The VRV air conditioning system is the world’s first individual air conditioning system with variable refrigerant flow control and was commercialized by Daikin in 1982. VRV is the trademark of Daikin Industries Ltd., which is derived from the technology we call ‘Variable Refrigerant Volume’.
European design Over the years, the Daikin VRV systems have been designed with European taste in mind, optimised for the European climate and manufactured in Europe for Europe. As the market leaders, Daikin understands the European market.
Setting the standard Daikin’s continuous development of the VRV air conditioning system means it has always been and will always continue as the benchmark standard for European air conditioning systems. The VRV VI is currently setting challenging new standards for seasonal efficiency, optimised climate control and ease of installation.
A total solution The Daikin VRV Total Solution service provides a single point of contact for the design and maintenance of each integrated climate control system. By making a careful choice from our modularised units the right mix of equipment and technology can be selected to ensure the optimal balance of temperature, humidity and air freshness for the perfect comfort zone while delivering maximum energy efficiency, minimum operating costs and reduced CO2 emissions.
3
VRV
VRV
The original
Why choose VRV? Low operating costs Our latest equipment is designed to optimise performance of the total system, automatically, every minute of the day. This includes highly efficiency outdoor units, indoor units with intelligent sensors, heat recovery technology, smart energy management controls and much more. According to the Franklin + Andrews, one of the world’s leading construction economists, running costs for VRV heat recovery systems compare highly favourably with a 2 or 4 pipe fan coil system. Running costs per m2 Gross Floor Area of a fan coil system can be 40 to 72% higher compared to a VRV heat recovery system. A VRV system is more space efficient than a chiller too, because it requires much less plant space. For example, Franklin + Andrews estimates that VRV system could take up 29% less plant space than a chiller system. And in a highly competitive market place, offering the most flexible and efficient use of office space can be a real deal breaker.
Personal comfort for tenants When viewed from the perspective of the occupants of a building, it is the comfort level provided by the climate control system that is the most important and so the temperature has to be right, there has to be enough fresh air with the correct humidity level and the sound level has to be minimized. Our VRV system addresses all of these requirements and provides individual control where possible. Sound levels of our indoor units can be as low as 19 dBA. Futhermore VRV IV continues to provide heating, even when in defrost mode, providing the answer to any perceived disadvatages of using a heat pump for monovalent heating. While in cooling mode it eliminates any cold draught thanks to higher outblow temperatures.
Meeting tomorrow’s legislation today VRV also meets the requirements of the Energyrelated Performance Directive and has been designed for seasonal efficiency with future legislative requirements in mind. Furthermore the VRV provides greater flexibility to meet current and future client requirements, because the system can be designed, built and commissioned zone by zone and tailored to the needs of each building tenant throughout a phased refurbishment programme.
4
VRV
Precise zone control to suit building occupancy Each floor – even each room – can be individually controlled to maximise energy efficiency and prevent energy waste. This versatility makes VRV ideal for buildings with multiple tenants, which may have vacant areas and variable periods of high and low usage.
Modular approach gives greater flexibility VRV’s modular approach provides greater flexibility to balance heat loads in different parts of the building. VRV also offers extended piping lengths so the system can be designed flexibly to suit buildings of many different sizes and shapes.
Reliability you can depend on Of course, ensuring lower running costs depends on system reliability and efficiency over its entire lifetime. So it’s reassuring to know that Daikin has an unparalleled reputation for quality, reliability and after sales service.
5
The VRV total solution Many buildings today typically operate quite separate systems for heating, cooling, refrigeration and hot water. As a result, a huge amount of energy is wasted. To provide a much more efficient alternative, VRV technology has been developed into a total solution managing up to 50% of a buildings energy consumption giving large potential to cost saving.
Manage up to 50% of your building’s energy consumption
Water heating
Other
Space heating
Office equipment
Integrate third party equipment
Lighting
Space cooling Ventilation
Source: EIA; Commercial buildings Energy consumption survey
6
For hotels, offices, retail, home, ...
Heating & cooling
Intelligent control systems 22
• •
• Mini BMS with integration of Daikin and third party equipment • Integration with intelligent control solutions with energy management tools to reduce running costs
Combine VRV indoor units with stylish indoor units in one system. New round flow cassette sets the standard for efficiency and comfort.
Low temperature hydrobox for highly efficient space heating through • • • •
Biddle air curtain
Underfloor heating Low temperature radiators Heat pump convector Hot water from 25 to 45°C
• A highly efficient solution for doorway climate separation
Ventilation
High temperature hydrobox* for efficient hot water production for • • • •
Showers Sinks Tapwater for cleaning Hot water from 25 to 80°C
• Combined fresh air treatment and air conditioning
*only for connection to VRV heat recovery
7
SOLUTIONS
One system, multiple applications
Hospitality
with economy
A hotel’s reputation depends on how welcome and comfortable guests feel during their stay. Yet at the same time, hotel owners must maintain complete control of their operation costs and energy consumption.
22
Intelligent hotel room controller
Concealed unit Especially developed for small, well-insulated rooms such as bedrooms
Puts the hotel owner in full control of the energy use
Hot water
Centralised control
Heating water with renewable energy
Smart energy management 8
SOLUTIONS
Efficiency in
the workplace Efficient building and facilities management are key to minimising operational costs
22
Fully flat cassette
Fresh air
Design & Genius in one
A healthier office atmosphere
Centralised control
Hot water
Complete Daikin package for office building management
Cutting the cost of hot water 9
Reducing
retail costs
In the current commercial environment, retailers are under pressure to reduce both store development and running costs. Legislation adds further financial pressure with different energy efficient schemes. Therefore affordable, energy efficient solutions are vital to minimise lifetime costs, while ensuring compliance with the latest regulations.
22
Round flow cassette with auto cleaning panel 50% energy saving compared to standard cassettes
User-friendly control
Biddle air curtain
Create a comfortable environment for customers
Highly efficient solutions to combat the issue of climate separation across your doorway
10
SOLUTIONS
Residential solutions There is no place like home. 22
Daikin Emura Remarkable blend of iconic design and functionality
Did you know that‌
22
Nexura Combines the feel of a radiator with the comfort and efficiency of a heat pump
‌ when you opt for a Daikin air conditioner, you are also thinking of the environment? When we produce your air conditioner, we do our utmost to recycle, reduce waste and use renewable energy.
11
What is new? VRV IV heat recovery – REYQ-T 360° efficiency
p44
›› Improved operational efficiency: ·· Improved efficiency during heat recovery mode with 15% ·· Free heating or hot water by recovering heat from areas requiring cooling ·· Optimal comfort for everybody by simultaneous ·· cooling spaces while heating others
›› Improved design efficiency: ·· Integrated climate control covering all thermal loads in the building ·· Free combination of outdoor units, single and multi BS boxes ·· Unique range of single and multi BS boxes
›› Improved installation efficiency: ·· Fully redesigned multi BS boxes, smaller and up to 70% lighter ·· No limit on number of unused ports ·· Connect indoor units up to 28kW to a single and multi BS box
Integrating VRV IV technologies on the full outdoor unit range ›› Replacement VRV IV heat recovery - RXYQQ-T ·· VRV IV standards: Variable Refrigerant Temperature, Continuous heating, VRV configurator & 7 segment display ·· VRV IV technologies ·· Covers all thermal needs of a building: hot water (LT & HT hydrobox), ventilation, air handling unit and Biddle air curtains ·· ‘Free’ heating and hot water by recovering heat from areas requiring cooling ·· The perfect personal comfort for guests/tenants via simultaneous cooling and heating ·· Unique range of single and multi BS boxes
›› Water cooled VRV IV - RWEYQ-T ·· VRV IV standards: Variable Refrigerant Temperature, VRV configurator & 7 segment display ·· Covers all thermal needs of a building: hot water (LT hydrobox), ventilation, air handling unit and Biddle air curtains ·· Unified range for standard and geothermal series simplifies stock ·· Variable Water Flow control of water pump increases flexibility and control
12
p66 / p72
Daikin Emura - FTXG-LW/S
p100
Heat reclaim ventilation - VAM and VKM ·· ·· ·· ·· ··
WATH’S NEW
·· Unique design. Designed in Europe for Europe. ·· Improved comfort thanks to 2-area intelligent eye, 3D air flow, sound levels down to 19dBA ·· Connectable to VRV IV and VRVIII-S heat pump
p118
High energy efficiency with DC fan motors Optional CO2 sensor saves energy while improving indoor air quality Optional medium (M6) and fine (F7, F8) dust filters for VAM-FB Shorter installation time thanks to easy adjustment of nominal air flow rate Total fresh air solution with optional supply of electrical heater (VAM-FA/FB)
Plug & play connection to Daikin Air Handling Units
p124
·· Complete plug & play solution including AHU, ERQ or VRV condensing unit and all unit control (EKEQ, EKEX, DDC controller), factory mounted and configured ·· Used when the commercial ventilation range cannot satisfy the ventilation requirement (up to 140,000 m³/h) ·· High efficiency ·· High comfort levels thanks to rapid response of ERQ and VRV to temperature fluctuations
Simplified wired remote control for hotel applications p135 ·· Symbol driven interface for intuitive control ·· Contemporary design ·· Change set point automatically when guests leaves the room or opens the window, saving energy ·· Meets all the guests needs because every room is individually controlled
- DCM601A51
·· Cost competitive mini BMS ·· Cross-pillar integration of Daikin products (VRV hydroboxes, air curtains, AHU, refrigeration indoors, Chillers, …) ·· Integration third party equipement via WAGO and BACnet
13
p138
Our references Porta fira Hotel santos porta fira
“This project reinforces Daikin's position as a leader in the air conditioning of large-scale structures, able to provide solutions that stand out not only for their accuracy and reliability, but also for their energy efficiency.”
74 outdoor units (60 x VRV heat recovery outdoor units) controlled via Intelligent manager, 664 indoor units, 2 x air cooled chillers (EWAD 600 BJYNN/Q)
The Range Super store
“We were very happy to work with Daikin UK to incorporate one of the latest fully integrated renewable systems that would provide heating, hot water, and air conditioning, allowing The Range at Warrington to have a fully controllable system with operation flexibility according to requirements.” Brad Hurter, CDS Group
The Range, UK 7 x VRV IV heat pump with continuous heating, 71 round flow cassettes, RTD control, Intelligent Touch Manager
14
the best solution? Heat Pump
VRV IV heat pump ›› ›› ›› ››
Covers all thermal needs of a building: hot water (LT hydrobox), ventilation, air handling unit and Biddle air curtains Connectable to stylish indoor units (Daikin Emura, Nexura) VRV IV standards: Variable Refrigerant Temperature, Continuous heating, VRV configurator & 7 segment display VRV IV technologies
Other VRV heat pumps VRVIII-S ›› ›› ››
VRVIII-C optimised for heating
Especially designed for small capacities Space saving design Either connect VRV or stylish indoor units: Daikin Emura, Nexura…
››
Developed for heating operation at low ambient conditions.
››
Extended operation range for heating down to -25°C Stable heating capacity and high efficiencies at low ambient temperatures
››
Heat Recovery
›› ›› ›› ›› ›› ››
REPLACEMENT
VRV Classic ››
For smaller projects with standard cooling & heating requirements
››
Connectable to all VRV indoor units, controls and ventilation
Covers all thermal needs of a building: hot water (LT & HT hydrobox), ventilation, air handling unit and Biddle air curtains ‘Free’ heating and hot water by recovering heat from areas requiring cooling The perfect personal comfort for guests/tenants via simultaneous cooling and heating Unique range of single and multi BS boxes VRV IV standards: Variable Refrigerant Temperature, Continuous heating, VRV configurator & 7 segment display VRV IV technologies
››
Cost-effective upgrade for R-22 systems, which cannot be serviced and maintained anymore after 01/01/2015
›› ›› ›› ›› ›› ››
Fast replacement Up to 81% more efficient than an R-22 system VRV IV standards: Variable Refrigerant Temperature, VRV configurator & 7 segment display VRV IV technologies Connectable to ventilation, air handling units and Biddle air curtains Available in heat recovery and heat pump
›› ›› ››
Allows heat recovery within the total building, thanks to the storage of energy in the water circuit. Compact design and stacked configuration possible. Suitable for multi-storey and large buildings because of the hardly unlimited possibilities of water piping.
›› ›› ››
Unified range for standard and geothermal series simplifies stock Variable Water Flow control of water pump increases flexibility and control VRV IV standards: Variable Refrigerant Temperature, VRV configurator & 7 segment display Covers all thermal needs of a building: hot water (LT hydrobox), ventilation, air handling unit and Biddle air curtains
››
15
PORTFOLIO
Which VRV outdoor system offers me
Portfolio
Outdoor unit range Type
Product name
HEAT PUMP
System
4
5
6
8
10
12
13
14
16
18
20
RYYQ-T Heat pump with continuous heating
*1
*1
*1
RXYQ-T Heat pump without continuous heating
*1
*1
*1
*1
*1
22
AIR COOLED
RXYSQ-P8V1 (Single phase) RXYSQ-P8Y1 (Three phase)
RTSYQ-PA Heat pump optimised for heating
RXYCQ-A
REYQ-T
new
*1
*1
*1
HEAT RECOVERY
REYQ-P8/P9 Small footprint combination
REYHQ-P High COP combination REYAQ-P
System
HEAT PUMP
HEAT RECOVERY
WATER COOLED
for connection with heating only hydrobox
RWEYQ-T
Type
new
Product name
4
VRVIV-Q - H/P HEAT PUMP
HEAT RECOVERY -
RXYQQ-T REPLACEMENT VRV
AIR COOLED
new
8
10 280
12
13 360
14
16
18
20
22
460
500
540
636
*1
RQCEQ-P VRVIII-Q - H/R
Single unit
Multi combination 1
5 140
Capacity class
Not a standard combination (free combination)
16
*1
*1
: component is connectable x : component is not connectable
PORTFOLIO
Not all components are connectable at the same time to one outdoor unit. Refer to the engineering databook for more information.
22
Capacity (HP)
28
30
32
34
36
38
40
42
44
46
48
50
52
54
Air Hydrobox curtain connection
Control systems
x
x
x
x
x
x
x
x
x x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
Low temperature hydrobox for VRV
26
Ventilation
High temperature hydrobox for VRV
24
Indoor units
Capacity (HP) 42
44
46
48
50
52
54
17
Network solutions (such as DCS6*/DAM/DMS)
40
Individual control (such as BRC)
848
38
Centralised control (such as DCS3*/DST)
816
36
Biddle Air curtain for VRV (CYV)
744
34
AHU connection kit (such as EKEXV)
712
32
Heat Reclaim ventilation (such as VAM)
30
Fresh air indoor units (such as FXMQ-MF)
28
VRV type indoor units (such as FXSQ)
26
Residential type indoor units (such as Daikin Emura)
24
Indoor unit range With 20 different indoor unit types and a range of 14 different capacities available, VRV indoor units fit rooms of any size or shape, tailored to the needs of the building owner.
Capacity 15
20
25
32
40
50
63
71
Cooling capacity (kW)1
1.7
2.2
2.8
3.6
4.5
5.6
7.1
Heating capacity (kW)2
1.9
2.5
3.2
4.0
5.0
6.3
8.0
FLOOR STANDING
CEILING SUSPENDED
WALL MOUNTED
CONCEALED CEILING
CEILING MOUNTED CASSETTE
Type
Model
Product name
Round flow cassette autocleaning function3 Presence & floor sensor3
FXFQ-A
Fully flat cassette Presence & floor sensor3
FXZQ-A
2-way blow ceiling mounted cassette
FXCQ-A
Ceiling mounted corner cassette
FXKQ-MA
Small concealed ceiling unit
FXDQ-M9
Slim concealed ceiling unit
FXDQ-A
Concealed ceiling unit with inverter driven fan
80
100
125
140
200
250
8.0
9.0
11.2
14.0
16.0
22.4
28.0
9.0
10.0
12.5
16.0
18.0
25.0
31.5
FXSQ-P
Concealed ceiling unit with inverter driven fan
FXMQ-P7
Large concealed ceiling unit
FXMQ-MA4
Wall mounted unit
FXAQ-P
Ceiling suspended unit
FXHQ-A
4-way blow ceiling suspended unit
FXUQ-A
Floor standing unit
FXLQ-P
Concealed floor standing unit
FXNQ-P
Nominal cooling capacities are based on: indoor temperature: 27°CDB, 19°CWB, outdoor temperature: 35°CDB, equivalent refrigerant piping: 5m, level difference: 0m. Nominal heating capacities are based on: indoor temperature: 20°CDB, outdoor temperature: 7°CDB, 6°CWB, equivalent refrigerant piping: 5m, level difference: 0m 3 Optional 4 Not connectable to VRV III-S 1 2
18
PORTFOLIO
Connectable outdoor unit
Capacity
CONCEALED CEILING
CEILING MOUNTED CASSETTE
Type
Round flow cassette (incl. autocleaning function1)
FCQG-F
FFQ-C
Fully flat cassette
WALL MOUNTED CEILING SUSPENDED FLOOR STANDING
15
20
25
35
42
50
60
71
Small concealed ceiling unit FDBQ-B
Slim concealed ceiling unit FDXS-F(9)
Concealed ceiling unit with inverter driven fan
FBQ-C8
FTXG-LW/ LS
Wall mounted unit
CTXS-K FTXS-K
Wall mounted unit
FTXS-G
Ceiling suspended unit
FHQ-C
Wall mounted unit
FVXG-K
Floor standing unit
FVXS-F
Flexi type unit
FLXS-B(9)
Nexura floor standing unit
1
RXYSQ-P8V1 RXYSQ-P8Y1
Product name
Daikin Emura
new
RYYQ-T RXYQ-T
Model
Decoration panel BYCQ140CG + BRC1E51A needed
19
Ventilation range Humidification: optimise the balance between indoor and outdoor humidity Ventilation: provision of fresh air Heat recovery: recovers heat and moisture from the outgoing air to maximise comfort & efficiency
Air processing: heats or cools incoming fresh air maximising comfort and minimizing the load on the air conditioning installation
Filtration: Removes dust, pollution and odours from the air
Air flow rate (m3/h) Type
name VAM-FA/FB
HEAT RECLAIM VENTILATION
OUTDOOR AIR PROCESSING UNIT 1
VKM-GB
2 3
0
200
400
600
800
1,000 1,500 2,000 4,000 6,000 8,000
›› Ventilation ›› Heat recovery ›› Ventilation ›› Heat recovery ›› Air processing
VKM-GBM
›› ›› ›› ››
FXMQ-MF
›› Ventilation ›› Air processing
AIR HANDLING DX total fresh air UNITS package
1
Components of indoor air quality
›› ›› ›› ›› ››
Ventilation Heat recovery Air processing Humidification
Ventilation Heat recovery Air processing Humidification Filtration
(3)
Not connectable to VRVIII-S (RXYSQ-PAV, RXYSQ-PAY) Air flow rate is a calculated indication only, based on the following values: heating capacity EKEXV-kit * 200m³/h Daikin AHU connected to Daikin chiller solution
20
124,000
Biddle air curtain range Product Name
BIDDLE AIR CURTAIN FREE HANGING
CYV S/M/L-DK-F
BIDDLE AIR CURTAIN CASSETTE
CYV S/M/L-DK-C
BIDDLE AIR CURTAIN RECESSED
CYV S/M/L-DK-R
PORTFOLIO
Type
Door height (m)
4
3.0m 3
2.75m
2.5m
2.3m
2.4m
2.5m
2.3m
2.15m
2.0m
2
1
S
M
L
Favourable ex: covered shopping mall or revolving door entrance
S
M
L
S
Normal ex: little direct wind, no opposite open doors, building with ground floor only
M
L
Unfavourable ex: location at a corner or square, multiple floors and / or open stairwell
Installation condition
Hydrobox range Capacity Product name
Leaving water temperature range
LOW TEMPERATURE HYDROBOX
HXY-A
5°C - 45°C
HIGH TEMPERATURE HYDROBOX
HXHD-A
25°C - 80°C
Type
80
125
Network solutions
ITC ITM
Maximum indoor unit groups
ACNSS connection Air Conditionning Network Service System
Free cooling
Sliding temperature
Pre-cool/heat
Interlock
Other
HTTP option
+
Web access & control
+
PPD
Visualisation
Options
History (operation, malfunction…)
Malfunction code
Filter status
Forced off
+
Basic control functions: ON/OFF status, operation mode, set point temp.
+
Timer extension
Weekly schedule & special day pattern
Monitoring
Automatic changeover
Setback
Temperature limitation
(3)
Refrigerant containment check
(3)
Control Basic control functions:on/off, temp, setting, air flow sttings
3rd party equipment integration
Touch screen
Integration Mini BMS for heating, air conditioning applied systems & refrigeration units
Layout screen
Screen
64
Std
+
2560
DMS-IF 1
64
BACNET 2
4x64
1
Gateway for Lonworks networks
2
Gateway for BACnet networks
3
BACnet and WAGO
21
Our references
Labo LADR Medical laboratory
4 x VRV heat recovery outdoor units (1 x REYQ42P8; 1 x REYQ44P8 1 x REYQ46P8; 1 x REYQ48P8) 2 x Sky Air outdoor units (RZQ200C) 4 x Sky Air indoor units (FHQ100B) Ventilation via air handling units Control via Intelligent Touch Controller
Total building approach using waste heat for offices and allowing individual control
Sky Tower
“The high quality of presales service provided by the Daikin sales team, the proposed solution with proven reliability from past references and extensive research to offer the best solution convinced the customer.”
Office and residential project
VRV: 8 x VRV III heat recovery outdoor units (8 x REMHQ12P8) 151 x VRV III heat pump outdoor units (57 x RXYQ18P9; 1 x RXYQ8P9; 1 x RXYQ10P9; 5 x RXYQ12P9; 2 x RXYQ16P9; 21 x RXYSQ4P8Y1; 2 x RXYSQ5P8Y1; 2 x RXYSQ6P8Y1) 653 x VRV indoor units Ventilation: 10 x ERQ250AW1; 154 x VAM500FA; 90 x VAM250FA; 42 x VAM800FA; 12 x VAM600FA
22
Advanced software tools for system design assistance, enabling you to select & sell the product that fits your customer needs
Sales supporting apps Daikin E-data app contains an overview of all Daikin Europe N.V. products that are available in your country, in your own language. You can easily browse the products to find the engineering data you need.
Seasonal Solutions Simulator With this software tool you can simulate the seasonal efficiency, the annual power consumption and CO2 emission for a given climate, load profile (cooling, heating, heat recovery, covalent, bivalent‌) and (combination of ) system(s). With its intuitive and graphical appealing interface, a simulation can be made in a matter of minutes. The solution basket system enables you to compare the results of several system configurations.
Selection software Xpress Xpress is a flexible design software to optimise equipment selection in cost and it enables you to make a high efficient building design.
VRV Pro VRV pro is a true VRV design tool. The program enables VRV air conditioning systems to be engineered in a precise and economical way, taking into account the complex piping rules. Moreover, it ensures optimum operating cycles and maximum energy efficiency. In this way, it gives the designer the possibility to make accurate selections and get competitive quotations for each project.
For a complete line-up of tools & downloads, visit: http://extranet.daikineurope.com/en/software/default.jsp or contact your local representative 23
PORTFOLIO
Tools
VRV IV = 3 revolutionary standards • Variable refrigerant temperature • Continuous comfort during defrost • VRV configurator
++ VRV IV technologies ++ Integrated climate control
24
Customize your VRV for best seasonal efficiency & comfort. Thanks to its revolutionary varialble refrigerant temperatue technology, VRV IV continuously adjusts the refrigerant temperature to the actual temperature and capacity needed, thus providing optimal seasonal efficiency at all times. • Improved seasonal efficiency with 28% • Weather dependent • Customer comfort is assured with automatic adjustement of refrigerant temperature leading to higher outblow temperatures (avoiding cold draft)
Different modes: The system can be easily customised via preset modes. With the modes you choose to optimise the system towards your required balance between comfort and efficiency
Automatic mode
High sensible mode
(Default setting on VRV IV)
Quick reaction speed
Top efficiency
The perfect balance : Top efficiency throughout most of the year. Quick reaction speed on the hottest days
Basic mode (current VRF standard)
Quick reaction Top speed efficiency Year round top efficiency
Quick reaction Top speed efficiency Quick reaction to peak load, to maintain set point
Effect of preset modes on efficiency and reaction speed: Automatic mode
(Default setting on VRV IV)
High sensible mode
Basic mode (current VRF standard)
Load
Load
Load
Refrigerant volume (VRV)
Refrigerant volume (VRV)
Refrigerant volume (VRV)
Refrigerant temperature (VRT)
Refrigerant temperature (VRT)
Refrigerant temperature (VRT) Efficiency
Efficiency
Efficiency
Unique VRT automatic mode leads to 28% increase in seasonal efficiency In automatic mode the system will go for maximum efficiency throughout most of the year and for quick reaction speed on the hottest days, ensuring comfort at all times while still resulting in an increased seasonal efficiency up to 28%.
Automatic mode
Quick reaction speed
(Default setting on VRV IV)
Top efficiency
The perfect balance : Maximum efficiency throughout most of the year. Quick reaction speed on the hottest days
25
VRV IV TECHNOLOGIES
1. Variable refrigerant temperature
2. Continuous heating during defrost VRV IV continues to provide heating even when in defrost mode, providing an answer to any perceived disadvantages of specifying a heat pump for monovalent heating. • Indoor comfort not affected either via the unique heat accumulating element or alternate defrost • The best alternative to traditional heating systems Room temperature
Heat pumps are known for their high energy efficiency in heating, but they accumulate ice during heating operation and this must be melted periodically using a defrost function that reverses the refrigeration cycle. This causes a temporary temperature drop and reduced comfort levels inside the building. Defrosting can take over 10 minutes (depending on the size of the system) and occurs most frequently between -7 and +7°C when there is most humidity in the air, which freezes to the coil, and this has a significant impact on the perceived indoor comfort levels.
new
VRV IV VRF benchmark
The VRV IV has changed the heating pardigm by providing heat even during defrost operation thus eliminating the temperature drop inside and providing comfort at all times.
How does it work? Heat accumulating element A unique heat-accumulating element, based upon phase change materials, provides the energy to defrost the outdoor unit. The energy needed for defrosting is stored in the element during normal heating operation.
The outdoor unit coil is defrosted … … with the energy stored in the heat accumulating element … … while indoors a comfortable temperature is maintained.
Alternate defrost On all our multi model combinations only 1 outdoor coil is defrosted at a time, ensuring continuous comfort during the whole process.
the outdoor unit coil is defrosted … … one at the time …
… so indoors a comfortable temperature is maintained
26
ΔT
Time
3. VRV configurator software • Graphical interface • Manage systems over multiple sites in exactly the same way • Retrieve initial settings
Simplified commissioning The VRV configurator is an advanced software solution that allows for easy system configuration and commissioning: • less time is required on the roof configuring the outdoor unit • multiple systems at different sites can be managed in exactly the same way, thus offering simplified commissioning forkey accounts • initial settings on the outdoor unit can be easily retrieved.
User friendly interface instead of push buttons
Simplified commissioning
Retrieve initial system settings
Simplified servicing Outdoor unit display for quick on-site settings and easy read out of errors together with the indication of service parameters for checking basic functions. • easy-to-read error report • clear menu indicating quick and easy on-site settings • indication of basic service parameters to quickly check basic functions: high pressure, low pressure, frequency ans operation time history of compressors, temperature of discharge/suction pipe.
3 digit 7-segment display
27
VRV IV TECHNOLOGIES
Software for simplified commissioning, configuration and customisation
VRV IV
technologies
4
3 2
1
1
Newly developed compressor
Full inverter • Enabling Variable Refrigerant Temperature and low start-up currents • Stepless capacity control Reluctance brushless DC motor • increased efficiency compared to AC motors by simultaneous using normal and reluctance torque • Powerful neodymium magnets efficiently generate high torque • High pressure oil reduces thrust losses High efficinency J-type 6-pole motor • 50% stronger magnetic force & higher rotation efficiency Newly developed compressor material • Compression volume is increased with 50% thanks to a new high strenght material casted in a semi molted state (thixocasting process)
2
new new compressor material 6 pole motor DC motor
new
4-side heat exchanger
Up to 50% more heat exchange surface (up to 235m2) leading to 30% better efficiency
28
• •
4
new
Gas cooled PCB Reliable cooling as it is not influenced by ambient air temperature Smaller switchbox for smoother air flow through the heat exchanger
VRV IV TECHNOLOGIES
3
DC Fan Motor
Outer rotor DC motor for higher efficiency • Bigger diameter of the rotor results in greater force for the same magnetic field • Better control resulting in more fan steps to match the actual capacity
100
Daikin outer rotor
80
rotor
F
Efficiency (%)
Conventional motor with inner rotor
DC motor efficiency (comparison with a conventional AC motor)
rotor
60 40
AC motor
20
F
0 200 300 400 500 600 700 800 900 1000 Motor speed (rpm)
Sine Wave DC Inverter Optimizing the sine wave curve, results in smoother motor rotation and improved motor efficiency.
DC Fan Motor The use of a DC fan motor offers substantial improvements in operating efficiency compared to conventional AC motors, especially during low speed rotation.
5
E-Pass Heat Exchanger
Optimization of the path layout of the heat exchanger prevents heat transferring from the overheated gas section towards the sub cooled liquid section - a more efficient use of the heat exchanger.
OUT 45°
OUT 45°
IN 85°C
IN 85°C
55°C
27°C
27°C
43°C
27°C
55°C
27°C
60°C
27°C
50°C
27°C
55°C OUT 45°
OUT 45°
I-Demand Function
Power
The newly introduced current sensor minimizes the difference between the actual power consumption and the predefined power consumption.
consumption (KVV)
6
e-Pass heat exchanger
Standard heat exchanger
8:00
12:00 Time
29
16:00 20:00
Benefits for
building owners Drastically reducing your running costs A long lasting investment Precise zone control VRV systems have low running costs because it permits each zone to be controlled individually. That is, only those rooms that require air conditioning will be heated or cooled, while the system can be shut down completely in rooms where no air conditioning is required.
ON
OFF
ON OFF
All inverter compressors
ALL
All inverter control compressors allow to control the refrigerant volume almost stepless. In this way the capacity perfectly matches the different loads in every room avoiding unnecessary energy use. Additionally all inverter compressors also allow precise refrigerant temperature control, automatically adapting your VRV to your building and climate requirements, reducing runnig costs with 28%.
Smart energy management Smart energy management tools reduce running costs by preventing energy wastage. Using the schedule function and monitoring tools you can easily detect origins of energy waste and track consumption to ensure it is according to plan. Our intelligent tools maximize efficiency at all times.
Indication of where energy saving is possible
30
ON
BENEFITS
Intelligent indoor units The round flow cassette, Daikin’s technology flagship indoor unit, shows that intelligent indoor units lead to great savings in runnings and pays itself back in no time!
Auto-cleaning panel The auto-cleaning filter automatically cleans itself once a day preventing the filter gets dirty, leading up to 50% savings. Dust can be simply removed from the unit with a vaccuum cleaner. Test of auto cleaning panel versus normal panel
50% lower
Energy consumption (kWh) 9000 8000 7000 6000 5000 4000 3000 2000 1000 0
energy consumption ly Ju
ne
ay M
Ju
M
ru
ar
Ap
r il
ch
y ar
ar
Fe b
De
Ja
ce
y
r
nu
m
be
be
r
r m ve No
Oc
to
be
r be em
Se
pt
Au
gu
Ju
ly
st
(Test site, Wolverhampton, UK)
Auto cleaning cassette Standard round flow cassette with regular servicing
Presence sensor The presence sensor adjusts the set point or switches off the unit if no persons are in the room, preventing up to 27% of unnecessary energy use. At the same time it can detect people and direct the airflow away from them for added comfort.
Presence sensor saves up to 27%
Nobody in the room
Inside temp. (°CDB) 26°
24°
Energy saved
22°
Cooling set point : 22° CDB
no presence detected for 15mins
0 .0
0 .3
31
17
16
0 .0
16
0
0
.3
.0
15
0 .3
15
14
0 .0
14
0
0
.3 13
.0 13
0 .3
12
0
0
.0 12
.3
0 .0
11
11
0
0
.3 10
.0
0 .3
10
09
09
.00
20°
Anti Corosion Treatment Special anti corrosion treatment of the heat exchanger provides 5 to 6 times greater resistance against acid rain and salt corrosion. The provision of rust proof steel sheet on the underside of the unit gives additional protection.
Up to 6 times greater resistance against corrosion Performed tests: VDA Wechseltest Contents of 1 cycle (7 days): ›› 24 hours salt spray test SS DIN 50021 ›› 96 hours humidity cycle test KFW DIN 50017 ›› 48 hours room temperature & room humidity testing period: 5 cycles
An anti-corrosion heat exchanger cutaway view Hydrophilic film Aluminium Heat exchanger
Corrosion-resistant Acrylic resin
Degree of corrosion 8 7 6 5 4 3 2 1 0
Bare aluminium 1 2 3 4 5
DAIKIN P.E.
Cycle Degree of corrosion
Kesternich test (SO2) ›› contents of 1 cycle (48 hours) according to DIN50018 (0.21) ›› testing period : 40 cycles
10 9 8 7 6 5 4 3 2 1 0 1 2 3 4 5 6 10 20 30 40 50 60 70 Cycle
Duty Cycling extends operation life The cyclical start-up sequence of multiple outdoor units systems equalises compressor duty and extends operating life.
Sequential Start Up to 3 outdoor units can be connected to 1 power supply and can be turned on sequentially. This allows the number of breakers and their capacities to remain small and simplifies wiring (for models of 10HP or less).
Only one power supply 32
BENEFITS
Our references
Edificio contenedor de institutos R & D building
15 x VRV IV heat pump with continuous heating outdoor units (RYYQ-T (254hp) 123 x VRV indoor units (54 x FXSQ-P; 28 x FXHQ-MA 25 x FXZQ-A; 8 x FXAQ-P; 8 x FXLQ-P) ventilation: 5 x ERQ-A; 5 x EKEQFCB+EV control: via Intelligent Touch Manager
“Both from a technical and efficiency point of view, we could offer the best solution, but, most important, the complex solution was made look easy for the customer as he only had one point of contact for both the HVAC systems and controls. A service only Daikin could offer.”
