WALL-CORN-PRD Wall corner fire barrier

Page 1

Letter # WALL-CORN-PRD Wall-corner conditions with fire barrier Construction Specialties, Inc. 6696 State Route 405, PO Box 380 Muncy, Pennsylvania (570) 546-5941 Fax: (570) 546-8022 www.c-sgroup.com

January 27, 2016 Spectrum Specialty Builders Attn: Dan Pridemore 3902 West Valley Hwy North, Suite 500 Auburn, WA 98001 Project: Lincoln Square II

Location: Bellevue, WA

C/S Project #156859 Re: Wall fire barrier in a corner wall condition

Mr. Pridemore, In reference to the above mentioned project it has come to our attention that the use of a fire barrier in a corner (perpendicular) configuration is of concern. It is the intent of the following UL listing #WW-D-1085, is to describe the wall assembly (see section 1) in regards to the required construction and not the required configuration. It is in our opinion that if the perpendicular wall is built to the required construction standard listed, the condition would be within compliance to the UL listing. If additional information is required, please feel free to contact us. Sincerely,

Justin Moon Product Development Specialist Expansion Joint Cover Systems P: 570-546-4602 E: jmoon@c-sgroup.com Encl Cc: file, Pam Weihermuller (C/S)





Turn static files into dynamic content formats.

Create a flipbook
Issuu converts static files into: digital portfolios, online yearbooks, online catalogs, digital photo albums and more. Sign up and create your flipbook.