ED 40 - 017A
- Packaged Air Conditioners Duct Connection Type (Middle Static Pressure Application)
FD(Y)M-FA Series — Cooling Only — — Heat Pump —
ED40-017A
Part 1 Indoor Unit FD(Y)M03~06FA .............................................. 1 1. External Appearance and Features ........................................................2 2. Power Supply ..........................................................................................3 2.1 Cooling Only.............................................................................................3 2.2 Heat Pump ...............................................................................................4
3. Specification............................................................................................5 3.1 Cooling Only.............................................................................................5 3.2 Heat Pump .............................................................................................11
4. Optional Accessories ............................................................................15 5. Dimensions ...........................................................................................16 5.1 Indoor Units ............................................................................................16
6. Remote Controller .................................................................................18 6.1 Dimensions.............................................................................................18 6.2 Operation................................................................................................19
7. Wiring Diagrams....................................................................................21 8. Sound Level ..........................................................................................23 8.1 Overall Sound Level ...............................................................................23 8.2 Octave Band Level .................................................................................24
9. Fan Performance ..................................................................................25 10.Installation .............................................................................................27
Part 2 Outdoor Unit KU Series.................................................... 37 1. External Appearance.............................................................................38 2. Power Supply ........................................................................................39 2.1 Cooling Only...........................................................................................39 2.2 Heat Pump .............................................................................................40
3. Specification..........................................................................................41 4. Dimensions and Service Space ............................................................42 4.1 Dimensions.............................................................................................42 4.2 Installation Service Space for R(Y)71KU, 100KU, 125KU, 140KU ........45 4.3 Installation Service Space for R(Y)200KU, 250KU ................................47
5. Piping Diagrams....................................................................................48 5.1 Cooling Only...........................................................................................48 5.2 Heat Pump .............................................................................................51
6. Wiring Diagrams....................................................................................55 6.1 Cooling Only...........................................................................................55 6.2 Heat Pump .............................................................................................60
7. Capacity Table ......................................................................................65 7.1 Cooling Only...........................................................................................65 7.2 Heat Pump .............................................................................................72 7.3 Capacity Correction Factor by the Length of Refrigerant Piping ............77
8. Operation Limits ....................................................................................78 8.1 Cooling Only...........................................................................................78 8.2 Heat Pump .............................................................................................79
9. Sound Level ..........................................................................................81 9.1 Overall Sound Level ...............................................................................81 9.2 Octave Band Level .................................................................................82
10.Electric Characteristics..........................................................................85 Table of Contents
i
ED40-017A
10.1 Cooling Only...........................................................................................85 10.2 Heat Pump .............................................................................................87
11.Field Piping and Wiring .........................................................................89 11.1 Field Piping (R(Y)71~140KU-(K))...........................................................89 11.2 Field Piping (R(Y)200·250KU)................................................................91 11.3 Field Wiring ............................................................................................93
Part 3 Outdoor Unit FU Series .................................................... 97 1. External Appearance.............................................................................98 2. Power Supply ........................................................................................99 2.1 Power Supply .........................................................................................99
3. Specification........................................................................................100 4. Dimensions and Service Space ..........................................................101 4.1 Dimensions...........................................................................................101 4.2 Installation Service Space for R(Y)71-125FU ......................................102
5. Piping Diagrams..................................................................................104 5.1 Cooling Only.........................................................................................104 5.2 Heat Pump ...........................................................................................105
6. Wiring Diagrams..................................................................................106 6.1 Cooling Only.........................................................................................106 6.2 Heat Pump ...........................................................................................110
7. Capacity Table ....................................................................................112 7.1 Cooling Only.........................................................................................112 7.2 Heat Pump ...........................................................................................115 7.3 Capacity Correction Factor by the Length of Refrigerant Piping ..........117
8. Operation Limit....................................................................................118 8.1 Cooling Only.........................................................................................118 8.2 Heat Pump ...........................................................................................119
9. Sound Level ........................................................................................120 9.1 Overall Sound Level .............................................................................120 9.2 Octave Band Level ...............................................................................121
10.Electric Characteristics........................................................................123 10.1 Cooling Only.........................................................................................123 10.2 Heat Pump ...........................................................................................124
11.Field Piping and Wiring .......................................................................125 11.1 Field Piping...........................................................................................125 11.2 Field Wiring ..........................................................................................127
ii
Table of Contents
ED40-017A
Part 1 Indoor Unit FD(Y)M03~06FA 1. External Appearance and Features ........................................................2 2. Power Supply ..........................................................................................3 2.1 Cooling Only.............................................................................................3 2.2 Heat Pump ...............................................................................................4
3. Specification............................................................................................5 3.1 Cooling Only.............................................................................................5 3.2 Heat Pump .............................................................................................11
4. Optional Accessories ............................................................................15 5. Dimensions ...........................................................................................16 5.1 Indoor Units ............................................................................................16
6. Remote Controller .................................................................................18 6.1 Dimensions.............................................................................................18 6.2 Operation................................................................................................19
7. Wiring Diagrams....................................................................................21 8. Sound Level ..........................................................................................23 8.1 Overall Sound Level ...............................................................................23 8.2 Octave Band Level .................................................................................24
9. Fan Performance ..................................................................................25 10.Installation .............................................................................................27
Indoor Unit FD(Y)M03~06FA
1
1
External Appearance and Features
ED40-017A
1. External Appearance and Features Indoor Units
FDM03FA / FDYM03FA
FDM04FA / FDM05FA FDYM04FA / FDYM05FA / FDYM06FA
Remote Controller
Wired Type
Wireless Remote Controller
Signal Receiving Unit (Separate Type)
Features ! ! ! !
Compact in size Fits to the small ceiling spaces Low operating sound: Top in the industry Central control and group control are available (by adopting the optional accessories)
Functions Type Functions Static Pressure Change Over
Heat Pump
FDM
FDYM
" " Field Setting by Remote Controller Field Setting by Remote Controller
Dehumidifying Operation
"
Hot Start
—
"
30m (KU Type Outdoor Units) 5m (R200, 250KU) 5m (FU Type Outdoor Units)
30m (KU Type Outdoor Units) 5m (RY200, 250KU) 5m (FU Type Outdoor Units)
Power Failure Compensation Operation
"
"
Auto Mode (Cooling / Heating) Operation
—
"
Control by 2 Remote Controllers
"
"
Group Control by 1 Remote Controller
"
"
Remote Control by Group
"
"
Central Control
"
"
Interlock with HRV (Heat Reclaim Ventilation)
"
"
Chargeless Length
2
Middle Static Pressure Type Cooling Only
"
Indoor Unit FD(Y)M03~06FA
ED40-017A
Power Supply
2. Power Supply 2.1
Cooling Only
2.1.1
50Hz Series
1 Indoor Unit
Cooling Only
FDYM03FAV1 !
R 71KUV1
FDYM04FAV1 !
R100KUV1
FDYM03FAV1 !
R 71KUY1
FDYM04FAV1 !
R100KUY1
FDYM05FAV1 !
R125KUY1
FDYM06FAV1 !
R140KUY1
FDYM04FAV1×2 !
R200KUY1
FDYM03FAV1×3 !
R200KUY1
FDYM05FAV1×2 !
R250KUY1
FDM03FAV1 !
R 71FUV1
FDM04FAV1 !
R100FUV1
FDM03FAV1 !
R 71FUY1
FDM04FAV1 !
R100FUY1
FDM05FAV1 !
R125FUY1
Indoor Unit
Cooling Only
FDYM03FAVAL !
R 71KUVAL
FDYM04FAVAL !
R100KUVAL
FDYM05FAVAL !
R125KUTAL
FDYM06FAVAL !
R140KUTAL(K)
FDYM04FAVAL×2 !
R200KUTAL
FDYM03FAVAL×3 !
R200KUTAL
FDYM05FAVAL×2 !
R250KUTAL
FDYM05FAVAL !
R125KUYAL
FDYM06FAVAL !
R140KUYAL(K)
FDYM04FAVAL×2 !
R200KUYAL
FDYM03FAVAL×3 !
R200KUYAL
FDYM05FAVAL×2 !
R250KUYAL
FDM03FAVAL !
R 71FUVAL
FDM04FAVAL !
R100FUVAL
FDM05FAVAL !
R125FUTAL
Power Supply 1 phase 220-240V
R-KU
3 phase 380-415V (4 wires)
1 phase 220-240V R-FU
2.1.2
3 phase 380-415V (4 wires)
60Hz Series
Power Supply 1 phase 220V
3 phase 220V
R-KU
3 phase 380V (4 wires)
1 phase 220V R-FU
Notes:
3 phase 220V
1. ! : New Model or Changed Model 2. Power Supply Intake: Outdoor Unit
Indoor Unit FD(Y)M03~06FA
3
Power Supply
ED40-017A
2.2
Heat Pump
2.2.1
50Hz Series
Indoor Unit
Heat Pump
FDYM03FAV1 !
RY 71KUV1
FDYM04FAV1 !
RY100KUV1
FDYM03FAV1 !
RY 71KUY1
FDYM04FAV1 !
RY100KUY1
FDYM05FAV1 !
RY125KUY1
FDYM06FAV1 !
RY140KUY1
FDYM04FAV1×2 !
RY200KUY1
FDYM03FAV1×3 !
RY200KUY1
FDYM05FAV1×2 !
RY250KUY1
Indoor Unit
Heat Pump
FDYM06FAVAL !
RY140KUTAL(K)
FDYM04FAVAL×2 !
RY200KUTAL
FDYM03FAVAL×3 !
RY200KUTAL
FDYM05FAVAL×2 !
RY250KUTAL
FDYM06FAVAL !
RY140KUYAL(K)
FDYM04FAVAL×2 !
RY200KUYAL
FDYM03FAVAL×3 !
RY200KUYAL
FDYM05FAVAL×2 !
RY250KUYAL
FDYM03FAVAL !
RY 71FUVAL
FDYM04FAVAL !
RY100FUVAL
FDYM05FAVAL !
RY125FUTAL
Power Supply 1 phase 220-240V
RY-KU
2.2.2
3 phase 380-415V (4 wires)
60Hz Series
Power Supply
3 phase 220V
RY-KU
3 phase 380V (4 wires)
1 phase 220V RY-FU
Notes:
4
3 phase 220V
1. ! : New Model or Changed Model 2. Power Supply Intake: Outdoor Unit
Indoor Unit FD(Y)M03~06FA
ED40-017A
Specification
3. Specification 3.1
Cooling Only
3.1.1
50Hz
1
FDYM-FA + R-KU Indoor Units Models
Outdoor Units
!1 Cooling Capacity (1)/(2)/(3)
Indoor Units Dimensions
H×W×D Type Coil Row×Stages×Fin Pitch Face Area Model Type Fan Motor Output AFR !2 External Static Pressure Sound Pressure Level !2 Machine Weight Liquid Piping Connections Gas Drain Wired Remote Controller (Option) Wireless Outdoor Units Colour Dimensions Coil
H×W×D Type Row×Stages×Fin Pitch Face Area Model
Comp.
Type Motor Output Model Type Fan Motor Output AFR !2 Sound Pressure Level !2
FDYM03FAV1
FDYM04FAV1
FDYM05FAV1
V1
R71KUV1
R100KUV1
—
Y1 kW Btu/h kcal/h
R71KUY1 7.8 / 7.7 / 7.7 26,600 / 26,200 / 26,200 6,700 / 6,600 / 6,600 FDYM03FAV1 295×1,100×680
mm
W m³/min Pa dB(A) kg mm mm mm
3×14×1.75 0.221 2D18H2AB1VG Sirocco Fan 125 (H) 20 – 22 98 (H) 39 – 41 42 φ9.5 (Flare) φ15.9 (Flare) I.D.φ25×O.D.φ32
V1
R71KUV1
Y1
R71KUY1 Ivory 816×880×370
m²
mm
m² V1 Y1 kW
Machine Weight
kg
Piping Connections
Liquid Gas Drain
W m³/min dB(A) V1 Y1 mm mm mm
Safety Devices Capacity Step Refrigerant Control Max. Length Ref. Piping Max. Height Difference Model Refrigerant Charge Model Ref. Oil Charge Drawing No.
Note:
% m m kg L
R100KUY1 R125KUY1 10.6 / 10.5 / 10.5 13.0 / 12.8 / 12.8 36,100 / 35,700 / 35,700 44,500 / 43,600 / 43,600 9,100 / 9,000 / 9,000 11,200 / 11,000 / 11,000 FDYM04FAV1 FDYM05FAV1 295×1,500×680 295×1,500×680 Cross Fin Coil 3×14×1.75 3×14×1.75 0.338 0.338 3D18H2AN1V1 3D18H2AP1V1 Sirocco Fan Sirocco Fan 135 225 (H) 26 – 28 (H) 35 – 40.5 98 98 (H) 39 – 41 (H) 44 – 46 56 57 φ9.5 (Flare) φ9.5 (Flare) φ19.1 (Flare) φ19.1 (Flare) I.D.φ25×O.D.φ32 I.D.φ25×O.D.φ32 BRC1C61 BRC4C64 R100KUV1 — R100KUY1 Ivory 1,215×880×370
R125KUY1 Ivory 1,215×880×370
FDYM06FAV1 — R140KUY1 14.5 / 14.2 / 14.2 49,400 / 48,400 / 48,400 12,500 / 12,200 / 12,200 FDYM06FAV1 295×1,500×680 3×14×1.75 0.338 3D18H2AP1V1 Sirocco Fan 290 (H) 37 – 42 98 (H) 46 – 48 57 φ9.5 (Flare) φ19.1 (Flare) I.D.φ25×O.D.φ32
— R140KUY1 Ivory 1,345×880×370
Cross Fin Coil 2×54×2.0 2×54×2.0 2×60×2.0 0.979 0.979 1.088 JT118BC – V1 — — JT118BC – YE JT150BC – YE JT170BC – YE Hermetically Sealed Scroll Type 2.2 3.0 3.75 4.5 P45J11SM P45J11SM×2 P45J11SM×2 P45J11SM×2 Propeller Propeller Propeller Propeller 60 70 + 55 70 + 55 90 + 80 46 – 48 87 – 89 87 – 89 101 – 103 48 – 49 50 – 51 50 – 51 55 – 56 82 106 — — 78 103 104 109 φ9.5 (Flare) φ9.5 (Flare) φ9.5 (Flare) φ9.5 (Flare) φ15.9 (Flare) φ19.1 (Flare) φ19.1 (Flare) φ19.1 (Flare) φ26.0 (Hole) φ26.0 (Hole) φ26.0 (Hole) φ26.0 (Hole) Thermal protector for outdoor fan motor and indoor fan motor. High pressure switch. Low pressure switch. Over current relay (compressor). Reverse phase protector (Y1). Fuse. 100 – 0 100 – 0 100 – 0 100 – 0 Expansion Valve (Electronic Type) 50 (Equivalent Length 70m) 50 (Equivalent Length 70m) 50 (Equivalent Length 70m) 50 (Equivalent Length 70m) 30 30 30 30 R22 R22 R22 R22 3.0 (Charged for 30m) 3.4 (Charged for 30m) 3.7 (Charged for 30m) 3.9 (Charged for 30m) SUNISO 4GSDID – K SUNISO 4GSDID – K SUNISO 4GSDID – K SUNISO 4GSDID – K 1.2 1.5 1.5 1.6 4D021043 4D028033A 2×36×2.0 0.653 JT90BC – V1 JT90BC – YE
1 Nominal capacities are based on the following conditions. !1 Cooling Piping Length
Hz – Volts
(1)
Indoor: 27°CDB, 19.5°CWB Outdoor: 35°CDB, 24°CWB
5m
50Hz – 220V(380V)
(2)
Indoor: 27°CDB, 19.0°CWB Outdoor: 35°CDB, 24°CWB
5m
50Hz – 220V(380V)
Conversion Formulae kcal/h=kW×860 Btu/h=kW×3414 cfm=m³/min×35.3
Indoor: 27°CDB, 19.0°CWB 7.5m 50Hz – 240V(415V) Outdoor: 35°CDB, 24°CWB !2 AFR (Air flow rate) and sound pressure level are shown at 220V(380V)–240V(415V). 3 Capacities are net, including a deduction for cooling for indoor fan motor heat. 4 In case of drain piping for outdoor unit, central drain plug (option) is needed. (3)
Indoor Unit FD(Y)M03~06FA
5
Specification
Models
ED40-017A
Indoor Units
FDYM03FAV1×3
Outdoor Units kW Btu/h kcal/h
!1 Cooling Capacity (1)/(2)/(3) !4 Indoor Units
Dimensions
H×W×D Type Coil Row×Stages×Fin Pitch Face Area Model Type Fan Motor Output AFR !2 External Static Pressure Sound Pressure Level !2 Machine Weight Liquid Piping Connections Gas Drain Wired Remote Controller (Option) Wireless Outdoor Units Colour Dimensions H×W×D Type Coil Row×Stages×Fin Pitch Face Area Model Comp. Type Motor Output Model Type Fan Motor Output AFR !2 Sound Pressure Level !2 Machine Weight Liquid Piping Connections Gas Drain
mm
m²
W m³/min Pa dB(A) kg mm mm mm
mm
m²
kW
W m³/min dB(A) kg mm mm mm
Safety Devices Capacity Step Refrigerant Control Max. Length Ref. Piping Max. Height Difference Model Refrigerant Charge Model Ref. Oil Charge Drawing No.
