HITACHI INVERTER-DRIVEN MULTI-SPLIT SYSTEM HEAT PUMP AIR CONDITIONERS - SET-FREE FSN SERIES -
Technical Catalog I - Design Information Models <Indoor Units> • In-the-Ceiling Type RPI-0.8FSN RPI-2.0FSN RPI-4.0FSN
RPI-1.0FSN RPI-2.5FSN RPI-5.0FSN
RPI-1.5FSN RPI-3.0FSN
• 4-Way Cassette Type RCI-1.0FSN RCI-2.5FSN RCI-5.0FSN
RCI-1.5FSN RCI-3.0FSN
RCI-2.0FSN RCI-4.0FSN
• 2-Way Cassette Type RCD-1.0FSN RCD-2.5FSN RCD-5.0FSN
RCD-1.5FSN RCD-3.0FSN
RCD-2.0FSN RCD-4.0FSN
• Wall Type RPK-0.8FSNSM1 RPK-1.0FSNSM1 RPK-1.5FSNSM1 RPK-2.0FSNSM RPK-2.5FSNSM RPK-3.0FSNSM RPK-3.5FSNSM RPK-4.0FSNSM
• Floor Type RPF-1.0FSN(E)
RPF-1.5FSN(E)
• Floor Concealed Type RPFI-1.0FSN(E)
RPFI-1.5FSN(E)
• Ceiling Type RPC-2.0FSN RPC-4.0FSN
RPC-2.5FSN RPC-5.0FSN
RPC-3.0FSN
RAS-36FSN RAS-42FSN
RAS-38FSN
<Outdoor Units> RAS-34FSN RAS-40FSN
<System Equipment> • Total Heat Exchangers KPI-2521
KPI-5021
KPI-8021
KPI-10021
SP1-S04, 2006
- CONTENTS 1. FEATURES ..................................................................................................................................................... 1 1.1
System Features .................................................................................................................................. 1
1.2
Features on Indoor Units and Outdoor Units ..................................................................................... 12
1.3
Features on Optional Liquid Crystal Remote Control Switch, Wireless Remote Control Switch, Remote Control Switch, 7-Day Timer and Central Station .................................................... 14
1.3.1
Application to the Unit ................................................................................................................... 14
1.3.2
Liquid Crystal Remote Control Switch, PC-2H2 (Optional), PC-P1H (Optional) .......................... 14
1.3.3
Wireless Remote Control Switch, PC-LH3A (Optional) ................................................................ 16
1.3.4
7-Day Timer .................................................................................................................................. 17
1.3.5
Central Station .............................................................................................................................. 18
2. GENERAL DATA ........................................................................................................................................... 19 2.1
General Data for Indoor Units ............................................................................................................ 19
2.2
General Data for Outdoor Units ......................................................................................................... 19
3. DIMENSIONAL DATA ................................................................................................................................... 21 3.1
Dimensional Data for Indoor Units ..................................................................................................... 21
3.2
Dimensional Data for Outdoor Units .................................................................................................. 21
4. SELECTION DATA ........................................................................................................................................ 23 4.1
Operation Space ................................................................................................................................ 23
4.2
Center of Gravity ................................................................................................................................ 23
4.3
Selection Guide .................................................................................................................................. 24
4.4
Capacity Characteristic Curve of Outdoor Units ................................................................................ 41
4.5
Cooling Capacity Table of 100% Combination (Dimension: kW) ....................................................... 44
4.6
Heating Capacity Table of 100% Combination (Dimension: kW) ....................................................... 45
4.7
Cooling Capacity Table of 100% Combination (Dimension: 1,000 kcal/h) ..................................... 47
4.8
Heating Capacity Table of 100% Combination (Dimension: 1,000 kcal/h) ..................................... 48
4.9
Correction Factor According to Piping Length ................................................................................... 50
4.10
Sensible Heat Factor (SHF) ............................................................................................................... 52
4.11
Correction Factor According to Defrosting Operation ........................................................................ 52
4.12
Fan Performance ............................................................................................................................... 52
4.13
Model Selection of Total Heat Exchangers ........................................................................................ 52
5. ELECTRICAL DATA ...................................................................................................................................... 53 6. SOUND DATA ............................................................................................................................................... 54 7. WORKING RANGE ....................................................................................................................................... 57 8. OPTIONAL ACCESSORIES ......................................................................................................................... 58 9. COMPONENT DATA ..................................................................................................................................... 59
i
- CONTENTS 10. CONTROL SYSTEM ................................................................................................................................... 61 10.1
Refrigeration Cycle ............................................................................................................................ 61
10.2
Control System .................................................................................................................................. 63
10.3
System Control .................................................................................................................................. 64
10.3.1 Control in a Room ......................................................................................................................... 64 10.3.2 Group Control from a Remote Place ............................................................................................ 65 10.3.3 Control in a Room/Control from a Remote Place ......................................................................... 65 10.4
Standard Operation Sequence .......................................................................................................... 66
10.5
Protection and Safety Control ............................................................................................................ 75
10.6
Safety and Control Device Setting ..................................................................................................... 75
10.7
Electrical Wiring Diagram ................................................................................................................... 77
11. FOUNDATION PROVISION ........................................................................................................................ 79 12. REFRIGERANT PIPING PROVISION ........................................................................................................ 80 13. FIELD WIRING PROVISION ....................................................................................................................... 83 14. MISCELLANEOUS NOTES ........................................................................................................................ 85 15. STANDARD SPECIFICATIONS .................................................................................................................. 87 16. CAUTION ON REFRIGERANT LEAKAGE ................................................................................................. 88
ii
16.1
Maximum Permissible Concentration of HFC Gas ............................................................................ 88
16.2
Calculation of Refrigerant Concentration ........................................................................................... 88
16.3
Countermeasure for Refrigerant Leakage According to KHK Standard ............................................. 88
FEATURES
1. FEATURES 1.1
System Features New SET-FREE FSN Series
HITACHI proudly introduces the New SET-FREE FSN series, the highly-efficient and reliable air conditioning system, for the East and the Southeast asian markets including 60Hz products. Recently, increased numbers of buildings are requiring "Intelligent" facilities - communication networks, office automation, including a comfortable
environment. Particularly, comfortable space is required all the day through the year in office buildings. This multi-split system air conditioner, SET-FREE can meet these requirements. The proven combination of the scroll compressor and the inverter provides the best air conditioning for office buildings.
FSN Series - Uses of the HFC Series New R410A Refrigerant HITACHI has developed and introduced the new SET-FREE FSN series to meet the global needs to help protect the Earth's environment by using non-
ozone depleting refrigerant, R410A as HITACHI's standard series.
Various Indoor Units and Combinations The line-up of new SET-FREE series indoor units has been extended up to 39 indoor units in 7 types Indoor Unit Type
0.8
1.0
1.5
to meet various building requirements. (0.8HP through 5HP) Nominal Horsepower (HP) 2.0 2.5 3.0
3.5
4.0
5.0
In-the-Ceiling 4-Way Cassette 2-Way Cassette Wall Floor Floor Concealed Ceiling : Available
Able to Connect One Outdoor Unit with up to 32 Indoor Units Utilizing an inverter control, a wide range of operation capacity control is also available. A maximum total combination horsepower of 130% and a minimum total combination horsepower of 50% can be chosen by combination of the indoor
units when compared with the nominal outdoor unit capacity. Therefore, the new system can meet individual air conditioning requirements in most office buildings. Indoor Unit
Outdoor Unit Model
Minimum Combination Capacity (HP)
Maximum Combination Capacity (HP)
Combination Quantity
Minimum Individual Operation Capacity (HP)
RAS-34FSN
17.0
44.2
4 to 32
0.8
RAS-36FSN
18.0
46.8
4 to 32
0.8
RAS-38FSN
19.0
49.4
4 to 32
0.8
RAS-40FSN
20.0
52.0
4 to 32
0.8
RAS-42FSN
21.0
54.6
5 to 32
0.8
1
FEATURES H-LINK System The new H-LINK wiring system requires only two transmission wires connecting each indoor unit and outdoor unit for up to 16 refrigerant cycles, and connecting wires for all indoor units and all outdoor units in series.
• The total wiring length is remarkably reduced. • Only one connection is required for the wiring between the indoor unit and outdoor unit. • Easy wiring connection to the central controllers
Example of H-Link System
Outdoor Unit
Transmission Wires Refrigerant Piping
Indoor Units
: One Refrigerant Cycle
CS-NET
<Specifications> 1) Transmission Wire: 2-Wire 2) Polarity of Transmission Wire: Non-Polar Wire 3) Maximum Outdoor Units To Be Connected: 16 Units per System 4) Maximum Indoor Units To Be Connected: 32 Units per Cycle and 128 Units per H-LINK System 5) Maximum Wiring Length: Total 1,000m (including CS-NET) 6) Recommended Cable: Twist-Pair Cable with Shield, over 0.75mm2 (Equivalent to KPEV-S) 7) Voltage: DC5V
NOTE: In case of applying H-LINK system, the setting of dip switches is required (Refer to the technical catalog II for setting).
❚ Setting of End Terminal Resistance Before shipment, set No.1 pin of DSW10 at the "ON" side. In the case that the outdoor units quantity in the same H-LINK is 2 or more, set No.1 pin of DSW10 at the "OFF" side from the 2nd unit. If only one outdoor unit is used, no setting is required.
If the dip switches are not set or set incorrectly, the alarm may occur due to the transmission failure.
Setting of End Terminal Resistance DSW10 Before Shipment ON
1
Cancellation ON
2
1
2
New Transmission System A non-polar 2-wire cable is applied for the transmission wires connecting indoor units and
2
outdoor unit. Miswiring by inverting connections 1 and 2 is eliminated.
FEATURES Wide Operation Range This unit has been designed for cooling operation under low ambient temperatures down to -5°C. This feature enables cooling to be obtained even in winter on buildings with high internal heat gains due to lighting, people and machines, particularly in
areas such as shops, lecture rooms, data processing areas etc. And the heating operation under low ambient temperature down to -20°C can be also performed.
23 19 17
43
Outdoor Suction Air Temp. (DBoC)
Outdoor Suction Air Temp. (DB oC)
Cooling Operation Area
9
0
Heating Operation Working Range
0 -5
(-20)
19/14.5
38/25
Compressor Stopped. (Indoor Fan Operation Area)
15
o
23 25 27 38
Indoor Suction Air Temp. (DB/WB C)
Indoor Suction Air Temp. (DB oC)
Working Range at Cooling Operation
Working Range at Heating Operation
Low Sound by PWM (Pulse Width Modulation) Control (RCD, RPI, RPC only) Fan motor control by PWM (Pulse Width Modulation) has realized low electromagnetic sounds remarkably; the voltage applied to the fan motor is controlled by chopping (ON/OFF) the power supply voltage at a
high frequency 20kHz. Therefore, the wave pattern is almost sinusoidal, the torque fluctuation is very smooth and a remarkable low level of electromagnetic noise has been achieved.
#$ #
#$ #
%
$
&'
!"
3
FEATURES Low Operation Sound Resulting from New Fan Shape and Propeller Fan Material The most appropriate fan shape for smooth air flow has been researched. Consequently, a new fan shape has been developed to minimize air turbulence around the propeller fan. Also, a new material of MRP (Mica polypropylene) which minimizes vibration characteristics against vibration sound has been adopted, and a laminated surface prevents turbulent flow. This combination has resulted in a low operation sound which was almost impractical in the previous units.
Low Sound Operation by Low Noise Fan Motor In order to minimize electromagnetic sounds, research was thoroughly performed on the materials to be used for the assembled fan motor. Consequently, aluminum die-casting was selected and a low sound operation has been achieved
without decreasing the operation performance. Also, a non-resonance suspension structure has been adopted to support the fan motor. Due to this structure, the vibration sound has been minimized.
Lower Sound Operation during Night Time Through computer simulation of fluid turbulence which is the main source of unwanted noise, and by visual observation of fluid flow, operation sound has been thoroughly analyzed. By improvement of the cabinet structure and fan
4
shape, and by the adoption of a new material and inverter, operation sound has been reduced. Friendly to people and the environment alike, a low sound operation design has been obtained.
FEATURES Grade-up on Flexibility and Comfortability Able to Establish Air Conditioning Systems for Various Requirements â&#x20AC;˘ A maximum piping length of 150 meters and maximum lift of 50 meters between the indoor units and outdoor unit are applicable, and a
maximum lift of 15 meters, which is almost equivalent to a 4 floor height, between indoor units is available.
Piping System
System Example 1 Line Branch System
System Example 2 Header Branch System
System Example 3 Combination Branch System
5
FEATURES Down-Size Piping System
In case that the total piping length is long or the outdoor unit is installed lower than the indoor units by more than 20m, change the pipe size of the main liquid pipe and perform the DSW setting correctly. If not selected correctly, it may cause the compressor failure. Table 1.1 Piping System < Outdoor Unit to First Branch > Outdoor Unit Capacity
Gas/Liquid (φmm) Equivalent Piping Length < 100m Equivalent Piping Length >100m *1)
34HP
31.75/19.05
38.1/22.2
36 to 42HP
38.1/19.05
44.45/22.2
< Multi-kit to Indoor Unit > Pipe Size Indoor Unit Capacity 0.8 to 1.5HP
12.7/6.35 *2)
2HP
H1
Gas/Liquid (φmm)
2.5 to 5HP
Max. Length of Liquid Pipe 15m
15.88/6.35 *2)
15m
15.88/9.53
30m
*2): In the case that liquid piping length is longer than 15m, use φ9.53 pipe and reducer (field-supplied).
Indoor Unit
< First Branch >
Indoor Unit
H2
Outdoor Unit Capacity
Multi-Kit
34 to 42HP
E-302SN
Indoor Unit
Indoor Unit
Indoor Unit L3
Indoor Unit
L3
L3
L3
L3
L3 L2
L1
< Piping Size and Multi-kit after First Branch > Total I. U. Capacity in HP
Gas/Liquid (φmm)
36~
38.1/19.05
26~35.99
31.75/19.05
18~25.99
28.6/15.88
16~17.99
28.6/12.7
12~15.99
25.4/12.7
Multi-kit Model E-302SN
Item Ref. Pipe Length: L1
Actual Equivalent
Applicable Range within 150m within 175m
Piping Length from 1st Branch to each I. U.: L2
within 40m
E-162SN
Piping Length from each Multi-kit to I. U.: L3
within 30m
E-242SN
9~11.99
22.2/9.53
E-102SN
Lift between
O. U. is Higher
within 50m
6~8.99
19.05/9.53
E-84HSN *3)
I. U. and O. U.: H1
O. U. is Lower
within 40m
lower than 6
15.88/9.53
E-108HSN *3)
Lift between Indoor Units: H2
within 15m
Total Actual Length of Liquid Pipes
within 300m
*3) Total I. U. Capacity in HP
Number of Branches
5~10
8 branches
E-108HSN
5~8
4 branches
E-84HSN
Multi-kit
G In the case that the selected multi-kit size is bigger than that of the first branch, use the same size as the first branch. G In the case that the selected pipe size after the first branch is bigger than the pipe size before the first branch, use the same size as before the branch. G If the pipe length from the O.U. to the first branch is more than 100m, the pipe size must be increased (refer to *1)). In this case, the pipe size from the first branch to the second branch should be selected according to the original pipe size. 6
FEATURES Multiple Capacity Control To effectively operate the indoor units, the most appropriate refrigerant flow volume is controlled by the number of operating indoor units. By sensing the air temperature difference between the inlet and outlet of the indoor unit, the electronic expansion opening is controlled to supply the most appropriate refrigerant flow volume. All units can
be operated according to their separate operating conditions. Due to the new control method, we are able to provide 15 meters (almost equal to a 4 floor height) lift between indoor units, resulting in flexible installation.
Outdoor Unit Lo-I
Ho-I
Indoor Unit
HI-I
Indoor Unit
* LO-I: 150m * HO-I: 50m (When outdoor unit is higher than indoor unit.) 40m (When indoor unit is higher than outdoor unit.) * HI-I: 15m
Precise Control with the Wide Range Inverter The compressor speed for FSN series' outdoor unit is controlled within a wide range of from 20Hz to 100Hz. Therefore, smooth operation is available without frequently using the ON/OFF control. This new
wide range capacity control can meet not only the needs of a wide space but also a small space such as guest rooms and management rooms. Defrosting operation can be quickly performed because of a high compressor speed.
5HP
Outdoor Unit 36HP
3HP 4HP 5HP
4HP 3HP
2HP 4HP 4HP 2HP
7
FEATURES Individual Operation at Minimum 0.8HP Indoor Unit The electronic expansion valves installed not only in the outdoor unit, but also in each indoor unit,
control the refrigerant flow.
Drying Operation Control This system combining the inverter speed control with indoor air volume control performs efficient
dehumidification with negligible change in room temperature.
Room Temperature and Humidity Variation During Dry Operation
o Room Temperature ( C)
Air Conditioning
Drying
Air Conditioning
30
25
20
Humidity (%)
70
60
50
40 10
11
12
13
14
15
16
Time (hours)
Trial Operation and Self-Diagnosing by Multi-Function Remote Control Switch and Printed Circuit Board in Outdoor Unit A high quality control by the new remote control switch has been developed. The self-diagnosing function, which enables quick checking of operation conditions in the indoor units and outdoor unit, has been newly equipped. Furthermore, alarm data can be put into the memory of a micro-computer when an abnormality occurs.
â?&#x161; Diagnosing using the Remote Control Switch Printed circuit boards (PCBs) can be checked using the optional LCD (Liquid Crystal Display) remote control switch. Therefore, diagnosing for PCBs at the site is quickly and accurately performed. â?&#x161; Data Memory in the Remote Control Switch In the case that an abnormality occurs, the LCD remote control switch will indicate an alarm code so that quick diagnosing is available at the site.
8
A self-diagnosing function for printed circuit boards is also available. Various operation data such as high pressure, low pressure, etc. are indicated on the 7-segments on the printed circuit board in the outdoor unit. By these functions, saving of maintenance period and labour during the trial operation and servicing has been achieved.
FEATURES Self-Diagnosing Function ❚ Diagnosing using the 7-Segment Display in Outdoor Unit The PCB in the outdoor unit is equipped with three 7-segment displays. This display indicates various operating modes such as; • Outdoor Air Temperature • Discharge Gas Temperature • Evaporating Temperature during Heating Operation • Condensing Temperature • Discharge Pressure • Suction Pressure • Compressor Run Time Therefore, quick and accurate diagnosing is available at the site during the trial operation or normal operation.
7-segment
New Remote Control Switch, PC-2H2 (Optional), PC-P1H (Optional) • PC-2H2: PC-P1H:
for KPI Model for RPI, RCI, RCD, RPK, RPF, RPFI and RPC Model
Example (1) Each indoor unit is individually controlled by remote control switch.
• Large Sized Liquid Crystal Display Indicating Operation Conditions. • Equipped with a Self-diagnosing Function. • Able to Set Timer from 0.5 hours to 24 hours. Example (2) Possible to Control ON/OFF Control for up to 16 Indoor Units.
9
FEATURES HITACHI Central Station, PSC-5S (Optional) Able to Control Simultaneously 16 Indoor Units as One Group and at a Maximum 16 Groups, totally 128 Indoor Units • PSC-5S:
for RPI, RCI, RCD, RPK, RPF, RPFI and RPC Model • A maximum of 128 indoor units can be controlled when the central station is connected with 16 groups consisting of 16 indoor units per group. Operation is independently controlled by each group. • Able to Set all the units in the same group at the same mode when the same operating conditions are required.
• Changeover Function to Individual Group Control after Operation has been Simultaneously Started. • Able to Manually Stop Indoor Units at the Central Station during Individual Operation. • Function to Permit or Prohibit Operation. • Monitoring of Operation Conditions on All Units. • Dry Cell Power Failure Back-up.
Example (1) Able to Individually or Simultaneously Control 16 Indoor Units as Maximum from one Central Station.
New Wireless Remote Control Switch, PC-LH3A (Optional) • Wiring installation is unnecessary. • Liquid Crystal Display Indicating Operation Conditions • Able to Set Temperature from 17°C to 30°C by 1 degree. • Able to Set Timer from 0.5 hours to 24 hours. • Automatic COOL/HEAT operation function is applied only to FX series. The COOL/HEAT operation is switched automatically according to the room temperature.
AUTO H E AT DRY COOL FA N
MODE
RESET
°C
TIMER ON OFF RUN/STOP
TEMP.
CANCEL
LOUVER
ON TIME TIMER
10
FAN
SET
OFF TIME
NOTE: When using wireless remote control switch, receiver kit are required.
Hi Me Lo
FEATURES HITACHI Computer Controlled Network System -CS-NET Version 6The CS-NET is the newly developed Computer Controlled Network System from HITACHI for SET-FREE multi-split air conditioners.
• Up to 16 outdoor units to be controlled per HARC40. • Up to 128 indoor units per H-LINK. • Up to 128 outdoor unis and 128 indoor units per computer.
● System Example 1: Outdoor Units < 16
P/C H-LINK USB Connect
Max.16 Outdoor Units
HARC40
Outdoor PCB Unit
Outdoor PCB Unit Max. 32 Indoor Units per cycle and 128 units per H-LINK
● System Example 2: 16 < Outdoor Units < 128
P/C USB Connect
USB HUB Max.16 Outdoor Units
H-LINK HARC40 PCB
Outdoor Unit
PCB
Outdoor Unit
PCB
Outdoor Unit
Max. 32 Indoor Units per cycle and 128 units per H-LINK Max.16 Outdoor Units
H-LINK HARC40 Max. 8 HARC40 * Max. total length of transmission wire is 1,000 meters.
PCB
Outdoor Unit
Max. 32 Indoor Units per cycle and 128 units per H-LINK
11
FEATURES 1.2
Features on Indoor Units and Outdoor Units
â&#x2013; Indoor Units Please refer to Technical Catalog I, SP1-S02 or SP1-S03, 2006.
â&#x2013; Outdoor Units Slim and Compact Outdoor Unit In-line installation is possible due to the structure of a rear intake and upward discharge design. Even a limited space can be effectively utilized.
Installation Space: 2.69m2
1745
3390 750
12
FEATURES Simple Electrical Wiring <380-415V/50Hz and 380V/60Hz> Max. 1 Outdoor Unit / Power Supply Line
No. 0 System Outdoor Unit TB1 L1 L2 L3 N
TB2 1 2
No. 1 System Outdoor Unit TB1 L1 L2 L3 N
TB2 1 2
No. 3 System Outdoor Unit TB1 L1 L2 L3 N
TB2 1 2
Operating Line (Shielded Twist Pair Cable) DC5V (Non-Pole Transmission H-LINK System)
ELB
Distribution Box or Pull Box *2
ELB
Distribution Box or Pull Box *2
FUSE Main Switch
ELB
3N 380-415V/50 Hz 380V/60 Hz
L1 L2 N
L1 L2 N
TB1
TB1
No. 0 Indoor Unit
1N 220-240V/50 Hz 220V/60 Hz
No. 1 Indoor Unit
Remote Control Cable (Shielded Twist Pair Cable) *1
TB2 1 2 A B
Operating Line (Shielded Twist Pair Cable) DC5V (Non-Pole Transmission H-LINK System)
1 2 A B
Remote Control Switch (PC-P1H)
TB : Terminal Board
Remote Control Cable (Shielded Twist Pair Cable) *1
TB2
Remote Control Switch (PC-P1H)
PCB : Printed Circuit Board : Field Wiring : Field Supplied
No.1 System Indoor Units
No. 0 System Indoor Units (Max. 32 Units per Refrigerant Cycle)
: Optional Accessory
*1: When installing PC-P1H remote control switch in Australia, connect the both ends of shield tube to earth. *2: It is need for Australia.
<220V/60Hz> Max. 1 Outdoor Unit / Power Supply Line
No. 0 System Outdoor Unit TB1 L1 L2 L3
TB2 1 2
No. 1 System Outdoor Unit TB1 L1 L2 L3
TB2 1 2
No. 3 System Outdoor Unit TB1 L1 L2 L3
TB2 1 2
Operating Line (Shielded Twist Pair Cable) DC5V (Non-Pole Transmission H-LINK System)
ELB
Distribution Box or Pull Box *2
ELB
Distribution Box or Pull Box *2
FUSE Main Switch
ELB
3φ 220V/60 Hz L1 L2 N
L1 L2 N
TB1
TB1
No. 0 Indoor Unit TB2
1φ 220V/60 Hz
1 2 A B
Operating Line (Shielded Twist Pair Cable) DC5V (Non-Pole Transmission H-LINK System) TB : Terminal Board
No. 1 Indoor Unit
Remote Control Cable (Shielded Twist Pair Cable) *1
TB2 1 2 A B
Remote Control Switch (PC-P1H)
Remote Control Cable (Shielded Twist Pair Cable) *1 Remote Control Switch (PC-P1H)
PCB : Printed Circuit Board : Field Wiring : Field Supplied : Optional Accessory
No. 0 System Indoor Units (Max. 32 Units per Refrigerant Cycle)
No.1 System Indoor Units
*1: When installing PC-P1H remote control switch in Australia, connect the both ends of shield tube to earth. *2: It is need for Australia.
It is necessary to install a field-supplied Earth Leakage Breaker (ELB). If not, it may cause electric shock or fire. All the field wiring must comply with national and local codes.
A power supply line for No.0 indoor unit can be connected from the 1ø power supply line as shown in the above figure and a power supply line of other indoor unit can be connected from the terminal of each indoor unit. 13
FEATURES 1.3
Features on Optional Liquid Crystal Remote Control Switch, Wireless Remote Control Switch, Remote Control Switch, 7-Day Timer and Central Station
1.3.1 Application to the Unit Remote Control Switch Model
RPI-
PC-2H2
Central Station
7-day Timer
PSC-5S
PSC-5T
PC-P1H
Remote Control Cable PRC-10E~30E for PC-2H2
FSN
RCI-
FSN
RCD-
FSN
RPK-
FSNSM(1)
RPF(I)-
FSN(E)
RPC-
FSN
KPI-
2521~10021
PRC-5,10,15K for PC-P1H (*2)
(*1)
: Applicable, : Not Applicable (*1): In case of simultaneous operation of plural wall type indoor units, the wired remote control switch PC-P1H or the Wireless Receiver Kit PC-RLH11 is required. (*2): PRC-5K is twist-pair cable. 5, 10, 15 meters cable length (m).
1.3.2 Liquid Crystal Remote Control Switch, PC-2H2 (Optional), PC-P1H (Optional) Liquid Crystal Display (L.C.D) Section Swing Louver Indicator "DEFROST" Indicator CENTRAL (Central Control) Indicator
Fan Speed Indicator Ventilation Indicator
ON / OFF Timer (Timer Operation) Indicator SET TEMP (Set Temperature) Indicator Alarm Code Indicator "NO FUNCTION" Indicator
Operation Mode Indicator Automatic Cooling / Heating Operation Indicator FAN HIGH
Run indicator (Red Lump)
SWING LOUVER
ON/OFF TIMER
ABNML (Alarm) Indicator "FILTER" Indicator
SET TEMP.
COOL MED HEAT
LOW DEFROST DRY A/C + CENTRAL AUTO VENT H.STRG
ADDS
RN HR
ABNML
FILTER
T. RUN CHECK
RUN / STOP
Operation Switch Section
UNIT
NO FUNCTION SERVICE
TEMP. TEMP (Temperature Setting) Switch
Run / Stop Switch MODE (Operation Mode Selection) Switch
MODE FAN SPEED
ON/OFF TIMER
RESET
RESET (Filter Reset) Switch VENTI LOUVER
CHECK TIME
FAN SPEED (Fan Speed Selection) Switch
CHECK Switch
" "(Up & Down Panel Operation) Switch (This function is not available.)
ON / OFF TIMER Switch
VENTI (Ventilator Operation) Switch
TIME (Time Setting) Switch
LOUVER (Swing Louver Operation) Switch
The above figure shows the remote control switch with the cover opened.
When opening the cover, pull the cover forward the arrow direction.
