Lennox Air Handler

Page 1

A P P L I C AT I O N GUIDE

AIR HANDLER BCRM

10 - 02



TABLE OF CONTENTS

1.

Air Handler Features

Page 2

2.

Physical data

Page 4

3.

Available kits

Page 6

4.

Model nomenclature

Page 8

5.

Air handler blower performance

Page 9

6.

Water heating capacity

Page 15

7.

Maximum line length for heating coils using pump option

Page 19

8.

Size 18-36 installation configuration

Page 23

9.

Size 42-60 installation configuration

Page 25

10. Dimensions

Unit with electric heater option

Page 27

Unit with hot water coil option

Application Guide / Air handler – Page 1


AIR HANDLER FEATURES All models • • • • • • • • • • • • •

Suitable for use with R22 and R410a Rifled Copper Tubing Patented lance fin design Ratings in conformity with ARI standard 210 ETL Listed Available voltage 22/1/50 Hz High efficiency 3-speed motors 40 VA control voltage transformer Dynamically balanced blowers for quiet vibration free operation Refrigerant connections are 3/8” ODF liquid and 3/4” ODF (12 – 36) or 7/8” ODF (31, 37 – 60) suction Dual 3/4” FPT condensate drains Drain pans are molded of corrosion proof engineering polymer Florator, non-bleed A/C or HP expansion valve also available as a kit for field installation (all screw-on connections)

BC 18 – 36 (Slant Coil) • • • • • • • • • • • • • • •

40 different models available to properly match heat pumps and air conditioners for maximum efficiency Choice of left or right drain and refrigerant connections during installation. This option makes it possible to have the return air enter the left or right side in addition to the bottom Filter rack with filter – built into every air handler Electric heat available factory installed or in kit form for field installation. Plug in connections simplify installation of kits Water heating coils available factory installed in 2 or 3 rows (with or without pump). Also available as a kit to add to no heat models Cabinet constructed of pre-painted heavy gauge galvanized steel to prevent corrosion. Lined with high quality 1” mat faced insulation Available from factory as upflow or upflow / horizontal. Field installed horizontal drain pan kit is also available Circuit breaker optional factory installed or as kit, 5 – 10 kW. Standard on 12,5 kW and higher. All field installed kits come with thorough, easy to follow instructions All air handlers are top handling (basiloid) packaged with bar coding and full description label. Electrical connections can be made on top or right side Fan time delay available as kit or factory installed Easy to follow wiring diagrams on all air handlers Easily converted to counterflow with kit All coils are individually pressure tested at 450 PSI, then pressurized and sealed

BC 42 - 60 (A-Coil) • • • • •

48 different models available to properly match heat pumps and air conditioners for maximum efficiency Choice of left or right drain connections during installation Filter rack with filter – built into every air handler Electric heat available factory installed or in kit form for field installation. Plug in connections simplify installation of kits Water heating coils available factory installed in 3 or 4 rows (with or without pump). Also available as a kit to add to no heat models

Application Guide / Air handler – Page 2


AIR HANDLER FEATURES Additional features for all water heat models • • • • • • • • •

Easy to replace water coil. Remove one screw and slide out Heating blower time delay standard on all models On models without a pump there is ample room inside cabinet for mounting aquastat if desired. This provides a clean looking installation Separate set of contacts for interfacing with external components (i.e burner relay, pump relay or zone valve) Easy to follow wiring diagrams for connecting to popular zoning controls Low water pressure drop through heating coil for excellent heating performance Easy to adjust blower speeds for fine tuning customer comfort Blower door safety switch Large water connections out the top. 7/8” ODF 1 ½ - 3 ton and 1 1/8” ODF 3 ½ - 5 ton models

Application Guide / Air handler – Page 3


PHYSICAL DATA 50 Hz - BC Series 2 speed Motor “- 005”

Available voltage Max. Elec. Heat available (kW) Transformer Size and Type Wheel (dia. x Width) Motor H.P. F. L. A @ 220V Blower Speed Data 3 Nominal (m /h) Nominal (cfm) Air Filter Size Refrigerant Conn. (IDS) Suction Refrigerant Conn. (IDS) Liquid Florator Piston Size Weights Approx. kg (base unit w/out heat) Weights Approx. lbs (base unit w/out heat)

18

24

10

12,5

9x6 1/5 1,7 2 1 020 600 14 x 20 3/4" 3/8" 0,053 55 120

9x6 1/4 2,0 2 1 360 800 14 x 20 3/4" 3/8" 0,059 55 120

Air Handler Size 30 36 220/50/1 17,5 20 40 VA, Class 2 10 x 8 10 x 8 1/3 1/3 3,7 3,7 2 2 1 700 2 040 1 000 1 200 16 x 20 16 x 20 3/4" 3/4" 3/8" 3/8" 0,067 0,073 65 65 140 140

48

60

25

25

10 x 8 1/2 5,0 2 2 720 1 600 16 x 25 7/8" 3/8" 0,084 105 230

10 x 10 3/4 6,4 2 3 400 2 000 16 x 25 7/8" 3/8" 0,093 110 240

48

60

25

25

10 x 8 3/4 4,3 3 3 400 2 000 18 x 25 7/8" 3/8" 0,084 105 230

10 x 10 3/4 4,3 3 3 400 2 000 20 x 25 7/8" 3/8" 0,093 110 240

50 Hz - BC Series 3 speed Motor “- 007”

Available voltage Max. Elec. Heat available (kW) Transformer Size and Type Wheel (dia. x Width) Motor H.P. F. L. A @ 220V Blower Speed Data 3 Nominal (m /h) Nominal (cfm) Air Filter Size Refrigerant Conn. (IDS) Suction Refrigerant Conn. (IDS) Liquid Florator Piston Size Weights Approx. kg (base unit w/out heat) Weights Approx. lbs (base unit w/out heat)

18

24

10

12,5

9x6 1/4 1,9 3 1 360 800 12 x 20 3/4" 3/8" 0,053 55 120

9x6 1/3 2,2 3 1 700 1 000 12 x 20 3/4" 3/8" 0,059 55 120

Air Handler Size 30 36 220/50/1 17,5 20 40 VA, Class 2 10 x 8 10 x 8 1/3 1/2 2,2 2,6 3 3 1 700 2 040 1 000 1 200 16 x 20 16 x 20 3/4" 3/4" 3/8" 3/8" 0,067 0,073 65 65 140 140

Application Guide / Air handler – Page 4


PHYSICAL DATA 60 Hz - BC Series 3 speed Motor “- 001” 18 Available voltage Max. Elec. Heat available (kW) 10 Transformer Size and Type Wheel (dia. x Width) 9x6 Motor H.P. 1/5 Blower F. L. A @ 240V 1,1 Data Speed 3 3 Nominal (m /h) 1 020 Nominal (cfm) 600 Air Filter Size 12 x 20 Refrigerant Conn. (IDS) Suction 3/4" Refrigerant Conn. (IDS) Liquid 3/8" Florator Piston Size 0,053 Weights Approx. kg (base unit w/out heat) 55 Weights Approx. lbs (base unit w/out heat) 120