Note:
% m m kg L
FDYM04FAV1×2
FDYM05FAV1×2
R200KUY1 22.5 / 22.2 / 22.0 76,800 / 75,800 / 75,100 19,400 / 19,100 / 18,900 FDYM03FAV1×3 295×1,100×680
R200KUY1 R250KUY1 22.5 / 22.2 / 22.0 27.1 / 26.6 / 26.3 76,800 / 75,800 / 75,100 92,500 / 90,800 / 89,800 19,400 / 19,100 / 18,900 23,300 / 22,900 / 22,600 FDYM04FAV1×2 FDYM05FAV1×2 295×1,500×680 295×1,500×680 Cross Fin Coil (Waffle Louver Fins and Hi-XA Tubes) 3×14×1.75 3×14×1.75 3×14×1.75 0.221 0.338 0.338 2D18H2AB1VG 3D18H2AN1V1 3D18H2AP1V1 Sirocco Fan Sirocco Fan Sirocco Fan 125 135 225 (H) 20 – 22 (H) 26 – 28 (H) 35 – 40.5 98 98 98 (H) 39 – 41 (H) 39 – 41 (H) 44 – 46 42 56 57 φ9.5 (Flare) φ9.5 (Flare) φ9.5 (Flare) φ15.9 (Flare) φ19.1 (Flare) φ19.1 (Flare) I.D.φ25×O.D.φ32 I.D.φ25×O.D.φ32 I.D.φ25×O.D.φ32 BRC1C61 BRC4C64 R200KUY1 R200KUY1 R250KUY1 Ivory Ivory Ivory 1,220×1,280×690 1,220×1,280×690 1,440×1,280×690 Cross Fin Coil (Waffle Louver Fins and Hi-XA Tubes) 2×40×2.0 2×40×2.0 2×50×2.0 1.57 1.57 1.97 JT236D – P1YE JT236D – P1YE JT335D – P1YE Hermetically Sealed Scroll Type 5.5 5.5 9.0 P52H11SM P52H11SM P52H11SM Propeller Propeller Propeller 230 + 190 230 + 190 230 + 190 150 – 154 150 – 154 175 – 179 60 – 61 60 – 61 61 – 62 178 178 202 φ12.7 (Flare) φ12.7 (Flare) φ15.9 (Flare) φ25.4 (Flange) φ25.4 (Flange) φ28.6 (Flange) — — — Thermal protector for compressor, outdoor fan motor and indoor fan motor. High pressure switch. Low pressure switch. Over current relay (compressor). Reverse phase protector. Fuse. 100 – 0 100 – 0 100 – 0 Capillary Tube 50 (Equivalent Length 70m) 50 (Equivalent Length 70m) 50 (Equivalent Length 70m) 30 30 30 R22 R22 R22 5.3 (Charged for 5m) 5.3 (Charged for 5m) 5.7 (Charged for 5m) SUNISO 4GSDID – K SUNISO 4GSDID – K SUNISO 4GSDID – K 3.0 3.0 3.0 4D029967 4D029969
1 Nominal capacities are based on the following conditions. !1 Cooling Piping Length
Hz – Volts
(1)
Indoor: 27°CDB, 19.5°CWB Outdoor: 35°CDB, 24°CWB
5m (Horizontal)
50Hz – 380V
(2)
Indoor: 27°CDB, 19.0°CWB Outdoor: 35°CDB, 24°CWB
5m (Horizontal)
50Hz – 380V
Conversion Formulae kcal/h=kW×860 Btu/h=kW×3414 cfm=m³/min×35.3
Indoor: 27°CDB, 19.0°CWB 7.5m 50Hz – 415V Outdoor: 35°CDB, 24°CWB (Horizontal) !2 AFR (Air flow rate) and sound pressure level are shown at 220V(380V)–240V(415V). 3 Capacities are net, including a deduction for cooling for indoor fan motor heat. !4 Each value for indoor unit shows the specification per one unit. (3)
6
Indoor Unit FD(Y)M03~06FA
ED40-017A
Specification
1
FDM-FA + R-FU Indoor Units Models
Outdoor Units
!1 Cooling Capacity (1)/(2)/(3)
FDM03FAV1
FDM04FAV1
V1
R71FUV1
R100FUV1
—
Y1 kW Btu/h kcal/h
R71FUY1 7.8 / 7.7 / 6.3 26,600 / 26,200 / 21,500 6,700 / 6,600 / 5,400 FDM03FAV1 295×1,100×680
R100FUY1 10.6 / 10.5 / 8.0 36,100 / 35,700 / 27,300 9,100 / 9,000 / 6,900 FDM04FAV1 295×1,500×680 Cross Fin Coil 3×14×1.75 0.338 3D18H2AN1V1 Sirocco Fan 135 (H) 26 98 (H) 39 56 φ9.5 (Flare) φ19.1 (Flare) I.D.φ25×O.D.φ32 BRC1C61 BRC4C64 R100FUV1
R125FUY1 13.0 / 12.8 / 11.2 44,500 / 43,600 / 38,200 11,200 / 11,000 / 9,600 FDM05FAV1 295×1,500×680
Indoor Units Dimensions
H×W×D Type Coil Row×Stages×Fin Pitch Face Area Model Type Fan Motor Output Air Flow Rate External Static Pressure Sound Pressure Level Machine Weight Liquid Piping Connections Gas Drain Wired Remote Controller (Option) Wireless Outdoor Units Colour Dimensions Coil
H×W×D Type Row×Stages×Fin Pitch Face Area Model
Comp.
Type No. of Cylinders Motor Output Model Type Fan Motor Output Air Flow Rate Sound Pressure Level Machine Weight
kg
Piping Connections
Liquid Gas Drain
Safety Devices Capacity Step Refrigerant Control Max. Length Ref. Piping Max. Height Difference Model Refrigerant Charge Model Ref. Oil Charge Drawing No.
Note:
mm
W m³/min Pa dB(A) kg mm mm mm
3×14×1.75 0.221 2D18H2AB1VG Sirocco Fan 125 (H) 20 98 (H) 39 42 φ9.5 (Flare) φ15.9 (Flare) I.D.φ25×O.D.φ32
V1
R71FUV1
Y1
R71FUY1 Ivory 816×880×370
m²
FDM05FAV1
3×14×1.75 0.338 3D18H2AP1V1 Sirocco Fan 225 (H) 35 98 (H) 44 57 φ9.5 (Flare) φ19.1 (Flare) I.D.φ25×O.D.φ32
—
R100FUY1 R125FUY1 Ivory Ivory mm 1,215×880×370 1,215×880×370 Cross Fin Coil 2×36×2.0 2×54×2.0 2×54×2.0 m² 0.653 0.979 0.979 V1 H23A35QABKA H23A46QABKA — Y1 H23A35QDBEA H23A46QDBEA H23A56QDBEA Hermetically Sealed Type 2 2 2 kW 2.2 3.0 3.75 P45J11SM P45J11SM×2 P45J11SM×2 Propeller Propeller Propeller W 50 75 + 35 75 + 60 m³/min 46 80 87 dB(A) 52 56 57 V1 87 117 — Y1 84 109 110 mm φ9.5 (Flare) φ9.5 (Flare) φ9.5 (Flare) φ15.9 (Flare) φ19.1 (Flare) φ19.1 (Flare) mm φ26.0 (Hole) φ26.0 (Hole) φ26.0 (Hole) mm Thermal protector for outdoor fan motor and indoor fan motor. Internal pressure relief valve. (compressor) Motor protector. (compressor) % 100 – 0 100 – 0 100 – 0 Capillary Tube m 50 (Equivalent Length 70m) 50 (Equivalent Length 70m) 50 (Equivalent Length 70m) m 30 30 30 R22 R22 R22 kg 2.1 (Charged for 5m) 2.4 (Charged for 5m) 2.8 (Charged for 5m) SUNISO 3GS SUNISO 3GS SUNISO 3GS L 1.48 1.63 1.63 4D021049
1 Nominal capacities are based on the following conditions. !1 Cooling
Piping Length
(1)
Indoor 27°C(81°F)DB, 19.5°C(67°F)WB Outdoor 35°C(95°F)DB, 24°C(75°F)WB
5m (Horizontal)
(2)
Indoor 27°C(81°F)DB, 19.0°C(66°F)WB Outdoor 35°C(95°F)DB, 24°C(75°F)WB
5m (Horizontal)
Conversion Formulae kcal/h=kW×860 Btu/h=kW×3414 cfm=m³/min×35.3
(3) Indoor 29°C(84°F)DB, 19.0°C(66°F)WB 7.5m (Horizontal) SSA 385/386 Outdoor 46°C(115°F)DB, 24°C(75°F)WB 2 Capacities are net, including a deduction for cooling for indoor fan motor heat. 3 In case of drain piping for outdoor unit, central drain plug (option) is needed.
Indoor Unit FD(Y)M03~06FA
7
Specification
3.1.2
ED40-017A
60Hz
FDYM-FA + R-KU Indoor Units Models
Outdoor Units
!1 Cooling Capacity (1)/(2)/(3)
Indoor Units Dimensions
H×W×D Type Coil Row×Stages×Fin Pitch Face Area Model Type Fan Motor Output Air Flow Rate External Static Pressure Sound Pressure Level Machine Weight Liquid Piping Connections Gas Drain Wired Remote Controller (Option) Wireless
Outdoor Units Colour Dimensions Coil
H×W×D Type Row×Stages×Fin Pitch Face Area Model
Comp. Type Motor Output Model Type Fan Motor Output Air Flow Rate Sound Pressure Level Machine Weight Liquid Piping Connections Gas Drain
FDYM03FAVAL
FDYM04FAVAL
FDYM05FAVAL
VAL
R71KUVAL
R100KUVAL
—
—
TAL
—
—
R125KUTAL
R140KUTAL(K)
YAL kW Btu/h kcal/h
— 8.3 / 8.1 / — 28,200 / 27,800 / — 7,100 / 7,000 / — FDYM03FAVAL 295×1,100×680
mm
W m³/min Pa dB(A) kg mm mm mm
VAL
R71KUVAL
TAL
—
—
R125KUTAL
R140KUTAL(K)
YAL
— Ivory 816×880×370
— Ivory 1,215×880×370
R125KUYAL Ivory 1,215×880×370
R140KUYAL(K) Ivory 1,345×880×370
mm
m² VAL TAL YAL kW
W m³/min dB(A) kg mm mm mm
Capacity Step Refrigerant Control Max. Length Ref. Piping Max. Height Difference Model Refrigerant Charge
kg
Model Charge
%
L
m m
Drawing No.
Note:
R140KUYAL(K) 16.1 / 15.8 / 14.0 55,000 / 53,900 / 47,800 13,800 / 13,500 / 12,000 FDYM06FAVAL 295×1,500×680
3×14×1.75 0.221 2D18H2AB1VG Sirocco Fan 125 (H) 22 118 (H) 42 42 φ9.5 (Flare) φ15.9 (Flare) I.D.φ25×O.D.φ32
m²
Safety Devices
Ref. Oil
— R125KUYAL 11.6 / 11.4 / — 14.5 / 14.3 / 12.5 39,700 / 38,900 / — 49,600 / 48,800 / 42,700 10,000 / 9,800 / — 12,500 / 12,300 / 10,800 FDYM04FAVAL FDYM05FAVAL 295×1,500×680 295×1,500×680 Cross Fin Coil 3×14×1.75 3×14×1.75 0.338 0.338 3D18H2AN1V1 3D18H2AP1V1 Sirocco Fan Sirocco Fan 135 225 (H) 28 (H) 38 118 118 (H) 42 (H) 47 56 57 φ9.5 (Flare) φ9.5 (Flare) φ19.1 (Flare) φ19.1 (Flare) I.D.φ25×O.D.φ32 I.D.φ25×O.D.φ32 BRC1C61 BRC4C64 R100KUVAL —
FDYM06FAVAL
—
Cross Fin Coil 2×54×2.0 2×54×2.0 2×60×2.0 0.979 0.979 1.088 JT118BC – VH — — — JT150BC JT170BC — JT150BC – YH JT170BC – YH Hermetically Sealed Scroll Type 2.2 3.0 3.75 4.5 P45J11SM P45J11SM×2 P45J11SM×2 P45J11SM×2 Propeller Propeller Propeller Propeller 75 65 + 50 65 + 50 120 + 100 54 92 92 103 49 52 52 56 82 106 104 109 φ9.5 (Flare) φ9.5 (Flare) φ9.5 (Flare) φ9.5 (Flare) φ15.9 (Flare) φ19.1 (Flare) φ19.1 (Flare) φ19.1 (Flare) φ26.0 (Hole) φ26.0 (Hole) φ26.0 (Hole) φ26.0 (Hole) Thermal protector for outdoor fan motor and indoor fan motor. High pressure switch. Low pressure switch. Over current relay (compressor). Reverse phase protector (TAL, YAL). Fuse. 100 – 0 100 – 0 100 – 0 100 – 0 Expansion Valve (Electronic Type) 50 (Equivalent Length 70m) 50 (Equivalent Length 70m) 50 (Equivalent Length 70m) 50 (Equivalent Length 70m) 30 30 30 30 R22 R22 R22 R22 3.9 (Charged for 30m) 3.0 (Charged for 30m) 3.4 (Charged for 30m) 3.7 (Charged for 30m) 2.7 (Charged for 5m) (-K) SUNISO 4GSDID – K SUNISO 4GSDID – K SUNISO 4GSDID – K SUNISO 4GSDID – K 1.2 1.5 1.5 1.6 4D020833A 4D028208A, 4D028027A 2×36×2.0 0.653 JT85BC – VH — —
1 Nominal capacities are based on the following conditions. !1 Cooling
Piping Length
Remark —
Conversion Formulae kcal/h=kW×860 Btu/h=kW×3414 cfm=m³/min×35.3
(1)
Indoor 27°C(81°F)DB, 19.5°C(67°F)WB Outdoor 35°C(95°F)DB, 24°C(75°F)WB
5m (Horizontal)
(2)
Indoor 27°C(81°F)DB, 19.0°C(66°F)WB Outdoor 35°C(95°F)DB, 24°C(75°F)WB
5m (Horizontal)
—
7.5m (Horizontal)
Applied to R125KUYAL R140KUTALK R140KUYALK
(3) SSA 385/386
3×14×1.75 0.338 3D18H2AF1 Sirocco Fan 290 (H) 40 118 (H) 49 57 φ9.5 (Flare) φ19.1 (Flare) I.D.φ25×O.D.φ32
Indoor 29°C(84°F)DB, 19.0°C(66°F)WB Outdoor 46°C(115°F)DB, 24°C(75°F)WB
2 Capacities are net, including a deduction for cooling for indoor fan motor heat. 3 In case of drain piping for outdoor unit, central drain plug (option) is needed.
