Contents
1. Introduction
02
1.1. Brief
02
1.2. Need for natural ventilation (a review)
03
2. Indoor thermal comfort
06
2.1. Modelling Basic Geometry
06
2.2. Modelling Windtower
06
2.3. Indoor ventilation parametric study
07
2.3.1. Duct inlet air velocity
08
2.3.2. Duct external vent area
09
2.3.3. Duct internal vent area
11
2.3.4. Indoor air temperature
13
3. Outdoor Thermal Comfort
15
3.1. Modelling geometry in site
15
3.2. Outdoor ventilation parametric study
15
3.2.1. Site inlet wind velocity
16
3.2.2. Site inlet wind direction
18
3.2.3. Direct solar radiation on the ground
20
3.2.4. Ground surface temperature
20
3.2.5. Ambient air temperature
22
4. Conclusion and Recommendations
23
4.1. Conclusions drawn from the project
23
4.2. Design recommendations
23
4.3. Limitations
24
5. Appendices
26
6. References
28
7. List of Figures
29
1
Introduction 1.1 Brief Increasing awareness of the need for energy efficient and environmentally friendly approach for building design has renewed emphasis on the integration of natural ventilation devices in buildings [1]. Traditional buildings in the hot dry region of Middle-East have developed mechanisms to catch the natural wind and direct it into the interiors, providing
Figure 1: Office space under consideration, (dimensions in meters)
passive cooling and thermal comfort for the inhabitants. This project has two main objectives; one, it investigates the potential of achieving indoor thermal comfort by varying the design of the wind tower under different climatic condition; and two, it investigates the outdoor thermal comfort by varying the site conditions under
Figure 2: Suggested working height
different climate. Study models, environment
The given climatic data represents that of a
and CFD has been simulated in Ansys work-
hot and humid region, like that of Malaysia.
bench, using DesignModeler, Mesh and Flu-
For the purpose of this study the average in-
ent. Ansys offers a comprehensive tool to
door temperatures is taken as 27°C and rela-
model and simulate air flow in a defined
tive humidity as 70%. Since people in an of-
space and offers a graphical means of under-
fice have a sedentary activity, their metabolic
standing the behaviour.
activity is rated at 1 Met, which is equal to
A predefined plan exists for which thermal comfort has to be achieved. The base geometry is in the form of an irregular polygon, largely resembling a rectangle of 9.75m by 7.5m, with niches and voids along the edge and a central courtyard. The typology is an office block with people working in a seated position at their desks.
58.2 W/m². The clothing is light and equal to 0.5clo. In most offices occupants are sitting at a computer, which is also releasing heat. To dissipate this heat as well as that of people the air is let out at this height, and thus the user plane (iso-surface) is taken at 750mm. For outdoors the user plane is taken at 1.2m, since the breeze will cool the neck region for maximum comfort.
2
1.2 Need for natural ventilation (a review) With the current trend in energy consumption it is estimated that we will need 2.5 earth to sustain us [2]. Countries like USA and UAE consume even more. Building sector is one
on the roof of a building which looks like a tower and brings in the fresh air from outside [5]. They are called Baud-Geer in the Persian Gulf area and Malqaf in the Arabic architecture [6-8].
of the major consumer of energy and it is high time that alternate means be adopted to conserve our resources. Space cooling, heating and ventilation consumes the highest percentage of energy in a building. In hot climates this is dominated by space cooling. Countries like Dubai, Egypt, Malaysia, Singapore, India etc have a high cooling demand. Another research [3] found that HVAC consumes more than 60% of total building energy demand. The aim is to produce a thermally comfortable space for the occupants.
Figure 4: A typical wind catcher in the form of a tower
Traditional solutions in vernacular architecture can be adopted or integrated with new technology to make them compatible with modern requirements [9]. In naturally ventilated buildings, occupants may accept higher temperatures than in air-conditioned buildings, and natural wind with a relatively high average velocity is more acceptable than mechanical wind [10]. In addition, de Dear and Brager [11] analysed thermal comfort in naturally ventilated buildings using the ASHRAE RP-884 database. They found that the occupants in naturally ventilated buildings pre-
Figure 3:Commercial Sector Buildings Energy End Use
ferred a wider range of conditions than those
It is interesting to note that traditional archi-
in HVAC buildings, and their indoor thermal
tecture in many hot regions adopted mecha-
comfort temperature ranges more closely re-
nisms to cool their houses naturally. One
flected the outdoor climate patterns.
such feature is the use of natural ventilation. Natural wind, not only provides a good indoor environmental quality but also provides a comfortable, healthy and hygiene indoor climate [4]. The means to achieve this, was by using a device called a wind catcher mounted
3
Figure 5: Types of traditional windcatchers
Natural ventilation uses the natural forces of wind pressure and stacks effect to aid and direct the movement of air through buildings [12]. Wind incident on a building face will produce a positive pressure on the windward side and a relative negative pressure on the leeward side. This pressure difference on the Figure 6: University of Qatar, Doha
outside as well as the pressure differences
With recent studies in thermal comfort of nat-
inside the building will drive airflow [13].
urally ventilated buildings, an increasing awareness has been generated in the bene-
Heat loss due to air change in a building is calculated using the following equation:
fits of naturally ventilated spaces. This is triggered the use of windcatchers in a more con-
Qv=ρ*V*C*dT……………………………….[1]
textual way, for instance, the University of
where Qv is heat in Watts [J/s], V is ventilation
Qatar, Doha has incorporated a brand new
rate [m³/s], C is specific heat capacity of air
windcatcher to ventilate the indoor spaces. 4
and dT is temperature difference inside and
The major drawback of natural ventilation is
outside [K]. The formula can be further sim-
that, it is dependent on wind velocity and di-
plified to:
rection which can constantly fluctuate, thus
Qv=(N*v*dT)/3…………………………….…[2]
reducing their efficiency. The presence of
(Building Services & Equipment- Volume 1 - 3rd edition. F Hall)
where N is number of air changes per hour in the building and v is the volume of the space. A much more complex relationship exists if humidity is also considered. For each specific relative humidity, a curve is plotted showing
many structures in an urban area change the wind pattern significantly, and thus taller towers have to be constructed to catch wind. Other disadvantage of the system is the limited controllability and slow charge/discharge process which are very important parameters for achieving internal thermal comfort [1].