14
FEATURES Length of Wire Cable for Optional Remote Control Switch
â&#x20AC;˘ PC-2H2 Length of the standard wire cable for the optional remote control switch is 8 meters. Extension up to 500m (with 0.75mm2 CVS wire) is available. â&#x20AC;˘ PC-P1H As the PC-P1H does not include a remote control cable, prepare one in the field, or use PRC-5K, 10K or 15K. Use the twist pair cable (1P-0.75mm2) as transmitting wire cable for prevention of the malfunction (The total cable length is max. 500m). When the total cable length is within 30m, other type cable (more than 0.3mm2) can be used. Indoor Unit Quantity: 1 Remote Control Switch Quantity: 1
Application Function of Remote Control Switch
One indoor unit can be controlled by two optional remote control switches separately mounted on the wall. Indoor Unit Quantity: 1 Remote Control Switch Quantity: 2
One optional remote control switch can start/stop indoor units up to the maximum number of 16 sets. Indoor Unit Quantity: 16 (Maximum) Remote Control Switch Quantity: 1
15
FEATURES 1.3.3 Wireless Remote Control Switch, PC-LH3A (Optional)
l Transmitter
Point the transmitter towards the receiver of the indoor unit when sending commands. The transmitting indication on the liquid crystal display flashes when sending commands.
l Transmitting Indication l Liquid Crystal Display AUTO H E AT DRY COOL FA N
MODE
RESET
°C
Hi Me Lo
TIMER ON OFF RUN/STOP
TEMP.
l Run/Stop Switch
Operation of the unit can be started or stopped by pressing this switch.
l Fan Speed Switch FAN
LOUVER
CANCEL
SET
OFF TIME
ON TIME TIMER
The set temperature, timer operation, position of air louver, operation mode, air flow mode, etc., are indicated. The diagram of the display shown on the left is for explanation purposes only. The display will differ during actual operation.
Press this switch to select the fan speed. By repeatedly pressing the button, the setting will change sequentially through HIGH, MED and LOW. (Fan speed is fixed at Low for dry operation.)
l Mode Selection Switch
By repeatedly pressing the mode switch, the unit cycles through the different operating modes in the order of HEAT, DRY, COOL and FAN. To select auto operation, press the switch for more than 3 seconds. If the switch is pressed again, it will return to FAN mode.
l Louver Angle Switch
The airflow angle and auto-louver operation can be set by this switch. When pressing the switch, the angle is changed in the following order. (In cool or dry operation modes, steps 1-5 and Auto swing are available.) 1 Step
2 Step
7 Step
Auto Swing
l Temp. Switch
The setting temperature can be adjusted using this switch.
l Timer Switches
Four switches control the timer operation. The set time can be changed by pressing “ON TIME” or “OFF TIME” and is set by pressing the “SET” switch. Timer operation can be cancelled using “CANCEL”.
l Reset Switch
(1) Press RESET to turn off the filter indicator lamp after filter cleaning. (2) If the unit is stopped abnormally due to protection devices etc., press the RESET switch to cancel the control stoppage after the cause of the abnormality has been remove.
16
FEATURES 1.3.4 7-Day Timer By plugging in this timer to the optional remote control switch, daily ON/OFF operation control throughout the week is available. 7-Day Timer has power failure back-up dry cell.
The ON/OFF control is three times in a day as a maximum and the setting is available every minute.
Functions This 7-day timer provides the following functions. 1. 2. 3. 4.
ON/OFF Setting Time in a Week. ON/OFF Setting in available three times a day. Present time is indicated. Running time is indicated.
Model: PSC-5T Name of Parts
Liquid Crystal Display Section
The figure below shows all the indications for reference. The actual display during operation is different. Indication of Pattern Setting
Indication of Mode Selection Indication of Holiday Setting
Indication of ON/OFF Setting Time * Setting 1, Setting 2 and Setting 3 <From Above>
Indication of Present Time
Indication of Present Day Indication of Running Day of A Week
Run Indicator (Red Lamp)
Setting Switch of ON/OFF Time
Change Switch of Operation Mode Setting Switch of Holiday
OK Switch
Change Switch of Setting Pattern
Cancel Switch of Setting Time
Setting Switch of Present Time
Setting Switch of Day of A Week
Operation Switch Section
Setting Switch of Running Day
Change Switch of Setting
Change Switch of ON/OFF Setting
The above figure shows the control timer with the cover opened.
The present time and the ON/OFF setting time are indicated by 12 hour units (AM0:00 â&#x20AC;&#x201C; 12:00, PM0:00 â&#x20AC;&#x201C; 12:00).
When opening the cover, pull the cover forward the arrow direction.
17
FEATURES 1.3.5 Central Station This central station is of the soft touch type. (Operation except with finger is not recommended.)
Activation can be checked by referring to the liquid crystal display and LEDs.
Model: PSC-5S INDICATION
Liquid Crystal Display Section
The figure below shows all the indications for reference. The actual display during operation is different. Indication of Group Number
Indication of Timer
Indication of Alarm Code
Indication of “NO FUNCTION” Indication of Each Group Operation
Indication of Operation Mode “AUTO” is indicated only when the optional function “Auto COOL/HEAT” is set.
Indication of Setting Temperature
Indication of Emergency Stop
Indication of Louver Angle
Indication of Fan Speed
Indication of Demand Control
Indication of “Remote Control Switch Not Available” “ALARM” Indicator
GROUP
HIGH COOL HEAT MED FAN
Run Indicator (Red Lamp)
DEMAND
“FILTER” Indicator
EMERGENCY NO FUNCTION
LOUVER 1 2 3 4 5 6 7 8
DRY AUTO
TIMER
SET TEMP.
RMT. SW NAVAL CHECK
LOW
9 10 11 12 13 14 15 16
ABNML
Group Selection Switch
FILTER
GROUP
RUN/STOP
“FILTER” Indication Reset Switch
RUN/STOP Switch RESET
MODE FAN SPEED
Fan Speed Selection Switch
TIMER
RMT. SW NAVAL LOUVER
Operation Mode Selection Switch
CHECK TEMP
Check Switch Do not touch. This switch is only for service use.
Timer Selection Switch “Remote Control Switch Not Available” Switch Auto Louver Switch
Operation Switch Section
Temperature Setting Switch
This switch is not used.
The above figure shows the central station with the cover opened.
When opening the cover, pull the cover forward the arrow direction.
18
GENERAL DATA
2. GENERAL DATA 2.1
General Data for Indoor Units
Please refer to Technical Catalog I, SP1-S02 or SP1-S03, 2006.
2.2
General Data for Outdoor Units Model
Power Supply Nominal Cooling Capacity *1) Nominal Cooling Capacity *2) Nominal Heating Capacity Cabinet Color Sound Pressure Level (Overall A Scale) (Night-Shift) Outer Dimensions Height Width Depth Net Weight Refrigerant Flow Control Compressor Model Quantity Motor Output (Pole) Heat Exchanger Condenser Fan Quantity Air Flow Rate Motor Output (Pole) Refrigerant Piping Liquid Line Gas Line Refrigerant Charge Wiring Holes Power Supply Control Circuit Connecting Wire between Indoor and Outdoor Unit Approximate Packing Measurement
kW kcal/h Btu/h kW kcal/h Btu/h kW kcal/h Btu/h
RAS-34FSN
RAS-36FSN
RAS-38FSN
96.0 82,600 327,900 97.2 83,700 332,000 108.0 92,900 368,800
AC 3N 380-415V/50Hz, 380V/60Hz, AC 3φ 220V/60Hz 101.0 86,900 344,900 102.3 88,000 349,400 113.0 97,200 385,900
107.0 92,100 365,400 108.4 93,300 370,200 119.5 102,800 408,100
Natural Gray Maximum dB
64 (59)
mm (in.) mm (in.) mm (in.) kg (lbs.)
1,745 (68-5/8) 3,390 (113-1/2) 750 (29-1/2) 920 (2,028)
kW
m3/min. (cfm) kW mm (in.) mm (in.) kg mm (in.) mm (in.)
m3
64 (59)
65 (60)
1,745 1,745 (68-5/8) (68-5/8) 3,390 3,390 (113-1/2) (113-1/2) 750 750 (29-1/2) (29-1/2) 920 920 (2,028) (2,028) R410A Micro-Computer Control Expansion Valve Hermetic (Scroll) E655DHD + E855DH x 4 E655DHD + E855DH x 4 E655DHD + E855DH x 4 1+1x4 1+1x4 1+1x4 3.4 (4) + 5.6 (2) x 4 4.9 (4) + 5.6 (2) x 4 6.6 (4) + 5.6 (2) x 4 Multi-Pass Cross-Finned Tube Propeller Fan 3 3 3 554 554 554 (19,564) (19,564) (19,564) 0.38 (8) + 0.275 (6) x 2 0.38 (8) + 0.275 (6) x 2 0.38 (8) + 0.275 (6) x 2 Flare-Nut Connection (with Flare Nuts) φ19.05 φ19.05 φ19.05 (3/4) (3/4) (3/4) φ31.75 φ38.1 φ38.1 (1-1/4) (1-1/2) (1-1/2) 28.5 31.0 31.0 φ70 (2-3/4) φ26.5 (1-1/16)
φ70 (2-3/4) φ26.5 (1-1/16)
φ70 (2-3/4) φ26.5 (1-1/16)
2
2
2
4.99
4.99
4.99
NOTES: 1. The above cooling and heating capacities show the capacities when the outdoor unit is operated with the 100% rating of indoor units, and are based on the standard JIS B8616-1984. Cooling Operation Conditions Heating Operation Conditions Indoor Air Inlet Temperature: 27oC DB (80oF DB) Indoor Air Inlet Temperature: 20oC DB (68oF DB) *1) 19.5oC WB (67oF WB) Outdoor Air Inlet Temperature: 7oC DB (45oF DB) *2) 19.0oC WB (66.2oF WB) 6oC WB (43oF WB) Outdoor Air Inlet Temperature: 35oC DB (95oF DB) Piping Length: 7.5 Meters Piping Lift: 0 Meter 2. The sound pressure is based on the following conditions. 1 Meter from the unit service cover surface, and 1.5 Meters from floor level. The above data is based on the cooling mode. In case of heating mode, the sound pressure level increases by approximately 1~2 dB. The above data was measured in an anechoic chamber so that reflected sound should be taken into consideration in the field.
19
GENERAL DATA
Model Power Supply Nominal Cooling Capacity *1) Nominal Cooling Capacity *2) Nominal Heating Capacity Cabinet Color Sound Pressure Level (Overall A Scale) (Night-Shift) Outer Dimensions Height Width Depth Net Weight Refrigerant Flow Control Compressor Model Quantity Motor Output (Pole) Heat Exchanger Condenser Fan Quantity Air Flow Rate Motor Output (Pole) Refrigerant Piping Liquid Line Gas Line Refrigerant Charge Wiring Holes Power Supply Control Circuit Connecting Wire between Indoor and Outdoor Unit Approximate Packing Measurement
kW kcal/h Btu/h kW kcal/h Btu/h kW kcal/h Btu/h
RAS-40FSN RAS-42FSN AC 3N 380-415V/50Hz, 380V/60Hz, AC 3φ 220V/60Hz 113.0 118.0 97,200 101,600 385,900 403,000 114.5 119.5 98,500 102,800 39,000 408,100 127.0 132.0 109,300 113,600 433,700 450,800 Natural Gray Maximum
dB
65 (60)
65 (60)
mm (in.) mm (in.) mm (in.) kg (lbs.)
1,745 (68-5/8) 3,390 (133-1/2) 750 (29-1/2) 970 (2,138)
1,745 (68-5/8) 3,390 (133-1/2) 750 (29-1/2) 970 (2,138)
kW
m3/min. (cfm) kW
R410A Micro-Computer Control Expansion Valve Hermetic (Scroll) E655DHD + E855DH x 5 E655DHD + E855DH x 5 1+1x5 1+1x5 2.5 (4) + 5.6 (2) x 5 4.1 (4) + 5.6 (2) x 5 Multi-Pass Cross-Finned Tube Propeller Fan 3 3 554 554 (19,564) (19,564) 0.38 (8) + 0.275 (6) x 2 0.38 (8) + 0.275 (6) x 2 Flare-Nut Connection (with Flare Nuts)
mm (in.) mm (in.) kg
φ19.05 (3/4) φ38.1 (1-1/2) 32.0
φ19.05 (3/4) φ38.1 (1-1/2) 32.0
mm (in.) mm (in.)
φ70 (2-3/4) φ26.5 (1-1/16)
φ70 (2-3/4) φ26.5 (1-1/16)
2
2
4.99
4.99
m3
NOTES: 1. The above cooling and heating capacities show the capacities when the outdoor unit is operated with the 100% rating of indoor units, and are based on the standard JIS B8616-1984. Cooling Operation Conditions Heating Operation Conditions Indoor Air Inlet Temperature: 27oC DB (80oF DB) Indoor Air Inlet Temperature: 20oC DB (68oF DB) *1) 19.5oC WB (67oF WB) Outdoor Air Inlet Temperature: 7oC DB (45oF DB) *2) 19.0oC WB (66.2oF WB) 6oC WB (43oF WB) o o Outdoor Air Inlet Temperature: 35 C DB (95 F DB) Piping Length: 7.5 Meters Piping Lift: 0 Meter 2. The sound pressure is based on the following conditions. 1 Meter from the unit service cover surface, and 1.5 Meters from floor level. The above data is based on the cooling mode. In case of heating mode, the sound pressure level increases by approximately 1~2 dB. The above data was measured in an anechoic chamber so that reflected sound should be taken into consideration in the field.
20
DIMENSIONAL DATA
3. DIMENSIONAL DATA 3.1
Dimensional Data for Indoor Units
Please refer to Technical Catalog I, SP1-S02 or SP1-S03, 2006.
3.2
Dimensional Data for Outdoor Units
Model: RAS-34FSN, RAS-36FSN and RAS-38FSN Unit: mm Viewed from A Hole for Condensate Drain (φ26x8)
2274 *782
98
1054 227 300 227
227
560
227
227
560
227
Hole for Power Supply Wiring (φ70)
14 17
10-Holes (38x16)
129
118
*782
157
*782
30 17
*782
750 *760 794
129
Hole for Refrigerant Piping (245x138) Holes for Control Line Wiring (φ26x2)
210
Electrical Control Box
306
Service Cover
Gas Line Refrigerant Piping Connection 34HP: φ31.75 Flange 36 and 38HP: φ38.1 Flange
Earth Terminal (M8)
Hole for Power Supply Wiring (φ70)
A
125 22
80
Hole for Refrigerant Piping
Holes for Transportation 1128
290
274 Liquid Line 247 Gas Line
1745 1104
Liquid Line Refrigerant Piping Connection φ19.05 Flare Nut
550 3390
290
Hanging Ring
290
Holes for Control Line Wiring (φ26.5x2)
138 234 99
P
159 Gas Line 171 Liquid Line
The Center of Gravity
580
Viewed from P
310
1560
Hole for Power Supply Wiring (φ70) Hole for Refrigerant Piping Holes for Control Line Wiring (φ26.5x2)
Holes for Transportation
more than 1500
Service Space
500
750
1/2H 300
Pipe Flange (Accessory) Insulation
212
Rear Side
190
Front Side
500
2. If there are no walls in front or behind the unit, a service space of 500mm for the front and 300mm for the rear is still required. 3. If there are walls around the unit, then vent holes must be made through the wall. 4. When there are obstacles above the unit, then the four surrounding sides should be kept open. 5. The dimensions marked with * indicate the distance between anchor bolts for fixing.
Pipe Flare Nut (Accessory)
less than 30
1. If there is a wall behind the unit higher than 500mm, then the air intake space required at the rear of the unit is 300+H/2 mm.
Field Installation (Example)
H
Notes:
(Front Side) Anchor Bolt (M12) Concrete Foundation
(Rear Side) Brazing 90
(Standard)
21
DIMENSIONAL DATA
Models: RAS-40FSN and RAS-42FSN
Unit: mm Viewed from A Hole for Condensate Drain (φ26x8)
2274 *782
98
1054 227 300 227
14 17
10-Holes (38x16)
129
118
*782
157
*782
30 17
*782
750 *760 794
129
227
560
227
227
560
227
Hole for Power Supply Wiring (φ70) Hole for Refrigerant Piping (245x138) Holes for Control Line Wiring (φ26x2)
210
Service Cover Electrical Control Box Earth Terminal (M8) 306
Gas Line Refrigerant Piping Connection φ38.1 Flange 274 Liquid Line 247 Gas Line
1745 1104
Liquid Line Refrigerant Piping Connection φ19.05 Flare Nut Hole for Power Supply Wiring (φ70)
A
125 22
80
Hole for Refrigerant Piping
Holes for Transportation 1128
290
550 3390
290
Hanging Ring
290
Holes for Control Line Wiring (φ26.5x2)
138 234 99
P
159 Gas Line 171 Liquid Line
The Center of Gravity
600
Viewed from P
320
1660
Hole for Power Supply Wiring (φ70) Hole for Refrigerant Piping
Holes for Transportation
Holes for Control Line Wiring (φ26.5x2)
more than 1500
Service Space
Notes:
Field Installation (Example) Pipe Flare Nut (Accessory) Pipe Flange (Accessory) Insulation less than 30
3. If there are walls around the unit, then vent holes must be made through the wall. 4. When there are obstacles above the unit, then the four surrounding sides should be kept open. 5. The dimensions marked with * indicate the distance between anchor bolts for fixing.
500
750
1/2H 300 (Front Side)
Anchor Bolt (M12) Concrete Foundation
22
212
Rear Side
190
Front Side
500
then the air intake space required at the rear of the unit is 300+H/2 mm. 2. If there are no walls in front or behind the unit, a service space of 500mm for the front and 300mm for the rear is still required.
H
1. If there is a wall behind the unit higher than 500mm,
(Rear Side) Brazing 90
(Standard)
SELECTION DATA
4. SELECTION DATA 4.1
Operation Space
■ Indoor Units Please refer to Technical Catalog I, SP1-S02 or SP1-S03, 2006. ■ Outdoor Units Models: RAS-34FSN, RAS-36FSN, RAS-38FSN, RAS-40FSN and RAS-42FSN
(mm) Min. 1500
Front Side
Rear Side
*H
500
500
4.2
750
300 1/2H
Center of Gravity
■ Outdoor Units Models: RAS-34FSN, RAS-36FSN and RAS-38FSN
Models: RAS-40FSN and RAS-42FSN
1745
1745
1830 580
1730 310
600
3390
320
3390 750
750
23
SELECTION DATA Cooling/Heating Performance at Various Combinations
4.3
Selection Guide
(1) Meaning of Model Name of Indoor Unit Example: RPI - 1.5 FSN SET-FREE FSN Horsepower Unit Type In-the-Ceiling Type Four-Way Cassette Type Two-Way Cassette Type Wall Type Floor Type Floor Concealed Type Ceiling Type
RPI RCI RCD RPK RPF RPFI RPC
NOTE: Select the indoor units and outdoor unit so as the total indoor horsepower is near to the outdoor horsepower.
(2) Nominal Capacity of Indoor Units Horsepower (HP) Capacity Cooling Capacity Heating Capacity
kW kcal/h Btu/h kW kcal/h Btu/h
0.8
1.0
1.5
2.0
2.5
3.0
3.5
4.0
5.0
2.2 1,900 7,500 2.5 2,200 8,500
2.8 2,400 9,500 3.2 2,800 11,000
4.0 3,500 13,600 4.8 4,200 16,300
5.6 4,800 19,000 6.3 5,400 21,500
7.1 6,100 24,200 8.5 7,300 29,000
8.0 6,900 27,300 9.0 7,700 30,700
9.0 7,700 30,600 10.0 8,600 34,100
11.2 9,600 38,000 12.5 10,800 42,600
14.0 12,000 47,800 16.0 13,800 54,600
(3) Nominal Capacity of Outdoor Units Model Horsepower (HP) kW Cooling kcal/h Capacity Btu/h kW Heating kcal/h Capacity Btu/h
RAS-34FSN 34 97.2 83,700 332,000 108.0 92,900 368,800
RAS-36FSN 36 102.3 88,000 349,400 113.0 97,200 385,900
RAS-38FSN 38 108.4 93,300 370,200 119.5 102,800 408,100
RAS-40FSN 40 114.5 98,500 391,000 127.0 109,300 433,700
RAS-42FSN 42 119.5 102,800 408,100 132.0 113,600 450,800
Nominal Capacity of Outdoor Unit is under the condition that the total indoor unit horsepower is same as outdoor unit horsepower. (4) Outdoor Unit Capacity at Nominal Temperature If the total indoor unit horsepower is not same to the outdoor unit horsepower, refer to "Capacity Characteristic Curve of Outdoor Units" in item 4.4.