Air Handler Size 30 36 42 208-240/60/1 12,5 17,5 20 22,5 40 VA, Class 2 9x6 10 x 8 10 x 8 10 x 8 1/4 1/3 1/3 1/2 1,9 2,2 2,6 3,0 3 3 3 3 1 360 1 700 2 040 2 380 800 1 000 1 200 1 400 12 x 20 16 x 20 16 x 20 18 x 25 3/4" 3/4" 3/4" 7/8" 3/8" 3/8" 3/8" 3/8" 0,059 0,067 0,073 0,080 55 65 65 105 120 140 140 230 24

48

60

25

25

10 x 8 10 x 10 1/2 3/4 4,0 4,3 3 3 2 720 3 400 1 600 2 000 18 x 25 20 x 25 7/8" 7/8" 3/8" 3/8" 0,084 0,093 105 110 230 240

Application Guide / Air handler – Page 5


AVAILABLE KITS

Horizontal Drain Pan Kit Filter Rack

Counterflow Conversion Kit

A/C TXV R22 HP TXV R22 A/C R410a HP TXV R410a 5 kW Electric Heat Kits Includes: Heating elements, Thermal limits, Sequencer(s), *Circuit breaker(s), and Mounting plate. *(12,5 kW above)

7,5 kW 10 kW 12,5 kW 15 kW 17,5 kW 20 kW 22,5 kW

Circuit breaker Kit

5 KW 7,5 kW 10 kW

Part # 991677-00 991678-00 991679-00 991680-00 655016-00 655017-00 650564-00 650565-00 991675-01 991675-02 991676-01 991676-02 650264-00 650264-01 655074-00 655009-01 655009-05 655010-04 655009-06 655010-06 655009-08 655010-08 655009-09 655010-09 655009-10 655010-10 655009-11 655010-11 655010-12 655010-13 991641-00 991642-00 991643-00

18 X

24 X

X

X

X

X

30 X

36 X

X

X

X

X

42

48

60

X

X

X

X

X X

X

X

X

X

X

X

X

X

X

X

X

X

X X X

X X X

X X X

X X X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X X

X X

X X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X X

X

X

X X X X

X X X X

X X

X X X

X X X

X X X

X X X

X X X

Application Guide / Air handler – Page 6


AVAILABLE KITS

Water Heat Kit Without Pump

Water Heat Kit With Pump

Pump Kit Freeze Stat

2 2 3 3 2 2 3 3 3 3 4 4 3 3 4 4

Part # 2 row 656141-03 3 row 656141-06 2 row 656141-09 3 row 656141-12 3 row 656141-15 4 row 656141-18 3 row 656141-21 4 row 656141-24 row (120 V) 656141-02 row (240 V) 656141-01 row (120 V) 656141-05 row (240 V) 656141-04 row (120 V) 656141-08 row (240 V) 656141-07 row (120 V) 656141-11 row (240 V) 656141-10 row (120 V) 656141-14 row (240 V) 656141-13 row (120 V) 656141-17 row (240 V) 656141-16 row (120 V) 656141-20 row (240 V) 656141-19 row (120 V) 656141-23 row (240 V) 656141-22 120 V 991644-00 240 V 991645-00 991662-00

18 X X

24 X X

30

36

X X

X X

42

48

X X

X X

60

X X X X X X

X X X X X X X X

X X X X X X X X

X X X

X X X

X X X

X X X

X X X

X X X X

X X X

X X X X X X X

Application Guide / Air handler – Page 7


MODEL NOMENCLATURE B

C

R

M

A1

2

24

-

S

05

2

B = Family

VOLTAGE 1 = 240-208/1/60 Hz 2 = 240-208/1/60 Hz w/ Time Delay 3 = 120/1/60 Hz 4 = 120/1/60 Hz w/ Time Delay 5 = 220/1/50 Hz 6 = 220/1/50 Hz w/ Time Delay 7 = 220/1/50 – 3 speeds

BLOWER MOTOR TYPE C = Constant speed blower V = Variable speed blower (Not currently available)

REFRIGERANT AND DRAIN CONNECTIONS R = Right Hand O = No Coil

HEAT 00 = 0 kW Elec. 05 = 5 kW Elec. 07 = 7,5 kW Elec. 10 = 10 kW Elec. 12 = 12,5 kW Elec 15 = 15 kW Elec. 17 = 17,5 kW Elec. 20 = 20 kW Elec. 22 = 22,5 kW Elec. 25 = 25 kW Elec.

AIR FLOW CONFIGURATION V = Vertical Only M = Multi-position

SLAB NUMBER A1 thru Z9 00 = No cooling coil, Heating only

Note: Max. 10 kW per elec. supply circuit

SIZE kW available

EXPANSION DEVICE

18 24 30

0 = No Cooling Coil 2 = Florator 3 = Bleed TXV Valve (R22) 4 = Non Bleed A/C TXV Valve (R22) 5 = Non Bleed HP-A/C TXV Valve (R22) 6 = Non Bleed A/C TXV Valve (R410a) 9 = Non Bleed HP-A/C TXV Valve (R410a)

36 42 48 60

UNIT SIZE (NOMINAL MBTUH) 18, 24, 30, 36

42, 48, 60

Slant coil

A coil

5 – 7,5 - 10 5 – 7,5 – 10 – 12,5 5 – 7,5 – 10 – 12,5 15 – 17,5 5 – 7,5 – 10 – 12,5 15 – 17,5 – 20 7,5 – 10 – 12,5 - 15 17,5 – 20 – 22,5 7,5 – 10 – 12,5 –15 17,5 – 20 – 22,5 - 25 10 – 12,5 – 15 17,5 – 20 – 22,5 - 25

2P = 2 Row hot water coil (w/ pump and valve assembly)

On 18, 24, 30 & 36 models 3P = 3 Row hot water coil (w/ pump and valve assembly)

LINE VOLTAGE CONNECTIONS / CIRCUIT PROTECTION

On all models 4P = 4 Row hot water coil

Amount of Heat S = Stripped Wire T = Terminal Block B = Circuit Breaker P = Pull Disconnect

Water #

0 #

# = Standard , O = Optional

5 # O O O

(w/ pump and valve assembly)

7,5

10

12,5

15

17,5

20

22,5

25

# O O

# O O

#

#

#

#

#

#

On 42, 48 & 60 models 2N = 2 Row hot water coil (no pump) On 18, 24, 30 & 36 models 3N = 3 Row hot water coil (no pump) On all models 4N = 4 Row hot water coil (no pump) On 42, 48 & 60 models

Application Guide / Air handler – Page 8


AIR HANDLER BLOWER PERFORMANCE (m3/h vs ESP Pa) All data is given while air handler is operating with DX coil and air filter installed. Speeds marked in bold with an asterix* are the factory speed settings for both heating and cooling. Cooling speeds should not be reduced below factory setting. Different speeds can be set for heating mode. See installation instructions for changing speeds and minimum settings on electric heat.