the relation between air speed and change in
For the first part of the research, the variable
temperature.
factors are indoor temperature, duct vent areas, and inlet velocity. For the second part of the research wind velocity, direction, solar radiation, ground surface temperature and ambient
Figure 7: Cooling effect by air movement
This cooling effect is the key behind naturally ventilated buildings. They help in conserving energy by relying on natural phenomenon, maintain a good ambient air quality and, also encourage people to adapt to a large range of temperatures. Based on the research work and finding of Povl Ole Fanger, a software is available which can calculate the predicted percentage dissatisfied (PPD) given the air temperature, mean radiant temperature, air velocity, relative humidity, clo value and met value. Thermal comfort of occupants is calculated using this software for this report.
5
Indoor Thermal Comfort
2.2 Modelling Windtower The next step is to plan windtowers to catch
2.1 Modelling Basic Geometry The office plan was sketched in DesignModeler and then the surface was extruded to a height of 2.4mts. The volume so formed is the total internal space, excluding the walls. Since the factor under study is the controlled ventilation through wind tower(s), no win-
and direct wind into the room. Since there is a cost associated with each tower, the optimal solution is the one with the least number of them. Following are some towers, from the design evolution stage, which were inspired by the architectural motifs of prominent styles in Malaysia.
dows or doors are placed which could interfere with the air movement.
Figure 8: Step 1 - Sketching the office footprint and extruding the volume Figure 11: A, B- Bidirectional windcatcher; C, D- Unidirectional windcatcher
The final design consists of two windcatchers in the form of minarets, on the windward side of the block and another on the leeward side to draw out air. To drive wind effectively into the duct below, the windcatchers have a funnel shaped head, and a slender triangular Figure 9: Step 2 - Sketching courtyard, extruding and subtracting the two geometries
tower which reduces in cross sectional area to speed up airflow. Air is let into the room at two heights, near the floor at 300mm and near the ceiling at 2100mm. Air is filtered through a damper before being let inside. This is represented by vertical bars of 10mm thickness and depth of 100mm, spaced at 30mm center to center.
Figure 10: The base geometry, isometric view
6
Figure 12: Building elevations, (not to scale)
2.3 Indoor Ventilation Parametric Study The table lists the independent variables under investigation in section A, and the dependent variables on which the change was observed, in Section B. For each experiment the indoor air velocity was recorded at four critical points determined by their proximity form the inlet and outlet vents. Figure 13: Location of critical points
0.5
Section A
Section B
Inlet Velocity (m/s)
Air Velocity
1.0
1.5
2.0
External Vent Area (m²) 1.395
1.815
2.515
3.119
Internal Vent Area (m²) 0.745
1.225
1
2
Temperature (°C) 26
27
29
At four key points Predicted Percentage Dissatisfied For the four key points Area-weighted Average Velocity At the workplane Air velocity Uniformity Index At the work plane
Table 1: Parameters to assess indoor thermal comfort
7
2.3.1 Inlet Velocity It is interesting to note that the PPD for each
For the first study the vent areas and the tem-
point at any inlet velocity is well less than
perature were held constant, while the veloc-
20%, which is the limit set by ASHRAE. Even
ity was varied from 0.5m/s to 2.0m/s with an
the area weighted average velocity at the
increment of 0.5m/s for each CFD simulation.
work plane has sufficient magnitude for ther-
The external vent area was kept 1.815m², the
mal comfort at any given inlet condition. The
internal vent area at 0.825m², and the indoor
uniformity index on an average is 74.5%.
temperature at 27°C.
Since people have control of the inlet velocity The converged result was recorded and the
through fan regulators, thermal comfort can
corresponding PPD calculated, along with
be achieved at almost any condition.