8
Indoor Unit FD(Y)M03~06FA
ED40-017A
Specification
Indoor Units Models
Outdoor Units
!1 Cooling Capacity (1)/(2)/(3) !3 Indoor Units Dimensions H×W×D Type Coil Row×Stages×Fin Pitch Face Area Model Type Fan Motor Output Air Flow Rate External Static Pressure Sound Pressure Level Machine Weight Liquid Piping Connections Gas Drain Wired Remote Controller (Option) Wireless
Outdoor Units Colour Dimensions Coil
H×W×D Type Row×Stages×Fin Pitch Face Area Model
Comp.
Type Motor Output Model Type Fan Motor Output Air Flow Rate Sound Pressure Level Machine Weight Liquid Piping Connections Gas Drain
FDYM03FAVAL×3
FDYM04FAVAL×2
FDYM05FAVAL×2
TAL
R200KUTAL
R200KUTAL
R250KUTAL
YAL kW Btu/h kcal/h
R200KUYAL 22.5 / 22.2 / 20.0 76,800 / 75,800 / 68,300 19,400 / 19,100 / 17,200 FDYM03FAVAL×3 295×1,100×680
mm
m²
W m³/min Pa dB(A) kg mm mm mm
TAL
R200KUTAL
YAL
R200KUYAL Ivory 1,220×1,280×690
mm
m² TAL YAL kW
W m³/min dB(A) kg mm mm mm
Safety Devices Capacity Step Refrigerant Control Max. Length Ref. Piping Max. Height Difference Model Refrigerant Charge Model Ref. Oil Charge Drawing No.
Note:
3×14×1.75 0.221 2D18H2AB1VG Sirocco Fan 125 (H) 22 118 (H) 42 42 φ9.5 (Flare) φ15.9 (Flare) I.D.φ25×O.D.φ32
% m m kg L
R200KUYAL R250KUYAL 22.5 / 22.2 / 20.0 27.1 / 26.6 / 24.1 76,800 / 75,800 / 68,300 92,500 / 90,800 / 82,300 19,400 / 19,100 / 17,200 23,300 / 22,900 / 20,700 FDYM04FAVAL×2 FDYM05FAVAL×2 295×1,500×680 295×1,500×680 Cross Fin Coil (Waffle Louver Fins and Hi-XA Tubes) 3×14×1.75 3×14×1.75 0.338 0.338 3D18H2AN1V1 3D18H2AP1V1 Sirocco Fan Sirocco Fan 135 225 (H) 28 (H) 38 118 118 (H) 42 (H) 47 56 57 φ9.5 (Flare) φ9.5 (Flare) φ19.1 (Flare) φ19.1 (Flare) I.D.φ25×O.D.φ32 I.D.φ25×O.D.φ32 BRC1C61 BRC4C64 R200KUTAL R250KUTAL
R200KUYAL R250KUYAL Ivory Ivory 1,220×1,280×690 1,440×1,280×690 Cross Fin Coil (Waffle Louver Fins and Hi-XA Tubes) 2×40×2.0 2×40×2.0 2×50×2.0 1.57 1.57 1.97 JT212D – P1 JT212D – P1 JT300D – P1 JT212D – P1YH JT212D – P1YH JT300D – P1YH Hermetically Sealed Scroll Type 5.5 5.5 7.5 P52H11SM P52H11SM P52H11SM Propeller Propeller Propeller 230 + 190 230 + 190 230 + 190 160 160 190 60 60 61 177 177 200 φ12.7 (Flare) φ12.7 (Flare) φ15.9 (Flare) φ25.4 (Flange) φ25.4 (Flange) φ28.6 (Flange) — — — Thermal protector for compressor, outdoor fan motor and indoor fan motor. High pressure switch. Low pressure switch. Over current relay (compressor). Reverse phase protector. Fuse. 100 – 0 100 – 0 100 – 0 Capillary Tube 50 (Equivalent Length 70m) 50 (Equivalent Length 70m) 50 (Equivalent Length 70m) 30 30 30 R22 R22 R22 5.3 (Charged for 5m) 5.3 (Charged for 5m) 5.7 (Charged for 5m) SUNISO 4GSDID – K SUNISO 4GSDID – K SUNISO 4GSDID – K 3.0 3.0 3.0 4D029968 4D029970
1 Nominal capacities are based on the following conditions. !1 Cooling
Piping Length
Hz-Volts
(1)
Indoor: 27°CDB, 19.5°CWB Outdoor: 35°CDB, 24°CWB
5m (Horizontal)
60Hz-220V 60Hz-380V
(2)
Indoor: 27°CDB, 19.0°CWB Outdoor: 35°DB, 24°CWB
5m (Horizontal)
60Hz-220V 60Hz-380V
(3) Indoor: 29°CDB, 19.0°CWB 7.5m (Horizontal) SSA 385/386 Outdoor: 46°CDB, 24°CWB 2 Capacities are net, including a deduction for cooling for indoor fan motor heat. !3 Each value for indoor unit shows the specification per one unit.
Indoor Unit FD(Y)M03~06FA
1
Conversion Formulae kcal/h=kW×860 Btu/h=kW×3414 cfm=m³/min×35.3
60Hz-220V 60Hz-380V
9
Specification
ED40-017A
FDM-FA + R-FU Indoor Units Models
Outdoor Units
!1 Cooling Capacity (1)/(2)/(3)
FDM03FAVAL
FDM04FAVAL
VAL
R71FUVAL
R100FUVAL
—
TAL kW Btu/h kcal/h
— 8.3 / 8.1 / 6.7 28,200 / 27,800 / 22,900 7,100 / 7,000 / 5,800 FDM03FAVAL 295×1,100×680
— 11.6 / 11.4 / 9.0 39,700 / 38,900 / 30,700 10,000 / 9,800 / 7,700 FDM04FAVAL 295×1,500×680 Cross Fin Coil 3×14×1.75 0.338 3D18H2AN1V1 Sirocco Fan 135 (H) 28 118 (H) 42 56 φ9.5 (Flare) φ19.1 (Flare) I.D.φ25×O.D.φ32 BRC1C61 BRC4C64 R100FUVAL
R125FUTAL 14.5 / 14.3 / 12.5 49,600 / 48,800 / 42,700 12,500 / 12,300 / 10,800 FDM05FAVAL 295×1,500×680
Indoor Units Dimensions
H×W×D Type Coil Row×Stages×Fin Pitch Face Area Model Type Fan Motor Output Air Flow Rate External Static Pressure Sound Pressure Level Machine Weight Liquid Piping Connections Gas Drain Wired Remote Controller (Option) Wireless Outdoor Units Colour Dimensions Coil
mm
W m³/min Pa dB(A) kg mm mm mm
3×14×1.75 0.221 2D18H2AB1VG Sirocco Fan 125 (H) 22 118 (H) 42 42 φ9.5 (Flare) φ15.9 (Flare) I.D.φ25×O.D.φ32
VAL
R71FUVAL
m²
Model Comp.
Type No. of Cylinders Motor Output Model Type Fan Motor Output Air Flow Rate Sound Pressure Level Machine Weight Liquid Piping Connections Gas Drain Safety Devices Capacity Step Refrigerant Control Max. Length Ref. Piping Max. Height Difference Model Refrigerant Charge Model Ref. Oil Charge Drawing No.
Note:
3×14×1.75 0.338 3D18H2AP1V1 Sirocco Fan 225 (H) 38 118 (H) 47 57 φ9.5 (Flare) φ19.1 (Flare) I.D.φ25×O.D.φ32
—
— R125FUTAL Ivory Ivory mm 1,215×880×370 1,215×880×370 Cross Fin Coil 2×36×2.0 2×54×2.0 2×54×2.0 m² 0.653 0.979 0.979 VAL H23A35QABCA H23A46QABCA — TAL — — H23A62QDBLA Hermetically Sealed Type 2 2 2 kW 2.2 3.0 3.75 P45J11SM P45J11SM×2 P45J11SM×2 Propeller Propeller Propeller W 80 90 + 60 90 + 80 m³/min 55 92 98 dB(A) 53 57 59 kg 87 117 110 mm φ9.5 (Flare) φ9.5 (Flare) φ9.5 (Flare) φ15.9 (Flare) φ19.1 (Flare) φ19.1 (Flare) mm φ26.0 (Hole) φ26.0 (Hole) φ26.0 (Hole) mm Thermal protector for outdoor fan motor and indoor fan motor. Internal pressure relief valve. (compressor) Motor protector. (compressor) % 100 – 0 100 – 0 100 – 0 Capillary Tube m 50 (Equivalent Length 70m) 50 (Equivalent Length 70m) 50 (Equivalent Length 70m) m 30 30 30 R22 R22 R22 kg 2.2 (Charged for 5m) 2.9 (Charged for 5m) 3.1 (Charged for 5m) SUNISO 3GS SUNISO 3GS SUNISO 3GS L 1.48 1.63 1.63 4D020831A TAL
H×W×D Type Row×Stages×Fin Pitch Face Area
FDM05FAVAL
— Ivory 816×880×370
1 Nominal capacities are based on the following conditions. !1 Cooling
Piping Length
(1)
Indoor 27°C(81°F)DB, 19.5°C(67°F)WB Outdoor 35°C(95°F)DB, 24°C(75°F)WB
5m (Horizontal)
(2)
Indoor 27°C(81°F)DB, 19.0°C(66°F)WB Outdoor 35°C(95°F)DB, 24°C(75°F)WB
5m (Horizontal)
Conversion Formulae kcal/h=kW×860 Btu/h=kW×3414 cfm=m³/min×35.3
(3) Indoor 29°C(84°F)DB, 19.0°C(66°F)WB 7.5m (Horizontal) SSA 385/386 Outdoor 46°C(115°F)DB, 24°C(75°F)WB 2 Capacities are net, including a deduction for cooling for indoor fan motor heat. 3 In case of drain piping for outdoor unit, central drain plug (option) is needed.
10
Indoor Unit FD(Y)M03~06FA
ED40-017A
Specification
3.2
Heat Pump
3.2.1
50Hz
1
FDYM-FA + RY-KU Indoor Units Models
Outdoor Units
!1 Cooling Capacity (1)/(2)/(3)
!1 Heating Capacity (1)/(2)/(3)
Indoor Units Dimensions
H×W×D Type Coil Row×Stages×Fin Pitch Face Area Model Type Fan Motor Output AFR !2 External Static Pressure Sound Pressure Level !2 Machine Weight Liquid Piping Connections Gas Drain Wired Remote Controller (Option) Wireless Outdoor Units Colour Dimensions Coil
H×W×D Type Row×Stages×Fin Pitch Face Area Model
Comp.
Type Motor Output Model Type Fan Motor Output AFR (C/H) !2 Sound Pressure Level (C/H) !2
FDYM03FAV1
FDYM04FAV1
FDYM05FAV1
V1
RY71KUV1
RY100KUV1
—
Y1 kW Btu/h kcal/h kW Btu/h kcal/h
RY71KUY1 7.8 / 7.7 / 7.7 26,600 / 26,200 / 26,200 6,700 / 6,600 / 6,600 7.9 / 7.9 / 7.9 27,000 / 27,000 / 27,000 6,800 / 6,800 / 6,800 FDYM03FAV1 295×1,100×680
mm
W m³/min Pa dB(A) kg mm mm mm
3×14×1.75 0.221 2D18H2AB1VG Sirocco Fan 125 (H) 20 – 22 98 (H) 39 – 41 42 φ9.5 (Flare) φ15.9 (Flare) I.D.φ25×O.D.φ32
V1
RY71KUV1
Y1
RY71KUY1 Ivory 816×880×370
m²
mm
m² V1 Y1 kW
Machine Weight
kg
Piping Connections
Liquid Gas Drain
W m³/min dB(A) V1 Y1 mm mm mm
Safety Devices Capacity Step Refrigerant Control Max. Length Ref. Piping Max. Height Difference Model Refrigerant Charge Model Ref. Oil Charge Drawing No.
Note:
% m m kg L
RY100KUY1 RY125KUY1 10.5 / 10.4 / 10.4 13.0 / 12.8 / 12.8 35,700 / 35,300 / 35,300 44,500 / 43,600 / 43,600 9,000 / 8,900 / 8,900 11,200 / 11,000 / 11,000 11.2 / 11.2 / 11.2 14.2 / 14.2 / 14.2 38,100 / 38,100 / 38,100 48,400 / 48,400 / 48,400 9,600 / 9,600 / 9,600 12,200 / 12,200 / 12,200 FDYM04FAV1 FDYM05FAV1 295×1,500×680 295×1,500×680 Cross Fin Coil 3×14×1.75 3×14×1.75 0.338 0.338 3D18H2AN1V1 3D18H2AP1V1 Sirocco Fan Sirocco Fan 135 225 (H) 26 – 28 (H) 35 – 40.5 98 98 (H) 39 – 41 (H) 44 – 46 56 57 φ9.5 (Flare) φ9.5 (Flare) φ19.1 (Flare) φ19.1 (Flare) I.D.φ25×O.D.φ32 I.D.φ25×O.D.φ32 BRC1C61 BRC4C62 RY100KUV1 — RY100KUY1 Ivory 1,215×880×370
3×14×1.75 0.338 3D18H2AP1V1 Sirocco Fan 290 (H) 37 – 42 98 (H) 46 – 48 57 φ9.5 (Flare) φ19.1 (Flare) I.D.φ25×O.D.φ32
— RY140KUY1 Ivory 1,345×880×370
Cross Fin Coil 2×54×2.0 2×54×2.0 2×60×2.0 0.979 0.979 1.088 JT125BC – V1 — — JT125BC – YE JT160BC – YE JT170BC – YE Hermetically Sealed Scroll Type 2.2 3.0 3.75 4.5 P45J11SM P45J11SM×2 P45J11SM×2 P45J11SM×2 Propeller Propeller Propeller Propeller 60 70 + 55 70 + 55 90 + 80 46 – 48 / 41 – 43 87 – 89 / 78 – 80 87 – 89 / 78 – 80 101 – 103 / 91 – 93 48 – 49 / 50 – 51 50 – 51 / 53 – 54 50 – 51 / 53 – 54 55 – 56 / 57 – 58 83 108 — — 80 105 106 112 φ9.5 (Flare) φ9.5 (Flare) φ9.5 (Flare) φ9.5 (Flare) φ15.9 (Flare) φ19.1 (Flare) φ19.1 (Flare) φ19.1 (Flare) φ26.0 (Hole) φ26.0 (Hole) φ26.0 (Hole) φ26.0 (Hole) Thermal protector for outdoor fan motor and indoor fan motor. High pressure switch. Low pressure switch. Over current relay (compressor). Reverse phase protector (Y1). Fuse. 100 – 0 100 – 0 100 – 0 100 – 0 Expansion Valve (Electronic Type) 50 (Equivalent Length 70m) 50 (Equivalent Length 70m) 50 (Equivalent Length 70m) 50 (Equivalent Length 70m) 30 30 30 30 R22 R22 R22 R22 3.0 (Charged for 30m) 3.4 (Charged for 30m) 3.7 (Charged for 30m) 3.9 (Charged for 30m) SUNISO 4GSDID – K SUNISO 4GSDID – K SUNISO 4GSDID – K SUNISO 4GSDID – K 1.2 1.5 1.5 1.6 4D021042 4D028033A
27°CDB, 19.5°CWB Outdoor 35°CDB, 24°CWB
Indoor Outdoor
7°CDB, 6°CWB
Indoor
Indoor
20°CDB
Outdoor
7°CDB, 6°CWB
Indoor
(2)
— RY140KUY1 14.5 / 14.2 / 14.2 49,400 / 48,400 / 48,400 12,500 / 12,200 / 12,200 16.3 / 16.3 / 16.3 56,000 / 56,000 / 56,000 14,000 / 14,000 / 14,000 FDYM06FAV1 295×1,500×680
2×36×2.0 0.653 JT95BC – V1 JT95BC – YE
1 Nominal capacities are based on the following conditions. !1 Cooling !1 Heating Piping Length (1)
RY125KUY1 Ivory 1,215×880×370
FDYM06FAV1
27°CDB, 19.0°CWB Outdoor 35°CDB, 24°CWB
Hz – Volts
21°CDB 5m
50Hz – 220V(380V)
5m
50Hz – 220V(380V)
Conversion Formulae kcal/h=kW×860 Btu/h=kW×3414 cfm=m³/min×35.3
Indoor
27°CDB, Indoor 21°CDB 50Hz – 19.0°CWB 7.5m 240V(415V) Outdoor 35°CDB, Outdoor 7°CDB, 24°CWB 6°CWB !2 AFR (Air Flow Rate) and sound pressure level are shown at 220V(380V)-240V(415V). 3 Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat. 4 In case of drain piping for outdoor unit, central drain plug (option) is needed. (3)
Indoor Unit FD(Y)M03~06FA
11
Specification
Models
ED40-017A
Indoor Units
FDYM03FAV1×3
Outdoor Units kW Btu/h kcal/h kW Btu/h kcal/h
!1 Cooling Capacity (1)/(2)/(3)
!1 Heating Capacity (1)/(2)/(3) !4 Indoor Units
Dimensions
H×W×D Type Coil Row×Stages×Fin Pitch Face Area Model Type Fan Motor Output AFR !2 External Static Pressure Sound Pressure Level !2 Machine Weight Liquid Piping Connections Gas Drain Wired Remote Controller (Option) Wireless Outdoor Units Colour Dimensions H×W×D Type Coil Row×Stages×Fin Pitch Face Area Model Comp. Type Motor Output Model Type Fan Motor Output AFR (C/H) !2 Sound Pressure Level (C/H) !2 Machine Weight Liquid Piping Connections Gas Drain
mm
m²
W m³/min Pa dB(A) kg mm mm mm
mm
m²
kW
W m³/min dB(A) kg mm mm mm
Safety Devices Capacity Step Refrigerant Control Max. Length Ref. Piping Max. Height Difference Model Refrigerant Charge Model Ref. Oil Charge Drawing No.