50 Hz - BC Series 2 speed Motor “- 005”

Size

Electric Heat Models 50 75 100

Speed

25

125

Low

1 056

967

847

682

569

*High

1 174

1 074

941

758

633

Low

1 369

1 259

1 184

1 087

826

*High

1 521

1 399

1 315

1 208

917

Low

1 548

1 349

1 332

1 132

999

*High

1 892

1 767

1 660

1 419

1 265

Low

1 626

1 416

1 399

1 189

1 049

*High

1 987

1 855

1 743

1 490

1 328

Low

2 514

2 318

2 183

2 023

1 673

*High

2 861

2 709

2 513

2 334

2 092

Low

3 080

2 926

2 780

2 641

2 509

*High

3 520

3 344

3 177

3 018

2 867

18

24

30

36

48

60

Water Coil 2 row 3 row 2 row 3 row 2 row 3 row 2 row 3 row 2 row 3 row 2 row 3 row 2 row 3 row 2 row 3 row 3 row 4 row 3 row 4 row 3 row 4 row 3 row 4 row

25 753 720 1 229 1 177 1 132 1 084 1 500 1 437 1 507 1 444 1 954 1 872 1 937 1 856 2 341 2 243 2 522 2 416 2 985 2 859 2 786 2 667 3 453 3 308

Water 50 709 680 1 211 1 160 1 067 1 022 1 479 1 417 1 422 1 361 1 820 1 743 1 827 1 751 2 309 2 212 2 379 2 279 2 944 2 820 2 627 2 516 3 405 3 262

Heat Models 75 100 666 652 637 624 1 018 981 975 940 1 000 978 958 937 1 460 1 412 1 398 1 352 1 335 1 305 1 278 1 249 1 706 1 667 1 634 1 597 1 646 1 609 1 577 1 542 2 277 2 204 2 181 2 112 2 231 2 179 2 137 2 088 2 903 2 809 2 781 2 691 2 467 2 409 2 346 2 307 3 357 3 247 3 216 3 111

125 635 608 940 900 954 914 1 364 1 307 1 274 1 220 1 628 1 559 1 571 1 505 2 130 2 040 2 128 2 039 2 713 2 599 2 351 2 253 3 135 3 004

Application Guide / Air handler – Page 9


AIR HANDLER BLOWER PERFORMANCE (cfm vs inches H 2O) 50 Hz - BC Series 2 speed Motor “- 005”

Size

Electric Heat Models 0,2 0,3 0,4

Speed

0,1

Low

622

569

498

401

*High

691

632

554

446

Low

806

741

697

640

*High

896

824

774

711

Low

911

794

784

666

*High

1 114

1 040

977

835

Low

957

833

823

700

*High

1 169

1 092

1 026

877

Low

1 480

1 364

1 285

1 191

*High

1 684

1 595

1 479

1 374

Low

1 813

1 722

1 636

1 554

*High

2 072

1 968

1 870

1 776

18

24

30

36

48

60

Water Coil 2 row 335 3 row 2 row 372 3 row 2 row 486 3 row 2 row 540 3 row 2 row 588 3 row 2 row 744 3 row 2 row 617 3 row 2 row 782 3 row 3 row 985 4 row 3 row 1 232 4 row 3 row 1 477 4 row 3 row 1 688 4 row 0,5

0,1 443 424 723 693 666 638 883 846 887 850 1 150 1 102 1 140 1 092 1 378 1 320 1 484 1 422 1 757 1 683 1 640 1 570 2 032 1 947

Water 0,2 417 400 713 683 628 602 871 834 837 801 1 071 1 026 1 075 1 031 1 359 1 302 1 400 1 341 1 733 1 660 1 546 1 481 2 004 1 920

Heat Models 0,3 0,4 392 384 375 367 599 577 574 553 589 576 564 552 859 831 823 796 786 768 752 735 1 004 981 962 940 969 947 928 908 1 340 1 297 1 287 1 243 1 313 1 283 1 258 1 229 1 709 1 653 1 637 1 584 1 452 1 418 1 381 1 358 1 976 1 911 1 893 1 831

0,5 374 358 553 530 562 538 803 769 750 718 958 918 925 886 1 254 1 201 1 253 1 200 1 597 1 530 1 384 1 326 1 845 1 768

Application Guide / Air handler – Page 10


AIR HANDLER BLOWER PERFORMANCE (m3/h vs ESP Pa) All data is given while air handler is operating with DX coil and air filter installed. Speeds marked in bold with an asterix* are the factory speed settings for both heating and cooling. Cooling speeds should not be reduced below factory setting. Different speeds can be set for heating mode. See installation instructions for changing speeds and minimum settings on electric heat.

50 Hz - BC Series 3 speed Motor “- 007”

Size

18

24

30

36

48

60

Electric Heat Models 50 75 100

Speed

25

125

Low

1 053

960

824

713

620

*Med

1 198

1 096

960

773

645

High

1 274

1 147

1 019

849

671

Low

1 452

1 359

1 265

1 121

892

*Med

1 690

1 554

1 461

1 342

1 019

High

1 733

1 605

1 503

1 350

1 121

Low

1 580

1 376

1 359

1 155

1 019

*Med

1 665

1 554

1 427

1 248

1 113

High

1 736

1 605

1 503

1 342

1 189

Low

2 089

1 945

1 851

1 709

1 554

*Med

2 302

2 132

2 013

1 877

1 707

High

2 358

2 225

2 072

1 945

1 809

Low

2 565

2 364

2 227

2 064

1 707

*Med

2 789

2 573

2 387

2 200

1 987

High

2 358

2 599

2 421

2 217

2 013

Low

2 850

2 627

2 474

2 293

1 897

*Med

3 020

2 859

2 652

2 463

2 208

High

3 099

2 888

2 689

2 444

2 236

Water Coil 2 row 3 row 2 row 3 row 2 row 3 row 2 row 3 row 2 row 3 row 2 row 3 row 2 row 3 row 2 row 3 row 2 row 3 row 2 row 3 row 2 row 3 row 2 row 3 row 3 row 4 row 3 row 4 row 3 row 4 row 3 row 4 row 3 row 4 row 3 row 4 row

25 666 638 852 816 883 846 887 850 1 135 1 087 1 150 1 102 887 850 1 135 1 087 1 150 1 102 1 140 1 092 1 377 1 319 1 378 1 320 1 485 1 422 1 793 1 718 1 757 1 683 1 640 1 570 1 980 1 896 2 032 1 947

Water 50 628 602 803 769 871 834 837 801 1 071 1 026 1 135 1 087 837 801 1 071 1 026 1 135 1 087 1 076 1 030 1 299 1 244 1 359 1 302 1 400 1 341 1 691 1 620 1 733 1 660 1 546 1 481 1 952 1 870 2 004 1 920

Heat Models 75 100 589 576 564 551 753 736 721 705 859 831 823 796 786 768 752 735 1 004 981 962 940 1 119 1 082 1 072 1 037 786 768 752 735 1 004 981 962 940 1 119 1 082 1 072 1 037 969 947 928 907 1 170 1 144 1 121 1 096 1 340 1 297 1 284 1 243 1 313 1 283 1 258 1 229 1 586 1 549 1 519 1 484 1 709 1 653 1 637 1 584 1 452 1 418 1 381 1 358 1 925 1 862 1 844 1 783 1 976 1 911 1 893 1 831