the uniformity index at the work plane (0.75m). Inlet Air Velocity 0.5 Name Point-a Point-b Point-c Point-d
Work Plane
Velocity Magnitude
1.0 PPD
0.14 0.06 0.01 0.11 Area wt. Avg Velocity
8.50% 12.60% 12.60% 10.10%
0.10
73.38%
UI
Velocity Magnitude
1.5 PPD
0.27 0.19 0.18 0.31 Area wt. Avg Velocity
5.40% 6.80% 7.10% 5.10%
0.24
75.28%
UI
Velocity Magnitude
2.0 PPD
0.60 0.25 0.39 0.20 Area wt. Avg Velocity
6.10% 5.70% 5.00% 6.50%
0.35
74.96%
UI
Velocity Magnitude 0.64 0.33 0.10 0.16 Area wt. Avg Velocity
6.50% 5.10% 10.80% 7.70%
0.43
74.20%
Table 2:Results from experiment one
Velocity at Critical Points 0.70 0.60 0.50 0.40 0.30 0.20 0.10 0.00 0.5 Point-a
1 Point-b
1.5 Point-c
Point-d
PPD
2 Area-Wt Avg Velocity
Figure 14: Graph of point velocity vs inlet speed
8
UI
The velocity of points near the inlet appear to have a positive correlation with the inlet velocity, while the points away from the inlet shows an increase and then deceasing magnitude. Overall the average velocity at the work plane also increases with the increase in inlet speed. The uniformity index reaches the highest value at 1m/s and then shows a downward trend. This can be attributed to the increased turbulence due to higher velocity. The region south of the courtyard, which in near the inlet vents, has in general well distributed velocity. While in the northern end, closer to the outlet vent, there are pockets of low air speed and wind shadow regions. The maximum speeds occur near the outlet as air rushes into the vent, creating a suction effect. 2.3.2 External Vent Area For the second part of the study, inlet velocity was held constant at 1m/s, the internal vent area and temperature was the same as before i.e. 0.825m² and 27°C respectively. The external vent area was changed to face more or less wind. The design of the tower and the ducts was also kept the same, while the windcatcher mounted on top of the tower had different alternatives with different areas. This was achieved by having multiple openings or increased funnel head. The design process considers the various styles of windcatcher existing traditionally. Figure 16 on the next page shows the design implemented. Figure 15: Work plane velocity contour at different inlet speed
9
On an average there is an increase in velocity at the work plane, with the increase in area of opening. Although the change is gradual and not well marked, it can be seen that there is a fall in average velocity in the last case. Point-a shows a positive correlation and point-c shows a negative correlation with the external vent area. Point-d has an increase in velocity until reaching a certain limit and then decreases, while a fluctuating value is seen at point-b. The relationship is represented in
Figure 16: Design of windcatcher
the graph below. Total External Vent Area (m²) 1.395 Name Point-a Point-b Point-c Point-d
Work Plane
Velocity Magnitude
1.815
2.515
3.119
PPD
Velocity Magnitude
PPD
Velocity Magnitude
PPD
Velocity Magnitude
PPD
0.18 0.08 0.19 0.09 Area wt. Avg Velocity
7.10% 12.50% 6.80% 11.60%
0.27 0.19 0.18 0.31
5.40% 6.80% 7.10% 5.10%
0.29 0.08 0.15 0.46
5.30% 12.50% 8.10% 5.20%
0.43 0.20 0.10 0.06
5.10% 6.50% 10.80% 12.60%
UI
Area wt. Avg Velocity
UI
Area wt. Avg Velocity
UI
Area wt. Avg Velocity
UI
0.20
72.04%
0.24
75.28%
0.34
74.19%
0.33
70.48%
Table 3: Point velocities recorded for different external vent areas
Velocity at Critical Points 0.50 0.45 0.40 0.35 0.30 0.25 0.20 0.15 0.10 0.05 0.00 Area 1.395
Area 1.815 Point-a
Point-b
Area 2.515 Point-c
Point-d
Area 3.119 Work Plane
Figure 17: Graph of velocity at a point vs the design type
10
In general, we see a higher ventilation rate with increasing external vent area, moreover even the building corners and edges are well ventilated and airier. Turbulence has also increased, resulting in eddy formation and velocities beyond 1m/s at some locations. Similar to the previous case observation, the southern half is more ventilated compared to the northern side, where there is are pockets of different velocities, especially in the corners. The presence of a courtyard creates a shadow region on the north side and the outlet creates a suction force, the two factors combined produce intense velocities near the exit. This feature is observed in each case 2.3.3 Internal Vent Area The terminal opening in the duct, which opens into the space, actually determine the characteristics of the air flow, since it can regulate the speed, direction as well as the smoothness of the flow. For this part of the study various internal vent design were considered having different opening characteristic and area. For each case the inlet velocity was set at 1m/s, external vent area at 1.815. The PPD was calculated for each critical point for a temperature of 27°C. In case one, the inlet had type A damper installed and outlet had type B. For the second case, the inlet had type B and outlet was type C. For the third case both were installed with type C, and for the final simulation, both inlet and outlet with increased area of type C. Figure 18: Work plane velocity contour for different vent areas
11
In type A damper, a grille of depth 10cm is put next to the vent opening, with mesh size of10mm. Type B damper is a similar structure but with vertical units only. Apart from reducing area of the vent, it also forces air to move in a straight path which gives rise to laminar flow of air in the room. The readings were taken at critical points along with the average velocity and uniformity index, which is shown in the table below. It is interesting to note that the average velocity (area weighted) has a positive correlation with the vent area, while the uniformity index has a negative. Figure 19: Damper types installed for controlling vent area
Total Internal Vent Area (m²) 0.610
0.825
1.125
2.250
Name
Velocity Magnitude
PPD
Velocity Magnitude
PPD
Velocity Magnitude
PPD
Velocity Magnitude
PPD
Point-a Point-b Point-c Point-d
0.22 0.18 0.11 0.08
6.10% 7.10% 10.10% 12.50%
0.27 0.19 0.18 0.31
5.40% 6.80% 7.10% 5.10%
0.19 0.26 0.12 0.28
6.80% 5.50% 9.50% 5.30%
0.36 0.17 0.20 0.06
5.00% 7.40% 6.50% 12.60%
Area wt. Avg Velocity
UI
Area wt. Avg Velocity
UI
Area wt. Avg Velocity
UI
Area wt. Avg Velocity
UI
0.19
71.25%
0.24
75.28%
0.22
68.96%
0.26
65.36%
Work Plane
Table 4: Point velocity recorded for different internal vent areas:
Velocity at Critical Points
0.40 0.35 0.30 0.25 0.20 0.15 0.10 0.05 0.00 0.610
0.825 Point-a
Point-b
1.125 Point-c
Point-d
2.250 Work Plane
Figure 20: Graph of point velocities vs internal vent area
12
This can be better understood by the velocity contours plotted at use plane. At lower area, the velocity is generally low and evenly spread. Increasing the vent area leads to higher velocities near the ducts and air shadow regions along the perimeter of the room. Moreover, there is much turbulence observed at higher areas. Points a, b and c, near the inlet, show increase in velocity with fluctuations suggesting the general rise in speed near the inlet coupled with erratic uncontrolled speeds sometime. Whereas point d, slight away from outlet and inlet showing no significant correlation. In essence, a higher vent area requires internal reorientation and planning to achieve a better uniformity. For instance the courtyard acts as a deflector, and other such features can be installed with such features. Wind wall is one example, also office furniture will have a diverse effect on the air flow. 2.3.4 Temperature Based on the optimal configurations from the previous studies, the critical points were evaluated for thermal comfort. Likewise, the inlet velocity was held constant at 1m/s for all the setups, external and internal vent areas were 1.815m² and 0.825m² respectively. The air flow pattern so achieved had the highest uniformity index of 75.28%, with the average velocity of 0.24m/s. The PPD for each point at various temperatures was consequently recorded and is shown in the table 5.
