Odorisation Control System OCS 2020/2030
Product information
serving the gas industry worldwide
OCS 2020/2030 Beschreibung, Funktionen, Gehäusevarianten
For safe and precise odor control The RMG OCS 2020/2030 control system was specially developed for the requirements of o dorisation technology. The control system enables the quantityproportional actuation of the dosing pump of a gas odorisation system. The required odorant quantity for the flowing gas quantity is calculated and imple mented in the control pulse for the odorant pump
Plain and simple The control unit operation takes place through a touch panel with plain text display. • Easy operation with intuitive menu guidance • Plain text display, meaning the translation of numbers or codes is omitted • Display in English or German, other languages on request
based on the volume pulse or quantity signal provided by the gas meter or the flow corrector. The control system is based on a Siemens PLC with plain text display on a 4" touch panel in black and white or an optional 6" colour display. The control unit has a modular design and can be individually adapted to the requirements of any odorisation system.
Safe If the flow signal fails, emergency odorisation can take place according to a fixed flow specifi cation or according to average values during the last 48 hours.
OCS 2020/2030
OCS 2020
OCS 2030
The control system in the basic design • Control of the dosing pump via externally generated quantity-proportional pulses • Meter pulse monitoring • Direct pump stroke setpoint / actual comparison • Fault message list with plain text display when the maximum stroke frequency of the dosing pump is exceeded • Buffering and eradication of external volume pulses • Addition or subtraction of the external volume pulse with two gas rails • Internal pulse transmitter • Automatic mode • Manual mode for maintenance and testing purposes • Calculation for the adjustment of the odorisation blast • Calculation of the pump setting • Time-dependent solenoid valve actuation for injection lines • Four outputs for freely programmable fault messages • Delivery rate monitoring with alarm triggering • Fill level monitoring with alarm triggering when the limit value is undercut • Collective fault message with indicator lamp • Inspection function • Conversion of the meter mode (Z-switching)
The control system with additional functions • Seven relay outputs for freely programmable messages • Calculation of the foreseeable time until the container replacement / container filling • Pump stroke calculation with correction factor (only ODM) • Calculation of the odorant concentration with remote indication (4 to 20 mA) • Freely programmable actuation of two dosing pumps with one control system • External setpoint specification (Hardware) • Actuation of the overfill safeguard • Setpoint feedback • Pump fault evaluation with automatic switch-over (main / reserve mode) • Customer-specific message input Additional options • Expansion possibilities with other interfaces • Larger 6" touch panel with colour display • Remote visualisation via internet connection • Independent control of additional pumps • Additional programmable customer-specific functions • Ethernet interface for remote connection • Processing of operational flow rates and VB pulses with additional switching of the meter pressure signal (quantity conversion function cannot be calibrated)
Voltage supply 230 V AC / 50 Hz
Housing options Wall housing (compact switch cabinet) As a control door housing, opening right or left, made of steel sheet with the dimensions: W x H x D = 500 x 500 x 210 mm Protection class: IP65 19" housing 19" dummy panel with cut-out for main switch and indicator lamp: 4" panel W x H x D = 88 MU x 4 U x 100 mm
6" panel W x H x D = 88 MU x 6 U x 100 mm 1 MU (modular unit) = 43.13 mm 1 RU (rack unit) = 5.02 mm Mounting plate For installation in the switch cabinet or on the 19" pivoting frame, dimensions: W x H x D = 441 mm x 470 mm x 200 mm
More information You want to know more about the solutions RMG can offer to the gas industry? Talk to your local contact. Or visit our website www.rmg.com GERMANY
ENGLAND
Honeywell Process Solutions
Honeywell Process Solutions
RMG Regel + Messtechnik GmbH
Bryan Donkin RMG Gas Controls Ltd.
Osterholzstrasse 45
Enterprise Drive, Holmewood
34123 Kassel, Germany
Chesterfield S42 5UZ, England
Phone: +49 (0)561 5007-0
Phone: +44 (0)1246 501-501
Fax:
Fax:
+49 (0)561 5007-107
+44 (0)1246 501-500
Honeywell Process Solutions
CANADA
RMG Messtechnik GmbH
Honeywell Process Solutions
Otto-Hahn-Strasse 5
Bryan Donkin RMG Canada Ltd.
35510 Butzbach, Germany
50 Clarke Street South, Woodstock
Phone: +49 (0)6033 897-0
Ontario N4S 0A8, Canada
Fax:
Phone: +1 (0)519 5398531
+49 (0)6033 897-130
Fax:
+1 (0)519 5373339
Honeywell Process Solutions RMG Gaselan Regel + Messtechnik GmbH
USA
Julius-Pintsch-Ring 3
Honeywell Process Solutions
15517 Fürstenwalde, Germany
Mercury Instruments LLC
Phone: +49 (0)3361 356-60
3940 Virginia Avenue
Fax:
Cincinnati, Ohio 45227, USA
+49 (0)3361 356-836
Phone: +1 (0)513 272-1111 Honeywell Process Solutions
Fax:
+1 (0)513 272-0211
WÄGA Wärme-Gastechnik GmbH Osterholzstrasse 45 34123 Kassel, Germany Phone: +49 (0)561 5007-0 Fax:
+49 (0)561 5007-207 Odorisation Control System OCS 2020/2030 2013-08 © 2013 Honeywell International Inc.