125 561 538 718 688 803 769 750 718 958 918 1 046 1 002 750 718 958 918 1 046 1 002 925 886 1 117 1 070 1 254 1 201 1 253 1 200 1 513 1 449 1 597 1 530 1 384 1 326 1 798 1 722 1 846 1 768

Application Guide / Air handler – Page 11


AIR HANDLER BLOWER PERFORMANCE (cfm vs inches H 2O) 50 Hz - BC Series 3 speed Motor “- 007”

Size

18

24

30

36

48

60

Electric Heat Models 0,2 0,3 0,4

Speed

0,1

0,5

Low

620

565

485

420

365

*Med

705

645

565

455

380

High

750

675

600

500

395

Low

855

800

745

660

525

*Med

995

915

860

790

600

High

1 020

945

885

795

660

Low

930

810

800

680

600

*Med

980

915

840

735

655

High

1 022

945

885

790

700

Low

1 230

1 145

1 090

1 006

915

*Med

1 355

1 255

1 185

1 105

1 005

High

1 388

1 310

1 220

1 145

1 065

Low

1 510

1 392

1 311

1 215

1 005

*Med

1 642

1 515

1 405

1 295

1 170

High

1 388

1 530

1 425

1 305

1 185

Low

1 678

1 547

1 457

1 350

1 117

*Med

1 778

1 683

1 561

1 450

1 300

High

1 824

1 700

1 583

1 439

1 317

Water Coil 2 row 3 row 2 row 3 row 2 row 3 row 2 row 3 row 2 row 3 row 2 row 3 row 2 row 3 row 2 row 3 row 2 row 3 row 2 row 3 row 2 row 3 row 2 row 3 row 3 row 4 row 3 row 4 row 3 row 4 row 3 row 4 row 3 row 4 row 3 row 4 row

0,1 392 376 501 480 520 498 522 500 668 640 677 649 522 500 668 640 677 649 671 643 811 776 811 777 874 837 1 055 1 011 1 034 991 965 924 1 165 1 116 1 196 1 146

Water 0,2 370 354 473 453 513 491 493 471 630 604 668 640 493 471 630 604 668 640 633 606 765 732 800 766 824 789 995 954 1 020 977 910 872 1 149 1 101 1 180 1 130

Heat Models 0,3 0,4 347 339 332 324 443 433 424 415 506 489 484 469 463 452 443 433 591 577 566 553 659 637 631 610 463 452 443 433 591 577 566 553 659 637 631 610 570 557 546 534 689 673 660 645 789 763 756 732 773 755 740 723 934 912 894 873 1 006 973 964 932 855 835 813 799 1 133 1 096 1 085 1 049 1 163 1 125 1 114 1 078

0,5 330 317 423 405 473 453 441 423 564 540 616 590 441 423 564 540 616 590 544 521 657 630 738 707 738 706 891 853 940 901 815 780 1 058 1 014 1 087 1 041

Application Guide / Air handler – Page 12


AIR HANDLER BLOWER PERFORMANCE (m3/h vs ESP Pa) All data is given while air handler is operating with DX coil and air filter installed. Speeds marked in bold with an asterix* are the factory speed settings for both heating and cooling. Cooling speeds should not be reduced below factory setting. Different speeds can be set for heating mode. See installation instructions for changing speeds and minimum settings on electric heat.

60 Hz - BC Series 3 speed Motor “- 001”

Size

18

24

30

36

42

48

60

Electric Heat Models 50 75 100

Speed

25

125

Low

800

754

709

693

676

*Med

1 235

1 166

1 092

1 069

1 043

High

1 308

1 290

1 273

1 232

1 189

Low

1 128

1 089

1 058

1 028

975

*Med

1 539

1 453

1 363

1 330

1 298

High

1 597

1 575

1 553

1 502

1 451

Low

1 604

1 512

1 420

1 388

1 356

*Med

2 051

1 935

1 815

1 774

1 733

High

2 080

2 052

2 023

1 957

1 891

Low

2 083

1 964

1 845

1 803

1 760

*Med

2 489

2 348

2 115

2 068

2 018

High

2 492

2 458

2 424

2 346

2 266

Low

2 396

2 258

2 120

2 071

2 020

*Med

2 932

2 766

2 593

2 533

2 474

High

2 944

2 904

2 863

2 769

2 674

Low

2 936

2 849

2 768

2 688

2 608

*Med

3 094

3 051

3 010

2 912

2 813

High

3 177

3 133

3 090

2 990

2 888

Low

2 965

2 795

2 625

2 564

2 503

*Med

3 579

3 530

3 480

3 366

3 250

High

3 675

3 624

3 573

3 456

3 337

Water Coil 2 row 3 row 2 row 3 row 2 row 3 row 2 row 3 row 2 row 3 row 2 row 3 row 2 row 3 row 2 row 3 row 2 row 3 row 2 row 3 row 2 row 3 row 2 row 3 row 3 row 4 row 3 row 4 row 3 row 4 row 3 row 4 row 3 row 4 row 3 row 4 row 3 row 4 row 3 row 4 row 3 row 4 row

25 753 720 1 160 1 112 1 229 1 177 1 132 1 084 1 448 1 387 1 500 1 437 1 507 1 444 1 928 1 847 1 954 1 872 1 937 1 856 2 339 2 241 2 341 2 243 2 282 2 186 2 756 2 640 2 767 2 650 2 522 2 416 3 046 2 918 2 985 2 859 2 786 2 667 3 363 3 222 3 453 3 308

Water 50 709 680 1 096 1 050 1 211 1 160 1 067 1 022 1 364 1 307 1 479 1 417 1 422 1 361 1 820 1 743 1 928 1 847 1 827 1 751 2 207 2 114 2 309 2 212 2 152 2 062 2 599 2 490 2 728 2 613 2 379 2 279 2 873 2 752 2 944 2 820 2 627 2 516 3 317 3 177 3 405 3 262

Heat Models 75 100 666 652 637 624 1 026 1 004 983 962 1 018 981 975 940 1 000 978 958 937 1 279 1 250 1 226 1 198 1 460 1 412 1 398 1 352 1 335 1 305 1 278 1 249 1 706 1 667 1 634 1 597 1 901 1 839 1 821 1 762 1 646 1 609 1 577 1 542 1 988 1 944 1 904 1 862 2 277 2 204 2 181 2 112 2 017 1 972 1 933 1 889 2 436 2 382 2 334 2 282 2 690 2 602 2 577 2 492 2 231 2 179 2 137 2 088 2 695 2 632 2 581 2 521 2 903 2 809 2 781 2 691 2 467 2 409 2 346 2 307 3 270 3 163 3 133 3 030 3 357 3 247 3 216 3 111

125 635 608 980 939 940 900 954 914 1 220 1 169 1 364 1 307 1 274 1 220 1 628 1 559 1 777 1 702 1 571 1 505 1 898 1 818 2 130 2 040 1 926 1 845 2 326 2 228 2 513 2 407 2 128 2 039 2 571 2 463 2 713 2 599 2 351 2 253 3 054 2 926 3 135 3 004