24
SELECTION DATA (5) Given Condition (Example) Total Load for Each Room Item Estimated Cooling Load Estimated Heating Load
kW kcal/h kW kcal/h
Room (1) 4.24 3,650 4.77 4,100
Room (2) 5.35 4,600 6.00 5,160
Room (3) 5.35 4,600 6.00 5,160
Room (4) 6.36 5,472 7.16 6,160
Room (5) 8.48 7,295 9.54 8,207
Item Estimated Cooling Load Estimated Heating Load
kW kcal/h kW kcal/h
Room (6) 8.48 7,295 9.54 8,207
Room (7) 10.6 9,119 11.9 10,238
Room (8) 10.6 9,119 11.9 10,238
Room (9) 10.6 9,119 11.9 10,238
Room (10) 10.6 9,119 11.9 10,238
Cooling Outdoor Coil Air Inlet Dry Bulb: 30oC Indoor Coil Air Inlet Dry Bulb: 27oC Wet Bulb: 19oC
Heating Outdoor Coil Air Inlet Dry Bulb: 0oC Wet Bulb: -1oC Indoor Coil Air Inlet Dry Bulb: 20oC
Equivalent Piping Length between Indoor Units and Outdoor Unit: 60m Piping Lift: 25m Correction Factor of Cooling Capacity = 0.88 Correction Factor of Heating Capacity = 0.94 Power Source: 50Hz
(6) Selecting Matching Indoor Units and Nominal Capacity Select in-the-ceiling type indoor units. (Example) Item Selected Model Nominal Cooling Capacity Nominal Heating Capacity
kW kcal/h kW kcal/h
Item Selected Model Nominal Cooling Capacity Nominal Heating Capacity
kW kcal/h kW kcal/h
Room (1)
Room (2)
Room (3)
Room (4)
Room (5)
Room (6)
RPI-2.0FSN 5.6 4,800 6.3 5,400
RPI-2.5FSN 7.1 6,100 8.5 7,300
RPI-2.5FSN 7.1 6,100 8.5 7,300
RPI-3.0FSN 8.0 6,900 9.0 7,700
RPI-4.0FSN 11.2 9,600 12.5 10,800
RPI-4.0FSN 11.2 9,600 12.5 10,800
Room (7)
Room (8)
Room (9)
Room (10)
(1)+(2)+(3)+(4) +(5)+(6)+(7) +(8)+(9)+(10)
Outdoor Unit
RPI-5.0FSN 14.0 12,000 16.0 13,800
RPI-5.0FSN 14.0 12,000 16.0 13,800
RPI-5.0FSN 14.0 12,000 16.0 13,800
RPI-5.0FSN 14.0 12,000 16.0 13,800
106.2 91,100 121.3 104,500
RAS-34FSN 97.2 83,700 108.0 92,900
25
SELECTION DATA (7) Actual Capacity In the case of the example, the total indoor horsepower is 38HP (=2.0HP+2.5HP×2+3.0HP+4.0HP×2+5.0HP×4). Therefore, the outdoor unit capacity at the nominal temperature which is selected from the “Capacity Characteristic Curve” is 106.6kW (91,700kcal/h) at the cooling operation, 110.3kW (94,800kcal/h) at the heating operation under nominal conditions. 1. Actual Capacity of Outdoor Unit Maximum Actual Capacity of Outdoor Unit = [Outdoor Unit Capacity at Nominal Temperature × Correction Factor According to Total Indoor Unit Capacity] × Correction Factor According to Piping Length and Lift × Correction Factor According to Temperature Condition Refer to the table in item 4.5 and item 4.6 for Correction Factor according to the temperature condition. Cooling: [106.6kW (91,700kcal/h)] × 0.91 × 1.0 = 97.0kW (83,447kcal/h) Heating: [110.3kW (94,800kcal/h)] × 0.96 × 0.94 = 99.5kW (85,548kcal/h) 2. Actual Capacity of Each Indoor Unit Actual Capacity of Each Indoor Unit = Actual Capacity of Outdoor Unit × [Each Indoor Unit’s Horsepower ÷ Summation of Each Indoor Unit Horsepower] ex. <RPI-2.0FSN> Cooling Capacity: 97.0× (2.0[HP]÷(2.0[HP]+2.5[HP]×2+3.0[HP]+4.0[HP]×2+5.0[HP]×4))=5.11kW (4,392kcal/h) Heating Capacity: 99.5× (2.0[HP]÷(2.0[HP]+2.5[HP]×2+3.0[HP]+4.0[HP]×2+5.0[HP]×4))=5.24kW (4,503kcal/h) <RPI-2.5FSN> Cooling Capacity: 97.0× (2.5[HP]÷(2.0[HP]+2.5[HP]×2+3.0[HP]+4.0[HP]×2+5.0[HP]×4))=6.38kW (5,490kcal/h) Heating Capacity: 99.5× (2.5[HP]÷(2.0[HP]+2.5[HP]×2+3.0[HP]+4.0[HP]×2+5.0[HP]×4))=6.55kW (5,628kcal/h) <RPI-3.0FSN> Cooling Capacity: 97.0× (3.0[HP]÷(2.0[HP]+2.5[HP]×2+3.0[HP]+4.0[HP]×2+5.0[HP]×4))=7.66kW (6,588kcal/h) Heating Capacity: 99.5× (3.0[HP]÷(2.0[HP]+2.5[HP]×2+3.0[HP]+4.0[HP]×2+5.0[HP]×4))=7.86kW (6,754kcal/h) <RPI-4.0FSN> Cooling Capacity: 97.0× (4.0[HP]÷(2.0[HP]+2.5[HP]×2+3.0[HP]+4.0[HP]×2+5.0[HP]×4))=10.21kW (8,784kcal/h) Heating Capacity: 99.5× (4.0[HP]÷(2.0[HP]+2.5[HP]×2+3.0[HP]+4.0[HP]×2+5.0[HP]×4))=10.48kW (9,005kcal/h) <RPI-5.0FSN> Cooling Capacity: 97.0× (5.0[HP]÷(2.0[HP]+2.5[HP]×2+3.0[HP]+4.0[HP]×2+5.0[HP]×4))=12.76kW (10,980kcal/h) Heating Capacity: 99.5× (5.0[HP]÷(2.0[HP]+2.5[HP]×2+3.0[HP]+4.0[HP]×2+5.0[HP]×4))=13.10kW (11,256kcal/h)
<Result> Item Selected Model Actual Maximum Actual Cooling Capacity Capacity Actual Maximum Heating Capacity Estimated Design Cooling Load Load Estimated Heating Load
Room (1)
kW kcal/h kW kcal/h kW kcal/h kW kcal/h
Item Selected Model Actual Maximum Actual Cooling Capacity Capacity Actual Maximum Heating Capacity Estimated Design Cooling Load Load Estimated Heating Load
26
Room (3)
Room (4)
Room (5)
Room (6)
RPI-2.0FSN RPI-2.5FSN RPI-2.5FSN RPI-3.0FSN RPI-4.0FSN RPI-4.0FSN 5.11 6.38 6.38 7.66 10.21 10.21 4,392 5,490 5,490 6,588 8,784 8,784 5.24 6.55 6.55 7.86 10.48 10.48 4,503 5,628 5,628 6,754 9,005 9,005 4.24 5.35 5.35 6.36 8.48 8.48 3,650 4,600 4,600 5,472 7,295 7,295 4.77 6.00 6.00 7.16 9.54 9.54 4,100 5,160 5,160 6,160 8,207 8,207
Room (7)
kW kcal/h kW kcal/h kW kcal/h kW kcal/h
Room (2)
Room (8)
Room (9)
Room (10)
RPI-5.0FSN RPI-5.0FSN RPI-5.0FSN RPI-5.0FSN 12.76 12.76 12.76 12.76 10,980 10,980 10,980 10,980 13.10 13.10 13.10 13.10 11,256 11,256 11,256 11,256 10.6 10.6 10.6 10.6 9,119 9,119 9,119 9,119 11.9 11.9 11.9 11.9 10,238 10,238 10,238 10,238
(1)+(2)+(3)+(4)+(5) +(6)+(7)+(8)+(9)+(10) 97.01 83,447 99.53 85,548 80.66 69,388 90.61 77,946
SELECTION DATA 3. Outdoor Unit Capacity with Total Horsepower of Combined Indoor Unit The following 14 tables show the examples of outdoor unit capacity which corresponds with total horsepower of combined indoor unit, according to the charts of 4.4 "Capacity Characteristic Curve of Outdoor Units". Table 1. Outdoor Unit Capacity (34, 36, 38HP) with Total Horsepower of Combined Indoor Unit (1)
Total
17.0 17.1 17.2 17.3 17.4 17.5 17.6 17.7 17.8 17.9 18.0 18.1 18.2 18.3 18.4 18.5 18.6 18.7 18.8 18.9 19.0 19.1 19.2 19.3 19.4 19.5 19.6 19.7 19.8 19.9 20.0 20.1 20.2 20.3 20.4 20.5 20.6 20.7 20.8 20.9 21.0 21.1 21.2 21.3 21.4 21.5 21.6 21.7 21.8 21.9 22.0
Outdoor Unit Capacity Unit: kW (x1,000kcal/h) RAS-34FSN Cooling Heating 47.50 (40.85) 53.00 (45.58) 47.79 (41.10) 53.32 (45.86) 48.07 (41.34) 53.65 (46.14) 48.36 (41.59) 53.97 (46.41) 48.64 (41.83) 54.29 (46.69) 48.93 (42.08) 54.62 (46.97) 49.21 (42.32) 54.94 (47.25) 49.50 (42.57) 55.26 (47.53) 49.78 (42.81) 55.59 (47.81) 50.07 (43.06) 55.91 (48.08) 50.35 (43.30) 56.24 (48.36) 50.64 (43.55) 56.56 (48.64) 50.92 (43.79) 56.88 (48.92) 51.21 (44.04) 57.21 (49.20) 51.49 (44.28) 57.53 (49.48) 51.78 (44.53) 57.85 (49.75) 52.06 (44.78) 58.18 (50.03) 52.35 (45.02) 58.50 (50.31) 52.64 (45.27) 58.82 (50.59) 52.92 (45.51) 59.15 (50.87) 53.21 (45.76) 59.47 (51.14) 53.49 (46.00) 59.79 (51.42) 53.78 (46.25) 60.12 (51.70) 54.06 (46.49) 60.44 (51.98) 54.35 (46.74) 60.76 (52.26) 54.63 (46.98) 61.09 (52.54) 54.92 (47.23) 61.41 (52.81) 55.20 (47.47) 61.74 (53.09) 55.49 (47.72) 62.06 (53.37) 55.77 (47.97) 62.38 (53.65) 56.06 (48.21) 62.71 (53.93) 56.34 (48.46) 63.03 (54.21) 56.63 (48.70) 63.35 (54.48) 56.91 (48.95) 63.68 (54.76) 57.20 (49.19) 64.00 (55.04) 57.49 (49.44) 64.32 (55.32) 57.77 (49.68) 64.65 (55.60) 58.06 (49.93) 64.97 (55.87) 58.34 (50.17) 65.29 (56.15) 58.63 (50.42) 65.62 (56.43) 58.91 (50.66) 65.94 (56.71) 59.20 (50.91) 66.26 (56.99) 59.48 (51.15) 66.59 (57.27) 59.77 (51.40) 66.91 (57.54) 60.05 (51.65) 67.24 (57.82) 60.34 (51.89) 67.56 (58.10) 60.62 (52.14) 67.88 (58.38) 60.91 (52.38) 68.21 (58.66) 61.19 (52.63) 68.53 (58.94) 61.48 (52.87) 68.85 (59.21) 61.76 (53.12) 69.18 (59.49)
RAS-36FSN Cooling Heating
RAS-38FSN Cooling
Heating
--
50.50 50.78 51.06 51.34 51.62 51.90 52.18 52.46 52.74 53.03 53.31 53.59 53.87 54.15 54.43 54.71 54.99 55.27 55.55 55.83 56.11 56.39 56.67 56.95 57.23 57.51 57.79 58.08 58.36 58.64 58.92 59.20 59.48 59.76 60.04 60.32 60.60 60.88 61.16 61.44 61.72
(43.43) (43.67) (43.91) (44.15) (44.40) (44.64) (44.88) (45.12) (45.36) (45.60) (45.84) (46.08) (46.33) (46.57) (46.81) (47.05) (47.29) (47.53) (47.77) (48.01) (48.26) (48.50) (48.74) (48.98) (49.22) (49.46) (49.70) (49.94) (50.19) (50.43) (50.67) (50.91) (51.15) (51.39) (51.63) (51.87) (52.12) (52.36) (52.60) (52.84) (53.08)
56.50 56.81 57.13 57.44 57.76 58.07 58.38 58.70 59.01 59.33 59.64 59.95 60.27 60.58 60.89 61.21 61.52 61.84 62.15 62.46 62.78 63.09 63.41 63.72 64.03 64.35 64.66 64.98 65.29 65.60 65.92 66.23 66.54 66.86 67.17 67.49 67.80 68.11 68.43 68.74 69.06
(48.59) (48.86) (49.13) (49.40) (49.67) (49.94) (50.21) (50.48) (50.75) (51.02) (51.29) (51.56) (51.83) (52.10) (52.37) (52.64) (52.91) (53.18) (53.45) (53.72) (53.99) (54.26) (54.53) (54.80) (55.07) (55.34) (55.61) (55.88) (56.15) (56.42) (56.69) (56.96) (57.23) (57.50) (57.77) (58.04) (58.31) (58.58) (58.85) (59.12) (59.39)
--
53.50 53.78 54.06 54.34 54.63 54.91 55.19 55.47 55.75 56.03 56.32 56.60 56.88 57.16 57.44 57.72 58.01 58.29 58.57 58.85 59.13 59.41 59.69 59.98 60.26 60.54 60.82 61.10 61.38 61.67 61.95
(46.01) (46.25) (46.49) (46.74) (46.98) (47.22) (47.46) (47.71) (47.95) (48.19) (48.43) (48.67) (48.92) (49.16) (49.40) (49.64) (49.88) (50.13) (50.37) (50.61) (50.85) (51.10) (51.34) (51.58) (51.82) (52.06) (52.31) (52.55) (52.79) (53.03) (53.27)
59.80 60.11 60.43 60.74 61.06 61.37 61.69 62.00 62.31 62.63 62.94 63.26 63.57 63.88 64.20 64.51 64.83 65.14 65.46 65.77 66.08 66.40 66.71 67.03 67.34 67.66 67.97 68.28 68.60 68.91 69.23
(51.43) (51.70) (51.97) (52.24) (52.51) (52.78) (53.05) (53.32) (53.59) (53.86) (54.13) (54.40) (54.67) (54.94) (55.21) (55.48) (55.75) (56.02) (56.29) (56.56) (56.83) (57.10) (57.37) (57.64) (57.91) (58.18) (58.45) (58.72) (58.99) (59.26) (59.53)
27
SELECTION DATA
Table 2. Outdoor Unit Capacity (34, 36, 38HP) with Total Horsepower of Combined Indoor Unit (2)
Total
22.1 22.2 22.3 22.4 22.5 22.6 22.7 22.8 22.9 23.0 23.1 23.2 23.3 23.4 23.5 23.6 23.7 23.8 23.9 24.0 24.1 24.2 24.3 24.4 24.5 24.6 24.7 24.8 24.9 25.0 25.1 25.2 25.3 25.4 25.5 25.6 25.7 25.8 25.9 26.0 26.1 26.2 26.3 26.4 26.5 26.6 26.7 26.8 26.9 27.0
28
Outdoor Unit Capacity Unit: kW (x1,000kcal/h) RAS-34FSN Cooling Heating 62.05 (53.36) 69.50 (59.77) 62.34 (53.61) 69.82 (60.05) 62.62 (53.85) 70.15 (60.33) 62.91 (54.10) 70.47 (60.60) 63.19 (54.34) 70.79 (60.88) 63.48 (54.59) 71.12 (61.16) 63.76 (54.84) 71.44 (61.44) 64.05 (55.08) 71.76 (61.72) 64.33 (55.33) 72.09 (62.00) 64.62 (55.57) 72.41 (62.27) 64.90 (55.82) 72.74 (62.55) 65.19 (56.06) 73.06 (62.83) 65.47 (56.31) 73.38 (63.11) 65.76 (56.55) 73.71 (63.39) 66.04 (56.80) 74.03 (63.67) 66.33 (57.04) 74.35 (63.94) 66.61 (57.29) 74.68 (64.22) 66.90 (57.53) 75.00 (64.50) 67.19 (57.78) 75.32 (64.78) 67.47 (58.02) 75.65 (65.06) 67.76 (58.27) 75.97 (65.33) 68.04 (58.52) 76.29 (65.61) 68.33 (58.76) 76.62 (65.89) 68.61 (59.01) 76.94 (66.17) 68.90 (59.25) 77.26 (66.45) 69.18 (59.50) 77.59 (66.73) 69.47 (59.74) 77.91 (67.00) 69.75 (59.99) 78.24 (67.28) 70.04 (60.23) 78.56 (67.56) 70.32 (60.48) 78.88 (67.84) 70.61 (60.72) 79.21 (68.12) 70.89 (60.97) 79.53 (68.40) 71.18 (61.21) 79.85 (68.67) 71.46 (61.46) 80.18 (68.95) 71.75 (61.71) 80.50 (69.23) 72.04 (61.95) 80.82 (69.51) 72.32 (62.20) 81.15 (69.79) 72.61 (62.44) 81.47 (70.06) 72.89 (62.69) 81.79 (70.34) 73.18 (62.93) 82.12 (70.62) 73.46 (63.18) 82.44 (70.90) 73.75 (63.42) 82.76 (71.18) 74.03 (63.67) 83.09 (71.46) 74.32 (63.91) 83.41 (71.73) 74.60 (64.16) 83.74 (72.01) 74.89 (64.40) 84.06 (72.29) 75.17 (64.65) 84.38 (72.57) 75.46 (64.89) 84.71 (72.85) 75.74 (65.14) 85.03 (73.13) 76.03 (65.39) 85.35 (73.40)
RAS-36FSN Cooling Heating 62.00 (53.32) 69.37 (59.66) 62.28 (53.56) 69.68 (59.93) 62.56 (53.80) 70.00 (60.20) 62.84 (54.05) 70.31 (60.47) 63.13 (54.29) 70.63 (60.74) 63.41 (54.53) 70.94 (61.01) 63.69 (54.77) 71.25 (61.28) 63.97 (55.01) 71.57 (61.55) 64.25 (55.25) 71.88 (61.82) 64.53 (55.49) 72.19 (62.09) 64.81 (55.74) 72.51 (62.36) 65.09 (55.98) 72.82 (62.63) 65.37 (56.22) 73.14 (62.90) 65.65 (56.46) 73.45 (63.17) 65.93 (56.70) 73.76 (63.44) 66.21 (56.94) 74.08 (63.71) 66.49 (57.18) 74.39 (63.98) 66.77 (57.42) 74.71 (64.25) 67.05 (57.67) 75.02 (64.52) 67.33 (57.91) 75.33 (64.79) 67.61 (58.15) 75.65 (65.06) 67.89 (58.39) 75.96 (65.33) 68.18 (58.63) 76.28 (65.60) 68.46 (58.87) 76.59 (65.87) 68.74 (59.11) 76.90 (66.14) 69.02 (59.35) 77.22 (66.41) 69.30 (59.60) 77.53 (66.68) 69.58 (59.84) 77.84 (66.95) 69.86 (60.08) 78.16 (67.22) 70.14 (60.32) 78.47 (67.49) 70.42 (60.56) 78.79 (67.76) 70.70 (60.80) 79.10 (68.03) 70.98 (61.04) 79.41 (68.30) 71.26 (61.28) 79.73 (68.57) 71.54 (61.53) 80.04 (68.84) 71.82 (61.77) 80.36 (69.11) 72.10 (62.01) 80.67 (69.38) 72.38 (62.25) 80.98 (69.65) 72.66 (62.49) 81.30 (69.92) 72.94 (62.73) 81.61 (70.19) 73.23 (62.97) 81.93 (70.46) 73.51 (63.21) 82.24 (70.73) 73.79 (63.46) 82.55 (71.00) 74.07 (63.70) 82.87 (71.27) 74.35 (63.94) 83.18 (71.54) 74.63 (64.18) 83.49 (71.81) 74.91 (64.42) 83.81 (72.08) 75.19 (64.66) 84.12 (72.35) 75.47 (64.90) 84.44 (72.62) 75.75 (65.15) 84.75 (72.89)
RAS-38FSN Cooling Heating 62.23 (53.52) 69.54 (59.80) 62.51 (53.76) 69.85 (60.08) 62.79 (54.00) 70.17 (60.35) 63.07 (54.24) 70.48 (60.62) 63.36 (54.49) 70.80 (60.89) 63.64 (54.73) 71.11 (61.16) 63.92 (54.97) 71.43 (61.43) 64.20 (55.21) 71.74 (61.70) 64.48 (55.45) 72.05 (61.97) 64.76 (55.70) 72.37 (62.24) 65.04 (55.94) 72.68 (62.51) 65.33 (56.18) 73.00 (62.78) 65.61 (56.42) 73.31 (63.05) 65.89 (56.66) 73.63 (63.32) 66.17 (56.91) 73.94 (63.59) 66.45 (57.15) 74.25 (63.86) 66.73 (57.39) 74.57 (64.13) 67.02 (57.63) 74.88 (64.40) 67.30 (57.88) 75.20 (64.67) 67.58 (58.12) 75.51 (64.94) 67.86 (58.36) 75.82 (65.21) 68.14 (58.60) 76.14 (65.48) 68.42 (58.84) 76.45 (65.75) 68.71 (59.09) 76.77 (66.02) 68.99 (59.33) 77.08 (66.29) 69.27 (59.57) 77.40 (66.56) 69.55 (59.81) 77.71 (66.83) 69.83 (60.06) 78.02 (67.10) 70.11 (60.30) 78.34 (67.37) 70.39 (60.54) 78.65 (67.64) 70.68 (60.78) 78.97 (67.91) 70.96 (61.02) 79.28 (68.18) 71.24 (61.27) 79.60 (68.45) 71.52 (61.51) 79.91 (68.72) 71.80 (61.75) 80.22 (68.99) 72.08 (61.99) 80.54 (69.26) 72.37 (62.23) 80.85 (69.53) 72.65 (62.48) 81.17 (69.80) 72.93 (62.72) 81.48 (70.07) 73.21 (62.96) 81.79 (70.34) 73.49 (63.20) 82.11 (70.61) 73.77 (63.45) 82.42 (70.88) 74.06 (63.69) 82.74 (71.15) 74.34 (63.93) 83.05 (71.42) 74.62 (64.17) 83.37 (71.69) 74.90 (64.41) 83.68 (71.96) 75.18 (64.66) 83.99 (72.24) 75.46 (64.90) 84.31 (72.51) 75.74 (65.14) 84.62 (72.78) 76.03 (65.38) 84.94 (73.05)
SELECTION DATA
Table 3. Outdoor Unit Capacity (34, 36, 38HP) with Total Horsepower of Combined Indoor Unit (3)
Total
27.1 27.2 27.3 27.4 27.5 27.6 27.7 27.8 27.9 28.0 28.1 28.2 28.3 28.4 28.5 28.6 28.7 28.8 28.9 29.0 29.1 29.2 29.3 29.4 29.5 29.6 29.7 29.8 29.9 30.0 30.1 30.2 30.3 30.4 30.5 30.6 30.7 30.8 30.9 31.0 31.1 31.2 31.3 31.4 31.5 31.6 31.7 31.8 31.9 32.0
Outdoor Unit Capacity Unit: kW (x1,000kcal/h) RAS-34FSN Cooling Heating 76.31 (65.63) 85.68 (73.68) 76.60 (65.88) 86.00 (73.96) 76.89 (66.12) 86.32 (74.24) 77.17 (66.37) 86.65 (74.52) 77.46 (66.61) 86.97 (74.79) 77.74 (66.86) 87.29 (75.07) 78.03 (67.10) 87.62 (75.35) 78.31 (67.35) 87.94 (75.63) 78.60 (67.59) 88.26 (75.91) 78.88 (67.84) 88.59 (76.19) 79.17 (68.08) 88.91 (76.46) 79.45 (68.33) 89.24 (76.74) 79.74 (68.57) 89.56 (77.02) 80.02 (68.82) 89.88 (77.30) 80.31 (69.07) 90.21 (77.58) 80.59 (69.31) 90.53 (77.86) 80.88 (69.56) 90.85 (78.13) 81.16 (69.80) 91.18 (78.41) 81.45 (70.05) 91.50 (78.69) 81.74 (70.29) 91.82 (78.97) 82.02 (70.54) 92.15 (79.25) 82.31 (70.78) 92.47 (79.52) 82.59 (71.03) 92.79 (79.80) 82.88 (71.27) 93.12 (80.08) 83.16 (71.52) 93.44 (80.36) 83.45 (71.76) 93.76 (80.64) 83.73 (72.01) 94.09 (80.92) 84.02 (72.26) 94.41 (81.19) 84.30 (72.50) 94.74 (81.47) 84.59 (72.75) 95.06 (81.75) 84.87 (72.99) 95.38 (82.03) 85.16 (73.24) 95.71 (82.31) 85.44 (73.48) 96.03 (82.59) 85.73 (73.73) 96.35 (82.86) 86.01 (73.97) 96.68 (83.14) 86.30 (74.22) 97.00 (83.42) 86.59 (74.46) 97.32 (83.70) 86.87 (74.71) 97.65 (83.98) 87.16 (74.95) 97.97 (84.25) 87.44 (75.20) 98.29 (84.53) 87.73 (75.44) 98.62 (84.81) 88.01 (75.69) 98.94 (85.09) 88.30 (75.94) 99.26 (85.37) 88.58 (76.18) 99.59 (85.65) 88.87 (76.43) 99.91 (85.92) 89.15 (76.67) 100.24 (86.20) 89.44 (76.92) 100.56 (86.48) 89.72 (77.16) 100.88 (86.76) 90.01 (77.41) 101.21 (87.04) 90.29 (77.65) 101.53 (87.32)
RAS-36FSN Cooling Heating 76.03 (65.39) 85.06 (73.15) 76.31 (65.63) 85.38 (73.42) 76.59 (65.87) 85.69 (73.69) 76.87 (66.11) 86.01 (73.96) 77.15 (66.35) 86.32 (74.23) 77.43 (66.59) 86.63 (74.50) 77.71 (66.83) 86.95 (74.77) 77.99 (67.08) 87.26 (75.04) 78.28 (67.32) 87.58 (75.31) 78.56 (67.56) 87.89 (75.58) 78.84 (67.80) 88.20 (75.85) 79.12 (68.04) 88.52 (76.12) 79.40 (68.28) 88.83 (76.39) 79.68 (68.52) 89.14 (76.66) 79.96 (68.76) 89.46 (76.93) 80.24 (69.01) 89.77 (77.20) 80.52 (69.25) 90.09 (77.47) 80.80 (69.49) 90.40 (77.74) 81.08 (69.73) 90.71 (78.01) 81.36 (69.97) 91.03 (78.28) 81.64 (70.21) 91.34 (78.55) 81.92 (70.45) 91.66 (78.82) 82.20 (70.69) 91.97 (79.09) 82.48 (70.94) 92.28 (79.36) 82.76 (71.18) 92.60 (79.63) 83.04 (71.42) 92.91 (79.90) 83.33 (71.66) 93.23 (80.17) 83.61 (71.90) 93.54 (80.44) 83.89 (72.14) 93.85 (80.71) 84.17 (72.38) 94.17 (80.98) 84.45 (72.62) 94.48 (81.25) 84.73 (72.87) 94.79 (81.52) 85.01 (73.11) 95.11 (81.79) 85.29 (73.35) 95.42 (82.06) 85.57 (73.59) 95.74 (82.33) 85.85 (73.83) 96.05 (82.60) 86.13 (74.07) 96.36 (82.87) 86.41 (74.31) 96.68 (83.14) 86.69 (74.55) 96.99 (83.41) 86.97 (74.80) 97.31 (83.68) 87.25 (75.04) 97.62 (83.95) 87.53 (75.28) 97.93 (84.22) 87.81 (75.52) 98.25 (84.49) 88.09 (75.76) 98.56 (84.76) 88.38 (76.00) 98.88 (85.03) 88.66 (76.24) 99.19 (85.30) 88.94 (76.49) 99.50 (85.57) 89.22 (76.73) 99.82 (85.84) 89.50 (76.97) 100.13 (86.11) 89.78 (77.21) 100.44 (86.38)
RAS-38FSN Cooling Heating 76.31 (65.62) 85.25 (73.32) 76.59 (65.87) 85.57 (73.59) 76.87 (66.11) 85.88 (73.86) 77.15 (66.35) 86.19 (74.13) 77.43 (66.59) 86.51 (74.40) 77.72 (66.84) 86.82 (74.67) 78.00 (67.08) 87.14 (74.94) 78.28 (67.32) 87.45 (75.21) 78.56 (67.56) 87.76 (75.48) 78.84 (67.80) 88.08 (75.75) 79.12 (68.05) 88.39 (76.02) 79.41 (68.29) 88.71 (76.29) 79.69 (68.53) 89.02 (76.56) 79.97 (68.77) 89.34 (76.83) 80.25 (69.02) 89.65 (77.10) 80.53 (69.26) 89.96 (77.37) 80.81 (69.50) 90.28 (77.64) 81.09 (69.74) 90.59 (77.91) 81.38 (69.98) 90.91 (78.18) 81.66 (70.23) 91.22 (78.45) 81.94 (70.47) 91.54 (78.72) 82.22 (70.71) 91.85 (78.99) 82.50 (70.95) 92.16 (79.26) 82.78 (71.19) 92.48 (79.53) 83.07 (71.44) 92.79 (79.80) 83.35 (71.68) 93.11 (80.07) 83.63 (71.92) 93.42 (80.34) 83.91 (72.16) 93.73 (80.61) 84.19 (72.41) 94.05 (80.88) 84.47 (72.65) 94.36 (81.15) 84.76 (72.89) 94.68 (81.42) 85.04 (73.13) 94.99 (81.69) 85.32 (73.37) 95.31 (81.96) 85.60 (73.62) 95.62 (82.23) 85.88 (73.86) 95.93 (82.50) 86.16 (74.10) 96.25 (82.77) 86.44 (74.34) 96.56 (83.04) 86.73 (74.58) 96.88 (83.31) 87.01 (74.83) 97.19 (83.58) 87.29 (75.07) 97.51 (83.85) 87.57 (75.31) 97.82 (84.12) 87.85 (75.55) 98.13 (84.39) 88.13 (75.80) 98.45 (84.67) 88.42 (76.04) 98.76 (84.94) 88.70 (76.28) 99.08 (85.21) 88.98 (76.52) 99.39 (85.48) 89.26 (76.76) 99.70 (85.75) 89.54 (77.01) 100.02 (86.02) 89.82 (77.25) 100.33 (86.29) 90.11 (77.49) 100.65 (86.56)