Note:
% m m kg L
FDYM04FAV1×2
RY200KUY1 RY250KUY1 22.5 / 22.2 / 22.0 27.1 / 26.6 / 26.3 76,800 / 75,800 / 75,100 92,500 / 90,800 / 89,800 19,400 / 19,100 / 18,900 23,300 / 22,900 / 22,600 22.6 / 22.7 / 22.4 28.3 / 28.4 / 28.0 77,200 / 77,500 / 76,500 96,600 / 97,000 / 95,600 19,400 / 19,500 / 19,300 24,300 / 24,400 / 24,100 FDYM04FAV1×2 FDYM05FAV1×2 295×1,500×680 295×1,500×680 Cross Fin Coil (Waffle Louver Fins and Hi-XA Tubes) 3×14×1.75 3×14×1.75 3×14×1.75 0.221 0.338 0.338 2D18H2AB1VG 3D18H2AN1V1 3D18H2AP1V1 Sirocco Fan Sirocco Fan Sirocco Fan 125 135 225 (H) 20 – 22 (H) 26 – 28 (H) 35 – 40.5 98 98 98 (H) 39 – 41 (H) 39 – 41 (H) 44 – 46 42 56 57 φ9.5 (Flare) φ9.5 (Flare) φ9.5 (Flare) φ15.9 (Flare) φ19.1 (Flare) φ19.1 (Flare) I.D.φ25×O.D.φ32 I.D.φ25×O.D.φ32 I.D.φ25×O.D.φ32 BRC1C61 BRC4C62 RY200KUY1 RY200KUY1 RY250KUY1 Ivory Ivory Ivory 1,220×1,280×690 1,220×1,280×690 1,440×1,280×690 Cross Fin Coil (Waffle Louver Fins and Hi-XA Tubes) 2×40×2.0 2×40×2.0 2×50×2.0 1.57 1.57 1.97 JT236D – P1YE JT236D – P1YE JT335D – P1YE Hermetically Sealed Scroll Type 5.5 5.5 9.0 P52H11SM P52H11SM P52H11SM Propeller Propeller Propeller 230 + 190 230 + 190 230 + 190 150 / 138 – 154 / 142 150 / 138 – 154 / 142 175 / 161 –179 / 165 60 / 62 – 61 / 63 60 / 62 – 61 / 63 61 / 63 – 62 / 64 180 180 206 φ12.7 (Flare) φ12.7 (Flare) φ15.9 (Flare) φ25.4 (Flange) φ25.4 (Flange) φ28.6 (Flange) — — — Thermal protector for compressor, outdoor fan motor and indoor fan motor. High pressure switch. Low pressure switch. Over current relay (compressor). Reverse phase protector. Fuse. 100 – 0 100 – 0 100 – 0 Capillary Tube 50 (Equivalent Length 70m) 50 (Equivalent Length 70m) 50 (Equivalent Length 70m) 30 30 30 R22 R22 R22 4.0 (Charged for 5m) 4.0 (Charged for 5m) 5.5 (Charged for 5m) SUNISO 4GSDID – K SUNISO 4GSDID – K SUNISO 4GSDID – K 3.0 3.0 3.0 4D029816 4D029818
1 Nominal capacities are based on the following conditions. !1 Cooling !1 Heating Piping Length 27°CDB, 19.5°CWB Outdoor 35°CDB, 24°CWB
Indoor
Indoor
Indoor
Indoor (1)
(2)
FDYM05FAV1×2
RY200KUY1 22.5 / 22.2 / 22.0 76,800 / 75,800 / 75,100 19,400 / 19,100 / 18,900 22.6 / 22.7 / 22.4 77,200 / 77,500 / 76,500 19,400 / 19,500 / 19,300 FDYM03FAV1×3 295×1,100×680
27°CDB, 19.0°CWB Outdoor 35°CDB, 24°CWB
Outdoor
Outdoor
Conversion Formulae
Hz – Volts
21°CDB, 15°CWB 7°CDB, 6°CWB
5m (Horizontal)
50Hz – 380V
20°CDB, 15°CWB 7°CDB, 6°CWB
5m (Horizontal)
50Hz – 380V
kcal/h=kW×860 Btu/h=kW×3414 cfm=m³/min×35.3
Indoor
27°CDB, Indoor 21°CDB, 19.0°CWB 15°CWB 7.5m 50Hz – 415V (Horizontal) Outdoor 35°CDB, Outdoor 7°CDB, 24°CWB 6°CWB !2 AFR (Air Flow Rate) and sound pressure level are shown at 220V(380V)-240V(415V). 3 Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat. !4 Each value for indoor unit shows the specification per one unit. (3)
12
Indoor Unit FD(Y)M03~06FA
ED40-017A
3.2.2
Specification
60Hz
1
FDYM-FA + RY-KU Indoor Units Models
Outdoor Units
!1 Cooling Capacity (1)/(2)/(3)
!1 Heating Capacity (1)/(2)/(3)
FDYM06FAVAL
FDYM03FAVAL×3
FDYM04FAVAL×2
FDYM05FAVAL×2
TAL
RY140KUTAL(K)
RY200KUTAL
RY200KUTAL
RY250KUTAL
YAL kW Btu/h kcal/h kW Btu/h kcal/h
RY140KUYAL(K) 16.1 / 15.8 / 14.0 55,000 / 53,900 / 47,800 13,800 / 13,500 / 12,000 18.1 / 18.1 / 17.0 61,900 / 61,900 / 58,000 15,600 / 15,600 / 14,600 FDYM06FAVAL 295×1,500×680 Cross Fin Coil 3×14×1.75 0.338 3D18H2AF1 Sirocco Fan 290 (H) 40 118 (H) 49 57 φ9.5 (Flare) φ19.1 (Flare) I.D.φ25×O.D.φ32
!3 Indoor Units
Dimensions
H×W×D Type Coil Row×Stages×Fin Pitch Face Area Model Type Fan Motor Output Air Flow Rate External Static Pressure Sound Pressure Level Machine Weight Liquid Piping Connections Gas Drain Wired Remote Controller (Option) Wireless Outdoor Units Colour Dimensions Coil
H×W×D Type Row×Stages×Fin Pitch Face Area Model
Comp.
Type Motor Output Model Type Fan Motor Output Air Flow Rate (C/H) Sound Pressure Level (C/H) Machine Weight Liquid Piping Connections Gas Drain
mm
m²
W m³/min Pa dB(A) kg mm mm mm
TAL
RY140KUTAL(K)
YAL
RY140KUYAL(K) Ivory 1,345×880×370 Cross Fin Coil 2×60×2.0 1.088 JT170BC JT170BC – YH
mm
m² TAL YAL kW
W m³/min dB(A) kg mm mm mm
Safety Devices Capacity Step
%
Refrigerant Control Ref. Piping Refrigerant Ref. Oil
Max. Length Max. Height Difference Model
m m
Charge
kg
Model Charge
L
Drawing No.
Note:
RY200KUYAL RY200KUYAL RY250KUYAL 22.5 / 22.2 / 20.0 22.5 / 22.2 / 20.0 27.1 / 26.6 / 24.1 76,800 / 75,800 / 68,300 76,800 / 75,800 / 68,300 92,500 / 90,800 / 82,300 19,400 / 19,100 / 17,200 19,400 / 19,100 / 17,200 23,300 / 22,900 / 20,700 22.6 / 22.7 / 22.4 22.6 / 22.7 / 22.4 28.3 / 28.4 / 28.0 77,200 / 77,500 / 76,500 77,200 / 77,500 / 76,500 96,600 / 97,000 / 95,600 19,400 / 19,500 / 19,300 19,400 / 19,500 / 19,300 24,300 / 24,400 / 24,100 FDYM03FAVAL×3 FDYM04FAVAL×2 FDYM05FAVAL×2 295×1,100×680 295×1,500×680 295×1,500×680 Cross Fin Coil (Waffle Louver Fins and Hi-XA Tubes) 3×14×1.75 3×14×1.75 3×14×1.75 0.221 0.338 0.338 2D18H2AB1VG 3D18H2AN1V1 3D18H2AP1V1 Sirocco Fan Sirocco Fan Sirocco Fan 125 135 225 (H) 22 (H) 28 (H) 38 118 118 118 (H) 42 (H) 42 (H) 47 42 56 57 φ9.5 (Flare) φ9.5 (Flare) φ9.5 (Flare) φ15.9 (Flare) φ19.1 (Flare) φ19.1 (Flare) I.D.φ25×O.D.φ32 I.D.φ25×O.D.φ32 I.D.φ25×O.D.φ32 BRC1C61 BRC4C62 RY200KUTAL RY200KUTAL RY250KUTAL
RY200KUYAL RY200KUYAL RY250KUYAL Ivory Ivory Ivory 1,220×1,280×690 1,220×1,280×690 1,440×1,280×690 Cross Fin Coil (Waffle Louver Fins and Hi-XA Tubes) 2×40×2.0 2×40×2.0 2×50×2.0 1.57 1.57 1.97 JT212D – P1 JT212D – P1 JT300D – P1 JT212D – P1YH JT212D – P1YH JT300D – P1YH Hermetically Sealed Scroll Type 4.5 5.5 5.5 7.5 P45J11SM×2 P52H11SM P52H11SM P52H11SM Propeller Propeller Propeller Propeller 120 + 100 230 + 190 230 + 190 230 + 190 103 / 93 160 / 147 160 / 147 190 / 175 56 / 58 60 / 62 60 / 62 61 / 63 112 179 179 204 φ9.5 (Flare) φ12.7 (Flare) φ12.7 (Flare) φ15.9 (Flare) φ19.1 (Flare) φ25.4 (Flange) φ25.4 (Flange) φ28.6 (Flange) φ26.0 (Hole) — — — Thermal protector for compressor (for RY200KUTAL, RY200KUYAL), outdoor fan motor and indoor fan motor. High pressure switch. Low pressure switch. Over current relay (compressor). Reverse phase protector. Fuse. 100 – 0 100 – 0 100 – 0 100 – 0 Expansion Valve Capillary Tube (Electronic Type) 50 (Equivalent Length 70m) 50 (Equivalent Length 70m) 50 (Equivalent Length 70m) 50 (Equivalent Length 70m) 30 30 30 30 R22 R22 R22 R22 3.9 (Charged for 30m) 4.0 (Charged for 5m) 4.0 (Charged for 5m) 5.5 (Charged for 5m) 2.7 (Charged for 5m) (-K) SUNISO 4GSDID – K SUNISO 4GSDID – K SUNISO 4GSDID – K SUNISO 4GSDID – K 1.6 3.0 3.0 3.0 4D028208A, 4D028027A 4D029817 4D029819
1 Nominal capacities are based on the following conditions. !1 Cooling
Indoor: (1)
(2)
!1 Heating
27°C(81°F)DB, 19.5°C(67°F)WB Outdoor: 35°C(95°F)DB, 24°C(75°F)WB
Indoor:
Indoor:
Indoor:
27°C(81°F)DB, 19.0°C(66°F)WB Outdoor: 35°C(95°F)DB, 24°C(75°F)WB
21°C(70°F)DB, 15°CWB Outdoor: 7°C(45°F)DB, 6°C(43°F)WB 20°C(68°F)DB, 15°CWB Outdoor: 7°C(45°F)DB, 6°C(43°F)WB
Piping Length
Conversion Formulae Hz-Volts
5m 60Hz – 220V (Horizontal) 60Hz – 380V
kcal/h=kW×860 Btu/h=kW×3414 cfm=m³/min×35.3
5m 60Hz – 220V (Horizontal) 60Hz – 380V
Indoor: 21°C(70°F)DB, 29°C(84°F)DB, 7.5m 60Hz – 220V 15°CWB 19.0°C(66°F)WB (Horizontal) 60Hz – 380V Outdoor: 46°C(115°F)DB, Outdoor: 7°C(45°F)DB, 6°C(43°F)WB 24°C(75°F)WB 2 Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat. !3 Each value for indoor unit shows the specification per one unit. 4 In case of drain piping for outdoor unit, central drain plug (option) is needed. (RY140KUTAL(K), YAL(K)) Indoor:
(3) SSA 385/386
Indoor Unit FD(Y)M03~06FA
13
Specification
ED40-017A
FDYM-FA + RY-FU Indoor Units Models
Outdoor Units
!1 Cooling Capacity (1)/(2)/(3)
!1 Heating Capacity (1)/(2)/(3)
FDYM03FAVAL
FDYM04FAVAL
VAL
RY71FUVAL
RY100FUVAL
—
TAL kW Btu/h kcal/h kW Btu/h kcal/h
— 8.3 / 8.1 / 6.7 28,200 / 27,800 / 22,900 7,100 / 7,000 / 5,800 9.0 / 9.0 / 8.5 30,600 / 30,600 / 29,000 7,700 / 7,700 / 7,300 FDYM03FAVAL 295×1,100×680
— 11.6 / 11.4 / 9.0 39,700 / 38,900 / 30,700 10,000 / 9,800 / 7,700 12.8 / 12.8 / 11.8 43,700 / 43,700 / 40,300 11,000 / 11,000 / 10,100 FDYM04FAVAL 295×1,500×680 Cross Fin Coil 3×14×1.75 0.338 3D18H2AN1V1 Sirocco Fan 135 (H) 28 118 (H) 42 56 φ9.5 (Flare) φ19.1 (Flare) I.D.φ25×O.D.φ32 BRC1C61 BRC4C62 RY100FUVAL
RY125FUTAL 14.5 / 14.3 / 12.5 49,600 / 48,800 / 42,700 12,500 / 12,300 / 10,800 16.2 / 16.2 / 15.0 55,200 / 55,200 / 51,200 13,900 / 13,900 / 12,900 FDYM05FAVAL 295×1,500×680
Indoor Units Dimensions
H×W×D Type Coil Row×Stages×Fin Pitch Face Area Model Type Fan Motor Output Air Flow Rate External Static Pressure Sound Pressure Level Machine Weight Liquid Piping Connections Gas Drain Wired Remote Controller (Option) Wireless
Outdoor Units Colour Dimensions Coil
H×W×D Type Row×Stages×Fin Pitch Face Area Model
Comp.