Figure 21: Work plane velocity contours for different internal vent areas
13
Temperature (°C) 26.000
27.000
28.000
29.000
Velocity Magnitude
PPD
Velocity Magnitude
PPD
Velocity Magnitude
PPD
Velocity Magnitude
PPD
Point-a Point-b Point-c Point-d
0.27 0.19 0.18 0.31
6.80% 5.30% 5.20% 7.80%
0.27 0.19 0.18 0.31
5.40% 6.80% 7.10% 5.10%
0.27 0.19 0.18 0.31
12.20% 15.70% 16.30% 11.30%
0.27 0.19 0.18 0.31
27.60% 32.30% 33.00% 25.70%
Average Velocity (area-wt)
0.24
6.10%
0.24
5.80%
0.24
13.40%
0.24
29.10%
Name
Table 5: PPD at critical points for different temperature conditions:
Percentage Dissatisfied at 1m/s inlet velocity
35.00% 30.00% 25.00% 20.00% 15.00% 10.00% 5.00% 0.00% 25.5
26 Point-a
26.5
27 Point-b
27.5 Point-c
28 Point-d
28.5
29
29.5
Average Velocity
Figure 22: PPD at critical points for various temperature range
It was not a surprise to observe that the PPD
tion when compared to points a and d. On
increased with higher temperatures. Higher
closer observation, it can be seen that points
temperature range values demand
more
b and c fall in a local dull region with a slightly
ventilation rate for thermal comfort since
lower velocity as compared to their surround-
more heat has to be dissipated. Since the ex-
ings. Points a and d on the other hand are in
periment limits the inlet velocity, the indoor
a draught region which accounts for a lower
space gets uncomfortable after a certain tem-
PPD at higher temperatures. In general, this
perature for a large section of the people.
design configuration works well for a temper-
What is interesting to observe is that the points b and c have overall higher dissatisfac-
ature up to 28°C, beyond which higher ventilation rate is needed.
14
Outdoor Thermal Sensation
3.2 Outdoor Ventilation Parametric Study
3.1 Modelling Combined Geometry on Site
For the study of outdoor comfort, the parameters listed n section A were varied to ob-
This part of the study deals with the response of the building with its context, mainly the
serve the effect on parameters listed in section B.
speed and direction of the prevalent wind. This is assumed to be blowing from the south, since the windcatchers were designed to take the benefit of pressure difference across the inlet and outlet. Thus, the inlet towers are in the south and outlet towers in the north. The basic geometry along with the ventilation system (with single side multiple opening) was placed in the centre of a site, repre-
Section A Site Inlet Velocity (m/s) 0.5 2.0 3.5 Wind Direction (due South) 0 45 90 Solar Radiation (W/m²) 50 250 450 Surface Temperature (°C) 30 60 90 Ambient Air Temperature (°C) 26 27 29
Section B Air Velocity
At four key points Thermal Sensation Index (TSI) For the four key points
Table 6: Parameters under study
sented by a body of dimension 19.5m by 16.5m, and a height of 15m. The resulting
Givoni et el developed an equation express-
subtracted volume, produced by subtracting
ing thermal sensation (TSI) as a function of
building geometry from site geometry, gives
five variables including surface temperatures
us the air around to simulate wind conditions.
of surrounding materials and solar radiation
The volume of the air enclosed is 4668.4m³.
[14]. The index is based on a 7-point scale with 4 as the neutral value. Index below 4 is for cold sensation and higher values for hot. Each parameter was individually studied, and TSI was calculated at five key point to evaluate user sensation at 1.2m height (mid-chest level for standing person). For this purpose, 2 points were chosen at 2 different windward edges (in the small building niche). One point was chosen in the, northern, wind shadow region, which has two arms of the building around it. The fourth point was taken in the courtyard, where users may sometime step out for fresh air, and the fifth was taken at the
Figure 23: Building on site; the grey region representing the volume of air around it.
south-eastern corner of the block.
15
The southern and western side surfaces was given an inlet velocity of varying magnitude but a constant direction. This was set at X=1, Y=0, Z=1; simulating the condition of southwesterly wind. Other parameters were kept constant for this part, namely direct solar radiation (250 W/m²), ground surface temperature (60°C), humidity (70% RH) and ambient air temperature (27°C). The velocities at key points were recorded and the thermal sensation index was calculated using WINCOM12.
Figure 24: Location of key points on site
The table below lists the point velocities and
3.2.1 Site Inlet Velocity
corresponding TSI for each different site inlet
To assess the effect of velocity on the ther-
condition.
mal comfort, CFD simulation was carried out on Fluent with the wind blowing from a single direction, 45° due south.