29
SELECTION DATA
Table 4. Outdoor Unit Capacity (34, 36, 38HP) with Total Horsepower of Combined Indoor Unit (4)
Total
32.1 32.2 32.3 32.4 32.5 32.6 32.7 32.8 32.9 33.0 33.1 33.2 33.3 33.4 33.5 33.6 33.7 33.8 33.9 34.0 34.1 34.2 34.3 34.4 34.5 34.6 34.7 34.8 34.9 35.0 35.1 35.2 35.3 35.4 35.5 35.6 35.7 35.8 35.9 36.0 36.1 36.2 36.3 36.4 36.5 36.6 36.7 36.8 36.9 37.0
30
Outdoor Unit Capacity Unit: kW (x1,000kcal/h) RAS-34FSN Cooling Heating 90.58 (77.90) 101.85 (87.59) 90.86 (78.14) 102.18 (87.87) 91.15 (78.39) 102.50 (88.15) 91.44 (78.63) 102.82 (88.43) 91.72 (78.88) 103.15 (88.71) 92.01 (79.13) 103.47 (88.98) 92.29 (79.37) 103.79 (89.26) 92.58 (79.62) 104.12 (89.54) 92.86 (79.86) 104.44 (89.82) 93.15 (80.11) 104.76 (90.10) 93.43 (80.35) 105.09 (90.38) 93.72 (80.60) 105.41 (90.65) 94.00 (80.84) 105.74 (90.93) 94.29 (81.09) 106.06 (91.21) 94.57 (81.33) 106.38 (91.49) 94.86 (81.58) 106.71 (91.77) 95.14 (81.82) 107.03 (92.05) 95.43 (82.07) 107.35 (92.32) 95.71 (82.31) 107.68 (92.60) 96.00 (82.56) 108.00 (92.88) 96.27 (82.79) 108.08 (92.95) 96.53 (83.02) 108.16 (93.01) 96.80 (83.24) 108.23 (93.08) 97.06 (83.47) 108.31 (93.15) 97.33 (83.70) 108.39 (93.22) 97.59 (83.93) 108.47 (93.28) 97.86 (84.16) 108.55 (93.35) 98.12 (84.38) 108.62 (93.42) 98.39 (84.61) 108.70 (93.48) 98.65 (84.84) 108.78 (93.55) 98.92 (85.07) 108.85 (93.61) 99.18 (85.30) 108.91 (93.67) 99.45 (85.53) 108.98 (93.72) 99.71 (85.75) 109.05 (93.78) 99.98 (85.98) 109.12 (93.84) 100.24 (86.21) 109.18 (93.90) 100.51 (86.44) 109.25 (93.96) 100.77 (86.67) 109.30 (93.99) 101.04 (86.89) 109.34 (94.03) 101.30 (87.12) 109.39 (94.07) 101.57 (87.35) 109.43 (94.11) 101.84 (87.58) 109.48 (94.15) 102.10 (87.81) 109.53 (94.19) 102.37 (88.03) 109.57 (94.23) 102.63 (88.26) 109.62 (94.27) 102.90 (88.49) 109.66 (94.31) 103.16 (88.72) 109.71 (94.35) 103.43 (88.95) 109.75 (94.39) 103.69 (89.18) 109.80 (94.43) 103.96 (89.40) 109.84 (94.46)
RAS-36FSN Cooling Heating 90.06 (77.45) 100.76 (86.65) 90.34 (77.69) 101.07 (86.92) 90.62 (77.93) 101.39 (87.19) 90.90 (78.17) 101.70 (87.46) 91.18 (78.42) 102.01 (87.73) 91.46 (78.66) 102.33 (88.00) 91.74 (78.90) 102.64 (88.27) 92.02 (79.14) 102.96 (88.54) 92.30 (79.38) 103.27 (88.81) 92.58 (79.62) 103.58 (89.08) 92.86 (79.86) 103.90 (89.35) 93.14 (80.10) 104.21 (89.62) 93.43 (80.35) 104.53 (89.89) 93.71 (80.59) 104.84 (90.16) 93.99 (80.83) 105.15 (90.43) 94.27 (81.07) 105.47 (90.70) 94.55 (81.31) 105.78 (90.97) 94.83 (81.55) 106.09 (91.24) 95.11 (81.79) 106.41 (91.51) 95.39 (82.03) 106.72 (91.78) 95.67 (82.28) 107.04 (92.05) 95.95 (82.52) 107.35 (92.32) 96.23 (82.76) 107.66 (92.59) 96.51 (83.00) 107.98 (92.86) 96.79 (83.24) 108.29 (93.13) 97.07 (83.48) 108.61 (93.40) 97.35 (83.72) 108.92 (93.67) 97.63 (83.96) 109.23 (93.94) 97.91 (84.21) 109.55 (94.21) 98.19 (84.45) 109.86 (94.48) 98.48 (84.69) 110.18 (94.75) 98.76 (84.93) 110.49 (95.02) 99.04 (85.17) 110.80 (95.29) 99.32 (85.41) 111.12 (95.56) 99.60 (85.65) 111.43 (95.83) 99.88 (85.89) 111.74 (96.10) 100.16 (86.14) 112.06 (96.37) 100.44 (86.38) 112.37 (96.64) 100.72 (86.62) 112.69 (96.91) 101.00 (86.86) 113.00 (97.18) 101.20 (87.03) 113.11 (97.28) 101.40 (87.21) 113.22 (97.37) 101.60 (87.38) 113.34 (97.47) 101.81 (87.55) 113.45 (97.56) 102.01 (87.73) 113.56 (97.66) 102.21 (87.90) 113.67 (97.76) 102.41 (88.07) 113.77 (97.84) 102.61 (88.25) 113.87 (97.93) 102.81 (88.42) 113.98 (98.02) 103.01 (88.59) 114.08 (98.11)
RAS-38FSN Cooling Heating 90.39 (77.73) 100.96 (86.83) 90.67 (77.97) 101.28 (87.10) 90.95 (78.22) 101.59 (87.37) 91.23 (78.46) 101.90 (87.64) 91.51 (78.70) 102.22 (87.91) 91.79 (78.94) 102.53 (88.18) 92.08 (79.19) 102.85 (88.45) 92.36 (79.43) 103.16 (88.72) 92.64 (79.67) 103.48 (88.99) 92.92 (79.91) 103.79 (89.26) 93.20 (80.15) 104.10 (89.53) 93.48 (80.40) 104.42 (89.80) 93.77 (80.64) 104.73 (90.07) 94.05 (80.88) 105.05 (90.34) 94.33 (81.12) 105.36 (90.61) 94.61 (81.37) 105.67 (90.88) 94.89 (81.61) 105.99 (91.15) 95.17 (81.85) 106.30 (91.42) 95.46 (82.09) 106.62 (91.69) 95.74 (82.33) 106.93 (91.96) 96.02 (82.58) 107.25 (92.23) 96.30 (82.82) 107.56 (92.50) 96.58 (83.06) 107.87 (92.77) 96.86 (83.30) 108.19 (93.04) 97.14 (83.54) 108.50 (93.31) 97.43 (83.79) 108.82 (93.58) 97.71 (84.03) 109.13 (93.85) 97.99 (84.27) 109.45 (94.12) 98.27 (84.51) 109.76 (94.39) 98.55 (84.76) 110.07 (94.66) 98.83 (85.00) 110.39 (94.93) 99.12 (85.24) 110.70 (95.20) 99.40 (85.48) 111.02 (95.47) 99.68 (85.72) 111.33 (95.74) 99.96 (85.97) 111.64 (96.01) 100.24 (86.21) 111.96 (96.28) 100.52 (86.45) 112.27 (96.55) 100.81 (86.69) 112.59 (96.83) 101.09 (86.93) 112.90 (97.10) 101.37 (87.18) 113.22 (97.37) 101.65 (87.42) 113.53 (97.64) 101.93 (87.66) 113.84 (97.91) 102.21 (87.90) 114.16 (98.18) 102.49 (88.15) 114.47 (98.45) 102.78 (88.39) 114.79 (98.72) 103.06 (88.63) 115.10 (98.99) 103.34 (88.87) 115.42 (99.26) 103.62 (89.11) 115.73 (99.53) 103.90 (89.36) 116.04 (99.80) 104.18 (89.60) 116.36 (100.07)
SELECTION DATA
Table 5. Outdoor Unit Capacity (34, 36, 38HP) with Total Horsepower of Combined Indoor Unit (5)
Total
37.1 37.2 37.3 37.4 37.5 37.6 37.7 37.8 37.9 38.0 38.1 38.2 38.3 38.4 38.5 38.6 38.7 38.8 38.9 39.0 39.1 39.2 39.3 39.4 39.5 39.6 39.7 39.8 39.9 40.0 40.1 40.2 40.3 40.4 40.5 40.6 40.7 40.8 40.9 41.0 41.1 41.2 41.3 41.4 41.5 41.6 41.7 41.8 41.9 42.0
Outdoor Unit Capacity Unit: kW (x1,000kcal/h) RAS-34FSN Cooling Heating 104.22 (89.63) 109.88 (94.50) 104.49 (89.86) 109.92 (94.53) 104.75 (90.09) 109.96 (94.57) 105.02 (90.32) 110.00 (94.60) 105.28 (90.54) 110.05 (94.64) 105.55 (90.77) 110.09 (94.67) 105.81 (91.00) 110.13 (94.71) 106.08 (91.23) 110.17 (94.74) 106.34 (91.46) 110.21 (94.78) 106.61 (91.68) 110.25 (94.82) 106.87 (91.91) 110.29 (94.85) 107.14 (92.14) 110.33 (94.89) 107.33 (92.31) 110.37 (94.92) 107.53 (92.47) 110.41 (94.96) 107.72 (92.64) 110.45 (94.99) 107.91 (92.81) 110.50 (95.03) 108.11 (92.97) 110.54 (95.06) 108.30 (93.14) 110.58 (95.10) 108.44 (93.26) 110.62 (95.13) 108.58 (93.38) 110.66 (95.17) 108.72 (93.50) 110.70 (95.20) 108.86 (93.62) 110.75 (95.24) 108.96 (93.70) 110.79 (95.28) 109.05 (93.78) 110.84 (95.32) 109.15 (93.86) 110.88 (95.36) 109.24 (93.95) 110.93 (95.40) 109.33 (94.03) 110.97 (95.43) 109.43 (94.11) 111.02 (95.47) 109.52 (94.19) 111.06 (95.51) 109.61 (94.27) 111.11 (95.55) 109.71 (94.35) 111.15 (95.59) 109.80 (94.43) 111.20 (95.63) 109.84 (94.46) 111.24 (95.67) 109.89 (94.50) 111.29 (95.71) 109.93 (94.54) 111.33 (95.74) 109.97 (94.57) 111.38 (95.78) 110.01 (94.61) 111.42 (95.82) 110.06 (94.65) 111.47 (95.86) 110.10 (94.68) 111.51 (95.90) 110.14 (94.72) 111.56 (95.94) 110.18 (94.76) 111.60 (95.98) 110.23 (94.79) 111.65 (96.02) 110.27 (94.83) 111.69 (96.06) 110.31 (94.87) 111.74 (96.09) 110.33 (94.89) 111.78 (96.13) 110.36 (94.91) 111.83 (96.17) 110.38 (94.93) 111.87 (96.21) 110.41 (94.95) 111.92 (96.25) 110.43 (94.97) 111.96 (96.29) 110.46 (94.99) 112.01 (96.33)
RAS-36FSN Cooling Heating 103.21 (88.76) 114.18 (98.19) 103.42 (88.94) 114.24 (98.24) 103.62 (89.11) 114.29 (98.29) 103.82 (89.28) 114.35 (98.34) 104.02 (89.46) 114.40 (98.39) 104.18 (89.59) 114.46 (98.43) 104.33 (89.73) 114.51 (98.48) 104.49 (89.86) 114.57 (98.53) 104.65 (90.00) 114.62 (98.58) 104.80 (90.13) 114.68 (98.62) 104.96 (90.26) 114.71 (98.65) 105.12 (90.40) 114.73 (98.67) 105.27 (90.53) 114.76 (98.70) 105.43 (90.67) 114.79 (98.72) 105.58 (90.80) 114.82 (98.74) 105.74 (90.94) 114.84 (98.77) 105.90 (91.07) 114.87 (98.79) 106.05 (91.21) 114.90 (98.81) 106.21 (91.34) 114.93 (98.84) 106.37 (91.48) 114.95 (98.86) 106.52 (91.61) 114.98 (98.88) 106.68 (91.74) 115.01 (98.91) 106.79 (91.84) 115.04 (98.93) 106.90 (91.93) 115.06 (98.95) 107.01 (92.03) 115.09 (98.98) 107.12 (92.12) 115.11 (98.99) 107.23 (92.22) 115.12 (99.01) 107.34 (92.31) 115.14 (99.02) 107.45 (92.41) 115.16 (99.03) 107.56 (92.50) 115.17 (99.05) 107.67 (92.60) 115.19 (99.06) 107.78 (92.69) 115.21 (99.08) 107.89 (92.79) 115.22 (99.09) 108.00 (92.88) 115.24 (99.11) 108.11 (92.97) 115.26 (99.12) 108.22 (93.07) 115.27 (99.13) 108.33 (93.16) 115.29 (99.15) 108.44 (93.26) 115.31 (99.16) 108.55 (93.35) 115.32 (99.18) 108.66 (93.45) 115.34 (99.19) 108.74 (93.52) 115.36 (99.21) 108.82 (93.58) 115.37 (99.22) 108.90 (93.65) 115.39 (99.23) 108.97 (93.72) 115.40 (99.25) 109.05 (93.78) 115.42 (99.26) 109.13 (93.85) 115.44 (99.28) 109.21 (93.92) 115.45 (99.29) 109.29 (93.99) 115.47 (99.31) 109.37 (94.05) 115.49 (99.32) 109.44 (94.12) 115.50 (99.33)
RAS-38FSN Cooling Heating 104.47 (89.84) 116.67 (100.34) 104.75 (90.08) 116.99 (100.61) 105.03 (90.32) 117.30 (100.88) 105.31 (90.57) 117.61 (101.15) 105.59 (90.81) 117.93 (101.42) 105.87 (91.05) 118.24 (101.69) 106.16 (91.29) 118.56 (101.96) 106.44 (91.54) 118.87 (102.23) 106.72 (91.78) 119.19 (102.50) 107.00 (92.02) 119.50 (102.77) 107.08 (92.09) 119.50 (102.77) 107.16 (92.16) 119.50 (102.77) 107.24 (92.22) 119.50 (102.77) 107.31 (92.29) 119.50 (102.77) 107.39 (92.36) 119.50 (102.77) 107.47 (92.43) 119.50 (102.77) 107.55 (92.49) 119.50 (102.77) 107.63 (92.56) 119.50 (102.77) 107.71 (92.63) 119.50 (102.77) 107.79 (92.70) 119.50 (102.77) 107.87 (92.76) 119.50 (102.77) 107.94 (92.83) 119.50 (102.77) 108.02 (92.90) 119.50 (102.77) 108.10 (92.97) 119.50 (102.77) 108.18 (93.04) 119.50 (102.77) 108.26 (93.10) 119.50 (102.77) 108.34 (93.17) 119.50 (102.77) 108.42 (93.24) 119.50 (102.77) 108.50 (93.31) 119.50 (102.77) 108.57 (93.37) 119.50 (102.77) 108.65 (93.44) 119.50 (102.77) 108.73 (93.51) 119.50 (102.77) 108.81 (93.58) 119.50 (102.77) 108.87 (93.63) 119.50 (102.77) 108.93 (93.68) 119.50 (102.77) 108.99 (93.73) 119.50 (102.77) 109.05 (93.78) 119.50 (102.77) 109.11 (93.83) 119.50 (102.77) 109.17 (93.88) 119.50 (102.77) 109.23 (93.94) 119.50 (102.77) 109.29 (93.99) 119.50 (102.77) 109.35 (94.04) 119.50 (102.77) 109.41 (94.09) 119.50 (102.77) 109.47 (94.14) 119.50 (102.77) 109.52 (94.19) 119.50 (102.77) 109.58 (94.24) 119.50 (102.77) 109.64 (94.29) 119.50 (102.77) 109.70 (94.34) 119.50 (102.77) 109.76 (94.40) 119.50 (102.77) 109.82 (94.45) 119.50 (102.77)
31
SELECTION DATA
Table 6. Outdoor Unit Capacity (34, 36, 38HP) with Total Horsepower of Combined Indoor Unit (6)
Total
42.1 42.2 42.3 42.4 42.5 42.6 42.7 42.8 42.9 43.0 43.1 43.2 43.3 43.4 43.5 43.6 43.7 43.8 43.9 44.0 44.1 44.2 44.3 44.4 44.5 44.6 44.7 44.8 44.9 45.0 45.1 45.2 45.3 45.4 45.5 45.6 45.7 45.8 45.9 46.0 46.1 46.2 46.3 46.4 46.5 46.6 46.7 46.8 46.9 47.0
32
Outdoor Unit Capacity Unit: kW (x1,000kcal/h) RAS-34FSN Cooling Heating 110.48 (95.01) 112.05 (96.37) 110.51 (95.04) 112.10 (96.40) 110.53 (95.06) 112.14 (96.44) 110.56 (95.08) 112.19 (96.48) 110.58 (95.10) 112.23 (96.52) 110.61 (95.12) 112.28 (96.56) 110.63 (95.14) 112.32 (96.60) 110.66 (95.16) 112.37 (96.64) 110.68 (95.18) 112.41 (96.68) 110.70 (95.21) 112.46 (96.71) 110.73 (95.23) 112.50 (96.75) 110.75 (95.25) 112.55 (96.79) 110.78 (95.27) 112.59 (96.83) 110.80 (95.29) 112.64 (96.87) 110.83 (95.31) 112.68 (96.91) 110.85 (95.33) 112.73 (96.95) 110.88 (95.35) 112.77 (96.99) 110.90 (95.38) 112.82 (97.02) 110.93 (95.40) 112.86 (97.06) 110.95 (95.42) 112.91 (97.10) 110.98 (95.44) 112.95 (97.14) 111.00 (95.46) 113.00 (97.18)
--
RAS-36FSN Cooling Heating 109.52 (94.19) 115.52 (99.35) 109.60 (94.26) 115.54 (99.36) 109.68 (94.32) 115.55 (99.38) 109.76 (94.39) 115.57 (99.39) 109.84 (94.46) 115.59 (99.41) 109.91 (94.53) 115.60 (99.42) 109.99 (94.59) 115.62 (99.43) 110.07 (94.66) 115.64 (99.45) 110.15 (94.73) 115.65 (99.46) 110.23 (94.80) 115.67 (99.48) 110.31 (94.86) 115.69 (99.49) 110.38 (94.93) 115.70 (99.50) 110.46 (95.00) 115.72 (99.52) 110.54 (95.07) 115.74 (99.53) 110.62 (95.13) 115.75 (99.55) 110.66 (95.17) 115.77 (99.56) 110.70 (95.21) 115.79 (99.58) 110.75 (95.24) 115.80 (99.59) 110.79 (95.28) 115.82 (99.60) 110.83 (95.31) 115.84 (99.62) 110.87 (95.35) 115.85 (99.63) 110.91 (95.38) 115.87 (99.65) 110.95 (95.42) 115.89 (99.66) 111.00 (95.46) 115.90 (99.68) 111.04 (95.49) 115.92 (99.69) 111.08 (95.53) 115.94 (99.70) 111.12 (95.56) 115.95 (99.72) 111.16 (95.60) 115.97 (99.73) 111.21 (95.64) 115.99 (99.75) 111.25 (95.67) 116.00 (99.76) 111.29 (95.71) 116.02 (99.78) 111.33 (95.74) 116.03 (99.79) 111.37 (95.78) 116.05 (99.80) 111.41 (95.82) 116.07 (99.82) 111.46 (95.85) 116.08 (99.83) 111.50 (95.89) 116.10 (99.85) 111.54 (95.92) 116.12 (99.86) 111.58 (95.96) 116.13 (99.88) 111.62 (96.00) 116.15 (99.89) 111.67 (96.03) 116.17 (99.90) 111.71 (96.07) 116.18 (99.92) 111.75 (96.10) 116.20 (99.93) 111.79 (96.14) 116.22 (99.95) 111.83 (96.18) 116.23 (99.96) 111.87 (96.21) 116.25 (99.98) 111.92 (96.25) 116.27 (99.99) 111.96 (96.28) 116.28 (100.00) 112.00 (96.32) 116.30 (100.02) --
RAS-38FSN Cooling Heating 109.88 (94.50) 119.50 (102.77) 109.94 (94.55) 119.50 (102.77) 110.00 (94.60) 119.50 (102.77) 110.06 (94.65) 119.50 (102.77) 110.12 (94.70) 119.50 (102.77) 110.18 (94.75) 119.50 (102.77) 110.22 (94.79) 119.50 (102.77) 110.27 (94.83) 119.50 (102.77) 110.31 (94.87) 119.50 (102.77) 110.35 (94.90) 119.50 (102.77) 110.40 (94.94) 119.50 (102.77) 110.44 (94.98) 119.50 (102.77) 110.48 (95.01) 119.50 (102.77) 110.53 (95.05) 119.50 (102.77) 110.57 (95.09) 119.50 (102.77) 110.61 (95.13) 119.50 (102.77) 110.66 (95.16) 119.50 (102.77) 110.70 (95.20) 119.50 (102.77) 110.74 (95.24) 119.50 (102.77) 110.78 (95.27) 119.50 (102.77) 110.83 (95.31) 119.50 (102.77) 110.87 (95.35) 119.50 (102.77) 110.91 (95.39) 119.50 (102.77) 110.96 (95.42) 119.50 (102.77) 111.00 (95.46) 119.50 (102.77) 111.04 (95.50) 119.50 (102.77) 111.09 (95.53) 119.50 (102.77) 111.13 (95.57) 119.50 (102.77) 111.16 (95.59) 119.50 (102.77) 111.18 (95.62) 119.50 (102.77) 111.21 (95.64) 119.50 (102.77) 111.23 (95.66) 119.50 (102.77) 111.26 (95.68) 119.50 (102.77) 111.28 (95.70) 119.50 (102.77) 111.31 (95.73) 119.50 (102.77) 111.34 (95.75) 119.50 (102.77) 111.36 (95.77) 119.50 (102.77) 111.39 (95.79) 119.50 (102.77) 111.41 (95.81) 119.50 (102.77) 111.44 (95.84) 119.50 (102.77) 111.46 (95.86) 119.50 (102.77) 111.49 (95.88) 119.50 (102.77) 111.51 (95.90) 119.50 (102.77) 111.54 (95.92) 119.50 (102.77) 111.57 (95.95) 119.50 (102.77) 111.59 (95.97) 119.50 (102.77) 111.62 (95.99) 119.50 (102.77) 111.64 (96.01) 119.50 (102.77) 111.67 (96.04) 119.50 (102.77) 111.69 (96.06) 119.50 (102.77)
SELECTION DATA
Table 7. Outdoor Unit Capacity (34, 36, 38HP) with Total Horsepower of Combined Indoor Unit (7) Outdoor Unit Capacity Unit: kW (x1,000kcal/h)
Total Cooling 47.1 47.2 47.3 47.4 47.5 47.6 47.7 47.8 47.9 48.0 48.1 48.2 48.3 48.4 48.5 48.6 48.7 48.8 48.9 49.0 49.1 49.2 49.3 49.4
RAS-34FSN Heating
--
RAS-36FSN Cooling Heating
--
RAS-38FSN Cooling Heating 111.72 (96.08) 119.50 (102.77) 111.73 (96.09) 119.50 (102.77) 111.74 (96.10) 119.50 (102.77) 111.76 (96.11) 119.50 (102.77) 111.77 (96.12) 119.50 (102.77) 111.78 (96.13) 119.50 (102.77) 111.79 (96.14) 119.50 (102.77) 111.81 (96.15) 119.50 (102.77) 111.82 (96.16) 119.50 (102.77) 111.83 (96.17) 119.50 (102.77) 111.84 (96.18) 119.50 (102.77) 111.85 (96.19) 119.50 (102.77) 111.87 (96.20) 119.50 (102.77) 111.88 (96.22) 119.50 (102.77) 111.89 (96.23) 119.50 (102.77) 111.90 (96.24) 119.50 (102.77) 111.91 (96.25) 119.50 (102.77) 111.93 (96.26) 119.50 (102.77) 111.94 (96.27) 119.50 (102.77) 111.95 (96.28) 119.50 (102.77) 111.96 (96.29) 119.50 (102.77) 111.98 (96.30) 119.50 (102.77) 111.99 (96.31) 119.50 (102.77) 112.00 (96.32) 119.50 (102.77)
33
SELECTION DATA
Table 8. Outdoor Unit Capacity (40, 42HP) with Total Horsepower of Combined Indoor Unit (1)
Total
20.0 20.1 20.2 20.3 20.4 20.5 20.6 20.7 20.8 20.9 21.0 21.1 21.2 21.3 21.4 21.5 21.6 21.7 21.8 21.9 22.0 22.1 22.2 22.3 22.4 22.5 22.6 22.7 22.8 22.9 23.0 23.1 23.2 23.3 23.4 23.5 23.6 23.7 23.8 23.9 24.0 24.1 24.2 24.3 24.4 24.5 24.6 24.7 24.8 24.9 25.0
34
Outdoor Unit Capacity Unit: kW (x1,000kcal/h) RAS-40FSN Cooling Heating 56.50 (48.59) 63.50 (54.61) 56.78 (48.83) 63.82 (54.88) 57.07 (49.08) 64.14 (55.16) 57.35 (49.32) 64.45 (55.43) 57.63 (49.56) 64.77 (55.70) 57.91 (49.80) 65.09 (55.98) 58.20 (50.05) 65.41 (56.25) 58.48 (50.29) 65.72 (56.52) 58.76 (50.53) 66.04 (56.79) 59.04 (50.78) 66.36 (57.07) 59.33 (51.02) 66.68 (57.34) 59.61 (51.26) 66.99 (57.61) 59.89 (51.51) 67.31 (57.89) 60.17 (51.75) 67.63 (58.16) 60.46 (51.99) 67.95 (58.43) 60.74 (52.23) 68.26 (58.71) 61.02 (52.48) 68.58 (58.98) 61.30 (52.72) 68.90 (59.25) 61.59 (52.96) 69.22 (59.52) 61.87 (53.21) 69.53 (59.80) 62.15 (53.45) 69.85 (60.07) 62.43 (53.69) 70.17 (60.34) 62.72 (53.93) 70.49 (60.62) 63.00 (54.18) 70.80 (60.89) 63.28 (54.42) 71.12 (61.16) 63.56 (54.66) 71.44 (61.44) 63.85 (54.91) 71.76 (61.71) 64.13 (55.15) 72.07 (61.98) 64.41 (55.39) 72.39 (62.26) 64.69 (55.64) 72.71 (62.53) 64.98 (55.88) 73.03 (62.80) 65.26 (56.12) 73.34 (63.07) 65.54 (56.36) 73.66 (63.35) 65.82 (56.61) 73.98 (63.62) 66.11 (56.85) 74.30 (63.89) 66.39 (57.09) 74.61 (64.17) 66.67 (57.34) 74.93 (64.44) 66.95 (57.58) 75.25 (64.71) 67.24 (57.82) 75.57 (64.99) 67.52 (58.07) 75.88 (65.26) 67.80 (58.31) 76.20 (65.53) 68.08 (58.55) 76.52 (65.81) 68.37 (58.79) 76.84 (66.08) 68.65 (59.04) 77.15 (66.35) 68.93 (59.28) 77.47 (66.62) 69.21 (59.52) 77.79 (66.90) 69.50 (59.77) 78.11 (67.17) 69.78 (60.01) 78.42 (67.44) 70.06 (60.25) 78.74 (67.72) 70.34 (60.49) 79.06 (67.99) 70.63 (60.74) 79.38 (68.26)
RAS-42FSN
59.00 59.28 59.56 59.84 60.12 60.40 60.69 60.97 61.25 61.53 61.81 62.09 62.37 62.65 62.93 63.21 63.50 63.78 64.06 64.34 64.62 64.90 65.18 65.46 65.74 66.02 66.30 66.59 66.87 67.15 67.43 67.71 67.99 68.27 68.55 68.83 69.11 69.40 69.68 69.96 70.24
Cooling
Heating
--
--
(50.74) (50.98) (51.22) (51.46) (51.71) (51.95) (52.19) (52.43) (52.67) (52.91) (53.16) (53.40) (53.64) (53.88) (54.12) (54.36) (54.61) (54.85) (55.09) (55.33) (55.57) (55.81) (56.06) (56.30) (56.54) (56.78) (57.02) (57.26) (57.51) (57.75) (57.99) (58.23) (58.47) (58.71) (58.96) (59.20) (59.44) (59.68) (59.92) (60.16) (60.40)
66.00 66.31 66.63 66.94 67.26 67.57 67.89 68.20 68.51 68.83 69.14 69.46 69.77 70.09 70.40 70.71 71.03 71.34 71.66 71.97 72.29 72.60 72.91 73.23 73.54 73.86 74.17 74.49 74.80 75.11 75.43 75.74 76.06 76.37 76.69 77.00 77.31 77.63 77.94 78.26 78.57
(56.76) (57.03) (57.30) (57.57) (57.84) (58.11) (58.38) (58.65) (58.92) (59.19) (59.46) (59.73) (60.00) (60.27) (60.54) (60.81) (61.08) (61.35) (61.63) (61.90) (62.17) (62.44) (62.71) (62.98) (63.25) (63.52) (63.79) (64.06) (64.33) (64.60) (64.87) (65.14) (65.41) (65.68) (65.95) (66.22) (66.49) (66.76) (67.03) (67.30) (67.57)
SELECTION DATA
Table 9. Outdoor Unit Capacity (40, 42HP) with Total Horsepower of Combined Indoor Unit (2)
Total
25.1 25.2 25.3 25.4 25.5 25.6 25.7 25.8 25.9 26.0 26.1 26.2 26.3 26.4 26.5 26.6 26.7 26.8 26.9 27.0 27.1 27.2 27.3 27.4 27.5 27.6 27.7 27.8 27.9 28.0 28.1 28.2 28.3 28.4 28.5 28.6 28.7 28.8 28.9 29.0 29.1 29.2 29.3 29.4 29.5 29.6 29.7 29.8 29.9 30.0
