Sav carbon reduction assessment 1 x xrgi 20 plantroom 2 25 06 2014

Page 1

SAV/CHP/SAV-106259/RS/25.06.2014 Claremont Hotel - plantroom 2 LoadTracker CHP (XRGI 20G) - CRA (Carbon Reduction Assessment)

Please note that the results presented in this assessment are specific to XRGI 20G LoadTracker Number of CHP units at 20 kWe

1

Recommended heat storage vessel

at least 500 ltr per CHP

Type of usage

Hotel

Data reference

Mike Glanfield 17.06.2014

of

Epsilon

e-mail

on

1.0 Summary of Usage: Annual electricity consumption

252,044 kWh

Electricity price (without CCL)

13.53 p/kWh

Annual gas consumption

334,871 kWh

Gas price (without CCL)

5.114 p/kWh

1.1 CO2 Emission Factors used: • For grid electricity = 0.519 kg/kWh • For grid displaced electricity = 0.519 kg/kWh • For gas = 0.216 kg/kWh 2.0 Carbon Footprint of Project User Centre:

Carbon Footprint

203,143 kg CO₂ pa

250,000

(a)

200,000

CO₂ (CHP)

170,517 kg CO₂ pa

150,000

Net reduction

(b) 32,626 kg CO₂ pa

kg CO2/year

CO₂ (conv)

100,000 50,000 -

Conventional Gas (CHP)

Gas (boiler)

LoadTracker Grid electricity

By introducing a CHP, a reduction of 32.6 tonnes of CO₂ emissions (32,626/203,143 = 16%) could be expected relative to a conventional mains supply/gas boiler system. Notes: (a) = (electricity consumption x 0.519) + (gas consumption x 0.216) =(252,044 kWh x 0.519) + (334,871 kWh x 0.216) = 203,143 CO₂ pa (b) = (CHP gas consumption x 0.216) + (supporting boiler gas consumption x 0.216) + (electricity consumption x 0.519) - (CHP electricity production x 0.519) =(399,827 kWh x 0.216) + (61,956 kWh x 0.216) + (252,044 kWh x 0.519) - (115,681 kWh x 0.519) = 170,517 kg CO₂ pa


3.0 Cost Savings: Comparisons are shown between the operational costs of a conventional system (mains supply/gas boiler) and 1 x LoadTracker 20G CHP unit.

Operational Cost Electricity Gas (Boiler) Gas (CHP)

0

Total

£51,227

CHP £18,450 (d) £3,168 (f) £20,447 (g) £42,065

60,000 50,000 40,000 30,000 20,000 10,000 £/year

Conv. £34,102 (c) £17,125 (e)

0

Conventional Gas (CHP)

LoadTracker

Gas (boiler)

Grid electricity

The use of LoadTracker CHP would result in annual savings of £51,227 - £42,065 = £9,161 pa relative to a conventional mains supply/boiler system. Notes: (c) = 252,044 kWh x 0.1353 £/kWh = £34,102 (d) = Assessed by LoadTracker programme (e) = 334,871 kWh x 0.05114 £/kWh = £17,125 (f) = Assessed by LoadTracker programme (g) = Assessed by LoadTracker programme 4.0 LoadTracker CHP Contribution to Electrical Needs of User Centre Typical seasonal variations in electricity consumption have been assumed, in producing an approximate consumption pattern for the User Centre. 25,000

20,000

kWh/month

15,000

10,000

5,000

‐ Jan

Feb

Mar

Apr

May

Site electricity demand

Jun

Jul

Aug

Sep

Oct

Nov

Dec

LoadTracker electricity production

CHP accounts for 115,681 kWh / 252,044 kWh = 46% of electricity requirements of the User Centre.


5.0 LoadTracker CHP Contribution to Heat Needs of User Centre Similarly to item 4.0, typical seasonal variations in heat requirements have been assumed. The CHP LoadTracker units can maintain a similar profile for heat production, as shown below:

45,000 40,000 35,000 30,000 25,000 kWh/month

20,000 15,000 10,000 5,000 ‐ Jan

Feb

Mar

Apr

May

Jun

Site heat and DHW demand

Jul

Aug

Sep

Oct

Nov

Dec

LoadTracker heat production

6.0 Heat Balance for User Centre Heat consumption by User Centre Heat production (CHP) Heat production (boiler) Consumption by boiler

284,640 kWh (h) 231,978 kWh (i) 52,662 kWh (j) 61,956 kWh (k)

Heat Balance Boiler 52,662 19%

CHP 231,978 81%

It can be seen that CHP account for 231,978 kWh/284,640 kWh = 81% of heat requirements of the user Notes: (h) = 334,871 kWh @ 85% (assumed boiler efficiency) = 284,640 kWh (i) = Assessed by LoadTracker programme, to give max possible CHP usage (j) = Net difference (h) - (i) (k) = Heat production (j) factored up assuming 85% efficiency = 52,662/0.85


Appendix CCL = Climate Change Levy. Extemption from this is granted to projects containing good quality CHP. Site Electrical Consumption:

May‐13 Jun‐13 Jul‐13 Aug‐13 Sep‐13 Oct‐13 Nov‐13 Dec‐13 Jan‐14 Feb‐14 Mar‐14 Apr‐14 Total

El. for Electricity for plantroom 2 plantroom 1 20,922 16,438 18,071 14,199 21,185 16,645 22,786 17,904 22,383 17,587 21,235 16,685 21,420 16,830 20,849 16,381 21,498 16,892 21,840 17,160 18,368 14,432 21,487 16,883 252,045 198,035

Site Gas Consumption:

Mar‐13 Apr‐13 May‐13 Jun‐13 Jul‐13 Aug‐13 Sep‐13 Oct‐13 Nov‐13 Dec‐13 Jan‐14 Feb‐14

34,320 42,326 32,648 17,310 14,749 15,953 19,759 19,313 33,165 25,872 47,589 31,867 334,871


Turn static files into dynamic content formats.

Create a flipbook
Issuu converts static files into: digital portfolios, online yearbooks, online catalogs, digital photo albums and more. Sign up and create your flipbook.