Site Inlet Air Velocity (m/s) 0.5 Point
2.0
3.5
Velocity Magnitude
Thermal Sensation Index
Velocity Magnitude
Thermal Sensation Index
Velocity Magnitude
Thermal Sensation Index
0.42 0.50 0.06 0.05 0.70
5 5 5 5 5
1.69 2.01 0.26 0.20 2.80
4 4 5 5 4
2.95 3.52 0.46 0.34 4.91
4 4 5 5 3
Point-a Point-b Point-c Point-d Point-e
Table 7: Velocity at key points for different site inlet velocity
TSI at Key Points Thermal Sensation Index
7.0 6.0 5.0 4.0 3.0 2.0 1.0 0.5
2.0
3.5
SIte Inlet Air Velocity Point-a
Point-b
Point-c
Point-d
Point-e
Figure 25: Graph of TSI vs site inlet velocity
16
At low velocities, most people would feel
The slope of velocity curve of points a, b and
warm at any point around the building, since
e is much greater than c and d, resulting in
the heat from the solar radiation and ground
this disparity.
creates a warm environment. At higher velocities, points a, b and e have a comfortable index. While points c and d are still considered warm. It is evident that these points lying in the wind shadow region never really get high wind intensities to feel comfortable. Point e being locate in the corner experiences higher wind speeds since the building offers resistance to the air flow, and deflects it around the corners. These corners are areas of high turbulence and velocity. At higher wind speeds it can become quite cold to stand at these points. We do however observe that the points c and d have slightly increased velocities with increasing inlet speed. As such there will be a stage when comfort will be achieved at those points also, but those high velocities will cause further cooling at the windward points.
Velocity at key points 5.00 4.50 4.00 3.50 3.00 2.50 2.00 1.50 1.00 0.50 0.00 0.5
2.0 Point-a
Point-b
Point-d
Point-e
Figure 26: Velocity at key points
3.5 Point-c
Figure 27: Velocity contours at 1.2m height
17
3.2.2 Site Inlet Wind Direction Wind direction is usually very erratic at a location, it can blow from one side for a while and instantly change direction after some time. A prevailing direction is usually considered when designing structures which may obstruct wind. For this part of the study, the wind speed is fixed at 2.0m/s with the direction changing from southerly to westerly wind.
Figure 28: Wind direction simulated for CFD
Wind Direction (measured from due South) 0° Name Point-a Point-b Point-c Point-d Point-e
45°
90°
Velocity Magnitude
Thermal Sensation Index
Velocity Magnitude
Thermal Sensation Index
Velocity Magnitude
Thermal Sensation Index
1.18 0.47 0.16 0.04 2.34
5 5 5 5 4
1.69 2.01 0.26 0.20 2.80
4 4 5 5 4
0.33 1.26 0.35 0.07 0.35
5 5 5 5 5
Table 8: Velocity at key points at varying wind direction
TSI at Key Points
Thermal Sensation Index
7.0 6.0 5.0 4.0 3.0 2.0 1.0 0
45
90
Wind Direction (from due South) Point-a
Point-b
Point-c
Point-d
Point-e
Figure 29 A graph of TSI vs wind direction for each selected point:
18
For most cases the comfort index reads
We can conclude that the best wind direction
warm. This is quite prominent for points c and
for this building configuration is when the
d which are in the, calm, wind shadow zone
wind blows from a corner position, leading to
for all scenarios. Point e experiences com-
higher number of comfort regions.
fortable conditions since it is a region of high velocity due to bending of wind around the building. For the case of 90°, it however, falls in a shadow zone and experiences higher (warmer) TSI. It is conclusive from the velocity contours that the areas around the corner experience higher velocities and thus should be made use of during site planning of the building. As for the case of the windcatchers, the two inlet towers are in a high velocity (high pressure) region, while the outlet is in a low velocity (low pressure) zone, this creates a suction force and drives the wind through the building. Only when the wind blows parallel to both the towers when it will be essential to use mechanical system for ventilation in the building.
Velocity at key points Wind velocity at key point
3.00 2.50 2.00 1.50 1.00 0.50 0.00 0
45
90
Inlet wind direction Point-a
Point-b
Point-d
Point-e
Point-c
Figure 30: Velocity at points vs wind direction
Figure 31: Velocity contours at 1.2m height
19
3.2.3 Direct Solar Radiation
A positive correlation is observed between
For the optimum condition of wind blowing
TSI and solar radiation, which is no surprise,
from south-west at a speed of 2m/s, the effect
since the sun’s rays have heating capacity. It
of varying solar radiation on TSI was calcu-
is, in fact, worth noting that the relationship is
lated at the key points to determine comfort
a linear one, and every point has the same
level.
gradient. The site exhibits all kind of thermal conditions ranging from as low as 3.7 to as
For this study, the actual value of TSI was
high as 5.3 TSI. Users can choose to move
plotted against solar radiation to give better
to a more comfortable region of their liking.
resolution for comparison.
Direct Solar Radiation (W/m²) 50 Name Point-a Point-b Point-c Point-d Point-e
250
450
Velocity Magnitude
Thermal Sensation Index
Velocity Magnitude
Thermal Sensation Index
Velocity Magnitude
Thermal Sensation Index
1.69 2.01 0.26 0.20 2.80
4.08 3.98 4.54 4.56 3.73
1.69 2.01 0.26 0.20 2.80
4.46 4.36 4.92 4.94 4.11
1.69 2.01 0.26 0.20 2.80
4.84 4.74 5.30 5.32 4.49
Figure 32: TSI at varying solar radiation
effect of solar radiation. At higher radiation
TSI at varying Solar Radiation 5.5
the wind speed is not strong enough to produce thermally comfortable condition. During
5.1
the course of a day, the points will have dif-
Thermal Sensation Index
5.3 4.9
ferent solar radiation falling on the ground
4.7 4.5
due to presence of buildings and other site
4.3
conditions. These obstructions will lead to
4.1
simulation of different thermally comfortable
3.9
conditions, of which the user can choose to
3.7 3.5 50
250
450
Direct Solar Radiation (W/m²) Point-a
Point-b
Point-d
Point-e
move from one to another. 3.2.4 Ground Surface Temperature
Point-c
Figure 33: Graph of TSI plotted at varying solar radiation
The urban heat island (UHI) phenomenon rises as urbanization increases. A key characteristic of urban areas is artificial surfaces,
Points c and d being in a lower wind speed
which can absorb and store great amounts of
region have a higher TSI i.e. are quite hot,
heat throughout the day [15]. Thus, it is im-
and will become unbearable after a certain
portant to study the impact of ground surface
solar radiation. Point e is quite cool to begin
temperatures on user comfort.