“Kaffee Partner chose Daikin VRV for its efficiency, low investment and small footprint.”
Kaffee Partner administration building and storage 7 x VRV heat pump outdoor units: (2 x RXYQ12P9; 2 x RXYQ14P9; 1 x RXYQ16P9; 1 x RXYQ22P; 1 x RXYQ8P9); 3 x ERQ250AW1; 114 x VRV indoor units: (2 x FXSQ20P; 13 x FXSQ40P; 5 x FXZQ15M9; 21 x FXZQ20M9; 26 x FXZQ25M9; 4 x FXZQ32M9; 9 x FXZQ40M9; 4 x FXZQ50M9)
33
Benefits for
end users Comfort guaranteed at all times
Smart Control Brings Comfort Stable room temperature An electronic expansion valve, using PID (Proportional Integral Differencial) control, continuously adjusts the refrigerant volume in respond to load variations of the indoor units. The VRV system thus maintains comfortable room temperatures at a virtually constant level, without the temperature variations typical of conventional ON/OFF control systems.
VRV SERIES (DAIKIN indoor unit (PID controlled))
Cooling
Suction air temp.
ON/OFF controlled indoor unit (2.5HP)
Stable room temperature
Time Note: The graph shows the data, measured in a test room assuming actual heating load. The thermostat can control stable room temperature at ± 0.5°C from set point.
No more cold draught Automatic or manual adjustment of refrigerant temperature leads to higher outblow temperatures which avoid the cold draught coming from the indoor unit.
16°
Constant and high air discharge temperature
34
Back -up Function In the event of a compressor malfunction another compressor or outdoor unit will take over in order to maintain 8 hour interim capacity, allowing time for maintenance or repair while comfort remains guaranteed.
BENEFITS
Single outdoor unit with multiple compressors
Multi outdoor unit system
Low indoor unit operation sound level Daikin indoor units have very low sound operation levels, down to 19dB(A), making them ideal for sound sensitive area’s as hotel bedrooms, etc‌
db(A)
Perceived loudness
Sound
0
Treshold of hearing
-
20
Extremely soft
Rustling leaves
40
Very soft
Quiet room
60
Moderately loud
Normal conversation
80
Very loud
City traffic noise
100
Extremely loud
Symphonic orchestra
120
Threshold of feeling
Jet taking off
19dB(A)
Daikin indoor units
25.5dB(A) FXZQ-A
emura
Connectable to VRV IV and VRV III-S heat pump
Connectable to all VRV heat pumps
35
Benefits for
design offices and consultants Maximum flexibility Meeting and exceeding legal requirements Wide operation range The VRV system can be installed practically anywhere. VRV outdoor units operate in cooling mode between -20°C and +46°C outdoor ambient and between -25°C and +15.5°C in heating mode.
-20C°
46°C
-25C°
Cooling mode
Heating mode
Contact your local dealer for more information and restrictions
VRV IV example Total piping length Longest length actual (Equivalent)
1000m 165m (190m)
Longest length after first branch
90m1
Level difference between indoor and outdoor units
90m1
Level difference between indoor units
30m
1 Contact your local dealer for more information and restrictions 2 In case outdoor unit is located below indoor units
36
90m piping length after first branch
1
165m Actual piping length
The long piping lengths, high level differences and small refrigerant piping allows for a design with little limitations and leaving maximum space for lettable space.
30m Level difference between indoor units
Flexible piping design
40m (90m1) Level difference between indoor and outdoor units
With the technical cooling function, the operation range in cooling of the heat recovery system is extended from -5°C to -20°C 1, making it perfect for integrating server rooms.
15.5°C
Night quiet mode For areas where there are stringent limitations to sound levels the outdoor unit sound level can be reduced, to meet the requirement.
Peak in the outdoor temperature
100%
8 hrs
10 hrs
50%
Capacity* % Load % Operation Sound dBA
Step 1: max. - 8dB (10HP)
Step 1: 50dB
Step 2: max. - 13dB (10HP)
Step 2: 45dB
50dBA 45 dBA
Night mode STARTS
Night mode ENDS
Example for VRV IV heat pump, factory setting.
Indoor installation The VRV optimised fan blade shape increases output and reduces pressure loss. Together with the high ESP setting (up to 78pa), it makes VRV outdoor units ideal for indoor installation using ducts.
ESP up to
78pa
Indoor installation leads to less piping length, lower installation costs, increased efficiency and better visual aesthetics.
Multiple tenants, one outdoor unit The multi tenant function ensures that the entire VRV system does not shut down when the main power supply of an indoor is switched off. This means that the indoor unit’s main fuse can be turned off when a part of the building is closed, is being serviced, …
operation in holiday in service operation
No structural reinforcement necessary Thanks to the vibration-free and sufficient light construction of the outdoor units, floors do not need to be reinforced, reducing the overall cost of the building when compared to a chiller.
max. 398kg for a 20HP unit
37
BENEFITS
Night mode
58 dBA
Benefits for
installers Fast installation and commissiong Easy servicing Compact design The compact design of the outdoor units is sufficient to allow them to be taken up to the top of a building in a commercial elevator, overcoming site transportation problem, particularly when outdoor units need to be installed on each floor.
Phased installation Installation of the VRV system can be implemented floor by floor, so that sections of the building can be put into use very quickly, or enabling the air conditioning system to be commissioned and operated in stages, rather than on final completion of the project.
Installation floor by floor
Under construction
X X VRV system
Top quality - Only brazed connections All flange and flare connections inside the unit have been replaced by brazing connections to ensure improved refrigerant containment. Also the connection of the outdoor in the main pipe is brazed.
Flare or flange
Brazing 38
Automatic charging & testing Efficient use of time Manual
1
2
3
4
Calculate extra refrigerant volume
Connect first bottle on VRV & start filling process
Check on regular times weight scale to check weight of refrigerant
Stop manually the VRV filling procedure & close valves
1
2
Connect bottle to VRV & active automatic charging function
BENEFITS
Automatic
Push button on the PCB
Filling procedure stops automatically: close valves
After charging pushing the test operation button initiates a check on the wiring, shut off valves, sensors and refrigerant volume. If the temperature drops below 20°C* manual charging is necessary. * 10°C for heat pump for cold regions * Not available for VRV Classic and VRV IV W-series
Did you know … Optimal charge = optimal efficiency Planned installation 64 m refrigerant piping
›
10% undercharged
calculation: 2.2kg extra refrigerant required
up to 25% capacity loss
0.5 kg Real installation 76 m refrigerant piping
›
33% more energy use
2.7kg extra refrigerant required in reality
Daikin Unified REFNET piping The unified Daikin REFNET piping system is especially designed for simple installation. Compared to regular T-joints, where refrigerant distribution is far from optimal, the Daikin REFNET joints have specifically been designed to optimise refrigerant flow. Daikin Europe N.V. advises only to use Daikin REFNET piping system.
REFNET joint
REFNET joint
Attached insulators for REFNET joint
T-joint 39
REFNET header
Attached insulators for REFNET header
Easy compliance to F-gas regulation Automatic refrigerant containment check Perform the refrigerant containment check remotely via Intelligent Touch Manager, when it is most convenient for you, preventing an on-site visit. At the same time increase your customer satisfaction because there is no disruption to the air conditioning during business hours. Next to remote checking, the refrigerant containment check function can also be activated on-site via a push button on the PCB.
Remotely set the time and start the refrigerant containment check
Connect to customer site via internet or 3G after working hours
Check the report once the check has been done
When activating the refrigerant containment check, the unit switches into cooling mode and duplicates certain reference conditions based on memory data. The result indicates whether or not refrigerant leakage has occurred. The refrigerant volume of the complete system is calculated for the following data: ›› Outdoor temperature ›› Reference system temperatures ›› Reference pressure temperatures ›› Refrigerant density ›› Types and number of indoor units Not available on VRVIII-S or in combination when one or more RA indoor units, hydroboxes, … are connected
Refrigerant Recovery Function When an indoor unit or outdoor needs to be replaced in case of malfunction the refrigerant can be easily drained from the system, making servicing easier.
40
Easy wiring - “Super Wiring” System Simplified wiring ›› ›› ››
Shared use of wiring between indoor units, outdoor units and centralised remote control Easy retrofit of centralised remote control Impossible to make incorrect connections thanks to non polarity wiring
Cross wiring check The cross wiring check facility warns operatives of connection errors in inter unit wiring and piping.
Auto Address Setting Function BENEFITS
Allows wiring between indoor and outdoor units, as well as group control wiring of multiple indoor units, to be performed without the bothersome task of manually setting each address.
Cinemeerse Large cinema
12 x VRV heat recovery 8HP outdoor units air handling units with VAV (70,000m³/h) connected to CO2 sensors
Installer: “I dare to assert that in a record time (construction took only four months) we have built the most energy efficient cinema in The Netherlands, and even in Europe.”
41
VRV
Outdoor systems
Variable Refrigerant Temperature Continuous heating (heat accumulating element) Continuous heating ( alternate defrost) VRV configurator 7 segment indicator Automatic refrigerant charge Refrigerant containment check Night quiet mode Manual low noise function Connectable to stylish indoor units (Daikin Emura, Nexura) Connectable to LT hydrobox for hot water Connectable to HT hydrobox for hot water Full inverter compressors Gas cooled PCB 4 side heat exchanger Reluctance brushless DC compressor Sine wave DC inverter DC fan motor E-pass heat exchanger I demand function Manual demand function 42
VRV IV Heat recovery
VRV IV heat pump with continous heating
VRV IV heat pump without continous heating
VRV III-S
p 44
p 50
p 50
VRV IV HEAT RECOVERY
Overview of functions VRV III-C
VRV Classic
Replacement VRV IV heat pump
Replacement VRV III Heat recovery
Water cooled VRV IV
p 56
p 60
p 64
p 66
p 66
p 72
-
-
-
-
-
-
-
43
22
Air curtain Biddle Air curtain for VRV (CYV)
Indoor units VRV type indoor units Hot water Low temperature hydrobox High temperature hydrobox
Control systems
VRV IV heat recovery
Ventilation Heat Reclaim ventilation (VAM/VKM) Fresh air indoor units (FXMQ-MF) AHU connection kit
VRV IV standards:
99 7 segment indicator
99Variable refrigerant temperature
99 Refrigerant containment check
Customize your VRV for best seasonal efficiency & comfort
99 Full inverter compressors
The new standard in heating comfort
99 Gas cooled PCB
99VRV configurator
99 Night quiet mode 99 Manual low noise function
99Continuous heating
99 Automatic refrigerant charge
99 4 side heat exchanger
Software for simplified commissioning, configuration and customisation
99 Reluctance brushless DC compressor 99 Sine wave DC inverter 99 DC fan motor 99 E-pass heat exchanger 99 I demand function 99 Manual demand function
For detailed explanation of these functions refer to VRV IV technologies tab
44
More free heat Power input Daikin
Daikin 3-pipe technology needs less energy to recover heat, meaning significant better efficiency during heat recovery mode. Our system can recover the heat at low condensing temperature because it has dedicated gas, liquid and discharge pipes.
Condensing 55°C Condensing 45°C Pressure
Power input 2-pipe system
In a 2-pipe system gas and liquid travel as a mixture so the condensing temperature needs to be higher in order to separate the mixed gas and liquid refrigerant. The higher condensing temperature means more energy is used to recover heat resulting in lower efficiency.
Free heat and hot water production Until now most commercial buildings have individual systems for cooling, heating, hot water etc. leading to big energy waste. An integrated heat recovery system reuses heat from offices, server rooms etc. to warm other areas or create hot water.
22
Extracted heat delivers
22
free hot water and heating
Cooling
Did you know … that re-using energy by heat recovery can lead to savings up to 10, meaning for 1 unit of electricity? This means huge savings in running costs and CO2 emissions.
Hot Water
COP
Heating
Ideal situation when heating and cooling
10 8 7 6 5
4 3 2 1 0 20 40 100 50% heating 60 80 Only cooling Only heating 50% cooling
Improved efficiency In heat recovery operation the VRV IV is up to 15% more efficient. In full load operation the seasonal efficiency is efficient even up to 28% better compared to VRV III thanks to Variable Refrigerant Temperature.
Load
Improved mix mode refrigerant control
Up to 15% more efficient T amb
45
VRV IV HEAT RECOVERY
Enthalpy
N
Maximum comfort A VRV heat recovery system allows simultaneous cooling and heating. ›› For hotel owners it means a perfect environment for guests as they can freely choose between cooling or heating. ›› For offices it means a perfect working climate both for tenants facing south and north.
S
More efficient due to lower pressure drop 110%
Smooth refrigerant flow in 3-pipe system thanks to 2 smaller gas pipes leading to higher energy efficiency
105% 100%
3-pipe
95% 90%
2-pip
R
e sys
85% 80%
VRV H/
0
Disturbed refrigerant flow in large gas pipe on 2-pipe system leading to bigger pressure drop
tem
50
100
m
Free combination of outdoor units Freely combine outdoor units to optimise for small footprint, continuous heating, highest efficiency or any other combination.
Flexible piping design 90m1
Level difference between indoor and outdoor units
90m1
Level difference between indoor units
30m
1
1 Contact your local dealer for more information and restrictions 2 In case outdoor unit is located below indoor units
46
90m maximum
Longest length after first branch
30m Level difference between indoor units
165m (190m)
40m (90m ) Level difference between indoor and outdoor units
Longest length actual (Equivalent)
1000m
165m Actual piping length
Total piping length
Fully redesigned BS boxes Maximum design flexibility and installation speed • Unique range of single and multi BS boxes for flexible and fast design • Major reduction in installation time thanks to wide range, compact size and light weight multi BS boxes Multi port: 4 – 6 – 8 – 10 – 12 – 16
BS1Q10,16,25A
• • • • •
Compact & light to install Ideal for remote rooms as no drain piping needed Allows integration of server rooms thanks to technical cooling function Connect up to 250 class unit (28kW) Allows multi tenant applications
BS4Q14A
• • • • • • •
BS6,8Q14A
BS10,12Q14A
BS16Q14A
Up to 70% smaller and 66% lighter than previous range Faster installation thanks to a reduced number of brazing points and wiring All indoor units connectable to one BS box Less inspection ports needed compared to installing single BS boxes Up to 16 kW capacity available per port Connect up to 250 class unit (28kW) by combining 2 ports No limit on unused ports allowing phased installation
Maximum comfort at all times Thanks to the VRV BS box, all indoor units which are not switching from cooling to heating or vica versa continue to provide heating or cooling. This is because our heat recovery system does not need to equalize pressure over the entire system after a change-over.
Faster installation thanks to open connection
Time saving! No need to cut the pipe before brazing (for indoor units smaller or equal to 5.6 kW (50 class))
Cut and braze the pipe (for indoor units bigger or equal to 7.1 kW (63 class))
47
VRV IV HEAT RECOVERY
Single port
Specifications VRV IV heat recovery - REYQ-T REYQ-T System
Capacity range Continuous heating Cooling capacity Nom Heating capacity Nom Heating capacity Max. Nom. Power input - 50Hz Cooling Nom. Heating EER ESEER COP Maximum number of connectable indoor units Indoor index Min connection Nom Max Dimensions Unit hxwxd Weight Unit Fan Air flow rate Cooling Nom Sound power level Cooling Nom Sound pressure level Cooling Nom Operation range Cooling Min~max Heating Min~max Space cooling Min~max Water production Space heating Min~max Domestic hot water Min~max Refrigerant Type Piping connection liquid OD gas OD discharge gas OD total piping length system Power supply Phase/Frequency/Voltage Current - 50Hz Maximum fuse amps (MFA) REYQ-T System
HP kW kW kW kW kW
mm kg m3/min dBA dBA °CDB °CWB °CDB °CWB °CWB
mm mm mm m Hz/V A
Outdoor unit module 1 Outdoor unit module 2 Outdoor unit module 3
Capacity range Continuous heating Cooling capacity Nom Heating capacity Nom Heating capacity Max. Nom. Power input - 50Hz Cooling Nom. Heating EER ESEER COP Maximum number of connectable indoor units Indoor index Min connection Nom Max Piping connection liquid OD gas OD discharge gas OD total piping lenght system Current - 50Hz Maximum fuse amps (MFA) OUTDOOR UNIT MODULE Dimensions Unit hxwxd Weight Unit Fan Air flow rate Sound power level Cooling Nom Sound pressure level Cooling Nom Operation range Cooling Min~max Heating Min~max Water production Space cooling Space heating Domestic hot water Refrigerant Power supply Current - 50Hz
8 REYQ8T
Outdoor unit module 1 Outdoor unit module 2
Type Phase/Frequency/Voltage Maxiimum fuse amps (MFA)
HP kW kW kW kW kW
mm mm mm m A
10 12 13 14 16 18 20 REYQ10T REMQ5T REYQ12T REYQ8T REYQ14T REYQ16T REYQ8T REYQ18T REYQ8T REYQ20T REYQ8T REMQ5T REMQ5T REYQ8T REYQ10T REYQ12T 8 10 10 12 13 14 16 16 18 18 20 20 v v v v v 22.4 28.0 28.0 33.5 36.4 40.0 45.0 44.8 50.0 50.4 56.0 55.9 22.4 28.0 28.0 33.5 36.4 40.0 45.0 44.8 50.0 50.4 56.0 55.9 25.0 31.5 32.0 37.5 41.0 45.0 50.0 50.0 56.0 56.5 63.0 62.5 64 (1) 100 125 125 150 162.5 175 200 200 225 225 250 250 200 250 250 300 325 350 400 400 450 450 500 500 260 325 325 390 422.5 455 520 520 585 585 650 650 1685x930x765 1685x930x765 1685x1240x765 1685x1240x765 1685x1240x765 198 205 205 319 319 329 329 162 175 185 223 260 251 261 78 79 81 81 81 81 86 81 86 82 88 83 58 58 61 61 61 61 64 61 65 61 66 63 -20(2) / -5~43 -20~15.5 8~43 -20~20 / 24 (2) -20~43
9.5 19.1 15.9
9.5 22.2 19.1
9.5 22.2 19.1
12.7 28.6 19.1
12.7 28.6 19.1
20
25
40
32
40 34 16 18
R-410A 12.7 12.7 28.6 28.6 22.2 22.2 1000 3N~ / 50 / 380-415 32 40
22 10 12
24 8 16
26 12 14
28 12 16
30 12 18
32 16 16
36 16 20
22 V 61.5 61.5 69.0 -
24 V 67.4 67.4 75.0 -
26 V 73.5 73.5 82.5 -
28 V 78.5 78.5 87.5 -
30 V 83.5 83.5 93.5 -
32 V 90 90 100 -
34 36 V V 95.0 101.0 95.0 101.0 106.0 113.0 -
275 550 715 15.9 28.6 28.6
300 600 780 15.9 34.9 28.6
325 650 845 19.1 34.9 28.6
350 700 910 19.1 34.9 28.6
375 750 975 19.1 34.9 28.6
400 800 1040 19.1 34.9 28.6
425 850 1105 19.1 34.9 28.6
450 900 1170 19.1 41.3 28.6
63
63
63
63
80
80
80
80
12.7 28.6 22.2
15.9 28.6 22.2
15.9 28.6 22.2
15.9 28.6 28.6
15.9 28.6 28.6
40
40
50
50
50
38 40 42 44 46 8 10 10 12 14 10 12 16 16 16 20 18 16 16 16 38 40 42 44 46 V V V V V 106.4 111.5 118.0 123.5 130.0 106.4 111.5 118.0 123.5 130.0 119.5 125.0 131.5 137.5 145.0 64 (1) 475 500 525 550 575 950 1000 1050 1100 1150 1235 1300 1365 1430 1495 19.1 19.1 19.1 19.1 19.1 41.3 41.3 41.3 41.3 41.3 34.9 34.9 34.9 34.9 34.9 1000 100 100 100 100 100
REMQ5T 1685x930x765 198 162 78 58 -20(2) / -5~43 -20~15.5 8~43 -20~20 / 24 (2) -20~43
mm kg m3/min dBA dBA °CDB °CWB
R-410A 3N~ / 50 / 380-415 20
Hz/V A
1 Actual number of connectable indoor units depends on the indoor unit type (VRV indoor, hydrobox, etc.) and the connection ratio restriction for the system (50%<=CR<=130%) 2 Field setting
48
48 16 16 16 48 V 135 135 150 -
50 52 16 16 16 18 18 18 50 52 V V 140.0 145.0 140.0 145.0 156.0 162.0 -
54 18 18 18 54 V 150 150 168 -
600 1200 1560 19.1 41.3 34.9
625 1250 1625 19.1 41.3 34.9
650 1300 1690 19.1 41.3 34.9
675 1350 1755 19.1 41.3 34.9
125
125
125
125
Individual branch selector for VRV IV heat recovery - BS1Q-A BS1Q10A Cooling Nom. Heating Nom. Maximum number of connectable indoor units Maximum capacity index of connectable indoor units Casing Material HeightxWidthxDepth Dimensions Unit Weight Unit Piping Outdoor unit Liquid Type/OD connections Gas Type/OD Discharge gas Type/OD Indoor unit Liquid Type/OD Gas Type/OD Sound absorbing thermal insulation Power supply Phase/Frequency/Voltage Total circuit Maximum fuse amps (MFA) Connectable outdoor units
BS1Q16A 0.005 0.005
kW kW 6 15 < x ≤ 100
BS1Q25A
8 100<x≤160 Galvanised steel plate
mm kg mm mm mm mm mm
160<x≤250 Galvanised steel
207x388x326 12
15
Brazing connection/9.5 Brazing connection/15.9 Brazing connection/12.7 Brazing connection/9.5 Brazing connection/15.9 Foamed polyurethane, frame resisting needle felt 1~/50/220-240 15 REYQ-T
Hz/V A
Brazing connection/22.2 Brazing connection/19.1 Brazing connection/22.2
Multi branch selector for VRV IV heat recovery - BS-Q14A Cooling Nom. kW Power input Heating Nom. kW Maximum number of connectable indoor units Maximum number of connectable indoor units per branch Number of branches Maximum capacity index of connectable indoor units Maximum capacity index of connectable indoor units per branch Casing Material Dimensions Unit HeightxWidthxDepth mm Weight Unit kg Liquid Type/OD mm Outdoor unit Gas Type/OD mm Piping connections Discharge gas Type/OD mm Liquid Type/OD mm Indoor unit Gas Type/OD mm Drain pipe size Power supply Phase/Frequency/Voltage Hz/V Total circuit Maximum fuse amps (MFA) A Connectable outdoor units
BS4Q14A 0.043 0.043 20
BS6Q14A 0.064 0.064 30
BS8Q14A 0.086 0.086 40
4 400 or less
6 600 or less
8
298x370x430 17 9.5 22.2 19.1
298x580x430 24 12.7 28.6 19.1
BS10Q14A 0.107 0.107 50
BS12Q14A 0.129 0.129 60
BS16Q14A 0.172 0.172 64
5
49
10 12 750 or less 140 or less Galvanised steel plate 298x580x430 298x820x430 298x820x430 26 35 38 12.7 15.9 15.9 28.6 28.6 28.6 19.1 28.6 28.6 9.5 15.9 ID 20 / OD 26 (VP20) 1~/220-240/50 15 REYQ-T
16
298x1060x430 50 19.1 34.9 28.6
VRV IV HEAT RECOVERY
Power input
Air curtain Biddle Air curtain for VRV (CYV) 22
Indoor units VRV type indoor units Residential type indoor units (such as Daikin Emura)
Hot water Low temperature hydrobox
Control systems
VRV IV heat pump VRV IV standards:
99 7 segment indicator
99Variable refrigerant temperature
Customize your VRV for best seasonal efficiency & comfort
99Continuous heating
99 Automatic refrigerant charge 99 Refrigerant containment check 99 Night quiet mode 99 Manual low noise function 99 Full inverter compressors
The new standard in heating comfort
99 Gas cooled PCB
99VRV configurator
Ventilation Heat Reclaim ventilation (VAM/VKM) Fresh air indoor units (FXMQ-MF) AHU connection kit
99 4 side heat exchanger
Software for simplified commissioning, configuration and customisation
99 Reluctance brushless DC compressor 99 Sine wave DC inverter 99 DC fan motor 99 E-pass heat exchanger 99 I demand function 99 Manual demand function
For detailed explanation of these functions refer to VRV IV technologies tab
50
VRV IV HEAT PUMP
Wide range of indoor units Combine VRV indoor units with stylish indoor units (Daikin Emura, Nexura, …)
FXSQ-P VRV indoor unit
FXFQ-A VRV indoor unit
FVXG-K Nexura BPMKS967B2
FTXG-LW Daikin Emura
Connectable indoor units 15 CLASS
20 CLASS
25 CLASS
35 CLASS
FTXG20LW FTXG20LS
FTXG25LW FTXG25LS
FTXG35LW FTXG35LS
FTXS20K
FTXS25K
FTXS35K CTXS35K
Nexura – Floor standing unit
FVXG25K
FVXG35K
FVXG50K
Floor standing unit
FVXS25F
FVXS35F
FVXS50F
Flexi type unit
FLXS25B
FLXS35B9
FLXS50B
Daikin Emura – Wall mounted unit Wall mounted unit
CTXS15K
BPMKS box needed to connect RA indoors to VRV IV (RYYQ-T and RXYQ-T)
51
42 CLASS
50 CLASS
60 CLASS
71 CLASS
FTXS60G
FTXS71G
FTXG50LW FTXG50LS FTXS42K
FTXS50K
FLXS60B
VRV IV proven in practice:
40% more efficient
A field trial at a German fashion chain store demonstrated how the innovative features of VRV IV have improved energy efficiency dramatically over previous models.
Results: up to 60% less energy consumed The results of the trial showed that the new VRV IV system consumed much less energy, particularly when cooling, compared with the VRV III system â&#x20AC;&#x201C; in some cases up to 60% less. When heating, savings were an average of 20%. The Unterhachingtrial demonstrates how VRV IV heat pump technology uses a renewable energy source â&#x20AC;&#x201C; air - to provide a complete and environmentally sustainable solution for heating, cooling, and ventilation in commercial environments. The trial also shows that businesses can only identify and control energy wastage through careful and intelligent monitoring of climate control systems, a service which Daikin can offer.
220
Energy use VRV III in 2012 in kWh Energy use VRV IV in 2013 in kWh Energy saving in % Trendline energy use VRV III Trendline energy use VRV IV Trendline energy saving
210 200 190 180 170 160 150 140 130 120 110
70
100
60
90
50
80 70
40
60
30
50
Average daily consumption during working hours in kWh
40
20
30
10
20
0%
10 -2
-1
0
1
2
3
4
5
6
7
8
9
10
11
12
52
13
14
15
16
17
18
19
20
21
22
23
24
25
26
Energy saving in %
VRV IV HEAT PUMP
Free combination of outdoor units Freely combine outdoor units to optimise for small footprint, continuous heating, highest efficiency or any other combination
Flexible piping design Total piping length
1000m
Longest length actual (Equivalent)
165m (190m)
Longest length after first branch
90m1
Level difference between indoor and outdoor units
90m1
Level difference between indoor units
30m
53
90m maximum
30m Level difference between indoor units
40m (90m1) Level difference between indoor and outdoor units
165m Actual piping length
1 Contact your local dealer for more information and restrictions 2 in case outdoor unit is located below indoor units
Specifications
VRV IV heat pump with continuous heating - RYYQ8-54T VRV IV heat pump without continuous heating - RXYQ8-54T OUTDOOR UNIT
Capacity range Cooling capacity Heating capacity
Nom. Nom. / Max. Cooling Nom. Power input - 50Hz Heating Nom. / Max. EER ESEER COP Nom. / Max. Maximum number of connectable indoor units Min. Indoor index Nom. connection Max. Dimensions Unit HeightxWidthxDepth Weight Unit RYYQ/RXYQ/RXYQQ Fan Air flow rate Cooling Nom. Sound power level Cooling Nom. Sound pressure level Cooling Nom. Cooling Min.~Max. Operation range Heating Min.~Max. Refrigerant Type Liquid OD Piping connections Gas OD Total piping length System Actual Power supply Phase/Frequency/Voltage Current - 50Hz Maximum fuse amps (MFA)
HP kW kW kW kW
Capacity range Cooling capacity Heating capacity
mm kg m³/min dBA dBA °CDB °CWB mm mm m Hz/V A
Outdoor unit module 1 Outdoor unit module 2 Outdoor unit module 3
Nom. Nom. / Max. Cooling Nom. Power input - 50Hz Heating Nom. / Max. EER ESEER COP Nom. / Max. Maximum number of connectable indoor units Min. Indoor index Nom. connection Max. Liquid OD Piping connections Gas OD Total piping length System Actual Current - 50Hz Maximum fuse amps (MFA)
10
12
14
16
18
20
8 22.4 22.4 / 25.0 5.21 4.75 / 5.5 4.30 6.37 (2) / 7.53 (3) 4.72 / 4.54
10 28.0 28.0 / 31.5 7.29 6.29 / 7.38 3.84 5.67 (2) / 7.20 (3) 4.45 / 4.27
12 33.5 33.5 / 37.5 8.98 7.77 / 9.1 3.73 5.50 (2) / 6.96 (3) 4.31 / 4.12
14 40.0 40.0 /45.0 11.0 9.52 / 11.2 3.64 5.31 (2) / 6.83 (3) 4.20 / 4.02 64 (1) 175 350 455
16 45.0 45.0 / 50.0 13.0 11.1 / 12.8 3.46 5.05 (2) / 6.50 (3) 4.05 / 3.91
18 50.0 50.0 / 56.0 14.7 12.4 / 14.4 3.40 4.97 (2) / 6.38 (3) 4.03 / 3.89
20 56.0 56.0 / 63.0 18.5 14.5 / 17.0 3.03 4.42 (2) / 5.67 (3) 3.86 / 3.71
100 200 260
OUTDOOR SYSTEM
System
8
125 150 250 300 325 390 1,685x930x765 268 / 194 / 194 175 185 79
261 / 187 / 187 162 78 58
200 225 400 450 520 585 1,685x1,240x765
364 / 305 / 305 223
398 / 314 / 314 260
81 61
250 500 650
251
261 88 66
86 64
65
-5~43 -20~15.5 R-410A 12.7
9.52 19.1
15.9
22.2
20
28.6 1,000 3N~ / 50 / 380-415 32
25
22
24
10 12
8 16
26
28
14
12 16
40
30
18
50
32
34
36
16
16 18
20
32 90.0 90.0 / 100.0 26.0 22.2 / 25.6 3.46 5.05 (2) / 6.50 (3) 4.05 / 3.91
34 95.0 95.0 / 106.0 27.7 23.5 / 27.2 3.43 5.01 (2) / 6.44 (3) 4.04 / 3.90
36 101.0 101.0 / 113.0 31.5 25.6 / 29.8 3.21 4.68 (2) / 6.02 (3) 3.95 / 3.79
400 800 1,040
425 850 1,105
450 900 1,170
HP kW kW kW kW
mm mm m A
22 61.5 61.5 / 69.0 16.3 14.06 / 16.5 3.77 5.58 (2) / 7.07 (3) 4.37 / 4.18
24 67.4 67.4 / 75.0 18.2 15.85 / 18.3 3.70 5.42 (2) / 6.81 (3) 4.25 / 4.10
26 73.5 73.5 / 82.5 20.0 17.29 / 20.3 3.68 5.39 (2) / 6.89 (3) 4.25 / 4.06
275 550 715
300 600 780
325 650 845
28 30 78.5 83.5 78.5 / 87.5 83.5 / 93.5 22.0 23.7 18.87 / 21.9 20.17 / 23.5 3.57 3.52 5.23 (2) / 6.69 (3) 5.17 (2) / 6.60 (3) 4.16 / 4.00 4.14 / 3.98 64 (1) 350 375 700 750 910 975
15.9
19.1
28.6
34.9 1,000 63
54
41.3 80
VRV IV HEAT PUMP OUTDOOR SYSTEM
System
38
Outdoor unit module 1 Outdoor unit module 2 Outdoor unit module 3
Capacity range Cooling capacity Heating capacity
Nom. Nom. / Max. Cooling Nom. Power input - 50Hz Heating Nom. / Max. EER ESEER COP Nom. / Max. Maximum number of connectable indoor units Min. Indoor index Nom. connection Max. Liquid OD Piping connections Gas OD Total piping length System Actual Current - 50Hz Maximum fuse amps (MFA)
HP kW kW kW kW
mm mm m A
OUTDOOR UNIT MODULE FOR RYYQ-T COMBINATIONS
Dimensions Weight Fan Sound power level Sound pressure level Operation range Refrigerant Power supply Current - 50Hz
Unit HeightxWidthxDepth Unit Air flow rate Cooling Nom. Cooling Nom. Cooling Nom. Cooling Min.~Max. Heating Min.~Max. Type Phase/Frequency/Voltage Maximum fuse amps (MFA)
40 42 44 46 48 50 52 54 8 10 10 12 14 16 16 16 18 10 12 16 18 20 18 16 18 38 40 42 44 46 48 50 52 54 106.0 112.0 118.0 124.0 130.0 135.0 140.0 145.0 150.0 106.0 / 120.0 112.0 / 125.0 118.0 / 132.0 124.0 / 138.0 130.0 / 145.0 135.0 / 150.0 140.0 / 156.0 145.0 /162.0 150.0 / 168.0 31.0 33.3 35.0 37.0 39.0 40.7 42.4 44.1 25.54 / 29.9 26.46 / 30.9 28.49 / 33.0 29.97 / 34.7 31.72 / 36.8 33.30 / 38.4 34.6 / 40.0 35.9 / 41.6 37.2 / 43.2 3.42 3.61 3.54 3.51 3.46 3.44 3.42 3.40 5.03 (2) / 6.36 (3) 5.29 (2) / 6.74 (3) 5.19 (2) / 6.65 (3) 5.17 (2) / 6.62 (3) 5.13 (2) / 6.60 (3) 5.05 (2) / 6.50 (3) 5.02 (2) / 6.46 (3) 4.99 (2) / 6.42 (3) 4.97 (2) / 6.38 (3) 4.15 / 4.01 4.23 / 4.05 4.14 / 4.00 4.14 / 3.98 4.10 / 3.94 4.05 / 3.91 4.05 / 3.90 4.04 / 3.89 4.03 / 3.89 64 (1) 475 500 525 550 575 600 625 650 675 950 1,000 1,050 1,100 1,150 1,200 1,250 1,300 1,350 1,235 1,300 1,365 1,430 1,495 1,560 1,625 1,690 1,755 19.1 41.3 1,000 100 125 RYMQ8T
mm kg m³/min dBA dBA °CDB °CWB Hz/V A
RYMQ10T 1,685x930x765 195 175 79
188 162 78 58
RYMQ12T
RYMQ14T
185
223
RYMQ16T
RYMQ18T 1,685x1,240x765
309 81 61
RYMQ20T
319 260
251 86
64
65
261 88 66
-5~43 -20~15.5
20
3N~ / 50 / 380-415 32
25
40
50
(1) Actual number of connectable indoor units depends on the indoor unit type (VRV indoor, Hydrobox, RA indoor, etc.) and the connection ratio restriction for the system (50% <= CR <= 130%) (2) The STANDARD ESEER value corresponds with normal VRV4 Heat Pump operation, not taking into account advanced energy saving operation functionality (3) The AUTOMATIC SEER value corresponds with normal VRV4 Heat Pump operation, taking into account advanced energy saving operation functionality ( variable refrigerant temperature control operation) (4) RYYQ-T multi combinations use RYMQ-T modules, RXYQ-T multi combinations use RXYQ-T modules.
