RMG 934-BP-T
RMG 934-BP-T End-of-line Flame Arrester Pipe Sizes
DN25, DN32, DN40, DN50, DN65, DN80, DN100, DN125, DN150, DN200 1", 11?4", 11 ?2", 2", 21 ?2", 3", 4", 5", 6", 8"
Connection Standards
-ISO 7005 PN10 -ANSI B16.5 – 150 RF
Materials
Strip protection: Stainless steel, special alloys Body: Carbon steel, stainless steel, special alloys Hood: Plexiglass
Coating
Optional
Temperature Sensor
Resistance thermometer with ignition protection type - Inherently safe (E Ex i) - Pressure-resistant enclosure (E Ex d)
Protection System
End-of-line deflagration and short-timeburning flame arrester
Approval
EC-type examination certificate based upon Directive 94/9/EG, according to ATEX 95 and EN 12874
Protection
Gas/air or steam/air mixtures of the following explosion groups: – I (methane) NSW ≥ 1.14 mm – IIA (D) NSW ≥ 0.90 mm – IIB3 (C) NSW ≥ 0.65 mm – IIC (B) NSW ≥ 0.50 mm To top