with since the high wind speed nullifies the 20
For this study the TSI was calculated for the
of temperatures as high as 93°C reaching in
key points with ground temperatures of 30°C,
the Death Valley, California. However, tem-
60°C and 90°C. The other parameters were
peratures even as high as this can be com-
kept constant, namely wind blowing at opti-
pensated by designing a properly ventilated
mal condition with 250W/m² solar radiation
region. The same can be observed when in
falling on site. For each point the TSI was cal-
the graph below. Clearly, at higher tempera-
culated for the three temperature values.
tures a velocity of more than 2m/s can create quite comfortable environment.
Again, we observe a similar trend, mainly, the linear relation of ground temperature with
Since the same velocity can create a chilly
TSI. Suffice to say that either extremes of
environment at cooler ground temperature, it
ground surface temperatures will cause dis-
is advisable to control the ventilation rate.
comfort for users. There have been reports Ground Surface Temperature (°C) 30
60
90
Name
Velocity Magnitude
Thermal Sensation Index
Velocity Magnitude
Thermal Sensation Index
Velocity Magnitude
Thermal Sensation Index
Point-a Point-b Point-c Point-d Point-e
1.69 2.01 0.26 0.20 2.80
4.30 4.19 4.76 4.78 3.94
1.69 2.01 0.26 0.20 2.80
4.46 4.36 4.92 4.94 4.11
1.69 2.01 0.26 0.20 2.80
4.62 4.52 5.08 5.10 4.27
Table 9: TSI at key points at varying ground surface temperatures
TSI at various Ground Surface Temperature 5.5
Thermal Sensation Index
5.3 5.1 4.9 4.7 4.5 4.3 4.1 3.9 3.7 3.5 30
60
90
Ground Surface Temperature (°C) Point-a
Point-b
Point-c
Point-d
Point-e
Figure 34: Graph of TSI plotted against various Ground Surface Temperatures
21
3.2.5 Ambient Air Temperature
ture. Even a degree rise in temperature of air
Finally, the ambient air temperature was par-
has led to higher TSI, which also means that
ametrized to observe the corresponding
rate of increase of ventilation is much more
change in the thermal index. TSI is essen-
for air temperature rather than ground tem-
tially similar to the PMV model but includes
perature.
more factors. Since both the models were
This is a major reason why during site plan-
generated based on intensive regression of
ning more care is taken in controlling the air
experimental data.
temperatures around, and people prefer airy
The graph is quite steep as compared to the
locations for higher wind speeds. In the cur-
relation of ground surface temperature. In the
rent context, points c and d require proper
first case we observe that the gradient is
measures to prevent over heating as well in-
0.005 while in the current case it is 0.109.
troduction of features to divert wind into the
This means that the air temperature play a
north and east sides of the building and the
more important role in determining outdoor
courtyard. Only then can there be thermal
comfort rather than ground surface tempera
comfort for these regions at all times.
Ambient Outdoor Air Temperature (°C) 26.000 Point Point-a Point-b Point-c Point-d Point-e
27.000
29.000
Velocity Magnitude
Thermal Sensation Index
Velocity Magnitude
Thermal Sensation Index
Velocity Magnitude
Thermal Sensation Index
1.69 2.01 0.26 0.20 2.80
4.35 4.24 4.81 4.83 3.99
1.69 2.01 0.26 0.20 2.80
4.46 4.36 4.92 4.94 4.11
1.69 2.01 0.26 0.20 2.80
4.68 4.58 5.15 5.17 4.33
Table 10: TSI for key points at various ambient air temperatures
TSI at varying Ambient Air Temperature 5.5
Thermal Sensation Index
5.3 5.1 4.9 4.7 4.5 4.3 4.1 3.9 3.7 3.5 26
27
29
Ambient Outside Air Temperature Point-a
Point-b
Point-c
Point-d
Point-e
Figure 35: Graph of TSI at key points plotted against air temperatures
22
Conclusion and Recommendations 4.1 Conclusions Drawn from the Project The indoor thermal comfort is a challenge for designers and consultants if decided to provide by natural means. In recent years it has become important to conserve and save en-
Thus, for a good uniformity index it is advisable to have more number of outlet vents as compared to inlet vents. They should also be spaced out depending on the building design so that the flow is well spread.
ergy. Factors which determine comfort needs
In case of pockets of draught or no wind
to be understood in detail and their relation-
zones, architectural features like book-
ship with each other.
shelves, desks, interior walls etc should be
For the indoor air flow, it is evident from the contour maps that outlet vent plays more important role in ventilation rather than inlet vents. Speed of inlet vent determines the flow characteristic of the air in the room,
places to divert wind. These features will act like wing walls and ventilated the shallow spaces. The design should be a gentle curve or similar nature to prevent further eddies in the room.
whether it is laminar or turbulent with eddies
The speed of inlet velocity also helps in better
in some room corners. The speed is again a
ventilation of the space, but at higher veloci-
function of the vent area, room dimension,
ties there is much turbulence in the air flow.
design of ducts etc.