55
Air curtain Biddle Air curtain for VRV (CYV) 22
Indoor units VRV type indoor units Residential type indoor units (such as Daikin Emura, ...)
Ventilation Heat Reclaim ventilation (VAM/VKM) AHU connection kit
Control systems
VRV III-S heat pump
Optimised design for small capacities
99 Automatic refrigerant charge 99 Refrigerant containment check 99 Night quiet mode 99 Manual low noise function 99 Full inverter compressors 99 Reluctance brushless DC compressor 99 Sine wave DC inverter 99 DC fan motor 99 E-pass heat exchanger 99 I demand function 99 Manual demand function
56
1,685 mm
Space saving design 1,345 mm
The VRVIII-S is slimmer and more compact, resulting in significant savings in installation space.
Volume Approx. 70% Reduction Footprint Approx. 60% Reduction
765mm
320mm 900mm
930mm
Wide range of indoor units Connect VRV units…
VRV III-S HEAT PUMP
FXFQ-A
FXZQ-A
FXSQ-P
FXAQ-P
… or stylish indoor units
FCQG-F
BPMKS967B2
FTXG-JA - Daikin Emura
FBQ-C FVXG-K Nexura
BPMKS967B2
Connectable indoor units 15 CLASS
20 CLASS
Round flow cassette Fully flat cassette Small concealed ceiling unit Slim concealed ceiling unit Concealed ceiling unit with inverter driven fan
new
FFQ25C
35 CLASS
50 CLASS
60 CLASS
FCQG35F
42 CLASS
FCQG50F
FCQG60F
FFQ35C
FFQ50C
FFQ60C
71 CLASS
FDBQ25B FDXS25F
Daikin Emura – Wall mounted unit Wall mounted unit
25 CLASS
CTXS15K
Ceiling suspended unit Nexura – Floor standing unit Floor standing unit Flexi type unit
FDXS35F
FDXS50F9
FDXS60F
FBQ35C8
FBQ50C8
FBQ60C8
FTXG50LW FTXG50LS
FTXG20LW FTXG20LS
FTXG25LW FTXG25LS
FTXG35LW FTXG35LS
FTXS20K
FTXS25K
FTXS35K CTXS35K
FTXS50K
FTXS60G
FHQ35C
FHQ50C
FHQ60C
FVXG25K
FVXG35K
FVXG50K
FVXS25F
FVXS35F
FVXS50F
FLXS25B
FLXS35B9
FLXS50B
* VRV indoor units and stylish indoor units cannot be combined.
57
FTXS42K
FLXS60B
FTXS71G
High COP values A major feature of VRVIII-S is its exceptional energy efficiency. The system achieves high COPs during both cooling and heating operation by the use of refined components and functions.
Cooling
Heating
Nominal cooling capacities are based on: indoor temperature: 27°CDB, 19°CWB, outdoor temperature: 35°C, equivalent refrigerant piping: 5m, level difference: 0m. 2 Nominal heating capacities are based on: indoor temperature: 20°CDB, outdoor temperature: 7°CDB, 6°CWB, equivalent refrigerant piping: 5m, level difference: 0m 1
3.99 1
4.55 2
0 1 2 3 4 5
-
Minimum piping length between BP and indoor unit
-
2m
Maximum piping length between BP and indoor unit
-
15m
40m
40m
Level difference between indoor and outdoor units Level difference between indoor units
5m
50m (40m1)
30m
15m
15m
Outdoor unit in lowest position
58
40m maximum
250m
Minimum length between outdoor unit and first branch
Longest length after first branch
1
300m 150m (175m)
15m Level difference between indoor units
Longest length actual (Equivalent)
Stylish indoors connected
150m Actual piping length
Total piping length
VRV indoors connected
50m Level difference between indoor and outdoor units
Flexible piping design
Advanced technologies
1 Super aero grille The spiral shaped ribs are aligned with the direction of discharge flow in order to minimise turbulence and reduce noise.
2 Smooth air inlet bell mouth
Aero spiral fan blade tips
and aero spiral fan
These features assist in significantly reducing noise. Guides are added to the bell mouth intake to reduce turbulence in the air flow generated by fan suction. The aero spiral fan features fan blades with bent blade edges, further reducing turbulence. Conventional
New
Escaping edges are sucked in by the bent blade edges, reducing overall turbulence.
Current Evaporativecapacity
Prevents accumulation of liquid refrigerant in the condenser. This results in more efficient use of the condenser surface under all conditions and leads in turn to better energy efficiency. Increased evaporative capacity stems from the newly developed refrigeration circuit, the SCe-bridge circuit, which adds super cooling prior to the expansion cycle. By adopting this circuit, the COPs in both coolingand heating have been drastically improved.
Evaporative capacity can be raised by taking super cooling just before the electronic expansion valve By the SCe- bridge circuit, cooling and heating attain the improvement in COP
Evaporative-capacity has been improved by adopting the SCe-Bridge Circuit circuit.
SCe-Bridge Circuit
3
Specifications
2 1
VRVIII-S Heat pump - single phase (P8V1), three phase (P8Y1) OUTDOOR UNIT Capacity range Cooling capacity Nom. Heating capacity Nom. Power input - 50Hz Cooling Nom. Heating Nom. EER COP Maximum number of connectable indoor units Indoor index Min. connection Nom. Max. HeightxWidthxDepth Dimensions Unit Weight Unit Fan Air flow rate Cooling Nom. Sound power level Cooling Nom. Sound pressure Cooling Nom. level Heating Nom. Operation range Cooling Min.~Max. Heating Min.~Max. Refrigerant Type Piping Liquid OD connections Gas OD Total piping length System Actual Power supply Phase/Frequency/Voltage Current - 50Hz Maximum fuse amps (MFA)
HP kW kW kW kW
RXYSQ4P8V1 4 12.6 14.2 3.24 3.12 3.89 4.55 8 (1) / 8 (2) 50
RXYSQ5P8V1 5 14.0 16.0 3.51 3.86 3.99 4.15 10 (1) / 9 (2) 62.5
RXYSQ6P8V1 6 15.5 18.0 4.53 4.57 3.42 3.94 12 (1) / 9 (2) 70
130
162.5
182
RXYSQ4P8Y1 4 12.6 14.2 3.33 3.21 3.78 4.42 8 (1) / 8 (2) 50
RXYSQ5P8Y1 5 14.0 16.0 3.61 3.97 3.88 4.03 10 (1) / 9 (2) 62.5
RXYSQ6P8Y1 6 15.5 18.0 4.66 4.70 3.33 3.83 12 (1) / 9 (2) 70
130
162.5
182
66 50 52
67 51 53
69 53 55
mm kg m³/min dBA dBA dBA °CDB °CWB mm mm m Hz/V A
1,345x900x320 120 106 66 50 52
67 51 53
69 53 55 -5~46 -20~15.5 R-410A 9.52
15.9 (1) / 19.1 (2) 300 (1) / 115 (2) 300 (1) / 135 (2) 1N~/50/220-240 32.0
(1) In case VRV indoor units are connected (2) In case RA indoors are connected
59
19.1 300 (1) / 145 (2)
15.9 (1) / 19.1 (2) 300 (1) / 115 (2) 300 (1) / 135 (2) 3N~/50/380-415 16.0
19.1 300 (1) / 145 (2)
VRV III-S HEAT PUMP
3 e-Bridge circuit
Air curtain Biddle Air curtain for VRV (CYV) 22
Indoor units VRV type indoor units
Ventilation Heat Reclaim ventilation (VAM/VKM) Fresh air indoor units (FXMQ-MF) AHU connection kit
Control systems
VRV heat pump optimised for heating
VRVIII-C 99 Automatic refrigerant charge 99 Refrigerant containment check 99 Night quiet mode 99 Manual low noise function 99 Reluctance brushless DC compressor 99 Sine wave DC inverter 99 DC fan motor 99 E-pass heat exchanger 99 I demand function 99 Manual demand function
60
High COP at low ambients The use of two stage compression technology results in improved energy saving performance at low ambients, with a COP of more than 3.0 at -10°C outdoor ambient for the entire range.
COP for a 10HP unit 4.00
ump
at p
he dard
2.00
Stan
VRV III-C HEAT PUMP
COP
3.00
1.00 0.00 -25
-20
-15 -10 -5 Outdoor temp. (WB°)
0
5
10
Wide heating operation range VRVIII-C has a standard operation range down to -25 °CWB outdoor ambient in heating and can also provide cooling down to - 5 °CDB outdoor ambient.
Heating mode
VRVIII-C -25°CWB
Standard VRV -20°CWB
Cooling mode -5°C
15.5°C
43°CDB
Outdoor Temp.
Outdoor Temp.
Stable heating capacity (kW) 35 30 heating capacity
VRVIII-C has a stable heating capacity, even in low ambients, making it suitable for single source heating. The heating capacity is 130% in comparison with the standard VRV heating capacity under similar conditions
25 20
standard heat pump
15 10 5 0
61
-25
-20
-15
-10 -5 0 Outdoor temp. (°CWB) Heating capacity 10HP outdoor unit
5
10
High heat up speed Heat up time is dramatically reduced, particularly under low ambient conditions. The required time for the indoor unit heat exchanger discharge temperature to reach 40°C has been reduced by 50%. °C
Start heating operation
60 50
30
30
25
20 10
20 Standard heat pump
0
-20
-5
0
5 6 10 Elapsed time (min.)
Indoor heat exchanger temperature VRVIII-C Indoor heat exchanger temperature standard heat pump
50% reduction
-10
Indoor temperature °C
Discharge temperature (°C)
40
Indoorpositie temperatureblauwe VRVIII-C lijnen:
15
14 15
20
X +10
Indoor temperature standard heat pump * Field test data in Japan with 14 HP unit (Akita City Jan 2006)
Short defrost time The time required for defrost is reduced to 4 minutes – less than half that of the standard VRVIII system (10 minutes), leading to a more stable interior indoor temperature and considerably improved comfort levels. * Field test data in Japan with 10 HP unit (Akita City Jan 2006)
500m 165m (190m)
Longest length between outdoor unit and function unit
10m
Longest length after first branch
40m (90m1)
Level difference between indoor and outdoor units
50m (40m²)
Level difference between indoor units
30m
1 Contact your local dealer for more information and restrictions 2 In case outdoor unit is located below indoor units
62
90m maximum
Longest length actual (Equivalent)
165m Actual piping length
Total piping length
50m Level difference between indoor and outdoor units 15m Level difference between indoor units
Flexible piping design
Two stage compression
Heating capacity
Two stage compression technology enables the system to create higher pressures resulting in a higher heating capacity under low ambient conditions. The second inverter compressor (located in the function unit) is specially designed to provide higher pressures.
High
After heat is exchanged in the indoor unit, gas and liquid are separated at the gas-liquid separator. This enables the refrigerant in gas condition to be recovered and transmitted direct to the high pressure compressor.
Liquid injection Gas-liquid separator Middle
Pressure
Gas injection
Low
Input power
Evaporator capacity
Enthalpy
VRV III-C HEAT PUMP
Specifications VRV Heat pump optimised for heating RTSYQ-PA OUTDOOR SYSTEM System
Outdoor unit module 1 Outdoor unit module 2 Function unit
Capacity range Cooling capacity Heating capacity
Nom. Nom. Cooling Nom. Power input - 50Hz Heating Nom. EER COP Maximum number of connectable indoor units Min. Indoor index Nom. connection Max. Sound pressure level Cooling Max./Nom. Liquid OD Gas OD Piping connections Oil equalizing OD Total piping length System Actual Current - 50Hz Maximum fuse amps (MFA)
RTSYQ10PA RTSQ10PAY1
RTSYQ14PA RTSQ14PAY1 -
10 28.0 (1) 31.5 (2) / 28.0 (3) 7.90 (1) 7.78 (2) / 8.18 (3) 3.54 (1) 4.05 (2) / 3.42 (3) 21 125 250 325 62/60 9.52 22.2
14 40.0 (1) 45.0 (2) / 40.0 (3) 12.6 (1) 11.4 (2) / 12.8 (3) 3.17 (1) 3.95 (2) / 3.13 (3) 30 175 350 455 63/61
RTSYQ16PA RTSQ16PAY1
RTSYQ20PA RTSQ8PAY1 RTSQ12PAY1
16 45.0 (1) 50.0 (2) / 45.0 (3) 14.9 (1) 13.0 (2) / 15.0 (3) 3.02 (1) 3.85 (2) / 3.00 (3) 34 200 400 520
20 56.0 (1) 63.0 (2) / 55.9 (3) 15.4 (1) 15.4 (2) / 18.7 (3) 3.64 (1) 4.09 (2) / 2.99 (3) 43 250 500 650
BTSQ20PY1 HP kW kW kW kW
dBA mm mm mm m A
65/63 12.7
15.9 28.6
-
19.1 500
25
35
40
50
(1) Cooling: Indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB; equivalent piping length: 7.5m; level difference: 0m; function unit length: 6m; (2) Heating: Indoor temp. 20°CDB; outdoor temp. 7°CDB,6°CWB; equivalent piping length: 7.5m; level difference: 0m; function unit length: 6m; (3) Heating: Indoor temp. 20°CDB; outdoor temp. -10°CWB; equivalent piping length: 7.5m; level difference 0m; function unit length: 6m
OUTDOOR UNIT MODULE HeightxWidthxDepth Dimensions Unit Weight Unit Fan Air flow rate Cooling Nom. Sound power level Cooling Nom. Operation range Cooling Min.~Max. Heating Min.~Max. Refrigerant Type Power supply Phase/Frequency/Voltage Current - 50Hz Maximum fuse amps (MFA)
mm kg m³/min dBA °CDB °CWB Hz/V A
BTSQ20P 1,570x460x765 110 -
RTSQ8PA
RTSQ10PA 1,680x930x765
205
RTSQ12PA 257
185
200
RTSQ14PA RTSQ16PA 1,680x1,240x765 338 344 233 239
-5~43 -25~15.5 R-410A 3~/50/380-415 20
25
63
35
40
22
Indoor units VRV type indoor units
Ventilation Heat Reclaim ventilation (VAM/VKM) Fresh air indoor units (FXMQ-MF)
Control systems
VRV Classic heat pump RXYCQ-A 99 Manual low noise function 99 Reluctance brushless DC compressor 99 Sine wave DC inverter 99 DC fan motor 99 E-pass heat exchanger 99 Manual demand function
64
Benefits • • • • •
For projects with standard cooling & heating requirements Fits any building as also indoor installation is possible as a result of high external static pressure of up to 78.4 Pa. Indoor installation leads to less piping length, lower installation costs, increased efficiency and better visual aesthetics The ability to control each conditioned zone individually keeps VRV system running costs to an absolute minimum Spread your installation cost by phased installation Connectable to all standard VRV indoor units, controls and ventilation
Flexible piping design 300m
Longest length actual (Equivalent)
VRV CLASSIC
Total piping length
135m (155m) 40m (90m1)
Longest length after first branch Level difference between indoor and outdoor units
30m
Level difference between indoor units
15m
1 Contact your local dealer for more information and restrictions
Specifications VRV Classic - RXYCQ-A OUTDOOR UNIT Capacity range Cooling capacity Nom. Heating capacity Nom. Power input - 50Hz Cooling Nom. Heating Nom. EER COP Maximum number of connectable indoor units Indoor index Min. connection Nom. Max. HeightxWidthxDepth Dimensions Unit Weight Unit Fan Air flow rate Cooling Nom. Sound power level Cooling Nom. Sound pressure level Cooling Nom. Operation range Cooling Min.~Max. Heating Min.~Max. Refrigerant Type Piping Liquid OD connections Gas OD Total piping length System Actual Power supply Phase/Frequency/Voltage Current - 50Hz Maximum fuse amps (MFA)
HP kW kW kW kW
mm kg m³/min dBA dBA °CDB °CWB mm mm m Hz/V A
RXYCQ8A 8 20.0 22.4 6.60 5.80 3.03 3.86 16 100 200 240 1,680x635x765 159 95 78 58
15.9
RXYCQ10A 10 25.0 28.0 6.74 7.00 3.71 4.00 20 125 250 300 187 171 59
9.52 19.1
RXYCQ12A RXYCQ14A 12 14 30.0 35.0 33.6 37.5 8.77 11.4 8.62 9.74 3.42 3.07 3.90 3.85 24 28 150 175 300 350 360 420 1,680x930x765 240 185 196 81 61 -5.0~43.0 -20.0~15.5 R-410A
RXYCQ16A 16 40.0 44.8 12.9 11.8 3.10 3.80 32 200 400 480
64
RXYCQ18A 18 45.0 50.4 15.0 13.8 3.00 3.65 36 225 450 540 1,680x1,240x765 316 233 86 65
12.7 22.2
16
25
65
324 239 88 66
15.9 28.6
300 3N~/50/380-415
(1) Connection ratio is 50~120%. If only FXFQ20,25 units are connected, maximum connection ratio is 100%
RXYCQ20A 20 50.0 56.0 17.8 16.0 2.81 3.50 40 250 500 600
40
Air curtain Biddle Air curtain for VRV (CYV)
22
Indoor units VRV type indoor units
Ventilation Heat Reclaim ventilation (VAM/VKM) Fresh air indoor units (FXMQ-MF) AHU connection kit
VRV III
Control systems
VRV IV
Replacement VRV RQYQ-P / RXYQQ-T (Heat pump) RQCEQ-P (Heat recovery) Heat pump
Heat pump & Heat recovery
99Variable refrigerant temperature
99 99 99 99 99 99 99 99 99 99
Customize your VRV for best seasonal efficiency & comfort
99VRV configurator
Software for simplified commissioning, configuration and customisation
99 99 99 99 99 99 99 99 99 99 99 99 99
7 segment indicator Automatic refrigerant charge Night quiet mode Manual low noise function Full inverter compressors Gas cooled PCB 4 side heat exchanger Reluctance brushless DC compressor Sine wave DC inverter DC fan motor E-pass heat exchanger I demand function Manual demand function
Automatic refrigerant charge Night quiet mode Manual low noise function Full inverter compressors Reluctance brushless DC compressor Sine wave DC inverter DC fan motor E-pass heat exchanger I demand function Manual demand function
For more information on these features refer to the VRV IV technologies tab
66
The Daikin solution to R-22 phase-out Replace your R-22 / R-407C outdoor unit with R-410A technology, but keep your refrigerant piping and in some cases your indoor units1.
1. 2. 3. 4.
Replace outdoor unit Replace BS-boxes (in case of H/R) Replace indoor units (check with your local dealer if needed) The system will automatically clean the piping & charge the correct amount of R-410A refrigerant
replace
KEEP replace
* When R-22 indoors are K-series or later, it is possible to keep the indoor units.
Plan your system replacement now 2014
01/01/2015
STOP
REPLACEMENT VRV
…
From 01/01/2015 there is a ban on the use of all R-22 for service & maintenance. Daikin advises to replace your system now to prevent unplanned downtime.
Increased efficiency Upgrading an old R-22 system to a Replacement VRV system will result in increased system efficiency. Efficiency gains of more than 70% in cooling can be realized, by virtue of technological developments in current heat pump technology such as variable refrigerant temperature and the more efficient R-410A refrigerant. Increased energy efficiency equals lower energy consumption, subsequent lower energy costs and lower CO2 emissions.
81%
less consumption in cooling mode
48%
Energy use of a 10HP system in cooling
less consumption in heating mode
Energy consumption
Energy consumption
Energy use of a 10HP system in heating
R-22
R-407C
R-410A
R-22 R-407C R-410A
67
Environmental awareness R-410A not only has a zero ozone depletion potential, it is also proven to be more energy efficient than R-22.
Fast installation It is not necessary to remove the existing piping and even the indoor units can remain (depending on type of indoor unit). The outdoor unit automatically charges the refrigerant and cleans the refrigerant piping. This unique Daikin feature makes the installation time even shorter.
No restrictions on system history As a result of the combined automatic charging and refrigerant pipe cleaning function, it is possible to ensure a clean piping network, even when a compressor breakdown has previously occurred.
Limited and planned-downtime As the refrigerant piping can be maintained the installation is less intrusive and less time consuming than for a completely new system. Moreover, downtime can be carefully planned: whereas if a problem occurs when not enough reclaimed R-22 is available, a long and unplanned downtime can be the result.
Limited and phased investment cost It is possible to spread the various stages of replacement over a certain period of time because the indoor units can remain in most cases. The air conditioning replacement therefore, can be incorporated in the general refurbishment schedule of the building and the investment cost can be spread. A further reduction in installation cost can be achieved by maintaining the old refrigerant copper pipe work.
68
Increase capacity Cooling loads often increase subsequent to the initial installation of the air conditioning system. The Replacement VRV(VRVIII-Q) enables system capacity to be increased without changing the refrigerant piping (depending on system characteristics).
Example: replace a 10HP VRV with a 16HP Replacement VRV unit
10â&#x20AC;&#x2030;HP
16â&#x20AC;&#x2030;HP
1.
1. Keep main piping 2. Add indoor units
2.
Reduced pressure As R-22 VRV systems used to work on a lower pressure than R-410A systems / thus the copper refrigerant piping was also designed for these lower pressures. Therefore the Replacement VRV must operate at lower pressures than the standard VRV series. However thanks to the sub cool circuit a high efficiency level can be kept even with the lower pressures.
Pressure
A
replace*
}
3.3 MPa
}
3.8 MPa
B
~ A B
~
Decompression to 3.3MPa(s) Extra sub cool circuit
Enthalpy
R-22 existing piping can be used
high COP
69
REPLACEMENT VRV
Technologies
Specifications RQYQ140P
RXYQQ-T
Replacement VRV heat pump (RQYQ-P / RXYQQ-T) OUTDOOR UNIT Capacity range Cooling capacity Heating capacity Power input 50Hz
Nom. Nom. Cooling Heating
Nom. Nom.
EER ESEER COP Maximum number of connectable indoor units Indoor index Min. connection Nom. Max. Dimensions Unit HeightxWidthxDepth Weight Unit Fan Air flow rate Cooling Nom. Sound power level Cooling Nom. Sound pressure level Cooling Nom. Operation range Cooling Min.~Max. Heating Min.~Max. Refrigerant Type Piping Liquid OD connections Gas OD Total piping length System Actual Power supply Phase/Frequency/Voltage Current - 50Hz Maximum fuse amps (MFA) OUTDOOR UNIT System
Capacity range Cooling capacity Heating capacity Power input 50Hz
Capacity range Cooling capacity Heating capacity Power input 50Hz
RXYQQ22T RXYQQ10T RXYQQ12T
Outdoor unit module 1 Outdoor unit module 2 Outdoor unit module 3 Nom. Nom. Cooling Heating
Nom. Nom.
EER ESEER COP Maximum number of connectable indoor units Piping Liquid OD connections Gas OD Total piping length System Actual Current - 50Hz Maximum fuse amps (MFA) OUTDOOR UNIT System
RQYQ140P RXYQQ8T RXYQQ10T RXYQQ12T RXYQQ14T RXYQQ16T RXYQQ18T RXYQQ20T 5 8 10 12 14 16 18 20 14.0 22.4 28.0 33.5 40.0 45.0 50.0 56.0 16.0 25.0 31.5 37.5 45.0 50.0 56.0 63.0 3.36 5.21 7.29 8.98 11.0 13.0 14.7 18.5 3.91 5.51 7.38 9.10 11.2 12.8 14.4 17.0 4.17 4.30 3.84 3.73 3.64 3.46 3.40 3.03 6.37 (2) / 7.53 (3) 5.67 (2) / 7.20 (3) 5.50 (2) / 6.96 (3) 5.31 (2) / 6.83 (3) 5.05 (2) / 6.50 (3) 4.97 (2) / 6.38 (3) 4.42 (2) / 5.67 (3) 4.09 4.54 4.27 4.12 4.02 3.91 3.89 3.71 10 64 (1) 62.5 100 125 150 175 200 225 250 125 200 250 300 350 400 450 500 162.5 260 325 390 455 520 585 650 mm 1,680x635x765 1,685x930x765 1,685x1,240x765 kg 175 187 194 305 314 m³/min 162 175 185 223 260 251 261 dBA 78 79 81 86 88 dBA 54 58 61 64 65 66 °CDB -5~43 °CWB -20~15.5 R-410A mm 9.52 12.7 15.9 mm 15.9 19.1 22.2 28.6 m 300 Hz/V 3~/50/380-415 3N~/50/380-415 A 15 20 25 32 40 50 HP kW kW kW kW
Nom. Nom.
EER ESEER COP Maximum number of connectable indoor units Piping Liquid OD connections Gas OD Total piping length System Actual Current - 50Hz Maximum fuse amps (MFA)
RXYQQ26T RXYQQ14T
RXYQQ28T RXYQQ12T RXYQQ16T
RXYQQ30T
RXYQQ32T
RXYQQ18T
RXYQQ16T
RXYQQ34T RXYQQ16T RXYQQ18T
RXYQQ36T RXYQQ20T
HP kW kW kW kW
mm mm m A
Outdoor unit module 1 Outdoor unit module 2 Outdoor unit module 3 Nom. Nom. Cooling Heating
RXYQQ24T RXYQQ8T RXYQQ16T
HP kW kW kW kW
22 24 26 28 30 32 34 36 61.5 67.4 73.5 78.5 83.5 90.0 95.0 101.0 69.0 75.0 82.5 87.5 93.5 100.0 106.0 113.0 16.3 18.2 20.0 22.0 23.7 26.0 27.7 31.5 16.5 18.3 20.3 21.9 23.5 25.6 27.2 29.8 3.77 3.70 3.68 3.57 3.52 3.46 3.43 3.21 5.58 (2) / 7.07 (3) 5.42 (2) / 6.81 (3) 5.39 (2) / 6.89 (3) 5.23 (2) / 6.69 (3) 5.17 (2) / 6.60 (3) 5.05 (2) / 6.50 (3) 5.01 (2) / 6.44 (3) 4.68 (2) / 6.02 (3) 4.18 4.10 4.06 4.00 3.98 3.91 3.90 3.79 64 (1) 15.9 19.1 28.6 34.9 41.3 300 63 80 RXYQQ38T RXYQQ8T RXYQQ10T RXYQQ20T 38 106.0 120.0
RXYQQ40T RXYQQ10T RXYQQ12T RXYQQ18T 40 112.0 125.0 31.0
29.9 3.42 5.03 (2) / 6.36 (3) 4.01
mm mm m A
30.9 3.61 5.29 (2) / 6.74 (3) 4.05 64 (1) 19.1 41.3 300 100
RXYQQ42T RXYQQ10T RXYQQ16T RXYQQ16T 42 118.0 132.0 33.3 33.0 3.54 5.19 (2) / 6.65 (3) 4.00
(1) Actual number of connectable indoor units depends on the indoor unit type (VRV indoor, Hydrobox, RA indoor, etc.) and the connection ratio restriction for the system (50% <= CR <= 130%) (2) The STANDARD ESEER value corresponds with normal VRV4 Heat Pump operation, not taking into account advanced energy saving operation functionality (3) The AUTOMATIC SEER value corresponds with normal VRV4 Heat Pump operation, taking into account advanced energy saving operation functionality ( variable refrigerant temperature control operation)
70
RQCEQ-P
Replacement VRV heat recovery (RQCEQ-P)
OUTDOOR UNIT MODULE HeightxWidthxDepth Dimensions Unit Weight Unit Sound pressure level Cooling Nom. Operation range Cooling Min.~Max. Heating Min.~Max. Refrigerant Type Power supply Phase/Frequency/Voltage
HP kW kW kW kW
dBA mm mm mm m m m A
RQCEQ280P RQCEQ360P RQCEQ460P RQCEQ500P RQCEQ540P RQCEQ636P RQCEQ712P RQCEQ744P RQCEQ816P RQCEQ848P RQEQ140P RQEQ180P RQEQ140P RQEQ180P RQEQ212P RQEQ140P RQEQ180P RQEQ212P RQEQ140P RQEQ180P RQEQ140P RQEQ180P RQEQ212P RQEQ180P RQEQ212P RQEQ180P RQEQ212P RQEQ180P RQEQ212P RQEQ212P 10 13 16 18 20 22 24 26 28 30 28.0 36.0 45.0 50.0 54.0 63.6 71.2 74.4 81.6 84.8 32.0 40.0 52.0 56.0 60.0 67.2 78.4 80.8 87.2 89.6 7.04 10.3 12.2 13.9 15.5 21.9 21.2 23.3 27.1 29.2 8.00 10.7 13.4 14.7 16.1 17.7 20.7 21.2 23.1 23.6 3.98 3.48 3.77 3.61 3.48 2.90 3.36 3.19 3.01 2.90 4.00 3.72 3.89 3.80 3.72 3.79 3.80 3.81 3.77 3.79 21 28 34 39 43 47 52 56 60 64 57 61 62 63 64 63 64 65 66 9.52 12.7 15.9 19.1 22.2 25.4 28.6 34.9 19.1 22.2 25.4 28.6 120 300 50 (outdoor unit in highest position) 30 40 50 60 70 80 90 RQEQ140P
mm kg dBA °CDB °CWB
RQEQ180P 1,680x635x765 175
54
58 -5~43 -20~15 R-410A 3~/50/380-415
Hz/V
Le Pigonnet Hotel
Heating & Air Conditioning
RQEQ212P 179 60
Refurbishment of the existing VRV system of a luxury 5 star hotel to anticipate R-22 phase out, keeping existing pipes in order to preserve interior decoration.
8 VRVIII-Q RQYQ140P + 36 FXLQ25 + 3FVXS50+1FTXS 3MXS52+ 2 FVXS25, RXS50 + 1 FTXS50, RXS50 + 1 FVXS50, 3 MXS68 + 2 FVXS 25 + 1 FVXS50, RXS25 + FVXS25
71
REPLACEMENT VRV
OUTDOOR SYSTEM System Outdoor unit module 1 Outdoor unit module 2 Outdoor unit module 3 Outdoor unit module 4 Capacity range Cooling capacity Nom. Heating capacity Nom. Power input Cooling Nom. 50Hz Heating Nom. EER COP Maximum number of connectable indoor units Sound pressure level Cooling Nom. Piping Liquid OD connections Gas OD Discharge gas OD Piping length OU - IU Max. Total piping length System Actual Level difference OU - IU Current - 50Hz Maximum fuse amps (MFA)
Air curtain Biddle Air curtain for VRV (CYV) 22
Indoor units VRV type indoor units
Hot water Low temperature hydrobox
Control systems
Ventilation Heat Reclaim ventilation (VAM/VKM) Fresh air indoor units (FXMQ-MF) AHU connection kit
Water cooled VRV IV W-series VRV IV standards:
99 Full inverter compressors
99Variable refrigerant temperature
Customize your VRV for best seasonal efficiency & comfort
99 Reluctance brushless DC compressor 99 Sine wave DC inverter 99 Manual demand function 99 Geothermal operation
For more information on these features refer to the VRV IV technologies tab
72
Efficiency not influenced by outdoor conditions The water cooled VRV unit operates at a superior efficiency, even in the most extreme outdoor temperatures thanks to geothermal operation. Because the temperature of ground water, lakes and rivers, remains relatively constant the year round, our water-cooled system maintains its superior efficiency, even in the most extreme outdoor temperatures, when the efficiency of air-cooled systems goes down.
Outside temperature
WATER COOLED VRV IV
Wind
Wide operation range Standard water cooled outdoor units have a wide operation range between 10°C & 45°C inlet water temperature, both in heating and cooling. In geothermal mode the operation range is extended even more, down to -10°C* in heating and 6°C in cooling mode. * Ethylene glycol should be added to the water when the water inlet temperature is below 5°C
-10°C
45°
-6°C
Heating
45°
Cooling
73
High energy efficiencies results from 2-stage heat recovery Stage 1: Heat recovery between indoor units in the same refrigerant circuit Heat exhausted from indoor units in cooling mode is transferred to units in areas requiring heating, maximising energy efficiency and reducing electricity costs.
Stage 2: Heat recovery between the outdoor units via the water loop - also available on heat pump units! Second stage heat recovery is achieved within the water loop between the water cooled outdoor units. stage 2
stage 2
stage 1
Heat recovery between indoor units
Heat recovery between outdoor units (Heat recovery and heat pump) Cooling tower (Closed type), boiler
All indoor units in cooling mode
Heat rejected to loop
VRV-W
Indoor units mainly cooling, partly heating
Heat rejected to loop
VRV-W
Full Heat Recovery
VRV-W
Indoor units mainly heating, partly cooling
Heat absorbed from loop
VRV-W
All indoor units in heating mode
Heat absorbed from loop * Above system configurations are for illustration purposes only. VRV-W
74
Space saving - Stacked configuration The adoption of a new water heat exchanger and optimization of the refrigerant control circuit has resulted in the industryâ&#x20AC;&#x2122;s most compact and lightweight design. The unit weight of 149kg* and height of 1,000â&#x20AC;&#x2030;mm makes installation easy. Stacked configuration is also possible, contributing further to space savings.