Application Guide / Air handler – Page 13


AIR HANDLER BLOWER PERFORMANCE (cfm vs inches H 2O) 60 Hz - BC Series 3 speed Motor “- 001”

Size

18

24

30

36

42

48

60

Electric Heat Models 0,2 0,3 0,4

Speed

0,1

0,5

Low

471

444

417

408

398

*Med

727

686

643

629

614

High

770

759

749

725

700

Low

664

641

623

605

574

*Med

906

855

802

783

764

High

940

927

914

884

854

Low

944

890

836

817

798

*Med

1 207

1 139

1 068

1 044

1 020

High

1 224

1 208

1 191

1 152

1 113

Low

1 226

1 156

1 086

1 061

1 036

*Med

1 465

1 382

1 245

1 217

1 188

High

1 467

1 447

1 427

1 381

1 334

Low

1 410

1 329

1 248

1 219

1 189

*Med

1 726

1 628

1 526

1 491

1 456

High

1 733

1 709

1 685

1 630

1 574

Low

1 728

1 677

1 629

1 582

1 535

*Med

1 821

1 796

1 772

1 714

1 656

High

1 870

1 844

1 819

1 760

1 700

Low

1 745

1 645

1 545

1 509

1 473

*Med

2 107

2 078

2 048

1 981

1 913

High

2 163

2 133

2 103

2 034

1 964

Water Coil 2 row 3 row 2 row 3 row 2 row 3 row 2 row 3 row 2 row 3 row 2 row 3 row 2 row 3 row 2 row 3 row 2 row 3 row 2 row 3 row 2 row 3 row 2 row 3 row 3 row 4 row 3 row 4 row 3 row 4 row 3 row 4 row 3 row 4 row 3 row 4 row 3 row 4 row 3 row 4 row 3 row 4 row

0,1 443 424 683 654 723 693 666 638 852 816 883 846 887 850 1 135 1 087 1 150 1 102 1 140 1 092 1 377 1 319 1 378 1 320 1 343 1 287 1 622 1 554 1 628 1 560 1 485 1 422 1 793 1 718 1 757 1 683 1 640 1 570 1 980 1 896 2 032 1 947

Water 0,2 417 400 645 618 713 683 628 602 803 769 871 834 837 801 1 071 1 026 1 135 1 087 1 076 1 030 1 299 1 244 1 359 1 302 1 267 1 214 1 530 1 466 1 605 1 538 1 400 1 341 1 691 1 620 1 733 1 660 1 546 1 481 1 952 1 870 2 004 1 920

Heat Models 0,3 0,4 392 384 375 367 604 591 579 566 599 577 574 553 589 576 564 551 753 736 721 705 859 831 823 796 786 768 752 735 1 004 981 962 940 1 119 1 082 1 072 1 037 969 947 928 907 1 170 1 144 1 121 1 096 1 340 1 297 1 284 1 243 1 187 1 161 1 137 1 112 1 434 1 402 1 374 1 343 1 584 1 531 1 517 1 467 1 313 1 283 1 258 1 229 1 586 1 549 1 519 1 484 1 709 1 653 1 637 1 584 1 452 1 418 1 381 1 358 1 925 1 862 1 844 1 783 1 976 1 944 1 893 1 831

0,5 374 358 577 553 553 530 561 538 718 688 803 769 750 718 958 918 1 046 1 002 925 886 1 117 1 070 1 254 1 201 1 134 1 086 1 369 1 312 1 479 1 417 1 253 1 200 1 513 1 449 1 597 1 530 1 384 1 326 1 798 1 722 1 846 1 768

Application Guide / Air handler – Page 14


WATER HEATING CAPACITY (kW) Unit Size 18 & 24

Water Coil Size

2 ROW

3 ROW

Ent. Water P.D Temp. (mmCE) (°C)

49 60 71 82 49 60 71 82

61 61 61 61 91 61 61 61

0,2 Air flow (m3/h) 680

1020

1360

2,6 3,9 5,2 9,6 3,3 4,8 6,4 7,9

3,2 4,6 6,0 7,3 4,0 5,7 7,4 9,1

3,5 5,0 6,5 8,0 4,4 6,2 8,1 9,9

Water flow (m3/h) 0,5 Air flow (m3/h) P.D (mmCE) 680 1020 1360

183 183 183 183 274 274 274 274

3,4 4,8 6,2 7,7 4,3 6,0 7,8 9,5

4,1 5,8 7,5 9,3 5,2 7,4 9,6 11,8

4,6 6,5 8,5 10,4 5,9 8,4 10,8 13,3

P.D (mmCE)

427 396 396 396 579 579 549 549

0,7 Air flow (m3/h) 680

1020 1360

3,7 4,5 5,2 6,4 6,7 8,3 8,2 10,2 4,6 5,8 6,4 8,1 8,3 10,5 10,2 12,9

5,1 7,3 9,4 11,6 6,6 9,4 12,1 14,9

Unit Size 30 & 36

Water Coil Size

2 ROW

3 ROW

Ent. Water Temp. (°C)

49 60 71 82 49 60 71 82

0,5 Air flow (m3/h)

P.D (mmCE) 1360 1700

152 152 152 122 213 183 183 183

5,1 5,3 7,2 7,5 9,3 9,8 11,5 12,0 6,2 6,7 8,8 9,5 11,5 12,3 14,1 15,1

2040

5,6 8,0 10,4 12,8 15,9 10,0 13,0 16,1

Water flow (m3/h) 0,7 0,9 3 Air flow (m /h) Air flow (m3/h) P.D P.D (mmCE) 1360 1700 2040 (mmCE) 1360 1700 2040

305 305 305 274 427 396 396 396

5,7 8,1 10,6 13,0 7,2 10,0 12,9 15,8

6,0 8,5 11,1 13,6 7,7 10,8 14,0 17,3

6,4 9,1 11,9 14,6 8,2 11,7 15,1 18,6

518 518 488 488 732 701 671 671

6,2 8,7 11,3 13,9 7,5 10,6 13,7

6,5 9,1 11,8 14,6 8,3 11,7 15,1 16,8 18,6

7,0 9,9 12,8 15,7 9,0 12,7 16,4 20,2

Unit Size 42 & 48

Water Coil Size

3 ROW

4 ROW

Ent. 0,7 Water Air flow (m3/h) P.D Temp. (mmCE) 2380 2550 2720 (°C)

49 60 71 82 49 60 71 82

244 244 244 274 305 305 305 305

9,6 13,6 17,7 21,8 11,3 16,0 20,7 25,5

9,9 14,0 18,1 22,3 11,6 16,4 21,3 26,1

10,1 14,3 18,5 22,8 11,9 16,8 21,8 26,8

Water flow (m3/h) 0,9 Air flow (m3/h) P.D (mmCE) 2380 2550 2720

427 396 396 396 518 518 518 488

10,6 15,0 19,4 23,9 12,5 17,7 22,9 28,1

10,9 15,4 20,0 24,6 12,9 18,2 23,6 29,0

11,2 15,8 20,5 25,3 13,2 18,7 24,2 29,8

1,1 Air flow (m3/h)

