SIUC Architecture| Senior Spring 2014 SI Airport Terminal

Page 1

Southern Illinois Airport Terminal

Ryan Northcutt 452 spring 2014


Project Description SI Airport Murphysboro, IL 37.777058,-89.252114

The Southern Illinois Airport is considering the replacement of its current terminal building. The existing facility, which consists of 15,260 sf on two levels, is too large, inflexible and inefficient for current airport needs. It is contemplated that a building in the 6000 sf foot range would be more appropriate for the current and foreseeable future. Uses within the new building would likely be: • The offices of the Airport Authority (approximately 2000 sf consisting of four offices of decreasing size and a generous conference room) • A food service facility. We believe a small full service café, a ‘grab and go’ window for students, a lounge/bar and, perhaps, a sectioned off seating area for special meetings or smaller special events would be a good configuration. • A common area including a lobby space for the greeting of passengers arriving/departing by air and restrooms. • In addition, one intriguing idea that has been proposed is a small number (4-6) of overnight accommodation rooms/suites. Servicing, including food service for guests, would be accomplished by the café. Maximum operating and energy efficiency would be sought in any building design as well as structures that would be representative of an airport but also reflect some local character. An additional feature would be a significant amount of airfield viewing from within the structure. (provided by Gary Schafer)


Program

Southern Illinois Airport Authority 1. Reception Office/Seating 2. Operations Office 3. Administrative Office 4. Manager Office 5. Workspace Room 6. Conference Room

Sq. Ft 294 257 258 407 360 600

Custodial Closet/Laundry Custodial Closet

209 130

Mechanical Space Overnight SIAA FBO Cafe

83 89 83 83

Fixed Base Operator Space 7. Entry/Greeter/Transaction Counter 8. Line Attendant Office 9. Back Office Bookkeeping 10. Flight Plan/Weather Office 11. Pilot Lounge/Bath with Shower 12. Vending/Seating Room

356 325 238 238 403 329

Total Footprint Total

11247sqft 18043sqft

Lobby

3008

CafĂŠ/Bar

1657

Research Center 13. Reception Office/Seating 14. Open Office Space 15. Restrooms 16. Test Track 17. Garage Space 18. Mechanical Space 19. Custodial Space x 2

300 400 600 10000 5000 200 150

Restrooms Mens Womens

297 295

Total

16800sqft

Overnight Space x 5

255


Transportation Research Center


Straddle Bus Height: 14.5’ Width: 25’ (two lanes) Length: 40’ Underpass clearance: 6.5’ 400 person capacity

Passengers enter through a lift through the top of the straddle bus or a side door like a typical train or bus. This allows the stations to be floating above ground level to save space in dense city environments. Two lanes of traffic are aloud to pass under the bus to relieve traffic jams from a parked vehicle as a typical city bus would do. Signals and alarms alert car drivers as the bus travels along the same road. The Straddle bus is to said replace 40 conventional buses and cuts down on 2,640 tons of carbon emissions a year. The bus can be powered by electricity and fueled by systems attached to street lights. Systems such as rails or painted white with a auto piloted gps system allow the bus to travel along the same road as cars.



ROUTE 51

ROUTE 51

CARBONDALE

ROUTE 13

Straddle Bus Route

TRES HOMBRE

STRADDLE BUS STATION CITY HALL

SI AIRPORT

ROUTE 13

AMTRAK

STRADDLE BUS TRANSIT ROUTE

NEW ERA RD RO

The bus route will use route 13 and New Era Road. A straddle bus station will be added in the downtown district of Carbondale on a development site. The station will be centrally located within the city to ensure efficient travel for the passengers to connect to the straddle bus. UT

E1

3

CARBONDALE

STRADDLE BUS TRANSIT ROUTE


Integration


Concept Many forms are possible for integration of an airport terminal building and use of the straddle bus. Only few are acceptable at this scale of application. Perception of passing by a divide rather than being intercepted. This allows for clear sight of the destination. The design follows a form based on the concept. Each program space is divided into its own module. A center corridor runs perpendicular in order to connect all the spaces internally. The straddle bus is treated as a user of the building as it is allowed to pass through the building, stopping to unload and load airport passangers and users.


