CGAP/H Air Cooled Scroll Liquid Chillers Cooling Only 60-210 kW 50Hz
Our business is a business of
Trane has the committed team with the
providing energy-efficient and
technical know-how and expertise to
environmentally responsible systems
help your building or your process
that sustain high performance for life...
perform at its utmost ability...
By doing so, we make it possible for buildings and industrial processes to operate at world-class levels... Trane systems do more than make chilled water or warm and cool air. Our systems ensure process reliability, energy efficiency, as well as superior indoor air quality. And these results are realized by carefully looking at how everything works together - before we put
Customer benefits Small footprint that minimizes installation space. Manifolded Compressors for improved part load efficiencies. BPHE Evaporators that save refrigerant. Wide application flexibility for comfort
galvanized and finished with polyester powder paint RAL 9002 Water flow switch. Factory supplied strainers. Coil protection guards (option on CGAH) Fully packaged with controls and starters.
Options Coated fin options. R22 or R407C Options.
and process applications to fit the customer s exact requirements.
Main features
anything together... So whether the challenge is creating
Multi Stage, Scroll Compressors.
sophisticated Integrated Comfort
Manifolded Hermetic, high efficiency,
TM
Systems for luxury hotels... enterprise services for high-
low vibration, low sound level. Full internal protections, including
performance working environments...
internal and external thermal
control systems for critical, regulated
overloads on compressors.
processes...
External sheet metal parts are
Built-in oil level sight glass and oil charging valve.
Factory-mounted LonTalk® serial link capability [optional] Allowing you to: - Modify the chilled water temperature set-point. - Start or stop the unit. - Monitor water temperature set-point, chiller operation, fans, water pumps, compressor alarms. - Trane Tracer Summit BMS direct compatibility LonTalk® is an open communication protocol used on The Carel controller and Trane MP air system controller
Microprocessor control module with liquid crystal display operator interface controlling and indicating: Leaving and Entering water temperature. History of the last 200 defaults. Cold or hot water reset. On/off scheduling. Anti-freeze protection of evaporator, control defrost. Remote control: dry contact for general fault, allows remote on-off and remote monitoring of the chiller.
Let it think for you...
These CGAP/H chillers are controlled by a chiller controller that monitors all operating and security parameters. It also offers programmable features such as scheduled start/stop or water temperature reset, and has remote starts/ stop or default signaling capabilities. The 6-key keypad along with the liquid crystal display will allow the user to interact very simply with the system, and to quickly diagnose eventual problems or even better: prevent them. These Trane chillers, have controllers allows you control over your installation with ease and a pleasant peace of mind.
Trane makes buildings work better and creates an optimum working environment while controlling operating costs for light commercial, small lodging , small and medium scale industry vertical market segments. Integrating Factory Engineered System Controls and Trane s air-system technology, allows for a full one stop system solution.
Application Benefits 1) High efficiency and low running noise
a. The Chiller system deliveries a steady thermal flow of chilled water that is
achieve high average running
non hazardous and system with
efficiency at partial and full load
minimum cycling of temperature
operation.
cycling.
b. Brazed Plate Heat Exchanger
Trane System Solutions... Trane Quantum Climate Changer, CLCP Euro CLCP
Multiple choices of indoor units make the system flexible in all diverse
Evaporators: Precision heat transfer
vertical market applications.
Low overall cost Maximum reliability Minimum energy consumption Environmentally responsible solution 2) Independent Operation / Service budget
FWDP
The Multi-Chiller system is designed for independent cooling demand as well as cater for redundancy. 3) Independent Operation / Service budget
LWHA
Compact in footprint. Easy installation and requires small outdoor space due to it s tall coils, enabling multiple installations as and when occupation demand arises.
Trane offers a full HVAC system solution with complete Factory integrated systems controls for one stop Convenience as well as state of the art controls and air-systems solutions.