Type No. of Cylinders Motor Output Model Type Fan Motor Output Air Flow Rate Sound Pressure Level (C/H) Machine Weight Liquid Piping Connections Gas Drain Safety Devices Capacity Step Refrigerant Control Max. Length Ref. Piping Max. Height Difference Model Refrigerant Charge Model Ref. Oil Charge Drawing No.
Note:
mm
W m³/min Pa dB(A) kg mm mm mm
3×14×1.75 0.221 2D18H2AB1VG Sirocco Fan 125 (H) 22 118 (H) 42 42 φ9.5 (Flare) φ15.9 (Flare) I.D.φ25×O.D.φ32
VAL
RY71FUVAL
TAL
— Ivory 816×880×370
m²
FDYM05FAVAL
3×14×1.75 0.338 3D18H2AP1V1 Sirocco Fan 225 (H) 38 118 (H) 47 57 φ9.5 (Flare) φ19.1 (Flare) I.D.φ25×O.D.φ32
—
— RY125FUTAL Ivory Ivory mm 1,215×880×370 1,215×880×370 Cross Fin Coil 2×36×2.0 2×54×2.0 2×54×2.0 m² 0.653 0.979 0.979 VAL H23A38QABCA H23A50QABCA — TAL — — H23A62QDBLA Hermetically Sealed Type 2 2 2 kW 2.2 3.0 3.75 P45J11SM P45J11SM×2 P45J11SM×2 Propeller Propeller Propeller W 80 90 + 60 90 + 80 m³/min 55 92 98 dB(A) 53 / 55 57 / 59 59 / 61 kg 91 120 115 mm φ9.5 (Flare) φ9.5 (Flare) φ9.5 (Flare) φ15.9 (Flare) φ19.1 (Flare) φ19.1 (Flare) mm φ26.0 (Hole) φ26.0 (Hole) φ26.0 (Hole) mm Thermal protector for outdoor fan motor and indoor fan motor. Internal pressure relief valve. (Compressor) Motor protector. (Compressor) % 100 – 0 100 – 0 100 – 0 Capillary tube m 50 (Equivalent Length 70m) 50 (Equivalent Length 70m) 50 (Equivalent Length 70m) m 30 30 30 R22 R22 R22 kg 2.3 (Charged for 5m) 2.6 (Charged for 5m) 3.1 (Charged for 5m) SUNISO 3GS SUNISO 3GS SUNISO 3GS L 1.48 1.63 1.63 4D020830A
1 Nominal capacities are based on the following conditions. !1 Cooling !1 Heating Mark
Piping Length
Conversion Formulae
27°C(81°F)DB, 19.5°C(67°F)WB Outdoor: 35°C(95°F)DB, 24°C(75°F)WB
Indoor: 21°C(70°F)DB Outdoor: 7°C(45°F)DB, 6°C(43°F)WB
5m (Horizontal)
kcal/h=kW×860 Btu/h=kW×3414 cfm=m³/min×35.3
Indoor:
Indoor: 20°C(68°F)DB Outdoor: 7°C(45°F)DB, 6°C(43°F)WB
5m (Horizontal)
Indoor: (1)
(2)
27°C(81°F)DB, 19.0°C(66°F)WB Outdoor: 35°C(95°F)DB, 24°C(75°F)WB
Indoor: 21°C(70°F)DB 29°C(84°F)DB, 19.0°C(66°F)WB Outdoor: 7°C(45°F)DB, 7.5m (Horizontal) 6°C(43°F)WB Outdoor: 46°C(115°F)DB, 24°C(75°F)WB !2 Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat. Indoor:
(3) SSA 385/386
14
Indoor Unit FD(Y)M03~06FA
ED40-017A
Optional Accessories
4. Optional Accessories
1
Name Of Option Wired Remote Controller Wireless Remote Controller
FDYM03~06FAV1/FAVAL FDM03~05FAV1/FAVAL BRC1C61
Heat Pump
BRC4C62
Cooling Only
BRC4C64
Central Remote Controller
DCS302B61
Unified On/Off Controller
DCS301B61
Schedule Timer
DST301B61
Group Control Adaptor
KRP4A51
Interface Adaptor for SkyAir Series
DTA102A52 C : 4D021001A
Note:
Refer to the Option Hand Book for the detail.
Indoor Unit FD(Y)M03~06FA
15
Dimensions
ED40-017A
5. Dimensions 5.1
Indoor Units
3D020891B
FDM03FA / FDYM03FA
16
Indoor Unit FD(Y)M03~06FA
ED40-017A
Dimensions
1
FDM04FA / FDYM04FA FDM05FA / FDYM05FA — / FDYM06FA
Indoor Unit FD(Y)M03~06FA
17
Remote Controller
ED40-017A
6. Remote Controller 6.1
Dimensions
BRC1C61
3D028952
BRC4C62 / BRC4C64
3D007898
18
Indoor Unit FD(Y)M03~06FA
ED40-017A
Remote Controller
6.2
Operation
6.2.1
Wired Remote Controller
1 5 11
Fig. 1
4
2
1
3 7
hr
C hr
6 8
NOT AVAILABLE
TEST
9 10
L H
12
13
20 19 TEST
15
18
14
16
NAME AND FUNCTION OF EACH SWITCH AND DISPLAY ON THE REMOTE CONTROLLER The illustrations in this operating manual correspond to the remote control format BRC1C type. Although the display and shape of the buttons on the BRC1B type are slightly different, they may be operated in the same manner.
3
9 10
3PN02535-7L-0
DISPLAY “
” (FAN SPEED)
This display shows the set fan speed. DISPLAY “ FILTER)
” (TIME TO CLEAN AIR
Not applied on this model.
11
DISPLAY “
” (DEFROST)
DISPLAY “ ” (UNDER CENTRALIZED CONTROL)
NON-FUNCTIONING DISPLAY If that particular function is not available, pressing the button may display the words “NOT AVAILABLE” for a few seconds. 12 When running multiple units simultaneously The “NOT AVAILABLE” message will only be appear if none of the indoor units is equipped with the function. If even one unit is equipped with the function, the display will not appear.
When this display shows, the system is UNDER CENTRALIZED CONTROL.
13
ON/OFF BUTTON 1 Press the button and the system will start. Press the button again and the system will stop.
2
17
OPERATION LAMP (RED) The lamp lights up during operation.
DISPLAY “ ”“ ”“ ”“ (VENTILATION/AIR CLEANING)
”
4 This display shows that the total heat exchange and the air cleaning unit are in operation (These are optional accessories). DISPLAY “ ” “ ” “ (OPERATION MODE)
”“
”“
”
5 This display shows the current OPERATION MODE. For cooling only type, “ ” (Auto) and “ ” (Heating) are not installed. DISPLAY “ TEST” (INSPECTION/TEST OPERATION)
6 When the INSPECTION/TEST OPERATION BUTTON is pressed, the display shows the system mode is in. hr
DISPLAY “
” (PROGRAMMED TIME) hr
7 This display shows the PROGRAMMED TIME of the system start or stop. DISPLAY “
C
” (SET TEMPERATURE)
8 This display shows the set temperature.
14
TIMER MODE START/STOP BUTTON TIMER ON/OFF BUTTON
INSPECTION/TEST OPERATION BUTTON 15 This button is used only by qualified service persons for maintenance purposes. PROGRAMMING TIME BUTTON 16 Use this button for programming “START and/or STOP” time. TEMPERATURE SETTING BUTTON 17 Use this button for SETTING TEMPERATURE.
18
FILTER SIGN RESET BUTTON Not applied on this model.
FAN SPEED CONTROL BUTTON 19 Press this button to select the fan speed, HIGH or LOW, of your choice. OPERATION MODE SELECTOR BUTTON 20 Press this button to select OPERATION MODE.
NOTE For the sake of explanation, all indications are shown on the display in figure 1 contrary to actual running situations. 3PN02535-7L-4
Indoor Unit FD(Y)M03~06FA
19
Remote Controller
6.2.2
ED40-017A
Wireless Remote Controller
Fig.1
20
Fig.2
Indoor Unit FD(Y)M03~06FA
ED40-017A
Wiring Diagrams
7. Wiring Diagrams
1
FDYM03FAV1 / FDYM03FAVAL FDYM04FAV1 / FDYM04FAVAL FDYM05FAV1 / FDYM05FAVAL FDYM06FAV1 / FDYM06FAVAL
Indoor Unit FD(Y)M03~06FA
21
Wiring Diagrams
ED40-017A
FDM03FAV1 / FDM03FAVAL FDM04FAV1 / FDM04FAVAL FDM05FAV1 / FDM05FAVAL
22
Indoor Unit FD(Y)M03~06FA
ED40-017A
Sound Level
8. Sound Level 8.1
Overall Sound Level
8.1.1
50Hz Model
220V
240V
39
41
44
46
39
41
FDYM05FAV1
44
46
FDYM06FAV1
46
48
FDM03FAV1 FDM04FAV1 FDM05FAV1 FDYM03FAV1 FDYM04FAV1
8.1.2
1 Measuring Location
60Hz Model FDM03FAVAL FDM04FAVAL FDM05FAVAL FDYM03FAVAL FDYM04FAVAL
Indoor Unit FD(Y)M03~06FA
220V
Measuring Location
42 47 42
FDYM05FAVAL
47
FDYM06FAVAL
49
23
Sound Level
8.2
Octave Band Level
8.2.1
50Hz
FDM03FAV1 / FDYM03FAV1
FDYM06FAV1
8.2.2
ED40-017A
FDM04FAV1 / FDYM04FAV1
FDM05FAV1 / FDYM05FAV1
220V 240V
60Hz
FDM03FAVAL / FDYM03FAVAL
FDM04FAVAL / FDYM04FAVAL
FDM05FAVAL / FDYM05FAVAL
FDYM06FAVAL
24
Indoor Unit FD(Y)M03~06FA
ED40-017A
Fan Performance
9. Fan Performance
1
FDM03FA / FDYM03FA
3D020899B
FDM04FA / FDYM04FA
Indoor Unit FD(Y)M03~06FA
25
Fan Performance
ED40-017A
FDM05FA / FDYM05FA
FDYM06FA
26
Indoor Unit FD(Y)M03~06FA
ED40-017A
Installation
10. Installation
Indoor Unit FD(Y)M03~06FA
1
27
Installation
ED40-017A
Caution to be taken when brazing refrigerant piping “Do not use flux when brazing copper-to-copper refrigerant piping. (Particularly for the HFC refrigerant piping) Therefore, use the phosphor copper brazing filler metal (BCuP) which does not require flux.” (Flux has extremely harmful influence on refrigerant piping systems. For instance, if the chlorine based flux is used, it will cause pipe corrosion or, in particular, if the flux contains fluorine, it will damage the refrigerant oil. The use of flux is strictly forbidden since the cleaning on site is impossible. (Remark) Keep in mind that if the phosphor copper brazing filler metal is used and the brazing temperature and the heating time exceed a certain point, the phoshor changes into the gaseous state (e.g. BCuP -1 to 5 : between 700 and 800°C)which causes pin holes and results in refrigerant leakage.
28
Indoor Unit FD(Y)M03~06FA
ED40-017A
Installation
1
Indoor Unit FD(Y)M03~06FA
29
Installation
30
ED40-017A
Indoor Unit FD(Y)M03~06FA
ED40-017A
Installation
1
Indoor Unit FD(Y)M03~06FA
31
Installation
32
ED40-017A
Indoor Unit FD(Y)M03~06FA
ED40-017A
Installation
1
Indoor Unit FD(Y)M03~06FA
33
Installation
34
ED40-017A
Indoor Unit FD(Y)M03~06FA
ED40-017A
Installation
1
Indoor Unit FD(Y)M03~06FA
35
Installation
36
ED40-017A
Indoor Unit FD(Y)M03~06FA
ED40-017A
Part 2 Outdoor Unit KU Series 1. External Appearance.............................................................................38 2. Power Supply ........................................................................................39 2.1 Cooling Only...........................................................................................39 2.2 Heat Pump .............................................................................................40
3. Specification..........................................................................................41 4. Dimensions and Service Space ............................................................42 4.1 Dimensions.............................................................................................42 4.2 Installation Service Space for R(Y)71KU, 100KU, 125KU, 140KU ........45 4.3 Installation Service Space for R(Y)200KU, 250KU ................................47
5. Piping Diagrams....................................................................................48 5.1 Cooling Only...........................................................................................48 5.2 Heat Pump .............................................................................................51
6. Wiring Diagrams....................................................................................55 6.1 Cooling Only...........................................................................................55 6.2 Heat Pump .............................................................................................60
7. Capacity Table ......................................................................................65 7.1 Cooling Only...........................................................................................65 7.2 Heat Pump .............................................................................................72 7.3 Capacity Correction Factor by the Length of Refrigerant Piping ............77
8. Operation Limits ....................................................................................78 8.1 Cooling Only...........................................................................................78 8.2 Heat Pump .............................................................................................79
9. Sound Level ..........................................................................................81 9.1 Overall Sound Level ...............................................................................81 9.2 Octave Band Level .................................................................................82
10.Electric Characteristics..........................................................................85 10.1 Cooling Only...........................................................................................85 10.2 Heat Pump .............................................................................................87
11.Field Piping and Wiring .........................................................................89 11.1 Field Piping (R(Y)71~140KU-(K))...........................................................89 11.2 Field Piping (R(Y)200·250KU)................................................................91 11.3 Field Wiring ............................................................................................93
Outdoor Unit KU Series
37
2
External Appearance
ED40-017A
1. External Appearance
R71KU RY71KU
R140KU RY140KU
38
R200KU RY200KU
R100KU / R125KU RY100KU / RY125KU
R250KU RY250KU
Outdoor Unit KU Series
ED40-017A
Power Supply
2. Power Supply 2.1
Cooling Only
2.1.1
50Hz Series
Indoor Unit
Cooling Only
FDYM03FAV1 !
R 71KUV1
FDYM04FAV1 !
R100KUV1
FDYM03FAV1 !
R 71KUY1
FDYM04FAV1 !
R100KUY1
FDYM05FAV1 !
R125KUY1
FDYM06FAV1 !
R140KUY1
FDYM04FAV1×2 !
R200KUY1
FDYM03FAV1×3 !
R200KUY1
FDYM05FAV1×2 !
R250KUY1
Power Supply
2
1 phase 220-240V
R-KU
2.1.2
3 phase 380-415V (4 wires)
60Hz Series
Indoor Unit
Cooling Only
FDYM03FAVAL !
R 71KUVAL
FDYM04FAVAL !
R100KUVAL
FDYM05FAVAL !
R125KUTAL
FDYM06FAVAL !
R140KUTAL(K)
FDYM04FAVAL×2 !
R200KUTAL
FDYM03FAVAL×3 !
R200KUTAL
FDYM05FAVAL×2 !
R250KUTAL
FDYM05FAVAL !
R125KUYAL
FDYM06FAVAL !
R140KUYAL(K)
FDYM04FAVAL×2 !
R200KUYAL
FDYM03FAVAL×3 !
R200KUYAL
FDYM05FAVAL×2 !
R250KUYAL
Power Supply 1 phase 220V
3 phase 220V
R-KU
Notes:
Outdoor Unit KU Series
3 phase 380V (4 wires)
1. ! : New Model or Changed Model 2. Power Supply Intake: Outdoor Unit
39
Power Supply
ED40-017A
2.2
Heat Pump
2.2.1
50Hz Series
Indoor Unit
Heat Pump
FDYM03FAV1 !
RY 71KUV1
FDYM04FAV1 !
RY100KUV1
FDYM03FAV1 !
RY 71KUY1
FDYM04FAV1 !
RY100KUY1
FDYM05FAV1 !
RY125KUY1
FDYM06FAV1 !
RY140KUY1
FDYM04FAV1×2 !
RY200KUY1
FDYM03FAV1×3 !
RY200KUY1
FDYM05FAV1×2 !
RY250KUY1
Indoor Unit
Heat Pump
FDYM06FAVAL !
RY140KUTAL(K)
FDYM04FAVAL×2 !
RY200KUTAL
FDYM03FAVAL×3 !
RY200KUTAL
FDYM05FAVAL×2 !
