DETECTINGANDLOCATINGCANCELINGFAULTS INSHUNTCAPACITORBANKS
OBJECTIVE
Todevelopandbuildatestbedtotest analgorithmthatcandetectsymmetric &asymmetriccancelingfaultsinshunt capacitorbanks(SCB)Thetestbed canalsobeusedinprotectionclasses.

VALUEPROPOSITION
1.ShuntCapacitorBankshortcircuits:
-Capacitorsfailshorted,shortsparallel capacitors;


-Overvoltagedevelopsovertheother un-faultedserieselements,possiblyfail;
-CurrentflowsincenterbranchofH bridge,protectiverelayscandetect faultsbasedonthatcurrent.
2CancelingfailuresinShuntCapacitor Banks:
-Failureofcapacitorsindifferentlegsof Hbridgeremovesvoltageandcurrent imbalance.Difficulttodetect;
-Ourgoalistobuildatestsystemto createsymmetricandasymmetric cancelingfailuresandprovide measurementdatatoarelay.

Figure6: Rp=16.73MΩ; R1-8=1MΩ; Cost:Free




Figure7: 45+5uf±5% 440VAC50/60Hz Cost=$15.85perunit

KEYREQUIREMENTS

-ATPmodelandlabscalemodelshouldbeableto createsymmetricandasymmetriccancelingfaults.


-Voltageandcurrentmeasurementpointsshouldbe addedtotheH-bridge.
-Faultconnectionpointsmustbewithswitches.

-Simulationmodelshouldmatchthephysicaltestbed
CONCEPTDEVELOPMENT& CONCLUSION
Firstversion:Using4capacitorstobuildtheH-bridgeat “ATP”simulation;Secondversion:Using8capacitorsto buildtheH-bridgein“ATP”andhardwaremodel;Third version:Using8capacitorsin“ATP”andhardware modelthenconnectprotectiveresistorsandshortthe capacitorsusingswitchesinparallel.Finally,buildthe finallabversion.



TEAMMEMBER
MohammadAlEbedan, ZeshengGuo, PeiChengJi, ZeyingChen
ACKNOWLEDGEMENTSSELClients:Dr.SatishSamineni,Dr.JadaHawaz; UniversityofIdahoInstructors:Dr.YacineChakhchoukh,Dr.BrianJohnson,Mr.SebastianGarcia