P.D (mmCE) 2380 2550 2720

610 610 579 579 793 793 762 732

11,3 15,9 20,6 25,3 13,3 18,8 24,3

11,6 16,4 21,3 26,2 13,8 19,4 25,1 29,9 30,9

11,9 16,9 21,9 26,9 14,2 20,0 25,9 31,8

All capacities are based on 21°C entering air temperature. For entering air temperature other than 21°C, use the following capacity correction factors: (22°C x 0,982) ♣ (20°C x 1,02) ♣ (19°C x 1,04) Glycol correction factors: (10% x 0,98) ♣ (20% x 0,95) ♣ (30% x 0,92) ♣ (40% x 0,88)

Application Guide / Air handler – Page 15


WATER HEATING CAPACITY (kW) Unit Size 60

Water Coil Size

3 ROW

4 ROW

Ent. 0,7 Water Air flow (m3/h) P.D Temp. (mmCE) 3060 3230 3400 (°C)

49 60 71 82 49 60 71 82

366 366 366 366 335 335 335 335

10,9 15,5 20,1 24,7 12,8 18,1 23,4 28,8

11,1 15,7 20,4 25,1 13,0 18,4 23,8 29,3

11,3 16,0 20,7 25,5 13,2 18,7 24,2 29,7

Water flow (m3/h) 0,9 Air flow (m3/h) P.D (mmCE) 3060 3230 3400

640 640 610 610 579 579 549 549

12,2 17,3 22,4 27,5 14,4 20,3 26,3 32,3

12,4 17,6 22,8 28,1 14,7 20,7 26,8 33,0

12,7 17,9 23,2 28,6 15,0 21,1 27,4 33,6

1,1 Air flow (m3/h)

P.D (mmCE) 3060 3230 3400

976 976 945 945 884 854 854 823

13,1 18,5 24,0 29,5 15,5 21,9 28,3

13,4 18,9 24,5 30,1 15,9 22,4 29,0 34,7 35,6

13,6 19,3 25,0 30,7 16,2 22,9 29,6 36,3

All capacities are based on 21°C entering air temperature. For entering air temperature other than 21°C, use the following capacity correction factors: (22°C x 0,982) ♣ (20°C x 1,02) ♣ (19°C x 1,04) Glycol correction factors: (10% x 0,98) ♣ (20% x 0,95) ♣ (30% x 0,92) ♣ (40% x 0,88)

Application Guide / Air handler – Page 16


WATER HEATING CAPACITY (Btu/h) Unit Size 18 & 24

Ent. Water Water Coil Temp. Size (°F) 120 2 140 ROW 160 180 120 3 140 ROW 160 180

H2O P.D. (ft) 0,2 0,2 0,2 0,2 0,3 0,2 0,2 0,2

1 Air flow (cfm) 400

600

800

9 004

10 979 11 914

13 209 17 628 32 738 11 286 16 401 21 792 26 908

15 600 20 302 25 065 13 771 19 506 25 320 31 193

16 942 22 065 27 260 14 944 21 177 27 500 33 891

Water flow (gpm) 2 H2O Air flow (cfm) P.D. 400 600 800 (ft) 11 639 13 997 15 683 0,6 16 452 19 823 22 240 0,6 21 316 25 727 28 834 0,6 26 217 31 687 35 621 0,6 14 528 17 826 20 160 0,9 20 495 25 194 28 524 0,9 26 511 32 641 36 991 0,9 32 564 40 145 45 532 0,9

3 Air flow (cfm)

H2O P.D. (ft) 1,4

400

600

800

12 536

15 396

17 522

1,3 1,3 1,3 1,9 1,9 1,8 1,8

17 683 22 872 28 091 15 582 21 942 28 343 34 771

21 757 28 184 34 659 19 636 27 701 35 833 44 014

24 793 32 151 39 573 22 659 32 004 41 442 50 947

Unit Size 30 & 36 Ent. Water Water Coil Temp. Size (°F) 120 2 140 ROW 160 180 120 3 140 ROW 160 180

H2O P.D. (ft) 05, 0,5 0,5 0,4 0,7 0,6 0,6 0,6

2 Air flow (cfm) 800

1 000

1 200

17 277 24 529 31 899 39 359 21 309 30 149 39 095 48 121

18 048 25 619 33 313 41 098 22 783 32 261 41 866 51 564

19 124 27 164 35 341 43 622 54 179 34 255 44 472 54 794

Water flow (gpm) 3 H2O Air flow (cfm) P.D. 800 1 000 1 200 (ft) 19 588 20 523 21 997 1,0 27 747 29 072 31 155 1,0 36 013 37 734 40 464 1,0 44 360 46 482 49 872 0,9 24 501 26 156 28 137 1,4 33 970 36 982 39 809 1,3 43 988 47 928 51 621 1,3 54 077 58 963 63 537 1,3

4 Air flow (cfm)

H2O P.D. (ft)

800

1 000

1 200

1,7 1,7 1,6 1,6 2,4 2,3 2,2 2,2

20 990 29 682 38 472 47 332 25 648 36 180 46 799 57 481

22 035 31 163 40 396 49 705 28 187 39 801 51 526 63 331

23 750 33 616 43 602 53 678 30 578 43 208 55 970 68 827

Unit Size 42 & 48 Ent. Water Water Coil Temp. Size (°F) 120 2 140 ROW 160 180 120 3 140 ROW 160 180

H2O P.D. (ft) 0,8 0,8 0,8 0,9 1,0 1,0 1,0 1,0

3 Air flow (cfm) 1 400

1 500

1 600

32 883 33 695 34 441 46 541 60 372 74 330 38 636 54 582 70 692 86 924

47 701 61 888 76 209 39 631 55 996 72 535 89 200

48 766 63 279 77 933 40 540 57 288 74 216 91 276

Water flow (gpm) 4 H2O Air flow (cfm) P.D. 1 400 1 500 1 600 (ft) 36 190 37 221 38 173 1,4 51 167 52 686 53 996 1,3 66 310 68 229 70 004 1,3 81 575 83 951 86 149 1,3 42 707 44 006 45 204 1,7 60 284 62 131 63 834 1,7 78 023 80 428 82 647 1,7 95 879 98 851 101 592 1,6

H2O P.D. (ft) 2,0 2,0 1,9 1,9 2,6 2,6 2,5 2,4

5 Air flow (cfm) 1 400

1 500

1 600

38 464

39 660

40 722

54 329 70 350 86 486 45 457 64 115 82 925

56 032 72 572 89 234 46 988 66 290 85 756

57 617 74 640 91 792 48 409 68 310 88 386

101 845

105 340

108 588

All capacities are based on 70°F entering air temperature. For entering air temperature other than 70°F, use the following capacity correction factors: (72°F x 0,982) ♣ (68°F x 1,02) ♣ (66°F x 1,04) Glycol correction factors: (10% x 0,98) ♣ (20% x 0,95) ♣ (30% x 0,92) ♣ (40% x 0,88)