RY250KUTAL
FDYM06FAVAL !
RY140KUYAL(K)
FDYM04FAVAL×2 !
RY200KUYAL
FDYM03FAVAL×3 !
RY200KUYAL
FDYM05FAVAL×2 !
RY250KUYAL
Power Supply 1 phase 220-240V
RY-KU
2.2.2
3 phase 380-415V (4 wires)
60Hz Series
Power Supply
3 phase 220V
RY-KU
3 phase 380V (4 wires)
Notes:
40
1. ! : New Model or Changed Model 2. Power Supply Intake: Outdoor Unit
Outdoor Unit KU Series
ED40-017A
Specification
3. Specification FDYM-F + R(Y)-KU Refer to “Specification” in Part 1 on page 5, 8, 11, 13.
2 Optional Accessories R71-140KU Name of Option
Remark
Kit Name R71KU
R100KU
Central Drain Plug
R125KU
R140KU
KKPJ5F180
Year-Round Cooling
KRK5F80V1
KRK5F140V1
KRK5F160V1
RY71-140KU Name of Option
Remark
Kit Name RY71KU
RY100KU
Central Drain Plug
RY125KU
RY140KU
KKPJ5F180 C : 3D014872A
R(Y)200·250KU Name of Option
Remark For Twin Type
Branch Piping Kit
For Triple Type For Double Twin Type
Kit Name R(Y)200KU
R(Y)250KU
KHD58C23A
KHD58C24A
KHD58D31
—
KHRJ5F224F
KHRJ5F280F 4D029784
Outdoor Unit KU Series
41
Dimensions and Service Space
ED40-017A
4. Dimensions and Service Space 4.1
Dimensions
R71KU RY71KU Unit (mm)
R100KU / R125KU RY100KU / RY125KU Unit (mm)
42
Outdoor Unit KU Series
ED40-017A
Dimensions and Service Space
R140KU RY140KU
Unit (mm)
2
3D027710
R200KU RY200KU
3D029265
Outdoor Unit KU Series
43
Dimensions and Service Space
ED40-017A
R250KU RY250KU
3D029264
44
Outdoor Unit KU Series
ED40-017A
4.2
Dimensions and Service Space
Installation Service Space for R(Y)71KU, 100KU, 125KU, 140KU Installation Servicing Space The numerical figures used herein represent the dimensions for the models R(Y)71 to 140. The figures inside ( ) indicate the dimensions for the models R(Y)100 to 140. (Unit:mm)
2
3D001951A-1
Outdoor Unit KU Series
45
Dimensions and Service Space
ED40-017A
3D001951A-2
46
Outdoor Unit KU Series
ED40-017A
4.3
Dimensions and Service Space
Installation Service Space for R(Y)200KU, 250KU
2
3D006578A
Outdoor Unit KU Series
47
Piping Diagrams
ED40-017A
5. Piping Diagrams 5.1
Cooling Only
R71KU
3D014832A
R100KU / R125KU
48
Outdoor Unit KU Series
ED40-017A
Piping Diagrams
R140KU
2
C : 3D014832A
R200KU (Twin System) R250KU (Twin System)
3D030194
Outdoor Unit KU Series
49
Piping Diagrams
ED40-017A
R200KU (Triple System)
3D030195
50
Outdoor Unit KU Series
ED40-017A
5.2
Piping Diagrams
Heat Pump
RY71KU
2
3D028236
RY100KU / RY125KU / RY140KU
140 C : 3D014830B
Outdoor Unit KU Series
51
Piping Diagrams
ED40-017A
RY200KUY1 (Twin System)
3D029823
RY250KUY1 (Twin System)
3D029827
52
Outdoor Unit KU Series
ED40-017A
Piping Diagrams
RY200KUTAL / RY200KUYAL (Twin System)
2
3D030158
RY250KUTAL / RY250KUYAL (Twin System)
3D030163
Outdoor Unit KU Series
53
Piping Diagrams
ED40-017A
RY200KUY1 (Triple System)
3D029825
RY200KUTAL / RY200KUYAL (Triple System)
3D030160
54
Outdoor Unit KU Series
ED40-017A
Wiring Diagrams
6. Wiring Diagrams 6.1
Cooling Only
6.1.1
50Hz (Including 60Hz YAL Models)
R71KUV1
2
3D014533C
R71KUY1
3D014601B
Outdoor Unit KU Series
55
Wiring Diagrams
ED40-017A
R100KUV1
3D014534D
R100KUY1 / R125KUY1 / R140KUY1
3D014602E
56
Outdoor Unit KU Series
ED40-017A
Wiring Diagrams
R200KUY1 / R250KUY1 / R200KUYAL / R250KUYAL
2
3D029091
6.1.2
60Hz
R71KUVAL
3D015460B
Outdoor Unit KU Series
57
Wiring Diagrams
ED40-017A
R100KUVAL
3D015459B
R125KUYAL R140KUYAL(K)
3D015461D
58
Outdoor Unit KU Series
ED40-017A
Wiring Diagrams
R140KUTAL(K)
2
3D015463D
R200KUTAL / R250KUTAL
3D029092
Outdoor Unit KU Series
59
Wiring Diagrams
6.2
Heat Pump
6.2.1
50Hz (Including 60Hz YAL Models)
ED40-017A
RY71KUV1
3D028199
RY71KUY1
3D014603B
60
Outdoor Unit KU Series
ED40-017A
Wiring Diagrams
RY100KUV1
2
3D014496C
RY100KUY1 / RY125KUY1 / RY140KUY1
3D014604D
Outdoor Unit KU Series
61
Wiring Diagrams
ED40-017A
RY200KUY1 / RY200KUYAL
3D028900
RY250KUY1 / RY250KUYAL
3D028901
62
Outdoor Unit KU Series
ED40-017A
6.2.2
Wiring Diagrams
60Hz
RY140KUTAL(K)
2
3D027416A
RY140KUYAL(K)
3D027413A
Outdoor Unit KU Series
63
Wiring Diagrams
ED40-017A
RY200KUTAL
3D028902
RY250KUTAL
3D028903
64
Outdoor Unit KU Series
ED40-017A
Capacity Table
7. Capacity Table 7.1
Cooling Only
7.1.1
50Hz
FDYM03FAV1 + R71KUV1 FDYM03FAV1 + R71KUY1
2
3D014882C
FDYM04FAV1 + R100KUV1 FDYM04FAV1 + R100KUY1
3D014883C
Outdoor Unit KU Series
65
Capacity Table
ED40-017A
FDYM05FAV1 + R125KUY1
3D014884C
FDYM06FAV1 + R140KUY1
C : 3D028069
66
Outdoor Unit KU Series
ED40-017A
Capacity Table
FDYM04FAV1×2 + R200KUY1 FDYM03FAV1×3 + R200KUY1
2
3D030166
FDYM05FAV1×2 + R250KUY1
3D030168
Outdoor Unit KU Series
67
Capacity Table
7.1.2
ED40-017A
60Hz
FDYM03FAVAL + R71KUVAL
3D015615B
FDYM04FAVAL + R100KUVAL
3D015616B
68
Outdoor Unit KU Series
ED40-017A
Capacity Table
FDYM05FAVAL + R125KUTAL
2
3D015645B
FDYM05FAVAL + R125KUYAL
3D015647C
Outdoor Unit KU Series
69
Capacity Table
ED40-017A
FDYM06FAVAL + R140KUTAL / FDYM06FAVAL + R140KUYAL
C : 3D028073
FDYM06FAVAL + R140KUTALK / FDYM06FAVAL + R140KUYALK
C : 3D028068
70
Outdoor Unit KU Series
ED40-017A
Capacity Table
FDYM03FAVAL×3 + R200KUYAL / FDYM03FAVAL×3 + R200KUTAL FDYM04FAVAL×2 + R200KUYAL / FDYM04FAVAL×2 + R200KUTAL
2
3D030167
FDYM05FAVAL×2 + R250KUYAL / FDYM05FAVAL×2 + R250KUTAL
3D030169
Outdoor Unit KU Series
71
Capacity Table
7.2
Heat Pump
7.2.1
50Hz
ED40-017A
FDYM03FAV1 + RY71KUV1 FDYM03FAV1 + RY71KUY1
3D014879C
FDYM04FAV1 + RY100KUV1 FDYM04FAV1 + RY100KUY1
3D014880C
72
Outdoor Unit KU Series
ED40-017A
Capacity Table
FDYM05FAV1 + RY125KUY1
2
3D014881C
FDYM06FAV1 + RY140KUY1
C : 3D028040
Outdoor Unit KU Series
73
Capacity Table
ED40-017A
FDYM04FAV1×2 + RY200KUY1 / FDYM03FAV1×3 + RY200KUY1
3D029856
FDYM05FAV1×2 + RY250KUY1
3D029853
74
Outdoor Unit KU Series
ED40-017A
7.2.2
Capacity Table
60Hz
FDYM06FAVAL + RY140KUTAL / FDYM06FAVAL + RY140KUYAL
2
C : 3D028201
FDYM06FAVAL + RY140KUTALK / FDYM06FAVAL + RY140KUYALK
C : 3D028060
Outdoor Unit KU Series
75
Capacity Table
ED40-017A
FDYM04FAVAL×2 + RY200KUTAL / FDYM04FAVAL×2 + RY200KUYAL FDYM03FAVAL×3 + RY200KUTAL / FDYM03FAVAL×3 + RY200KUYAL
3D029857
FDYM05FAVAL×2 + RY250KUTAL / FDYM05FAVAL×2 + RY250KUYAL
3D029855
76
Outdoor Unit KU Series
ED40-017A
7.3
Capacity Table
Capacity Correction Factor by the Length of Refrigerant Piping
Cooling (heating) capacity correction factor
The cooling and heating capacity of the unit has to be corrected in accordance with the length of refrigerant piping. (The distance between the indoor unit and the outdoor unit) Reference Valve 100
2
71~250
95
90 200 100, 250 71 125
85
80 140 75
0
5
10
20 25 30 35 15 Length of refrigerant piping (Total length)
40
45
50 (m) C : 3D006500B
Notes:
Outdoor Unit KU Series
1.
line: Correction factor for cooling capacity line: Correction factor for heating capacity 2. The correction factor remains the same whether the outdoor unit is to be installed above or below the indoor unit. 3. Calculation method for cooling (heating) capacity Capacity = Cooling (heating) capacity obtained from the capacity table Ă— cooling (heating) capacity correction ratio.
77
Operation Limits
ED40-017A
8. Operation Limits 8.1
Cooling Only
R71KUV1 R71KUY1 R71KUVAL
R100KUV1 R100KUY1 R100KUVAL
R125KUY1 R125KUTAL
R140KUTALK R140KUYALK
R140KUY1
R125KUYAL
R200KUY1 R250KUY1
R140KUTAL R140KUYAL
R200KUTAL R200KUYAL
3D028099
R250KUTAL R250KUYAL
3D030170 3D030170
78
Outdoor Unit KU Series
ED40-017A
8.2
Operation Limits
Heat Pump
RY71KUV1 RY71KUY1
RY100KUV1 RY100KUY1
RY125KUY1
RY140KUY1 RY140KUTAL RY140KUYAL
2
RY140KUTALK RY140KUYALK
3D028098
Outdoor Unit KU Series
79
Operation Limits
RY200KUY1 RY250KUY1
ED40-017A
RY200KUTAL RY200KUYAL
RY250KUTAL RY250KUYAL
3D029783
Notes:
The graphs are based on the following conditions. ! Equivalent piping length 5m ! Level difference 0m ! Air flow rate High
80
Outdoor Unit KU Series
ED40-017A
Sound Level
9. Sound Level 9.1
Overall Sound Level
9.1.1
Cooling Only dBA Model
50Hz 380V
50Hz 415V
60Hz 220V
R71KU R100KU R125KU R140KUY1 R140KUTAL(K)
48 50 50 55 —
49 51 51 56 —
49 52 52 — 56
Measuring Location
2
R71~140KU
Microphone
60Hz 380V —
—
50Hz 380V
50Hz 415V
60 61
61 62
R140KUYAL(K) R200KU R250KU
4D028042
56 60Hz 220 · 380V R200KU / R250KU 60 61
Microphone
4D030106
Note:
9.1.2
Operation sound is measured in an anechoic chamber.
Heat Pump dBA Model RY71KU RY100KU
50Hz 220V
50Hz 240V
60Hz 220V·380V
Cooling
Heating
Cooling
Heating
Cooling
Heating
48 50
50 53
49 51
51 54
— —
— —
Measuring Location RY71~140KU
Microphone
4D028042
Model RY71KU RY100KU RY125KU RY140KU(-K) RY200KU RY250KU
Note:
Outdoor Unit KU Series
50Hz 380V
50Hz 415V
Cooling
Heating
Cooling
Heating
48 50 50 55 60 61
50 53 53 57 62 63
49 51 51 56 61 62
51 54 54 58 63 64
RY200KU / RY250KU — — — 56 60 61
— — — 58 62 63
Microphone
4D030106
Operation sound is measured in an anechoic chamber.
