RMG 931-A-T

Flame arrester RMG-931 A-T Pipe Protection Protection System

Tube protection against deflagration

Approval

EC-type-examination certificate based on directive 94/9/EC, according to ATEX 95 and EN 12874

Protection

Gas/air or steam/air mixtures of the explosion groups: – I (methane) NSW ≥ 1.14 mm – IIA (D) NSW ≥ 0.90 mm

Pipe Sizes

-DN40 11/2“

Connection Standards

-DIN 2501 PN10 -ANSI B16.5 – 150 RF

Materials

Strip protection: Stainless steel Body/cap: Carbon steel, stainless steel

Coating

Optional

Temperature Sensor

Resistance thermometer with ignition protection type – Inherently safe (E Ex i) – Pressure-resistant enclosure (E Ex d) To top