Application Guide / Air handler – Page 17


WATER HEATING CAPACITY (Btu/h) Unit Size 60 Ent. Water Water Coil Temp. Size (°F) 120 2 140 ROW 160 180 120 3 140 ROW 160 180

H2O P.D. (ft) 1,2 1,2 1,2 1,2 1,1 1,1 1,1 1,1

3 Air flow (cfm) 1 800

1 900

2 000

37 308 37 936 38 521 52 797 68 481 84 309 43 662 61 666 79 853 98 192

53 693 69 650 85 756 44 406 62 721 81 224 99 863

54 526 70 737 87 101 45 095 63 698 82 492 101 427

Water flow (gpm) 4 H2O Air flow (cfm) P.D. 1 800 1 900 2 000 (ft) 41 636 42 459 43 229 2,1 58 874 60 047 61 145 2,1 76 308 77 839 79 273 2,0 93 886 95 781 97 555 2,0 49 104 50 118 51 065 1,9 69 318 70 759 72 104 1,9 89 723 91 598 93 347 1,8 110 265 112 579 114 739 1,8

H2O P.D. (ft) 3,2 3,2 3,1 3,1 2,9 2,8 2,8 2,7

5 Air flow (cfm) 1 800

1 900

2 000

44 672

45 650

46 570

63 115 81 747

64 508 83 564

65 818 85 273

100 517

102 764

104 879

52 882 74 605 96 514

54 114 76 356 98 793

55 271 77 999

118 557

121 369

124 009

100 931

All capacities are based on 70°F entering air temperature. For entering air temperature other than 70°F, use the following capacity correction factors: (72°F x 0,982) ♣ (68°F x 1,02) ♣ (66°F x 1,04) Glycol correction factors: (10% x 0,98) ♣ (20% x 0,95) ♣ (30% x 0,92) ♣ (40% x 0,88)

Application Guide / Air handler – Page 18


MAXIMUM LINE LENGTH FOR HEATING COILS USING PUMP OPTION All line lengths are total for supply and return Air Nominal Handler Pipe Size Size (ID) 0,23 18 & 24 1/2" 78 2 Row 3/4" 18 & 24 1/2" 78 3 Row 3/4" 1/2" 30 & 36 3/4" 2 Row 1” 1/2" 30 & 36 3/4" 3 Row 1” 3/4" 42 & 48 1” 3 Row 1 1/4" 3/4" 42 & 48 1” 4 Row 1 1/4" 3/4" 60 1” 3 Row 1 1/4" 3/4" 60 1” 4 Row 1 1/4" -

0,29 45 45 -

0,34 30 30 -

0,41 22 141 21 138 -

0,45 16 110 16 107 17 113 16 110 -

Maximum Supply Pipe Length (m) – Type K copper 3 Water flow (m /h) 0,52 0,57 0,64 0,68 0,75 0,79 0,86 0,91 0,98 1,02 11 7 5 2 80 60 46 36 10 6 4 2 77 57 43 32 11 8 5 3 83 63 49 39 30 23 18 13 154 122 98 78 11 7 4 2 80 57 46 36 27 20 15 10 141 109 85 66 41 32 25 19 15 11 8 160 129 104 84 67 54 176 38 30 23 17 13 9 6 151 121 97 78 61 48 157 37 28 21 16 11 7 4 144 113 89 70 52 39 131 37 29 22 16 12 8 5 148 116 93 74 57 44 145

1,09 5 43 142 3 37 123 1 27 97 2 32 112

1,13 3 34 115 1 27 96 18 69 23 85

1,36 -

1,59 -

1,81 -

Notes: 1. 2. 3.

Line lengths are based on water only. To adjust maximum line lengths for glycol, divide length by the factors shown in Table 2 IMPORTANT: Glycol should never be used in a potable water system All lengths are based on closed loop systems

Application Guide / Air handler – Page 19


4. 5. 6. 7.

Line lengths within the shaded areas should not be used when a water heater is the source of heat. When using a boiler for these line lengths, excessive line temperature loss will occur and must be accounted for Supply and return lines must be properly insulated to reduce temperature loss and to prevent freezing when passing through an unconditioned space All lengths include (12) 90° short radius elbows. To adjust for extra or fewer fittings, use the factors in Table 1 Always use full flow ball or gate valves to minimize pressure drop

Table 1 Pipe Size 1/2" 3/4" 1” 1 1/4"

90° SR el 0,46 0,61 0,82 1,10

Equivalent m of pipe 90° LR el 45° el 0,24 0,30 0,30 0,43 0,40 0,58 0,55 0,76

Gate valve 0,30 0,43 0,58 0,76

Table 2 % Glycol 10 20 30 40 50

60 1,04 1,08 1,13 1,19 1,24

Fluid temperature (°C) 71 82 1,04 1,02 1,07 1,04 1,11 1,08 1,16 1,12 1,21 1,17

Application Guide / Air handler – Page 20


MAXIMUM LINE LENGTH FOR HEATING COILS USING PUMP OPTION All line lengths are total for supply and return Air Nominal Handler Pipe Size Size (ID) 18 & 24 2 Row 18 & 24 3 Row 30 & 36 2 Row 30 & 36 3 Row 42 & 48 3 Row 42 & 48 4 Row 60 3 Row 60 4 Row

1/2" 3/4" 1/2" 3/4" 1/2" 3/4" 1” 1/2" 3/4" 1” 3/4" 1” 1 1/4" 3/4" 1” 1 1/4" 3/4" 1” 1 1/4" 3/4" 1” 1 1/4"

1 256 256 -

1,3 149 148 -

1,5 100 98 -

1,8 71 464 70 454 -

2 53 361 51 351 55 372 53 361 -

2,3 35 263 33 251 37 273 35 263 -

Maximum Supply Pipe Length (ft) – Type K copper Water flow (gpm) 2,5 2,8 3 3,3 3,5 3,8 4 4,3 23 15 8 198 152 118 20 12 5 186 140 105 25 16 10 208 162 128 99 76 58 43 504 401 321 257 23 14 8 188 152 118 89 66 48 33 461 359 280 217 134 104 81 63 48 35 526 422 341 277 221 126 97 75 57 43 30 497 397 319 257 200 121 92 69 51 37 23 473 372 293 230 172 123 94 72 54 40 27 485 382 306 244 187 -

4,5 25 177 576 19 156 514 12 127 430 16 143 476

4,8 16 141 467 11 120 405 3 90 318 8 106 367

5 9 111 378 4 90 315 59 228 77 278

6 -

7 -

8 -

Notes: 8. Line lengths are based on water only. To adjust maximum line lengths for glycol, divide length by the factors shown in Table 2 9. IMPORTANT: Glycol should never be used in a potable water system 10. All lengths are based on closed loop systems