81
Sound Level
ED40-017A
9.2
Octave Band Level
9.2.1
Cooling Only
! 50Hz R71KUV1 / R71KUY1
R100KUV1 / R100KUY1 / R125KUY1
R140KUY1
4D028042A
R200KUY1
R250KUY1
4D027634
4D027632
! 60Hz R71KUVAL
R100KUVAL / R125KUTAL / R125KUYAL
R140KUTAL(K) / R140KUYAL(K)
4D028089A
R200KUTAL / R200KUYAL
R250KUTAL / R250KUYAL
4D030106
82
4D030108
Outdoor Unit KU Series
ED40-017A
9.2.2
Sound Level
Heat Pump
! 50Hz RY71KUV1 / RY71KUY1 (Cooling)
RY71KUV1 / RY71KUY1 (Heating)
RY100KU / RY125KU (Cooling)
2
RY100KU / RY125KU (Heating)
RY140KUY1 (Cooling)
RY140KUY1 (Heating)
4D028048A
4D028042A
RY200KUY1 (Cooling)
RY200KUY1 (Heating)
4D027632
RY250KUY1 (Cooling)
4D027631
4D027634
RY250KUY1 (Heating)
4D027633
Outdoor Unit KU Series
83
Sound Level
ED40-017A
! 60Hz RY140KUTAL(K) / RY140KUYAL(K) (Cooling)
RY140KUTAL(K) / RY140KUYAL(K) (Heating)
4D028049A
4D028089A
RY200KUTAL / RY200KUYAL (Heating)
RY250KUTAL / RY250KUYAL (Cooling)
4D030105
4D030108
RY200KUTAL / RY200KUYAL (Cooling)
4D030106
RY250KUTAL / RY250KUYAL (Heating)
4D030107
240V, 415V 220V, 380V
84
Outdoor Unit KU Series
ED40-017A
Electric Characteristics
10. Electric Characteristics 10.1 Cooling Only 10.1.1 50Hz Unit Combination Indoor FDYM03FAV1
Power Supply
Outdoor
Hz – Volts
R71KUV1
50 – 220 50 – 230 50 – 240
FDYM04FAV1
R100KUV1
50 – 220 50 – 230 50 – 240
FDYM03FAV1
R71KUY1
50 – 380 / 220 50 – 400 / 230 50 – 415 / 240
FDYM04FAV1
R100KUY1
FDYM05FAV1
R125KUY1
FDYM06FAV1
R140KUY1
50 – 380 50 – 400 50 – 415
FDYM04FAV1×2
R200KUY1
50 – 380 / 220 50 – 400 / 230 50 – 415 / 240
FDYM03FAV1×3
R200KUY1
FDYM05FAV1×2
R250KUY1
Voltage Range
Comp
MCA
TOCA
Max.50Hz 456V Min.50Hz 342V
50 – 380 / 220 Max.50Hz 456 / 264V 50 – 400 / 230 Min.50Hz 50 – 415 / 240 342 / 198V 50 – 380 / 220 50 – 400 / 230 50 – 415 / 240
IFM
LRA
RLA
kW
FLA
kW
FLA
12.9 13.3 13.7
0.06
0.6
0.125
0.9
18.6
23.5
30
88 93 97
23.3
28.3
40
109 114 118
16.0 16.5 16.8
0.07 + 0.055
0.7 + 0.6
0.135
1.0
7.4
9.0
15
38 40 42
4.6 4.6 4.7
0.06
0.6
0.125
0.9
9.8
12.3
15
51 53 55
5.6 5.8 6.0
0.07 + 0.055
0.7 + 0.6
0.135
1.0
12.1
15.7
20
63 67 69
7.2 7.2 7.5
0.07 + 0.055
0.7 + 0.6
0.225
1.4
13.6
18.3
25
75 79 82
7.9 8.0 8.2
0.09 + 0.08
0.9 + 0.8
0.270
1.6
20.8
22.5
30
87 92 95
12.6 12.4 13.0
0.23 + 0.19
1.3 + 1.2
0.135 ×2
1.0×2
21.5
23.2
30
87 92 95
12.6 12.4 13.0
0.23 + 0.19
1.3 + 1.2
0.125 ×3
0.9×3
26.8
29.3
40
128 135 140
16.3 15.7 17.2
0.23 + 0.19
1.3 + 1.2
0.225 ×2
1.4×2
Max.50Hz 264V Min.50Hz 198V
50 – 380 / 220 Max.50Hz 456 / 264V 50 – 400 / 230 Min.50Hz 50 – 415 / 240 342 / 198V 50 – 380 / 220 50 – 400 / 230 50 – 415 / 240
OFM
MFA
3D014873C 3D014874C 3D014875C 3D028076A 3D029999 3D030000 3D015613C
Outdoor Unit KU Series
85
2
Electric Characteristics
ED40-017A
10.1.2 60Hz Unit Combination
Power Supply
Indoor
Outdoor
Hz – Volts
FDYM03FAVAL
R71KUVAL
60 – 220
Voltage Range
Comp
OFM
IFM
MCA
TOCA
MFA
LRA
RLA
kW
FLA
kW
FLA
20.3
24.0
30
101
14.6
0.075
0.8
0.125
1.2
0.9 + 0.8
0.135
1.3
FDYM04FAVAL
R100KUVAL
60 – 220
25.8
29.0
40
112
18.2
0.065 + 0.050
FDYM05FAVAL
R125KUTAL
60 – 220
20.8
25.7
30
121
13.7
0.065 + 0.050
0.9 + 0.8
0.225
2.0
FDYM06FAVAL
R140KUTAL
60 – 220
24.5
32.2
40
165
16.2
0.12 + 0.10
1.1 + 1.0
0.270
2.2
FDYM04FAVAL×2
R200KUTAL
60 – 220
35.3
39.0
50
161
23.4
0.23 + 0.19
1.8 + 1.6
0.135 ×2
1.3×2
FDYM03FAVAL×3
R200KUTAL
60 – 220
36.3
40.0
50
161
23.4
0.23 + 0.19
1.8 + 1.6
0.125 ×3
1.2×3
FDYM05FAVAL×2
R250KUTAL
60 – 220
42.3
53.4
60
225
27.9
0.23 + 0.19
1.8 + 1.6
0.225 ×2
2.0×2
FDYM05FAVAL
R125KUYAL
60 – 380
13.5
16.7
20
58
7.8
0.065 + 0.050
0.9 + 0.8
0.225
2.0
Max.60Hz 242V Min.60Hz 198V
Max.60Hz 418V Min.60Hz 342V FDYM06FAVAL
R140KUYAL
60 – 380
14.8
19.2
25
69
8.5
0.12 + 0.10
1.1 + 1.0
0.270
2.2
FDYM04FAVAL×2
R200KUYAL
60 – 380 / 220
23.0
24.0
30
81
13.6
0.23 + 0.19
1.8 + 1.6
0.135 ×2
1.3×2
FDYM03FAVAL×3
R200KUYAL
60 – 380 / 220
24.0
25.0
30
81
13.6
0.23 + 0.19
1.8 + 1.6
0.125 ×3
1.2×3
FDYM05FAVAL×2
R250KUYAL
60 – 380 / 220
29.0
31.4
40
107
17.3
0.23 + 0.19
1.8 + 1.6
0.225 ×2
2.0×2
Max.60Hz 418 / 242V Min.60Hz 342 / 198V
3D014873C 3D014874C 3D014875C 3D028076A 3D029999 3D030000 3D015613C
86
Outdoor Unit KU Series
ED40-017A
Electric Characteristics
10.2 Heat Pump 10.2.1 50Hz Unit Combination
Power Supply
Comp
OFM
IFM
Indoor
Outdoor
Hz – Volts
Voltage Range
MCA
TOCA
MFA
LRA
RLA
kW
FLA
kW
FLA
FDYM03FAV1
RY71KUV1
50 – 220 50 – 230 50 – 240
Max.50Hz 264V Min.50Hz 198V
19.6
23.5
30
88 93 97
13.5 14.0 14.5
0.06
0.6
0.125
0.9
FDYM04FAV1
50 – 380 / 220 RY100KUV1 50 – 400 / 230 50 – 415 / 240
16.7 17.2 17.7
0.07 + 0.055
0.7 + 0.6
0.135
1.0
FDYM03FAV1
FDYM04FAV1
50 – 380 / 220 50 – 400 / 230 Max.50Hz 50 – 415 / 240 456 / 264V 50 – 380 / 220 Min.50Hz 342 / 198V RY100KUY1 50 – 400 / 230 50 – 415 / 240 RY71KUY1
FDYM05FAV1
50 – 380 / 220 RY125KUY1 50 – 400 / 230 50 – 415 / 240
FDYM06FAV1
RY140KUY1
50 – 380 50 – 400 50 – 415
Max.50Hz 456V Min.50Hz 342V
50 – 380 / 220 FDYM04FAV1×2 RY200KUY1 50 – 400 / 230 50 – 415 / 240 50 – 380 / 220 Max.50Hz 456 / 264V FDYM03FAV1×3 RY200KUY1 50 – 400 / 230 Min.50Hz 50 – 415 / 240 342 / 198V 50 – 380 / 220 FDYM05FAV1×2 RY250KUY1 50 – 400 / 230 50 – 415 / 240
24.4
28.3
40
109 114 118
7.9
9.0
15
43 46 47
5.0 5.0 5.1
0.06
0.6
0.125
0.9
10.3
12.3
15
51 53 55
6.1 6.2 6.4
0.07 + 0.055
0.7 + 0.6
0.135
1.0
12.5
15.7
20
63 70 74
7.6 7.6 7.8
0.07 + 0.055
0.7 + 0.6
0.225
1.4
13.9
18.3
25
75 79 82
8.2 8.3 8.5
0.09 + 0.08
0.9 + 0.8
0.270
1.6
20.8
22.5
30
87 92 95
12.6 12.4 13.0
0.23 + 0.19
1.3 + 1.2
0.135 ×2
1.0×2
21.5
23.2
30
87 92 95
12.6 12.4 13.0
0.23 + 0.19
1.3 + 1.2
0.125 ×3
0.9×3
26.8
29.3
40
128 135 140
16.3 15.7 17.2
0.23 + 0.19
1.3 + 1.2
0.225 ×2
1.4×2
3D014873C 3D014874C 3D014875C 3D028076A 3D029820 3D029821
Outdoor Unit KU Series
87
2
Electric Characteristics
ED40-017A
10.2.2 60Hz Unit Combination
Power Supply Voltage Range
Comp
OFM
IFM
MCA
TOC A
MFA
LRA
RLA
kW
FLA
kW
FLA 2.2
Indoor
Outdoor
Hz – Volts
FDYM06FAVAL
RY140KUTAL
60 – 220
25.0
32.2
40
165
16.6
0.12 + 0.10
1.1 + 1.0
0.270
FDYM04FAVAL×2 RY200KUTAL
60 – 220
35.3
39.0
50
161
23.4
0.23 + 0.19
1.8 + 1.6
0.135 1.3×2 ×2
Max.60Hz 242V Min.60Hz 198V FDYM03FAVAL×3 RY200KUTAL
60 – 220
36.3
40.0
50
161
23.4
0.23 + 0.19
1.8 + 1.6
0.125 1.2×3 ×3
FDYM05FAVAL×2 RY250KUTAL
60 – 220
42.3
53.4
60
225
27.9
0.23 + 0.19
1.8 + 1.6
0.225 2.0×2 ×2
15.2
19.2
25
69
8.8
0.12 + 0.10
1.1 + 1.0
0.270
FDYM04FAVAL×2 RY200KUYAL 60 – 380 / 220
23.0
24.0
30
81
13.6
0.23 + 0.19
1.8 + 1.6
0.135 1.3×2 ×2
Max.60Hz 418 / 242V FDYM03FAVAL×3 RY200KUYAL 60 – 380 / 220 Min.60Hz 342 / 198V
24.0
25.0
30
81
13.6
0.23 + 0.19
1.8 + 1.6
0.125 1.2×3 ×3
FDYM05FAVAL×2 RY250KUYAL 60 – 380 / 220
29.0
31.4
40
107
17.3
0.23 + 0.19
1.8 + 1.6
0.225 2.0×2 ×2
FDYM06FAVAL
RY140KUYAL
60 – 380
Max.60Hz 418V Min.60Hz 342V
2.2
3D028076A 3D029820 3D029821
88
Outdoor Unit KU Series
ED40-017A
Field Piping and Wiring
11. Field Piping and Wiring 11.1 Field Piping (R(Y)71~140KU-(K)) 11.1.1 Maximum Allowable Piping Length and Level Difference Max. Allowable Piping Length
50 m (Equivalent Length 70 m)
Max.Allowable Level Difference
30 m
2
11.1.2 Refrigerant Charge This unit requires additional charging of refrigerant according to the length of pipe connected at the site. When the entire refrigerant pipe length is within 30 meters, the additional changing is not needed. Take the following steps for proper charging. When Connected to Indoor Unit
1. Additional Charging of Refrigerant Select the appropriate refrigerant charging amount from the Table below and charge the refrigerant. Fill out the notice plate attached in the rear of the front plate (2) for future servicing. For R(Y)71~140KU Table 1 Additional charging amount <Unit : kg> The maximum alllowable pipe length is 50 meters.
<unit : kg> 30m or less More than 30m and 50m or less
Length of Pipe Connected (L) Cooling Only Additional Charging Amount
R71KU / R100KU / R125KU / R140KU
—
0.5
RY71KU
—
1.0
RY100KU / RY125KU / RY140KU
—
1.5
Heat Pump
For R(Y)140KUTALK(YALK) Table 2 Additional charging amount <unit: kg > The maximum allowable pipe length is 50 meters. Length of pipe connected (L) Additional charging amount
5m
10 m
15 m
20 m
25 m
30 m
35 m
40 m
45 m
50 m
—
0.25
0.50
0.75
1.00
1.25
1.50
1.75
2.00
2.25
<PRECAUTION> Contact your DAIKIN dealer when installing the unit using pipes of 3 m or less. 2. Complete Charging of The Refrigerant When the entire refrigerant pipe length is within 5 meters, charge the refrigerant in accordance with the amount mentioned in the nameplate, and when the pipe length exceeds 5 meters, the charging amount mentioned in the nameplate and that required for additional charging are to be totaled as the net charging amount. 3. Precautions for Pumping-Down Operation The outdoor unit is equipped with a low-pressure switch to protect the compressor. Take the following steps to perform the pumping-down operation.
Outdoor Unit KU Series
89
Field Piping and Wiring
Caution
ED40-017A
Never short-circuit the low-pressure switch during the Pump Down Operation. Procedure
Precautions
1. Start the fan operation with the remote controller.
Confirm that stop valves both on the liquid and gas side are open.
2. Push the pumping-down button on the PC board of the outdoor unit.
Compressor and outdoor fan will start operation automatically.
3. Continue operation for 1 min. until operation condition stabilizes. 4. Close the stop valve on the liquid side securely. (Refer to Fig. 13) Insecure closing of the valve may result in burning of the compressor. 5. When the low-pressure switch is activated, the unit stops working. At this time, close the stop valve on the gas side.
This is the end of pumping-down operation. After pumping-down operation, the remote controller shows “U4” even when ON button on the remote controller is pressed, and it will not operate. Turn off the main power supply switch and turn it on again in need of operation.
! Necessity of a trap
Since there is fear of the oil held inside the riser piping flowing back into the compressor when stopped and causing liquid compression phenomenon, or cases of deterioration of oil retgurn, it will be necessary to provide a trap at an appropriate place in the riser gas piping. ! Trap installation spacing Indoor unit Oil trap
Gas piping
H15m
Liquid piping
H Marks. Install trap at each difference in height 15m
Outdoor unit
Note:
(P1010)
A trap is not necessary when the outdoor unit is installed in a higher position than the indoor unit. Caution to be taken when brazing refrigerant piping “Do not use flux when brazing copper-to-copper refrigerant piping. (Particularly for the HFC refrigerant piping) Therefore, use the phosphor copper brazing filler metal (BCuP) which does not require flux.” (Flux has extremely harmful influence on refrigerant piping systems. For instance, if the chlorine based flux is used, it will cause pipe corrosion or, in particular, if the flux contains fluorine, it will damage the refrigerant oil. The use of flux is strictly forbidden since the cleaning on site is impossible. (Remark) Keep in mind that if the phosphor copper brazing filler metal is used and the brazing temperature and the heating time exceed a certain point, the phoshor changes into the gaseous state (e.g. BCuP -1 to 5 : between 700 and 800°C) which causes pin holes and results in refrigerant leakage.
90
Outdoor Unit KU Series
ED40-017A
Field Piping and Wiring
11.2 Field Piping (R(Y)200·250KU)
2
1PN04787-1A
Outdoor Unit KU Series
91
Field Piping and Wiring
ED40-017A
1PN04788-1
Caution to be taken when brazing refrigerant piping “Do not use flux when brazing copper-to-copper refrigerant piping. (Particularly for the HFC refrigerant piping) Therefore, use the phosphor copper brazing filler metal (BCuP) which does not require flux.” (Flux has extremely harmful influence on refrigerant piping systems. For instance, if the chlorine based flux is used, it will cause pipe corrosion or, in particular, if the flux contains fluorine, it will damage the refrigerant oil. The use of flux is strictly forbidden since the cleaning on site is impossible. (Remark) Keep in mind that if the phosphor copper brazing filler metal is used and the brazing temperature and the heating time exceed a certain point, the phoshor changes into the gaseous state (e.g. BCuP -1 to 5 : between 700 and 800°C) which causes pin holes and results in refrigerant leakage. 92
Outdoor Unit KU Series
ED40-017A
Field Piping and Wiring
11.3 Field Wiring 11.3.1 50Hz R(Y)71~140(KU)
2
Outdoor Unit KU Series
93
Field Piping and Wiring
ED40-017A
11.3.2 60Hz R(Y)71~140KU
94
Outdoor Unit KU Series
ED40-017A
Field Piping and Wiring
11.3.3 50 / 60Hz R(Y)200KU, R(Y)250KU
2
3D029782
Outdoor Unit KU Series
95
Field Piping and Wiring
96
ED40-017A
Outdoor Unit KU Series
ED40-017A
Part 3 Outdoor Unit FU Series 1. External Appearance.............................................................................98 2. Power Supply ........................................................................................99 2.1 Power Supply .........................................................................................99
3. Specification........................................................................................100 4. Dimensions and Service Space ..........................................................101 4.1 Dimensions...........................................................................................101 4.2 Installation Service Space for R(Y)71-125FU ......................................102
5. Piping Diagrams..................................................................................104 5.1 Cooling Only.........................................................................................104 5.2 Heat Pump ...........................................................................................105
6. Wiring Diagrams..................................................................................106 6.1 Cooling Only.........................................................................................106 6.2 Heat Pump ...........................................................................................110
7. Capacity Table ....................................................................................112 7.1 Cooling Only.........................................................................................112 7.2 Heat Pump ...........................................................................................115 7.3 Capacity Correction Factor by the Length of Refrigerant Piping ..........117
8. Operation Limit....................................................................................118 8.1 Cooling Only.........................................................................................118 8.2 Heat Pump ...........................................................................................119
9. Sound Level ........................................................................................120 9.1 Overall Sound Level .............................................................................120 9.2 Octave Band Level ...............................................................................121
10.Electric Characteristics........................................................................123 10.1 Cooling Only.........................................................................................123 10.2 Heat Pump ...........................................................................................124
11.Field Piping and Wiring .......................................................................125 11.1 Field Piping...........................................................................................125 11.2 Field Wiring ..........................................................................................127
Outdoor Unit FU Series
97
3
External Appearance
ED40-017A
1. External Appearance
R71FU RY71FU
98
R100FU / R125FU RY100FU / RY125FU
Outdoor Unit FU Series
ED40-017A
Power Supply
2. Power Supply 2.1
Power Supply
2.1.1
Cooling Only 50Hz Series
Indoor Unit
Cooling Only
FDM03FAV1 !