Ceiling height
3,200mm or higher
* for 8HP unit
Floor level 100-300mm
Stacked configuration is possible.
Variable water flow control The variable water flow control option reduces energy use by the circulation pump by reducing the water flow when possible and not using a fixed water flow all the time.
Variable water Flow Control Valve
Cooling tower (Closed type), boiler
WATER COOLED VRV IV
Inverter Pump
Standard water strainer A standard water strainer reduces installation time. The new filter also has less pressure drop at higher water flows.
40 35
Pressure drop (lkPa)
30
new filter
25 20 15 10
old filter
5 0 50
70
90
110
water flow (l/min)
75
130
150
For Gerard Schröder the choice for this system
‘As far as I’m concerned, with the VRV Heat Recovery system, Daikin has the Rolls Royce in heat pump technology. If you want to build a sustainable office building, there really is no other alternative.’
was an easy one:
Park Phi, Enschede The Netherlands
VRV-WIII geothermal system, Daikin Altherma HT, Sky Air, aircooled chiller with heat recovery, iManager, iTouch Manager, ACNSS
BREEAM excellent office building Flexible piping design Flexible water piping Water cooled VRV uses water as its heat source, so it is optimal for large buildings, including tall, multi-storey buildings, because the system can tolerate water pressure of up to 1.96 MPa. Furthermore, if the currently installed heat source’s water temperature is between 10°C and 45°C, it may be possible to use the existing water pipe work and heat source. This alone makes it an ideal system solution for building refubishment projects.
Actual piping length between the VRV-W and indoor units: 120m (Equivalent piping length: 140m)
Water piping Refrigerant piping
Level difference between indoor units: 15m VRV-W
Level difference between the VRV-W and indoor units: 50m if the VRV-W is above 40m if the VRV-W is below
Total piping length VRV-W
Longest length actual (Equivalent)
300m 120m (140m)
Longest length after first branch
40m (90m1)
Level difference between indoor and outdoor units
50m (40m²)
Level difference between indoor units
Indoor installation
1 Contact your local dealer for more information and restrictions 2 In case outdoor unit is located below indoor units
Unlimited water piping length
76
15m
Specifications
Heat recovery Heating & Cooling Capacity EER PI Heating capacity Capacity EER PI Power input - 50Hz Cooling Nom. Heating Nom. EER COP Maximum number of connectable indoor units Indoor index Min. connection Nom. Max. HeightxWidthxDepth Dimensions Unit Weight Unit Sound power level Cooling Nom. Sound pressure level Cooling Nom. Operation range Inlet water Cooling Min.~Max. temperature Heating Min.~Max. Refrigerant Type Piping Liquid OD connections Gas OD Discharge gas OD Water Inlet/Outlet Piping length OU - IU Max. Total piping length System Actual Level difference OU - IU Power supply Phase/Frequency/Voltage Current - 50Hz Maximum fuse amps (MFA)
Geothermal operation
RWEYQ8T 8 22.4 5.07 4.42 25.0 5.94 4.21 4.42 4.21 5.07 5.94
HP kW kW kW kW kW kW
RWEYQ10T 10 28.0 4.56 6.14 31.5 5.25 6.00 6.14 6.00 4.56 5.25 36
100 200 260 mm kg dBA dBA 째CDB 째CWB
125 250 325 1,000x780x550
137
137 -
50
51 10~45 10~45 R-410A 9.52
mm mm mm
19.1 (1) 22.2 (1) 15.9 (2) / 19.1 (3) 19.1 (2) / 22.2 (3) PT1 1/4B internal thread/PT1 1/4B internal thread 120 300 50 (outdoor unit in highest position) / 40 (indoor unit in highest position) 3N~/50/380-415 20
m m m Hz/V A
WATER COOLED VRV IV
OUTDOOR UNIT Capacity range Cooling capacity
Standard operation
(1) In case of heat pump system, gas pipe is not used (2) In case of heat recovery system (3) In case of heat pump system
OUTDOOR SYSTEM System Outdoor unit module 1 Outdoor unit module 2 Outdoor unit module 3 Capacity range Cooling capacity Capacity EER PI Heating capacity Capacity EER PI Power input - 50Hz Cooling Nom. Heating Nom. EER COP Maximum number of connectable indoor units Sound pressure level Cooling Nom. Piping Liquid OD connections Gas OD Discharge gas OD Piping length OU - IU Max. Total piping length System Actual Level difference OU - IU Current - 50Hz Maximum fuse amps (MFA)
RWEYQ16T RWEYQ18T RWEYQ20T RWEYQ8T RWEYQ10T RWEYQ8T RWEYQ10T HP kW kW kW kW kW kW
dBA mm mm mm m m m A
16 44.8 5.07 8.8 50.0 5.94 8.4 9.10 8.48 4.92 5.87
18 50.4 4.77 10.6 56.5 5.53 10.2 10.6 10.3 4.63 5.48
53 12.7
20 56.0 4.56 12.3 63.0 5.25 12.0 12.1 12.1 4.41 5.21 54 15.9
RWEYQ24T RWEYQ26T RWEYQ8T RWEYQ8T RWEYQ8T 24 26 672 72.8 5.07 4.86 13.3 15.0 75.0 81.5 5.94 5.65 12.6 14.4 13.7 15.1 12.7 14.5 4.91 4.74 5.91 5.62 36 55
RWEYQ28T RWEYQ30T RWEYQ10T RWEYQ10T RWEYQ10T 28 30 78.4 84.0 4.69 4.56 16.7 18.4 88.0 94.5 5.43 5.25 16.2 18.0 16.6 18.1 16.3 18.2 4.57 4.43 5.40 5.19 56 19.1
28.6 (1) 34.9 (1) 22.2 (2) / 28.6 (3) 22.2 (2) / 28.6 (3) 22.2 (2) / 28.6 (3) 28.6 (2) / 34.9 (3) 28.6 (2) / 34.9 (3) 28.6 (2) / 34.9 (3) 28.6 (2) / 34.9 (3) 120 300 50 (outdoor unit in highest position) / 40 (indoor unit in highest position) 32 50
(1) In case of heat pump system, gas pipe is not used (2) In case of heat recovery system (3) In case of heat pump system
77
Indoor units
As many as 64 separate indoor units can be operated from the single refrigerant circuit of a 54 HP VRV heat pump system. In fact, the Daikin VRV indoor unit range, one of the widest on the market, currently comprises no less than 26 different stylish and elegant models in 116 different variants â&#x20AC;&#x201D; all designed to maximise comfort, minimise operating noise and simplify installation and servicing. Designed to fit rooms of any size and shape, Daikin indoor units are also user friendly, quiet running, ultra reliable, easy to control and supply users with that relaxing â&#x20AC;&#x2DC;extra somethingâ&#x20AC;&#x2122; to the indoor climate.
From 01/2013 all indoor units will have to comply to the Ecodesign legislation on fans. As a market leader Daikin takes the step to be the first to comply with all indoors units to this legislation by adopting DC fans in all indoor units, improving their energy efficiency even further.
78
Ceiling suspended units
Concealed ceiling units
Floor standing units
Wall mounted units
Stylish indoor units
INDOOR UNITS
Ceiling mounted cassettes
Benefits overview 80 Ceiling mounted cassettes 82 Concealed ceiling units 88 Wall mounted units 93 Ceiling suspended units 94 Floor standing units 96 Stylish indoor units 99 Hydroboxes for VRV 108 Hydroboxes for VRV
79
Benefits overview VRV indoor units
Ceiling mounted cassette FXFQ-A
FXZQ-A
FXCQ-A
FXKQ-MA
FXDQ-M9
Inverter technology
Home leave operation
Fan only
Auto cleaning filter
Floor & presence sensor
Draught prevention
Auto cooling-heating changeover
Whisper quiet
Individual flap control
Ceiling soiling prevention
Vertical auto swing
Fan speed steps
3
3
3
2
2
Humidity control
Dry programme
Air treatment
Air filter
Weekly timer
Infrared remote control
Wired remote control
Centralised control
Auto-restart
Self-diagnosis
Multi tenant
Standard
Standard
INVERTER
We care icons Comfort Air flow Remote control & timer Other funtions
Drain pump kit
80
Standard
Standard
Concealed ceiling unit FXDQ-A
Wall mounted unit
Ceiling suspended unit
Floor standing unit
FXSQ-P
FXMQ-P7
FXMQ-MA
FXAQ-P
FXHQ-A
FXUQ-A
FXNQ-P
FXLQ-P
3
3
3
2
2
3
3
2
2
Standard
Standard
Standard
Optional
Optional
Optional
81
Standard
INDOOR UNITS
Round flow cassette
Round flow cassette: setting the standard for efficiency and comfort
The round flow cassette is designed for use in all forms and sizes of commercial offices & retail environments. Today, Daikin has improved its technology even further to enhance your comfort and provide you better energy efficient models.
presence sensor floor sensor
Even more energy efficient… With the optional infrared presence sensor the set point can be adjusted or the round flow cassette switched off when there is nobody in the room. Up to 27% energy can be saved (estimated) with this new function. If no presence is detected in the room for 15mins, the set temperature is changed until a minimum temperature (for heating) or maximum temperature (for cooling) is reached. When selecting the setback function, the unit will maintain the temperature within a preset minimum and maximum temperature, when there is no presence detected in the room for 1 hour.
Without sensor 26°
Nobody in the room
inside temperature (°CDB)
24°
22°
24°
22°
no presence detected for 15mins
0
0
.0 17
0
.3 16
0
.0 16
0
.3 15
0
.0 15
0
.3 14
0
.0 14
0
.3 13
0
.0 13
0
.3 12
0
.0 12
0
.3 11
0
.0 11
0
.3 10
.0 10
0
.3
.0 09
09
0
0
.0 17
0
.3 16
0
.0 16
0
.3 15
0
.0 15
0
.3 14
0
.0 14
0
.3 13
0
.0 13
0
.3 12
0
.0 12
0
.3 11
0
.0 11
0
.3
.0
10
10
0
0
.0
.3
09
09
time
0
20°
20° time
Nobody in the room
26°
… and improved comfort • Daikin was the first to launch an auto-cleaning decoration panel. With this panel the costs can be further reduced as the filter cleans itself automatically once a day. Up to 50% energy can be saved thanks to daily filter cleaning.
• With the optional infrared floor sensor having cold feet will become history. This sensor detects the average floor temperature and ensures even temperature distribution between ceiling and floor. • The presence sensor directs air flow away from any person detected in the room, when the air flow control is on.
Test site, Wolverhampton, UK Energy consumption (kWh)
ly Ju
ne Ju
ay M
Standard round flow cassette
Flexible installation When refurbishing or rearranging the interior of your office, shop or other area, you no longer need to change the location of your indoor unit. With the round flow cassette one flap can be easily closed via the wired remote controller (BRC1E52A/B – optional). Optional closure kits are available as well.
82
r il
ch ar
y
M
Fe b
ru
ar
y ar
r
nu
ce De
Auto cleaning cassette
Ja
m
be
be
r
r m ve No
Oc
to
be
r be
st
em pt
Se
Au
Ju
ly
• The unique 360° airflow discharge pattern ensures a uniform temperature distribution across the room without dead corners.
50%
difference in electricity consumption
(Test site, Wolverhampton, UK)
Ap
9000 8000 7000 6000 5000 4000 3000 2000 1000 0
gu
inside temperature (°CDB)
With sensor (BRC1E52A/B required)
Cooling Set point: 22° CDB
Round flow cassette
FXFQ-A
FXFQ20-63A
›› ›› ›› ›› ›› ›› ›› ››
›› ›› ›› ›› ›› ››
presence sensor
BRC1E52A/B BRC7A532F
floor sensor
The round flow cassette provides a more comfortable environment and offers greater savings in energy consumption to shop, office and restaurant owners 360° air discharge ensures uniform air flow and temperature distribution Modern style decoration panel is available in 3 different variations: pure white (RAL9010) auto cleaning panel, pure white (RAL9010) standard panel with grey louvers and pure white (RAL9010) standard panel with white louvers Daikin introduces first auto cleaning cassette to European market. Higher efficiency and comfort thanks to daily auto cleaning of the filter. Lower maintenance costs thanks to auto cleaning function. Easy dust removal with vacuum cleaner without opening the unit. The presence sensor (optional) adjusts the set point with standard 1°C if no one is detected in the room, it is possible to adjust the set point with 2, 3 or 4°C (optional). It also automatically directs air flow away from any person to avoid draught. The floor sensor (optional) detects the average floor temperature and ensures even temperature distribution between ceiling and floor. Cold feet will become history. Individual flap control: one flap can be easily closed via the wired remote control (BRC1E52) in case you would refurbish or rearrange your interior Low energy consumption thanks to specially developed small tube heat exchanger, DC fan motor and drain pump Fresh air intake: up to 20 % Low installation height: 214mm for class 20-63 Standard drain pump with 850mm lift
INDOOR UNIT Cooling capacity Nom. Heating capacity Nom. Power input - 50Hz Cooling Nom. Heating Nom. HeightxWidthxDepth Dimensions Unit Weight Unit Decoration panel Model Colour HeightxWidthxDepth Dimensions Weight Decoration panel 2 Model Colour HeightxWidthxDepth Dimensions Weight Decoration panel 3 Model Colour HeightxWidthxDepth Dimensions Weight Fan-Air flow rate Cooling High/Nom./Low - 50Hz Heating High/Nom./Low Sound power level Cooling High/Nom. Sound pressure Cooling High/Nom./Low level Heating High/Nom./Low Refrigerant Type Piping connections Liquid/OD/Gas/OD/Drain Power supply Phase/Frequency/Voltage Current - 50Hz Maximum fuse amps (MFA)
kW kW kW kW mm kg
mm kg
mm kg
mm kg m³/min m³/min dBA dBA dBA mm Hz/V A
FXFQ20A 2.2 2.5
FXFQ25A FXFQ32A FXFQ40A 2.8 3.6 4.5 3.2 4.0 5.0 0.038 0.038 204x840x840 19 20
FXFQ50A 5.6 6.3 0.053 0.053
FXFQ63A 7.1 8.0 0.061 0.061
FXFQ80A FXFQ100A 9.0 11.2 10.0 12.5 0.092 0.115 0.092 0.115 246x840x840 24
FXFQ125A 14.0 16.0 0.186 0.186 288x840x840 26
21 BYCQ140D7W1 Pure White (RAL 9010) 60x950x950 5.4 BYCQ140D7W1W Pure White (RAL 9010) 60x950x950 5.4 BYCQ140D7GW1 Pure White (RAL 9010) 145x950x950 10.3 12.5/10.6/8.8 13.6/11.6/9.5 15.0/12.8/10.5 16.5/13.5/10.5 22.8/17.6/12.4 26.5/19.5/12.4 33.0/26.5/19.9 12.5/10.6/8.8 13.6/11.6/9.5 15.0/12.8/10.5 16.5/13.5/10.5 22.8/17.6/12.4 26.5/19.5/12.4 33.0/26.5/19.9 49/51/53/55/60/61/31/29/28 33/31/29 35/33/30 38/34/30 43/37/30 45/41/36 31/29/28 33/31/29 35/33/30 38/34/30 43/37/30 45/41/36 R-410A 6.35/12.7/VP25 (O.D. 32 / I.D. 25) 9.52/15.9/VP25 (O.D. 32 / I.D. 25) 1~/50/60/220-240/220 16
BYCQ140D7W1 = pure white panel with grey louvers , BYCQ140D7W1W = pure white standard panel with white louvers, BYCQ140D7GW1 = Pure white auto cleaning panel The BYCQ140D7W1W has white insulations. Be informed that formations of dirt on white insulation is visibly stronger & that it is consequently not advised to install the decoration panel in environments exposed to concentrations of dirt.
83
INDOOR UNITS
850 mm
Fully flat cassette
Design & Genius in one Unique in the market, the fully flat cassette is a remarkable blend of iconic design and engineering excellence with an elegant white or a silver and white finish. Fitting flush within the ceiling modules and fully flat with the ceiling itself, the cassette is both stylish and unobtrusive. Superb efficiency and comfort is delivered through the combined use of floor and presence sensors and, when necessary, the individual flap control via the wired remote controller makes it simple to close one flap.
84
FXZQ-A
Fully flat cassette
presence sensor FXZQ-A (white panel)
›› ›› ››
›› ›› ›› ›› ››
BRC1E52A/B
BRC7F530W/S
Unique design in the market: integrates fully flat into the ceiling and fits flush into architectural ceiling modules Remarkable blend of iconic design and engineering excellence with an elegant finish in white or a combination of silver and white 15 class unit especially developed for small or well-insulated rooms, such as hotel bedrooms, small offices, etc. The presence sensor (optional) adjusts the set point with standard 1°C if no one is detected in the room, it is possible to adjust the set point with 2, 3 or 4°C (optional). It also automatically directs air flow away from any person to avoid draught. The floor sensor (optional) detects the average floor temperature and ensures even temperature distribution between ceiling and floor. Cold feet will become history. Individual flap control: one flap can be easily closed via the wired remote control (BRC1E52) in case you would refurbish or rearrange your interior Low energy consumption thanks to specially developed small tube heat exchanger, DC fan motor and drain pump Fresh air intake for healthy living Standard drain pump with 850mm lift
INDOOR UNIT Cooling capacity Nom. Heating capacity Nom. Power input - 50Hz Cooling Nom. Heating Nom. HeightxWidthxDepth Dimensions Unit Weight Unit Decoration panel Model Colour HeightxWidthxDepth Dimensions Weight Decoration panel 2 Model Colour HeightxWidthxDepth Dimensions Weight Decoration panel 3 Model Colour HeightxWidthxDepth Dimensions Weight Fan-Air flow rate Cooling High/Nom./Low - 50Hz Heating High/Nom./Low Sound power level Cooling High/Nom. Sound pressure Cooling High/Nom./Low level Heating High/Nom./Low Refrigerant Type Piping connections Liquid/OD/Gas/OD/Drain Power supply Phase/Frequency/Voltage Current - 50Hz Maximum fuse amps (MFA)
kW kW kW kW mm kg
FXZQ15A 1.7 1.9
FXZQ20A 2.2 2.5 0.043 0.036
FXZQ32A 3.6 4.0 0.045 0.038 260x575x575
15.5
mm kg
mm kg
mm kg m³/min m³/min dBA dBA dBA
FXZQ25A 2.8 3.2
8.5/7/6.5 8.5/7/6.5
8.7/7.5/6.5 8.7/7.5/6.5 49/-
31.5/28/25.5 31.5/28/25.5
32/29.5/25.5 32/29.5/25.5
mm Hz/V A
(1) Dimensions include control box
85
FXZQ40A 4.5 5.0 0.059 0.053 16.5
BYFQ60CW White (N9.5) 46x620x620 2.8 BYFQ60B3 White (N9.5) + Silver 46x620x620 2.8 BYFQ60B2 White (RAL9010) 55x700x700 2.7 9/8/6.5 10/8.5/7 9/8/6.5 10/8.5/7 50/51/33/30/25.5 33.5/30/26 33/30/25.5 33.5/30/26 R-410A 6.35/12.7/VP20 (I.D. 20/O.D. 26) 1~/50/220-240 16
FXZQ50A 5.6 6.3 0.092 0.086 18.5
11.5/9.5/8 11.5/9.5/8 54/37/32/28 37/32/28
14.5/12.5/10 14.5/12.5/10 60/43/40/33 43/40/33
INDOOR UNITS
››
floor sensor
FXZQ-A (silver and white panel)
FXCQ-A
2-way blow ceiling mounted cassette
FXCQ20_40A
›› ›› ›› ›› ›› ›› ››
BRC1E52A/B
BRC7CA52
Low energy consumption thanks to specially developed small tube heat exchanger, DC fan motor and drain pump Stylish unit blends easily with any interior, as the flaps close entirely when not in operation Improved comfort thanks to automatic air flow adjustment to required load Individual flap control: one flap can be easily closed via the wired remote control (BRC1E52) in case you would refurbish or rearrange your interior Easy to install: depth of all units is 620mm Maintenance operations can be performed by removing the front panel Standard drain pump with 500mm lift
INDOOR UNIT Cooling capacity Nom. Heating capacity Nom. Power input - 50Hz Cooling Nom. Heating Nom. Casing Material HeightxWidthxDepth Dimensions Unit Weight Unit Decoration panel Model Colour HeightxWidthxDepth Dimensions Weight Fan-Air flow rate - 50Hz Cooling High/Nom./Low Sound power level Cooling Nom. Sound pressure Cooling High/Nom./Low level Heating High/Nom./Low Refrigerant Type Piping connections Liquid/OD/Gas/OD/Drain Air filter Type Power supply Phase/Frequency/Voltage Current - 50Hz Maximum fuse amps (MFA)
kW kW kW kW mm kg
mm kg m³/min dBA dBA dBA mm Hz/V A
FXCQ20A 2.2 2.5 0.031 0.028
FXCQ25A 2.8 3.2
FXCQ32A 3.6 4.0
FXCQ40A FXCQ50A FXCQ63A FXCQ80A FXCQ125A 4.5 5.6 7.1 9.0 14.0 5.0 6.3 8.0 10.0 16.0 0.039 0.041 0.059 0.063 0.090 0.149 0.035 0.037 0.056 0.060 0.086 0.146 Galvanised steel plate 305x775x620 305x990x620 305x1,445x620 19 22 25 33 38 BYBCQ40HW1 BYBCQ63HW1 BYBCQ125HW1 Fresh white (6.5Y 9.5/0.5) 55x1,070x700 55x1,285x700 55x1,740x700 10 11 13 10.5/9/7.5 11.5/9.5/8 12/10.5/8.5 15/13/10.5 16/14/11.5 26/22.5/18.5 32/27.5/22.5 32.0/30.0/28.0 34.0/31.0/29.0 34.0/32.0/30.0 36.0/33.0/31.0 37.0/35.0/31.0 39.0/37.0/32.0 42.0/38.0/33.0 46.0/42.0/38.0 32.0/30.0/28.0 34.0/31.0/29.0 34.0/32.0/30.0 36.0/33.0/31.0 37.0/35.0/31.0 39.0/37.0/32.0 42.0/38.0/33.0 46.0/42.0/38.0 R-410A 6.35/12.7/VP25 (O.D. 32 / I.D. 25) 9.52/15.9/VP25 (O.D. 32 / I.D. 25) Resin net with mold resistance 1~/50/220-240 16
86
FXKQ-MA
Ceiling mounted corner cassette
FXKQ-MA
›› ››
BRC4C61
Compact dimensions, can easily be mounted in a narrow ceiling void (only 220mm ceiling space required, 195 with panel spacer, available as accessory) Optimum air flow conditions are created by either downward air discharge or frontal air discharge (via optional grille) or a combination of both
Standard drain pump with 500mm lift
INDOOR UNITS
››
BRC1E52A/B
INDOOR UNIT Cooling capacity Nom. Heating capacity Nom. Power input - 50Hz Cooling Nom. Heating Nom. HeightxWidthxDepth Dimensions Unit Weight Unit Decoration panel Model Colour HeightxWidthxDepth Dimensions Weight Fan-Air flow rate - 50Hz Cooling High/Low Sound power level Cooling Nom. Sound pressure level Cooling High/Low Refrigerant Type Piping connections Liquid/OD/Gas/OD/Drain Power supply Phase/Frequency/Voltage Current - 50Hz Maximum fuse amps (MFA)
kW kW kW kW mm kg
FXKQ25MA 2.8 3.2
FXKQ32MA 3.6 4.0
FXKQ40MA 4.5 5.0 0.076 0.056
0.066 0.046 215x1,110x710 31 BYK45FJW1
FXKQ63MA 7.10 8.00 0.105 0.085 215x1,310x710 34 BYK71FJW1
White mm kg m³/min dBA dBA
70x1,240x800 8.5 11/9
13/10
70x1,440x800 9.5 18/15
40.0/34.0
42.0/37.0
38.0/33.0 R-410A
mm Hz/V A
6.35/12.7/VP25 (O.D. 32 / I.D. 25) 1~/50/60/220-240/220 15
87
9.52/15.9/VP25 (O.D. 32 / I.D. 25)
FXDQ-M9
Small concealed ceiling unit
FXDQ-M9
›› ›› ›› ›› ››
BRC1E52A/B
BRC4C62
Designed for hotel bedrooms Compact dimensions (230mm high & 652mm deep), can easily be mounted in a ceiling void Blends unobtrusively with any interior décor: only the suction and discharge grilles are visible The air suction direction can be altered from rear to bottom suction For easy mounting, the drain pan can be located to the left or right of the unit
INDOOR UNIT Cooling capacity Nom. Heating capacity Nom. Power input - 50Hz Cooling Nom. Heating Nom. Casing Colour HeightxWidthxDepth Dimensions Unit Required ceiling void > Weight Unit Fan-Air flow rate Cooling High/Low - 50Hz Heating High/Low Sound power level Cooling Nom. Sound pressure Cooling High/Low level Heating High/Low Refrigerant Type Piping connections Liquid/OD/Gas/OD/Drain Power supply Phase/Frequency/Voltage Current - 50Hz Maximum fuse amps (MFA)
kW kW kW kW mm mm kg m³/min m³/min dBA dBA dBA
FXDQ20M9 2.2 2.5
FXDQ25M9 2.8 3.2 0.050 0.050 Unpainted 230x502x652 250 17
6.7/5.2 6.7/5.2
7.4/5.8 7.4/5.8 50 37/32 37/32 R-410A 6.35/12.7/I.D. 21.6, O.D. 27.2 1~/50/230 16
mm Hz/V A
88
FXDQ-A
Slim concealed ceiling unit
FXDQ15-32A
›› ›› ›› ›› ››
BRC4C65
Compact dimensions, can easily be mounted in a ceiling void of only 240mm Blends unobtrusively with any interior décor: only the suction and discharge grilles are visible 15 class unit especially developed for small or well-insulated rooms, such as hotel bedrooms, small offices, etc. Low energy consumption thanks to DC inverter fans Medium external static pressure facilitates unit use with flexible ducts of varying lengths Standard drain pump with 750mm lift
INDOOR UNITS
››
BRC1E52A/B
INDOOR UNIT Cooling capacity Nom. Heating capacity Nom. Power input - 50Hz Cooling Nom. Heating Nom. Casing Colour HeightxWidthxDepth Dimensions Unit Required ceiling void > Weight Unit Fan-Air flow rate - 50Hz Cooling High/Nom./Low Fan-External static pressure - 50Hz High/Nom. Sound power level Cooling Nom. Sound pressure level Cooling High/Nom./Low Refrigerant Type Piping connections Liquid/OD/Gas/OD/Drain Power supply Phase/Frequency/Voltage Current - 50Hz Maximum fuse amps (MFA)
kW kW kW kW mm mm kg m³/min Pa dBA dBA mm Hz/V A
FXDQ15A 1.7 1.9
7.5/7.0/6.4 50 32/31/27
FXDQ20A 2.2 2.5
FXDQ40A FXDQ50A 4.5 5.6 5.0 6.3 0.071 0.078 0.099 0.068 0.075 0.096 Galvanised steel / Non painted 200x750x620 200x950x620 240 22 26 8.0/7.2/6.4 10.5/9.5/8.5 12.5/11.0/10.0 30/10 44/15 51 52 53 33/31/27 34/32/28 35/33/29 R-410A 6.35/12.7/VP20 (I.D. 20/O.D. 26) 1~/50/60/220-240/220 16
89
FXDQ25A 2.8 3.2
FXDQ32A 3.6 4.0
FXDQ63A 7.1 8.0 0.110 0.107 200x1,150x620 29 16.5/14.5/13.0 54 36/34/30 9.52/15.9/VP20 (I.D. 20/O.D. 26)
FXSQ-P, FXMQ-P7
Concealed ceiling unit with inverter driven fan
FXMQ20-32P7
FXSQ20-32P
›› ›› ›› ›› ›› ›› ›› ››
BRC1E52A/B
BRC4C65
Easy installation thanks to automatic air flow adjustment towards nominal air flow rate Blends unobtrusively with any interior décor: only the suction and discharge grilles are visible Up to 140Pa external static pressure (ESP) facilitates using flexible ducts of variying lengths: ideal for shops and medium size offices (FXSQ) Up to 200Pa external static pressure allows extensive ductwork runs and flexible application: ideal for use in large areas (FXMQ) Low energy consumption thanks to DC inverter fans Possibility to change ESP via wired remote control allows optimisation of the supply air volume The air suction direction can be altered from rear to bottom suction Standard built-in drain pump increases reliability of the drain system
Easy installation thanks to automatic air flow adjustment towards nominal air flow: Installation made easier
›› ›› ›› ››
After installation, it is possible that the actual duct resistance is lower than expected at time of designing. As a consequence the air flow will be too high. With the automatic air flow adjustment function the unit can adapt its fan speed to a lower curve, so the air flow decreases. The air flow will always be within 10% of the rated air flow because of the amount of possible fan curves (more than 8 fan curves available per model). Alternatively the installer can manually select a fan curve with the wired remote control. +/- 10%
External static pressure (Pa)
Reduced installation time
Fan characteristic curve Actual duct resistance curve Duct resistance curve at the time of designing Rated air flow Airflow without air flow automatic adjustment Actual airflow
Air flow (m³/min)
+/- 10%
FXSQ-P - Medium static pressure INDOOR UNIT Cooling capacity Nom. Heating capacity Nom. Power input - 50Hz Cooling Nom. Heating Nom. Casing Colour HeightxWidthxDepth Dimensions Unit Required ceiling void > Weight Unit Decoration panel Model Colour HeightxWidthxDepth Dimensions Weight Fan-Air flow rate Cooling High/Nom./Low - 50Hz Heating High/Nom./Low Fan-External static pressure - 50Hz High/Nom. Sound power level Cooling Nom. Sound pressure Cooling High/Low level Heating High/Low Refrigerant Type Piping connections Liquid/OD/Gas/OD/Drain Power supply Phase/Frequency/Voltage Current - 50Hz Maximum fuse amps (MFA)
kW kW kW kW mm mm kg
mm kg m³/min m³/min Pa dBA dBA dBA mm Hz/V A
FXSQ20P FXSQ25P 2.2 2.8 2.5 3.2 0.041 0.029
FXSQ32P 3.6 4.0 0.044 0.032
FXSQ40P FXSQ50P FXSQ63P FXSQ80P FXSQ100P FXSQ125P FXSQ140P 4.5 5.6 7.1 9.0 11.2 14.0 16.0 5.0 6.3 8.0 10.0 12.5 16.0 18.0 0.097 0.074 0.118 0.117 0.185 0.261 0.085 0.062 0.106 0.105 0.173 0.249 Unpainted 300x550x700 300x700x700 300x1,000x700 300x1,400x700 350 23 26 35 46 47 BYBS32DJW1 BYBS45DJW1 BYBS71DJW1 BYBS125DJW1 White (10Y9/0.5) 55x650x500 55x800x500 55x1,100x500 55x1,500x500 3.0 3.5 4.5 6.5 19.5/17.8/16 25/22.5/20 32/27.5/23 39/33.5/28 46/39/32 9/7.8/6.5 9.5/8.3/7 16/13.5/11 19.5/17.8/16 25/22.5/20 32/27.5/23 39/33.5/28 46/39/32 9/7.8/6.5 9.5/8.3/7 16/13.5/11 70/30 100/30 100/40 120/40 120/50 140/50 55 56 63 59 63 61 66 67 32/26 33/27 37/29 37/30 38/32 40/33 42/34 32/26 33/27 37/29 37/30 38/32 40/33 42/34 R-410A 6.35/12.7/VP25 (O.D. 32 / I.D. 25) 9.52/15.9/VP25 (O.D. 32 / I.D. 25) 1~/50/60/220-240/220 16
90
INDOOR UNIT Cooling capacity Nom. Heating capacity Nom. Power input - 50Hz Cooling Nom. Heating Nom. Casing Colour Material HeightxWidthxDepth Dimensions Unit Required ceiling void > Weight Unit Decoration panel Model Colour HeightxWidthxDepth Dimensions Weight Fan-Air flow rate Cooling High/Nom./Low - 50Hz Heating High/Nom./Low Fan-External static pressure - 50Hz High/Nom. Sound power level Cooling High/Nom. Sound pressure Cooling High/Nom./Low level Heating High/Nom./Low Refrigerant Type Piping connections Liquid/OD/Gas/OD/Drain Air filter Type Power supply Phase/Frequency/Voltage Current - 50Hz Maximum fuse amps (MFA)
kW kW kW kW
mm mm kg
mm kg m続/min m続/min Pa dBA dBA dBA mm Hz/V A
FXMQ20P7 FXMQ25P7 2.2 2.8 2.5 3.2 0.049 0.037
FXMQ32P7 3.6 4.0 0.053 0.041
INDOOR UNITS
FXMQ-P7-High static pressure FXMQ50P7 FXMQ63P7 FXMQ80P7 FXMQ100P7 FXMQ125P7 5.6 7.1 9.0 11.2 14.0 6.3 8.0 10.0 12.5 16.0 0.110 0.120 0.171 0.176 0.241 0.098 0.108 0.159 0.164 0.229 Unpainted Galvanised steel plate 300x550x700 300x700x700 300x1,000x700 300x1,400x700 350 23 26 35 46 BYBS32DJW1 BYBS45DJW1 BYBS71DJW1 BYBS125DJW1 White (10Y9/0.5) 55x650x500 55x800x500 55x1,100x500 55x1,500x500 3.0 3.5 4.5 6.5 9/7.8/6.5 9.5/8.3/7 16/13.5/11 18/16.5/15 19.5/17.8/16 25/22.5/20 32/27.5/23 39/33.5/28 9.0/7.8/6.5 9.5/8.3/7 16/13.5/11 18/16.5/15 19.5/17.8/16 25/22.5/20 32/27.5/23 39/33.5/28 100/50 160/100 200/100 56/57/65/61/64/67/65/70/33/31/29 34/32/30 39/37/35 41/39/37 42/40/38 43/41/39 44/42/40 33/31/29 34/32/30 39/37/35 41/39/37 42/40/38 43/41/39 44/42/40 R-410A 6.35/12.7/VP25 (I.D. 25/O.D. 32) 9.52/15.9/VP25 (I.D. 25/O.D. 32) Resin net with mold resistance 1~/50/60/220-240/220 16
91
FXMQ40P7 4.5 5.0 0.151 0.139
FXMQ-MA
Large concealed ceiling unit
FXMQ-MA
›› ›› ››
BRC1E52A/B
BRC4C65
Up to 270Pa external static pressure allows extensive ductwork runs and flexible application: ideal for use in large areas Blends unobtrusively with any interior décor: only the suction and discharge grilles are visible Up to 31.5kW in heating mode