Outdoor Unit Capacity Unit: kW (x1,000kcal/h) RAS-40FSN Cooling Heating 70.91 (60.98) 79.69 (68.54) 71.19 (61.22) 80.01 (68.81) 71.47 (61.47) 80.33 (69.08) 71.76 (61.71) 80.65 (69.35) 72.04 (61.95) 80.96 (69.63) 72.32 (62.20) 81.28 (69.90) 72.60 (62.44) 81.60 (70.17) 72.89 (62.68) 81.92 (70.45) 73.17 (62.92) 82.23 (70.72) 73.45 (63.17) 82.55 (70.99) 73.73 (63.41) 82.87 (71.27) 74.02 (63.65) 83.19 (71.54) 74.30 (63.90) 83.50 (71.81) 74.58 (64.14) 83.82 (72.09) 74.86 (64.38) 84.14 (72.36) 75.15 (64.62) 84.46 (72.63) 75.43 (64.87) 84.77 (72.90) 75.71 (65.11) 85.09 (73.18) 75.99 (65.35) 85.41 (73.45) 76.28 (65.60) 85.73 (73.72) 76.56 (65.84) 86.04 (74.00) 76.84 (66.08) 86.36 (74.27) 77.12 (66.33) 86.68 (74.54) 77.41 (66.57) 87.00 (74.82) 77.69 (66.81) 87.31 (75.09) 77.97 (67.05) 87.63 (75.36) 78.25 (67.30) 87.95 (75.63) 78.54 (67.54) 88.27 (75.91) 78.82 (67.78) 88.58 (76.18) 79.10 (68.03) 88.90 (76.45) 79.38 (68.27) 89.22 (76.73) 79.67 (68.51) 89.54 (77.00) 79.95 (68.75) 89.85 (77.27) 80.23 (69.00) 90.17 (77.55) 80.51 (69.24) 90.49 (77.82) 80.80 (69.48) 90.81 (78.09) 81.08 (69.73) 91.12 (78.37) 81.36 (69.97) 91.44 (78.64) 81.64 (70.21) 91.76 (78.91) 81.93 (70.46) 92.08 (79.18) 82.21 (70.70) 92.39 (79.46) 82.49 (70.94) 92.71 (79.73) 82.77 (71.18) 93.03 (80.00) 83.06 (71.43) 93.35 (80.28) 83.34 (71.67) 93.66 (80.55) 83.62 (71.91) 93.98 (80.82) 83.90 (72.16) 94.30 (81.10) 84.19 (72.40) 94.62 (81.37) 84.47 (72.64) 94.93 (81.64) 84.75 (72.89) 95.25 (81.92)
70.52 70.80 71.08 71.36 71.64 71.92 72.20 72.49 72.77 73.05 73.33 73.61 73.89 74.17 74.45 74.73 75.01 75.30 75.58 75.86 76.14 76.42 76.70 76.98 77.26 77.54 77.82 78.10 78.39 78.67 78.95 79.23 79.51 79.79 80.07 80.35 80.63 80.91 81.20 81.48 81.76 82.04 82.32 82.60 82.88 83.16 83.44 83.72 84.00 84.29
RAS-42FSN Cooling Heating (60.65) 78.89 (67.84) (60.89) 79.20 (68.11) (61.13) 79.51 (68.38) (61.37) 79.83 (68.65) (61.61) 80.14 (68.92) (61.85) 80.46 (69.19) (62.10) 80.77 (69.46) (62.34) 81.09 (69.73) (62.58) 81.40 (70.00) (62.82) 81.71 (70.27) (63.06) 82.03 (70.54) (63.30) 82.34 (70.81) (63.55) 82.66 (71.09) (63.79) 82.97 (71.36) (64.03) 83.29 (71.63) (64.27) 83.60 (71.90) (64.51) 83.91 (72.17) (64.75) 84.23 (72.44) (65.00) 84.54 (72.71) (65.24) 84.86 (72.98) (65.48) 85.17 (73.25) (65.72) 85.49 (73.52) (65.96) 85.80 (73.79) (66.20) 86.11 (74.06) (66.45) 86.43 (74.33) (66.69) 86.74 (74.60) (66.93) 87.06 (74.87) (67.17) 87.37 (75.14) (67.41) 87.69 (75.41) (67.65) 88.00 (75.68) (67.89) 88.31 (75.95) (68.14) 88.63 (76.22) (68.38) 88.94 (76.49) (68.62) 89.26 (76.76) (68.86) 89.57 (77.03) (69.10) 89.89 (77.30) (69.34) 90.20 (77.57) (69.59) 90.51 (77.84) (69.83) 90.83 (78.11) (70.07) 91.14 (78.38) (70.31) 91.46 (78.65) (70.55) 91.77 (78.92) (70.79) 92.09 (79.19) (71.04) 92.40 (79.46) (71.28) 92.71 (79.73) (71.52) 93.03 (80.00) (71.76) 93.34 (80.27) (72.00) 93.66 (80.55) (72.24) 93.97 (80.82) (72.49) 94.29 (81.09)
35
SELECTION DATA
Table 10. Outdoor Unit Capacity (40, 42HP) with Total Horsepower of Combined Indoor Unit (3)
Total
30.1 30.2 30.3 30.4 30.5 30.6 30.7 30.8 30.9 31.0 31.1 31.2 31.3 31.4 31.5 31.6 31.7 31.8 31.9 32.0 32.1 32.2 32.3 32.4 32.5 32.6 32.7 32.8 32.9 33.0 33.1 33.2 33.3 33.4 33.5 33.6 33.7 33.8 33.9 34.0 34.1 34.2 34.3 34.4 34.5 34.6 34.7 34.8 34.9 35.0
36
Outdoor Unit Capacity Unit: kW (x1,000kcal/h) RAS-40FSN Cooling Heating 85.03 (73.13) 95.57 (82.19) 85.32 (73.37) 95.89 (82.46) 85.60 (73.61) 96.20 (82.73) 85.88 (73.86) 96.52 (83.01) 86.16 (74.10) 96.84 (83.28) 86.45 (74.34) 97.16 (83.55) 86.73 (74.59) 97.47 (83.83) 87.01 (74.83) 97.79 (84.10) 87.29 (75.07) 98.11 (84.37) 87.58 (75.31) 98.43 (84.65) 87.86 (75.56) 98.74 (84.92) 88.14 (75.80) 99.06 (85.19) 88.42 (76.04) 99.38 (85.46) 88.71 (76.29) 99.70 (85.74) 88.99 (76.53) 100.01 (86.01) 89.27 (76.77) 100.33 (86.28) 89.55 (77.02) 100.65 (86.56) 89.84 (77.26) 100.97 (86.83) 90.12 (77.50) 101.28 (87.10) 90.40 (77.74) 101.60 (87.38) 90.68 (77.99) 101.92 (87.65) 90.97 (78.23) 102.24 (87.92) 91.25 (78.47) 102.55 (88.20) 91.53 (78.72) 102.87 (88.47) 91.81 (78.96) 103.19 (88.74) 92.10 (79.20) 103.51 (89.01) 92.38 (79.44) 103.82 (89.29) 92.66 (79.69) 104.14 (89.56) 92.94 (79.93) 104.46 (89.83) 93.23 (80.17) 104.78 (90.11) 93.51 (80.42) 105.09 (90.38) 93.79 (80.66) 105.41 (90.65) 94.07 (80.90) 105.73 (90.93) 94.36 (81.15) 106.05 (91.20) 94.64 (81.39) 106.36 (91.47) 94.92 (81.63) 106.68 (91.74) 95.20 (81.87) 107.00 (92.02) 95.49 (82.12) 107.32 (92.29) 95.77 (82.36) 107.63 (92.56) 96.05 (82.60) 107.95 (92.84) 96.33 (82.85) 108.27 (93.11) 96.62 (83.09) 108.59 (93.38) 96.90 (83.33) 108.90 (93.66) 97.18 (83.57) 109.22 (93.93) 97.46 (83.82) 109.54 (94.20) 97.75 (84.06) 109.86 (94.48) 98.03 (84.30) 110.17 (94.75) 98.31 (84.55) 110.49 (95.02) 98.59 (84.79) 110.81 (95.29) 98.88 (85.03) 111.13 (95.57)
84.57 84.85 85.13 85.41 85.69 85.97 86.25 86.53 86.81 87.10 87.38 87.66 87.94 88.22 88.50 88.78 89.06 89.34 89.62 89.90 90.19 90.47 90.75 91.03 91.31 91.59 91.87 92.15 92.43 92.71 93.00 93.28 93.56 93.84 94.12 94.40 94.68 94.96 95.24 95.52 95.80 96.09 96.37 96.65 96.93 97.21 97.49 97.77 98.05 98.33
RAS-42FSN Cooling Heating (72.73) 94.60 (81.36) (72.97) 94.91 (81.63) (73.21) 95.23 (81.90) (73.45) 95.54 (82.17) (73.69) 95.86 (82.44) (73.94) 96.17 (82.71) (74.18) 96.49 (82.98) (74.42) 96.80 (83.25) (74.66) 97.11 (83.52) (74.90) 97.43 (83.79) (75.14) 97.74 (84.06) (75.39) 98.06 (84.33) (75.63) 98.37 (84.60) (75.87) 98.69 (84.87) (76.11) 99.00 (85.14) (76.35) 99.31 (85.41) (76.59) 99.63 (85.68) (76.83) 99.94 (85.95) (77.08) 100.26 (86.22) (77.32) 100.57 (86.49) (77.56) 100.89 (86.76) (77.80) 101.20 (87.03) (78.04) 101.51 (87.30) (78.28) 101.83 (87.57) (78.53) 102.14 (87.84) (78.77) 102.46 (88.11) (79.01) 102.77 (88.38) (79.25) 103.09 (88.65) (79.49) 103.40 (88.92) (79.73) 103.71 (89.19) (79.98) 104.03 (89.46) (80.22) 104.34 (89.73) (80.46) 104.66 (90.01) (80.70) 104.97 (90.28) (80.94) 105.29 (90.55) (81.18) 105.60 (90.82) (81.43) 105.91 (91.09) (81.67) 106.23 (91.36) (81.91) 106.54 (91.63) (82.15) 106.86 (91.90) (82.39) 107.17 (92.17) (82.63) 107.49 (92.44) (82.88) 107.80 (92.71) (83.12) 108.11 (92.98) (83.36) 108.43 (93.25) (83.60) 108.74 (93.52) (83.84) 109.06 (93.79) (84.08) 109.37 (94.06) (84.33) 109.69 (94.33) (84.57) 110.00 (94.60)
SELECTION DATA
Table 11. Outdoor Unit Capacity (40, 42HP) with Total Horsepower of Combined Indoor Unit (4)
Total
35.1 35.2 35.3 35.4 35.5 35.6 35.7 35.8 35.9 36.0 36.1 36.2 36.3 36.4 36.5 36.6 36.7 36.8 36.9 37.0 37.1 37.2 37.3 37.4 37.5 37.6 37.7 37.8 37.9 38.0 38.1 38.2 38.3 38.4 38.5 38.6 38.7 38.8 38.9 39.0 39.1 39.2 39.3 39.4 39.5 39.6 39.7 39.8 39.9 40.0
Outdoor Unit Capacity Unit: kW (x1,000kcal/h) RAS-40FSN Cooling Heating 99.16 (85.28) 111.44 (95.84) 99.44 (85.52) 111.76 (96.11) 99.72 (85.76) 112.08 (96.39) 100.01 (86.00) 112.40 (96.66) 100.29 (86.25) 112.71 (96.93) 100.57 (86.49) 113.03 (97.21) 100.85 (86.73) 113.35 (97.48) 101.14 (86.98) 113.67 (97.75) 101.42 (87.22) 113.98 (98.02) 101.70 (87.46) 114.30 (98.30) 101.98 (87.70) 114.62 (98.57) 102.27 (87.95) 114.94 (98.84) 102.55 (88.19) 115.25 (99.12) 102.83 (88.43) 115.57 (99.39) 103.11 (88.68) 115.89 (99.66) 103.40 (88.92) 116.21 (99.94) 103.68 (89.16) 116.52 (100.21) 103.96 (89.41) 116.84 (100.48) 104.24 (89.65) 117.16 (100.76) 104.53 (89.89) 117.48 (101.03) 104.81 (90.13) 117.79 (101.30) 105.09 (90.38) 118.11 (101.57) 105.37 (90.62) 118.43 (101.85) 105.66 (90.86) 118.75 (102.12) 105.94 (91.11) 119.06 (102.39) 106.22 (91.35) 119.38 (102.67) 106.50 (91.59) 119.70 (102.94) 106.79 (91.84) 120.02 (103.21) 107.07 (92.08) 120.33 (103.49) 107.35 (92.32) 120.65 (103.76) 107.63 (92.56) 120.97 (104.03) 107.92 (92.81) 121.29 (104.31) 108.20 (93.05) 121.60 (104.58) 108.48 (93.29) 121.92 (104.85) 108.76 (93.54) 122.24 (105.12) 109.05 (93.78) 122.56 (105.40) 109.33 (94.02) 122.87 (105.67) 109.61 (94.26) 123.19 (105.94) 109.89 (94.51) 123.51 (106.22) 110.18 (94.75) 123.83 (106.49) 110.46 (94.99) 124.14 (106.76) 110.74 (95.24) 124.46 (107.04) 111.02 (95.48) 124.78 (107.31) 111.31 (95.72) 125.10 (107.58) 111.59 (95.97) 125.41 (107.85) 111.87 (96.21) 125.73 (108.13) 112.15 (96.45) 126.05 (108.40) 112.44 (96.69) 126.37 (108.67) 112.72 (96.94) 126.68 (108.95) 113.00 (97.18) 127.00 (109.22)
RAS-42FSN Cooling Heating 98.61 (84.81) 110.31 (94.87) 98.90 (85.05) 110.63 (95.14) 99.18 (85.29) 110.94 (95.41) 99.46 (85.53) 111.26 (95.68) 99.74 (85.77) 111.57 (95.95) 100.02 (86.02) 111.89 (96.22) 100.30 (86.26) 112.20 (96.49) 100.58 (86.50) 112.51 (96.76) 100.86 (86.74) 112.83 (97.03) 101.14 (86.98) 113.14 (97.30) 101.42 (87.22) 113.46 (97.57) 101.70 (87.47) 113.77 (97.84) 101.99 (87.71) 114.09 (98.11) 102.27 (87.95) 114.40 (98.38) 102.55 (88.19) 114.71 (98.65) 102.83 (88.43) 115.03 (98.92) 103.11 (88.67) 115.34 (99.19) 103.39 (88.92) 115.66 (99.47) 103.67 (89.16) 115.97 (99.74) 103.95 (89.40) 116.29 (100.01) 104.23 (89.64) 116.60 (100.28) 104.51 (89.88) 116.91 (100.55) 104.80 (90.12) 117.23 (100.82) 105.08 (90.37) 117.54 (101.09) 105.36 (90.61) 117.86 (101.36) 105.64 (90.85) 118.17 (101.63) 105.92 (91.09) 118.49 (101.90) 106.20 (91.33) 118.80 (102.17) 106.48 (91.57) 119.11 (102.44) 106.76 (91.82) 119.43 (102.71) 107.04 (92.06) 119.74 (102.98) 107.32 (92.30) 120.06 (103.25) 107.60 (92.54) 120.37 (103.52) 107.89 (92.78) 120.69 (103.79) 108.17 (93.02) 121.00 (104.06) 108.45 (93.26) 121.31 (104.33) 108.73 (93.51) 121.63 (104.60) 109.01 (93.75) 121.94 (104.87) 109.29 (93.99) 122.26 (105.14) 109.57 (94.23) 122.57 (105.41) 109.85 (94.47) 122.89 (105.68) 110.13 (94.71) 123.20 (105.95) 110.41 (94.96) 123.51 (106.22) 110.70 (95.20) 123.83 (106.49) 110.98 (95.44) 124.14 (106.76) 111.26 (95.68) 124.46 (107.03) 111.54 (95.92) 124.77 (107.30) 111.82 (96.16) 125.09 (107.57) 112.10 (96.41) 125.40 (107.84) 112.38 (96.65) 125.71 (108.11)
37
SELECTION DATA
Table 12. Outdoor Unit Capacity (40, 42HP) with Total Horsepower of Combined Indoor Unit (5)
Total
40.1 40.2 40.3 40.4 40.5 40.6 40.7 40.8 40.9 41.0 41.1 41.2 41.3 41.4 41.5 41.6 41.7 41.8 41.9 42.0 42.1 42.2 42.3 42.4 42.5 42.6 42.7 42.8 42.9 43.0 43.1 43.2 43.3 43.4 43.5 43.6 43.7 43.8 43.9 44.0 44.1 44.2 44.3 44.4 44.5 44.6 44.7 44.8 44.9 45.0
38
Outdoor Unit Capacity Unit: kW (x1,000kcal/h) RAS-40FSN Cooling Heating 113.08 (97.24) 127.00 (109.22) 113.15 (97.31) 127.00 (109.22) 113.23 (97.37) 127.00 (109.22) 113.30 (97.44) 127.00 (109.22) 113.38 (97.50) 127.00 (109.22) 113.45 (97.57) 127.00 (109.22) 113.53 (97.63) 127.00 (109.22) 113.60 (97.70) 127.00 (109.22) 113.68 (97.76) 127.00 (109.22) 113.75 (97.83) 127.00 (109.22) 113.83 (97.89) 127.00 (109.22) 113.91 (97.96) 127.00 (109.22) 113.98 (98.02) 127.00 (109.22) 114.06 (98.09) 127.00 (109.22) 114.13 (98.15) 127.00 (109.22) 114.21 (98.22) 127.00 (109.22) 114.28 (98.28) 127.00 (109.22) 114.36 (98.35) 127.00 (109.22) 114.43 (98.41) 127.00 (109.22) 114.51 (98.48) 127.00 (109.22) 114.58 (98.54) 127.00 (109.22) 114.66 (98.61) 127.00 (109.22) 114.73 (98.67) 127.00 (109.22) 114.81 (98.74) 127.00 (109.22) 114.87 (98.79) 127.00 (109.22) 114.92 (98.83) 127.00 (109.22) 114.98 (98.88) 127.00 (109.22) 115.04 (98.93) 127.00 (109.22) 115.10 (98.98) 127.00 (109.22) 115.15 (99.03) 127.00 (109.22) 115.21 (99.08) 127.00 (109.22) 115.27 (99.13) 127.00 (109.22) 115.32 (99.18) 127.00 (109.22) 115.38 (99.23) 127.00 (109.22) 115.44 (99.28) 127.00 (109.22) 115.50 (99.33) 127.00 (109.22) 115.55 (99.37) 127.00 (109.22) 115.61 (99.42) 127.00 (109.22) 115.67 (99.47) 127.00 (109.22) 115.72 (99.52) 127.00 (109.22) 115.78 (99.57) 127.00 (109.22) 115.84 (99.62) 127.00 (109.22) 115.89 (99.67) 127.00 (109.22) 115.95 (99.72) 127.00 (109.22) 116.01 (99.77) 127.00 (109.22) 116.07 (99.82) 127.00 (109.22) 116.12 (99.87) 127.00 (109.22) 116.18 (99.91) 127.00 (109.22) 116.22 (99.95) 127.00 (109.22) 116.26 (99.98) 127.00 (109.22)
RAS-42FSN Cooling Heating 112.66 (96.89) 126.03 (108.38) 112.94 (97.13) 126.34 (108.65) 113.22 (97.37) 126.66 (108.93) 113.50 (97.61) 126.97 (109.20) 113.79 (97.86) 127.29 (109.47) 114.07 (98.10) 127.60 (109.74) 114.35 (98.34) 127.91 (110.01) 114.63 (98.58) 128.23 (110.28) 114.91 (98.82) 128.54 (110.55) 115.19 (99.06) 128.86 (110.82) 115.47 (99.31) 129.17 (111.09) 115.75 (99.55) 129.49 (111.36) 116.03 (99.79) 129.80 (111.63) 116.31 (100.03) 130.11 (111.90) 116.60 (100.27) 130.43 (112.17) 116.88 (100.51) 130.74 (112.44) 117.16 (100.76) 131.06 (112.71) 117.44 (101.00) 131.37 (112.98) 117.72 (101.24) 131.69 (113.25) 118.00 (101.48) 132.00 (113.52) 118.08 (101.54) 132.00 (113.52) 118.15 (101.61) 132.00 (113.52) 118.23 (101.67) 132.00 (113.52) 118.30 (101.74) 132.00 (113.52) 118.38 (101.80) 132.00 (113.52) 118.45 (101.87) 132.00 (113.52) 118.53 (101.93) 132.00 (113.52) 118.60 (102.00) 132.00 (113.52) 118.68 (102.06) 132.00 (113.52) 118.75 (102.13) 132.00 (113.52) 118.83 (102.19) 132.00 (113.52) 118.90 (102.26) 132.00 (113.52) 118.98 (102.32) 132.00 (113.52) 119.05 (102.39) 132.00 (113.52) 119.13 (102.45) 132.00 (113.52) 119.20 (102.51) 132.00 (113.52) 119.28 (102.58) 132.00 (113.52) 119.35 (102.64) 132.00 (113.52) 119.43 (102.71) 132.00 (113.52) 119.50 (102.77) 132.00 (113.52) 119.58 (102.84) 132.00 (113.52) 119.65 (102.90) 132.00 (113.52) 119.73 (102.97) 132.00 (113.52) 119.80 (103.03) 132.00 (113.52) 119.88 (103.10) 132.00 (113.52) 119.94 (103.15) 132.00 (113.52) 119.99 (103.19) 132.00 (113.52) 120.05 (103.24) 132.00 (113.52) 120.11 (103.29) 132.00 (113.52) 120.16 (103.34) 132.00 (113.52)
SELECTION DATA
Table 13. Outdoor Unit Capacity (40, 42HP) with Total Horsepower of Combined Indoor Unit (6)
Total
45.1 45.2 45.3 45.4 45.5 45.6 45.7 45.8 45.9 46.0 46.1 46.2 46.3 46.4 46.5 46.6 46.7 46.8 46.9 47.0 47.1 47.2 47.3 47.4 47.5 47.6 47.7 47.8 47.9 48.0 48.1 48.2 48.3 48.4 48.5 48.6 48.7 48.8 48.9 49.0 49.1 49.2 49.3 49.4 49.5 49.6 49.7 49.8 49.9 50.0
Outdoor Unit Capacity Unit: kW (x1,000kcal/h) RAS-40FSN Cooling Heating 116.30 (100.02) 127.00 (109.22) 116.34 (100.05) 127.00 (109.22) 116.38 (100.09) 127.00 (109.22) 116.42 (100.12) 127.00 (109.22) 116.46 (100.15) 127.00 (109.22) 116.50 (100.19) 127.00 (109.22) 116.54 (100.22) 127.00 (109.22) 116.58 (100.26) 127.00 (109.22) 116.62 (100.29) 127.00 (109.22) 116.66 (100.32) 127.00 (109.22) 116.69 (100.36) 127.00 (109.22) 116.73 (100.39) 127.00 (109.22) 116.77 (100.43) 127.00 (109.22) 116.81 (100.46) 127.00 (109.22) 116.85 (100.49) 127.00 (109.22) 116.89 (100.53) 127.00 (109.22) 116.93 (100.56) 127.00 (109.22) 116.97 (100.60) 127.00 (109.22) 117.01 (100.63) 127.00 (109.22) 117.05 (100.66) 127.00 (109.22) 117.09 (100.70) 127.00 (109.22) 117.13 (100.73) 127.00 (109.22) 117.15 (100.75) 127.00 (109.22) 117.18 (100.77) 127.00 (109.22) 117.20 (100.80) 127.00 (109.22) 117.23 (100.82) 127.00 (109.22) 117.25 (100.84) 127.00 (109.22) 117.28 (100.86) 127.00 (109.22) 117.30 (100.88) 127.00 (109.22) 117.33 (100.90) 127.00 (109.22) 117.35 (100.92) 127.00 (109.22) 117.38 (100.94) 127.00 (109.22) 117.40 (100.96) 127.00 (109.22) 117.43 (100.99) 127.00 (109.22) 117.45 (101.01) 127.00 (109.22) 117.47 (101.03) 127.00 (109.22) 117.50 (101.05) 127.00 (109.22) 117.52 (101.07) 127.00 (109.22) 117.55 (101.09) 127.00 (109.22) 117.57 (101.11) 127.00 (109.22) 117.60 (101.13) 127.00 (109.22) 117.62 (101.15) 127.00 (109.22) 117.65 (101.18) 127.00 (109.22) 117.67 (101.20) 127.00 (109.22) 117.70 (101.22) 127.00 (109.22) 117.72 (101.24) 127.00 (109.22) 117.73 (101.25) 127.00 (109.22) 117.74 (101.26) 127.00 (109.22) 117.76 (101.27) 127.00 (109.22) 117.77 (101.28) 127.00 (109.22)
RAS-42FSN Cooling Heating 120.22 (103.39) 132.00 (113.52) 120.28 (103.44) 132.00 (113.52) 120.33 (103.49) 132.00 (113.52) 120.39 (103.54) 132.00 (113.52) 120.45 (103.59) 132.00 (113.52) 120.50 (103.63) 132.00 (113.52) 120.56 (103.68) 132.00 (113.52) 120.62 (103.73) 132.00 (113.52) 120.68 (103.78) 132.00 (113.52) 120.73 (103.83) 132.00 (113.52) 120.79 (103.88) 132.00 (113.52) 120.85 (103.93) 132.00 (113.52) 120.90 (103.98) 132.00 (113.52) 120.96 (104.02) 132.00 (113.52) 121.02 (104.07) 132.00 (113.52) 121.07 (104.12) 132.00 (113.52) 121.13 (104.17) 132.00 (113.52) 121.19 (104.22) 132.00 (113.52) 121.24 (104.27) 132.00 (113.52) 121.30 (104.32) 132.00 (113.52) 121.34 (104.35) 132.00 (113.52) 121.38 (104.38) 132.00 (113.52) 121.42 (104.42) 132.00 (113.52) 121.45 (104.45) 132.00 (113.52) 121.49 (104.48) 132.00 (113.52) 121.53 (104.52) 132.00 (113.52) 121.57 (104.55) 132.00 (113.52) 121.61 (104.58) 132.00 (113.52) 121.65 (104.62) 132.00 (113.52) 121.68 (104.65) 132.00 (113.52) 121.72 (104.68) 132.00 (113.52) 121.76 (104.71) 132.00 (113.52) 121.80 (104.75) 132.00 (113.52) 121.84 (104.78) 132.00 (113.52) 121.88 (104.81) 132.00 (113.52) 121.92 (104.85) 132.00 (113.52) 121.95 (104.88) 132.00 (113.52) 121.99 (104.91) 132.00 (113.52) 122.03 (104.95) 132.00 (113.52) 122.07 (104.98) 132.00 (113.52) 122.11 (105.01) 132.00 (113.52) 122.15 (105.05) 132.00 (113.52) 122.18 (105.08) 132.00 (113.52) 122.22 (105.11) 132.00 (113.52) 122.26 (105.14) 132.00 (113.52) 122.30 (105.18) 132.00 (113.52) 122.32 (105.20) 132.00 (113.52) 122.35 (105.22) 132.00 (113.52) 122.37 (105.24) 132.00 (113.52) 122.40 (105.26) 132.00 (113.52)
39
SELECTION DATA
Table 14. Outdoor Unit Capacity (40, 42HP) with Total Horsepower of Combined Indoor Unit (7)
Total
50.1 50.2 50.3 50.4 50.5 50.6 50.7 50.8 50.9 51.0 51.1 51.2 51.3 51.4 51.5 51.6 51.7 51.8 51.9 52.0 52.1 52.2 52.3 52.4 52.5 52.6 52.7 52.8 52.9 53.0 53.1 53.2 53.3 53.4 53.5 53.6 53.7 53.8 53.9 54.0 54.1 54.2 54.3 54.4 54.5 54.6
40
Outdoor Unit Capacity Unit: kW (x1,000kcal/h) RAS-40FSN Cooling Heating 117.78 (101.29) 127.00 (109.22) 117.79 (101.30) 127.00 (109.22) 117.80 (101.31) 127.00 (109.22) 117.81 (101.32) 127.00 (109.22) 117.83 (101.33) 127.00 (109.22) 117.84 (101.34) 127.00 (109.22) 117.85 (101.35) 127.00 (109.22) 117.86 (101.36) 127.00 (109.22) 117.87 (101.37) 127.00 (109.22) 117.88 (101.38) 127.00 (109.22) 117.90 (101.39) 127.00 (109.22) 117.91 (101.40) 127.00 (109.22) 117.92 (101.41) 127.00 (109.22) 117.93 (101.42) 127.00 (109.22) 117.94 (101.43) 127.00 (109.22) 117.95 (101.44) 127.00 (109.22) 117.97 (101.45) 127.00 (109.22) 117.98 (101.46) 127.00 (109.22) 117.99 (101.47) 127.00 (109.22) 118.00 (101.48) 127.00 (109.22)
--
--