Thus, an optimum balance has to be reached
For outdoor comfort, a site cannot have the same condition throughout, since there will be variation in landscape and landform, either natural or man-made. Thus, there are points of different TSI around the building. The building also provides shading from sun
for each design to determine the maximum allowable speed. Similarly, the external duct area also needs to be optimized for each design. A higher area generally leads to increased velocity and turbulence, and a balance has to be sought.
and wind on certain zones around it, which
Inlet vent area, if maintained small and well
may become region of comfort or discomfort.
distributed will give a good uniformity index
Thus, built form orientation is important for
and devoid of turbulences. In the case of us-
site planning and urban growth.
ing grilles and vertical dampers the UI was
4.2 Design Recommendations
much higher compared to the other cases., but due to decreased area the speed of air
The design and position of the duct is a key
was less. To compensate that numerous
in achieving indoor comfort. A higher number
vents can be placed which has the same area
of outlet vents, placed in more parts of the
as an uncovered went. Offices do not gener-
room will lead to a good spread of air. This is
ally also want velocities beyond 0.6m/s, as
the criteria of a good ventilation system. 23
then papers and other desktop object begin
changing pattern. The current model uses
to fly off and create discomfort.
only 4-5 points for measurement. This
The inlet vent when placed higher up on a wall generally has a better uniformity index on the work plane below. The current model with vents near the ceiling was developed after finding poor UI when the same vents were placed near the floor. Hence the experiment takes into account both positions to determine the suitability of inlet vents.
leaves margins for error, but gives scope for future experiment to be done and behaviour to be ascertained. b) The main windcatcher design has been inspired by the styles of the traditional architecture. In vernacular ventilation systems, straight sections were employed to di-vert wind into the room. There is much pressure lost in this system, with generation of
For outdoor thermal comfort the main prob-
turbulence. In practice this is avoided by
lem of having some region with high TSI is
having curved edges and gentle bends in
because they are in wind shadow region. The
the duct section to prevent such losses. In
design intent should be such that these
the present experiment, dampers have
spaces are also well ventilated to create cool-
been installed at the terminal openings of
ing effect. For instance, the central courtyard
a duct. to generate laminar flow.
seems to have very little air flow to cause sufficient cooling, if the building does not provide shading from the sun then the region can get severely hot inside. Shading is required in many parts of the site to prevent high values of solar irradiance falling on the people. Shading is also needed to prevent high wind area on the wind ward side, this can be done by planting trees and plants. They have a two-fold advantage. Apart from providing shade they also help in reducing heat island effect by absorbing the heat, corollary the ground surface temperature is also kept low. 4.3 Limitations a) The number and location of test points vary from design to design and a higher number of them are required to be simu-
Figure 36: Windtower with curved edges to reduce air friction
lated for air velocity and observe the 24
c) The user plane is assumed to be at
plane (900mm) is given in the table below.
750mm, which is also the height of working
It shows a better UI, while the average ve-
desk, but in reality, people may move
locity is more or less the same. We may
around the place or there may be other fur-
observe better UI at even higher heights of
niture with higher level. Thus, diverse
about 1.2m (standing people). Moreover,
range of work plane is required to monitor
office furniture can cause turbulence in
comfort. For instance, if people are sitting
wind flow at lower levels. The table below
on low chairs, their neck will be around the
lists the average speeds on two different
heights of 900mm to 1000mm. The aver-
level for comparison, along with the stand-
age velocity and uniformity index at that
ard 750mm. Inlet Air Velocity
0.5
1.0
Area wt. Avg Velocity
UI
Area wt. Avg Velocity
0.75 m
0.10
73.38%
0.9 m
0.09
1.2 m
0.09
IsoSurface @
1.5
2.0
UI
Area wt. Avg Velocity
UI
Area wt. Avg Velocity
UI
0.24
75.28%
0.35
74.96%
0.43
74.20%
74.50%
0.23
75.50%
0.33
75.70%
0.41
75.11%
73.65%
0.21
75.29%
0.31
76.86%
0.37
74.44%
Table 11: Average velocities and UI at higher work plane:
25
Appendices The convergence criteria for the simulation is as shown in figure 37.
Figure 40: Convergence at 300 for case 2.3.1 (1.5m/s)
Figure 37: Convergence criteria
For each simulation controls have been adjusted to achieve convergence. The number of iterations needed to reach convergence for each case is shown in Figures 38 to 45.
Figure 41: Convergence at 358 for case 2.3.1 (2.0m/s)
Figure 38: Convergence at 358 for case 2.3.1 (0.5m/s)
Figure 42: Convergence at 161 for case 2.3.2 (1.395m²)
Figure 39: Convergence at 202 for case 2.3.1 (1.0m/s) Figure 43: Convergence at 391 for case 2.3.2 (2.515m²)
26
Figure 48: Convergence at ~3700 for case 3.2.1 (2m/s) Figure 44: Convergence at 1480 for case 2.3.3 (0.610m²)
Figure 49: Convergence at ~5500 for case 3.2.1 (3m/s)
Figure 45: Convergence at 2491 for case 2.3.3 (1.125m²)
Figure 50: Convergence at ~7716 for case 3.2.2 (0°)
Figure 46: Convergence at 1102 for case 2.3.3 (2.25m²)
Figure 51: Convergence at ~3830 for case 3.2.2 (45°) Figure 47: Convergence at ~1900 for case 3.2.1 (0.5m/s)
The solution for case 3.2.2 (90°) had not reached convergence, the program was allowed to run for more than 9000 iterations multiple times. The least residual value is presented in this report. 27
References [1]. Ben Richard Hughes, John Kaiser Calautit, Saud Abdul Ghani. The development of commercial wind towers for natural ventilation: A review (2011) [2]. Global Footprint Network, Annual report 2011 [3]. Chan H-Y, Riffat SB, Zhu J. Review of passive solar heating and cooling technologies. Renewable and Sustainable Energy Reviews 2010. [4]. Omidreza Saadatian, Lim Chin Haw, K. Sopian, M.Y. Sulaiman.