Site Plan sawtooth roof design straddle bus lane geothermal reflecting pond pull thru drop off lanes roadway pavers

50 25 13.5 0


Floor Plan *In order Left to Right LINE ATT.

OPERATIONS

Overnight LAUNDRY WORK ROOM

TRANSACTION

FBO

ADMIN

BOOKKEEP

HOTEL

Lobby

FLIGHT PLAN MANAGER

RECEPTION

CAFE

KITCHEN

SIAA LOBBY

Cafe

CONFERENCE CUST.

VENDING

Exits

HOTEL

PILOT LOUNGE

MEC.

MEC.

MEC.


Circulation Straddle Bus Pilot Cars, Bikes, Walking


East West Section

The bus lane is dropped below grade, while floor height is lifted above. This helps account for the hieght of the bus for loading of passangers.


Landside Approach


Lobby Space


Systems


Heating and cooling for the building will come from a geothermal heating and cooling system. The system will use coils that will be placed in the reflecting pond located on the south side of the terminal building. A sawtooth roof system will also account for primary indirect lighting during daylight hours. Additional LED lighting will be used when needed.

Heating Cooling Ventilation Daylighting

Operable windows on the south facade and sawtooth roof structure will allow for ventilation for the building.

above http://www.metalocus.es/content/en/blog/ dao%C3%ADz-y-velarde-cultural-centre below http://www.archdaily.com/286624/terrencedonnelly-health-sciences-complex-kongatsarchitects/

The building will use sawtooth roofing for daylighting effects and an aluminum panel facade with daylight fenistrations. (examples shown above)


Geothermal Interior Coil Mechanical Room Exterior Coil


Structure


T.O. Floor 3' - 0" Ground Level 0' - 0" T.O. Footings -3' - 0"

Consultant Address Address Address Phone

Consultant Address Address Address Phone

0"

Consultant Address Address Address Phone

Consultant Address Address Address Phone

A

B

C

D

E

F

G

H

I

J

M

L

K

N

P

O

Consultant Address Address Address Phone

Q

230' - 0"

Structural Grid

42' - 0"

42' - 0"

22' - 0"

10' - 0"

10' - 0"

62' - 0"

22' - 0"

10' - 0"

10' - 0"

13' - 0"

42' - 0"

10' - 0"

29' - 0"

10' - 0"

42' - 0"

22' - 0"

10' - 0"

10' - 0"

22' - 0"

10' - 0"

10

8' - 2"

10' - 0"

11' - 1 1/8"

9

No.

Description

14' - 1"

8

102' - 2"

12' - 6"

14' - 1"

7 6

8' - 8"

5' - 4 7/8" 7' - 0 5/8"

7' - 0 3/8"

14' - 1"

5

Owner

4 3 2 1

Project Name Unnamed

Projec Is

Project Number Date Drawn By

structural floor plan

Checked By

Scale

A

B

C

D

E

F

G

H

I

J

M

L

K

N

P

O

A104

1

Q

230' - 0" 42' - 0" 10' - 0"

42' - 0"

22' - 0"

10' - 0"

10' - 0"

62' - 0"

22' - 0"

10' - 0"

10' - 0"

13' - 0"

42' - 0"

10' - 0"

29' - 0"

10' - 0"

42' - 0"

22' - 0"

10' - 0"

10' - 0"

22' - 0"

10' - 0"

T.O. Structural Wall 26' - 0" T.O. Roof 22' - 0" T.O. Beams 18' - 0" T.O. Frame Wall 16' - 0"