R 71FUV1
FDM04FAV1 !
R100FUV1
FDM03FAV1 !
R 71FUY1
FDM04FAV1 !
R100FUY1
FDM05FAV1 !
R125FUY1
Power Supply 1 phase 220-240V
R-FU
3
3 phase 380-415V (4 wires)
60Hz Series
Indoor Unit
Cooling Only
FDM03FAVAL !
R 71FUVAL
FDM04FAVAL !
R100FUVAL
FDM05FAVAL !
R125FUTAL
Power Supply 1 phase 220V
R-FU
2.1.2
3 phase 220V
Heat Pump 60Hz Series
Indoor Unit
Heat Pump
FDYM03FAVAL !
RY 71FUVAL
FDYM04FAVAL !
RY100FUVAL
FDYM05FAVAL !
RY125FUTAL
Power Supply 1 phase 220V
RY-FU
Notes:
Outdoor Unit FU Series
3 phase 220V
1. !: New Model or Changed Model 2. Power Supply Intake: Outdoor Unit
99
Specification
ED40-017A
3. Specification FD(Y)M-F + R(Y)-FU Refer to “Specification” in Part 1 on Page 7, 10, 14.
Optional Accessories R(Y)71~125FU Name of Option Central Drain Plug
100
Remark
Kit Name 71
100
125
KKPJ5F180
Outdoor Unit FU Series
ED40-017A
Dimensions and Service Space
4. Dimensions and Service Space 4.1
Dimensions
R71FU RY71FU Unit (mm)
3
R100FU, R125FU RY100FU, RY125FU Unit (mm)
Outdoor Unit FU Series
101
Dimensions and Service Space
4.2
102
ED40-017A
Installation Service Space for R(Y)71-125FU
Outdoor Unit FU Series
ED40-017A
Dimensions and Service Space
3
Outdoor Unit FU Series
103
Piping Diagrams
ED40-017A
5. Piping Diagrams 5.1
Cooling Only
R71FU R100FU R125FU
104
Outdoor Unit FU Series
ED40-017A
5.2
Piping Diagrams
Heat Pump
RY71FU RY100FU RY125FU
3
Outdoor Unit FU Series
105
Wiring Diagrams
ED40-017A
6. Wiring Diagrams 6.1
Cooling Only
6.1.1
50Hz
R71FUV1
R71FUY1
106
Outdoor Unit FU Series
ED40-017A
Wiring Diagrams
R100FUV1
3
R100FUY1 R125FUY1
Outdoor Unit FU Series
107
Wiring Diagrams
6.1.2
ED40-017A
60Hz
R71FUVAL
R100FUVAL
108
Outdoor Unit FU Series
ED40-017A
Wiring Diagrams
R125FUTAL
3
Outdoor Unit FU Series
109
Wiring Diagrams
6.2
Heat Pump
6.2.1
60Hz
ED40-017A
RY71FUVAL
RY100FUVAL
110
Outdoor Unit FU Series
ED40-017A
Wiring Diagrams
RY125FUTAL
3
Outdoor Unit FU Series
111
Capacity Table
ED40-017A
7. Capacity Table 7.1
Cooling Only
7.1.1
50Hz
FDM03FAV1 + R71FUV1 FDM03FAV1 + R71FUY1
FDM04FAV1 + R100FUV1 FDM04FAV1 + R100FUY1
3D001844G
112
Outdoor Unit FU Series
ED40-017A
Capacity Table
FDM05FAV1 + R125FUY1
3
3D001845F
7.1.2
60Hz
FDM03FAVAL + R71FUVAL
3D007447F
Outdoor Unit FU Series
113
Capacity Table
ED40-017A
FDM04FAVAL + R100FUVAL
3D007448E
FDM05FAVAL + R125FUTAL
3D007449F
114
Outdoor Unit FU Series
ED40-017A
7.2
Heat Pump
7.2.1
60Hz
Capacity Table
FDYM03FAVAL + RY71FUVAL
3
3D007444E
FDYM04FAVAL + RY100FUVAL
3D007445E
Outdoor Unit FU Series
115
Capacity Table
ED40-017A
FDYM05FAVAL + RY125FUTAL
3D007446E
116
Outdoor Unit FU Series
ED40-017A
7.3
Capacity Table
Capacity Correction Factor by the Length of Refrigerant Piping The cooling and heating capacity of the unit has to be corrected in accordance with the length of refrigerant piping. (The distance between the indoor unit and the outdoor unit) Reference Valve Cooling (heating) capacity correction factor
100 71~125
95
90
3 85
100 71 125
80
75
0
5
10
20 25 30 35 15 Length of refrigerant piping (Total length)
40
45
50 (m) C : 3D006500B
Notes:
Outdoor Unit FU Series
1.
line: Correction factor for cooling capacity line: Correction factor for heating capacity 2. The correction factor remains the same whether the outdoor unit is to be installed above or below the indoor unit. 3. Calculation method for cooling (heating) capacity Capacity = Cooling (heating) capacity obtained from the capacity table Ă&#x2014; cooling (heating) capacity correction ratio.
117
Operation Limit
ED40-017A
8. Operation Limit 8.1
Cooling Only
8.1.1
50Hz
R71FUV1 / R71FUY1 R100FUV1 / R100FUY1 â&#x20AC;&#x201D; / R125FUY1
8.1.2
60Hz
R71FUVAL R100FUVAL R125FUTAL
118
Outdoor Unit FU Series
ED40-017A
8.2
Heat Pump
8.2.1
60Hz
Operation Limit
RY71FUVAL RY100FUVAL RY125FUTAL
3
C : 3D006675
Outdoor Unit FU Series
119
Sound Level
ED40-017A
9. Sound Level 9.1
Overall Sound Level
9.1.1
Cooling Only 50Hz Model
220V
R 71FUV1
52
R100FUV1
56
Model
380V
R 71FUY1
52
R100FUY1
56
R125FUY1
57
Measuring Location
Microphone (S0012)
60Hz Model
220V
R 71FUVAL
53
R100FUVAL
57
Measuring Location
Microphone
R125FUTAL
9.1.2
59
(S0012)
Heat Pump 60Hz Model
120
220V
Measuring Location
Cooling
Heating
RY 71FUVAL
53
55
RY100FUVAL
57
59
RY125FUTAL
59
61
Microphone (S0012)
Outdoor Unit FU Series
ED40-017A
9.2
Octave Band Level
9.2.1
Cooling Only
Sound Level
! 50Hz R71FUV1 / R71FUY1
R100FUV1 / R100FUY1
R125FUY1
3
! 60Hz R71FUVAL
R100FUVAL
R125FUTAL
220V, 380V
Outdoor Unit FU Series
121
Sound Level
9.2.2
ED40-017A
Heat Pump
! 60Hz RY71FUVAL (Cooling)
RY71FUVAL (Heating)
RY100FUVAL (Cooling)
RY100FUVAL (Heating)
RY125FUTAL (Cooling)
RY125FUTAL (Heating)
122
Outdoor Unit FU Series
ED40-017A
Electric Characteristics
10. Electric Characteristics 10.1 Cooling Only 10.1.1 50Hz Unit Combination
Power Supply
Indoor
Outdoor
Hz – Volts
FDM03FAV1
R71FUV1
50 – 220 50 – 230 50 – 240
Voltage Range
Compressor
OFM
IFM
MCA
TOCA
MFA
LRA
RLA
kW
FLA
kW
FLA
17.0
22.5
25
78
12.4
0.050
0.6
0.125
0.9
23.0
34.2
35
100
16.6
0.075 + 0.035
0.7 + 0.5
0.135
1.0
Max.50Hz 264V Min.50Hz 198V
FDM04FAV1
R100FUV1
50 – 220 50 – 230 50 – 240
FDM03FAV1
R71FUY1
50 – 380 / 220 50 – 400 / 230 50 – 415 / 240
6.8
8.5
15
35
4.2
0.050
0.6
0.125
0.9
FDM04FAV1
R100FUY1
50 – 380 / 220 Max.50Hz 456V 50 – 400 / 230 Min.50Hz 342V 50 – 415 / 240
9.1
9.2
15
45
5.5
0.075 + 0.035
0.7 + 0.5
0.135
1.0
FDM05FAV1
R125FUY1
50 – 380 / 220 50 – 400 / 230 50 – 415 / 240
11.3
12.3
15
62
6.8
0.075 + 0.060
0.7 + 0.7
0.225
1.4
MCA
TOCA
MFA
LRA
RLA
kW
FLA
kW
FLA
20.1
26.0
30
87
14.5
0.080
0.8
0.125
1.2
0.8 + 0.6
0.135
1.3
0.8 + 0.8
0.225
2.0
3
10.1.2 60Hz Unit Combination
Power Supply
Indoor
Outdoor
Hz – Volts
FDM03FAVAL
R71FUVAL
60 – 220
FDM04FAVAL
R100FUVAL
60 – 220
FDM05FAVAL
R125FUTAL
60 – 220
Voltage Range
Max.60Hz 242V Min.60Hz 198V
Compressor
OFM
28.1
39.7
45
118
20.3
0.090 + 0.060
22.5
27.9
35
124
15.1
0.090 + 0.080
IFM
3D007342D 3D007348D 3D007347D
Outdoor Unit FU Series
123
Electric Characteristics
ED40-017A
10.2 Heat Pump 10.2.1 60Hz Unit Combination
Power Supply
Indoor
Outdoor
Hz – Volts
FDYM03FAVAL
RY71FUVAL
60 – 220
FDYM04FAVAL
RY100FUVAL
60 – 220
FDYM05FAVAL
RY125FUTAL
60 – 220
Voltage Range
Max.60Hz 242V Min.60Hz 198V
Compressor
OFM
IFM
MCA
TOCA
MFA
LRA
RLA
kW
FLA
kW
FLA
22.9
35.0
35
97
16.7
0.080
0.8
0.125
1.2
0.8 + 0.6
0.135
1.3
0.8 + 0.8
0.225
2.0
28.6
41.2
45
138
20.7
0.090 + 0.060
22.0
27.9
35
124
14.7
0.090 + 0.080
3D007115D 3D007340D 3D007346E
124
Outdoor Unit FU Series
ED40-017A
Field Piping and Wiring
11. Field Piping and Wiring 11.1 Field Piping 11.1.1 Maximum Allowable Piping Length and Level Difference Max. Allowable Piping Length
50 m (Equivalent Length 70 m)
Max.Allowable Level Difference
30 m
11.1.2 Refrigerant Charge This unit requires additional charging of refrigerant according to the length of pipe connected at the site. Take the following steps for proper charging. When connected to one indoor unit (pair system)
1. Additional Charging of Refrigerant Select the appropriate refrigerant charging amount from the Table below and charge the refrigerant. Fill out the notice plate attached in the rear of the front plate (2) for future servicing. Table Additional Charging Refrigerant Amount R71FU / R100FU / R125FU
<unit: kg>
Length of Pipe Connected
5m
10 m
15 m
20 m
25 m
30 m
35 m
40 m
45 m
50 m
Straight Cooling Models
â&#x20AC;&#x201D;
0.13
0.25
0.38
0.50
0.63
0.75
0.88
1.00
1.13
RY71FU / RY100FU / RY125FU
<unit: kg>
Length of Pipe Connected
5m
10 m
15 m
20 m
25 m
30 m
35 m
40 m
45 m
50 m
Heat Pump Models
â&#x20AC;&#x201D;
0.25
0.50
0.75
1.00
1.25
1.50
1.75
2.00
2.25
<PRECAUTION> ! Contact your DAIKIN dealer when installing the unit using pipes of 3 m or less. 2. Complete Charging of The Refrigerant When the entire refrigerant pipe length is within 5 meters, charge the refrigerant in accordance with the amount mentioned in the nameplate, and when the pipe length exceeds 5 meters, the charging amount mentioned in the nameplate and that required for additional charging are to be totaled as the net charging amount. 3. Precautions for Pumping-Down Operation The outdoor unit is equipped with a low-pressure switch to protect the compressor. Take the following steps to perform the pumping-down operation.
Outdoor Unit FU Series
125
3
Field Piping and Wiring
Caution
ED40-017A
Never short-circuit the low-pressure switch in this operation. Procedure
Precautions
1. Start the fan operation with the remote controller.
Confirm that stop valves both on the liquid and gas side are open.
2. Push the pumping-down button on the PC board of the outdoor unit.
Compressor and outdoor fan will start operation automatically.
3. Continue operation for 1 min. until operation condition stabilizes. 4. Close the stop valve on the liquid side securely. (Refer to Fig. 13) Insecure closing of the valve may result in burning of the compressor. 5. When the low-pressure switch is activated, the unit stops working. At this time, close the stop valve on the gas side.
This is the end of pumping-down operation. After pumping-down operation, the remote controller shows “U4” even when ON button on the remote controller is pressed, and it will not operate. Turn off the main power supply switch and turn it on again in need of operation.
! Necessity of a trap
Since there is fear of the oil held inside the riser piping flowing back into the compressor when stopped and causing liquid compression phenomenon, or cases of deterioration of oil retgurn, it will be necessary to provide a trap at an appropriate place in the riser gas piping. ! Trap installation spacing Indoor unit Oil trap
Gas piping
H15m
Liquid piping
H Marks. Install trap at each difference in height 15m
Outdoor unit
Note:
(P1009)
A trap is not necessary when the outdoor unit is installed in a higher position than the indoor unit. Caution to be taken when brazing refrigerant piping “Do not use flux when brazing copper-to-copper refrigerant piping. (Particularly for the HFC refrigerant piping) Therefore, use the phosphor copper brazing filler metal (BCuP) which does not require flux.” (Flux has extremely harmful influence on refrigerant piping systems. For instance, if the chlorine based flux is used, it will cause pipe corrosion or, in particular, if the flux contains fluorine, it will damage the refrigerant oil. The use of flux is strictly forbidden since the cleaning on site is impossible. (Remark) Keep in mind that if the phosphor copper brazing filler metal is used and the brazing temperature and the heating time exceed a certain point, the phoshor changes into the gaseous state (e.g. BCuP -1 to 5 : between 700 and 800°C) which causes pin holes and results in refrigerant leakage.
126
Outdoor Unit FU Series
ED40-017A
Field Piping and Wiring
11.2 Field Wiring 11.2.1 50¡60Hz
3
Note
1. 2. 3. 4. 5. 6. 7. 8. 9.
Outdoor Unit FU Series
Line voltage wiring Control circuit wiring All wiring, components and materials to be procured on the site must comply with the applicable local and national codes. Use copper conductor only. As for details, see wiring diagrams. Install fuse and mainswitch for safety. All field wiring and components must be provided by a licensed electrician. Unit shall be grounded in compliance with the applicable local and national codes. Wiring shown are general points-of-connection quides only and are not intended for or to include all details for a specific installation. Never share a common power source with other equipment.
127
Dealer Head Office: Umeda Center Bldg., 4-12, Nakazaki-Nishi 2-chome, Kita-ku, Osaka, 530-8323 Japan Tokyo Office: Shinjuku Sumitomo Bldg., 6-1, Nishi-Shinjuku 2-chome, Shinjuku-ku, Tokyo, 163-0235 Japan Internet: http://www.daikin.com c All rights reserved
This book is made of recycled paper. ED 40-017A Printed in Japan 02/2002 K AK FS