INDOOR UNIT Cooling capacity Nom. Heating capacity Nom. Power input - 50Hz Cooling Nom. Heating Nom. HeightxWidthxDepth Dimensions Unit Weight Unit Fan-Air flow rate - 50Hz Cooling High/Low Fan-External static pressure - 50Hz High/Nom. Sound power level Cooling Nom. Sound pressure level Cooling High/Low Refrigerant Type Piping connections Liquid/OD/Gas/OD/Drain Power supply Phase/Frequency/Voltage Current - 50Hz Maximum fuse amps (MFA)
kW kW kW kW mm kg m³/min Pa dBA dBA mm Hz/V A
FXMQ200MA 22.4 25.0 1.294 1.294
FXMQ250MA 28.0 31.5 1.465 1.465 470x1,380x1,100 137
58/50 221/132
72/62 270/191 48/45 R-410A
9.52/19.1/PS1B
9.52/22.2/PS1B 1~/50/60/220-240/220 15
92
FXAQ-P
Wall mounted unit
FXAQ15-32P
›› ›› ›› ›› ››
BRC7E618
Ideal solution for shops, restaurants or offices with no or narrow false ceilings Low energy consumption thanks to DC fan motor Can be installed in both new and existing buildings Flat, stylish front panel blends easily within any interior décor and is more easy to clean 15 class unit especially developed for small or well-insulated rooms, such as hotel bedrooms, small offices, etc. 5 different discharge angles can be programmed via the remote control Maintenance operations can be performed from the front of the unit
INDOOR UNITS
›› ››
BRC1E52A/B
INDOOR UNIT Cooling capacity Nom. Heating capacity Nom. Power input - 50Hz Cooling Nom. Heating Nom. Casing Colour HeightxWidthxDepth Dimensions Unit Weight Unit Fan-Air flow rate - 50Hz Cooling High/Low Sound power level Cooling Nom. Sound pressure level Cooling High/Low Refrigerant Type Piping connections Liquid/OD/Gas/OD/Drain Power supply Phase/Frequency/Voltage Current - 50Hz Maximum fuse amps (MFA)
kW kW kW kW mm kg m³/min dBA dBA
FXAQ15P 1.7 1.9 0.017 0.025
7.0/4.5 34.0/29.0
FXAQ20P 2.2 2.5 0.019 0.029
FXAQ25P 2.8 3.2 0.028 0.034
290x795x238 11 7.5/4.5 8/5 35.0/29.0
mm Hz/V A
93
FXAQ32P FXAQ40P 3.6 4.5 4.0 5.0 0.030 0.020 0.035 0.020 White (3.0Y8.5/0.5)
8.5/5.5 36.0/29.0 37.5/29.0 R-410A 6.35/12.7/VP13 (I.D. 13/O.D. 18) 1~/50/220-240 16
FXAQ50P 5.6 6.3 0.033 0.039
FXAQ63P 7.1 8.0 0.050 0.060
12/9
290x1,050x238 14 15/12
19/14
39.0/34.0
42.0/36.0
47.0/39.0 9.52/15.9/VP13 (I.D. 13/O.D. 18)
FXHQ-A
Ceiling suspended unit
FXHQ100A
›› ››
BRC1E52A/B
BRC7G53
›› ››
Ideal solution for commercial spaces with narrow or no false ceilings The unit can easily be mounted in corners and narrow spaces, as it only needs 30mm lateral service space Low energy consumption thanks to DC fan motor and drain pump Stylish unit blends easily with any interior, as the flaps close entirely when not in operation Can be installed in both new and existing buildings Wider air discharge thanks to Coanda effect: up to 100°
››
Air flow distribution for ceiling heights up to 3.8m without capacity loss
›› ››
INDOOR UNIT Cooling capacity Nom. Heating capacity Nom. Power input - 50Hz Cooling Nom. Heating Nom. Casing Colour HeightxWidthxDepth Dimensions Unit Weight Unit Fan-Air flow rate Cooling High/Nom./Low - 50Hz Heating High/Nom./Low Sound power level Cooling Nom. Sound pressure Cooling High/Nom./Low level Heating High/Nom./Low Refrigerant Type Piping connections Liquid/OD/Gas/OD/Drain Power supply Phase/Frequency/Voltage Current - 50Hz Maximum fuse amps (MFA)
kW kW kW kW mm kg m³/min m³/min dBA dBA dBA mm Hz/V A
FXHQ32A 3.6 4.0 0.107 0.107 235x960x690 24 14.0/12.0/10.0 14.0/12.0/10.0 36.0/34.0/31.0 36.0/34.0/31.0 6.35/12.7/VP20 (I.D. 20/O.D. 26)
94
FXHQ63A FXHQ100A 7.1 11.2 8.0 12.5 0.111 0.237 0.111 0.237 Fresh White 235x1,270x690 235x1,590x690 33 39 20.0/17.0/14.0 29.5/24.0/19.0 20.0/17.0/14.0 29.5/24.0/19.0 37.0/35.0/34.0 44.0/37.0/34.0 37.0/35.0/34.0 44.0/37.0/34.0 R-410A 9.52/15.9/VP20 (I.D. 20/O.D. 26) 1~/50/220-240 16
FXUQ-A
4-way blow ceiling suspended unit
FXUQ-A
›› ›› ›› ›› ›› ››
BRC7C58
Ideal solution for commercial spaces with narrow or no false ceilings Separate BEVQ box is no longer needed: the expansion valve is integrated in the indoor unit. Low energy consumption thanks to DC fan motor and drain pump Stylish unit blends easily with any interior, as the flaps close entirely when not in operation Improved comfort thanks to automatic air flow adjustment to required load Individual flap control: one flap can be easily closed via the wired remote control (BRC1E52) in case you would refurbish or rearrange your interior
Can be installed in both new and existing buildings Same outlook for all models (unified dimensions) Air can be discharged in 5 different angles between 0 and 60° Air flow distribution for ceiling heights up to 3.5m without capacity loss Standard drain pump with 500mm lift
INDOOR UNITS
›› ›› ›› ›› ››
BRC1E52A/B
INDOOR UNIT Cooling capacity Nom. Heating capacity Nom. Power input - 50Hz Cooling Nom. Heating Nom. Casing Colour HeightxWidthxDepth Dimensions Unit Weight Unit Fan-Air flow rate Cooling High/Nom./Low - 50Hz Heating High/Nom./Low Sound power level Cooling Nom. Sound pressure Cooling High/Nom./Low level Heating High/Nom./Low Refrigerant Type Piping connections Liquid/OD/Gas/OD/Drain Power supply Phase/Frequency/Voltage Current - 50Hz Maximum fuse amps (MFA)
kW kW kW kW mm kg m³/min m³/min dBA dBA dBA
FXUQ71A 8.0 9.0 0.090 0.073
FXUQ100A 11.2 12.5 0.200 0.179 Fresh White 198x950x950
26 22.5/19.5/16.0 22.5/19.5/16.0
27 31.0/26.0/21.0 31.0/26.0/21.0 -
40.0/38.0/36.0 40.0/38.0/36.0
47.0/44.0/40.0 47.0/44.0/40.0 R-410A 9.52/15.9/I.D. 20/O.D. 26 1~/50/60/220-240/220-230 16
mm Hz/V A
95
FXNQ-P
Concealed floor standing unit
FXNQ20-25P
›› ›› ›› ››
BRC1E52A/B
BRC4C65
Its low height enables the unit to fit perfectly beneath a window Blends unobtrusively with any interior décor: only the suction and discharge grilles are visible Requires very little installation space The connecting port faces downward, eliminating the need to attach auxiliary piping
INDOOR UNIT Cooling capacity Nom. Heating capacity Nom. Power input - 50Hz Cooling Nom. Heating Nom. HeightxWidthxDepth Dimensions Unit Weight Unit Fan-Air flow rate - 50Hz Cooling High/Low Sound power level Cooling Nom. Sound pressure level Cooling High/Low Refrigerant Type Piping connections Liquid/OD/Gas/OD/Drain Power supply Phase/Frequency/Voltage Current - 50Hz Maximum fuse amps (MFA)
kW kW kW kW mm kg m³/min dBA dBA
FXNQ20P 2.2 2.5
FXNQ25P 2.8 3.2
0.049 0.049 610x930x220 19 7/6
FXNQ32P 3.6 4.0
FXNQ40P 4.5 5.0
FXNQ50P 5.6 6.3
0.090 0.090 610x1,070x220 23 8/6
FXNQ63P 7.1 8.0
0.110 0.110 610x1,350x220 27 11/8.5
14/11
16/12
38/33 R-410A 6.35/12.7/O.D. 21 1~/50/60/220-240/220 15
39/34
40/35
35/32
mm Hz/V A
96
9.52/15.9/O.D. 21
FXLQ-P
Floor standing unit
FXLQ20-25
›› ›› ›› ›› ››
Stylish modern casing finished in pure white (RAL9010) and iron grey (RAL7011) Unit can be installed as free standing model by use of optional back plate Its low height enables the unit to fit perfectly beneath a window Requires very little installation space Wall mounted installation facilitates cleaning beneath the unit where dust tends to accumulate
Wired remote control can easily be integrated in the unit
INDOOR UNITS
››
BRC7C62
BRC1E52A/B
INDOOR UNIT Cooling capacity Nom. Heating capacity Nom. Power input - 50Hz Cooling Nom. Heating Nom. Casing Colour HeightxWidthxDepth Dimensions Unit Weight Unit Fan-Air flow rate - 50Hz Cooling High/Low Sound power level Cooling Nom. Sound pressure level Cooling High/Low Refrigerant Type Piping connections Liquid/OD/Gas/OD/Drain Power supply Phase/Frequency/Voltage Current - 50Hz Maximum fuse amps (MFA)
kW kW kW kW mm kg m³/min dBA dBA
FXLQ20P 2.2 2.5
FXLQ25P 2.8 3.2 0.049 0.049
600x1,000x232 27 7/6 35/32
mm Hz/V A
97
FXLQ32P 3.6 4.0
FXLQ40P 4.5 5.0
0.090 0.090 Fresh white (RAL9010) / Dark grey (RAL7011) 600x1,140x232 32 8/6 11/8.5 38/33 R-410A 6.35/12.7/O.D. 21 1~/50/60/220-240/220 15
FXLQ50P 5.6 6.3
FXLQ63P 7.1 8.000 0.110 0.110
600x1,420x232 38 14/11
16/12
39/34
40/35 9.52/15.9/O.D. 21
98
Stylish indoor unit range for connection to VRV IV and VRV III-S
Connectable outdoor unit
Capacity
Round flow cassette (incl. autocleaning function1)
FCQG-F
FFQ-C
Fully flat cassette
WALL MOUNTED CEILING SUSPENDED
15
20
25
35
42
50
60
71
Small concealed ceiling unit FDBQ-B
Slim concealed ceiling unit FDXS-F(9)
Concealed ceiling unit with inverter driven fan
FBQ-C8
FTXG-LW/ LS
Wall mounted unit
CTXS-K FTXS-K
Wall mounted unit
FTXS-G
Ceiling suspended unit
FHQ-C
Wall mounted unit
FVXG-K
Floor standing unit
FVXS-F
Flexi type unit
FLXS-B(9)
Nexura floor standing unit
FLOOR STANDING
RXYSQ-P8V1 RXYSQ-P8Y1
Product name
Daikin Emura
new
RYYQ-T RXYQ-T
Model
99
INDOOR UNITS
CONCEALED CEILING
CEILING MOUNTED CASSETTE
Type
Fall in love with Daikin Emura.
Daikin Emura is reÂfined on the outside and smart on the inside. Built-in intelligence and innovative features enÂsure low energy consumption. Its smart sensors provide optimal performances for year round comfort. Still, youâ&#x20AC;&#x2122;re always in control via the easy-to-use remote controller and the smartphone app with intuitive interface. You see... The new Daikin Emura has everything to fall in love with.
Find out more on www.daikinemura.eu 100
FTXG-LW/S / RXG-L
FTXG-LW/S
›› ›› ›› ››
RXG-L
emura
ARC466A1
Remarkable blend of iconic design and engineering excellence with an elegant finish in matt crystal white or silver Completely new European design, while keeping the identity of the 1st generation Daikin Emura. SEER up to A+++ Whisper quiet in operation: the operating of the unit can hardly be heard. The sound pressure level goes down to 19dBA! Online controller (optional): control your indoor unit from any location via smartphone or tablet.
INDOOR UNITS
››
Wall mounted unit
Heating & Cooling INDOOR UNIT Cooling capacity Heating capacity Power input
Min./Nom./Max. Min./Nom./Max. Cooling Min./Nom./Max. Heating Min./Nom./Max. Casing Colour HeightxWidthxDepth Dimensions Unit Weight Unit High/Nom./Low/Silent operation Fan - Air flow rate Cooling High/Nom./Low/Silent operation Heating Sound power level Cooling Heating High/Nom./Low/Silent operation Sound pressure Cooling level High/Nom./Low/Silent operation Heating Piping Liquid OD connections Gas OD Drain OD Power supply Phase / Frequency / Voltage
kW kW kW kW mm kg m³/min m³/min dBA dBA dBA dBA mm mm mm Hz / V
FTXG20LW FTXG20LS 1.3 /-/2.8 1.3 /-/4.3 0.32 /0.501 /0.76 0.31 /0.50 /1.12 White Silver
FTXG25LW FTXG25LS FTXG35LW FTXG35LS 1.3 /-/3.0 1.4 /-/3.8 1.3 /-/4.5 1.4 /-/5.0 0.32 /0.523 /0.82 0.35 /0.882 /1.19 0.31 /0.769 /1.32 0.32 /0.985 /1.49 White Silver White Silver 303x998x212 12 8.9/6.6/4.4/2.6 10.9/7.8/4.8/2.9 10.2/8.4/6.3/3.8 11.0/8.6/6.3/3.8 12.4/9.6/6.9/4.1 54 59 56 59 38/32/25/19 45/34/26/20 40/34/28/19 41/34/28/19 45/37/29/20 6.35 9.5 18 1~ / 50 / 220-240
(1) EER/COP according to Eurovent 2012, for use outside EU only.
101
FTXG50LW FTXG50LS 1.7 /-/5.3 1.7 /-/6.5 0.37 /1.360 /1.88 0.31 /1.589 /2.49 White Silver
10.9/8.9/6.8/3.6 12.6/10.5/8.1/5.0 60 60 46/40/35/32 47/41/35/32 12.7
FTXS-K & CTXS-K
Optimal design and comfort Integrated design ›› Discreet, modern design. Its smooth curve blends beautifully with the wall resulting in an unobtrusive presence that matches all interior décors. › High quality matt crystal white finish. ›› New remote controller design, in the same high quality matt white finish to create a perfect match with the indoor unit.
Top performance The FTXS-K series delivers top performance and are equipped with a weekly timer and intelligent eye to generate further energy savings. The weekly timer allows you to programme your unit so that it best suits your needs, whereas the intelligent eye detects the presence of people in the room and activates the economy mode when no one is there.
The right indoor for the right room We have a full range of wall units to provide optimal design and comfort in any room. Our small wall mounted units (CTXS15,35K and FTXS20,25K) are optimised for small offices or hotel bedrooms. ›› Recognising the trend for less spacious rooms or offices and better insulation, we extended our range with the 15 class to deliver exactly the right comfort in smaller rooms. ›› In general, silence is even more important in bedrooms than in other areas: our small wall mounted series go almost unnoticed with operating sound levels as low as 19dBA Our larger wall mounted units (FTXS35, 42, 50K) deliver perfect comfort to your larger area's. ›› ›› ››
The new discharge air pattern - using the `Coanda effect’ - provides a greater airflow length ensuring perfect comfort in every corner of the room. The two-area intelligent eye detects where people are located in the room and can project the airflow away from the occupants to avoid direct draught. To optimize comfort even further the new wall mounted series are whisper quiet.
102
FTXS-K/G / RXS-K/F
FTXS20-25K//CTXS15-35K
›› ›› ›› ›› ››
››
ARC466A6
Discreet, modern design. Its smooth curve blends beautifully with the wall resulting in an unobtrusive presence that matches all interior décors. High quality matt crystal white finish Whisper quiet in operation: the operating of the unit can hardly be heard. The sound pressure level goes down to 19dBA! Ideal for installation in small or well insulated rooms (20,25 class) and larger or irregular shaped areas (35,42,50 class) 2 area intelligent eye: air flow is sent to a zone other than where the person is located at that moment. If no people are detected, the unit will automatically switch over to the energy-efficient setting. (FTXS35,42,50K) Online controller (optional): control your indoor unit from any location via smartphone, laptop, pc, tablet or touch screen (FTXS35,42,50,60,71) Improved air discharge pattern, using the Coanda effect
INDOOR UNITS
››
Wall mounted unit
Heating & Cooling INDOOR UNIT Casing Dimensions Weight Fan - Air flow rate
Colour HeightxWidthxDepth Unit Unit High/Nom./Low/Silent operation Cooling Heating High/Nom./Low/Silent operation Sound power level Cooling Heating High/Nom./Low/Silent operation Sound pressure Cooling level High/Nom./Low/Silent operation Heating Piping Liquid OD connections Gas OD Drain OD Power supply Phase / Frequency / Voltage
CTXS15K mm kg m³/min m³/min dBA dBA dBA dBA mm mm mm Hz / V
7.9/6.3/4.7/3.9 9.0/7.5/6.0/4.3 55 56 37/31/25/21 38/33/28/21
CTXS35K
FTXS20K
FTXS25K
FTXS35K White
289x780x215 8 9.2/7.2/5.2/3.9 8.8/8.8/4.7/3.9 9.1/9.1/5.0/3.9 10.1/8.1/6.3/4.3 9.5/7.8/6.0/4.3 10.0/8.0/6.0/4.3 59 58 58 42/35/28/21 40/32/24/19 41/33/25/19 41/36/30/21 40/34/27/19 41/34/27/19
298x900x215 11 11.2/11.2/5.8/4.1 11.2/11.2/7.0/4.1 12.1/9.3/6.5/4.2 12.4/10.0/7.8/5.2 59 59 45/37/29/19 45/39/33/21 45/39/29/19 45/39/33/22 6.35
9.5
FTXS50K
FTXS60G
FTXS71G
290x1,050x250 12 11.9/11.9/7.4/4.5 16.0/16.0/11.3/10.1 17.2/17.2/11.5/10.5 13.3/10.8/8.4/5.5 17.2/14.9/12.6/11.3 19.5/16.7/14.2/12.6 60 63 60 59 62 46/40/34/23 45/41/36/33 46/42/37/34 47/40/34/24 44/40/35/32 46/42/37/34 12.7
18 1~ / 50 / 220-240
103
FTXS42K
15.9
Logo grijs
The best of two worlds united Pure comfort and design
Comfort is key Nexura makes your world a comfortable one. The coolness of a summer breeze or the cosiness of an extra heat source brings a feeling of wellbeing all year round. Its unobtrusive yet stylish design with a front panel that radiates additional heat, its low noise level and reduced air flow turn your space into a haven.
radiant heat
104
FVXG-K/RXLG-K
Floor standing unit with radiant heat panel
radiant heat
FVXG-K
›› ›› ››
›› ››
The aluminium part of the front panel of the Nexura indoor unit has the capability of warming up, just like a traditional radiator, to add even more comfort on cold days Quiet and discrete, Nexura offers you the best in heating and cooling, in comfort and design The indoor unit distributes air at the sound of a whisper. The noise produced amounts to barely 22dB(A) in cooling and 19dB(A) in radiant heat mode. In comparison, the ambient sound in a quiet room amounts to 40dB(A) on average. Comfortable vertical auto swing ensures draughtfree operation and prevents ceiling soiling Online controller (optional): control your indoor unit from any location via smartphone, laptop, pc, tablet or touch screen Can be installed against a wall or recessed
INDOOR UNITS
››
ARC466A2
Heating & Cooling INDOOR UNIT Casing Dimensions Weight Fan - Air flow rate
Colour HeightxWidthxDepth Unit Unit High/Nom./Low/Silent operation Cooling High/Nom./Low/Silent operation Heating Sound power level Cooling Heating High/Nom./Low/Silent operation Sound pressure Cooling level High/Nom./Low/Silent operation Heating Piping Liquid OD connections Gas OD Power supply Phase / Frequency / Voltage
FVXG25K mm kg m³/min m³/min dBA dBA dBA dBA mm mm Hz / V
FVXG35K Fresh white (6.5Y 9.5/0.5) 600x950x215 22 9.1/9.1/5.3/4.5 10.2/8.0/5.8/5.0
8.9/8.9/5.3/4.5 9.9/7.8/5.7/4.7 52 53 38/32/26/23 39/32/26/22/19
39/33/27/24 40/33/27/23/19 6.35 9.5
10.6/10.3/7.3/6.0 12.2/10.0/7.8/6.8 58 60 44/40/36/32 46/40/34/30/26 12.7
1~ / 50 / 220-240
105
FVXG50K
FVXS-F / RXS-K
FVXS-F
›› ›› ›› ›› ››
Floor standing unit
ARC452A1
Its low height enables the unit to fit perfectly beneath a window Can be installed against a wall or recessed Whisper quiet operation: down to 23dBA sound pressure level Vertical auto swing moves the discharge flaps up and down for efficient air and temperature distribution throughout the room Online controller (optional): control your indoor unit from any location via smartphone, laptop, pc, tablet or touch screen
Heating & Cooling INDOOR UNIT Casing Dimensions Weight Fan - Air flow rate
Colour HeightxWidthxDepth Unit Unit High/Nom./Low/Silent operation Cooling High/Nom./Low/Silent operation Heating Sound power level Cooling Heating High/Nom./Low/Silent operation Sound pressure Cooling level High/Nom./Low/Silent operation Heating Piping Liquid OD connections Gas OD Drain OD Power supply Phase / Frequency / Voltage
FVXS25F mm kg m³/min m³/min dBA dBA dBA dBA mm mm mm Hz / V
FVXS35F White 600x700x210 14 8.5/8.5/4.9/4.5 9.4/7.3/5.2/4.7
8.2/8.2/4.8/4.1 8.8/6.9/5.0/4.4 52 52 38/32/26/23 38/32/26/23
39/33/27/24 39/33/27/24 6.35 9.5
10.7/10.7/7.8/6.6 11.8/10.1/8.5/7.1 60 60 44/40/36/32 45/40/36/32 12.7
20 1~ / 50 / 220-240
106
FVXS50F
FLXS-B(9) / RXS-K
FLXS-B
›› ››
ARC433A6
FLXS-B
Can fit on either ceiling or lower wall; its low height enables the unit to fit beneath a window Vertical auto swing moves the discharge flaps up and down for efficient air and temperature distribution throughout the room Whisper quiet operation: down to 28dBA sound pressure level Online controller (optional): control your indoor unit from any location via smartphone, laptop, pc, tablet or touch screen
INDOOR UNITS
›› ››
Flexi type unit
Heating & Cooling INDOOR UNIT Casing Colour HeightxWidthxDepth Dimensions Unit Weight Unit High/Nom./Low/Silent operation Fan - Air flow rate Cooling High/Nom./Low/Silent operation Heating Sound power level Cooling Heating High/Nom./Low/Silent operation Sound pressure Cooling level High/Nom./Low/Silent operation Heating Piping Liquid OD connections Gas OD Drain OD Power supply Phase / Frequency / Voltage
FLXS25B mm kg m³/min m³/min dBA dBA dBA dBA mm mm mm Hz / V
FLXS35B9
FLXS50B
FLXS60B
Almond white 490x1,050x200 16 7.6/7.6/6.0/5.2 9.2/8.3/7.4/6.6 51 51 37/34/31/28 37/34/31/29
17 8.6/7.6/6.6/5.6 12.8/10.4/8.0/7.2 53 59 38/35/32/29 46/36/33/30
11.4/11.4/8.5/7.5 12.1/9.8/7.5/6.8
12.0/10.7/9.3/8.3 12.8/10.6/8.4/7.5 60
47/43/39/36 46/41/35/33
59 48/45/41/39 47/42/37/34
6.35 9.5 18.0
12.7 20 1~ / 50 / 220-240
107
18
HXY-A HXY-A
Low temperature hydrobox for VRV
HXY-A
›› ›› ›› ›› ›› ›› ›› ›› ››
Highly efficient space heating/cooling Air to water connection to VRV for applications such as underfloor, AHU, low temperture radiators, … Leaving water temperature range from 5°C to 45°C without electric heater Super wide operating range for cold/hot water production from -20 to +43°C ambient outdoor temperature Saves time on system design as all water-side components are fully integrated with direct control over leaving water temperature Saves space with contemporary wall hung design Requires no gas connection or oil tank Connectable to VRV IV heat pump and heat recovery
Liquid pipe Gas pipe F1, F2 communication Hot/cold water
VRV indoor units Air handling unit
Low temp. radiator
Under floor heating
VRV IV heat pump
INDOOR UNIT Cooling capacity Heating capacity Casing
Nom. Nom. Colour Material Dimensions Unit Weight Unit Sound pressure level Nom. Operation range Heating Cooling
kW kW
HeightxWidthxDepth
Ambient Water side Ambient Water side
Min.~Max. Min.~Max. Min.~Max. Min.~Max.
Refrigerant Type Refrigerant circuit Gas side diameter Liquid side diameter Water circuit Piping connections diameter Power supply Phase/Frequency/Voltage Recommended fuses
HXY080A 8 9
HXY125A 12.5 14 White Precoated sheet metal 890x480x344 44 -20~24 25~45 10~43 5~20 R-410A 15.9 9.5 G 1”1/4 (female) 1~/50/220-240 6~16
mm kg dBA °C °C °C °C mm mm inch Hz/V A
108
HXHD-A
HXHD-A
›› ›› ›› ›› ››
High temperature hydrobox for VRV
EKHTS-AC
EKHWP-B
››
Air to water connection to VRV for applications such as bathrooms, sinks, underfloor heating, radiators and air handling units Free heating provided by transferring heat from areas requiring cooling to areas requiring heating or hot water Uses heat pump technology to produce hot water efficiently, providing up to 17% savings compared to a gas boiler Possibility to connect thermal solar collectors to the domestic hot water tank Leaving water temperature range from 25 to 80°C without electric heater
Hot water production and heating: maximum savings by heat recovery Cooling demand Heating demand Hot water demand
›› ›› ›› ›› ››
0 5000 10000 15000 20000 25000 30000
Jan
Partial heat recovery
Super wide operating range for hot water production from -20 to +43°C ambient outdoor temperature Saves time on system design as all water-side components are fully integrated with direct control over leaving water temperature Various control possibilities with weather dependant set point or thermostat control The indoor unit and domestic hot water tank can be stacked to save space, or installed next to each other, if only limited height is available Requires no gas connection or oil tank Connectable to VRV IV heat recovery (REYQ-T) and VRV III heat recovery (REAYQ-P)
Feb Mar Apr May Jun
Hot water and heating virtually for free thanks to heat recovery
Jul Aug Sep Oct
Heat recovery
Nov
Partial heat recovery
Dec
45°C - 75°C Liquid pipe Gas pipe Discharge gas pipe F1, F2 communication Hot water
Domestic hot water
VRV indoor units Air handling unit 25°C - 75°C
Domestic hot water tank 45°C - 75°C
BS-Box
Heating only hydrobox for VRV
VRV heat recovery with connection to heating only hydrobox (REYAQ10-16P)
INDOOR UNIT Heating capacity
Nom. Colour Casing Material Dimensions Unit HeightxWidthxDepth Weight Unit Nom. Sound pressure level Night quiet mode Level 1 Ambient Min.~Max. Heating Water side Min.~Max. Operation range Ambient Min.~Max. Domestic hot water Water side Min.~Max. Refrigerant Type Gas side diameter Refrigerant circuit Liquid side diameter Piping connections diameter Water circuit Heating water system Water volume Min.~Max. Power supply Phase/Frequency/Voltage Current Recommended fuses
Under floor heating 25°C - 35°C
HXHD125A 14.0 Metallic grey Precoated sheet metal 705x600x695 92 42 (1) / 43 (2) 38 (1) -20~20 / 24 (3) 25~80 -20~43 45~75 R-134a 12.7 9.52 G 1” (female) 20~200 1~/50/220-240 20
kW
mm kg dBA dBA °C °C °CDB °C mm mm inch l Hz/V A
(1) Sound levels are measured at: EW 55°C; LW 65°C (2) Sound levels are measured at: EW 70°C; LW 80°C (3) Field setting
109
Low temp. radiator
HOT WATER
BS-Box
HXHD-A
Accessories
Domestic hot water tank: Overview 1/ EKHTS-AC
Functions
Domestic hot water only
Domestic hot water – possibility for solar connection
The water stored in the tank is used for domestic hot water
Domestic hot water is not stored in the tank but flows through the tank’s coil
Preferred application
Operation
2/ EKHWP-B
1. EKHTS – domestic hot water only ›› ›› ››
Available in 200 and 260 litres Efficient temperature heat-up: from 10°C to 50°C in only 60 minutes Stainless steel domestic hot water tank INDOOR UNIT Casing Dimensions Weight Tank
Heat exchanger
EKHTS200AC Colour Material Unit
EKHTS260AC Metallic grey Galvanised steel (precoated sheet metal)
Height(Integrated on mm indoor unit)xWidthxDepth Empty kg l
Unit Water volume Material Maximum water temperature Quantity Tube material Face area Internal coil volume
2,010x600x695
2,285x600x695
70 200
78 260 Stainless steel (EN 1.4521) 75 1 Duplex steel (EN 1.4162) 1.56 7.5
°C
m² l
110
2. EKHWP-B – Domestic hot water with possibility for solar connection Solar connection ›› ›› ›› ››
Environmentally friendly and energy efficient Solar panels can produce up to 70% of the energy needed for hot water production – a major cost saving Specialised coatings make our solar panels highly energy efficient – all shortwave solar energy is transferred into heat The solar panels are charged with water only when needed for heating – avoiding the need for ‘anti-freeze’ protection SOLAR COLLECTOR HeightxWidthxDepth Dimensions Unit Weight Unit Volume Surface Outer Aperture Absorber Coating Absorber Glazing Allowed roof angle Min.~Max. Operating pressure Max. Stand still temperature Max. Thermal performance Zero loss collector efficiency η0 Installed position
mm kg l m² m² m²
° bar °C %
EKSH26P EKSV21P EKSV26P 1,300x2,000x85 2,000x1,006x85 2,000x1,300x85 42 35 42 2.1 1.3 1.7 2.6 2.01 2.6 2.350 1.79 2.35 2.360 1.8 2.36 Micro-therm (absorption max.96%, Emission ca. 5% +/-2%) Harp-shaped copper pipe register with laser-welded highly selective coated aluminium plate Single pane safety glass, transmission +/- 92% 15~80 6 200 Horizontal Vertical
Domestic hot water tank Available in 300 and 500 litres (Pre-)heat the water for your heating system with solar energy
DOMESTIC HOT WATER TANK Dimensions Unit
Weight Tank
Heat exchanger
Height Width Depth Empty
Unit Water volume Maximum water temperature Insulation Heat loss Domestic hot Tube material water Face area Internal coil volume Operating pressure Average specifc thermal output Charging Tube material Face area Internal coil volume Operating pressure Average specifc thermal output Auxiliary solar Tube material heating Face area Internal coil volume Operating pressure Average specifc thermal output
EKHWP300B 1,640 595 615 59 300
mm mm mm kg l °C kWh/24h
EKHWP500B 1,640 790 790 93 500 85
1.3
1.4 Stainless steel
m² l bar W/K
5.8 27.9
6 29 6
2,790
2,900 Stainless steel
m² l bar W/K
2.7 13.2
3.8 18.5 3
1,300
1,800 Stainless steel
m² l bar W/K
-
0.5 2.3 3
-
Pump station ››
The pump station ensures that the correct water pressure and flow rates are maintained for optimum efficiency
INDOOR UNIT Mounting HeightxWidthxDepth Dimensions Unit Thermal performance Zero loss collector efficiency η0 Control Type Power consumption Sensor Solar panel temperature sensor Storage tank sensor Return flow sensor Feed temperature and flow sensor Power supply Voltage
mm % W
V
EKSRPS3 On side of tank 815x230x142 Digital temperature difference controller with plain text display 2 Pt1000 PTC PTC Voltage signal (3.5V DC) 230
111
280
HOT WATER
›› ››
Biddle connected to Benefits of
Daikin Heat Pumps
Biddle air curtains provide highly efficient solutions for retailers and consultants to combat the issue of climate separation across their outlet or office doorway.
â&#x20AC;&#x2DC;Open Doorâ&#x20AC;&#x2122; Trading Although the customer friendly aspects of open door trading are widely appreciated by retail and commercial outlet managers, open doors can also give rise to massive losses in conditioned warm or cold air and hence, energy. Biddle air curtains however, not only preserve indoor temperatures and generate significant economies, they also represent an invitation for customers, to enter a pleasant trading and working environment.
High efficiency and low CO2 emission
An efficient outdoor/indoor climate separation limits heat loss through the door opening and enhances the efficiency of the air conditioning system. Combining Biddle air curtains with Daikin heat pumps can lead to savings up to 72% compared to electric air curtains and a paypack period of less than 1.5 years!
112
Air Curtains Which air curtain offers me the best solution? Biddle air curtains come in 2 versions, one to connect to VRV end one for connection to ERQ. Both of them ar available in varying door widths from 1 up to 2.5 meters. Below you can find an overview of the different versions and available door heights.
