line. Upon exiting the space any luminaires left on will switch off after an adjustable time out period.
Dimmable Luminaires – 20% Emergency Luminaires
Luminaires daylight link – window row only dimmable. SW1
SW2
SW3
Emergency Lighting Test
Config 62 – 3 cellular offices working in presence mode with a detector and manual switch in each. Window row daylight switching.
Windows
Windows
Windows
CH7
Windows
CH6
CH5
CH1
SW1
CH2
SW2
CH3
CH4
L
SW3
N E
Detector/scene plate inputs
Each switch operates luminaires within the same colour dashed line. Upon exiting the space any luminaires left on will switch off after an adjustable time out period.
PL
Switch inputs
Daylight Switching Emergency Luminaires
Luminaires daylight link – window row only daylight switching. SW1
SW2
SW3
Emergency Lighting Test
Config 63 – 4 cellular offices working in presence mode with a presence detector and/or manual switch in each. Window row dimming.
Windows
Windows
Windows
Windows
CH3
Windows
CH6
Windows
CH5
CH1
SW1
CH2
CH4
CH7
SW2
L
SW3
SW4
N E
Detector/scene plate inputs
PL
Switch inputs
Each switch operates luminaires within the same colour dashed line. Upon exiting the space any luminaires left on will switch off after an adjustable time out period.
Dimmable Luminaires – 20% Emergency Luminaires
Luminaires daylight link – window row only dimmable. SW1
SW2
SW3
SW4 Emergency Lighting Test
Config 64 – 4 cellular offices working in presence mode with a presence detector and/or manual switch in each. Window row daylight switching.
Windows
Windows
Windows
Windows
CH3
Windows
CH6
Windows
CH5
CH1
SW1
CH2
SW2
CH4
CH7
L
SW3
SW4
N E
Detector/scene plate inputs
Each switch operates luminaires within the same colour dashed line. Upon exiting the space any luminaires left on will switch off after an adjustable time out period.
PL
Switch inputs
Daylight Switching Emergency Luminaires
Luminaires daylight link – window row only daylight switching. SW1
SW2
SW3
SW4 Emergency Lighting Test
Config 65 – 3 cellular offices working in presence mode with a detector and/or switch in each. Window row dimming.
Windows
Windows
Windows
SW3
Windows
Windows
CH5
CH7
CH1
CH2
SW1
CH4
CH3
CH6
SW2
SW3
L N E
Detector/scene plate inputs
PL
Switch inputs
Each switch operates luminaires within the same colour dashed line. Upon exiting the space any luminaires left on will switch off after an adjustable time out period.
Dimmable Luminaires – 20% Emergency Luminaires
Luminaires daylight link – window row only dimmable. SW1
SW2
SW3
Emergency Lighting Test
Config 66 – 3 cellular offices working in presence mode with a detector and/or switch in each. Window row daylight switching.
Windows
Windows
Windows
SW3
Windows
Windows
CH5
CH7
CH1
CH2
SW1
CH4
CH3
CH6
SW2
SW3
L N E
Detector/scene plate inputs
Each switch operates luminaires within the same colour dashed line. Upon exiting the space any luminaires left on will switch off after an adjustable time out period.
PL
Switch inputs
Daylight Switching Emergency Luminaires
Luminaires daylight link – window row only daylight switching. SW1
SW2
SW3
Emergency Lighting Test
Config 67 – Open plan office with a Graduated dimming group and separate occupancy dimming group on a single LCM. Detector/scene plate inputs Windows
Windows
CH1
CH2
CH3
L
Switch inputs CH4
CH5
N E PL
CH7
CH6
SW1
SW1
SW2
Each switch operates luminaires within the same colour dashed line.
Luminaires daylight link – graduated dimming from window row.
Upon exiting the space any luminaires left on will switch off after an adjustable time out period.
Dimmable Luminaires
SW2
Emergency Luminaires
Config 68 – Open plan office with a Graduated dimming group and separate occupancy dimming group on a single LCM.
Windows
CH1
CH2
CH5
SW1
CH3
CH7
CH4
CH6
L
SW2
N E
Detector/scene plate inputs
Each switch operates luminaires within the same colour dashed line. Upon exiting the space any luminaires left on will switch off after an adjustable time out period.
PL
Switch inputs
Dimmable Luminaires Emergency Luminaires
Luminaires daylight link – graduated dimming from window row. SW1
SW2