Review of
windcatcher technologies (2012). [5]. Bahadori MM. Passive cooling systems in Iranian architecture. Scientific American Journal 1978. [6]. Hughes BR, Chaudhry HN, Ghani SA. A review of sustainable cooling technologies in buildings. Renewable and Sustainable Energy Reviews 2011. [7]. Yaghoubi MA, Sabzevari A, Goneshan AA. Wind towers: measurement and performance. Solar Energy 1991 [8]. Battle McCarthy Consulting E. Wind towers: Academy Editions; 1999 [9]. Fathy H. Natural energy and vernacular architecture: principles and examples with reference to hot arid climates. University of Chicago Press; 1986. [10]. Busch, J.F. A tale of two populations: thermal comfort in air-conditioned and naturally ventilated offices in Thailand. EnergyBuild (1992). [11]. de Dear,R., Brager,G.S. Thermal comfort in naturally ventilated buildings: revisions to ASHRAE Standard 55. Energy Build (2002) [12]. E. Olsen, Q. Chen, Energy consumption and comfort analysis for different low energy cooling systems in a mild climate, Energy & Buildings 35 (2003). [13]. Naghman Khan, Yuehong Su, Saffa B. Riffat. A review of wind driven ventilation techniques (2007). [14]. Wendy Walls, Nicki Parker and Jillian Walliss. Designing with thermal comfort indices in outdoor sites [15]. Surface and ambient air temperatures associated with different ground material: a case study at the University of California, Berkeley. Katharine K. Guan Figure 2. Neufert Architects’ Data, third edition Figure 3. US Department of Energy Annual report 2008 Figure 4. https://www.designingbuildings.co.uk/ wiki/Windcatcher Figure 5, 6. Review of windcatcher technologies (2012)
28
List of Figures Figure 1: Office space under consideration, (dimensions in meters) ........................................... 2 Figure 2: Suggested working height ............................................................................................. 2 Figure 3:Commercial Sector Buildings Energy End Use .............................................................. 3 Figure 4: A typical wind catcher in the form of a tower ................................................................. 3 Figure 5: Types of traditional windcatchers .................................................................................. 4 Figure 6: University of Qatar, Doha .............................................................................................. 4 Figure 7: Cooling effect by air movement..................................................................................... 5 Figure 8: Step 1 - Sketching the office footprint ........................................................................... 6 Figure 9: Step 2 - Sketching courtyard, ........................................................................................ 6 Figure 10: The base geometry, isometric view............................................................................. 6 Figure 11: A, B- Bidirectional windcatcher; C, D- Unidirectional windcatcher .............................. 6 Figure 12: Building elevations, (not to scale) ............................................................................... 7 Figure 13: Location of critical points ............................................................................................. 7 Figure 14: Graph of point velocity vs inlet speed ......................................................................... 8 Figure 15: Work plane velocity contour at different inlet speed .................................................... 9 Figure 16: Design of windcatcher ............................................................................................... 10 Figure 17: Graph of velocity at a point vs the design type.......................................................... 10 Figure 18: Work plane velocity contour for different vent areas ................................................. 11 Figure 19: Damper types installed for controlling vent area ....................................................... 12 Figure 20: Graph of point velocities vs internal vent area .......................................................... 12 Figure 21: Work plane velocity contours for different internal vent areas ................................... 13 Figure 22: PPD at critical points for various temperature range ................................................. 14 Figure 23: Building on site; the grey region representing the volume of air around it. ................ 15 Figure 24: Location of key points on site .................................................................................... 16 Figure 25: Graph of TSI vs site inlet velocity .............................................................................. 16 Figure 26: Velocity at key points ................................................................................................ 17 Figure 27: Velocity contours at 1.2m height ............................................................................... 17
29
Figure 28: Wind direction simulated for CFD ............................................................................. 18 Figure 29 A graph of TSI vs wind direction for each selected point: .......................................... 18 Figure 30: Velocity at points vs wind direction ........................................................................... 19 Figure 31: Velocity contours at 1.2m height ............................................................................... 19 Figure 32: TSI at varying solar radiation .................................................................................... 20 Figure 33: Graph of TSI plotted at varying solar radiation .......................................................... 20 Figure 34: Graph of TSI plotted against various Ground Surface Temperatures ....................... 21 Figure 35: Graph of TSI at key points plotted against air temperatures ..................................... 22 Figure 36: Windtower with curved edges to reduce air friction ................................................... 24 Figure 37: Convergence criteria ................................................................................................. 26 Figure 38: Convergence at 358 for case 2.3.1 (0.5m/s) ............................................................. 26 Figure 39: Convergence at 202 for case 2.3.1 (1.0m/s) ............................................................. 26 Figure 40: Convergence at 300 for case 2.3.1 (1.5m/s) ............................................................. 26 Figure 41: Convergence at 358 for case 2.3.1 (2.0m/s) ............................................................. 26 Figure 42: Convergence at 161 for case 2.3.2 (1.395m²)........................................................... 26 Figure 43: Convergence at 391 for case 2.3.2 (2.515m²)........................................................... 26 Figure 44: Convergence at 1480 for case 2.3.3 (0.610m²)......................................................... 27 Figure 45: Convergence at 2491 for case 2.3.3 (1.125m²)......................................................... 27 Figure 46: Convergence at 1102 for case 2.3.3 (2.25m²) .......................................................... 27 Figure 47: Convergence at ~1900 for case 3.2.1 (0.5m/s) ......................................................... 27 Figure 48: Convergence at ~3700 for case 3.2.1 (2m/s) ............................................................ 27 Figure 49: Convergence at ~5500 for case 3.2.1 (3m/s) ............................................................ 27 Figure 50: Convergence at ~7716 for case 3.2.2 (0°) ................................................................ 27 Figure 51: Convergence at ~3830 for case 3.2.2 (45°) .............................................................. 27
30