CGAP/H Dimensions
TOP VIEW
SIDE VIEW
Trane Air-Systems, Chillers & Factory Engineered Controls
a. Multi scroll compressors design
4) No refrigerant piping around your living space
CGAP- CGAH General Data Performances (1) (1) Gross Cooling Capacity [R22] Gross Cooling Capacity (R407C) Unit Capacity Steps (%) (1) Total Compressor Power Input Main Power Supply Utilization Range Sound Power Level Compressor Number Type Model Speeds Number Motors Number (3) Unit MCA Amps (2) RLA / LRA Motor RPM
(kW)/(MBH) (kW)/(MBH) (kW) (dB(A)
(A) (A) (rpm)
Condenser Coil Type Tube Size (m m ) Tube Type ( in ) Height ( in ) Length Quantity Rows Fins Per Inch (fpf) Evaporator Data Type W ater Flowrate US GPM ft H2O Nominal Flow, water PD Minimum Flowrate US GPM Maximum Flowrate US GPM Water Strainer W ater Connection BSPT Fan Type Number Diameter (mm)/(in) Drive Type Speeds Number Motors Quantity (2) Motors kW kw/hp (2) FLA (A) Motor RPM (rpm) Dimensions Height (m m ) W idth (m m ) Length (m m ) W eight Uncrated (kg) Weight Crated (kg) System Data Refri erant Circuit Minimum Outdoor Air Temperature for Mechanical Cooling Standard AmbientOperating Range (F) (C) High Pressure [cut out - cut in] (psig) Low Pressure [cut out - cut in] (psig)
CGAP 025
CGAP 030
CGAP 040
CGAP 050
CGAP 060
CGAH 080
64.5 / 220.3 61.3 / 209.3 100-50
77.7 / 265.2 73.8 / 252 100-50
100.1 /341.8 95 / 324.7 100-75-50-25
127.1 / 433.8 120.7 / 412 100-75-50-25
156.1 / 532.8 148.3 / 506.2 100-75-50-25
208 / 710 197 / 674 100-75-50-25
25.2 400/3/50
26.8 400/3/50
53.6 400/3/50
400/3/50
87
89
92
92
2 Scroll 2x13T 1 1
2 Scroll 2 x15T 1 1
4 Scroll 2 x (13T+13T) 1 1
4 Scroll 2 x (15T+15T) 1 1
Scroll 2 x (20Tx2) 1
49
57
75
93
108
147
20.5/135 2900
24/175 2900
16.5/130 2900
20.5/135 2900
24/175 2900
31 / 215
Plate Fin 9.52 Smooth 72 70 1 2+3 144
Plate Fin 9.52 Smooth 72 70 1 3 144
Plate Fin 9.52 Smooth 72 70 2 2 144
Plate Fin 9.52 Smooth 72 70 2 2+3 144
Plate Fin 9.52 Smooth 72 70 2 3 144
Plate Fin 9.52 Smooth 62 107.5
36.2 50.4 400/3/50 400/3/50 400 +, - 10% 89 90 4 Scroll 2x(10T+10T) 1 1
<------- Brazed Plate Heat Exchanger --------> 54.1 69.6 88.3 108.5 9.4 8.6 9.1 9.4 30 40 50 60 90 120 150 180 Standard, Accessory, Ship with but installed at site
44.9 9.1 25 75
75.2
4
1
2900
2 3
144
142 17.9 112 208
2 1/2"
2 1/2"
2 1/2"
2 1/2"
2 1/2"
2 1/2"
Propeller 2 711/28 Direct 1 2
Propeller 2 711/28 Direct 1 2
Propeller 3 711/28 Direct 1 3
Propeller 4 711/28 Direct 1 4
Propeller 4 711/28 Direct 1 4
Propeller
0.6/0.75
0.6/0.75
0.6/0.75
0.6/0.75
0.6/0.75
0.9 / 1.2
1.5 900
1.5 900
1.5 900
1.5 900
1.5 900
720
1911 1002 2264 583 603
1911 1002 2264 593 613
1911 1992 2264 990 1025
1911 1992 2264 1153 1188
1911 1992 2264 1177 1212
2002 1950 3160 2030 2080
1
1
2
2
2
2
59-109 F 15-43 C
59-109 F 15-43 C
59-109 F 15-43 C
59-109 F 15-43 C
59-109 F 15-43 C
59-109 F 15-43 C
6 760/30 Direct 1 6 2.5
415 10 psig, 250 15 psig 45 5 psig, 60 5 psig
Notes [1]
Based on chilled water EWT & LWT of 54 deg. F & 44 deg F and 95 deg F, ambient air temp.
[2]
Per Motor @ 400V
[3] Minimum Circuit Ampacity (MCA) is 125% of the largest compressor RLA plus 100% of the other compressor RLA plus the sum of the condenser fan FLA.
BC-SLB005-E4 June 2008 New Malaysia