RAS-42FSN Cooling Heating 122.42 (105.28) 132.00 (113.52) 122.45 (105.30) 132.00 (113.52) 122.47 (105.32) 132.00 (113.52) 122.50 (105.35) 132.00 (113.52) 122.52 (105.37) 132.00 (113.52) 122.54 (105.39) 132.00 (113.52) 122.57 (105.41) 132.00 (113.52) 122.59 (105.43) 132.00 (113.52) 122.62 (105.45) 132.00 (113.52) 122.64 (105.47) 132.00 (113.52) 122.67 (105.49) 132.00 (113.52) 122.69 (105.51) 132.00 (113.52) 122.71 (105.53) 132.00 (113.52) 122.74 (105.56) 132.00 (113.52) 122.76 (105.58) 132.00 (113.52) 122.79 (105.60) 132.00 (113.52) 122.81 (105.62) 132.00 (113.52) 122.84 (105.64) 132.00 (113.52) 122.86 (105.66) 132.00 (113.52) 122.89 (105.68) 132.00 (113.52) 122.91 (105.70) 132.00 (113.52) 122.92 (105.71) 132.00 (113.52) 122.93 (105.72) 132.00 (113.52) 122.94 (105.73) 132.00 (113.52) 122.96 (105.74) 132.00 (113.52) 122.97 (105.75) 132.00 (113.52) 122.98 (105.76) 132.00 (113.52) 122.99 (105.77) 132.00 (113.52) 123.00 (105.78) 132.00 (113.52) 123.01 (105.79) 132.00 (113.52) 123.03 (105.80) 132.00 (113.52) 123.04 (105.81) 132.00 (113.52) 123.05 (105.82) 132.00 (113.52) 123.06 (105.83) 132.00 (113.52) 123.07 (105.84) 132.00 (113.52) 123.08 (105.85) 132.00 (113.52) 123.10 (105.86) 132.00 (113.52) 123.11 (105.87) 132.00 (113.52) 123.12 (105.88) 132.00 (113.52) 123.13 (105.89) 132.00 (113.52) 123.14 (105.90) 132.00 (113.52) 123.15 (105.91) 132.00 (113.52) 123.17 (105.92) 132.00 (113.52) 123.18 (105.93) 132.00 (113.52) 123.19 (105.94) 132.00 (113.52) 123.20 (105.95) 132.00 (113.52)
SELECTION DATA 4.4
Capacity Characteristic Curve of Outdoor Units
The following charts show the characteristics of outdoor unit capacity which corresponds with total horsepower of combined indoor unit, on standard condition with refrigerant piping of horizontal and 7.5m at length. See page 27~40 for the examples of the actual combinations. Cooling Capacity Cooling Characteristic Curve of RAS-34FSN
Heating Capacity Heating Characteristic Curve of RAS-34FSN
Cooling Capacity Cooling Characteristic Curve of RAS-36FSN
Heating Capacity Heating Characteristic Curve of RAS-36FSN
41
SELECTION DATA
Cooling Capacity Cooling Characteristic Curve of RAS-38FSN
Heating Capacity Heating Characteristic Curve of RAS-38FSN
Cooling Capacity Cooling Characteristic Curve of RAS-40FSN
Heating Capacity Heating Characteristic Curve of RAS-40FSN
42
SELECTION DATA
Cooling Capacity Cooling Characteristic Curve of RAS-42FSN
Heating Capacity Heating Characteristic Curve of RAS-42FSN
43
SELECTION DATA 4.5
Cooling Capacity Table of 100% Combination (Dimension: kW) Table 1. Cooling Capacity Table for RAS-34FSN
Outdoor Air Inlet Dry Bulb (oC) 25.0 30.0 35.0 40.0
16.0 83.0 (0.86) 83.0 (0.86) 83.0 (0.86) 79.0 (0.82)
18.5 93.8 (0.98) 93.8 (0.98) 93.8 (0.98) 86.1 (0.90)
Unit of Capacity: kW (Correction Factor) Indoor Air Inlet Wet Bulb (oC) 19.0 20.0 22.0 24.0 96.0 100.3 105.1 109.9 (1.00) (1.04) (1.09) (1.14) 96.0 100.3 105.1 109.9 (1.00) (1.04) (1.09) (1.14) 96.0 100.3 104.7 106.2 (1.00) (1.04) (1.09) (1.11) 87.5 88.5 90.0 91.2 (0.91) (0.92) (0.94) (0.95)
Table 2. Cooling Capacity Table for RAS-36FSN Outdoor Air Inlet Dry Bulb (oC) 25.0 30.0 35.0 40.0
16.0 87.3 (0.86) 87.3 (0.86) 87.3 (0.86) 83.2 (0.82)
18.5 98.7 (0.98) 98.7 (0.98) 98.7 (0.98) 90.5 (0.90)
Unit of Capacity: kW (Correction Factor) Indoor Air Inlet Wet Bulb (oC) 19.0 20.0 22.0 24.0 101.0 105.0 110.2 115.6 (1.00) (1.04) (1.09) (1.14) 101.0 105.0 110.2 115.6 (1.00) (1.04) (1.09) (1.14) 101.0 105.0 110.2 111.8 (1.00) (1.04) (1.09) (1.11) 92.0 92.9 94.8 96.5 (0.91) (0.92) (0.94) (0.96)
Table 3. Cooling Capacity Table for RAS-38FSN Outdoor Air Inlet Dry Bulb (oC) 25.0 30.0 35.0 40.0
16.0 92.5 (0.86) 92.5 (0.86) 92.5 (0.86) 88.1 (0.82)
18.5 104.6 (0.98) 104.6 (0.98) 104.6 (0.98) 95.9 (0.90)
Unit of Capacity: kW (Correction Factor) Indoor Air Inlet Wet Bulb (oC) 19.0 20.0 22.0 24.0 107.0 111.8 117.1 122.5 (1.00) (1.04) (1.09) (1.14) 107.0 111.8 117.1 122.5 (1.00) (1.04) (1.09) (1.14) 107.0 111.8 116.7 118.4 (1.00) (1.04) (1.09) (1.11) 97.5 98.8 100.1 102.2 (0.91) (0.92) (0.94) (0.96)
Table 4. Cooling Capacity Table for RAS-40FSN Outdoor Air Inlet Dry Bulb (oC) 25.0 30.0 35.0 40.0
16.0 97.7 (0.86) 97.7 (0.86) 97.7 (0.86) 93.0 (0.82)
18.5 110.4 (0.98) 110.4 (0.98) 110.4 (0.98) 101.3 (0.90)
Unit of Capacity: kW (Correction Factor) Indoor Air Inlet Wet Bulb (oC) 19.0 20.0 22.0 24.0 113.0 118.0 123.7 129.3 (1.00) (1.04) (1.09) (1.14) 113.0 118.0 123.7 129.3 (1.00) (1.04) (1.09) (1.14) 113.0 118.0 123.3 125.1 (1.00) (1.04) (1.09) (1.11) 103.0 104.5 106.3 108.0 (0.91) (0.92) (0.94) (0.96)
Table 5. Cooling Capacity Table for RAS-42FSN Outdoor Air Inlet Dry Bulb (oC) 25.0 30.0 35.0 40.0 44
16.0 102.0 (0.86) 102.0 (0.86) 102.0 (0.86) 97.2 (0.82)
18.5 115.4 (0.98) 115.4 (0.98) 115.4 (0.98) 105.8 (0.90)
Unit of Capacity: kW (Correction Factor) Indoor Air Inlet Wet Bulb (oC) 19.0 20.0 22.0 24.0 118.0 123.2 128.8 135.0 (1.00) (1.04) (1.09) (1.14) 118.0 123.2 128.8 135.0 (1.00) (1.04) (1.09) (1.14) 118.0 123.2 128.8 130.6 (1.00) (1.04) (1.09) (1.11) 107.5 108.6 110.4 112.8 (0.91) (0.92) (0.94) (0.96)
SELECTION DATA 4.6
Heating Capacity Table of 100% Combination (Dimension: kW) Table 1. Heating Capacity Table for RAS-34FSN
Outdoor Air Inlet Wet Bulb (oC) -10.0 -5.0 0.0 5.0 6.0 10.0 15.0
16.0 84.5 (0.78) 96.1 (0.89) 104.9 (0.97) 113.3 (1.05) 114.9 (1.06) 120.9 (1.12) 122.3 (1.13)
Unit of Capacity: kW (Correction Factor) Indoor Air Inlet Dry Bulb (oC) 18.0 20.0 22.0 24.0 83.5 82.5 81.5 80.5 (0.77) (0.76) (0.75) (0.75) 94.5 93.0 91.1 89.2 (0.88) (0.86) (0.84) (0.83) 103.6 101.1 98.8 94.0 (0.96) (0.94) (0.91) (0.87) 111.1 107.4 102.7 95.1 (1.03) (0.99) (0.95) (0.88) 112.4 108.0 102.7 95.1 (1.04) (1.00) (0.95) (0.88) 116.3 110.3 102.7 95.1 (1.08) (1.02) (0.95) (0.88) 116.3 110.3 102.7 95.1 (1.08) (1.02) (0.95) (0.88)
Table 2. Heating Capacity Table for RAS-36FSN Outdoor Air Inlet Wet Bulb (oC) -10.0 -5.0 0.0 5.0 6.0 10.0 15.0
16.0 88.4 (0.78) 100.5 (0.89) 109.7 (0.97) 118.5 (1.05) 120.2 (1.06) 126.4 (1.12) 128.8 (1.14)
18.0 87.2 (0.77) 98.9 (0.88) 108.4 (0.96) 116.3 (1.03) 117.6 (1.04) 121.7 (1.08) 121.7 (1.08)
Unit of Capacity: kW (Correction Factor) Indoor Air Inlet Dry Bulb (oC) 20.0 22.0 24.0 86.1 85.0 83.6 (0.76) (0.75) (0.74) 97.3 94.9 93.3 (0.86) (0.84) (0.83) 105.8 102.8 98.3 (0.94) (0.91) (0.87) 112.3 107.5 99.4 (0.99) (0.95) (0.88) 113.0 107.5 99.4 (1.00) (0.95) (0.88) 114.6 107.5 99.4 (1.01) (0.95) (0.88) 114.6 107.5 99.4 (1.01) (0.95) (0.88)
Table 3. Heating Capacity Table for RAS-38FSN Outdoor Air Inlet Wet Bulb (oC) -10.0 -5.0 0.0 5.0 6.0 10.0 15.0
16.0 93.4 (0.78) 106.2 (0.89) 116.0 (0.97) 125.4 (1.05) 127.1 (1.06) 133.7 (1.12) 135.4 (1.13)
Unit of Capacity: kW (Correction Factor) Indoor Air Inlet Dry Bulb (oC) 18.0 20.0 22.0 24.0 92.2 90.9 89.3 88.5 (0.77) (0.76) (0.75) (0.74) 104.6 102.9 100.4 98.7 (0.88) (0.86) (0.84) (0.83) 114.6 111.9 109.3 104.0 (0.96) (0.94) (0.91) (0.87) 123.0 119.0 112.8 104.0 (1.03) (1.00) (0.94) (0.87) 124.4 119.5 113.6 105.1 (1.04) (1.00) (0.95) (0.88) 128.7 122.0 113.6 105.1 (1.08) (1.02) (0.95) (0.88) 128.7 122.0 113.6 105.1 (1.08) (1.02) (0.95) (0.88)
45
SELECTION DATA
Table 4. Heating Capacity Table for RAS-40FSN Outdoor Air Inlet Wet Bulb (oC) -10.0 -5.0 0.0 5.0 6.0 10.0 15.0
16.0 99.3 (0.78) 112.9 (0.89) 123.3 (0.97) 133.2 (1.05) 135.1 (1.06) 142.1 (1.12) 143.8 (1.13)
18.0 98.0 (0.77) 111.1 (0.87) 121.1 (0.95) 130.7 (1.03) 132.2 (1.04) 136.8 (1.08) 136.8 (1.08)
Unit of Capacity: kW (Correction Factor) Indoor Air Inlet Dry Bulb (oC) 20.0 22.0 24.0 96.7 95.4 94.1 (0.76) (0.75) (0.74) 109.3 107.1 104.9 (0.86) (0.84) (0.83) 118.9 115.9 110.5 (0.94) (0.91) (0.87) 126.2 120.7 111.9 (0.99) (0.95) (0.88) 127.0 120.7 111.9 (1.00) (0.95) (0.88) 129.4 120.7 111.9 (1.02) (0.95) (0.88) 129.4 120.7 111.9 (1.02) (0.95) (0.88)
Table 5. Heating Capacity Table for RAS-42FSN Outdoor Air Inlet Wet Bulb (oC) -10.0 -5.0 0.0 5.0 6.0 10.0 15.0
46
16.0 102.1 (0.77) 116.5 (0.88) 128.2 (0.97) 138.5 (1.05) 140.4 (1.06) 147.3 (1.12) 152.3 (1.15)
Unit of Capacity: kW (Correction Factor) Indoor Air Inlet Dry Bulb (oC) 18.0 20.0 22.0 24.0 101.4 100.4 99.3 98.1 (0.77) (0.76) (0.75) (0.74) 115.2 113.5 111.5 109.0 (0.87) (0.86) (0.84) (0.83) 126.6 124.5 120.8 114.8 (0.96) (0.94) (0.92) (0.87) 135.8 131.2 124.6 115.4 (1.03) (0.99) (0.94) (0.87) 137.4 132.0 125.5 115.4 (1.04) (1.00) (0.95) (0.87) 142.2 134.7 125.5 115.4 (1.08) (1.02) (0.95) (0.87) 143.7 134.7 125.5 115.4 (1.09) (1.02) (0.95) (0.87)
SELECTION DATA 4.7
Cooling Capacity Table of 100% Combination (Dimension: 1,000 kcal/h) Table 1. Cooling Capacity Table for RAS-34FSN
Outdoor Air Inlet Dry Bulb ( oC) 25.0 30.0 35.0 40.0
16.0 71.4 (0.86) 71.4 (0.86) 71.4 (0.86) 67.9 (0.82)
18.5 80.7 (0.98) 80.7 (0.98) 80.7 (0.98) 74.0 (0.90)
Unit of Capacity: x 1,000 kcal/h (Correction Factor) Indoor Air Inlet Wet Bulb ( oC) 19.0 20.0 22.0 24.0 82.6 86.3 90.4 94.5 (1.00) (1.04) (1.09) (1.14) 82.6 86.3 90.4 94.5 (1.00) (1.04) (1.09) (1.14) 82.6 86.3 90.0 91.3 (1.00) (1.04) (1.09) (1.11) 75.3 76.1 77.4 78.4 (0.91) (0.92) (0.94) (0.95)
Table 2. Cooling Capacity Table for RAS-36FSN Outdoor Air Inlet Dry Bulb ( oC) 25.0 30.0 35.0 40.0
16.0 75.1 (0.86) 75.1 (0.86) 75.1 (0.86) 71.6 (0.82)
18.5 84.9 (0.98) 84.9 (0.98) 84.9 (0.98) 77.8 (0.90)
Unit of Capacity: x 1,000 kcal/h (Correction Factor) Indoor Air Inlet Wet Bulb ( oC) 19.0 20.0 22.0 24.0 86.9 90.3 94.8 99.4 (1.00) (1.04) (1.09) (1.14) 86.9 90.3 94.8 99.4 (1.00) (1.04) (1.09) (1.14) 86.9 90.3 94.8 96.1 (1.00) (1.04) (1.09) (1.11) 79.1 79.9 81.5 83.0 (0.91) (0.92) (0.94) (0.96)
Table 3. Cooling Capacity Table for RAS-38FSN Outdoor Air Inlet Dry Bulb ( oC) 25.0 30.0 35.0 40.0
16.0 79.6 (0.86) 79.6 (0.86) 79.6 (0.86) 75.8 (0.82)
18.5 90.0 (0.98) 90.0 (0.98) 90.0 (0.98) 82.5 (0.90)
Unit of Capacity: x 1,000 kcal/h (Correction Factor) Indoor Air Inlet Wet Bulb ( oC) 19.0 20.0 22.0 24.0 92.0 96.1 100.7 105.4 (1.00) (1.04) (1.09) (1.14) 92.0 96.1 100.7 105.4 (1.00) (1.04) (1.09) (1.14) 92.0 96.1 100.4 101.8 (1.00) (1.04) (1.09) (1.11) 83.9 85.0 86.1 87.9 (0.91) (0.92) (0.94) (0.96)
Table 4. Cooling Capacity Table for RAS-40FSN Outdoor Air Inlet Dry Bulb ( oC) 25.0 30.0 35.0 40.0
16.0 84.0 (0.86) 84.0 (0.86) 84.0 (0.86) 80.0 (0.82)
18.5 94.9 (0.98) 94.9 (0.98) 94.9 (0.98) 87.1 (0.90)
Unit of Capacity: x 1,000 kcal/h (Correction Factor) Indoor Air Inlet Wet Bulb ( oC) 19.0 20.0 22.0 24.0 97.2 101.5 106.4 111.2 (1.00) (1.04) (1.09) (1.14) 97.2 101.5 106.4 111.2 (1.00) (1.04) (1.09) (1.14) 97.2 101.5 106.0 107.6 (1.00) (1.04) (1.09) (1.11) 88.6 89.9 91.4 92.9 (0.91) (0.92) (0.94) (0.96)
Table 5. Cooling Capacity Table for RAS-42FSN Outdoor Air Inlet Dry Bulb ( oC) 25.0 30.0 35.0 40.0
16.0 87.7 (0.86) 87.7 (0.86) 87.7 (0.86) 83.6 (0.82)
18.5 99.2 (0.98) 99.2 (0.98) 99.2 (0.98) 91.0 (0.90)
Unit of Capacity: x 1,000 kcal/h (Correction Factor) Indoor Air Inlet Wet Bulb ( oC) 19.0 20.0 22.0 24.0 101.5 106.0 110.8 116.1 (1.00) (1.04) (1.09) (1.14) 101.5 106.0 110.8 116.1 (1.00) (1.04) (1.09) (1.14) 101.5 106.0 110.8 112.3 (1.00) (1.04) (1.09) (1.11) 92.5 93.4 94.9 97.0 (0.91) (0.92) (0.94) (0.96) 47
SELECTION DATA 4.8
Heating Capacity Table of 100% Combination (Dimension: 1,000 kcal/h) Table 1. Heating Capacity Table for RAS-34FSN
Outdoor Air Inlet Wet Bulb (oC) -10.0 -5.0 0.0 5.0 6.0 10.0 15.0
16.0 72.7 (0.78) 82.6 (0.89) 90.2 (0.97) 97.4 (1.05) 98.8 (1.06) 104.0 (1.12) 105.2 (1.13)
Unit of Capacity: x Indoor Air Inlet Dry Bulb (oC) 18.0 20.0 71.8 71.0 (0.77) (0.76) 81.3 80.0 (0.88) (0.86) 89.1 86.9 (0.96) (0.94) 95.5 92.4 (1.03) (0.99) 96.7 92.9 (1.04) (1.00) 100.0 94.9 (1.08) (1.02) 100.0 94.9 (1.08) (1.02)
1,000 kcal/h (Correction Factor) 22.0 70.1 (0.75) 78.3 (0.84) 85.0 (0.91) 88.3 (0.95) 88.3 (0.95) 88.3 (0.95) 88.3 (0.95)
24.0 69.2 (0.75) 76.7 (0.83) 80.8 (0.87) 81.8 (0.88) 81.8 (0.88) 81.8 (0.88) 81.8 (0.88)
Table 2. Heating Capacity Table for RAS-36FSN Outdoor Air Inlet Wet Bulb (oC) -10.0 -5.0 0.0 5.0 6.0 10.0 15.0
16.0 76.0 (0.78) 86.4 (0.89) 94.3 (0.97) 101.9 (1.05) 103.4 (1.06) 108.7 (1.12) 110.8 (1.14)
18.0 75.0 (0.77) 85.1 (0.88) 93.2 (0.96) 100.0 (1.03) 101.1 (1.04) 104.7 (1.08) 104.7 (1.08)
Unit of Capacity: x Indoor Air Inlet Dry Bulb (oC) 20.0 74.0 (0.76) 83.7 (0.86) 91.0 (0.94) 96.6 (0.99) 97.2 (1.00) 98.6 (1.01) 98.6 (1.01)
1,000 kcal/h (Correction Factor) 22.0 73.1 (0.75) 81.6 (0.84) 88.4 (0.91) 92.5 (0.95) 92.5 (0.95) 92.5 (0.95) 92.5 (0.95)
24.0 71.9 (0.74) 80.2 (0.83) 84.5 (0.87) 85.5 (0.88) 85.5 (0.88) 85.5 (0.88) 85.5 (0.88)
Table 3. Heating Capacity Table for RAS-38FSN Outdoor Air Inlet Wet Bulb (oC) -10.0 -5.0 0.0 5.0 6.0 10.0 15.0
48
16.0 80.3 (0.78) 91.3 (0.89) 99.8 (0.97) 107.8 (1.05) 109.3 (1.06) 115.0 (1.12) 116.4 (1.13)
18.0 79.3 (0.77) 90.0 (0.88) 98.6 (0.96) 105.8 (1.03) 107.0 (1.04) 110.7 (1.08) 110.7 (1.08)
Unit of Capacity: x Indoor Air Inlet Dry Bulb (oC) 20.0 78.2 (0.76) 88.5 (0.86) 96.2 (0.94) 102.3 (1.00) 102.8 (1.00) 104.9 (1.02) 104.9 (1.02)
1,000 kcal/h (Correction Factor) 22.0 76.8 (0.75) 86.3 (0.84) 94.0 (0.91) 97.0 (0.94) 97.7 (0.95) 97.7 (0.95) 97.7 (0.95)
24.0 76.1 (0.74) 84.9 (0.83) 89.4 (0.87) 89.4 (0.87) 90.4 (0.88) 90.4 (0.88) 90.4 (0.88)
SELECTION DATA
Table 4. Heating Capacity Table for RAS-40FSN Outdoor Air Inlet Wet Bulb (oC) -10.0 -5.0 0.0 5.0 6.0 10.0 15.0
16.0 85.4 (0.78) 97.1 (0.89) 106.0 (0.97) 114.6 (1.05) 116.2 (1.06) 122.2 (1.12) 123.7 (1.13)
Unit of Capacity: x Indoor Air Inlet Dry Bulb (oC) 18.0 20.0 84.3 83.2 (0.77) (0.76) 95.5 94.0 (0.87) (0.86) 104.1 102.3 (0.95) (0.94) 112.4 108.5 (1.03) (0.99) 113.7 109.2 (1.04) (1.00) 117.6 111.3 (1.08) (1.02) 117.6 111.3 (1.08) (1.02)
1,000 kcal/h (Correction Factor) 22.0 82.0 (0.75) 92.1 (0.84) 99.7 (0.91) 103.8 (0.95) 103.8 (0.95) 103.8 (0.95) 103.8 (0.95)
24.0 80.9 (0.74) 90.2 (0.83) 95.0 (0.87) 96.2 (0.88) 96.2 (0.88) 96.2 (0.88) 96.2 (0.88)
Table 5. Heating Capacity Table for RAS-42FSN Outdoor Air Inlet Wet Bulb (oC) -10.0 -5.0 0.0 5.0 6.0 10.0 15.0
16.0 87.8 (0.77) 100.2 (0.88) 110.3 (0.97) 119.1 (1.05) 120.7 (1.06) 126.7 (1.12) 131.0 (1.15)
18.0 87.2 (0.77) 99.1 (0.87) 108.9 (0.96) 116.8 (1.03) 118.2 (1.04) 122.3 (1.08) 123.6 (1.09)
Unit of Capacity: x Indoor Air Inlet Dry Bulb (oC) 20.0 86.3 (0.76) 97.6 (0.86) 107.1 (0.94) 112.8 (0.99) 113.5 (1.00) 115.8 (1.02) 115.8 (1.02)
1,000 kcal/h (Correction Factor) 22.0 85.4 (0.75) 95.9 (0.84) 103.9 (0.92) 107.2 (0.94) 107.9 (0.95) 107.9 (0.95) 107.9 (0.95)
24.0 84.4 (0.74) 93.7 (0.83) 98.7 (0.87) 99.2 (0.87) 99.2 (0.87) 99.2 (0.87) 99.2 (0.87)
49
SELECTION DATA 4.9
Correction Factor According to Piping Length
Correction Factor for Cooling Capacity According to Piping Length The cooling capacity should be corrected according to the following formula: CCA=CC F CCA: Actual Corrected Cooling Capacity CC: Cooling Capacity in the Performance Table F: Correction Factor Based on the Equivalent Piping Length
The correction factors are shown in the following figure. Equivalent Piping Length for • One 90o Elbow is 0.5m. • One 180o Bend is 1.5m. • One Multi-Kit is 0.5m.
• In case of gas piping size; φ31.75 for 34HP, φ38.1 for 36HP to 42HP (COOLING)
Normal
H (m)
50
Size Up
45 40 35 30 25 20
-15 -20 -25 -30 -35 -40
50
20
30
50
60
70
80
80%
85%
90%
40
90
100
110
EL(m) 120
130
140 85%
-5 -10
10
90%
0
95%
5
95%
10
100%
15
150
160
170
180
SELECTION DATA
Correction Factor for Heating Capacity According to Piping Length The heating capacity should be corrected according to the following formula: HCA=HC F HCA: Actual Corrected Heating Capacity HC: Heating Capacity in the Performance Table F: Correction Factor Based on the Equivalent Piping Length
The correction factors are shown in the following figure. Equivalent Piping Length for • One 90o Elbow is 0.5m. • One 180o Bend is 1.5m. • One Multi-Kit is 0.5m.
• In case of gas piping size; φ31.75 for 34HP, φ38.1 for 36HP to 42HP (HEATING) H (m)
50 45 40 35 30 25
130
86%
89%
120
87%
90%
110
88%
91%
92%
93%
94%
40
95%
30
96%
97%
5
98%
10
99%
15
100%
20
EL (m)
0 10
-5
20
50
60
70
80
90
100
140
150
160
170 180
-10 -15 -20 -25 -30 -35 -40
H: Outdoor Unit
L L
+H
Indoor Unit
Indoor Unit
Outdoor Unit -H
Vertical Distance Between Indoor Unit and Outdoor Unit in Meters EL: Equivalent Total Distance Between Indoor Unit and Outdoor Unit in Meters (Equivalent One-Way Piping Length) H>0: Position of Outdoor Unit Higher Than Position of Indoor Unit L: Actual One-Way Piping Length Between Indoor Unit and Outdoor Unit in Meters
51
SELECTION DATA 4.10 Sensible Heat Factor (SHF) Please refer to Technical Catalog I, SP1-S02 or SP1-S03, 2006.
4.11 Correction Factor According to Defrosting Operation The heating capacity in the preceding paragraph, excludes the condition of the frost or the defrosting operation period. In consideration of the frost or the defrosting operation, the heating capacity is corrected by the equation below. Corrected Heating Capacity = Correction Factor Heating Capacity Outdoor Inlet Air Temp. (oC DB) (Humidity=85% RH) Correction Factor
-7
-5
-3
0
3
5
7
0.95
0.93
0.88
0.85
0.87
0.90
1.0
NOTE: The correction factor is not available for the special condition like a snowfall or a operation in a transitional period.
4.12 Fan Performance Please refer to Technical Catalog I, SP1-S02 or SP1-S03, 2006.
4.13 Model Selection of Total Heat Exchangers Please refer to Technical Catalog I, SP1-S02 or SP1-S03, 2006.
52
ELECTRICAL DATA
5. ELECTRICAL DATA ■ Indoor Unit Please refer to Technical Catalog I, SP1-S02 or SP1-S03, 2006. ■ Outdoor Unit Model
Unit Main Power VOL
PH
HZ
Applicable Voltage Maximum
STC
Minimum
RAS-34FSN
158
RAS-36FSN
158
RAS-38FSN
380/415
3
50
457
342
158
Cooling Operation
Heating Operation
Maximum Current
RNC
IPT
RNC
IPT
56.0/ 51.3 59.7/ 54.7 63.4/ 58.0 67.2/ 61.6 69.7/ 63.8
32.1
47.7/ 43.6 49.6/ 45.4 58.0/ 48.1 61.6/ 52.4 63.8/ 54.9
27.3
67
28.4
72
30.1
76
32.8
81
34.3
84
34.2 36.3 38.5
RAS-40FSN
172
RAS-42FSN
172
RAS-34FSN
158
53.2
31.5
45.2
26.8
64
RAS-36FSN
158
56.6
33.5
46.9
27.8
68
158
60.1
35.6
49.8
29.5
72
RAS-40FSN
172
63.6
37.7
54.4
32.2
76
RAS-42FSN
172
66.0
39.1
56.7
33.6
79
RAS-34FSN
274
96.1
31.5
81.8
26.8
115
RAS-36FSN
274
102.2
33.5
84.8
27.8
123
274
108.6
35.6
90.0
29.5
130
RAS-40FSN
297
115.0
37.7
98.3
32.2
138
RAS-42FSN
297
119.3
39.1
102.5
33.6
143
RAS-38FSN
RAS-38FSN
VOL: HZ: STC:
380
220
3
3
60
60
418
242
Rated Unit Power Supply Voltage (Plated)(V) Frequency (Hz) Starting Current (A)
342
198
RNC: PH: IPT:
39.9
Running Current (A) Phase (φ) Input (kW)
NOTES: 1. The above compressor data is based on 100% capacity combination of the indoor units at rated operating frequency. RAS-34FSN .............. 42Hz RAS-36FSN .............. 62Hz RAS-38FSN .............. 81Hz RAS-40FSN .............. 29Hz RAS-42FSN .............. 48Hz 2. The above performance data is based on 7.5m equivalent piping length and 0m piping lift. 3. These data are based on the same conditions as the nominal heating and cooling capacities. 4. The compressor is started by an inverter, resulting in extremely low starting current.
53
SOUND DATA
6. SOUND DATA ■ Indoor Units Please refer to Technical Catalog I, SP1-S02 or SP1-S03, 2006. ■ Outdoor Units
54
SOUND DATA
55
SOUND DATA
56
WORKING RANGE
7. WORKING RANGE Power Supply Working Voltage: 90% to 110% of the Rated Voltage Voltage Imbalance: Within a 3% Deviation from Each Voltage at the Main Terminal of Outdoor Unit Starting Voltage: Higher than 85% of the Rated Voltage Temperature Range The temperature range are given in the following table.