Application Guide / Air handler – Page 21


11. Line lengths within the shaded areas should not be used when a water heater is the source of heat. When using a boiler for these line lengths, excessive line temperature loss will occur and must be accounted for 12. Supply and return lines must be properly insulated to reduce temperature loss and to prevent freezing when passing through an unconditioned space 13. All lengths include (12) 90° short radius elbows. To adjust for extra or fewer fittings, use the factors in Table 1 14. Always use full flow ball or gate valves to minimize pressure drop

Table 1 Pipe Size 1/2" 3/4" 1” 1 1/4"

90° SR el 1,5 2 2,7 3,6

Equivalent ft of pipe 90° LR el 45° el 0,8 1 1 1,4 1,3 1,9 1,8 2,5

Gate valve 1 1,4 1,9 2,5

Table 2 % Glycol 10 20 30 40 50

140 1,04 1,08 1,13 1,19 1,24

Fluid temperature (°F) 160 180 1,04 1,02 1,07 1,04 1,11 1,08 1,16 1,12 1,21 1,17

Application Guide / Air handler – Page 22


SIZE 18 – 36 installation configurations Shading indicates proper line connections Upflow

Upflow As shipped from factory (return in bottom or left side)

*Counterflow Field converted with kit (return in top)

Field converted (return in bottom or right side)

Bottom / Filter Frame

Liq.

Suc. Drains

Optional filter rack

Liq. Liq. Suc.

Optional filter rack

Suc.

Drains

Drains

Bottom / Filter Frame

Horizontal Right Factory ready if ordered as multi-position Or field converted with horizontal drain pan kit

Bottom / Filter Frame

Liq. Suc. Drains

* See price sheet for restriction on counterflow kits

Application Guide / Air handler – Page 23


SIZE 18 – 36 installation configurations Shading indicates proper line connections Horizontal Left Easily converted if ordered as multi-position Or with optional horizontal drain pan kit

Bottom / Filter Frame

Liq. Drains

Suc.

Application Guide / Air handler – Page 24


SIZE 42 - 60 installation configurations Shading indicates proper line connections Upflow As shipped from factory (return in bottom)

*Counterflow Field converted with kit (return in top) Bottom / Filter Frame

Suc.

Drains

Liq. Either set may be used

Drains

Suc.

Drains

Bottom / Filter Frame

Liq. Either set may be used

Drains

Horizontal Right Factory ready if ordered as multi-position Or field converted with horizontal drain pan kit

Suc. Liq.

Drains

* See price sheet for restriction on counterflow kits

Application Guide / Air handler – Page 25


SIZE 42 - 60 installation configurations Shading indicates proper line connections Horizontal Left Easily converted if ordered as multi-position Or with optional horizontal drain pan kit

Bottom / Filter Frame

Liq. Suc.

Drains

Application Guide / Air handler – Page 26


DIMENSIONS Size 18 - 36 Water connections

On cooling and electric line, voltage enters top on both sides

D

Line voltage

E

Knock out for pull disconnect if used

Right side & top only

Knock out for circuit breaker if used

24V Right hand side

Front View

Side View A

Liquid

Suction

Filter & rack

B

C

Return Duct Opening ( Unit Size 18 & 24 30 & 36

A 1 118 1 219

B 559 559

Dimensions in mm C D E 381 432 343 470 432 432

B 22” 22”

Dimensions in inches C D E 15” 17” 13 ½” 18 ½” 17” 17”

Depth x Width 438 260 438 356

Return Duct Opening Unit Size 18 & 24 30 & 36

A 44” 48”

Depth x Width 17 ¼” 10 ¼” 17 ¼” 14”

Application Guide / Air handler – Page 27


DIMENSIONS Size 42 - 60 Water connections

On cooling and electric line, voltage enters top on both sides

D

E

Line voltage Knock out f or pull disconnect if used

Right side & top only

Knock out for circuit breaker if used

24V Right hand side

Front View

Side View A

Suction

Liquid

Filter & rack

B

C

Return Duct Opening ( Unit Size 42 & 48 60

A 1 245 1 346

B 660 660

Dimensions in mm C D E 508 533 470 559 533 521

Depth x Width 559 400 559 451

Return Duct Opening Unit Size 42 & 48 60

A 49” 53”

B 26” 26”

Dimensions in inches C D E 20” 21” 18 ½” 22” 21” 20 ½”

Depth x Width 22” 15 ¾” 22” 17 ¾”

Application Guide / Air handler – Page 28



BELGIUM :

LENNOX BENELUX N.V./S.A. tel. : + 32 3 633 30 45 fax : + 32 3 633 00 89 e-mail : info.be@lennoxbenelux.com

CZECH REPUBLIC

:

JANKA LENNOX tel. : + 420 2 510 88 111 fax : + 420 2 579 10 393 e-mail : janka@janka.cz

FRANCE

:

LENNOX FRANCE tel. : + 33 1 64 76 23 23 fax : + 33 1 64 76 35 75 e-mail : marketing.france@lennoxfrance.com

GERMANY

:

LENNOX DEUTSCHLAND GmbH tel. : + 49 69 42 09790 fax : + 49 69 42 09 79 40 e-mail :info.de@lennoxdeutschland.com

GREAT BRITAIN , IRELAND :

LENNOX INDUSTRIES LTD tél. : + 44 1604 599400 fax : + 44 1604 594200 e-mail : ukmarketing@lennoxind.com

NETHERLANDS

LENNOX BENELUX B.V. tel. : + 31 33 2471 800 fax : + 31 33 2459 220 e-mail : info@lennoxbenelux.com

:

POLAND :

PORTUGAL

LENNOX POLSKA Sp. z o.o. tel. : + 48 22 832 26 61 fax : + 48 22 832 26 62 e-mail : info@lennoxpolska.pl

:

LENNOX CLIMATIZAÇAO LDA. tel. : +351 22 999 84 60 fax : +351 22 999 84 68 e-mail : marketing@lennoxportugal.com

RUSSIA :

LENNOXDISTRIBUTIONMOSCOW tel. : + 7 095 246 07 46 fax : + 7 502 933 29 55 e-mail : lennox.dist.moscow@mtu-net.ru

SLOVAKIA

:

LENNOX SLOVENSKO tel. : + 421 2 44 87 19 27 fax : + 421 2 44 88 64 72 e-mail : lennox.slovensko@lennox.sk

SPAIN :

LENNOX REFAC S.A. tel. : + 34 915 40 18 10 fax : + 34 915 42 84 04 e-mail : marketing@lennox-refac.com

UKRAINE

:

OTHER

EUROPEAN COUNTRIES, AFRICA, MIDDLE-EAST :

AGU_AH_1002-E

LENNOX DISTRIBUTION KIEV tel. : + 380 44 213 14 21 fax : + 380 44 213 14 21 e-mail : jankauk@uct.kiev.ua LENNOX DISTRIBUTION tel. : + 33 4 72 23 20 14 fax : + 33 4 72 23 20 28 e-mail : marketing@lennoxdist.com

Anari cn=Anari, o, ou, email=anari2011 @gmail.com, c=IR

www.Lennoxeurope.com


Turn static files into dynamic content formats.

Create a flipbook
Issuu converts static files into: digital portfolios, online yearbooks, online catalogs, digital photo albums and more. Sign up and create your flipbook.