Biddle air curtain for connection to VRV (CYV) or to ERQ (CYQ) Biddle comfort air curtain range Free-Hanging (F)
4
Door height (m)
3.8m
3.5m
3.3m 3.0m
2.8m
3
3.0m 2.5m
2.5m
2.4m
2.2m
2.2m
2
Cassette (C)
1
S
M
L
XL
S
M
L
Normal
Favourable
ex: covered shopping mall or revolving door entrance
XL
ex: little direct wind, no opposite open doors, building with ground floor only
M
L
Unfavourable
XL Installation condition
ex: location at a corner or square, multiple floors and / or open stairwell
Biddle comfort air curtian nomenclature CA V S 150 DK 80 F S C Controller (standard) Color. B=White (RAL6010), S: Grey (RAL9006) Installation type: F=Freehanging, C=Cassette, R=Recessed Capacity class (kW) Daikin direct expansion Door width (cm) Range. S=small, M=Medium, L=Large, XL= Extra Large Connectable to VRV Biddle comfort air curtain
113
BIDDLE AIR CURTAINS
Recessed (C)
CYVS/M/L-DK-F/C/R
CYVM150DK80FSC
›› ›› ›› ›› ›› ›› ›› ›› ›› ››
CYVM150DK80CSN
CYVM150DK80RSN
Connectable to VRV heat recovery and heat pump VRV is among the first DX systems suitable for connection to air curtains Free-hanging model (F): easy wall mounted installation Cassette model (C): mounted into a false ceiling leaving only the decoration panel visible Recessed model (R): neatly concealed in the ceiling Provides virtually free air curtain heating via recovered heat from indoor units in cooling mode (in case of VRV heat recovery) Easy and quick to install at reduced costs since no additional water sytems, boilers and gas connections are required Maximum energy efficiency stemming from almost zero down flow turbulence, optimised air flow and the application of advanced discharge rectifier technology Around 85% air separation efficiency, greatly reducing both heat loss and required indoor unit heating capacity
less than 1.5 years Packtime of
electric air curtain
12000
total cost (installation + running cost) in €
PATENTED TECHNOLOGY
Biddle air curtain for VRV
10000 8000 Daikin heat pump with Biddle air curtain*
6000 4000 2000 0 1
2
years
* Payback period and gains calculated based upon the following: Air curtain is 9hrs/day – 156 days year (1,404 hrs/year) in use. Annual energy consumption for an electric air curtain: 3,137EUR (COP = 0.95). Typical installation cost: 1,000EUR; Typical equipment cost: 2,793EUR. Annual energy consumption for CYQS200DK100FBN and ERQ100AV: 748EUR (COP 4.00). Typical installation cost: 2,000EUR; Typical equipment cost: 5,150EUR. Calculation based upon electricity cost: 0,1705EUR /kWh
114
VRV Network Solution
Biddle comfort air curtain (ca) Integration in a VRV total solution
Small CYVS100DK80*BN/*SN Heating capacity Power input Delta T Casing Dimensions
Speed 3 Fan only Heating Speed 3 Colour Unit
Nom. Nom.
Height F/C/R Width F/C/R Depth F/C/R
Required ceiling void > Door height Max. Door width Max. Weight Unit Fan-Air flow rate Heating Speed 3 Sound pressure level Heating Speed 3 Refrigerant Type Piping connections Liquid/OD/Gas/OD Required accessories (should be ordered separately) Power supply Voltage
kW kW kW K mm mm mm mm m m kg m続/h dBA mm V
Medium
CYVS150DK80*BN/*SN CYVS200DK100*BN/*SN CYVS250DK140*BN/*SN CYVM100DK80*BN/*SN CYVM150DK80*BN/*SN CYVM200DK100*BN/*SN CYVM250DK140*BN/*SN
7.40 0.23 0.23 19
9.0 0.35 0.35
11.6 0.46 0.46
16.2 9.2 11.0 13.4 19.9 0.58 0.37 0.56 0.75 0.94 0.58 0.37 0.56 0.75 0.94 15 16 17 14 13 15 BN: RAL9010 / SN: RAL9006 270/270/270 1,000/1,000/1,048 1,500/1,500/1,548 2,000/2,000/2,048 2,500/2,500/2,548 1,000/1,000/1,048 1,500/1,500/1,548 2,000/2,000/2,048 2,500/2,500/2,548 590/821/561 420 2.3 (1) / 2.15 (2) / 2.0 (3) 2.3 (1) / 2.15 (2) / 2.0 (3) 2.3 (1) / 2.15 (2) / 2.0 (3) 2.3 (1) / 2.15 (2) / 2.0 (3) 2.5 (1) / 2.4 (2) / 2.3 (3) 2.5 (1) / 2.4 (2) / 2.3 (3) 2.5 (1) / 2.4 (2) / 2.3 (3) 2.5 (1) / 2.4 (2) / 2.3 (3) 1.0 1.5 2.0 2.5 1.0 1.5 2.0 2.5 56 66 83 107 57 73 94 108 1,164 1,746 2,328 2,910 1,605 2,408 3,210 4,013 47 49 50 51 50 51 53 54 R-410A 9.52/16.0 9.52/19.0 9.52/16.0 9.52/19.0 Daikin wired remote control (BRC1E52A/B or BRC1D52) 230
Heating capacity Power input Delta T Casing Dimensions
Speed 3 Fan only Heating Speed 3 Colour Unit
Nom. Nom.
Height F/C/R Width F/C/R Depth F/C/R
Required ceiling void > Door height Max. Door width Max. Weight Unit Fan-Air flow rate Heating Speed 3 Sound pressure level Heating Speed 3 Refrigerant Type Piping connections Liquid/OD/Gas/OD Required accessories (should be ordered separately) Power supply Voltage
kW kW kW K
CYVL150DK200*BN/*SN
CYVL200DK250*BN/*SN
CYVL250DK250*BN/*SN
15.6 0.75 0.75
23.3 1.13 1.13
29.4 1.50 1.50 14
31.1 1.88 1.88 12
15
mm mm mm mm m m kg m続/h dBA
3.0 (1) / 2.75 (2) / 2.5 (3) 1.0 76 3,100 53
mm
9.52/16.0
BN: RAL9010 / SN: RAL9006 370/370/370 1,500/1,500/1,548 2,000/2,000/2,048 2,500/2,500/2,548 774/1,105/745 520 3.0 (1) / 2.75 (2) / 2.5 (3) 3.0 (1) / 2.75 (2) / 2.5 (3) 3.0 (1) / 2.75 (2) / 2.5 (3) 1.5 2.0 2.5 100 126 157 4,650 6,200 7,750 54 56 57 R-410A 9.52/19.0 9.52/22.0 Daikin wired remote control (BRC1E52A/B or BRC1D52) 230
1,000/1,000/1,048
V
(1) Favorable conditions: covered shopping mall or revolving door entrance (2) Normal conditions: little direct wind, no opposite open doors, building with ground floor only (3) Unfavorable conditions: location at a corner or square, multiple floors and/or open stairway
115
BIDDLE AIR CURTAINS
Large CYVL100DK125*BN/*SN
Integrated
ventilation Daikin offers a variety of solutions for the provision of fresh air ventilation to offices, hotels, stores and other commercial outlets â&#x20AC;&#x201C; each one complementary to and as flexible as the VRV system itself.
Heat Reclaim Ventilation Proper ventilation is a key component of climate control in buildings, offices and shops. In its basic function, it ensures a flow of incoming fresh air and outgoing stale air. Our HRV (heat reclaim ventilation) solution can do much more. It can recover heat and optimise the balance between indoor and outdoor temperature and humidity, thus reducing the load on the system and increasing efficiency.
Outdoor air processing in a single unit
Our FXMQ-MF air processing solution uses heat pump technology to combine fresh air treatment and air conditioning in a single system, thereby eliminating the usual design problems associated with balancing air supply and discharge. Total system cost is reduced and design flexibility enhanced because the airconditioning fan coil units and an outdoor air treatment unit can be connected to the same refrigerant line.
VRV air handling applications For medium and large commercial spaces, we offer a range of R-410A inverter condensing units that connect to air handling units. This approach combines the flexibility of our VRV units with Air Handling Applications, resulting in a simple, reliable design for optimum control of indoor air quality and maximum efficiency. For more information consult the Daikin ventilation catalogue or contact your local dealer.
116
Heat reclaim ventilation
Outdoor air processing unit
117
Heat reclaim ventilation
118
Outdoor air processing unit
122
Air handling applications
124
VENTILATION
VRV air handling applications
VAM-FA/FB Total heat exchanged foul air
Heat Reclaim Ventilation
››
Clean outdoor air
›› ›› ›› ››
Foul indoor air
›› ›› ›› ››
Total heat exchanged clean air
›› ›› ›› ››
Energy saving ventilation using indoor heating, cooling and moisture recovery Ideal solution for shops, restaurants or offices requiring maximum floor space for furniture, decorations and fittings Free cooling possible when outdoor temperature is below indoor temperature (eg. during nighttime) Low energy consumption thanks to DC inverter fans Prevent energy losses from over-ventilation while maintaining indoor air quality with optional CO2 sensor Can be used as stand alone unit or integrated in the VRV system Wide range of units: air flow rate from 150 up to 2,000 m³/h High efficiency filters available in F6 ,F7, F8 grades Shorter installation time thanks to easy adjustment of nominal air flow rate, so less need for dampers compared with traditional installations Specially developed heat exchange element with High Efficiency Paper (HEP) No drain piping needed Can operate in over- and under pressure Total solution for fresh air with Daikin supply of both VAM and electrical heater
High efficiencies filters available in F6, F7, F8 grades
Prevent energy losses from over ventilation with CO2 sensor Enough fresh air is needed to create an enjoyable environment, but ventilating constantly is leading to energy waste. Therefore an optional CO2 sensor can be installed which switches off the ventilation system when there is enough fresh air in the room, thus saving energy. CO2 level
Example of CO2 sensor operation in a meeting room:
9 AM
12 PM
Fixed ventilation rate Ventilation amount
5 PM
Decrease in air volume and more energy saving compared to fixed ventilation rate Increase in air volume and better comfort compared to fixed ventilation rate
7
8
9
10
Morning meeting
When many people are in the room, more fresh air is brought in to maintain comfortable CO2 levels. When fewer people are in the room, energy is saved by bringing in less fresh air.
11
12
13
14
Lunch time
15
16
17
18
19
hour
Meeting
Using CO2 sensors has the most energy-saving potential in buildings where occupancy fluctuates during a 24-hour period, is unpredictable and peaks at a high level. For example office buildings, government facilities, retail stores and shopping malls, movie theaters, auditoriums, schools, entertainment clubs and nightclubs. The ventilation unit's reaction to fluctuations in CO2 can be easily adjusted by the customer.
118
Heat recovery ventilation
High Efficiency Paper OUTDOOR Operation of the high effiency paper.
INDOOR
30.6°C 62% RH
Cross flow of air to exchange heat and moisture.
32°C 70% RH
SA 27.4°C 63% RH
RA 26°C 50% RH
Integrally-formed liner
Temperature and humidity is exhanged between the layers
SA Integrallyformed liner RA
RH: Relative Humidity SA: Supply Air (to room) RA: Return Air (from room)
Heat exchange mode Nom. Ultra high Ultra high Bypass mode Nom. Temperature exchange efficiency - 50Hz Ultra high Ultra high Enthalpy exchange Cooling efficiency - 50Hz Heating Ultra high Operation mode Heat exchange system Heat exchange element Dimensions Unit HeightxWidthxDepth Weight Unit Fan-Air flow rate Heat exchange mode Ultra high - 50Hz Bypass mode Ultra high Fan-External static pressure - 50Hz Ultra high Heat exchange mode Ultra high Sound pressure level - 50Hz Bypass mode Ultra high Min. Operation range Max. Relative humidity Connection duct diameter Power supply Phase/Frequency/Voltage Current Maximum fuse amps (MFA)
kW kW % % %
mm kg m³/h m³/h Pa dBA dBA °CDB °CDB % mm Hz/V A
VAM150FA 0.116 0.116 74
VAM250FA 0.141 0.141 72
VAM350FB VAM500FB VAM650FB VAM800FB VAM1000FB VAM1500FB VAM2000FB 0.132 0.178 0.196 0.373 0.375 0.828 0.852 0.132 0.178 0.196 0.373 0.375 0.828 0.852 75 74 75 58 61 58 60 61 64 65 62 63 65 66 Heat exchange mode / Bypass mode / Fresh-up mode Air to air cross flow total heat (sensible + latent heat) exchange Specially processed non-flammable paper 285x776x525 301x828x816 364x1,004x868 364x1,004x1,156 726x1,512x868 726x1,512x1,156 24 33 52 55 64 131 152 150 250 350 500 650 800 1,000 1,500 2,000 150 250 350 500 650 800 1,000 1,500 2,000 69 64 98 93 137 157 137 27 / 28.5 28 / 29 32 33 34.5 36 39.5 40 27 / 28.5 28 / 29 32 33.5 34.5 36 40.5 40 -15 50 80% or less 100 150 200 250 350 1~/50/60/220-240/220 15 16
Total solution for fresh air with Daikin supply of both VAM and electrical heaters Increased comfort in low outdoor temperature thanks to the heated outdoor air Integrated electrical heater concept (no additional accessories required) Standard dual flow and temperature sensor Flexible setting with adjustable setpoint Increased safety with 2 cut-outs: manual & automatic BMS integration thanks to: • Volt free relay for error indication • 0-10VDC input for setpoint control ›› Capacities ranging from 1 to 2.5 kW
VENTILATION
VENTILATION Power input - 50Hz
›› ›› ›› ›› ›› ››
119
VH electrical heater
VKM-GM / VKM-G
Heat Reclaim Ventilation, humidification and air processing ›› ›› ›› ›› ›› ›› ›› ›› ›› ››
Energy saving ventilation using indoor heating, cooling and moisture recovery Creates a high quality indoor environment by pre conditioning incoming fresh air Humidification of the incoming air results in comfortable indoor humidity level, even during heating Ideal solution for shops, restaurants or offices requiring maximum floor space for furniture, decorations and fittings Free cooling possible when outdoor temperature is below indoor temperature (eg. during nighttime) Low energy consumption thanks to DC fan motor Prevent energy losses from over-ventilation while maintaining indoor air quality with optional CO2 sensor Shorter installation time thanks to easy adjustment of nominal air flow rate, so less need for dampers compared with traditional installation. Specially developed heat exchange element with High Efficiency Paper (HEP) Can operate in over- and under pressure
Operation example: humidification & air processing (heating mode)1
Exhaust Fan EA (Exhaust air to outdours)
Heat Exchanger Elements
Damper Motor Damper
DX coil (Direct expansion coil)
OA (Fresh air from outdoors)
RA (Return air from room)
Air Supply Fan
SA (Supply air to room)
Electronics Box (Control box)
Float switch
Humidifier element: Utilizing the principle of capillary action, water is permeated throughout the humidifier element. The heated air from the DX coil passes through the humidifier and absorbs the moisture.
water
AIRFLOW
Drain pan 1
Solenoid valve
VKM-GM example
120
Drain
SA
VKM-GM example
Heat recovery ventilation, humidification & air processing
Heat reclaim ventilation, air processing and humidication kW kW kW kW % % %
mm kg m³/h m³/h Pa dBA dBA °CDB °CDB °CDB °CDB °CDB mm mm mm mm
Hz/V A
Heat reclaim ventilation and air processing
VKM50GBM 0.270 0.270 4.71 / 1.91 / 3.5 5.58 / 2.38 / 3.5 76/76/77.5 64/64/67 67/67/69
VKM80GBM VKM100GBM VKM50GB VKM80GB VKM100GB 0.330 0.410 0.270 0.330 0.410 0.330 0.410 0.270 0.330 0.410 7.46 / 2.96 / 5.6 9.12 / 3.52 / 7.0 4.71 / 1.91 / 3.5 7.46 / 2.96 / 5.6 9.12 / 3.52 / 7.0 8.79 / 3.79 / 5.6 10.69 / 4.39 / 7.0 5.58 / 2.38 / 3.5 8.79 / 3.79 / 5.6 10.69 / 4.39 / 7.0 78/78/79 74/74/76.5 76/76/77.5 78/78/79 74/74/76.5 66/66/68 62/62/66 64/64/67 66/66/68 62/62/66 71/71/73 65/65/69 67/67/69 71/71/73 65/65/69 Heat exchange mode / Bypass mode / Fresh-up mode Air to air cross flow total heat (sensible + latent heat) exchange Specially processed non-flammable paper Natural evaporating type Galvanised steel plate 387x1,764x832 387x1,764x1,214 387x1,764x832 387x1,764x1,214 100 119 123 94 110 112 500 750 950 500 750 950 500 750 950 500 750 950 200 205 110 210 150 38 40 39 41.5 41 39 41 40 41.5 41 0°C~40°CDB, 80% RH or less -15°C~40°CDB, 80% RH or less 0°C~40°CDB, 80% RH or less -15 43 R-410A 200 250 200 250 6.35 12.7 6.4 PT3/4 external thread Multidirectional fibrous fleeces 1~/50/220-240 15
121
VENTILATION
VENTILATION Ultra high Power input - 50Hz Heat exchange mode Nom. Ultra high Bypass mode Nom. Fresh air Cooling conditioning load Heating Temperature exchange efficiency - 50Hz Ultra high/High/Low Ultra high/High/Low Enthalpy exchange Cooling efficiency - 50Hz Heating Ultra high/High/Low Operation mode Heat exchange system Heat exchange element Humidifier System Casing Material HeightxWidthxDepth Dimensions Unit Weight Unit Fan-Air flow rate Heat exchange mode Ultra high - 50Hz Bypass mode Ultra high Fan-External static pressure - 50Hz Ultra high Heat exchange mode Ultra high Sound pressure level - 50Hz Bypass mode Ultra high Operation range Around unit Supply air Return air On coil Cooling Max. temperature Heating Min. Refrigerant Type Connection duct diameter Piping Liquid OD connections Gas OD Water supply Drain Air filter Type Power supply Phase/Frequency/Voltage Current Maximum fuse amps (MFA)
FXMQ-MF
Outdoor Air Processing Unit, ventilation and air processing
Combined fresh air treatment and air conditioning via a single system ›› ›› ›› ›› ››
1
100% fresh air intake possible Leaves maximum floor and wall space for furniture, decorations and fittings Operation range: -5°C to 43°C 225 Pa external static pressure allows extensive ductwork runs and flexible application: ideal for use in large areas Drain pump kit available as accessory
Not connectable to VRVIII-S (RXYSQ-P8V1, RXYSQ-PBY1)
122
Ventilation and air processing in one system
Piping connections Power supply
Nominal Nominal HeightxWidthxDepth
Nominal Nominal (220V) Cooling max. Heating min. OD OD
Liquid Gas Drain Phase / Frequency / Voltage
kW kW kW kW mm kg m3/min m3/min Pa dBA dBA 째CDB 째CDB mm mm
FXMQ125MF 14.0 8.9 0.359 0.359 470x744x1,100 86 18 185
FXMQ200MF 22.4 13.9 0.548 0.548
FXMQ250MF 28.0 17.4 0.638 0.638 470x1,380x1,100 123
28 225 R-410A -
42
35 205
47 43 -5 9.52 19.1 PS1B 1~ / 50 / 220-240
15.9
Hz / V
123
22.2
VENTILATION
VENTILATION & AIR PROCESSING Cooling capacity Nom. Heating capacity Nom. Power Input Cooling (50Hz) Heating Dimensions Unit Weight Unit Air Flow Rate Cooling Heating External Static Pressure Standard Refrigerant Type Sound Power Cooling Sound Pressure Cooling Operation range On coil temperature
Daikin Air handling unit Wide range of air flows In situations where the Daikin commercial range of ventilation units cannot satisfy the ventilation requirement due to building constraints (large atriums, banquet halls, etc) air handling units represent the ideal solution. Daikin’s wide range of air handling systems handle air flow rates from 500 m³/h up to 140,000 m³/h. The air handler unit can be adapted to deliver whatever air flow you require, via the specific dimensions of flow section available at the installation.
Air flow (m3/h * 1000)
0
15
30
45
60
75
90
105
120
135
The most flexible solution D-AHU Professional
Daikin AHU Range
1,100 m3/h
D-AHU Energy
up to 140,000 m3/h
Best seasonal performance and return on investment
1,500 m3/h
up to 70,000 m3/h
Ideal to cover your basic AHU needs
D-AHU Easy 500 m3/h
up to 30,000 m3/h
Daikin fresh air package - plug & play The D-AHU Professional and Energy series provide a complete solution including unit control (EKEXV, EKEQ, DDC controller) factory mounted and configured, plug & play with our ERQ and VRV condensing units. The easiest solution as you save time and only have one point of contact!
Return on investment The air handling unit (AHU) is critical to an effective climate control system and, although the initial investment can appear high, the savings generated by our advanced designs and operating efficiencies guarantee a rapid return on the investment made. Our AHU Energy series has been designed to deliver exceptional performance thus driving down the energy consumed and so lowering energy bills. Taken over the expected 15-year life-span of the equipment, this will result in a substantial saving, especially in a time of ever increasing energy prices.
124
Pre-defined sizes
VENTILATION
27 fixed sizes are available, optimized to reach the best compromise between competitiveness and manufacturing standardisation. However, Daikinâ&#x20AC;&#x2122;s section by section design means that units can be sized by 1cm increments and assembled on site, without welding, to suit the space constraints of the installation.
High efficiency components All Daikin air handlers have been designed for optimum energy efficiency. Polyurethane or Mineral wool panels guarantee excellent thermal insulation performance. Filters are provided with a large choice of efficiency filtration class.
125
Air handling unit applications
Why use ERQ and VRV condensing units for connection to air handling units? High Efficiency Daikin heat pumps are renowned for their high energy efficiency with COPs up to 4.56 in heating1. The VRV range offers both heat pump and heat recovery units with part load efficiencies as high as 9.02. Integrating the AHU with a heat recovery system is highly effective since an office system can frequently be in cooling mode while the outdoor air is too cold to be brought inside in an unconditioned state. In this case heat from the offices is merely transferred to heat up the cold incoming fresh air. In the absence of an AHU this ‘free heating’ the incoming fresh air would not be possible. 1 ERQ100AV1 heat pump 2 REYQ8P8 50% cooling - 50% heating load. Conditions: outdoor temperature 11°CDB, indoor temperature 18°CWB, 22°CDB
Fresh air supplied at 21°C. The temperature difference with the outdoor air is heated up for free by heat recovery via A/C system
Outside air = 10°C
Indoor temperature 22°C, needs cooling because of solar radiation. The excessive heat can be transferred to the AHU.
High comfort levels Daikin ERQ and VRV units respond rapidly to fluctuations in supply air temperature, resulting in a steady indoor temperature and resultant high comfort levels for the end user. Daikin ERQ and VRV units respond rapidly to fluctuations in the supply air temperature, resulting in a steady indoor temperature, together with the dehumidification this results in high comfort levels for the end user. The ultimate is the VRV range which improves comfort even more by offering continuous heating, also during defrost.
Easy Design and Installation The system is easy to design and install since no additional water systems such as boilers, tanks and gas connections etc. are required. This also reduces the total system cost.
126
Flexible control possibilities for air handling units In order to maximize installation flexibility, 3 types of control systems are offered Control x: Control of air temperature
(discharge temperature, suction temperature, room temperature) via external device (DDC controller)
Control y: Control of evaporating temperature via Daikin control (no DDC controller needed) Control z: Control of air temperature (suction temperature, room temperature) via Daikin control (no DDC controller needed)
Possibility X (Td/Tr control): Air temperature control via DDC controller
Ts
Room temperature is controlled as a function of the air handling unit suction or discharge air (customer selection). The DDC controller is translating the temperature difference between set point and air suction temperature (or air discharge temperature or room temperature) into a reference voltage (0-10V) which is transferred to the Daikin control box (EKEQFCBA). This reference voltage will be used as the main input value for the compressor frequency control.
Te
Daikin control box: EKEQFCB
DDC
Td
AHU Tr
Room
Possibility Y (Te/Tc control): By fixed evaporating temperature A fixed target evaporating temperature of between 3°C and 8°C can be set by the customer. In this case, room temperature is only indirectly controlled. The cooling load is determined from the actual evaporating temperature (i.e. load to the heat exchanger). A Daikin infrared remote control (BRC1D52 or BRC1E52A/B - optional) can be connected for error indication.
Daikin control box: EKEQFCB
KRP4A51 Ts Daikin control box: EKEQDCB EKEQMCB
Set point can be fixed via standard Daikin infrared remote control. Remote ON/ OFF can be achieved by an optional adapter KRP4A51. No external DDC controller should be connected. The cooling load is determined from the air suction temperature and set point on the Daikin controller.
EKEQFCB
Possibility z
FEATURES DDC controller is required Temperature control using air suction or air discharge temperature
Using Daikin infrared remote control BRC1D52 or BRC1E52A/B Temperature control using air suction temperature
* EKEQMCB (for ’multi’ application)
127
Td
Tr
Room
VENTILATION
= Air suction temperature = Air discharge temperature = Room temperature = Evaporating temperature = Air Handling Unit = Digital Display Controller
Using fixed evaporating temperature, no set point can be set using remote control EKEQDCB EKFQMCB*
Te AHU
BRC1D52 BRC1E52A/B Ts Td Tr Te AHU DDC
Possibility y
Td Room
ON / OFF
Using Daikin infrared remote control (BRC1D52 or BRC1E52A/B - optional)
Possibility x
Tr
BRC1D52 BRC1E52A/B
Possibility Z (Ts/Tr control):
OPTION KIT
AHU Te
Ts
VRV
Air handling application (pair & multi)
A R-410A inverter condensing units range for multi application with air handling units ›› ›› ›› ›› ›› ›› ›› ››
Inverter controlled units Large capacity range (from 8 to 54HP) Heat recovery, heat pump R-410A Control of room temperature via Daikin control Large range of expansion valve kits available BRC1E52A/B is used to set the set point temperature (connected to the EKEQMCB). Connectable to all VRV heat recovery and heat pump systems
Different control possibilities VRV IV heat pump
Control possibilities
VRV heat recovery
VRV III-S
VRV III-C
VRV IV W-series
R*YQ8-10T
R*YQ12-30T
4 x R*YQ8T 4 x R*YQ10T
R*YQ52-54T
REYQ-T REYHQ-P8/P9 REYHQ-P REYAQ-P
RXYSQ-PAV RXYSQ-PAY
RTSYQ-PA
RWEYQ-T
X
P
P1
P2
-
-
-
-
-
Y
P
P1
P2
-
-
-
-
-
Z
M
M
M
M
M
M
M
M
P = pair M = multi 1 By use of split coil (interlaced) 2 Separate coil per outdoor unit
128
X,Y control for VRV IV R*YQ8-10T
4 x R*YQ8T 4 x R*YQ10T
R*YQ12-30T
VENTILATION
Z control for all VRV outdoor units
Refrigerant piping F1-F2 other communication
129
ERQ
Air handling application (pair)
A range of R-410A inverter condensing units for pair application with air handling units ›› ›› ›› ›› ›› ››
Inverter controlled units Large capacity range (from 100 to 250 class) Heat pump R-410A Wide range of expansion valve kits available Up to 4 ERQ units can be connected to an interlaced coil in one air handling unit
F1 - F2 Refrigerant piping
The “Daikin Fresh Air Package” provides a complete Plug & Play Solution including AHU, ERQ or VRV Condensing Unit and all unit control (EKEQ, EKEX, DDC controller) factory mounted and configured. The easiest solution with only one point of contact.
VENTILATION Capacity range Cooling capacity Heating capacity Power input
Nom. Nom. Cooling Heating
EER COP Dimensions Weight Fan-Air flow rate
Power supply Current
VENTILATION Capacity range Cooling capacity Heating capacity Power input EER COP Dimensions Weight Fan-Air flow rate
Power supply Current
ERQ125AV1 5 14.0 16.0 3.51 3.86
ERQ140AV1 6 15.5 18.0 4.53 4.57 3.42 3.94
3.99 HeightxWidthxDepth Nom. Nom. Nom. Nom. Nom. Min./Max. Min./Max. Heating Min. Cooling Max.
mm kg m³/min m³/min dBA dBA dBA °CDB °CWB °CDB °CDB
Type Liquid OD Gas OD Drain OD Phase/Frequency/Voltage Maximum fuse amps (MFA)
mm mm mm Hz/V A
Nom. Nom. Cooling Heating
HP kW kW kW kW
Unit Unit Cooling Heating Sound power level Nom. Sound pressure level Nom. Operation range Cooling Heating On coil temperature Refrigerant Piping connections
ERQ100AV1 4 11.2 12.5 2.81 2.74 4.56
Unit Unit Cooling Heating Sound power level Cooling Sound pressure Cooling level Heating Operation range Cooling Heating On coil temperature Refrigerant Piping connections
Nom. Nom.
HP kW kW kW kW
Nom. Nom.
HeightxWidthxDepth Nom. Nom.
Min./Max. Min./Max. Heating Min. Cooling Max.
Type Liquid OD Gas OD Phase/Frequency/Voltage Maximum fuse amps (MFA)
mm kg m³/min m³/min dBA dBA °CDB °CWB °CDB °CDB mm mm Hz/V A
4.15 1,345x900x320 120 106
102 66 50 52
105 67 51 53 -5/46 -20/15.5 10 35 R-410A 9.52
69 53 55
15.9
19.1 26x3 1N~/50/220-240 32.0
ERQ125AW1 5 14.0 16.0 3.52 4.00 3.98 4.00 1,680x635x765 159 95 95 72 54
15.9 16
ERQ200AW1 8 22.4 25.0 5.22 5.56 4.29 4.50
ERQ250AW1 10 28.0 31.5 7.42 7.70 3.77 4.09 1,680x930x765
187 171 171
240 185 185 78
57 -5/43 -20/15 10 35 R-410A 9.52 19.1 3N~/50/400
58
22.2 25
130
Overview of expansion valves and control boxes Daikin also offers a range of expansion valve kits and control boxes to connect ERQ and VRV condensing units to third party air handling units VRV combination table EKEXV CLASS
ALLOWED HEAT EXCHANGER CAPACITY (KW) COOLING (EVAPORATION TEMPERATURE 6°C) HEATING (CONDENSING TEMPERATURE 46°C) MINIMUM STANDARD MAXIMUM MINIMUM STANDARD MAXIMUM 5.0 5.6 6.2 5.6 6.3 7.0 6.3 7.1 7.8 7.1 8.0 8.8 7.9 9.0 9.9 8.9 10.0 11.1 10.0 11.2 12.3 11.2 12.5 13.8 12.4 14.0 15.4 13.9 16.0 17.3
50 63 80 100 125 140 200 250
15.5 17.7 24.7
16.0 22.4 28.0
17.6 24.6 30.8
17.4 19.9 27.8
18.0 25.0 31.5
19.8 27.7 34.7
ERQ combination table OUTDOOR UNIT
1~
3~
ERQ100AV1 ERQ125AV1 ERQ140AV1 ERQ125AW1 ERQ200AW1
CLASS 63 EKEXV63 P P P -
CLASS 80 EKEXV80 P P P P -
CLASS 100 EKEXV100 P P P P P
EXPANSION VALVE KIT CLASS 125 EKEXV125 P P P P P
CLASS 140 EKEXV140 P P P P
CLASS 200 EKEXV200 P
CLASS 250 EKEXV250 P
ERQ250AW1
-
-
-
P
P
P
P
P: Pair: Combination depending on air handling units coils volume.
EKEXV - Expansion valve kit for air handling applications VENTILATION Dimensions Weight Sound pressure level Operation range Refrigerant Piping connections
EKEXV50 Unit Unit Nom. On coil temperature Type Liquid Gas
HeightxWidthxDepth
Heating Min. Cooling Max.
mm kg dBA °CDB °CDB
OD OD
mm mm
EKEXV63
EKEXV80
6.35 6.35
EKEXV100 EKEXV125 401x215x78 2.9 45 10 (1) 35 (2) R-410A 9.52 9.52
EKEXV140
EKEXV200
EKEXV250
VENTILATION
(1) The temperature of the air entering the coil in heating mode can be reduced to -5°CDB. Contact your local dealer for more information. (2) 45% Relative humidity.
EKEQ - Control box for air handling applications VENTILATION Application Outdoor unit Dimensions Weight Power supply
EKEQFCB
EKEQDCB
EKEQMCB Multi VRV
Pair ERQ Unit HeightxWidthxDepth Unit Phase/Frequency/Voltage
mm kg Hz/V
132x400x200 3.9
3.6 1~/50/230
131
User friendly
control systems
An air conditioning system will only operate as efficiently as its control system allows and the importance of precise, user friendly equipment is as relevant to simple residential room temperature controls as it is to full remote monitoring and regulation of large scale commercial buildings. In buildings with multiple air conditioning units that operate for long hours, system efficiency plays a paramount role in the pursuit of reduced energy consumption. Maximum efficiency demands that maximum control of all aspects of system operation must be in harmony with important allied considerations such as round the clock monitoring, preventive maintenance, fault predictive analysis and rapid response in the event of malfunctions.. Daikin manufactures and markets an extensive portfolio of state of the art computerised control systems that offer building owners, landlords and tenants comprehensive system cover backed up by vital data on operational performance and running costs on air conditioning systems of any size and complexity.
132
Control systems Individual control systems Wired / infrared remote control
134 134
Remote monitoring and maintenance 146 ACNSS (Air Conditioning Network Service System) 146
Centralised control systems 136 Centralised remote control / Unified ON/OFF control / Schedule timer 136 137 137 Mini BMS 138 138
148
Wireless room temperature sensor Wired room temperature sensor Other integration devices
149 149 150
CONTROL SYSTEMS
Communication interfaces 140 Modbus interface 140 KNX Interface 142 144 145
Daikin configurator software
133
BRC1E52A/B
User friendly remote control with contemporary design
Save energy
A series of energy saving functions that can be individually selected ›› ›› ›› ›› ›› ››
Temperature range limit Setback function Presence & floor sensor connection (available on new round flow cassette) kWh indication Set temperature auto reset Off timer
Temperature range limit avoids excessive heating or cooling Save energy by constraining the lower temperature limit in cooling and upper temperature limit in heating mode. note : Also available in auto cooling/heating change over mode.
kWh indication keeps track of your consumption The kWh indication shows an indicative electricity consumption of the last day/month/year.