T.O. Floor 3' - 0" Ground Level 0' - 0" T.O. Footings -3' - 0"

structural south elevation

0"

www.autodesk.com/rev

Consultant Address Address Address Phone

Consultant Address Address Address Phone

Consultant Address Address Address Phone

Consultant Address Address Address Phone

Consultant Address Address Address Phone

230' - 0" 42' - 0"

42' - 0"

62' - 0"

42' - 0"

42' - 0"


components

psf 1 1.5 8

roof aluminum insulation: rigid foam plastic skylight: glass with steel frame

Structural Analysis

10.5plf

total

3 3

ceiling suspended lighting and air sprinkler system

6plf

total walls steel studs @ 16 in o.c. aluminum sheathing curtain walls poured concrete 24 in

4 1 12 170 178pfl

total

48

floor steel deck, concrete fill

48plf

total

line attendant custodial/ laundry

325 SF

operations office

255 SF

hotel room 255 SF

www.autodesk.com/revit

1004 SF

work room administration

441 SF

hotel room

restaraunt seating

257 SF

transaction counter

197 SF

back office

Consultant Address Address Address Phone

360 SF

258 SF

kitchen

238 SF

flight plan/ weather office 238 SF

manager office

reception office

407 SF

294 SF

832 SF

Consultant Address Address Address Phone

Consultant Address Address Address Phone

hotel room 255 SF

pilot lounge

vending

lobby

457 SF

354 SF

2956 SF

hotel room 255 SF

conference room

custodial

527 SF

197 SF

Consultant Address Address Address Phone

Consultant Address Address Address Phone

hotel room 253 SF

No.

Description

portion of structural analysis

Owner Project Name Unnamed

Date


page

Project: 462structuresproject

rnorthcutt Carbondale, IL 62901

Location: Multi-Span Roof Beam 2 Multi-Span Roof Beam [2009 International Building Code(AISC 13th Ed ASD)] A992-50 W12x14 x 60.0 FT Section Adequate By: 151.8% Controlling Factor: Deflection

Structural Analysis

Center DEFLECTIONS Live Load 0.00 IN L/Infinity Dead Load 1.59 in Total Load 1.59 IN L/453 Live Load Deflection Criteria: L/240 REACTIONS Live Load Dead Load Total Load Bearing Length

A 0 420 420 0.53

B 0 lb lb 420 lb 420 in 0.53

BEAM DATA Span Length Unbraced Length-Top Unbraced Length-Bottom Roof Pitch 0 :12

of

StruCalc Version 8.0.113.0 LOADING DIAGRAM

4/13/2014 9:19:35 PM

Total Load Deflection Criteria: L/180

lb lb lb in

Center 60 ft 0 ft 60 ft

A

STEEL PROPERTIES W12x14 - A992-50 Properties: Yield Stress: Fy = Modulus of Elasticity: E= Depth: d= Web Thickness: tw = Flange Width: bf = Flange Thickness: tf = Distance to Web Toe of Fillet: k= Moment of Inertia About X-X Axis: Ix = Section Modulus About X-X Axis: Sx = Plastic Section Modulus About X-X Axis: Zx = Design Properties per AISC 13th Edition Steel Manual: Flange Buckling Ratio: FBR = Allowable Flange Buckling Ratio: AFBR = Web Buckling Ratio: WBR = Allowable Web Buckling Ratio: AWBR = Controlling Unbraced Length: Lb = Limiting Unbraced Length for lateral-torsional buckling: Lp = Nominal Flexural Strength w/ safety factor: Mn = Controlling Equation: F2-1 Web height to thickness ratio: h/tw = Limiting height to thickness ratio for eqn. G2-2: h/tw-limit = Cv Factor: Cv = Controlling Equation: G2-3 Nominal Shear Strength w/ safety factor: Vn =