Indoor Temperature:
Minimum Maximum Outdoor Temperature: Minimum Maximum
Cooling Operation 21oC DB/15.0oC WB 32oC DB/23.0oC WB -5oC DB 43oC DB
Heating Operation 15oC DB 27oC DB -20oC WB 15oC WB
Piping Provision I Maximum Piping Length LO-I: • 150m in Actual Length • 175m in Equivalent Length (On Way for Each Indoor Unit) I Maximum Piping Lift Between Outdoor Unit and Indoor Unit HO-I: • 50m When Outdoor Unit is Higher than Indoor Unit • 40m When Indoor Unit is Higher than Outdoor Unit I Maximum Piping Lift Between each Indoor Unit HI-I: • 15m
Outdoor Unit Lo-I
Ho-I
Indoor Unit
HI-I
Indoor Unit
57
OPTIONAL ACCESSORIES
8. OPTIONAL ACCESSORIES Please refer to Technical Catalog I, SP1-S02 or SP1-S03, 2006.
58
COMPONENT DATA
9. COMPONENT DATA â&#x2013; Indoor Heat Exchanger and Fan Please refer to Technical Catalog I, SP1-S02 or SP1-S03, 2006.
I Outdoor Heat Exchanger and Fan RAS-34FSN
Model
RAS-36FSN
Heat Exchanger Type
RAS-38FSN
Multi-Pass Cross Finned Tube
Tube Material
Copper Tube
Outer Diameter
mm
Rows Number of Tube/Coil
9.53
9.53
2
2
2
112
112
112
Fin Material
9.53
Aluminum
Pitch Maximum Operating Pressure
mm
2
2
2
MPa
4.15
4.15
4.15
m2
Total Face Area Number of Coil/Unit
2.49
2.12
2.49
2.12
2.49
2.12
2
1
2
1
2
1
Outdoor Fan
Propeller Fan
Number/Unit
3
3
3
Outer Diameter
mm
644
644
644
Revolution
rpm
990+900+900
990+900+900
990+900+900
Nominal Air Flow
3
210+172+172
210+172+172
210+172+172
m /min.
Outdoor Fan Motor
Drip-Proof Type Enclosure
Starting Method Nominal Output
DC Motor + PSC (Permanent Split Capacitor) 380+275x2
380+275x2
Quantity
W
3
3
3
Insulation Class
E
E
E
RAS-40FSN
RAS-42FSN
Model Heat Exchanger Type
Multi-Pass Cross Finned Tube
Tube Material Outer Diameter
Copper Tube mm
9.53
Rows Number of Tube/Coil
9.53
2
2
112
112
Fin Material Pitch Maximum Operating Pressure Total Face Area
Aluminum mm
2
2
MPa
4.15
4.15
m2
Number of Coil/Unit
2.49
2.12
2.49
2.12
2
1
2
1
Outdoor Fan
Propeller Fan
Number/Unit Outer Diameter Revolution Nominal Air Flow
mm
3
3
644
644
rpm
990+900+900
990+900+900
m3/min.
210+172+172
210+172+172
Outdoor Fan Motor
Drip-Proof Type Enclosure
Starting Method Nominal Output
380+275x2
DC Motor + PSC (Permanent Split Capacitor) W
380+275x2
380+275x2
Quantity
3
3
Insulation Class
E
E
59
COMPONENT DATA
I Component Detailed Data Compressor Compressor Model
E655DHD
Type
E855DH Hermetic Scroll Type
Air Tight Pressure Discharge
MPa
4.15
4.15
Suction
MPa
2.21
2.21
Motor Type
Special Squirrel-Cage Three-Phase Motor
Starting Method
Inverter-Driven
Direct-on-Line
Poles
4
2
Insulation
E
Oil Type Charge
60
E FVC68D
Liters
0.5
1.1
CONTROL SYSTEM
10. CONTROL SYSTEM 10.1 Refrigeration Cycle ■ Indoor Units Please refer to Technical Catalog I, SP1-S02 or SP1-S03, 2006. ■ Outdoor Units RAS-34FSN, RAS-36FSN and RAS-38FSN
61
CONTROL SYSTEM
RAS-40FSN and RAS-42FSN
62
CONTROL SYSTEM 10.2 Control System Table 1 shows the control system of refrigerant cycle. Table 1. Refrigerant Cycle Control Cooling Operation
Control Subject Inverter Frequency of Compressor
Purpose
(Setting DSW6)
Opening Degree of Expansion Valve of Outdoor Unit
Opening Degree of Expansion Valve for Plate Heat Exchanger (more than 10HP)
(1) For Controlling Temp. of Discharge Gas Super-Heat: TdSH (2) For Comp. Protection
Opening Degree of Expansion Valve of Indoor Unit
(1) For Controlling Temp. of Discharge Gas Super-Heat: TdSH (2) For Controlling Temp. Difference between Gas Pipe and Liquid Pipe of I.U. Heat Exchanger (3) For Balancing Temp. Differences between Gas Pipe and Liquid Pipe of each I.U. For Controlling Discharge Pre. : Pd For Controlling Inner Pre. of Stoppage Comp. For Controlling Oil Circulation Volume from Oil Separator to Each Comp.
Equalized Pressure Valve (SVA) Solenoid Valve for Oil Return (SVF)
Solenoid Valve for Shut-Off from High and Low Pressure Side at Ref. Collection (SVG)
Fully Open Response to Various Heat Exchanger Running Mode (Fully Close when Unused Heat Exchanger) (1) Tc+30<95 (2) Tdmax>100 oC and EVI>1500pls and over 5 minutes
(1) Capacity Control (2) Changeover of Total I.U. Cap. For Controlling Temp. of Discharge Gas Super-Heat: TdSH
Tdo=Tc+35<90
o
Tdmax>100 C and EVo>430pls and over 5 minutes
(1) Tc+30<95 (2) Temp. Difference between Gas Pipe and Liquid Pipe of Indoor Heat Exchanger <4 deg
(1) For Controlling Temp. Difference between Air Outlet and Air Inlet of I.U. (2) For Balancing Temp. Differences between Gas Pipe and Liquid Pipe of each I.U.
Air Outlet Temperature - Air Inlet Temp.<24deg
2.5<Pd<2.9 (MPa)
For Controlling Pre. Based on Outdoor Air Temp. For Controlling Inner Pre. of Stoppage Comp. For Controlling Oil Circulation Volume from Oil Separator to Each Comp.
Fan Step Control by Outdoor Temp. In case of Running Inverter Comp. after Operation Turn ON in Comp. Operation Turn OFF in Comp. Stoppage
For Ref. Collection
(1) Turn ON in Comp. Operation (2) Pd>3.7(MPa)
In case of Running Inverter Comp. after Operation Turn ON in Comp. Operation Turn OFF in Comp. Stoppage
(1) Turn ON in Comp. Operation (2) Pd>3.7(MPa) Pd<2.3 (MPa)
-
Solenoid Valve for Liquid (SVC)
Cap. : Capacity Pre. : Pressure
(1) 8Hz/Indoor Unit HP (2) 10Hz/Indoor Unit HP (Setting DSW6) (3) Pd>2.1MPa
For Comp. Protection
For Ref. Collection
Solenoid Valve for Bypass (SVB)
I.U. : Indoor Unit O.U. : Outdoor Unit
Contents
(1) Total Operating I.U. Cap. (2) Collection According to Piping Length (3) Discharge Pre. (Pd)
(3) Pd>1.0MPa
(1) Cap. Control (2) Changeover of Total I.U. Cap. (1) Cap. Control (2) Changeover of Total I.U. Cap.
Outdoor Fan
Purpose
(1) 8Hz/Indoor Unit HP (2) 10Hz/Indoor Unit HP
(1) Total Operating I.U. Cap. (2) Collection According to Piping Length (3) Discharge Pre. (Pd)
Change of Operating Compressor Number
Heating Operation Contents
-
-
-
-
Temp.: Temperature Comp.: Compressor
Figure below shows the outline of the control system.
Remote Control MCU
Thermistor for Inlet Air Thermistor of Discharge Air
Suction Gas Pressure Sensor Discharge Gas Pressure Sensor
Thermistor for Gas Pipe
Transmission Circuit
Wireless Remote Control Switch
Thermistor for Ambient Temperature
Thermistor for Liquid Pipe
Discharge Gas Thermistor Thermistor for Heating Evaporation Temperature
Multiple Signals
PSC Protection Circuit
Wireless Transmission Circuit
Symbol
A D Conversion Circuit
A D Conversion Circuit
Transmission Circuit
Indoor Unit MCU
Transmission Circuit
Transmission Circuit
Remote Control Switch
Remote Control MCU
Single Signal Operation Signal
Power Source
Inverter Power Section
Inverter Control MCU
Outdoor Unit MCU
Motor (for Compressor)
MIF
Motor (for Indoor Blower)
MOF1, 2
Motor (for Outdoor Blower)
MS
Motor (for Auto-Louver)
MV1,
Electronic Expansion Valve
2
Electric Heater
EHW Electrical Control Expansion Valve Drive Circuit
MV
Relay Drive Circuit
EHW
MS
Indoor Unit
Thyristor Control Circuit
MIF
Protection Circuit
Electrical Control Expansion Valve Drive Circuit
MV 1, 2
CH1
CMC 2~6
Relay Drive Circuit
MOF1
To Transmission Circuit of the next Indoor Unit or the next Outdoor Unit (H-Link)
RVR 1, 2
Inverter Control for Fan MCU
SVA, F, G
CT1
MC
RVR1,
2
4-Way Valve
SVA
Solenoid Valve (for Hot Gas Bypass)
PSC
Pressure Switch
CT1~6
Diverter
CH
Crankcase Heater
MOF2
Outdoor Unit
Magnetic Contactor
CMC CT 2~6
Name
MC
63
CONTROL SYSTEM 10.3 System Control 10.3.1 Control in a Room
Individual Operation System Each indoor unit is individually controlled by its own remote control switch.
Control Method
(1) (2) (3) (4) (5) (6) (7) (8) (9) (10) Yes: * :
by each Optional Remote Control Switch Individual Yes Yes* Yes Yes Yes Yes Yes Yes Yes Yes
Operation Method ON/OFF Setting of Operation Mode Room Temperature Setting Fan Speed Setting Timer Setting ON/OFF by Timer Control Operation Indication Alarm Indication Self-Checking Test Mode Available Cooling and heating can not be operated simultaneously.
Remote Control Switch
Group Control Operation System One remote control switch can control simultaneously up to 16 indoor units. This system can be applied to a wide space air conditioning such as in a lobby of hotel / hospital,
Control Method
(1) (2) (3) (4) (5) (6) (7) (8) (9) (10) Yes: * :
64
by One Optional Remote Control Switch by One Group Yes Yes* Yes Yes Yes Yes Yes Yes Yes Yes
Operation Method ON/OFF Setting of Operation Mode Room Temperature Setting Fan Speed Setting Timer Setting ON/OFF by Timer Control Operation Indication Alarm Indication Self-Checking Test Mode Available Only if all units in one group are connected to the same outdoor unit.
an office building, etc. By one remote control switch, starting and stopping are easily and quickly performed for all the units.
One Remote Control Switch in the Room
CONTROL SYSTEM 10.3.2 Group Control from a Remote Place One remote control switch can control from a remote location simultaneously up to 16 indoor units. This system is the most appropriate for an open plan air conditioning such as in a lobby of
Control Method
(1) (2) (3) (4) (5) (6) (7) (8) (9) (10) Yes: * :
by One Optional Remote Control Switch by One Group Yes Yes* Yes Yes Yes Yes Yes Yes Yes Yes
Operation Method ON/OFF Setting of Operation Mode Room Temperature Setting Fan Speed Setting Timer Setting ON/OFF by Timer Control Operation Indication Alarm Indication Self-Checking Test Mode Available Only if all units in one group are connected to the same outdoor unit.
hotel / hospital, an office building, etc. By one remote control switch, starting and stopping are easily and quickly performed for all the units.
One Remote Control Switch Located Outside of Rooms
10.3.3 Control in a Room/Control from a Remote Place By Utilizing Sub-Remote Control Switch and Main Remote Control Switch for Maximum 16 Indoor Unit Control Simultaneous Operation System
Two remote control switches are used to control indoor units up to 16 sets. One remote control switch is installed in the room and another one is installed in a remote central control room.
Control Method
(1) (2) (3) (4) (5) (6) (7) (8) (9) (10) Yes: * :
This system is the most appropriate for an open plan space such a lobby in the hotel, restaurant, etc.
by Optional by Optional Remote Control Remote Control Switch in the Switch from Room Remote Place by One Group by One Group Yes Yes Yes* Yes* Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes
Operation Method ON/OFF Setting of Operation Mode Room Temperature Setting Fan Speed Setting Timer Setting ON/OFF by Timer Control Operation Indication Alarm Indication Self-Checking Test Mode Available Only if all units in one group are connected to the same outdoor unit.
Main Remote Control Switch
Sub-Remote Control Switch
NOTE: The last setting remote control switch in the two remote control switches has priority in this system.
65
CONTROL SYSTEM 10.4 Standard Operation Sequence I Restricted Control
1. Purpose Reduce for number of operation stop by alarm.
2. Measure
3. Applicable Case
Protection Control change after retry. (Protection Control is activated quickly than before.)
Restricted Control
(1) Discharge Gas Super Heat Decrease (2) Discharge Gas Temperature Increase (3) Pressure Ratio Decrease (4) High Pressure Increase (5) Over Current of Inverter
4. Example 4-1 Protection Control for Discharge Gas Temperature Increase
4-2 Protection Control for High Pressure
Normal Operation
Normal Operation Enforced Decrease of Frequency
Prohibited increase of Frequency
Enforced Decrease of Frequency
Abnormality is detected.
Normal Control
More than 5 Sec.
Prohibited increase of Frequency Abnormality is detected.
Normal Control
Constant Speed Compressor: OFF
More than 10 Min. 110
118 120
132
140
3.30
Temperature at the top of Inverter Compressor Td1
Restricted Control (After Retry)
3.50 3.55
Enforced Decrease of Frequency
Abnormality is detected.
Normal Control
More than 5 Sec. More than 10 Min.
100 108 110 132 140 Temperature at the top of Inverter Compressor Td1
66
3.80
Restricted Control (After Retry)
Enforced Decrease of Frequency Prohibited increase of Frequency
3.60
Discharge Gas Pressure Pd (MPa)
Prohibited increase of Frequency Normal Control
Abnormality is detected. Constant Speed Compressor: OFF
3.20 3.40 3.45 3.50 3.80 Discharge Gas Pressure Pd (MPa)
CONTROL SYSTEM I Cooling Operation
I.U.: Indoor Unit O.U.: Outdoor Unit T.C.: Temperature of Condensing Power to CH1 ~ CH6
Power to O.U.: ON
Reverse Phase (Alarm Code 05)
Is phase correct?
Power to PCB in O.U.: ON
Auto - louver 0 Reset Power to I.U.: ON
Power to I.U.: OFF
Correct Phase
only for indoor unit with auto - louver
Start of Transmitting between I.U. and O.U. Start of Transmitting between I.U. and Remote Control Switch
Power to PCB in I.U.: ON OFF (Higher than Activation Level)
FS
Power to AR in I.U.: OFF
MD : ON
ON (Lower than Activation Level)
Power to AR in I .U.: ON Setting at COOL
COOL Indication for Unit with Drain Pump HIGH Indication
High Pressing FAN Switch
Air Flow Change Over Switch
Medium
MEDIUM Indication
Low
LOW Indication
Switch: Increasing Set Temp. Switch: Decreasing Set Temp.
Pressing Temp. Switch
Set Temp. Indicated
Run LED: ON, RUN is Indicated Power to YH2 for 20 sec. Pressing RUN/STOP Switch
Power to YH2 : ON
Power to EHW: ON Power to MC2 ~ MC6 : ON Power to CH2 ~ CH6 : OFF
Power to CMC2 ~ CMC6 : ON Power to Y211 : ON
Power to RVR1 : ON Power to CH1 : OFF
Higher than Set Temp. Cooling Operation
I.U. Air Intake Temp.
PID Control for I.U. and O.U. Electronic Ex. Valve
Yes Is heat load big?
No Power to CMC1 : ON
O. D. Temp.
> -5oC
< -5oC
Lower than Set Temp.
*PID Control for Comp. Q'ty Power to MC1 ~ MC6 : OFF Power to CH1 ~ CH6 : ON
Outdoor Fan (MOF) Air Flow 100 % for 10 sec. Air Flow Change according to Outdoor Air Temp.
Power to MC1 with * Inverter Frequency PID Control: ON
Discharge Pressure
≥ 2.7MPa (27kg/cm2G)
Fan Speed: One Step-up
< 2.7MPa (27kg/cm2G) Discharge Pressure
< 2.3MPa (23kg/cm2G)
Fan Speed: One Step-down
≥ 2.3MPa (23kg/cm2G)
to 1
Operation at Set Indoor Fan Speed
67
CONTROL SYSTEM I Cooling Operation
I.U.: Indoor Unit O.U.: Outdoor Unit
1
Start of Auto-Louver Pressing AUTO-LOUVER Switch
only for Air Panel or Indoor Unit with Auto-Louver
Alternatively Stop of Auto-Louver
Pressing RUN/STOP Switch
Power to Y52C : OFF
Power to CMC1 ~ CMC6 : OFF
Stop of MC1 ~ MC6 Stop of MOF1 & MOF2
No After 3 min. 20 sec.
Power to CH1 ~ CH6 : ON for unit with drain pump
Yes Power to YH2 : OFF
MD Stop Power to EHW : OFF Power to MIF : OFF RUN/STOP Lamp: OFF, COOL, Set Fan Speed & Set Temp. Indication: Continuously ON
STOP
Electronic Ex. Valve in I.U. and O.U. : Fixed Opening Power to Solenoid Valve SVA : ON
Power to Y211 : OFF
68
Power to I.U.: OFF
Power to PCB in I.U.: OFF
Power to O.U.: OFF
Power to PCB in O.U.: OFF
Power to RVR1 : OFF
LCD Indication: OFF
Power to CH1 ~ CH6 : OFF
CONTROL SYSTEM I Dry Operation
I.U.: Indoor Unit O.U.: Outdoor Unit T.C.: Temperature of Condensing Power to CH
Power to O.U.: ON Power to PCB in O.U.: ON
Reverse Phase (Alarm Code 05)
Is phase correct?
Auto - louver 0 Reset Power to I.U.: ON
Power to I.U.: OFF
Correct phase
only for indoor unit with auto - louver
Start of Transmitting between I.U. and O.U. Start of Transmitting between I.U. and Remote Control Switch
Power to PCB in I.U.: ON OFF (Higher than Activation Level)
FS
ON (Lower than Activation Level)
Power to AR in I .U.: ON
Power to AR in I.U.: OFF
MD : ON for unit with drain pump
Setting at DRY
DRY Indication
Switch: Increasing Set Temp. Switch: Decreasing Set Temp.
Pressing TEMP. Switch
Pressing RUN/STOP Switch
Set Temp. indicated
Run LED: ON, RUN is indicated Power to YH2 for 20 sec. Power to YH2 : ON
Power to EHW: ON Power to MC1 ~ MC6 : ON Power to CH2 ~ CH6 : OFF
Power to CMC2 ~ CMC6 : ON Power to Y211 : ON
Power to RVR : ON PID Control for I.U. Electronic Ex. Valve
Higher than Set Temp.
Dry Operation
I.U. Air Intake Temp.
Power to CH1 : OFF
Yes MIF: Lo
Is heat load big?
No
Power to CMC1 : ON
Lower than Set Temp.
O. D. Temp.
≥ -5oC
MC1 with Inverter Frequency PID Control
< -5oC Power to MC2 ~ MC6 : OFF Power to CH2 ~ CH6 : ON
Outdoor Fan (MOF) Air Flow: 100 % for 10 sec.
No 6 min. MIF: OFF
Air Flow Change according to Outdoor Air Temp.
Discharge Pressure
≥ 2.7MPa
(27kg/cm2G)
Fan Speed: One Step-up
< 2.7MPa (27kg/cm2G) < 2.3MPa (23kg/cm2G) Discharge Pressure ≥ 2.3MPa (23kg/cm2G)
Yes
No 6 min. Fan Speed: One Step-down
Yes MIF: Lo
To 2
69
CONTROL SYSTEM I Dry Operation
I.U.: Indoor Unit O.U.: Outdoor Unit
2
Start of Auto-Louver Pressing AUTO-LOUVER Switch
only for Air Panel or Indoor Unit with Auto-Louver
Alternatively Stop of Auto-Louver
Pressing RUN/STOP Switch
Power to Y52C : OFF
Power to CMC1 ~ CMC6 : OFF
Stop of MC1 ~ MC6 Stop of MOF1 & MOF2
No After 3 min. 20 sec.
Power to CH1 ~ CH6 : ON for unit with drain pump
Yes Power to YH2 : OFF
MD Stop Power to EHW : OFF Power to MIF : OFF RUN/STOP Lamp: OFF, COOL, Set Fan Speed & Set Temp. Indication: Continuously ON
STOP
Electronic Ex. Valve in I.U. and O.U. : Fixed Opening Power to Solenoid Valve SVA : ON
Power to Y211 : OFF
70
Power to I.U.: OFF
Power to PCB in I.U.: OFF
Power to O.U.: OFF
Power to PCB in O.U.: OFF
Power to RVR1 : OFF
LCD Indication: OFF
Power to CH1 ~ CH6 : OFF
CONTROL SYSTEM I Freezing Protection Control during Cooling or Dry Operation Power Supply
Cooling Operation or Dry Operation
No
Is compressor operated for more than *30 min.? * The judging time varies under the condition. Yes
Cooling Operation or Dry Operation Pipe Surface Temp. of Indoor Heat Exchanger
Higher than 0oC
Lower than 0oC
Is it continuous for more than 3 min.?
No
Yes MIF Operation at Set Fan Speed (In Case of DRY Operation MIF OFF for 6 min.)
Fully Closed Electronic Exp. Valve in Indoor Unit
Is it continuous for more than 3 min.? (6 min. in case of DRY Operation)
No
Yes
Gas Pipe Surface Temp. of Indoor Heat Exchanger
Lower than 14oC
Higher than 14oC
Yes After 15 min.
No
Liquid Pipe Temp. of Indoor Heat Exchanger
Lower than 2oC
Higher than 2oC
71
CONTROL SYSTEM I Heating Operation
I.U.: Indoor Unit O.U.: Outdoor Unit Power to CH1 ~ CH6
Power to O.U.: ON Power to PCB in O.U.: ON
Power to I.U.: ON
Reverse Phase (Alarm Code 05)
Is phase correct?
Power to I.U.: OFF
Power to PCB in I.U.: ON Auto - louver 0 Reset
only for indoor unit with auto - louver
Correct phase
Start of Transmitting between I.U. and O.U. Start of Transmitting between I.U. and Remote Control Switch
Setting Operation Mode at "HEAT"
HEAT Indication
HIGH Indication
High Setting Fan Speed
Air Flow Changeover Switch
Medium
MEDIUM Indication
Low
LOW Indication
Setting Required Temp.
Pressing RUN/STOP Switch
Switch: Increasing Set Temp. Switch: Decreasing Set Temp.
Power to YH2 for 20 sec.
MD : ON
for unit with drain pump Run LED: ON, RUN : ON
Outdoor Fan (MOF) Air Flow: 100 % for 1 min. at Max.
Power to MC2 ~ MC6 : ON Power to CH2 ~ CH6 : OFF
Power to CMC2 ~ CMC6 : ON
Lower than Setting Temp. Heating Operation
Indication of Set Temp.
Yes
Indoor Unit Intake Air Temp.
Is heat load big?
No Power to CMC1 : ON
Power to CH1 : OFF Power to MC1 with Inverter Frequency PID Control: ON
Higher than Setting Temp. Power to Y212 : ON
MIF Operation at Low Speed
Power to RVR2 : ON
Heat Load
Indoor Fan Stop for 3 min. at max.
PID Control for Indoor/ Outdoor Electric Ex. Valve
Small
Power to Y52H : OFF
Big Yes
Indoor Unit Air Discharge Temp. ≤ 10oC and Pd ≤ 2.2MPa (22kg/cm2G) No
Power to Y52H : ON
EH Operation
After 3 to 48 sec. Lower than 25oC Indoor Unit Operation at Air Discharge Slow Fan Speed Temp.
To 3
Higher than 30oC
Operation at Setting Fan Speed Permitting Downward Air by Auto-Louver
o
Operation at Low Fan Speed
72
Power to CEH : ON
25 to 30 C
CONTROL SYSTEM I Heating Operation
3
I.U.: Indoor Unit O.U.: Outdoor Unit Start of Auto-Louver Pressing Auto-Louver Switch
only for Air Panel or Indoor Unit with Auto-Louver
Alternatively Stop of Auto-Louver
Power to Y52C : OFF
Pressing RUN/STOP Switch
Stop of MC1 ~ MC6
Power to CMC1 ~ CMC6 : OFF
Stop of MOF1 & MOF2 Power to CH1 ~ CH6 : ON
Power to Y52H : OFF
Indoor Unit Discharge Air Temp. Heat Rejection Operation
Power to CEH : OFF
Lower than 50oC
Indoor Fan Motor MIF : OFF
Higher than 50oC
Slow Fan Speed
EH : Stop
Shorter than 2 min. Indoor Unit Discharge Air Temp.
Higher than 40°C
Lower than 40°C
Operation at Slow Speed
after 2 min.
RUN LED: OFF. HEAT, Set Air Flow & Set Temp. Indication: Continuously ON Electronic Exp. Valve in I.U.: Fixed Opening STOP
Power to I.U.: OFF
Power to O.U.: OFF
Power to PCB in I.U.: OFF
LCD Indication: OFF
Power to PCB in O.U.: OFF
Resetting of Timer for Defrosting
Power to CH1 ~ CH6 : OFF
Power to Y212 : OFF
Power to RVR2 : OFF
: Not Equipped
73
CONTROL SYSTEM I Defrosting Operation Control
Heating
Heating Operation Time 40 Minutes or Above
Temperature Difference between Outdoor Temperature and Evaporating Temperature (Te) at Heat Exchanger
Yes
No
Big
Small
Defrosting DEFROST on LCD appears according to indoor heat load
RVR1 : ON
RVR2 : OFF
Outdoor FAN MOF1 & MOF2 : OFF
Indoor FAN MIF : OFF 1 Minute Later
Compressor Operating at Low Frequency
High Frequency Operation
Fixed Opening Degree of Electronic Exp. Valve
Defrosting Time 9 Minutes or Above Yes
Defrosting Completion
No
Evaporating Temperature (Te) at Heat Exchanger is 15°C or Above
No
Discharge Gas Pressure 1.7MPa (17kg/cm2G) or Above Yes
Yes
RVR1 : OFF
RVR2 : ON
DEFROST on LCD disappears
Heating
74
No
CONTROL SYSTEM 10.5 Protection and Safety Control Compressor Protection The compressor is protected by the following devices and their combinations. High Pressure Switch - This switch cuts out the operation of the compressor when the discharge pressure exceeds the setting.
Fan Motor Protection Internal Thermostat-Embedded in the fan motor winding, this internal thermostat cuts out the operation of the fan motor when the fan motor winding temperature exceeds the setting.
Oil Heater - This band type heater protects against oil Carry-over during cold starting, as it is energized
while the compressor is stopped.
10.6 Safety and Control Device Setting ■ Indoor Units Please refer to Technical Catalog I, SP1-S02 or SP1-S03, 2006. ■ Outdoor Units Model For Compressor Pressure Switches High Cut-Out Cut-In
MPa MPa
RAS-34FSN RAS-40FSN RAS-36FSN RAS-42FSN RAS-38FSN Automatic Reset, Non-Adjustable (each one for each compressor) -0.05 -0.05 4.15 4.15 -0.15 -0.15 3.20+0.15 3.20+0.15
Fuse Capacity 3φ 380-415V 50Hz/380V 60Hz 3φ 220V 60Hz Oil Heater Capacity CCP Timer Setting Time For Condenser Fan Motor Internal Thermostat Cut-Out Cut-In For DC Fan Module Fuse Capacity
A A
40 x 2 + 32 x 8 60 x 10
W
40 x 5
40 x 2 + 32 x 10 60 x 12 40 x 6 Non-Adjustable
min.
o o
C C
A
3 3 Automatic Reset, Non-Adjustable (each one for each motor) 130+5 130+5 83+15 83+15 12
12
75
CONTROL SYSTEM
76
CONTROL SYSTEM 10.7 Electrical Wiring Diagram ELECTRICAL WIRING DIAGRAM (380-415V/50Hz, 380V/60Hz)
77
CONTROL SYSTEM
ELECTRICAL WIRING DIAGRAM (220V/60Hz)
78
FOUNDATION PROVISION
11. FOUNDATION PROVISION Concrete Foundations (1) The height of the foundation should be 100 to 300mm higher than the ground level. (2) Install a drainage around foundation for smooth drain. more than 100 90 17
5
125
Outdoor Unit Vibration Proof Mat
Less than 300
Anchor Bolt
Drainage
P
Drainage (Width 100 x Depth 20)
more than 100
(760) (614) 794
17 90
Mortar Hole 100 x Depth 20
Details of P
Correct
17 90
Incorrect
Foundation
Foundation
Fig. 1. Foundations (3) Install the outdoor unit in the front-rear and right-left direction horizontally. Check to ensure that the gradient in four directions (front, rear, right and left) is within 10mm.
