Sav carbon reduction assessment 1 x xrgi 20 plantroom 2 25 06 2014

Page 1

SAV/CHP/SAV-106259/RS/25.06.2014 Claremont Hotel - plantroom 2 LoadTracker CHP (XRGI 20G) - CRA (Carbon Reduction Assessment)

Please note that the results presented in this assessment are specific to XRGI 20G LoadTracker Number of CHP units at 20 kWe

1

Recommended heat storage vessel

at least 500 ltr per CHP

Type of usage

Hotel

Data reference

Mike Glanfield 17.06.2014

of

Epsilon

e-mail

on

1.0 Summary of Usage: Annual electricity consumption

252,044 kWh

Electricity price (without CCL)

13.53 p/kWh

Annual gas consumption

334,871 kWh

Gas price (without CCL)

5.114 p/kWh

1.1 CO2 Emission Factors used: • For grid electricity = 0.519 kg/kWh • For grid displaced electricity = 0.519 kg/kWh • For gas = 0.216 kg/kWh 2.0 Carbon Footprint of Project User Centre:

Carbon Footprint

203,143 kg CO₂ pa

250,000

(a)

200,000

CO₂ (CHP)

170,517 kg CO₂ pa

150,000

Net reduction

(b) 32,626 kg CO₂ pa

kg CO2/year

CO₂ (conv)

100,000 50,000 -

Conventional Gas (CHP)

Gas (boiler)

LoadTracker Grid electricity

By introducing a CHP, a reduction of 32.6 tonnes of CO₂ emissions (32,626/203,143 = 16%) could be expected relative to a conventional mains supply/gas boiler system. Notes: (a) = (electricity consumption x 0.519) + (gas consumption x 0.216) =(252,044 kWh x 0.519) + (334,871 kWh x 0.216) = 203,143 CO₂ pa (b) = (CHP gas consumption x 0.216) + (supporting boiler gas consumption x 0.216) + (electricity consumption x 0.519) - (CHP electricity production x 0.519) =(399,827 kWh x 0.216) + (61,956 kWh x 0.216) + (252,044 kWh x 0.519) - (115,681 kWh x 0.519) = 170,517 kg CO₂ pa