50 29000 11.9 0.2 3.97 0.23 0.53 88.6 14.9 17.4

8.82 9.15 54.25 90.55 0 ft 2.66 ft 43413 ft-lb 54.25 53.95 1 42754 lb

6300 ft-lb Controlling Moment: 30.0 Ft from left support of span 2 (Center Span) Created by combining all dead loads and live loads on span(s) 2 420 lb Controlling Shear: At left support of span 2 (Center Span) Created by combining all dead loads and live loads on span(s Comparisons with required sections: Moment of Inertia (deflection): Moment: Shear:

Req'd 35.19 in4 6300 ft-lb 420 lb

ksi ksi in in in in in in4 in3 in3

Provided 88.6 in4 43413 ft-lb 42754 lb

ROOF LOADING Roof Live Load Roof Dead Load Roof Tributary Width Side One Roof Tributary Width Side Two Wall Load

60 ft

Center RLL = 25 psf RDL = 40 psf TW1 = 0 ft TW2 = 0 ft WALL = 0 plf

Center BEAM LOADING Total Live Load 0 plf Total Dead Load (Adjusted for Roof Pitch) 0 plf Beam Self Weight 14 plf Total Load 14 plf

B


Roof Connection


Lighting


Model Light Study Lighting Objective Primary lighting will come indirect lighting controller by a sawtooth roofing system. Metal and reflective materials will allow light to reflect into the space maximizing day lighting. When lighting is needed, energy efficient LED lighting should be used. The use of whiter light fixtures should be used to increase work, awareness and feeling. Primary use of pendant lighting will be used due to the nature of the design. Floor lighting will be added for visual effect.


Selected Design Area line attendant custodial/ laundry

325 SF

operations office

work room

197 SF

administration

441 SF

hotel room 255 SF

hotel room 255 SF

back office

hotel room 255 SF

hotel room 253 SF

1002 SF

360 SF

258 SF

kitchen

238 SF 706 SF

flight plan/ weather office 238 SF

hotel room 255 SF

restaraunt seating

257 SF

transaction counter

pilot lounge

vending

lobby

457 SF

354 SF

2956 SF

manager office

reception office

407 SF

294 SF

conference room

custodial

527 SF

197 SF


8' - 0"

Lighting Plan (Lobby)

4' - 0" 8' - 0"

8' - 0"

administration A

258 SF

8' - 0"

A

A

407 SF

B

12' - 9"

Symbology 8’ Pendent Light w/ Emergency back up Recessed Wall Base Light Exit Sign custodial S Switch

A

A

8' - 0"

A B

A

lobby A

A

A

A

527 SF

197 SF Mark Manufacture & Description

2956 SF

8' - 0" 5' - 11"

354 SF

8' - 0"

457 SF

vending

6' - 0"

conference room pilot lounge

5' - 0"

4' - 0"

Sheet Keynotes reception office 1. Ceiling height is 15’ above finished floor unless noted. 2. All spaces include acoustical cloud solution unless noted. 294 SF 3. HVAC and plumbing are exposed. 5' - 6" 4. HVAC and plumbing are manufacturer finish.

manager office

5' - 6"

238 SF

706 SF

8' - 0"

6' - 0"

A

8' - 0"

t plan/ weather office

5' - 0"

A

5' - 0"

A

8' - 0"

238 SF

8' - 0"

257 SF

5' - 0"

back office

A

4' - 0"

3' - 1" 5' - 11"

441 SF

A 8' - 0"

8' - 0"

transaction counter

A

8' - 0"

General Sheet Notes 1. Drawings do not scale. 2. All dimensions in feet and inches. 3. Maximize dist. btw diffusers in adj. spaces. 4. Seal all openings in walls btw spaces. restaraunt seating 5. Do not place wall outlets back to back. 6. Wall assembly construction will provide 1002 stc SF of 55. work room 7. Reverb time btw 1.5-1.8 shall be maintained. 8. Emergency lighting intensity must be greater than 1fc at 360 SF floor 9. All exit lighting must be connected to an emergency power source that will assure illumination kitchen for 1-1.5 hours during power failure.