Other functions ›› ›› ›› ›› ›› ›› ››
Up to 3 independent schedules can be set, so the user can easily change the schedule himself throughout the year (e.g. Summer, winter, mid-season) Possibility to individually restrict menu functions Easy to use: all main functions directly accessible Easy setup: clear graphical user interface for advanced menu settings Real time clock with auto update to daylight saving time Built-in backup power: when a power failure occurs all settings remain stored up to 48 hours Supports multiple languages -- English, German, Dutch, Spanish, Italian, Portuguese, French, Greek, Russian, Turkish, Polish (BRC1E52A) -- English, German, Czech, Croatian, Hungarian, Romanian, Slovenian, Bulgarian, Slovak, Serbian, Albanian (BRC1E52B)
Graphical display of indicative electricity consumption 134
ARC*/BRC*
BRC1D52
Individual control systems
BRC944B2
ARC466A1
BRC4*/BRC7*
BRC944B2*/BRC1D52 Wired remote control
Display
››
›› ›› ›› ›› ›› ›› ›› ›› ›› ›› ›› ›› ››
›› ›› ›› ›› ››
Schedule timer: • Five day actions can be set as follows: -- set point: unit is switched ON and normal operation is maintained -- OFF: unit is switched OFF1 -- limits: unit is switched ON and min./max. control (cf. limit operation for more details) Home leave (frost protection): during absence, the indoor temperature can be maintained at a certain level. This function can also switch the unit ON/OFF User friendly HRV function, thanks to the introduction of a button for ventilation mode and fan speed Constantly monitoring of the system for malfunctions in a total of 80 components Immediate display of fault location and condition Reduction of maintenance time and costs
Operating mode1 Heat Recovery Ventilation (HRV) in operation Cool / heat changeover control Centralised control indication Group control indication Set temperature1 Air flow direction1 Programmed time Inspection test / operation Fan speed1 Clean air filter Defrost / hot start Malfunction 1
Only functions marked with ‘1’ are available on BRC944B2
ARC4*/BRC4*/BRC7* Infrared remote control
Operation buttons: ON / OFF, timer mode start / stop, timer mode on / off, programme time, temperature setting, air flow direction (1), operating mode, fan speed control, filter sign reset (2), inspection (2)/ test indication (2) Display: Operating mode, battery change, set temperature, air flow direction (1), programmed time, fan speed, inspection / test operation (2) 1. 2. 3.
Not applicable for FXDQ, FXSQ, FXNQ, FBDQ, FDXS, FBQ For FX** units only For all features of the remote control, refer to the operation manual
NEW BRC2E52A / BRC3E52A
›› ›› ›› ›› ›› ›› ›› ››
Symbol driven interface for intuitive control Functions restricted to basic customer needs Contemporary design Energy saving thanks to set point limitation Flat backpanel for easy installation 2 versions available: • Heat pump type: temperature, fan speed, ON/OFF • Heat recovery type: temperature, mode, fan speed, ON/OFF Replaces existing BRC2C51 & BRC3A61 Available spring 2014
135
CONTROL SYSTEMS
Simplified wired remote control developed for hotel applications
Centralised control systems
DCS302C51
DCS301B51
DST301B51
Centralised control of the Sky Air and VRV system can be achieved via 3 user friendly compact controls: centralised remote control, unified on/off control and schedule timer. These controls may be used independently or in combination where 1 group = several (up to 16) indoor units in combination and 1 zone = several groups in combination. A centralised remote control is ideal for use in tenanted commercial buildings subject to random occupation, enabling indoor units to be classified in groups per tenant (zoning). The schedule timer programmes the schedule and operation conditions for each tenant and the control can easily be reset according to varying requirements.
DCS302C51
DCS301B51
DST301B51
Providing individual control of 64 groups (zones) of indoor units.
Providing simultaneous and individual control of 16 groups of indoor units.
Enabling 64 groups to be programmed.
• a maximum of 64 groups (128 indoor units, max. 10 outdoor units) can be controlled • a maximum of 128 groups (128 indoor units, max. 10 outdoor units) can be controlled via 2 centralised remote controls in separate locations • zone control • group control • malfunction code display • maximum wiring length of 1,000m (total: 2,000m) • air flow direction and air flow rate of HRV can be controlled • expanded timer function
• a maximum of 16 groups (128 indoor units) can be controlled • 2 remote controls in separate locations can be used • operating status indication (normal operation, alarm) • centralised control indication • maximum wiring length of 1,000m (total: 2,000m)
• a maximum of 128 indoor units can be controlled • 8 types of weekly schedule • a maximum of 48 hours back up power supply • a maximum wiring length of 1,000m (total: 2,000m)
Centralised remote control
Unified ON/OFF control
136
Schedule timer
DTA113B51 Basic solution for control of Sky Air and VRV ›› ››
DS-NET adapter DTA113B51
Rotation function Backup operation function.
BRC1D52
Up to 4 units / 1 adapter
DCS601C51 Detailed & easy monitoring and operation of VRV systems (max. 64 indoor units groups). Public line
third party controller (domotics, BMS, etc.) Fire alarm
Onboard modem
Ethernet
Forced OFF contact input
Air conditioning Network Service System
DIII-NET
Indoor units
HRV
DCS601C51
Languages
Control
Monitoring
Open interface
›› ›› ›› ›› ›› ›› ››
››
››
››
System layout ›› ››
Up to 64 indoor units can be controlled Touch panel (full colour LCD via icon display)
Management ›› ››
Easy management of electricity consumption Enhanced history function
›› ›› ›› ›› ›› ›› ›› ›› ›› ›› ›› ›› ››
Individual control (set point, start/stop, fan speed) (max. 64 groups/indoor units) Set back shedule Enhanced scheduling function (8 schedules, 17 patterns) Flexible grouping in zones Yearly schedule Fire emergency stop control Interlocking control Increased HRV monitoring and control function Automatic cooling / heating change-over Heating optimization Temperature limit Password security: 3 levels (general, administration & service) Quick selection and full control Simple navigation
›› ›› ›› ››
Visualisation via Graphical User Interface (GUI) Icon colour display change function Indoor units operation mode Indication filter replacement Multi PC
Cost performance ›› ›› ›› ›› ››
137
Free cooling function Labour saving Easy installation Compact design: limited installation space Overall energy saving
Communication to any third party controller (domotics, BMS, etc.) is possible via open interface (http option)
Connectable to
›› ›› ›› ››
VRV HRV Sky Air Split (via interface adapter)
CONTROL SYSTEMS
English French German Italian Spanish Dutch Portuguese
New
Management control 99 Cost competitive mini BMS 99 Cross-pillar integration of Daikin products 99 Integration of third party equipment
Full integration across all product pillars System overview iTM Integrator (DCM601A53)
Up to 2,560 groups
HUB
A maximum of 5 intelligent Touch Managers can be connected to a single iTM Integrator.
Integration of third party equipment
Di/Pi line Max. 200m
Fire alarm
Full control of Daikin HVAC-R portfolio
internet intranet LAN
Web Access
3G iTM plus adaptor line
Max. 7 adapters
DCM601A51 DCM601A52 Di/Pi port
kWh meter
Direct plug & play connection!
Lighting
Pump
Chillers and AHU
Split indoor units, air curtain
I/O module
WAGO interface
indoor units, air curtain, hydrobox
Fan Refrigeration coil units
I/O module
BACnet protocol
Fan
138
W NE
NE
Sensor
W
I/O module
NE
W
USB memory
DCM601A51 User friendliness ›› ›› ››
Intuitive user interface Visual lay out view and direct access to indoor unit main funtions All functions direct accessible via touch screen or via web interface
Smart energy management ›› ›› ›› ››
Monitoring if energy use is according to plan Helps to detect origins of energy waste Powerful schedules guarantee correct operation throughout the year Save energy by interlocking A/C operation with other equiment such as heating
Flexibility ›› ›› ›› ››
BACnet protocol for 3rd party products integration I/O for integration of equipment such as lights, pumps… on WAGO modules Modular concept for small to large applications Control up to 2,560 indoor unit groups
Flexibility in size 64 up to 2,560 groups
Easy servicing and commissioning Remote refrigerant containment check preventing on site visit Simplified troubleshooting Save time on commissioning thanks to the pre-commissioning tool Auto registration of indoor units
Functions overview
System layout
WAGO Interface
››
››
››
Up to 2,560 unit groups can be controlled (ITM plus Integrator + 7 iPU (incl. iTM adaptor) Ethernet TCPIP
Management ›› ›› ›› ››
DCM601A51
Languages ›› ›› ›› ›› ›› ›› ››
English French German Italian Spanish Dutch Portuguese
›› ››
Web access Power Proportional Distribution (option) Operational history (malfunctions, operation hours, …) Smart energy management - monitor if energy use is according to plan - detect origins of energy waste Setback function Sliding temperature
Control ›› ›› ›› ›› ››
Individual control (2,560 groups) Schedule setting (Weekly schedule, yearly calender, seasonal schedule) Interlock control Setpoint limitation Temperature limit
139
Modular integration of 3rd party equipment - WAGO coupler (interface between WAGO and Modbus) - Di module - Do module - Ai module - Thermistor module
Connectable to ›› ›› ›› ›› ›› ›› ›› ›› ››
DX Split, Sky Air, VRV Chillers (with Microtech controller) Daikin AHU Fan coils Daikin Altherma Flex type LT and HT hydroboxes Air curtains WAGO I/O BACnet protocol
CONTROL SYSTEMS
›› ›› ›› ››
RTD
Modbus Interface
Integration of RA, Sky Air, VRV, Daikin Altherma Flex and AHU in BMS or home automation systems
RTD-RA
RTD-20
››
›› ›› ››
Modbus interface for monitoring and control of residential indoor units
RTD-NET ››
››
Modbus interface for monitoring and control of Sky Air, VRV, VAM and VKM
Advanced control of Sky Air, VRV, VAM/VKM and air curtains Clone or independent zone control Increased comfort with integration of CO2 sensor for fresh air volume control Save on runningcosts via - pre/post and trade mode - set point limitation - overall shut down - PIR sensor for adaptive deadband
RTD-10
RTD-HO
››
››
››
Advanced integration into BMS of Sky Air, VRV, VAM and VKM through either: -- Modbus -- Voltage (0-10V) -- Resistance Duty/standby function for server rooms
›› ››
RTD-W ››
RTD-LT ››
››
Modbus interface for monitoring and control of Sky Air, VRV, VAM and VKM Intelligent hotel room controller
Modbus interface for monitoring and control of Daikin Altherma low temperature (EHVH(X)-C / EHBH(X)-C) Voltage and resistance control Photovoltaic operation signal for energy saving
140
Modbus interface for monitoring and control of Daikin Altherma Flex Type, VRV HT hydrobox and small inverter chiller
Overview functions MAIN FUNCTIONS Dimensions HxWxD mm On/off prohibition Key card + window contact Set back function Prohibit or restrict remote control functions (setpoint limitation, ...) Modbus (RS485) Dry contact control Group control 0 - 10 V control Resistance control IT application Heating interlock Output signal (on/defrost, error) Space heating / cooling operation Domestic hot water control Retail application Partitioned room control Air curtain Smart grid control
RTD-RA 80 x 80 x 37,5
RTD-NET
RTD-10
RTD-20 RTD-HO 100 x100 x 22
(1)
***
***
**
****
RTD-W
RTD-LT/CA
(1): By combining RTD-RA devices RTD-RA M M
RTD-NET M M
RTD-10 M,V,R M,V,R
RTD-20 M M
RTD-HO M* M*
M M M
M M M M M
M,V,R M,V,R M,V,R M,V,R M,V,R
M M M M M
M* M* M*
M M
MONITORING FUNCTIONS RTD-RA On/Off M Room temperature setpoint M Set point leaving water temperature (heating/cooling) Operation mode M Domestic Hot Water reheat Domestic Hot Water storage Number of units stored in the group Average leaving water temperature Remocon room temperature fan M Louver M RC temperature RC mode nbr units Fault M Fault code M Circulation pump operation Flow rate Solar pump operation Compressor status Desinfection operation Setback operation Return air temperature (Average /Min/Max) M Filter alarm Termo on M Defrost Hot start Booster heater operation 3-way valve status Coil In/Out temperature M Pump running hours accumulated Compressor running hours accumulated Actual leaving water temperature Actual return water temperature Actual DHW tank temperature (*) Actual refrigerant temperature Actual outdoor temperature M : Modbus / R : Resistance / V : Voltage / C: Contact * : only when room is occupied / ** : setpoint limitation / (*) if available *** : no fan speed control on the CYV air curtain / **** : run & fault
RTD-W M,C M M,V M
RTD-LT/CA M,C,V,R M M,V,R M,V,R
M,C
M,V,R M M,V,R
M*
M M,C M M M RTD-NET M M
RTD-10 M M
RTD-20 M M
RTD-HO M M
M
M
M
M
M M M M M M M
M M M M M M M
M M M M M M M
M M M M M M M
M M M M
M M M M
M M M M
M M M M
M
M
M
M
RTD-W M,C M M M M M M
M,C M M M M M
RTD-LT/CA M,C M M M M M M
M,C M M,C M M M M
M
M M M M
M
M M M M M M M
M M M M
141
M M,C M M R M
CONTROL SYSTEMS
CONTROL FUNCTIONS On/Off Room temperature setpoint Set point leaving water temperature (heating / cooling) Operation mode fan Louver HRV Damper control Prohibit/Restrict functions Forced thermo off Domestic hot water On Domestic Hot Water reheat Domestic hot water reheat setpoint Domestic Hot Water storage Domestic hot water booster setpoint Quiet mode Weather dependent setpoint enable Weather dependent curve shift Fault/pump info relay choice Control source prohibition
KLIC-DD KLIC-DI
KNX interface
Integration of Split, Sky Air and VRV in HA/BMS systems Connect split indoor units to KNX interface for Home Automation system
Concept
light house Interface Daikin protocol/ KNX
Domotica Controller
shutter control tv
Connect Sky Air / VRV indoor units to KNX interface for BMS integration
Concept
light shop Interface Daikin protocol/ KNX
Domotica Controller
shutter control
tv
KNX interface line-up The integration of Daikin indoor units through the KNX interface allows monitoring and control of several devices, such as lights and shutters, from one central controller. One particularly important feature is the ability to programme a ‘scenario’ - such as “Home leave” - in which the end-user selects a range of commands to be executed simultaneously once the scenario is selected. For instance in “Home leave” , the air conditioner is off, the lights are turned off, the shutters are closed and the alarm is on.
KNX interface for KLIC-DD Size 90x60x35mm Split
KLIC-DI Size 45x45x15mm Sky Air
VRV
BASIC CONTROL ON/OFF Mode Temperature Fan speed levels Swing
Auto, heat, dry, fan, cool
3 or 5 + auto Stop or movement
ADVANCED FUNCTIONALITIES Error management Scenes Auto switch off Temperature limitation Initial configuration Master and slave configuration
142
Auto, heat, dry, fan, cool
2 or 3 Stop or movement
Communication errors, Daikin unit errors
Auto, heat, dry, fan, cool
2 or 3 Swing or fixed positions (5)
143
CONTROL SYSTEMS
BACnet Interface
Interfaces
Integrated control system for seamless connection between VRV, applied Systems, air handling units and BMS systems BMS
›› ›› ››
Interface for BMS system Communication via BACnet protocol (connection via Ethernet) Unlimited sitesize Easy and fast installation PPD data is available on BMS system (only for VRV)
VRV network DIII- NET BACNET / ETHERNET
›› ››
Local Control
DMS502A51
VRV Outdoor unit HRV
up to 256 units connectable per interface
Remote Control
Applied systems network
Serial Card BACnet MSTP
EKACBACMSTP
Serial sequencing panel
EKCM200J
EKCM200J
EKCM200J
EKDSSP-S
Air handling unit network
EKCMBACIP EKCMBACMSTP
Fire alarm
BUILDING CONTROL NETWORK
Pump
144
Security
Lighting
Power supply facility
Elevator
LonWorks Interface
Interfaces
Open network integration of VRV and applied systems monitoring and control functions into LonWorks networks
›› ››
VRV network LON BMS
adapter
DIII- NET
LonTalk
DMS504B51
Local Control VRV Outdoor unit
HRV
up to 64 units connectable per interface
Remote Control
Applied systems network
Serial card LON FTT 10
adapter
LonTalk EKACLONP
Serial sequencing panel
EKCM200J
EKCM200J
EKCM200J
EKDSSP-S
adapter
LonTalk LonPoint
BUILDING CONTROL NETWORK
Security
LonPoint
Fire alarm System
CONTROL SYSTEMS
››
Interface for Lon connection to LonWorks networks Communication via Lon protocol (twisted pair wire) Unlimited sitesize Quick and easy installation
ETHERNET (TCP/IP)
››
145
ACNSS Air Conditioning Network Service System (ACNSS) The challenge of your technical management is safeguarding in the long term optimal operation of your air conditioning system without incurring huge costs along the way. Daikin's Air Conditioning Network Service System improves the effectiveness of your management. The network service system is a link via the internet, between the air conditioning system and Daikin's Remote Monitoring Centre. In so doing, expert service engineers monitor the operating status of the entire system nonstop all through the year. The 'ACNSS monitoring service' prevents troubles and prolongs the life of your equipment.
Data
Thanks to the prediction of malfunctions and the technical advise following from data analysis, you not only maximise equipment availability, but also control cost without sacrificing comfort levels. Daikin's ACNSS is also supported by the optional 'ACNSS energy saving service' as energy use is one of the largest operating expenses of any business. This service enables you to optimise on power consumption without failing to keep the customer's amenity.
WWW.
146
ACNSS monitoringservice
ACNSS energy saving service
Comfort maintained 1â&#x20AC;&#x201A; Data transmission
2 â&#x20AC;&#x201A; Daikin Remote Monitoring Centre
Air conditioners's running information and other necessary data are collected and compiled, and sent to the centre. Advance failure forecasts and monitoring data for accidental problems are transmitted.
Daikin's control implemented
OPTION: energy-saving control determination Operating information is analyzed, and the optimum energy-saving control settings are calculated according to weather data for the region.
Weather information
Information to customers, service company
Reporting data is reviewed and system is monitored 24/7 for any occurances.
Energy-saving Report Maintenance Report Malfunction and prediction call
* A contract with Daikin is necessary for applying Energy-saving Air conditioning Network Service System. If you would like an estimation, please contact us.
147
CONTROL SYSTEMS
3â&#x20AC;&#x201A; Data analysis & system monitoring
Daikin Configurator Software
Simplified commissioning:
Simplified commissioning
graphical interface to configure, commission and upload system settings
The Daikin configurator for Daikin Altherma and VRV is an advanced software solution that allows for easy system configuration and commissioning: ›› Less time is required on the roof configuring the outdoor unit ›› Multiple systems at different sites can be managed in exactly the same way, thus offering simplified commissioning for key accounts ›› Initial settings on the outdoor unit can be easily retrieved
Simplified commissioning
Retrieve initial system settings
148
K.RSS
Wireless room temperature sensor
Flexible and easy installation ›› ››
Accurate temperature measurement thanks to flexible placement of the sensor No need for wiring
Connection diagram Daikin indoor unit PCB (FXSQ-P example) Power supply – X35, X13
Air sensor – X16A, X19 RF SENDER
RF RECEIVER
Specifications
WIRELESS ROOM TEMPERATURE SENSOR KIT (K.RSS) WIRELESS ROOM TEMPERATURE RECEIVER WIRELESS ROOM TEMPERATURE SENSOR
Dimensions
mm
Weight
g
Power supply Battery life Battery type Operation range
››
16VDC, max. 20 mA
N/A
N/A
+/- 3 years 10
°C
0~50
MHz
868.3
Type Frequency
3 Volt Lithium battery
m
RF
Room temperature is sent to the indoor unit every 90 seconds or if the temperature difference is 0.2°C or larger.
KRCS01-1B KRCS01-4B ››
ø 75 60
N/A
Maximum range
Communication
50 x 50 40
Wired room temperature sensor
Accurate temperature measurement,
CONTROL SYSTEMS
thanks to flexible placement of the sensor
Specifications Dimensions (HxW)
mm
Weight
g
60 x 50 300
Length of branch wiring
m
12
149
Other integration devices
Adapter PCB’s – Simple solutions for unique requirements Daikin’s adapter PCB’s provide simple solutions for unique requirements. They are a low cost option to satisfy simple control requirements and can be used on single or multiple units. (E)KRP1B* adapter for wiring
KRP2A*/KRP4A* Wiring adapter for electrical appendices
DTA104A* Outdoor Unit External Control Adapter
›› ››
Facilitates integration of auxiliary heating apparatus, humidifiers, fans, damper Powered by and installed at the indoor unit
›› ›› ›› ››
Remotely start and stop up to 16 indoor units (1 group) (KRP2A* via P1 P2) Remotely start and stop up to 128 indoor units (64 groups) (KRP4A* via F1 F2) Alarm indication/ fire shut down Remote temperature setpoint adjustment
›› ›› ››
Individual or simultaneous control of VRV system operating mode Demand control of individual or multiple systems Low noise option for individual or multiple systems
››
Allows integration of split units to Daikin central controls
›› ›› ›› ›› ››
Switch off auto restart after power failure Indication of operation mode / error Remotely start /stop Remotely change operation mode Remotely change fan speed
›› ›› ››
Connect a wired remote control Connect to Daikin central controls Allow external contact
KRP928* Interface adapter for DIII-net
KRP413* Wiring adapter normal open contact / normal open pulse contact
KRP980* Adapter for split units without an S21 port
Concept and benefits
›› ››
Low cost option to satisfy simple control requirements Deployed on single or multiple units
150
Option & accessories VRV outdoor
152
Option & accessories VRV indoor
154
Options & accessories Stylish indoor unit
158
Options & accessories Ventilation 162 164 OPTIONS & ACCESSORIES
Options - Control systems
151
Options & accessories outdoor
VRV IV with continuous heating
VRV IV without con 2-module systems
3-module systems
RYYQ8-12T
RYYQ14-20T
RYMQ8-12T
RYMQ14-20T
Multi-module connection kit (obligatory) - Connects multiple modules into a single refrigerant system
-
-
-
-
BHFQ22P1007
BHFQ22P1517
-
-
Extended level difference kit - Allows outdoor unit to be more than 50m above indoor units
-
-
-
-
-
-
-
-
Central drain pan kit - Installs onto the underside of the outdoor unit and collects drain water from all bottom plate outlets into a single outlet. In cold areas should be heated by a field-supplied heater to prevent drain water from freezing in the drain pan.
-
-
-
-
-
-
-
-
EKBPH012T* + EKBPHPCBT*
EKBPH020T* + EKBPHPCBT*
EKBPH012T* + EKBPHPCBT*
EKBPH020T* + EKBPHPCBT*
-
-
EKBPH012T* + EKBPHPCBT*
EKBPH020T* + EKBPHPCBT*
Heater tape kit - Optional electrical heater to guarantee trouble-free operation in extremely cold and humid climates External control adapter for outdoor unit - Allows to activate Low Noise Operation and three levels of Demand Limiting via external dry contacts. Connects to the F1/F2 communication line and requires power supply from an indoor unit*, BSVQ box, or VRVWIII outdoor unit.
RXYQ8-12T
RXYQ14-20T
For installation into an indoor unit: exact adapter type depends on type of indoor unit. See Options & Accessories of indoor units
BHGP26A1 - Digital pressure gauge kit – displays current condensing and evaporating pressures in the system as standard, or expansion valve positions and temperature sensor data in a special service mode. Connect to the outdoor unit PCB, for installation in the outdoor unit.
1 kit per system
1 kit per system
KRC19-26A - Mechanical cool/heat selector – allows to switch an entire Heat Pump system, or one BS-box of a Heat Recovery system between cooling, heating and fan only. Connects to the A-B-C terminals of the outdoor unit / BS-box.
BRP2A81 - Cool/heat selector PCB (required for VRV IV)
KKSA26A560* - Cool/heat selector PCB mounting plate (only required when cool/heat selector PCB and Heater tape kit are combined)
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
KJB111A - Installation box for remote cool/heat selector KRC19-26A EKPCCAB1 - VRV configurator BPMKS967B2B/B3B - Branch provider (for connection of 2/3 RA indoor units) KKPJ5F180 - Central drain plug DTA104A61/62* - Demand PCB allowing external input to limit power consumption KKSB2B61* - Demand PCB mounted plate. Needed to mount Demand PCB for some outdoor units.
-
-
VRV IV-Q Heat Pump Replacement VRV RQYQ 140
RXYQQ8-12T
RXYQQ14-20T
2-module systems
3-module systems
-
-
-
BHFQ22P1007
BHFQ22P1517
KWC26B160
-
-
-
-
-
EKBPH012T* + EKBPHPCBT*
EKBPH020T* + EKBPHPCBT*
-
-
Multi-module connection kit (obligatory) - Connects multiple modules into a single refrigerant system Central drain pan kit - Installs onto the underside of the outdoor unit and collects drain water from all bottom plate outlets into a single outlet. In cold areas should be heated by a field-supplied heater to prevent drain water from freezing in the drain pan. Heater tape kit - Optional electrical heater to guarantee trouble-free operation in extremely cold and humid climates External control adapter for outdoor unit - Allows to activate Low Noise Operation and three levels of Demand Limiting via external dry contacts. Connects to the F1/F2 communication line and requires power supply from an indoor unit*, BSVQ box, or VRVWIII outdoor unit.
DTA104A53/61/62 For installation into an indoor unit: exact adapter type depends on type of indoor unit. See Options & Accessories of indoor units
BHGP26A1 - Digital pressure gauge kit – displays current condensing and evaporating pressures in the system as standard, or expansion valve positions and temperature sensor data in a special service mode. Connect to the outdoor unit PCB, for installation in the outdoor unit.
1 kit per system
1 kit per system
KRC19-26A - Mechanical cool/heat selector – allows to switch an entire Heat Pump system, or one BS-box of a Heat Recovery system between cooling, heating and fan only. Connects to the A-B-C terminals of the outdoor unit / BS-box.
1 kit per system
1 kit per system
BRP2A81 - Cool/heat selector PCB (required for VRV IV)
-
KKSA26A560* - Cool/heat selector PCB mounting plate (only required when cool/heat selector PCB and Heater tape kit are combined)
-
-
1 kit per system
-
-
1 kit per system
-
-
-
KJB111A - Installation box for remote cool/heat selector KRC19-26A EKPCCAB1 - VRV configurator
-
DTA104A61/62* - Demand PCB allowing external input to limit power consumption KKSB2B61* - Demand PCB mounted plate. Needed to mount Demand PCB for some outdoor units.
Heat Pump systems (2-pipe)
Heat Recovery systems (3-pipe)
Refnet Joints
Metric-size connections Imperial-size connections
Capacity index
Capacity index
Capacity index
< 201
201~290
291~640
Capacity index > 640
KHRQM23M20T
KHRQM23M29T
KHRQM23M64T
KHRQM23M75T
KHRQ23M20T
KHRQ23M29T9
KHRQ23M64T
KHRQ23M75T
Sound reduction kit (sound insulation)
-
-
-
-
Mechanical cool/heat selector – allows to switch an entire Heat Pump system, or one BS-box of a Heat Recovery system between cooling, heating and fan only. Connects to the A-B-C terminals of the outdoor unit / BS-box.