Right Side and Left Side
Front Side and Rear Side
760
(4) Provide a strong and correct foundation so that; a. The outdoor unit is not declined. b. Abnormal sound does not occur. c. The outdoor unit does not fall down due to a strong wind or earthquake. (5) When installing the outdoor unit, fix the unit by anchor bolts. Refer to Fig. 2 regarding the location of fixing holes. Unit: mm
782
782
782
782
10-38x16 Hole of Anchor Bolt
Fig. 2 Position of Anchor Bolts 79
REFRIGERANT PIPING PROVISION
12. REFRIGERANT PIPING PROVISION Piping Connection Size of Outdoor Unit
mm (in.) Piping Size
Model RAS-34FSN RAS-36FSN, RAS-38FSN, RAS-40FSN, RAS-42FSN
Gas
Liquid
φ31.75 (1-1/4)
φ19.05 (3/4)
φ38.1 (1-1/2)
φ19.05 (3/4)
Piping Connection Size of Indoor Unit
mm (in.) Piping Size
Model RPI-0.8FSN, RPK-0.8FSNSM1 RPI-1.0FSN, RCI-1.0FSN, RCD-1.0FSN, RPK-1.0FSNSM1, RPF-1.0FSN(E), RPFI-1.0FSN(E) RPI-1.5FSN, RCI-1.5FSN, RCD-1.5FSN, RPK-1.5FSNSM1, RPF-1.5FSN(E), RPFI-1.5FSN(E) RPI-2.0FSN, RCI-2.0FSN, RCD-2.0FSN, RPK-2.0FSNSM, RPC-2.0FSN RPI-2.5FSN, RCI-2.5FSN, RCD-2.5FSN, RPK-2.5FSNSM, RPC-2.5FSN RPI-3.0FSN, RCI-3.0FSN, RCD-3.0FSN, RPK-3.0FSNSM, RPC-3.0FSN RPK-3.5FSNSM RPI-4.0FSN, RCI-4.0FSN, RCD-4.0FSN, RPK-4.0FSNSM, RPC-4.0FSN RPI-5.0FSN, RCI-5.0FSN, RCD-5.0FSN, RPC-5.0FSN
Gas
Liquid
φ12.7 (1/2)
φ6.35 (1/4)
φ15.88 (5/8)
φ6.35 (1/4)
φ15.88 (5/8)
φ9.53 (3/8)
φ15.88 (5/8)
φ9.53 (3/8)
Select the piping connection sizes according to the following procedures. ❚ Between Outdoor Unit and Multi-Kit: Select the same pipe connection size as the pipe size of the outdoor unit. ❚ Between Multi-Kit and Multi-Kit: Select the same pipe connection size as the pipe size of the outdoor unit. In some cases, the liquid piping size is also required to be changed. Outdoor Unit Capacity (HP) 34 36 and 38 40 and 42
80
Wo: Outdoor Unit Ref. Charge (kg) 28.5 31.0 32.0
REFRIGERANT PIPING PROVISION
Additional Refrigerant Charge Calculation
Additional Charge of Refrigerant R410A (FSN Series) Although refrigerant has been charged into this unit, it is required that additional refrigerant be charged according to piping length. A. Determine an additional refrigerant quantity according to the following procedure, and charge it into the system. B. Record the additional refrigerant quantity to facilitate service activities thereafter.
42HP
φ19.05x20m
φ9.53x5m φ9.53x5m φ9.53x5m φ6.35x10m φ9.53x5m φ9.53x5m φ9.53x5m φ9.53x5m φ9.53x5m 2.5HP 4.0HP 5.0HP 4.0HP 5.0HP 2.5HP 2.5HP 2.5HP 2.0HP No. 2 No. 4 No. 6 No. 8 No. 0 No. 1 No. 3 No. 5 No. 7
φ19.05x5m φ15.88x5m φ19.05x5m φ19.05x5m φ12.7x5m
1. Calculating Method of Additional Refrigerant Charge (W kg) 1.1 Additional Refrigerant Charge Calculation for Liquid Piping (W1 kg) See Example for Model RAS-42FSN, and fill in the following table. Pipe Diameter φ22.2 ..... φ19.05 ... φ15.88 ... φ12.7 ..... φ9.53 ..... φ6.35 ..... Example
Total Piping Length (0) (20 + 5 x 3) (5) (5) (5 x 8) (10) Additional Charge W1
Pipe Diameter φ22.2 ..... φ19.05 ... φ15.88 ... φ12.7 ..... φ9.53 ..... φ6.35 ..... This System
Additional Charge (kg) x 0.390 = 0.00 x 0.280 = 9.80 x 0.190 = 0.95 x 0.120 = 0.60 x 0.07 = 2.80 x 0.03 = 0.30
Total Piping Length
<Table 1>
Total = 14.45 (kg) Additional Charge (kg) x 0.390 = x 0.280 = x 0.190 = x 0.120 = x 0.07 = x 0.03 =
Additional Charge W1
Total =
Outdoor Unit
W0 Outdoor Unit Ref. Charge (kg)
RAS-34FSN
28.5
RAS-36FSN
31.0
RAS-38FSN
31.0
RAS-40FSN
32.0
RAS-42FSN
32.0
NOTE: W0 is outdoor unit ref. charge before shipment.
(kg)
1.2 Additional Refrigerant Charge Calculation for Indoor Unit (W2 kg) Additional refrigerant charge is 1 kg/unit of 8HP and 10HP indoor unit. Additional refrigerant charge of less than 8HP indoor units are not needed. (Total Combination unit of 8HP and 10HP.)
(Example) This System
W2 = W2 =
0
unit x 1.0 kg/unit = unit x 1.0 kg/unit =
0.0
kg kg
1.3 Calculation of Additional Charge (W kg) Put weight W1 and weight W2 calculated in items 1.1 and 1.2 into the following formula. Total Volume of Additional Charge W = W1 + W2 (Example) W = 14.45 + 0.0 = 14.45 kg This System W = + = kg
2. Charging Work Charge refrigerant (R410A) into the system according to the instructions described in the "Installation Manual".
Total Additional Charge W
kg
Total Ref. Charge of This System
kg
Date of Ref. Charge Work Year
Month
Day
3. Record of Additional Charge Record the refrigerant charging quantity in order to facilitate maintenance and servicing activities. Total refrigerant charge of this system is calculated in the following formula. Total Ref. Charge of This System = W + W0 This System = + = kg
81
REFRIGERANT PIPING PROVISION
Refrigerant Piping Work < Outdoor Unit to First Branch > Outdoor Unit Capacity
Gas/Liquid (φmm) Equivalent Piping Length < 100m Equivalent Piping Length >100m *1)
34HP
31.75/19.05
38.1/22.2
36 to 42HP
38.1/19.05
44.45/22.2
< Multi-kit to Indoor Unit > Pipe Size Indoor Unit Capacity 0.8 to 1.5HP 2HP
H1
2.5 to 5HP
Gas/Liquid (φmm)
Max. Length of Liquid Pipe
12.7/6.35 *2)
15m
15.88/6.35 *2)
15m
15.88/9.53
30m
*2): In the case that liquid piping length is longer than 15m, use φ9.53 pipe and reducer (field-supplied).
Indoor Unit
< First Branch >
Indoor Unit
H2
Outdoor Unit Capacity
Multi-Kit
34 to 42HP
E-302SN
Indoor Unit
Indoor Unit
Indoor Unit L3
Indoor Unit
L3
L3
L3
L3
L3 L2
L1
< Piping Size and Multi-kit after First Branch > Total I. U. Capacity in HP
Gas/Liquid (φmm)
36~
38.1/19.05
26~35.99
31.75/19.05
18~25.99
28.6/15.88
16~17.99
28.6/12.7
12~15.99
25.4/12.7
Multi-kit Model E-302SN
Item Ref. Pipe Length: L1
Actual Equivalent
Applicable Range within 150m within 175m
Piping Length from 1st Branch to each I. U.: L2
within 40m
E-162SN
Piping Length from each Multi-kit to I. U.: L3
within 30m within 50m
E-242SN
9~11.99
22.2/9.53
E-102SN
Lift between
O. U. is Higher
6~8.99
19.05/9.53
E-84HSN *3)
I. U. and O. U.: H1
O. U. is Lower
lower than 6
15.88/9.53
E-108HSN *3)
Lift between Indoor Units: H2
within 15m
Total Actual Length of Liquid Pipes
within 300m
*3) Total I. U. Capacity in HP
Number of Branches
5~10
8 branches
E-108HSN
5~8
4 branches
E-84HSN
within 40m
Multi-kit
In the case that the selected multi-kit size is bigger than that of the first branch, use the same size as the first branch. In the case that the selected pipe size after the first branch is bigger than the pipe size before the first branch, use the same size as before the branch. If the pipe length from the O.U. to the first branch is more than 100m, the pipe size must be increased (refer to *1)). In this case, the pipe size from the first branch to the second branch should be selected according to the original pipe size.
82
FIELD WIRING PROVISION
13. FIELD WIRING PROVISION Electrical Wiring All the field wiring and equipment must comply with local codes. Max. 1 Outdoor Unit / Power Supply Line
No. 0 System Outdoor Unit TB1 L1 L2 L3 N
TB2 1 2
No. 1 System Outdoor Unit TB1 L1 L2 L3 N
TB2 1 2
No. 3 System Outdoor Unit TB1 L1 L2 L3 N
TB2 1 2
Operating Line (Shielded Twist Pair Cable) DC5V (Non-Pole Transmission H-LINK System)
ELB
Distribution Box or Pull Box *2
ELB
Distribution Box or Pull Box *2
FUSE Main Switch
ELB
3N 380-415V/50 Hz 380V/60 Hz
L1 L2 N
L1 L2 N
TB1
TB1
No. 0 Indoor Unit
1N 220-240V/50 Hz 220V/60 Hz
No. 1 Indoor Unit
Remote Control Cable (Shielded Twist Pair Cable) *1
TB2 1 2 A B
Operating Line (Shielded Twist Pair Cable) DC5V (Non-Pole Transmission H-LINK System)
1 2 A B
Remote Control Switch (PC-P1H)
TB : Terminal Board
Remote Control Cable (Shielded Twist Pair Cable) *1
TB2
Remote Control Switch (PC-P1H)
PCB : Printed Circuit Board : Field Wiring : Field Supplied
No.1 System Indoor Units
No. 0 System Indoor Units (Max. 32 Units per Refrigerant Cycle)
: Optional Accessory
*1: When installing PC-P1H remote control switch in Australia, connect the both ends of shield tube to earth. *2: It is need for Australia.
Instruction for Electrical Wiring Connection (380-415V/50Hz and 380V/60Hz)
Max. 1 Outdoor Unit / Power Supply Line
No. 0 System Outdoor Unit TB1 L1 L2 L3
TB2 1 2
No. 1 System Outdoor Unit TB1 L1 L2 L3
TB2 1 2
No. 3 System Outdoor Unit TB1 L1 L2 L3
TB2 1 2
Operating Line (Shielded Twist Pair Cable) DC5V (Non-Pole Transmission H-LINK System)
ELB
Distribution Box or Pull Box *2
ELB
Distribution Box or Pull Box *2
FUSE Main Switch
ELB
3φ 220V/60 Hz L1 L2 N
L1 L2 N TB1
TB1 No. 0 Indoor Unit TB2
1φ 220V/60 Hz
1 2 A B
Operating Line (Shielded Twist Pair Cable) DC5V (Non-Pole Transmission H-LINK System) TB : Terminal Board
No. 1 Indoor Unit
Remote Control Cable (Shielded Twist Pair Cable) *1
TB2 1 2 A B
Remote Control Switch (PC-P1H)
Remote Control Cable (Shielded Twist Pair Cable) *1 Remote Control Switch (PC-P1H)
PCB : Printed Circuit Board : Field Wiring : Field Supplied : Optional Accessory
No. 0 System Indoor Units (Max. 32 Units per Refrigerant Cycle)
No.1 System Indoor Units
*1: When installing PC-P1H remote control switch in Australia, connect the both ends of shield tube to earth. *2: It is need for Australia.
Instruction for Electrical Wiring Connection (220V/60Hz) 83
FIELD WIRING PROVISION
Table for Terminal Connection Wiring
O.U.: Outdoor Unit, I.U.: Indoor Unit
[ Connection (Connection of Terminals) ]
Power Supply
[ O.U.-O.U. (L1-L1, L2-L2, L3-L3, N-N) ]
Operating
[ I.U.-I.U. (L1-L1, N-N) ] [ O.U.-I.U., I.U.-I.U. (1-1, 2-2) ]
Field Wiring 1. All the field wiring and equipment must comply with local codes. 2. The recommended breaker size are shown in the table below. Electrical Data and Recommended Wiring, Breaker Size / 1 Outdoor Unit
Model
RAS-34FSN RAS-36FSN RAS-38FSN RAS-40FSN RAS-42FSN RAS-34FSN RAS-36FSN RAS-38FSN RAS-40FSN RAS-42FSN RAS-34FSN RAS-36FSN RAS-38FSN RAS-40FSN RAS-42FSN
Power Supply
380-415V/50Hz
380V/60Hz
220V/60Hz
ELB: Earthleakage Breaker MLFC: Flame Retardant Polyflex Wire
84
ELB
Max. Running Current
Power Supply Line
Nominal Current
(A) 67 72 76 81 84 64 68 72 76 79 115 123 130 138 143
(mm2) MLFC22SQ MLFC22SQ MLFC22SQ MLFC22SQ MLFC22SQ MLFC22SQ MLFC22SQ MLFC22SQ MLFC22SQ MLFC22SQ MLFC38SQ MLFC38SQ MLFC50SQ MLFC50SQ MLFC50SQ
(A) 125 125 125 150 150 125 125 125 125 150 200 200 200 200 200
Nominal Sensitive Current (mA) 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100
Fuse (A) 70 80 80 90 90 70 70 80 80 80 125 125 150 150 150
MISCELLANEOUS NOTES
14. MISCELLANEOUS NOTES Special Notes 1. Provide a service access door near the unit piping connection part on the false ceiling for the cassette type units. 2. Consider the air distribution from the unit to the space of the room, and select a suitable location so that uniform air temperature in the room can be obtained. Cassette and Ceiling Types - Avoid unit installation in a room where the ceiling height (distance between the floor to the false ceiling) exceeds three meters. If the indoor unit is installed in a room with a ceiling of higher than 3 meters, it is recommended that an air circulation fan be installed separately to obtain uniform air temperature in the room, especially during the heating operation. 3. Check to ensure that the ceiling slab is strong enough and that the false ceiling is flat and level. 4. Avoid obstacles which may restrict the air intake or the discharge flow. 5. Do not install the unit in a machinery shop or kitchen where vapor from oil or its mist can enter to the unit. The oil will deposit on the heat exchanger, thereby reducing the unit performance, and may deform, in the worst case, break the plastic parts of the unit. 6. Pay attention to the following points when the unit is installed in a hospital or other facilities where electromagnetic wave is radiated from medical equipment. (A) Do not install the unit where the electromagnetic wave is directly radiated to the electrical box, remote control cable or remote control switch. (B) Install the unit and component as far as practical (at least three meters) from the electromagnetic wave radiator. (C) Prepare a steel box and install the remote control switch in it. Prepare a steel conduit pipe and wire the remote control cable in it. And then, connect earth wire with the box and the pipe. (D) Install a noise filter when the power supply emits harmful noise. 7. Do not install the units in an acid or alkaline environment due to the corrosive action on the heat exchanger. In the case that outdoor units are installed near the sea, it is recommended that optional corrosion-resistant type outdoor unit be used. 8. Do not install the units in a flammable environment due to the danger of an explosion. 9. Regarding cassette type indoor units, consider the direct and reflected sound level, when selecting the unit for spaces where extremely low sound is required.
10. During heating operation, the outdoor heat exchanger produces condensate dew or melting water from frost. Install the outdoor unit where drainage of such water is convenient, or provide a drain passage. 11. Heating Performance: The heating capacity normally decreases when outdoor temperatures decrease. Therefore, provide an auxiliary heating unit if outdoor temperatures are very low. 12. In the case that an outdoor temperature is low and humidity is high, the outdoor heat exchanger will covered with frost, resulting in lower heating capacity. In order to remove the frost, the unit is automatically changed to the defrosting mode. During this defrosting operation, the unit is stopped for approximately 3 to 10 minutes. 13. As this unit is of heat pump type by circulating hot air in the whole room space, it takes time to heat up the room temperature. 14. The operating sound data is based on an anechoic chamber. Therefore, the actual operating sound will be higher due to reflected sound from the floor and wall. 15. In the case that the unit is operated for a long time higher than the indoor temperature of 27oCDB or the humidity of 80%, dewing may occur on the cabinets resulting in dew drops. If dewing, it is required to add thermal insulator on the cabinets. 16. Provide snow-protection hoods to prevent the outdoor heat exchanger from snow clogging. If the unit is operated in an are where it snows heavily, provide a base under the outdoor unit which should be 50cm higher than the presumable maximum snow height. 17. It is recommended that periodical service and maintenance be performed by authorized service engineers before air conditioning seasons, in order to avoid performance decrease due to dust or dirt. 18. This heat pump air conditioner has been designed for normal air conditioning for men. Do not apply to other purposes such as for food, animals, plants, high precision machines or work of art. Also do not apply to vehicles or vessels. It will results in water leakage or electrical leakage. 19. It is recommended that the system be installed by authorized engineers. If not, it may cause water leakage, electric shock or fire. 20. In a place where fibers or dusts are floating, the air filter or heat exchangers or the drain pipe may be clogged, resulting in water leakage from the drain pan.
85
MISCELLANEOUS NOTES Special Notes on Refrigerant, R410A Use tools and measuring instruments only for the new refrigerant which is directly touch to refrigerant. : Interchangeability is available with current R22 : Prohibited Measuring Instrument and Tool Pipe Cutter Chamfering Reamer Flaring Tool Extrusion Adjustment Gauge
Refrigerant Pipe
Interchangeability with R22 R410A R407C
-
Pipe Bender
Expanding Tool
Torque Wrench
Lubrication Oil (for Flare Surface)
Refrigerant Cylinder
Brazing Tool Nitrogen Gas
Vacuum Pump
Vacuum Drying . Refrigerant Charge
Adapter for Vacuum Pump Manifold Valve
Charging Hose
Charging Cylinder Weight Scale
Refrigerant Gas Leakage Detector
: Interchangeability with R407C.
86
: only for Refrigerant R410A (No Interchangeability with R22) : only for Refrigerant R407C (No Interchangeability with R22) Reason of Non-Interchangeability and Attention ( : Strictly Required) * The flaring tools for R407C are applicable to R22. * If using flaring tube, make dimension of tube larger for R410A. * In case of material 1/2H, flaring is not available. * In case of material 1/2H, bending is not available. Use elbow for bend and braze. * In case of material 1/2H, expanding of tube is not available. Use socket for connecting tube. * For φ12.7, φ15.88, spanner size is up 2mm. * For φ6.35, φ9.53, φ19.05, spanner size is the same. * Perform correct brazing work. * Strict Control against Contamin (Blow nitrogen during brazing.) * Use a synthetic oil which is equivalent to the oil used in the refrigeration cycle. * Synthetic oil absorbs moisture quickly. * Check refrigerant cylinder color. Liquid refrigerant charging is required regarding zeotoropic refrigerant. The current ones are applicable. However, it is required to mount a vacuum pump adapter which can prevent from reverse flow when a vacuum pump stops, resulting in no reverse oil flow. * No interchangeability is available due to higher pressures when compared with R22. Do not use current ones to the different refrigerant. If used, mineral oil will flow into the cycle and cause sludges, resulting in clogging or compressor il the weight scale. * fUse * The current gas leakage detector (R22) is not applicable due to different detecting method.
Use Cutting Pipe Removing Burrs Flaring for Tubes Dimensional Control for Extruded Portion of Tube after Flaring Bending Expanding Tubes Connection of Flare Nut Brazing for Tubes Prevention from Oxidation during Brazing Applying Oil to the Flared Surface Refrigerant Charging
Vacuum Pumping
Vacuum Pumping, Vacuum Holding, Refrigerant Charging and Check of Pressures
Measuring Instrument for Refrigerant Charging Gas Leakage Check
STANDARD SPECIFICATIONS
15. STANDARD SPECIFICATIONS UNIT - The unit shall be a multi-split system inverterdriven heat pump air conditioner for application with R410A refrigerants, and shall be composed of 4-way cassette type indoor units, or in-the-ceiling type indoor units, 2-way cassette type indoor units, ceiling type indoor units, wall type indoor units, floor type indoor units and an outdoor unit, with a distributed refrigeration cycle, electrical components and enclosing cabinets. Optional accessories shall also be provided upon customer request. The indoor unit shall be constructed for installation, and the outdoor unit shall be completely weather-proofed for outdoor installation. Both indoor unit and the outdoor unit shall be properly assembled, internally piped and wired, throughly tested, and charged with R410A refrigerant at the factory and shall comply with Japanese Industrial Standards and other Japanese standardization statues.
OUTDOOR UNIT
CAPACITY - The total capacity of the multi-split system inverter-driven heat pump air conditioner shall be o kW or greater with C air inlet dry bulb, o o C air inlet wet bulb, C outdoor air inlet m3/min. indoor air flow. The total temperature and compressor power inputs shall not exceed kW. The total heating capacity of the split-type air conditioners o kW or greater, with C indoor heat shall be o exchanger inlet air dry bulb, C outdoor heat o C outdoor heat exchanger air inlet dry bulb, m3/min. indoor air exchanger air inlet wet bulb, and flow. The total compressor power input shall not exceed kW.
OUTDOOR FAN AND FAN MOTOR - The outdoor fan(s) shall be the plastic propeller type, dynamically balanced, W motor for and the fan shall be directly driven by a vertical-flow air discharge. The fan motor shall be permanently lubricated and be protected from ingress of water.
CABINET - The cabinet shall be constructed of galvanized steel sheet, baked with synthetic resin paint. The service panel shall be easily removable for service access to the electrical components and the compressor section. REFRIGERATION CYCLE - Each refrigeration cycle shall be equipped with (a) scroll compressor(s), a solenoid valve, a heat exchanger, an accumulator, a 4Way valve and flare connection parts. COMPRESSOR PROTECTION - The compressor shall be protected against breakdown by a quick response overcurrent relay, a high pressure switch, a wrap-around type oil heater and a discharge gas thermistor.
OUTDOOR HEAT EXCHANGER - The heat exchanger shall be the multi-pass, cross-finned tube type, equipped with highly-efficient aluminum fins, mechanically bonded to oxygen-free copper tubes. The coil shall be cleaned, dehydrated and tested for leakage at the factory. CONTROL - All electrical control devices, shall be enclosed in the indoor and outdoor units.
INDOOR UNIT CABINET - The cabinet shall be constructed of galvanized steel sheet or finished steel sheet, baked with synthetic resin-paint, with a plastic air panel assembly for cassette type unit, and be constructed of galvanized steel sheet for the in-the-ceiling duct type unit. REFRIGERATION CYCLE - The refrigeration cycle shall be equipped with a heat exchanger, an electronic expansion valve, solenoid valves and flare connections. INDOOR FAN AND FAN MOTOR - The indoor fan shall be the multi-blade centrifugal type, statically and W dynamically balanced, and directly driven by a motor for model and a W motor for model . The fan motor bearing shall be permanently m3/min. air flow for lubricated. The fan shall deliver 3 model and m /min. for model at the nominal air flow. Three operating positions Hi, Me and Lo can be selected according to the required conditions.
In addition to the compressor protection devices, the indoor fan motor shall be equipped with an internal thermostat. The outdoor fan motor shall be protected by an internal thermostat. The indoor fan motor shall be directly supplied with the power source from the control circuit. The functions of these control devices shall compose an electrical sequence of manual starting and stopping, automatic continuous operation whenever the room thermostat requires, and the protection devices allow the operation. CABINET - The cabinet shall be constructed of galvanized steel sheet. REFRIGERATION CYCLE - The refrigeration cycle shall be equipped with solenoid valves and flare connections to changeover the cycle in mediating between outdoor unit and indoor unit.
INDOOR HEAT EXCHANGER - The heat exchanger shall be the multi-pass, cross-finned tube type, equipped with highly-efficient aluminum fins, mechanically bonded to seamless, oxygen-free copper tubes. The fins shall be spaced at no more than 12 fins per 25.4mm. The face m2 for model and area shall not be less than m2 for model . The coil shall be cleaned, dehydrated and tested for leakage at the factory.
87
CAUTION
16. CAUTION ON REFRIGERANT LEAKAGE 16.1 Maximum Permissible Concentration of HFC Gas The refrigerant R410A, charged in the SET-FREE FSN system, is an incombustible and non-toxic gas. However, if leakage occurs and gas fills a room, it may cause suffocation. The maximum permissible concentration of R410A in air is *0.3 kg/m3, according to the refrigeration and air conditioning facility standard (KHK S 0010) by the KHK (High Pressure Gas Protection Association) Japan. Therefore, some effective measure must be taken to lower the R410A concentration in air below *0.3 kg/m3, in case of leakage.
16.2 Calculation of Refrigerant Concentration (1) Calculate the total quantity of refrigerant R (kg) charged in the system connecting all the indoor units of rooms to be air-conditioned. (2) Calculate the room Volume V (m3) of each room. (3) Calculate the refrigerant concentration C (kg/m3) of the room according to the following equation. R: Total Quantity of Charged Refrigerant (kg) = C: Refrigerant V: Room Volume (m3) Connection < *0.3 (kg/m3)
16.3 Countermeasure for Refrigerant Leakage According to KHK Standard The facility shall be arranged as follows referring to the KHK standards, so that the refrigerant concentration will be below *0.3 kg/m3. (1) Provide a shutterless opening which will allow fresh air to circulate into the room. (2) Provide a doorless opening of 0.15% or more size to the floor area. (3) Provide a ventilator, linked with a gas leak detector, of 0.4 m3/min. or more ventilating capacity per Japanese Refrigeration Ton (= compressor displacement m3/h / 5.7) of the air conditioning system utilizing refrigerant R410A. 50Hz / 60Hz RAS-34FSN ................................ 13.83 / 15.79 ton RAS-36FSN ................................ 13.83 / 15.79 ton RAS-38FSN ................................ 13.83 / 15.79 ton RAS-40FSN ................................ 16.26 / 18.71 ton RAS-42FSN ................................ 16.26 / 18.71 ton (4) Pay a special attention to the place, such as a basement, etc., where refrigerant can stay, since refrigerant is heavier than air. *: Use this value for a reference only, since this value is not fixed yet. Follow upon local regulations.
88
CAUTION <Example> System A Outdoor Unit
System B Outdoor Unit
20HP
System A Refrigerant: 60kg
16HP
2
4
4
E
D
C
B
A
Floor 40m2
Floor 70m2
Floor 70m2
Floor 400m2
Floor 120m2
Gas Leak Detector Ventilator
5
5
5
System B Refrigerant: 50kg
5
3
3
Opening: 0.06m2
2m3/min
Room
R (kg)
V (m3)
C (kg/m3)
Countermeasure
A
50
300
0.17
-
B
110
1,000
0.11
C
60
175
0.34
0.06m Opening
D
60
175
0.34
0.06m2 Opening
C+D
60
350
0.171
E
Height 2.5m
60
100
0.6
2
3
2 m /min. Ventilator Linked with Gas Leak Detector
If local codes or regulations are specified, follow them. <Example> British Standard BS4434 1989 R410A Commercial Office Building Class D Occupancy MR = C V MR: Maximum Charge or Leakage of Refrigerant (kg) C: Maximum Allowable Concentration = 0.17 (kg/m3) V: Volume of Space (m3)
89
Specifications in this catalog are subject to change without notice, in order that HITACHI may bring the latest innovations to their customers.
Catalog No. SP1-S04, 2006