operations office

325 SF

8' - 0"

8' - 0"

ne attendant

8' - 0"

A

Luminare Schedule Lamps Type

QTY WATTS

Lens

Finish Mounting Notes

A

LED Mod 44 LED 30 P-D-L44, S-D-L44 distributed Pendant-Mounted LED Direct array

32

acrylic white pendant soft glow lens

15’ above Finished Floor

B

Cove-15 CC-AI-L 15 LED Concealed Cove Asymmetric Indirect

32

acrylic white concealed soft cove glow lens

concealed cove in bearing wall

Cree LEDs 12


Lighting Section (Lobby)


Power Plan (Lobby)

e attendant 325 SF

transaction counter

8' - 0"

441 SF

8' - 0"

8' - 0"

General Sheet Notes 1. Drawings do not scale. 2. All dimensions in feet and inches. 3. Maximize dist. btw diffusers in adj. spaces. 4. Seal all openings in walls btw spaces. 5. Do not place wall outlets back to back. 6. Wall assembly construction operations office will provide stc of 55. 7. Reverb time btw 1.5-1.8 shall be maintained. 8. Emergency lighting intensity must be greater than 1fc at 257 SF floor 9. All exit lighting must be connected to an emergency power source that will assure illumination for 1-1.5 hours work room during power failure. 360 SF

administration Sheet Keynotes 1. Ceiling height is 15’ above finished floor unless noted. 2. All spaces include cloud solution unless noted. 258acoustical SF 3. HVAC and plumbing are exposed. 4. HVAC and plumbing are manufacturer finish.

ack office 238 SF

Symbology 8’ Pendent Light w/ Emergency back up managerWall office reception office Recessed Base Light Exit Sign 407 SF 294 SF S Switch

plan/ weather office 238 SF

pilot lounge

vending

lobby

457 SF

354 SF

2956 SF

Floor Outlet Duo

conference room

custodial

527 SF

197 SF


Lighting Plan (Cafe)

8' - 0"

8' - 0"

8' - 0"

A

A

A

4' - 0"

restaraunt seating A

A

8' - 0"

A

A

A

1002 SF

A

Sheet Keynotes 1. Ceiling height is 15’ above finished floor unless noted. 2. All spaces include acoustical cloud solution unless noted. 3. HVAC and plumbing are exposed. 4. HVAC and plumbing are manufacturer finish.

A

8' - 0"

work room

8' - 0"

General Sheet Notes 1. Drawings do not scale. 2. All dimensions in feet and inches. 3. Maximize dist. btw diffusers in adj. spaces. 4. Seal all openings in walls btw spaces. 5. Do not place wall outlets back to back. 6. Wall assembly construction will provide stc of 55. 7. Reverb time btw 1.5-1.8 shall be maintained. 8. Emergency lighting intensity must be greater than 1fc at floor 9. All exit lighting must be connected to an emergency power source that will assure illumination for 1-1.5 hours during power failure.

360 SF

8' - 0"

A

5' - 0"

A

A

5' - 0"

4' - 0"

A

706 SF

A

A

A

5' - 0"

4' - 0"

A

reception office

kitchen

Symbology 8’ Pendent Light w/ Emergency back up Recessed Wall Base Light Exit Sign S Switch

5' - 6" A

A

Luminare Schedule Mark Manufacture & Description

Lamps Type

QTY WATTS

Lens

Finish Mounting Notes

A

LED Mod 44 LED 30 P-D-L44, S-D-L44 distributed Pendant-Mounted LED Direct array

32

acrylic white pendant soft glow lens

15’ above Finished Floor

B

Cove-15 CC-AI-L 15 LED Concealed Cove Asymmetric Indirect

32

acrylic white concealed soft cove glow lens

concealed cove in bearing wall

A

5' - 6"

8' - 0"

294 SF

5' - 0"

A

Cree LEDs 12


Lighting Section (Cafe)