-
-
-
-
Installation box for remote cool/heat selector KRC19-26
-
-
-
-
KHRQM22M20T
KHRQM22M29T
KHRQM22M64T
KHRQM22M75T
KHRQ22M20T
KHRQ22M29T9
KHRQ22M64T
KHRQ22M75T
Metric-size connections Imperial-size connections
152
VRV III-S Mini VRV
ntinuous heating
VRV III-C Cold Region VRV
VRV Classic
Total Solution VRV
VRV III Heat Recovery
2-module systems
3-module systems
RXYSQ
RTSYQ 10
RTSYQ 14~16
RTSYQ 20
RXYCQ8A
RXYCQ10-14A
RXYCQ16-20A
REYQ 8~16
REMQ 8~12
REMQ 14~16 REMHQ12
2-module systems
3-module systems
REYAQ 10~16
BHFQ22P1007
BHFQ22P1517
-
-
-
BHFQ22P1007
-
-
-
-
-
-
BHFQ23P907
BHFQ23P1357
-
-
-
-
-
-
-
-
-
-
-
-
-
KWC26B280
KWC26B450
2x KWC26B280
KWC26B160
KWC26B280
KWC26B450
KWC25C450
KWC26B280
KWC26B450
1 kit per module
1 kit per module
KWC25C450
-
-
-
BEH22A10Y1L
BEH22A18Y1L
2x BEH22A10Y1L
-
-
-
-
-
-
-
-
-
Special order unit
-
For installation into an indoor unit: exact adapter type depends on type of indoor unit. See Options & Accessories of indoor units
1 kit per system
1 kit per system
-
1 kit per system
1 kit per system
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
VRV-W IV Water-cooled VRV
VRV III-Q Heat Recovery Replacement VRV
Heat Pump application
Heat Recovery application
RQEQ 140~212
2-module systems
3-module systems
4-module systems
RWEYQ8-10T
2-module systems
3-module systems
2-module systems
3-module systems
-
BHFP26P36C
BHFP26P63C
BHFP26P84C
-
BHFQ22P1007
BHFQ22P1517
BHFQ23P907
BHFQ23P1357
KWC26B160
1 kit per module
1 kit per module
1 kit per module
-
-
-
-
-
-
-
-
-
-
-
-
-
-
DTA104A62 Installation in the RWEYQ outdoor unit possible. For installation in indoor units, use appropriate type (DTA104A53/61/62) for particular indoor unit. See Options & Accessories of indoor units
DTA104A53/61/62 For installation into an indoor unit: exact adapter type depends on type of indoor unit. See Options & Accessories of indoor units
1 kit per system
1 kit per system
1 kit per system
-
-
-
-
-
-
-
-
-
1 kit per system
1 kit per system
-
-
-
-
-
-
1 kit per system
1 kit per system
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
1 kit per system
-
-
-
-
-
1 kit per system
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
Heat Recovery Branch Selector Boxes (BS-Boxes)
Capacity index
Capacity index
Capacity index
1-port
1-port
1-port
4-port
6-port
< 291
291~640
> 640
Capacity index < 101
Capacity index 101 ~ 160
Capacity index 161 ~ 250
Capacity index < 100 per port
Capacity index < 100 per port
KHRQM23M29H
KHRQM23M64H
KHRQM23M75H
-
-
-
-
-
KHRQ23M29H
KHRQ23M64H
KHRQ23M75H
BSVQ100P8B
BSVQ160P8B
BSVQ250P8B
BSV4Q100PV
BSV6Q100PV
-
-
-
EKBSVQLNP
EKBSVQLNP
EKBSVQLNP
-
-
-
-
-
KRC19-26
KRC19-26
KRC19-26
KRC19-26 1 kit per port necessary
KRC19-26 1 kit per port necessary
-
-
-
KJB111A
KJB111A
KJB111A
KJB111A
KJB111A
KHRQM22M29H
KHRQM22M64H
KHRQM22M75H
-
-
-
-
-
KHRQ22M29H
KHRQ22M64H
KHRQ22M75H
-
-
-
-
-
153
OPTIONS & ACCESSORIES
Refnet Headers
Options & accessories indoor Ceiling mounted cassette units Round flow (800x800)
4-way (600x600)
FXFQ 20~125A
FXZQ 15~50A
FXCQ 20~40A
FXCQ 50~63A
FXCQ 80 ~125A
*4
*4
*4
*4
*4
BRC7F532F
BRC7F530W *9*10 (white panel) BRC7F530S *9*10 (grey panel) BRC7EB530 *9*10 (standard panel)
BRC7C52
BRC7C52
BRC7C52
BRC2C51 Simplified wired remote control
-
-
-
-
-
BRC3A61 Remote control for hotel use
BRC1E52A/B Premium wired remote control with full-text interface and back-light BRC1D52 Standard wired remote control with weekly timer
Adapters and control
Infrared remote control including receiver
-
-
-
-
-
DCS302C51 Central remote control
DCS301B51 Unified ON/OFF control
DST301B51 Schedule timer
DCS601C51 Intelligent Touch Manager External wired temperature sensor External wireless temperature sensor
KRCS01-4
KRCS01-4
KRCS01-4
KRCS01-4
KRCS01-4
K.RSS
K.RSS
K.RSS
K.RSS
K.RSS
KRP4A53 *2*7
KRP4A53 *2
KRP4A51
KRP4A51
KRP4A51
-
KRP2A52
KRP2A51
KRP2A51
KRP2A51
Wiring adapter with 4 output signals (Compressor / Error, Fan, Aux. heater, Humidifier output)
EKRP1C11 *2*7
EKRP1B2
EKRP1B2
EKRP1B2
EKRP1B2
Wiring adapter with 2 output signals (Compressor / Error, Fan output)
KRP1B57 *2*7
KRP1B57
-
-
-
Adapter for multi-tenant applications (24VAC PCB power supply interface)
DTA114A61
DTA114A61
-
-
-
Wiring adapter for external monitoring/control via dry contacts and setpoint control via 0-140Ω Wiring adapter for external central monitoring/control (controls 1 entire system)
External control adapter for outdoor unit
-
-
DTA104A61
DTA104A61
DTA104A61
KRP1H98 *7
KRP1A101
KRP1C96
KRP1C96
KRP1C96
Connector for forced-off contact
standard
-
standard
standard
standard
Connection to centralized control
standard
-
-
-
-
Electrical box with earth terminal (2 blocks)
KJB212A
-
KJB212A
KJB212A
KJB212A
Electrical box with earth terminal (3 blocks)
KJB311A
-
KJB311A
KJB311A
KJB311A
BYBCQ40H
BYBCQ63H
BYBCQ125H
Installation box / Mounting plate for adapter PCBs (For units where there is no space in the switchbox)
Decoration panel (obligatory for cassette units, optional for others, rear panel for FXLQ)
Others
2-way blow
BYCQ140D7GW1 (self clean) *5/*6 BYFQ60CW (white panel) BYCQ140D7W1W (white) *3 BYFQ60CS (grey panel) BYCQ140D7W1 (standard) BYFQ60B3 (standard panel)
Kit for mounting of decoration panel direct onto unit
-
-
-
-
-
Panel spacer for reducing required installation height
-
KDBQ44B60 (standard panel)
-
-
-
KDBHQ55B140 *7
BDBHQ44C60 (white & grey panel)
-
-
-
KDDQ55B140-1 + KDDQ55B140-2 *7*8
KDDQ44XA60
-
-
-
-
-
-
-
-
Sealing kit for 3-directional or 2-directional air discharge Fresh air intake kit Air discharge adapter for round duct Filter chamber for bottom suction Replacement long life filter Drain pump kit Sensor kit Noise filter (for electromagnetic use only)
-
-
KDDFP53B50
KDDFP53B80
KDDFP53B160
KAFP551K160
KAFQ441BA60
KAFP531B50
KAFP531B80
KAFP531B160
standard
standard
standard
standard
standard
BRYQ140A
BRYQ60AW (white panel) BRYQ60AS (grey panel)
-
-
-
-
-
KEK26-1A
KEK26-1A
KEK26-1A
*2 Installation box is necessary for these adapters *3 The BYCQ140D7W1W has white insulation
Be informed that formation of dirt on white insulation is visibly stronger and that it is consequently not advised to install the BYCQ140D7W1W decoration panel in environments exposed to concentrations of dirt"
*4 Not recommended because of the limitation of the functions *5 To be able to control the BYCQ140D7GW1 the controller BRC1E is needed *6 The BYCQ140DGW1 is not compatible with Mini VRV, Multi and Split Non-Inverter Outdoor units *7 Option not available in combination with BYCQ140D7GW1 *8 Both parts of the fresh air intake are needed for each unit *9 Sensing function not available *10 Independently controllable flaps function not available
154
Concealed ceiling units (duct units) Corner (1-way blow)
Small
Slim
Standard
FXKQ 25~40
FXKQ 63
FXDQ 20~25 M9
FXDQ 15~63A
FXSQ 20~32
FXSQ 40~50
FXSQ 63~80
FXSQ 100~140
*4
*4
*4
*4
*4
*4
*4
*4
BRC4C61
BRC4C61
BRC4C62
BRC4C65
BRC4C65
BRC4C65
BRC4C65
BRC4C65
-
-
-
-
KRCS01-1
KRCS01-1
KRCS01-1
KRCS01-4B
KRCS01-4
KRCS01-4
KRCS01-4
KRCS01-4
K.RSS
K.RSS
K.RSS
K.RSS
K.RSS
K.RSS
K.RSS
KRP4A51
KRP4A51
KRP4A54
KRP4A51
KRP4A51
KRP4A51
KRP4A51
KRP2A51
KRP2A51
KRP2A51
KRP2A53
KRP2A61
KRP2A51
KRP2A51
KRP2A51
KRP1B61
KRP1B61
EKRP1B2
KRP1B56
EKRP1B2
EKRP1B2
EKRP1B2
EKRP1B2
-
-
-
-
-
-
-
-
-
-
EKMTAC
DTA114A61
DTA114A61
DTA114A61
DTA114A61
DTA114A61
DTA104A61
DTA104A61
DTA104A61
DTA104A53
DTA104A61
DTA104A61
DTA104A61
DTA104A61
-
-
-
KRP1B101
KRP4A96
KRP4A96
KRP4A96
KRP4A96
Standard
Standard
Standard
-
Standard
Standard
Standard
Standard
Standard
Standard
Standard
-
Standard
Standard
Standard
Standard
-
-
-
KJB212A
-
-
-
-
-
-
-
KJB311A
-
-
-
-
BYK45F
BYK71F
-
-
BYBS32D
BYBS45D
BYBS71D
BYBS125D
-
-
-
-
EKBYBSD
EKBYBSD
EKBYBSD
EKBYBSD
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
KDAJ25K36A
KDAJ25K56
KDAJ25K71
KDAJ25K140
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
Standard
Standard
KDAJ25K56
standard
Standard
Standard
Standard
Standard
-
-
-
-
-
-
-
-
-
-
-
KEK26-1A
-
-
-
-
OPTIONS & ACCESSORIES
K.RSS KRP4A51
155
Options & accessories indoor Concealed ceiling units (duct units) High ESP BRC1E52A/B Premium wired remote control with full-text interface and back-light BRC1D52 Standard wired remote control with weekly timer
Adapters and control
FXMQ 40
FXMQ 50~80
FXMQ 100~125
FXMQ 200~250
*4
*4
*4
*4
*4
BRC4C65
BRC4C65
BRC4C65
BRC4C65
BRC4C65
BRC2C51 Simplified wired remote control
BRC3A61 Remote control for hotel use
DCS302C51 Central remote control
DCS301B51 Unified ON/OFF control
DCS601C51 Schedule timer
Infrared remote control including receiver
Others
Large
FXMQ 20~32
DCS301B51 Intelligent Touch Controller External wired temperature sensor External wireless temperature sensor
KRCS01-4
KRCS01-4
KRCS01-4
KRCS01-4
KRCS01-1
K.RSS
K.RSS
K.RSS
K.RSS
K.RSS
Wiring adapter for external monitoring/control via dry contacts and setpoint control via 0-140Ω
KRP4A51
KRP4A51
KRP4A51
KRP4A51
KRP4A51
Wiring adapter for external central monitoring/control (controls 1 entire system)
KRP2A51
KRP2A51
KRP2A51
KRP2A51
KRP2A51
Wiring adapter with 4 output signals (Compressor / Error, Fan, Aux. heater, Humidifier output)
EKRP1B2
EKRP1B2
EKRP1B2
EKRP1B2
KRP1B61
Wiring adapter with 2 output signals (Compressor / Error, Fan output)
-
-
-
-
-
Adapter for multi-tenant applications (24VAC PCB power supply interface)
DTA114A61
DTA114A61
DTA114A61
DTA114A61
-
External control adapter for outdoor unit
DTA104A61
DTA104A61
DTA104A61
DTA104A61
DTA104A61
Installation box / Mounting plate for adapter PCBs (For units where there is no space in the switchbox)
KRP4A96
KRP4A96
KRP4A96
KRP4A96
-
Connector for forced-off contact
Standard
Standard
Standard
Standard
Standard
Connection to centralized control
Standard
Standard
Standard
Standard
Standard
Electrical box with earth terminal (2 blocks)
-
-
-
-
-
Electrical box with earth terminal (3 blocks)
-
-
-
-
-
Decoration panel (obligatory for cassette units, optional for others, rear panel for FXLQ)
BYBS32D
BYBS45D
BYBS71D
BYBS125D
-
Kit for mounting of decoration panel direct onto unit
EKBYBSD
EKBYBSD
EKBYBSD
EKBYBSD
-
Panel spacer for reducing required installation height
-
-
-
-
-
Sealing kit for 3-directional or 2-directional air discharge
-
-
-
-
-
Decorationpanel for air discharge
-
-
-
-
-
Fresh air intake kit
-
-
-
-
-
KDAJ25K36A
KDAJ25K56
KDAJ25K71
KDAJ25K140
-
-
-
-
-
-
Air discharge adapter for round duct Replacement long life filter Drain pump kit
Standard
Standard
Standard
Standard
-
Sensor kit
-
-
-
-
-
Noise filter (for electromagnetic use only)
-
-
-
-
-
L-type piping kit (for upward direction)
-
-
-
-
-
*2 Installation box is necessary for these adapters *3 The BYCQ140D7W1W has white insulation
Be informed that formation of dirt on white insulation is visibly stronger and that it is consequently not advised to install the BYCQ140D7W1W decoration panel in environments exposed to concentrations of dirt
*4 Not recommended because of the limitation of the functions *5 To be able to control the BYCQ140D7GW1 the controller BRC1E is needed *6 The BYCQ140DGW1 is not compatible with Mini VRV, Multi and Split Non-Inverter Outdoor units *7 Option not available in combination with BYCQ140D7GW1 *8 Both parts of the fresh air intake are needed for each unit *9 Sensing function not available *10 Independently controllable flaps function not available
156
Ceiling suspended units 1-way blow
Wall mounted units 4-way blow
Floor standing units Concealed
Free-standing
FXHQ 32A
FXHQ 63A
FXHQ 71~100A
FXUQ 71~100A
FXAQ 15~63
FXNQ 20~63
FXLQ 20~25
FXLQ 32~40
FXLQ 50~63
*4
*4
*4
*4
*4
*4
*4
*4
*4
BRC7G53
BRC7G53
BRC7G53
BRC7C58
BRC7E618
BRC4C65
BRC4C65
BRC4C65
BRC4C65
-
-
-
-
-
-
-
-
-
-
-
-
-
-
KRCS01-4
KRCS01-4
KRCS01-4
KRCS01-4
KRCS01-1
KRCS01-1
KRCS01-1
KRCS01-1
KRCS01-1
K.RSS
K.RSS
K.RSS
K.RSS
K.RSS
K.RSS
K.RSS
K.RSS
K.RSS
KRP4A52
KRP4A52
KRP4A52
KRP4A53 *2
KRP4A51
KRP4A51
KRP4A51
KRP4A51
KRP4A51
KRP2A62
KRP2A62
KRP2A62
-
KRP2A51
KRP2A51
KRP2A51
KRP2A51
KRP2A51
-
-
-
-
-
KRP1B61
KRP1B61
KRP1B61
KRP1B61
KRP1B54
KRP1B54
KRP1B54
-
-
-
-
-
-
-
-
-
-
DTA114A61
EKMTAC
EKMTAC
EKMTAC
EKMTAC
DTA104A62
DTA104A62
DTA104A62
-
DTA104A61
-
-
-
-
KRP1D93A
KRP1D93A
KRP1D93A
KRP1B97
KRP4A93
-
-
-
-
EKRORO4
EKRORO4
EKRORO4
EKRORO5
Standard
Standard
Standard
Standard
Standard
-
-
-
-
Standard
Standard
Standard
Standard
Standard
KJB212A
KJB212A
KJB212A
KJB212A
-
-
-
-
-
KJB311A
KJB311A
KJB311A
KJB311A
-
-
-
-
-
-
-
-
-
-
-
EKRDP25A
EKRDP40A
EKRDP63A
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
KDBHP49B140
-
-
-
-
-
-
-
KDBTP49B140
-
-
-
-
-
KDDQ50A140
KDDQ50A140
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
KAFP501A56
KAFP501A80
KAFP501A160
KAFP551K160
-
-
-
-
-
KDU50P60
KDU50P140
KDU50P140
-
K-KDU572EVE
-
-
-
-
-
-
-
-
-
-
-
-
-
KEK26-1
KEK26-1
KEK26-1
-
-
-
-
-
-
KHFP5M35
KHFP5N63
KHFP5N160
-
-
-
-
-
-
OPTIONS & ACCESSORIES
KDDQ50A140
157
Options & accessories Stylish indoor units INDOOR UNITS - CONTROL SYSTEMS
FTXG20L
FTXG25L
Wired remote control Wireless remote control
FTXG35L
FTXG50L
FTXG35L
FTXG50L
BRC944 (3) -
Simplified remote control
-
Remote control for hotel use
3m
Cord for wired remote control
BRCW901A03
8m
BRCW901A08
Wiring adapter normal open contact / normal open pulse contact Centralised control board
KRP413A1S (1)
Up to 5 rooms
KRC72 (2)
Anti-theft protection for remote control
KKF910A4
Central remote control
DCS302C51
Unified on/off control
DCS301B51
Schedule timer
DST301B51
Wiring adapter for electrical appendices
-
Remote sensor
-
Installation box for adapter PCB
-
Electric box with earth terminal 2 / 3 blocks
-
Interface adapter for DIII-net
KRP928A2S
Online controller
BRP069A41
External mounting kit for online controller
-
Wifi power cable for online controller
-
Touch LCD wall controller (4)
-
Simple wall controller (4)
-
KNX gateway
KLIC-DD
INDOOR UNITS
FTXG20L
FTXG25L
Photocatalytic deodorising filter, with frame Photocatalytic deodorising filter, without frame
-
Air purification filter, with frame
-
Notes (1) Wiring adapter supplied by Daikin. Time clock and other devices : to be purchased locally. (2) Wiring adapter is also required for each indoor unit. (3) Cord for wired remote control BRCW901A03 or BRCW901A08 required. (4) Can only be used in combination with online controller KKRP01A. (5) Standard there is no remote control delivered with this indoor unit. Wired or wireless control to be ordered separately.
INDOOR UNITS - CONTROL SYSTEMS
CTXS15K
FTXS20K
FTXS25K
Wired remote control (3) Cord for wired remote control
3m 8m
FTXS42K
FTXS50K
KRP413A1S (6)
Up to 5 rooms
KRC72 (2)
Anti-theft protection for remote control
KKF910A4
Interface adapter for wired remote control
KRP980A1
Central remote control
DCS302C51
Unified on/off control
DCS301B51
Schedule timer
DST301B51
Interface adapter for DIII-net
KRP928A2S (6)
Online controller
KKRP01A
External mounting kit for online controller
KKRPM01A
Wifi power cable for online controller
KKRPW01A
Touch LCD wall controller (4)
KBRC01A
Simple wall controller (4)
KBRCS01A
KNX gateway
KLIC-DD (6)
INDOOR UNITS
FTXS35K
BRCW901A08
Wiring adapter normal open contact / normal open pulse contact Centralised control board
CTXS35K BRC944 (3) (6) BRCW901A03
CTXS15K
FTXS20K
Titanium apatite photocatalytic air-purification filter without frame Installation leg
FTXS25K
CTXS35K -
Notes (1) Wiring adapter supplied by Daikin. Time clock and other devices : to be purchased locally. (2) Wiring adapter is also required for each indoor unit. (3) Cord for wired remote control BRCW901A03 or BRCW901A08 required. (4) Can only be used in combination with online controller KKRP01A. (5) Standard there is no remote control delivered with this indoor unit. Wired or wireless control to be ordered separately. (6) Interface adapter KRP980A1 required.
158
FTXS35K
FTXS42K
FTXS50K
FDXS35F
FDXS50F9
FDXS60F
FVXS25F
BRC1D52 / BRC1E52A / BRC1E52B (5) BRC4C65
FDXS25F
FVXS35F
FVXS50F
FLXS25B
FLXS35B9
-
FLXS50B
BRC2C51
-
-
BRC3A61
-
-
-
-
-
-
-
-
-
KRP413A1S (1)
KRP413A1S (1)
-
KRC72 (2)
KRC72 (2)
-
-
KKF917AA4
DCS302C51
DCS302C51
DCS302C51
DCS301B51
DCS301B51
DCS301B51
DST301B51
DST301B51
DST301B51
KRP4A54
-
-
KRCS01-4
-
-
KRP1BA101
-
-
KJB212A / KJB311A
-
-
-
KRP928A2S
KRP928A2S
-
KKRP01A
KKRP01A
-
KKRPM01A
KKRPM01A
-
KKRPW01A
KKRPW01A
-
KBRC01A
KBRC01A
-
KBRCS01A
KBRCS01A
-
KLIC-DD
KLIC-DD
FDXS35F
FDXS50F9
FDXS60F
FVXS25F
FVXS35F
FVXS50F
FLXS25B
FLXS35B9
-
-
KAZ917B41 KAZ917B42
-
-
KAF925B41
FTXS60G
FTXS71G
FVXG25K
FVXG35K
BRC944 (3) BRCW901A03
FLXS50B
FLXS60B
FVXG50K
BRC944 (3) BRCW901A03
BRCW901A08
BRCW901A08
KRP413A1S (1)
KRP413A1S (1)
KRC72 (2)
KRC72 (2)
KKF910A4
KKF910A4
-
-
DCS302C51
DCS302C51
DCS301B51
DCS301B51
DST301B51
DST301B51
KRP928A2S
KRP928A2S
KKRP01A
KKRP01A
KKRPM01A
KKRPM01A
KKRPW01A
KKRPW01A
KBRC01A
KBRC01A
KBRCS01A
KBRCS01A
KLIC-DD
KLIC-DD
FTXS60G
FLXS60B
-
FTXS71G
FVXG25K
FVXG35K
-
FVXG50K
BKS028
OPTIONS & ACCESSORIES
FDXS25F
159
Options & accessories Stylish indoor units INDOOR UNITS - CONTROL SYSTEMS
FCQG35F
FCQG50F
FCQG60F
Wired remote control I-touch controller Infrared remote control (heat pump) Remote control for hotel use Centralised remote control Unified ON/OFF control Schedule timer Adapter for wiring (interlock for fresh air intake fan) Adapter for external ON/OFF and monitoring/for electrical appendices Installation box for adapter PCB Remote sensor Electrical box with earth terminal (3 blocks) Electrical box with earth terminal (2 blocks) Adapter for wiring (hour meter) Options PCB for external electrical heater, humidifier and/or hour meter Notes (1) Installation box for adapter PCB is necessary (2) Interface adapter for Sky Air series (DTA112B51) is necessary (3) Including following languages: English, German, French, Italian, Spanish, Dutch, Greek, Russian, Turkish, Purtuguese, Polish (4) Including following languages: English, German, Czech, Croatian, Hungarian, Romanian, Slovenian, Bulgarian, Slovak, Serbian, Albanian. (5) Option not available in combination with BYCQ140*G (6) Installation box for adapter PCB (KRP1B101) is necessary (7) Electrical heater, humidifier and hour meter are field supply. These parts should not be installed inside the equipment. (8) Sensing function is not available (9) Independently controllable flaps function is not available
INDOOR UNITS
FCQG35F
FCQG50F
FCQG71F
FCQG100F
FCQG125F
FCQG140F
FCQG100F
FCQG125F
FCQG140F
BRC1D52 / BRC1E52A (3) / BRC1E52B (4) DCS601C51 BRC7FA532F (5) BRC3A61 DCS302C51 DCS301B51 DST301B51 KRP1B57/KRP4A53 (1)(5) KRP1H98 (5) KRCS01-4 KJB311A KJB212A EKRP1C11 (1)(5) -
FCQG60F
FCQG71F
Replacement long-life filter KAFP551K160 Drain pump kit Standard Sealing member of air discharge outlet KDBHQ55B140 (4) Decoration panel BYCQ140D + BYCQ140DW(1) + BYCQ140DG (2)(3) Kit for mounting of decoration panel direct onto unit Fresh air intake kit (direct installation type) KDDQ55B140-1 (4)+ KDDQ55B140-2 (6) Air discharge adapter for round duct Panel spacer Sensor kit BRYQ140A (5) Notes (1) The BYCQ140DW has white insulations. Be informed that dirt is more visible on white insulation and that it is consequently not advised to install the BYCQ140DW decoration panel in environments exposed to concentrations of dirt. (2) To be able to control the BYCQ140DG, the controller BRC1E* is needed (3) The BYCQ140DG is only compatible with Sky Air RZQ(G), RZQS(G); All VRV outdoors; Split RKS, RXS (4) Option not available in combination with BYCQ140DG (5) Sensor kit can only be operated with BRC1E52A/B (6) BYFQ60B2 = basic , BYFQ60CW = White , BYFQ60CS = Grey (7) BRYQ60AW = White, BRYQ60AS = Grey
INDOOR UNITS - CONTROL SYSTEMS
FHQ35C
FHQ50C
FHQ60C
FHQ71C
FHQ100C
FHQ125C
Wired remote control BRC1D52 / BRC1E52A (3) / BRC1E52B (4) Infrared remote control (heat pump) BRC7G53 Centralised remote control DCS302C51 Unified ON/OFF control DCS301B51 Schedule timer DST301B51 Adapter for external ON/OFF and monitoring/for electrical appendices KRP1B54 / KRP4A52(1) Installation box for adapter PCB KRP1D93A Remote sensor KRCS01-4B Remote ON/OFF, forced OFF EKRORO4 Electrical box with earth terminal (3 blocks) KJB311A Electrical box with earth terminal (2 blocks) KJB212A Options PCB for external electrical heater, humidifier and/or hour meter Notes (1) Installation box for adapter PCB is necessary (2) Interface adapter for Sky Air series (DTA112B51) is necessary (3) Including following languages: English, German, French, Italian, Spanish, Dutch, Greek, Russian, Turkish, Purtuguese, Polish (4) Including following languages: English, German, Czech, Croatian, Hungarian, Romanian, Slovenian, Bulgarian, Slovak, Serbian, Albanian.
INDOOR UNITS Replacement long-life filter Drain pump kit L-type piping kit (upward direction) Fresh air intake kit (direct installation type)
FHQ35C
FHQ50C
KAFP501A56 KDU50P60 KHFP5M35 KHFP5N63
FHQ60C
FHQ71C KAFP501A80
KDDQ50A140
160
FHQ100C
FHQ125C
KAFP501A160 KDU50P140 KHFP5N160
FHQ140C
FFQ35C
FFQ50C
FFQ60C
BRC1D52 / BRC1E52A (3) / BRC1E52B (4)(9) DCS601C51 BRC7EB530/BRC7F530W/BRC7F530S (8-9) DCS302B51 DCS301B51 DST301B51 KRP1B57/KRP4A53(6) KRP1B101/ KRP1BA101 KRCS01-4 EKRP1B2 -
FFQ25C
FFQ35C
FFQ50C
KAFQ441BA60 Standard BDBHQ44C60 BYFQ60B3/BYFQ60CW/BYFQ60CS (6) KDDQ44XA60 KDBQ44B60 BRYQ60AW/BRYQ60AS (7)
FDBQ25B
FBQ35C8
FBQ50C8
FBQ60C8
BRC1D52 / BRC1E52A (3) BRC1E52B (4) EKRP1B2 -
FFQ60C
FDBQ25B -
FBQ71C8
FBQ100C8
FBQ125C8
FBQ140C8
FBQ100C8
FBQ125C8
FBQ140C8
BRC1D52 / BRC1E52A (3/ BRC1E52B (4) DCS601C51 (2) BRC4C65 BRC3A61 DCS302C51 DCS301B51 DST301B51 KRP1B54 KRP4A51/KRP2A51 KRCS01-1 EKRP1B2A (7)
FBQ35C8
FBQ50C8
FBQ60C8
FBQ71C8 Standard -
BYBS45D
BYBS71D
KDAJ25K56A
EKBYBSD KDAJ25K71A -
BYBS125D
KDAJ25K140A
OPTIONS & ACCESSORIES
FFQ25C
161
Options & accessories Ventilation OPTIONS Dust filters
Silencer
VAM150FA
VAM250FA
VAM350FB
VAM500FB
VAM650FB
EN779 Medium M6
-
-
EKAFV50F6
EKAFV50F6
EKAFV80F6
EN779 Fine F7
-
-
EKAFV50F7
EKAFV50F7
EKAFV80F7
EN779 Fine F8
-
-
EKAFV50F8
EKAFV50F8
EKAFV80F8
Model name
-
-
-
-
KDDM24B100
Nominal pipe Diameter (mm)
-
-
-
200
200
-
-
BRYMA65
BRYMA65
BRYMA65
VH1B
VH2B
VH2B
VH3B
VH3B
CO2 sensor VH electrical heater for VAM
INDIVIDUAL CONTROL SYSTEMS Wired remote control
VAM-FA/FB
VKM-GB(M)
BRC1E52A/B / BRC1D52
BRC1E52A/B / BRC1D52
BRC301B61
-
VAM wired remote control
CENTRALISED CONTROL SYSTEMS
VAM-FA/FB
VKM-GB(M)
Centralised remote control
DCS302C51
DCS302C51
Unified ON/OFF control
DCS301B51
DCS301B51
Schedule timer
DST301B51
DST301B51
OTHERS Wiring adapter for electrical appendices (6) Adapter PCB for humidifier Adapter PCB for 3rd party heater
VAM150-250FA
VAM350-2000FB
VKM-GB(M)
KRP2A51 (6) KRP50-2
KRP2A51 (3) BRP4A50A (4/5)
BRP4A50A (4/5) BRP4A50A (4/5)
BRP4A50
BRP4A50A (4/5)
BRP4A50A (4/5)
-
-
-
Remote sensor
Notes (1) Cool/heat selector required for operation (2) Do not connect the system to DIII-net devices (Intelligent controller, Intelligent Manager, LonWorks interface, BACnet interface…) (3) Installation box KRP1BA101 needed for VAM350-2000FB (4) Fixing plate EKMPVAM additionally needed for VAM1500-2000FB (5) 3rd party heater and 3rd party humidifier cannot be combined (6) For external control and monitoring (ON/OFF control, operation signal, error indication)
VH ELECTRICAL HEATER FOR VAM Supply voltage Output current (maximum) Temperature sensor Temperature control range Run on timer Control fuse
220/250V ac 50/60 Hz. +/-10% 19A at 40°C (ambient) 5k ohms at 25°C (table 502 1T) 0 to 40°C / (0-10V 0-100%) Adjustable from 1 to 2 minutes (factory set at 1.5 minutes) 20 X5 mm 250 m A
LED indicators
Power ON - Yellow Heater ON - Red (solid or flashing, indicating pulsed control) Airflow fault - Red
Mounting holes Maximum ambient adjacent to terminal box Auto high temp. cutout Man. reset high temp. cutout Run relay BMS setpoint input
VH ELECTRICAL HEATER FOR VAM Capacity Duct diameter Connectable VAM
kW mm
98mm X 181mm centres 5 mm ø holes 35°C (during operation) 100°C Pre-set 125°C Pre-set 1A 120V AC or 1A 24V DC 0-10VDC
VH1B
VH2B
VH3B
VH4B
VH4/AB
VH5B
1 100 VAM150FA
1 150 VAM250FA VAM350FB
1 200 VAM500FB VAM650FB
1.5 250 VAM800FB VAM1000FB
2.5 250 VAM800FB VAM1000FB
2.5 350 VAM1500FB VAM2000FB
-
162
VAM800FB
VAM1000FB
VAM1500FB
VAM2000FB
VKM50GB(M)
VKM80GB(M)
VKM100GB(M)
EKAFV80F6
EKAFV100F6
EKAFV80F6 x2
EKAFV100F6 x2
-
-
-
EKAFV80F7
EKAFV100F7
EKAFV80F7 x2
EKAFV100F7 x2
-
-
-
EKAFV80F8
EKAFV100F8
EKAFV80F8 x2
EKAFV100F8 x2
-
-
-
KDDM24B100
KDDM24B100
KDDM24B100 x2
KDDM24B100 x2
-
KDDM24B100
KDDM24B100
250
250
250
250
-
250
250
BRYMA100
BRYMA100
BRYMA200
BRYMA200
BRYMA65
BRYMA100
BRYMA200
VH4B / VH4/AB
VH4B / VH4/AB
VH5B
VH5B
-
-
-
FXMQ-MF
EKEQFCB (2)
EKEQDCB (2)
EKEQMCB (2)
BRC1E52A/B / BRC1D52
BRC1E52A/B / BRC1D52
BRC1E52A/B / BRC1D52 (1)
BRC1E52A/B / BRC1D52 (1)
-
-
-
-
FXMQ-MF
EKEQFCB (2)
EKEQDCB (2)
DCS302C51
-
-
-
DCS301B51
-
-
-
DST301B51
-
-
-
FXMQ-MF
EKEQFCB (2)
EKEQDCB (2)
EKEQMCB (2)
-
-
-
-
-
-
-
KRCS01-1
OPTIONS & ACCESSORIES
-
EKEQMCB (2)
163
Options - Control systems DCM601A51
iTM plus adapter
DCM601A52
iTM integrator
DCM601A53
iTM ppd software
DCM002A51
iTM energy navigator software Modbus communication unit
787-712 750-613
Connector:
750-960
WAGO I/O
750-600 750-513/000-001, 750-504
Ai module:
750-454, 750-479, 750-455, 750-459, 750-461, 750-61/000-003, 750-461/000-004, 750-461/ 000-005, 750-460, 750-460/ 000-003, 750-460/000-005
Ao module:
750-555, 750-559, 750-554, 750-560
Thermistor module:
BACnet Interface
750-400, 750-432, 750-430
Do module:
Pi module:
LonWorks Interface
DCM008A51
DC24V power supply unit:
Di module:
DMS502A51
WGDCMCPLR
DC24V power supply unit:
Terminator module:
DMS504B51
750-638 750-461/020-000
Interface adapter for connection to RA units
KRP928A2S
KRP928A2S
Interface adapter for connection to R-407C/R-22 Sky Air units
DTA102A52
DTA102A52
Interface adapter for connection to R-410A Sky Air units
DTA112B51
DTA112B51
DIII board
DAM411B51
Digital input/output
DAM412B51
164
165
OPTIONS & ACCESSORIES
Over 30 years of
VRV History
The original VRV air conditioning system developed by Daikin Industries Ltd. in 1982 is introduced into Europe in VRV standard format. VRV D series can supply conditioned air from up to 6 indoor units connected to a single outdoor unit.
1987
1991
A further step forward is taken in 1991 with the introduction of the VRV heat recovery system, offering simultaneous cooling and heating from different indoor units on the same refrigeration circuit.
The introduction of the VRVII-S series extends the VRV operating scope into the light commercial sectors. Available in 4, 5 and 6HP capacities, the system is designed for installation in up to 9â&#x20AC;Żrooms.
In anticipation of phase out dates for all CFC based equipment, Daikin Europe launched a VRV interter series with R-407C. As many as 16 indoor units can be connected to 1 single outdoor unit.
1994
1998
Consistent high quality and efficiency lead to the widespread acceptance of the VRV concept and Daikin becomes the first Japanese air conditioning manufacturer to be awarded the ISO9001 certification.
166 PB
2003
2004
Daikin introduces the VRVII, the worldâ&#x20AC;&#x2122;s first R-410A operated variable refrigerant flow system. Available in cooling only, heat pump and heat recovery versions. No less than 40 indoor units in heat recovery as well as heat pump format can be connected to a single refrigerant circuit.
2005
Daikin Daikin extends the operational scope of its acclaimed VRVII inverter driven dx air conditioning system, with a new water cooled version, VRV-WII. Available in both heat pump and heat recovery versions.
2006-2007
Daikin extends the VRVIII range with the water cooled VRV-WIII. A geothermal version is also available now. This system uses geothermal heat as a renewable energy source and can operate down to -10°C in heating mode.
2008
Daikin announces the third generation of its much acclaimed VRV range with the extensively re-engineered VRVIII. Available in heat recovery, heat pump and cooling versions, VRVIII incorporates all the best features of earlier VRV systems. However, it also possesses a considerable number of new design, installation and maintenance refinements such as automatic charging and testing. Up to 64 indoor untis can be connected to one system.
2009
2010
Daikin extends its VRV range with the innovative replacement VRV – a highly cost effective replacement for VRV systems still operating on the banned R-22 refrigerant. This cost effective upgrade is possible because VRVIII-Q outdoor units can be installed using existing piping and in some cases existing indoor units.
PB
Daikin launches the ‘total solution’ concept by integrating hot water production and Biddle air curtains in the VRV system. The range of indoor units is also expanded by offering the possibility to connect residential indoor units as Daikin Emura or Nexura to the VRV system. 2011 also confirms VRV as established solution in the market reaching 400,000 outdoor units and 2.2 million indoor units sold.
2011
2012
The fourth generation of VRV is launched. The unit sets new standards in the industry with 28% better seasonal efficiency and continuous heating on heat pumps.
HISTORY AND R&D
Daikin introduces a new heat pump range optimised for heating (VRVIII-C). This new range has an extended operation range down to -25°C and has a greatly improved COP in low ambient temperatures, with the newly developed 2-stage compressor system.
Research & development Creating value through innovative technologies R&D is essential for the creation of products that enrich people's lives. As symbolised by the VRV, Daikin is at the forefront of innovative technology and the development of market leading products: the result of our advanced R&D system.
Superior products from multi-part development approach To create more advanced functions with added value, Daikin has set up the 'Environmental Technology Research Laboratory' and the 'Solution Product Development Center'. Working with the Product Development Group, the three divisions cooperate closely to ascertain and meet the customers' needs and to enable commercialisation of products incorporating advanced technology.
Development
Product Development Group
IT Solution Product Development Center
Intensive research on environmental impact The diverse needs in different countries encountered during the accelerating globalisation of our air conditioning business have presented us with increased research challenges particularly in terms of environmental impact. To promote energy savings in and to lower the environmental impact of our air conditioners, we have developed technologies based on fundamental research into motor inverters and many other areas.
168 PB
Development Environmental Technology Research laboratory
IT and air conditioners: the obvious solution With advances in computerisation and networking, we have integrated IT into our air conditioners including communication technology and advanced software for total control. Our new control systems enable users to develop comfortable environments with superior energy savings by networking air conditioners to enable them to exchange information with each other and with our service centres.
Environment Five-year results for the environmental action plan 2010
Europe Fifteen-fold increase in heat-pump hot water and space heating We have successfully promoted the use of the Daikin Altherma hot water and space heating system in the process contributing to the reduction of 210,000 tons of CO2 emissions.
Under the five-year FUSION 10 strategic management plan, which targeted fiscal year 2010, the Daikin Group strove to develop and promote the use of environmentally conscious products and services on a basic policy of actively contributing to solving global environmental problems and expanding business. Our environmental measures were conducted under our Environmental Action Plan 2010.
Proliferating results Units of Daikin ALtherma
sold in Europe
Reducing Environmental Impact from products
Heat pump heaters as percentage of all heaters sold
in Europe Reduction of 210,000 tons of CO2 emissions compared to using combustiontype heaters
Five year result Promote and expand the use of environmentally conscious products to meet the particular needs of each world region.
15 times
We have developed and provided air conditioner products and services that meet the environmental needs of each world region in terms of weather, culture, and economy.
2006
Five years target
2010
HEAT PUMP HEATERS 4%
FY 2010
FY
Promote the use of environmentally conscious products, particularly in rapidly growing developing countries
PB
HISTORY AND R&D
Daikin will continue to provide air conditioning products and services that meet the environmental needs of each world region. Particularly in developing countries, which are growing fast but where increasing environmental impact is a problem, Daikin will provide products and technologies that contribute to economic progress yet still protect the environment.